Sie sind auf Seite 1von 15

Appendix: Technical Specifications and Special Features of the S7-400

SIMATIC S7
Siemens AG 2003. All rights reserved.

Date: File:

08.09.2011 PRO1_17E.

SITRAIN Training for


Automation and Drives

Technical Specifications of the S7-300


CPU Execution time in s Bit instruction Word instruction Integer (+/-) Real (+/-) User memory Work memory Load memory integr. Load memory extern Addresses Bit memories Clock memories Timers Counters Block types/Number FBs FCs DB's Size of process image I/O in bytes Maximum I/O address area in bytes Interfaces 312 IFM 0.6 - 1.2 2.0 3.0 60.0 6 KB 20 KB 1024 8 64 32 32 32 63 32 each 32 each 313 0.6 - 1.2 2.0 3.0 60.0 12 KB 20 KB 4 MB 2048 8 128 64 128 128 127 128 each 32 each 314 0.3 - 0.6 1.2 2.0 50.0 24 KB 40 KB 4 MB 2048 8 128 64 128 128 127 128 each 768 each 314 IFM 0.3 - 0.6 1.2 2.0 50.0 32 KB 48 KB (4 MB) 2048 8 128 64 128 128 127 124 each 752 each 315 0.3 - 0.6 1.0 2.0 50.0 48 KB 80 KB 4 MB 2048 8 128 64 192 192 255 128 each 768 each

CPUs (1)
315-2 DP 0.3 - 0.6 1.0 2.0 50.0 64 KB 96 KB 4 MB 2048 8 128 64 192 192 255 128 each 1024 each 316-2 DP 0.3 - 0.6 1.0 2.0 50.0 128 KB 192 KB 4 MB 2048 8 128 64 256 512 511 128 each 1024 each 318-2 DP 0.1 0.1 0.1 0.6 512 KB 64 KB 4 MB 8192 8 512 512 1024 1024 2047 256 each (2048) 8192 each

MPI

MPI

MPI

MPI

MPI

MPI, DP

MPI, DP

MPI/DP, DP

SIMATIC S7
Siemens AG 2003. All rights reserved.

Date: File:

08.09.2011 PRO1_17E.

SITRAIN Training for


Automation and Drives

Technical Specifications of the S7-300


CPU Organization blocks Free cycle Time-of-day interrupts Time-delay interrupts Cyclic interrupts Hardware interrupts Background execution Startup Errors, asynchronous Errors, synchronous Local data in bytes Maximum block length Block nesting depth per execution level Communication Maximum connections static/dynamic Global data communication with MPI: GD circles per CPU 4 Send GD packets per GD circle Receive GD packets per GD circle Maximum user data size of a packet 1 1 22 bytes 4 1 1 22 bytes 4 1 1 22 bytes 4 1 1 22 bytes 4 1 1 22 bytes 4 1 1 312 IFM OB No. 1 40 100 512 8 KB 8 313 OB No. 1 10 20 35 40 100 80-82, 85, 87 121,122 1536 8 KB 8 314 OB No. 1 10 20 35 40 100 80-82, 85, 87 121,122 1536 8 KB 8 314 IFM OB No. 1 10 20 35 40 100 80-82, 85, 87 121,122 1536 8 KB 8 315 OB No. 1 10 20 35 40 100 80-82, 85, 87 121,122 1536 16 KB 8

CPUs (2)
315-2 DP OB No. 1 10 20 35 40 100 80-82, 85 87 121,122 1536 16 KB 8 316-2 DP OB No. 1 10 20 35 40 100 80-82, 85 87 121,122 1536 16 KB 8 318-2 DP OB No. 1 10,11 20,21 32,35 40,41 90 100,102 80-82, 85 87 121,122 4096(8192) 64 KB 20

4/2

4/4

4/8

4/8

4/8

4/8

4/8

32

4 1 1 22 bytes

8 1 2 54 bytes

22 bytes

SIMATIC S7
Siemens AG 2003. All rights reserved.

Date: File:

08.09.2011 PRO1_17E.

SITRAIN Training for


Automation and Drives

Technical Specifications of the S7-400


CPU Execution time in s Bit instruction Word instruction Integer (+/-) Real (+/-) User memory Work memory int. Load memory integr. Load memory extern Addresses Byte memories Clock memories Timers Counters Block types/Number FBs FCs DBs Size of process image I/O in bytes Maximum I/O address area in bytes Interfaces 412-1 0.2 0.2 0.2 0.6 2x48 KB 256 KB 64 MB 4K 8 256 256 256 256 511 4 K each 4 K each 412-2 0.2 0.2 0.2 0.6 2x48 KB 256 KB 64 MB 4K 8 256 256 256 256 511 4 K each 4 K each 414-2 0.1 0.1 0.1 0.6 2x128 KB 256 KB 64 MB 8K 8 256 256 1024 1024 1023 8 K each 8K each 414-3 0.1 0.1 0.1 0.6 2x 384 KB 256 KB 64 MB 8K 8 256 256 1024 1024 1023 8 K each 8 K each 416-2 0.08 0.08 0.08 0.48 2x 0.8 MB 256 KB 64 MB 16 K 8 512 512 2048 2048 4096 16 K each 16 K each

CPUs (1)
416-3 0.08 0.08 0.08 0.48 2x 1.6 MB 256 KB 64 MB 16 K 8 512 512 2048 2048 4096 16 K each 16 K each 417-4 0.1 0.1 0.1 0.6 2x2 MB 256 KB 64 MB 16 K 8 512 512 6144 6144 8191 16 K each 16 K each 417H 0.1 0.1 0.1 0.6 2x2 MB 256 KB 64 MB 16 K 8 512 512 6144 6144 8191 16 K each 16 K each

MPI/DP

MPI/DP DP

MPI/DP DP

MPI/DP 2xDP

MPI/DP DP

MPI/DP 2x DP

MPI/DP 3x DP

MPI/DP DP

SIMATIC S7
Siemens AG 2003. All rights reserved.

Date: File:

08.09.2011 PRO1_17E.

SITRAIN Training for


Automation and Drives

Technical Specifications of the S7-400


CPU Organization blocks Free cycle Time-of-day interrups Time-delay interrupts Cyclic interrupts Hardware interrupts Multicomputing Background execution Startup Errors, asynchronous Errors, synchronous Local data in bytes Maximum block length Block nesting depth per execution level Communication Maximum connections static/dynamic Global data communication with MPI: GD circles per CPU Send GD packets per GD circle Receive GD packets per GD circle Maximum user data size of a packet 412-1 OB No. 1 10,11 20,21 32,35 40,41 60 90 100-102 80-87 121,122 4 KB 48 KB 16 412-2 OB No. 1 10,11 20,21 32,35 40,41 60 90 100-101 80-87 121,122 4 KB 64 KB 16 414-2 OB No. 1 10-13 20-23 32-35 40-43 60 90 100-102 80-87 121,122 8 KB 64 KB 16 414-3 OB No. 1 10-13 20-23 32-35 40-43 60 90 100-102 80-87 121,122 8 KB 64 KB 16 416-2 OB No. 1 10-17 20-23 30-38 40-47 60 90 100-102 80-87 121,122 16 KB 64 KB 16

CPUs (2)
416-3 OB No. 1 10-17 20-23 30-38 40-47 60 90 100-102 80-87 121,122 16 KB 64 KB 16 417-4 OB No. 1 10-17 20-23 30-38 40-47 60 90 100-102 80-87 121,122 32 KB 64 KB 16 417H OB No. 1 10-17 20-23 30-38 40-47 60 90 100,102 80-87 121,122 32 KB 64 KB 24

16

16

32

32

64

64

64

64

8 1 2 54 bytes

8 1 2 54 bytes

8 1 2 54 bytes

8 1 2 54 bytes

16 1 2 54 bytes

16 1 2 54 bytes

16 1 2 54 bytes

16 1 2 54 bytes

SIMATIC S7
Siemens AG 2003. All rights reserved.

Date: File:

08.09.2011 PRO1_17E.

SITRAIN Training for


Automation and Drives

Main Differences between the S7-400


Larger memory and more I/Q/M/T/C Addresses of input/output modules selectable

and the S7-300

Can connect EUs from S5 and use S5 CP/IP modules More system functions, such as programmed block communication Block size up to 64KB and twice as many DBs Complete restart and restart Setpoint/actual comparison of configuration on startup Modules can be removed without disconnecting the power supply Several part process images Priorities of OBs are parameter-assignable Several OBs for cyclic, hardware and time-of-day interrupts Block nesting up to 16 levels Size of L Stack selectable for each execution level 4 accumulators Multicomputimg

SIMATIC S7
Siemens AG 2003. All rights reserved.

Date: File:

08.09.2011 PRO1_17E.

SITRAIN Training for


Automation and Drives

S7- 400

Components
Communication Communication processors (CP) processors (CP)

Racks Racks

- Universal rack (UR 1/2) for use as CR and ER - Universal rack for H systems - Extension rack (ER 1/2) - Segmented central rack (CR2)
Power supplies (PS) Power supplies (PS)

- Point-to-Point CP441-1, 1- channel CP441-2, 2- channel - Networks Profibus Ethernet


Signal modules (SM) Signal modules (SM)

- AC 120V/230V, 4A/10A/20A - DC 24V, 4A/10A/20A


CPUs CPUs

- DI/DO 32,16,8 channels - DO wit h relay output - AI/AO 16,8 channels - diagnostics-capable modules
Function Function modules (FM) modules (FM)

CPU 412-1, 412-2 CPU 414-2, 414-3, CPU 416-2, 416-3 CPU 417-4, 417H

- Counting - Positioning - Closed-loop control


SITRAIN Training for
Automation and Drives

SIMATIC S7
Siemens AG 2003. All rights reserved.

Date: File:

08.09.2011 PRO1_17E.

S7 - 400
Type of Rack

Racks
Usable in Central rack Expansion rack

UR1 / UR2 (Universal Rack)

P bus

Yes
K bus

Yes

CR2 (Central Rack)

P bus, Segment 1

P bus, Segment 2

Yes
K bus

No

ER1 / ER2 (Expansion Rack)

P bus

No

Yes

SIMATIC S7
Siemens AG 2003. All rights reserved.

Date: File:

08.09.2011 PRO1_17E.

SITRAIN Training for


Automation and Drives

Module Parameters: Logical Addresses

SIMATIC S7
Siemens AG 2003. All rights reserved.

Date: File:

08.09.2011 PRO1_17E.

SITRAIN Training for


Automation and Drives

CPU Parameters: Startup

SIMATIC S7
Siemens AG 2003. All rights reserved.

Date: File:

08.09.2011 PRO1_17E.

SITRAIN Training for


Automation and Drives

CPU Parameters: Interrupts

SIMATIC S7
Siemens AG 2003. All rights reserved.

Date: File:

08.09.2011 PRO1_17E.

SITRAIN Training for


Automation and Drives

CPU Parameters: Memory

SIMATIC S7
Siemens AG 2003. All rights reserved.

Date: File:

08.09.2011 PRO1_17E.

SITRAIN Training for


Automation and Drives

Configuring Multicomputing Operation

SIMATIC S7
Siemens AG 2003. All rights reserved.

Date: File:

08.09.2011 PRO1_17E.

SITRAIN Training for


Automation and Drives

SFC 35 for Synchronization in Multicomputing Operation

Parameter
JOB RET_VAL

Declaration
INPUT OUTPUT

Data type Memory


BYTE INT I, Q, M, D, L, Const. I, Q, M, D, L

Description
Task identifier (possible values: 1 to 15) Return value (error code).

SIMATIC S7
Siemens AG 2003. All rights reserved.

Date: File:

08.09.2011 PRO1_17E.

SITRAIN Training for


Automation and Drives

Remove and Insert Interrupt

Module exists

Module available

Remove/Insert interrupt
max. max.

1s

1s

Parameter assignment of module through the operating system Removing a module Inserting a module

SIMATIC S7
Siemens AG 2003. All rights reserved.

Date: File:

08.09.2011 PRO1_17E.

SITRAIN Training for


Automation and Drives

Das könnte Ihnen auch gefallen