Sie sind auf Seite 1von 2

Oil Distribution Transformers

Minera MP From 5 to 60 MVA, for 7.2 to 123 kV systems


1 dial type thermometer (without contact); 4 directional flat rollers; Lifting and/or untanking lugs; 1 rating plate; 1 filling plug; 1 draining device and treatment valve with sampler.

PM102310

Minera MP Oil immersed medium power transformer Standard These transformers comply with standards: IEC standards; French standards NFC 52 100 (1990); Schneider Electric guarantees that its transformers are assembled using new PCB-free components. Description This range consists of transformers complying with the following specification: Three-phase transformers, 50 or 60 Hz, for indoor or outdoor use (installation to be specified); Maximum ambient temperature: 40C (others ambient temperatures 45C, 50C, 55C, etc. upon request); Mineral oil immersed (other dielectric upon request); Breathing type with conservator ; Cover bolted on tank or welded bell type as per specification; ONAN, ONAF, ODAF or ODWF cooling type; Standard anti-corrosion surface treatment and coating (others possibilities upon request); Final colour RAL 7033. Standard fitting Each transformer includes: 1 off-circuit tappings switch with padlocking located on the cover ; this switch operates on the highest rated voltage to bring the transformer to the supply voltage-actual value (generally 5%, 3 or 5 positions); Porcelain bushings on primary and secondary sides; 2 earthing terminals; 1 conservator with level indicator tube; 1 silicagel airdryer; 1 Buchholz relay with 2 contacts (alarm and tripping); 1 thermostat with two contact (alarm and tripping);

Options The following fittings may be provided as an option: 1 on-load tap changer in the main tank (generally 12% - 19 positions maximum) with: - 1 motor drive unit fitted on tank; - 1 tap changer compartment in the conservator with a level indicator; - 1 protective relay and eventually, on request: - 1 parallel operation device; - 1 voltage regulator with voltage drop equalizer; - 1 remote indicator of tap changer position. Magnetic level indicator (with or without contact, please specify); HV fixed plug-in connectors HN 52 S 61 : - 250, 400, 630 or 1250 A - 24 kV; - 400, 630 or 1250 A - 36 kV. HV mobile plug-in connectors HN 52 S 61, straight or elbow (the cable characteristics should be specified); Condenser bushings; Increased creepage distance bushings; 1 bonnet on HV bushings: - in the air for connection by dry cables or busducts (except rated insulation level 72.5 kV) ; - oil immersed, hermetically sealed for cable connection; - SF6 immersed, hermetically sealed for connection by busbars on oil/SF6 bushings; Winding temperature indicator by thermal image ; Current transformer: bushing type around terminals - standard type for earth fault current detector; 1 overpressure valve (with or without contact, please specify); 1 automatic oil retaining valve (between conservator and tank); Atmoseal oil protection system; 1 treatment valve at the upper part of the tank ; 1 insulation valve for radiators; 4 jacking lugs with hauling eyes. The above options concern usual cases and are not restrictive. For other information,please consult us.

Oil Distribution Transformers


Electrical characteristics
Power (MVA) Insulation level - Primary - Secondary No-load losses (w) Load losses (w) Impedance voltage (%) 5 10 20

Minera MP

25

10

20

25

30

24-36 kV 7.2- 12 - 17.5 - 24 6 43 8 10 71 9 17 120 10 21 140 11

72.5 kV 7.2 - 17.5 7 43 8 11 71 9 18 120 10 22 140 11 25 160 11

Dimensions and weights ONAN Type Cooling Typical dimensions and weights are indicated in the table below for mineral oil immersed transformers, completely set up* with a standard type cooling. They correspond to transformers intented for systems of 7.2 to 72.5 kV having electrical characteristics as indicated in the previous table. For other voltages, other characteristics or when the transformers are immersed in another dielectric,dimensions and weights would be different, please, consult us.

E A

B
A

Transformers 5 MVA, with off-voltage tappings switch.

Transformers 5 MVA with on-load tap changer, or 10 to 25 MVA with off-voltage tappings switch or with on-load tap changer.

with off-voltage tappings switch Rated power (MVA) Dimensions (mm)


A B C E

with on-load tap changer Total weight Kg Dimensions (mm)


A B C E

Total weight Kg

Rated insulation level 24 kV


5 10 20 31 to 60

2700 3750 4300 4000

2100 2450 3900 3900

2500 3500 3600 3800

1000 1500 1500 1500

8500 17000 26500 35000

3400 3800 4600 4100

2200 2500 3900 3900

2550 3500 3600 3800

1000 1500 1500 1500

10000 19000 27000 37000

Rated insulation level 36 kV


5 10 20 31 to 60

3300 3900 4400 4200

2400 3300 3950 4300

2950 3600 3700 4000

1000 1500 1500 1500

11000 18000 27000 36000

3600 3900 4700 4800

2400 3400 4000 4300

3000 3600 3700 4000

1000 1500 1500 1500

13000 20000 29000 38000

Rated insulation level 72.5 kV


5 10 20 31 to 60

4100 3900 4500 4400

2600 3400 4000 4600

3300 3500 4000 4300

1000 1500 1500 1500

17000 18000 27000 41000

4000 5000 5000

3900 4100 4600

3600 4000 4300

1500 1500 1500

22000 32000 43000

ODAF Type Cooling


With off-voltage tappings switch
C

With on-load tap changer Dimensions (mm)


A B C

Rated power (MVA)


B

Dimensions (mm)
A B C

Total weight Kg

Total weight Kg

Rated insulation level 72.5 kV


20 25

3500 4000

2700 3000

4000 4300

21000 25000

4500 4700

3000 3000

4000 4300

23000 28000 Schneider Electric. All rights reserved. 11-2011

Rated insulation level >72.5 kV


Transformers 20 to 25 MVA, with off-voltage switch or on-load tap changer.

The above options concern usual cases and are not restrictive. For other information,please consult us.

Schneider Electric Industries SAS


35, rue Joseph Monier CS 30323 F - 92506 Rueil Malmaison Cedex (France) Tl. : +33 (0)1 41 29 70 00 RCS Nanterre 954 503 439 Capital social 896 313 776 www.schneider-electric.com NRJED311273EN As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this publication. Design: Schneider Electric Industries SAS Photos: Schneider Electric Industries SAS