Beruflich Dokumente
Kultur Dokumente
Copyright
This document and parts thereof must not be reproduced or copied without written permission from ABB, and the contents thereof must not be imparted to a third party, nor used for any unauthorized purpose. The software or hardware described in this document is furnished under a license and may be used, copied, or disclosed only in accordance with the terms of such license.
Trademarks
ABB and Relion are registered trademarks of the ABB Group. All other brand or product names mentioned in this document may be trademarks or registered trademarks of their respective holders.
Warranty
Please inquire about the terms of warranty from your nearest ABB representative.
ABB S.p.A. Power Products Division Unit Operativa Sace-MV Via Friuli, 4 I-24044 Dalmine Telephone: +39 035 6952 111 Facsimile: +39 035 6952 874 sacetms.tipm@it.abb.com http://www.abb.com
Disclaimer
The data, examples and diagrams in this manual are included solely for the concept or product description and are not to be deemed as a statement of guaranteed properties. All persons responsible for applying the equipment addressed in this manual must satisfy themselves that each intended application is suitable and acceptable, including that any applicable safety or other operational requirements are complied with. In particular, any risks in applications where a system failure and/ or product failure would create a risk for harm to property or persons (including but not limited to personal injuries or death) shall be the sole responsibility of the person or entity applying the equipment, and those so responsible are hereby requested to ensure that all measures are taken to exclude or mitigate such risks. This document has been carefully checked by ABB but deviations cannot be completely ruled out. In case any errors are detected, the reader is kindly requested to notify the manufacturer. Other than under explicit contractual commitments, in no event shall ABB be responsible or liable for any loss or damage resulting from the use of this manual or the application of the equipment.
Conformity
The IED is designed in accordance with the international standards of the IEC 60255 series, EMC Directive 2004/108/EC and MV circuit breaker standard IEC 62271-100.
Safety information
Dangerous voltages can occur on the connectors, even though the auxiliary voltage has been disconnected.
The frames of the IED and of the HMI have to be carefully earthed.
When the plug-in unit has been detached from the docking unit, do not touch the inside of the DU. The IED DU internals may contain high voltage potential and touching these may cause personal injury.
The IED contains components which are sensitive to electrostatic discharge. Unnecessary touching of electronic components must therefore be avoided.
Whenever changes are made in the IED, measures should be taken to avoid inadvertent tripping.
Table of contents
Table of contents
Section 1 Introduction.......................................................................5
This manual........................................................................................5 Intended audience..............................................................................5 Product documentation.......................................................................6 Product documentation set............................................................6 Document revision history.............................................................7 Related documentation..................................................................8 Symbols and conventions...................................................................8 Symbols.........................................................................................8 Document conventions..................................................................8 Functions, codes and symbols......................................................9
Section 2
Section 3
PCM600 tool...................................................................21
Connectivity packages......................................................................22 PCM600 and IED connectivity package version...............................22 PCM600 projects..............................................................................23 Communication between PCM600 and the IED...............................23
Section 4
Setting up a project........................................................25
Installing connectivity packages.......................................................25 Activating connectivity packages......................................................25 Setting up communication between PCM and the IED.....................26 Setting up IP addresses..............................................................26 Setting up the PC or workstation for point-to-point access to the local HMI's front port..........................................................27 Creating a new project......................................................................30 Building the plant structure...............................................................30 Inserting an IED................................................................................31 Inserting an IED in online mode..................................................32 Inserting an IED in offline mode..................................................38 Inserting an IED from the template directory...............................40 Setting the IED IP address in a project.............................................42 Technical key....................................................................................44 IEC 61850 naming conventions to identify an IED......................44 Setting the technical key..............................................................46
Table of contents
Section 5
Section 6
LHMI engineering...........................................................63
Single-line diagram engineering.......................................................63 Diagrams in Graphical Display Editor..........................................63 Display window and sequence order......................................64 Symbol library.........................................................................64 Supported single-line diagram symbols.................................65 HMI display raster layout and text font selection....................67 Text handling..........................................................................67 Adding static text....................................................................68 Adding a measurand..............................................................68 Adding symbols into a display page.......................................69 Drawing lines to create links...................................................69 Bay configuration engineering.....................................................70 Creating a complete HMI display page..................................70 Linking process objects..........................................................71
Section 7
Table of contents
IEC 61850 engineering process.......................................................78 Exporting SCL files from PCM600...............................................79 Exporting SCD files................................................................79 Exporting ICD or CID files......................................................81 Engineering vertical and horizontal communication in CCT600.......................................................................................82 Importing SCL files to PCM600...................................................84 Importing SCD files................................................................84 Importing ICD or CID files......................................................86
Section 8
Glossary.........................................................................89
1MRS757306 B
Section 1 Introduction
Section 1
Introduction
1.1
This manual
The engineering manual contains instructions on how to engineer the IEDs using the different tools in PCM600. The manual provides instructions on how to set up a PCM600 project and insert IEDs to the project structure. The manual also recommends a sequence for engineering of protection and control functions, LHMI functions as well as communication engineering for IEC 61850 and other supported protocols.
1.2
Intended audience
This manual addresses system and project engineers involved in the engineering process of a project, and installation and commissioning personnel, who use technical data during engineering, installation and commissioning, and in normal service. The system engineer must have a thorough knowledge of protection and/or control systems, protection and/or control equipment, protection and/or control functions and the configured functional logics in the IEDs. The installation and commissioning personnel must have a basic knowledge of handling electronic equipment.
Section 1 Introduction
1MRS757306 B
1.3
1.3.1
Product documentation
Product documentation set
Decommissioning deinstalling & disposal Planning & purchase
Commissioning
Engineering
Engineering manual Installation manual Commissioning manual Operation manual Service manual Application manual Technical manual Communication protocol manual en07000220.vsd
IEC07000220 V1 EN
Figure 1:
The engineering manual contains instructions on how to engineer the IEDs using the different tools in PCM600. The manual provides instructions on how to set up a PCM600 project and insert IEDs to the project structure. The manual also recommends a sequence for engineering of protection and control functions, LHMI functions as well as communication engineering for IEC 61850 and other supported protocols. The installation manual contains instructions on how to install the IED. The manual provides procedures for mechanical and electrical installation. The chapters are organized in chronological order in which the IED should be installed. The commissioning manual contains instructions on how to commission the IED. The manual can also be used by system engineers and maintenance personnel for assistance during the testing phase. The manual provides procedures for checking of external circuitry and energizing the IED, parameter setting and configuration as
Operation
Installing
Maintenance
1MRS757306 B
Section 1 Introduction
well as verifying settings by secondary injection. The manual describes the process of testing an IED in a substation which is not in service. The chapters are organized in chronological order in which the IED should be commissioned. The operation manual contains instructions on how to operate the IED once it has been commissioned. The manual provides instructions for monitoring, controlling and setting the IED. The manual also describes how to identify disturbances and how to view calculated and measured power grid data to determine the cause of a fault. The troubleshooting manual contains quick answers to frequently asked questions about the IED use. The manual provides instant solutions to the problems that the end used might face while using the IED, both at commissioning and during the eVD4 life. The service manual contains instructions on how to service and maintain the IED. The manual also provides procedures for de-energizing, de-commissioning and disposal of the IED. The application manual contains application descriptions and setting guidelines sorted per function. The manual can be used to find out when and for what purpose a typical protection function can be used. The manual can also be used when calculating settings. The technical manual contains application and functionality descriptions and lists function blocks, logic diagrams, input and output signals, setting parameters and technical data sorted per function. The manual can be used as a technical reference during the engineering phase, installation and commissioning phase, and during normal service. The communication protocol manual describes a communication protocol supported by the IED. The manual concentrates on vendor-specific implementations. The point list manual describes the outlook and properties of the data points specific to the IED. The manual should be used in conjunction with the corresponding communication protocol manual. Some of the manuals are not available yet.
1.3.2
Section 1 Introduction
1MRS757306 B
Download the latest documents from the ABB Web site http://www.abb.com/mediumvoltage.
1.3.3
Related documentation
1.4
1.4.1
The information icon alerts the reader of important facts and conditions.
The tip icon indicates advice on, for example, how to design your project or how to use a certain function. Although warning hazards are related to personal injury, it is necessary to understand that under certain operational conditions, operation of damaged equipment may result in degraded process performance leading to personal injury or death. Therefore, comply fully with all warning and caution notices.
1.4.2
Document conventions
A particular convention may not be used in this manual. Abbreviations and acronyms in this manual are spelled out in the glossary. The glossary also contains definitions of important terms. Push-button navigation in the LHMI menu structure is presented by using the push-button icons. To navigate between the options, use and . HMI menu paths are presented in bold. Select Main menu/Settings. WHMI menu names are presented in bold. Click Information in the WHMI menu structure. LHMI messages are shown in Courier font. To save the changes in non-volatile memory, select Yes and press . Parameter names are shown in italics.
Breaker Integrated Protection RBX615 Engineering Manual
1MRS757306 B
Section 1 Introduction
The function can be enabled and disabled with the Operation setting. Parameter values are indicated with quotation marks. The corresponding parameter values are "On" and "Off". IED input/output messages and monitored data names are shown in Courier font. When the function starts, the START output is set to TRUE.
1.4.3
Section 1 Introduction
Function Three-phase overvoltage protection IEC 61850 PHPTOV1 PHPTOV2 PHPTOV3 Positive-sequence undervoltage protection Negative-sequence overvoltage protection Three-phase thermal protection for feeders, cables and distribution transformers Negative-sequence overcurrent protection for motors Loss of load supervision Motor load jam protection Motor start-up supervision Phase reversal protection Thermal overload protection for motors Circuit breaker failure protection Three-phase inrush detector Protection trip conditioning PSPTUV1 NSPTOV1 T1PTTR1 IEC 60617 3U> (1) 3U> (2) 3U> (3) U1< U2> 3Ith>F
1MRS757306 B
MNSPTOC1 MNSPTOC2 LOFLPTUC1 JAMPTOC1 STTPMSU1 PREVPTOC MPTTR1 CCBRBRF1 INRPHAR1 TRPPTRC1 TRPPTRC2
I2>M (1) I2>M (2) 3I< Ist> Is2t n< I2>> 3Ith>M 3I>/I0>BF 3I2f> Master Trip (1) Master Trip (2)
46M (1) 46M (2) 37 51LR 49,66,48,51 LR 46R 49M 51BF/ 51NBF 68 94/86 (1) 94/86 (2)
Control Fixed circuit-breaker control Withdrawable circuit-breaker control Earthing switch indication Earthing switch control Truck control H-bridge control FCBXCBR1 WCBXCBR1 ESSXSWI1 MESXSWI1 TRXSWI HBGAPC1 HBGAPC2 Emergency startup Auto-reclosing Condition monitoring Circuit-breaker condition monitoring Current circuit supervision Coil switch supervision (open) Coil switch supervision (close) Fuse failure supervision Motor runtime counter Measurement Disturbance recorder Three-phase current measurement Table continues on next page 10 Breaker Integrated Protection RBX615 Engineering Manual RDRE1 CMMXU1 3I 3I ESSCBR1 CCRDIF1 OCSSCBR1 CCSSCBR1 SEQRFUF1 MDSOPT1 CBCM MCS 3I TCS (Open) TCS (Close) FUSEF OPTS CBCM MCS 3I TCM (Open) TCM (Close) 60 OPTM ESMGAPC1 DARREC1 I O CB I O CB I O ES I O ES I O DC HBC HBC ESTART OI I O CB I O CB I O ES I O ES I O DC HBC HBC ESTART 79
1MRS757306 B
Section 1 Introduction
Function Sequence current measurement Residual current measurement Three-phase voltage measurement Residual voltage measurement Sequence voltage measurement Three-phase power and energy measurement Sensor temperature IEC 61850 CSMSQI1 RESCMMXU1 VMMXU1 RESVMMXU1 VSMSQI1 PEMMXU1 VDSTMP IEC 60617 I1, I2, I0 I0 3U U0 U1, U2, U0 P, E VDTS IEC-ANSI I1, I2, I0 In 3U Vn U1, U2, U0 P, E VDTM
11
12
1MRS757306 B
Section 2
PCM600 is used for various tasks in the IED engineering process. IED engineering management Organizing the bay IEDs in the structure of the substation by defining voltage levels and bays below the substation. PCM600 manages the project. Configuring the IED functions (for example, protection and control functions) by using the Application Configuration tool. Configuring the parameters and setting values for the IED itself and for the process functions by using the Parameter Setting tool. Drawing single-line diagrams and making links to dynamic process values by using the Graphical Display Editor. The single-line diagrams are displayed in LHMI on the bay IED. Configuring connections between the application configuration function blocks and physical hardware input and outputs by using the Signal Matrix tool.
Communication management IEC 61850 station communication engineering is done with a separate tool, for example, CCT600. PCM600 interacts with CCT600 by importing and exporting SCL files. Configuring the GOOSE receive data connections to the IED's application configuration function blocks. Configuring protocol data mapping with the Communication Management tool for the supported protocols.
Disturbance record management Generating overviews on the available (disturbance) recordings in all connected protection IEDs by using the Disturbance Handling tool. Manually reading the recording files (in the COMTRADE format) from the protection IEDs by using the Disturbance Handling tool or automatically by using the PCM600 Scheduler. Managing recording files with the Disturbance Handling tool. Creating recording file content overview reports for fast evaluation with assistance of the Disturbance Handling tool.
Service management Monitoring the selected signals of an IED for commissioning or service purposes by using the Signal Monitoring tool.
13
1MRS757306 B
GUID-AEEFCDDD-591F-4555-A6D5-78FC69BF623F V1 EN
Figure 2:
There are also additional functions for managing projects and organizing user rights. PCM600 user management Organizing users regarding their rights, profiles and passwords to use different tools and functions in the tools. Defining allowed activities for user profiles to use tools in PCM600.
Once the engineering of the IED is finished, the results must be written to the IED. The connection between the physical IED and PCM600 is established via an Ethernet link on the front or rear port on the IED.
2.1
14
1MRS757306 B
The number of IEDs in one PCM600 project is limited. An error message is displayed if you exceed the limit. Divide larger projects into several PCM600 projects.
HSI
(station-IED1)
NCC-GW
(station-IED2)
PCM600
(tool set)
Station level
Station bus
Station Communication
bay IED 1
bay IED 2
bay IED n
Bay level
IEC08000101.vsd
IEC08000101 V1 EN
Figure 3:
The monitoring and control system can be divided into three main parts. Bay level IEDs Station communication Station level IEDs
All three parts require specific engineering and configuration. The plant structure is used to identify each IED in its location within the substation organization. Plant structure is a logical image of the substation and the bays within the substation. The organization structure for the IEDs may differ from the structure of the primary equipment in the substation. In PCM600 it is possible to set up a hierarchical structure of five levels for the IED identification. Project Substation = name of the substation Voltage level = identifies to which grid type or part the IED belongs in the substation Bay = bay within the voltage level IED = the selection of the IED that is used in the bay; it is possible to insert several IEDs within a bay, for example, one control IED and two protection IEDs
15
1MRS757306 B
2.2
Preconfigurations concept
The RBX615 is a configurable device but it is offered with optional factory-made application, called preconfigurations, that contain protection, control, supervision and measurement function blocks and default logical connections. The preconfigurations contribute to faster commissioning and less engineering of the IED. The product also includes the preconfiguration specific default single-line diagram. Current and voltage channels for protection and measurement functions are fixed and cannot be reassigned with Signal Matrix or Application Configuration in PCM600. The single-line diagram consists of an application-specific general arrangement of a single-line diagram that includes position indications and the selection of controllable objects and measurements. The content of the preconfiguration depends on the intended power system application. The standard configurations also have selectable options, which are selected when ordering the IED. Some of the options are related to the IED hardware. The preconfigurations can be used as such, but they can also be modified by using PCM600. The standard preconfiguration itself can be modified or extended by using the Application Configuration tool, the Signal Matrix tool and the Communication Configuration tools. The single-line diagram can also be modified with Graphical Display Editor. Some of the preconfigurations offer very wide functionality in means of number of different functions available as part of the product configuration. It is possible to use all of the offered functions at the same time. However, if unused function blocks are removed from the preconfiguration with the Application Configuration, more resources in the IED can be used for other purposes, for example : More advanced user application logic with Application Configuration Extensive use of GOOSE sending and receiving Increasing the amount of data reported for 61850 clients
In case the configuration capacity of the IED is exceeded, the relay will enter to IRF error state at the bootup.
16
1MRS757306 B
2.3
Workflow
Start
Create plant structure and insert IED objects
Parametrization
GDE
Supported protocols
Signal engineering
CMT
IEC09000623_1_en.vsd
IEC09000623 V1 EN
Figure 4:
IED engineering workflow proposal based on practical experience and dependencies of the steps
It is possible to make a different kind of a sequence based on the information available at the time when the project is started. This means that several iterations may be needed to complete the project. Setting up a PCM600 project The plant structure is built according to the substation structure.
17
1MRS757306 B
The number of IEDs in one PCM600 project is limited. An error message is displayed if you exceed the limit. Divide larger projects into several PCM600 projects. The IED is created in offline or online mode. In both cases a suitable IED connectivity package is used. Additionally, a project template can be used for the IED creation. The IED objects in PCM600 are renamed uniquely according to the project definitions.
Application configuration in the Application Configuration tool The protection or control function is configured, for example, for a feeder, as requested. The configuration made in the Application Configuration tool is saved to make the interfaces and signals available for other engineering tools within PCM600, for example, for the Parameter Setting tool.
Parameter setting and configuration in the Parameter Setting tool The configuration parameters of the physical IED for communication channels and the CT and VT conversion values of the transformer module, for example, are checked. If needed, the setting values are checked and adjusted with the Parameter Setting tool.
Single-line diagram configuration in the Graphical Display Editor A single-line diagram of the switching devices in a bay is created. Measurements are included when needed. The dynamic elements are linked to the functions created in the Application Configuration tool; for example, a breaker object is linked to the circuit breaker control function.
LHMI engineering The LED behavior is defined with Parameter Setting. The LEDs are configured with Application Configuration.
Communication protocol engineering The communication engineering details are protocol dependent. The connectivity package creates the IEC 61850 configuration for vertical communication automatically and it is directly suitable, in most cases, for IEC
18
1MRS757306 B
61850 client configuration. A station configuration tool, for example CCT600, is used for horizontal communication. The Communication Management tool is used for other protocols; for example, Modbus. The IED restarts automatically when writing an IED configuration where changes have been made. It is not possible to communicate with the IED during restart.
19
20
1MRS757306 B
Section 3
PCM600 tool
Protection and Control IED Manager PCM600 offers all the necessary functionality to work throughout all stages of the IED life cycle. Planning Engineering Commissioning Operation and disturbance handling Functional analysis
With the individual tool components, you can perform different tasks and functions and control the whole substation. PCM600 can operate with many different topologies, depending on the customer needs. PCM600 is used to conduct complete engineering and configuration activities needed for the bay level IEDs. Product type and version specific engineering data needed by PCM600 for protection, control and communication engineering of a particular bay IED is provided in an IED connectivity package. PCM600 communicates with the bay IEDs via an Ethernet connection. The connection allows to read and write all configuration data needed for proper operation from or to the IED. The IEDs have communication interfaces for protocols and media used for station communication. Bay IED IEC 61850 station communication files can be exported from PCM600 to the station engineering tools for engineering of station communication between the bay IEDs and station IEDs. A PC with PCM600 can be connected to any 615 series IED within a station by using the Ethernet connection. The Ethernet connection can later be used also for service and maintenance purposes. In addition, the connection is used to handle disturbance records from the protection IEDs using the IEC 61850 file transfer. The modern-day IEDs are designed on the concept of the IEC 61850 standard. This is mainly given for the organization of functions represented by an equivalent logical node in the IEC 61850 standard. See the IEC 61850 parameter list for the available logical nodes in the IED, following the structure and rules in part 7 of the IEC 61850 standard in an IED configuration. The engineering of the used communication protocols is a separate task and an addition to the engineering of protection and control functions. PCM600 can be used for different purposes throughout the IED life cycle. A set of special tools is available for different applications.
21
1MRS757306 B
The applications can be organized into groups. IED product engineering IED communication engineering per protocol IED system monitoring IED product diagnostic For more information, see PCM600 documentation.
3.1
Connectivity packages
Connectivity package is a collection of software and information related to a specific protection and control terminal providing system products and tools to connect and interact with the IED. Connectivity packages are used to create configuration structures in PCM600. The latest PCM600 and connectivity packages are backward compatible with older IED versions. Update Manager is a tool that helps in defining the right connectivity package versions for different system products and tools. Update Manager is included in products supporting the connectivity concept. In addition to other products supporting the connectivity concept, the connectivity packages for PCM600 contain a description of IED's internal parameters and their properties (such as data format, unit, setting range, visibility and access rights) as well as software components that adapt the IED-specific interfaces to the standard interfaces of system products and tools, such as IED-specific dispatchers for tools. This means that there is a protocol-specific adaptation for the parameter setting and disturbance handling tool components, for example, disturbance recorder reading according to COMTRADE. The description texts can be translated into other languages as well.
3.2
22
1MRS757306 B
3.3
PCM600 projects
A typical project in PCM600 contains a plant structure including one or several IED objects, where each IED object contains the engineering data created or modified using the different PCM600 tools. Several projects can be created and managed by PCM600, but only one project can be active at a time. With PCM600, it is possible to do various tasks. Open existing projects Import projects Create new projects Export projects Delete projects Rename projects Copy and paste projects
The extension of the exported project file is .pcmp. The files are only used for exporting and importing projects between PCM600s.
3.4
1MRS757306 B
For successful IED engineering and usage, check the workstation firewall TCP and UDP port configurations, especially for IEC 61850 and FTP. Other protocols are not used for engineerging and/or they are optional.
Table 2:
Protocol File Transfer Protocol (FTP) IEC 61850 Web Server HTTP Simple Network Time Protocol (SNTP) Modbus TCP
24
1MRS757306 B
Section 4
Setting up a project
4.1
4.2
GUID-913278D2-3A75-4E48-9DCA-70F97FEC2580 V1 EN
Figure 5:
2.
The Update Manager shows the IEDs that are compatible with the installed PCM600 version. Select ABB IED Connectivity Package eCB. Always use the latest version of the connectivity package.
25
1MRS757306 B
GUID-54B480BC-E69A-4BFE-BE0F-42B7BF073ABB V1 EN
Figure 6:
PCM600 recognizes the installed connectivity package(s) during startup and the corresponding IED types are available in PCM600 when starting a new project.
4.3
4.3.1
1.
Set the default IP address for the IED rear port and the corresponding subnet mask via the LHMI path: Configuration/Communication/Ethernet/Rear port.
Default IP address for the IED rear port Corresponding subnet mask
26
1MRS757306 B
192.168.2.10
255.255.0.0
Communication fails if the IP addresses of the front and the rear port belong to the same subnet.
4.3.2
Setting up the PC or workstation for point-to-point access to the local HMI's front port
This instruction is an example that applies to standard PCs using the Microsoft Windows operating system. A laptop with one Ethernet interface is used in the example. Administrator rights are required to change the PC communication setup. The IED's DHCP server for the front port assigns an IP address for the computer. The computer must be configured to obtain its IP address automatically. 1. With an Ethernet cable, connect two physical Ethernet interfaces together without a hub, router, bridge or switch in between. Use standard straight-through or crossover Ethernet cables. The minimum length for the cable is 2 m. The connector type is RJ-45.
IED
RJ-45
PCM600
Tx Rx
IEC09000096-1-en.vsd
Tx Rx
IEC09000096 V1 EN
Figure 7:
Point-to-point link between the IED and PCM600 using a crossover Ethernet cable
2.
27
1MRS757306 B
IEC09000355-1-en.vsd
IEC09000355 V1 EN
Figure 8:
3.
The Network connections dialog box is displayed. Right-click the Local Area Connection and select Properties.
IEC09000356-1-en.vsd
IEC09000356 V1 EN
Figure 9:
28
1MRS757306 B
IEC09000357-1-en.vsd
IEC09000357 V1 EN
Figure 10:
4.
From the list of configured components, select Internet Protocol (TCP/IP) using this connection and click Properties. The Internet Protocol (TCP/IP) Properties dialog box is displayed.
IEC09000358-1-en.vsd
IEC09000358 V1 EN
Figure 11:
TCP/IP settings
5. 6.
Click Obtain an IP address automatically and OK. Close all open dialog boxes and start PCM600.
29
1MRS757306 B
4.4
IEC09000375-1-en.vsd
IEC09000375 V1 EN
Figure 12:
6. 7. 8.
In the Project Name box, give a name for the project. Optionally, write a description of the project in the Description box. Click Create.
4.5
30
1MRS757306 B
1.
Create a new plant structure. In the Plant Structure view, right-click and select New/ Create from Template. In the Plant Structure view, right-click and select New/ General and select the element: either IED Group or Substation.
2. 3.
On the menu bar, click View/ Object Types. Select the needed elements and drag-and-drop them into the plant structure.
GUID-5805326F-8DFC-49D7-B1B4-B856937E7278 V1 EN
Figure 13:
4.
Rename each level in the structure by the names/identifications used in the grid. Right-click the level and select Rename. Rename the levels in the Object Properties view.
4.6
Inserting an IED
The context menu or the Object Types view shows the available 615 series IEDs that can be inserted, on the bay level, into the plant structure according to the installed connectivity package. It is possible to do various tasks in the plant structure. Insert an IED to offline mode or online mode Import a template IED that is available in the template library as a .pcmt file
31
1MRS757306 B
From the plant structure it is possible to see whether the inserted IED is in the offline or online mode. A red cross in front of the IED symbol indicates an offline mode, a green tick indicates online mode.
GUID-1A8FC193-A6F6-498B-9B55-5D3BDCEDF182 V1 EN
Figure 14:
GUID-012A0469-CD89-4D3E-A4D2-712148BF2C5A V1 EN
Figure 15:
4.6.1
32
1MRS757306 B
To set up an IED online, the IED must be connected to PCM600. 1. In the Plant Structure view, right-click the bay and from the list that appears, select New/eCB/eVD4 RBX615.
GUID-084696CA-213B-431B-A7E0-4225874E9320 V1 EN
Figure 16:
You can also drag-and-drop an IED from the Object Types view to the bay level. The Configuration Mode Selection Page dialog box opens.
33
1MRS757306 B
GUID-5AB4ABCB-9E1E-4F89-B74F-4BCA30B80BD9 V1 EN
Figure 17:
2.
Select Online Configuration and click Next. The Communication protocol selection page is displayed.
34
1MRS757306 B
GUID-38779D93-3C55-489B-B3FD-2C0DA6999627 V1 EN
Figure 18:
3.
In the IED protocol list, select the IED communication protocol and click Next. The Communication protocol page is displayed.
35
1MRS757306 B
GUID-92C1276D-B27F-40EA-9F51-A1F7ADDD7317 V1 EN
Figure 19:
4.
In the Port list, select the port. If the rear port is selected, insert the correct IP address (of the physical IED to be configured) into the IP address box.
5.
Communication configuration is now defined. Click Next in the Configuration Wizard. The Composition code detection page is displayed.
36
1MRS757306 B
GUID-F10E0D96-D3EE-4B9F-9D0E-A7BB0FE3BD39 V2 EN
Figure 20:
6. 7.
Click Scan to scan/read the Composition code of the IED. When the generation process is completed press Next. The Setup Complete page is displayed.
37
1MRS757306 B
GUID-DF705520-4F7F-4A2A-B47A-B896EEBA0031 V1 EN
Figure 21:
8.
4.6.2
38
1MRS757306 B
You can also drag-and-drop an IED from the Object Types view to the bay level. The Configuration Mode Selection Page dialog box opens.
GUID-8C581D98-4489-4102-A765-24A834CCA7A9 V1 EN
Figure 22:
3.
4.
Select Offline Configuration and click Next. Setting up an IED in the offline mode is similar as in the online mode; however, with offline mode it is not necessary to type the correct IP address in the Communication port and IP address dialog box. Select the composition code of the IED.
39
1MRS757306 B
GUID-369A3572-7A42-4E95-878C-714DFCFBD831 V2 EN
Figure 23:
5.
4.6.3
40
1MRS757306 B
You can insert a template IED only when the bay is selected in the plant structure.
1.
In the Plant structure view, select the bay, right-click and select New/ Create from template. The Create New Object from Template dialog box opens.
GUID-39D15219-A1B4-45DB-989C-893F22096AC3 V1 EN
Figure 24:
2. 3.
Select the eCB from the list of available IEDs. Click the icon on the right column in the list of available templates. The Template Properties dialog box opens.
41
1MRS757306 B
GUID-E768E45D-8449-4B86-A7B8-76183E9FF262 V1 EN
Figure 25:
4. 5.
Check and verify the template information and click Close to close the window. The Create New Object from Template dialog box is displayed. You can now delete, import or create a template by clicking the corresponding button. To delete the selected template, click Delete Template. To import a template from the selection window, click Import Template. To insert the selected IED to the bay, click Create. It is possible to insert more than one IED from the Create New Object from Template dialog box. The dialog box remains open until you click Close.
6.
4.7
42
1MRS757306 B
On the first page of the wizard when including a new IED into a project. In the IP address box of the IED's Object Properties dialog box.
GUID-D2BD7144-A7BE-4D23-B047-6E269368A5A3 V1 EN
Figure 26:
GUID-2C5E84EF-9FCD-4596-B1FE-FF659E9D323F V1 EN
Figure 27:
The used alternative depends on the time at which the IP address is available. Entering the IP address via the IED Object Properties dialog box is possible at any time. 1. 2.
Breaker Integrated Protection RBX615 Engineering Manual
In the Plant Structure view, select the IED to which the IP address is to be entered. Select View/Object Properities on the menu bar.
43
1MRS757306 B
3.
Object Properties dialog box is opened. Type in the IP address to the IP Address row.
4.8
Technical key
Both a physical IED and an IED object in PCM600 have a technical key. The purpose of the technical key is to prevent a configuration download to a wrong IED. The technical key in the IED and PCM600 must be the same, otherwise it is not possible to download a configuration. Each IED in a PCM600 project must have a unique technical key. Therefore, it is not possible to set the same technical key for several IEDs in the same PCM600 project. The IED is delivered with a factory default technical key. The validation of the technical keys between PCM600 and the IED does not occur if the IED contains the factory default technical key.
The technical key property in PCM600 corresponds to the IED name attribute in SCL files. Avoid changing the IED name attribute outside PCM600, because data in PCM600 may get lost when importing the SCL files. The technical key must be the same for the communication between the IED and PCM600. The technical key can be read from the IED and updated to PCM600, or the PCM600 technical key can be written to the IED. Alternatively, a separate technical key can be defined. It is not possible to write a configuration to IED if the there is a mismatch between the IED object and the physical IED technical key. Ensure that the IED object in PCM600 has the same IP address as the physical IED that is intended to be connected.
You can change the technical key for an IED object in the Object Properties dialog box in PCM600.
4.8.1
44
1MRS757306 B
6 clause 8.4, the SCL model allows two kinds of project designations in the object properties: a technical key and a user-oriented textual designation. Technical key is used in engineering drawings and for signal identifications. This is contained in the attribute name as an identification of each object. If the value is used as a reference to an object, it is contained in an attribute name starting with a string denoting the reference target object type and ending with the string Name. The technical key is used within SCL for referencing to other objects. Note that the name is a relative identification within a hierarchy of objects. User-oriented textual designation is contained in the desc attribute. Attributes are not allowed to contain carriage return, line feed or tab characters. The semantics of desc must also be relative within an object hierarchy. PCM600 takes care of the two possibilities. The two possible signal designations are available per object in the object properties for all hierarchical levels beginning with the station as the highest level. The technical key is automatically generated based on the rules and type specifications of IEC 61346 and the extended definitions assigned for substations by a technical committee. The technical key is shown in the Object Properties dialog box under SCL Technical Key or Technical Key. The station is predefined by AA1" where 1 is the index. To get the real station name that is used, it is possible to rename the SCL Technical Key for the station as the name used by the project. To minimize the word length, take a short form because this name is used also in the transmitted messages to identify the events, for example. The voltage level. In the example it is 20 kV and J1 is selected from the list below SCL Technical Key in the Object Properties dialog box. The bay and the IED are appended with the coding defined in the IEC 61346 standard and the substation definition lists. In the example, Bay SCL Technical Key part is Q01 and IED is A1.
The user-oriented textual designation is visible in the Plant structure view for each object. It is the name given by default or changed by using the Rename function.
45
1MRS757306 B
GUID-2DE68621-F1B5-4A7D-8D3F-CDF1B18F57AE V1 EN
Figure 28:
The created technical key for the full path name of the IED would be: AA1J1Q01A1. AA1 = substation in the project J1 = voltage level from 20 to 30 kV Q01= the third bay in the voltage level A1 = first IED in the bay Q01
4.8.2
46
1MRS757306 B
GUID-D7F9CA98-E37D-42F0-9A80-B76B2E6B966D V1 EN
Figure 29:
47
1MRS757306 B
GUID-96ECAC44-6A11-4C1F-B50C-3E8A80051950 V1 EN
Figure 30:
3.
Click OK. The technical key is read from the IED and the Set Technical Key dialog box opens.
GUID-12A08880-C3B8-4339-B0A2-112CF301E464 V1 EN
Figure 31:
4.
In Set Technical Key dialog box, select the techical key to be used. There are three alternatives. Use the existing technical key in the IED Use the existing technical key defined for the IED object in PCM600 Set a user-defined technical key, which changes the technical key for both the physical IED and IED object in PCM600 Do not use a technical key that has more than 10 characters.
5.
48
1MRS757306 B
It is not possible to set a user-defined name or select the Technical key in IED if the value is the same as already given to another IED object in the PCM600 project. In that kind of a situation, a dialog box opens informing of the situation.
49
50
1MRS757306 B
Section 5
5.1
For more information on the function blocks, see the technical manual. Most function blocks are mapped as logical nodes according to the IEC 61850 standard. See the 61850 parameter list for more information. If a function block is removed with Application Configuration, the function related data disappears from the menus, with the exception of some basic function blocks, which are mandatory and thus cannot be removed from the IED configuration by removing them from the Application Configuration. Other function blocks are not mapped as logical nodes; for example, logical gates. The basic features of the Application Configuration tool include organizing of an application configuration as well as different application configuration programming features. Organizating an application configuration Organize an application configuration into a number of logical parts (MainApplication) Organize a MainApplication over a number of pages Insert function blocks, make connections and create variables Include the hardware I/O channels directly to the application configuration Calculate the execution order automatically by clicking Calculate execution order on the toolbar.
51
1MRS757306 B
Document the application configuration: for example, make printouts Save application configurations as templates in an application library to reuse them in other IEDs Validate the application configuration during the configuration process on demand and while writing the application configuration to the IED
For instructions on how to perform the different tasks in PCM600, see PCM600 online help.
5.1.1
Function blocks
Function blocks are the main elements of an application configuration. They are designed for a various number of functions and organized into type groups. The different function block types are shown in the Object Types view. Function block data can be modified with the Application Configuration tool. Set user-defined names for function blocks and signals marked with blue text. Signals that have a user-defined name created with the Application Configuration tool are only visible in the Parameter Setting tool if the IED configuration is written to the IED and read back to PCM600. Otherwise, the default signal name is shown in the Parameter Setting tool.
If possible, set the user-defined name to a signal before connecting the signal to other function blocks. Set IEC 61850, ANSI or IEC 60617 symbol standard. Set IEC or/and ANSI naming style. Lock function blocks. Set visibility for execution order, cycle time and instance number. Manage signals; for example, hide, show and rearrange.
52
1MRS757306 B
GUID-8286E540-2E3C-41FD-BCC7-F46E09A5A030 V1 EN
Figure 32:
1. 2. 3. 4. 5. 6. 7. 8. 9.
Hardware, binary input channel User-defined signal name Function block, locked (red) User-defined function block name User-defined signal name Function block inputs Execution order, cycle time Hardware, binary output channel Function block outputs
5.1.2
5.1.3
53
1MRS757306 B
Each time a new function block is selected, these parameters must be selected from the lists in the Application Configuration tool. Depending on the function block type, some of the three parameters are selectable and some not. The cycle time may be predefined to one value. The instance number is a counter for the total possible number of function blocks of that type used within the application configuration. The Execution Order and Instance Number are a combination that is predefined within a product. It is possible to select a pair out of the list.
GUID-10D677B2-9F92-423C-ABAB-3C84ECD8DCA6 V1 EN
GUID-35B60A3A-D995-4B61-ADFD-4B5BB3C60474 V1 EN
Figure 33:
For eVD4 the Cycle Time is always equal to 0 since the correct cycle time is automatically selected according to the frequency of the network IED is connected to.
To automatically calculate the execution order, click Calculate Execution Order on the tool bar.
54
1MRS757306 B
Section 5 Protection and control engineering Execution order and feedback loops
With the Application Configuration tool it is possible to draw multi-layer configuration logic that contains feedback loops. The execution order of logic functions is calculated automatically in the Application Configuration tool, but the execution order can be set manually also. If the automatically calculated value causes the function to be executed one task cycle time after the other logic functions in the same loop, the execution order number can be set manually to prevent delays, for example, in output activation. The following example shows a simple situation where the execution order causes one cycle time delay if the NOT port is executed in the order determined by the automatic calculation.
5.1.4
GUID-29F2FA2A-CB9C-4715-A0DE-069BE4F93B08 V1 EN
Figure 34:
To change the execution order, right-click the function block and select Change Cycle Time ExecOrder. When the window opens, set the desired value.
55
Figure 35: Feedback loop situation with automatically calculated execution order
1MRS757306 B
To change the execution order right-click the function block and select Change Cycle Time ExecOrder. When the window opens set the desired value.
GUID-351BC533-DFF5-4472-AC32-497E37865E40 V1 EN
Figure 35:
52
By setting a smaller execution number than in the AND port to where the NOT port is connected, it is possible to fix the execution order of all functions in a loop so that they are handled in the same task.
eVD4 RBX615 Engineering Manual
GUID-9FB644DD-B602-4EC7-8118-A5BDD1983C48 V1 EN
Figure 36:
Feedback loop situation with manually fixed execution order for NOT port
Once the execution order has been manually changed, the system will disable the automatic calculation of the execution order for that logic function. To restore it right click on the block and select the Include FB in calculation option.
56
1MRS757306 B
GUID-F8D63528-3D27-43A3-AE31-5B81070F4D09 V1 EN
Figure 37:
5.1.5
Configuration parameters
Configuration parameters can be viewed and set with the Parameter Setting tool.
5.1.6
5.1.7
Hardware channels
Hardware channels can only be connected to a function block input or output. A hardware connection can be established with the Application Configuration tool or Signal Matrix tool. When a hardware channel is connected, a graphical symbol appears in the Application Configuration tool. The connection is also displayed in the Signal Matrix tool with a cross mark. Hardware channels are always visible in the Signal Matrix tool.
57
1MRS757306 B
GUID-800CC4B4-F21A-4619-A9BA-32130D17B422 V1 EN
Figure 38:
There are three types of supported hardware channels. Binary input channels Binary output channels
Hardware input channel can be used as often as needed. A hardware binary output channel is taken from the list of available channels when a new channel is requested. This prevents using the same hardware binary output channel twice.
5.1.8
Validation
Validation checks the application configuration for errors concerning the rules and restrictions defined for making a MainApplication on three levels. During the logic creation, while making a connection or placing a function block On demand by starting the validation When writing the application configuration to the IED
5.1.8.1
5.1.8.2
Validation on demand
The validity of an application configuration can be checked by clicking Validate Configuration in the toolbar. The Application Configuration tool checks the application configuration for formal correctness. The found problems are divided into warnings and errors. Warnings, marked with a yellow warning icon
58
1MRS757306 B
Example: a variable connected to an output signal that is not connected Example: if the user connects an output from a higher execution order function to inputs of lower execution order function Example: unconnected hardware output
Warnings do not prevent writing to the IED. However, errors must be corrected before writing the application configuration to the IED. The application configuration can be saved and the Application Configuration tool can be closed with open errors, but not written to the IED. These problems are listed in the Output view under the Application Configuration tab. Double-clicking the error or warning row navigates to the MainApplication/ Page/ Area, where the problems are identified.
GUID-303A5310-DB12-4713-B406-5ED6098B35A1 V1 EN
Figure 39:
5.1.8.3
59
1MRS757306 B
5.2
A common writing from PCM600 to the IED, where parameters are changed in the Parameter Setting tool, overwrites any parameter changes made locally with LHMI. All variables listed and displayed in the parameter list can be sorted into two groups. Configuration parameters Setting parameters
5.2.1
Configuration parameter
Configuration parameter specifies the operation mode of an application function or of the IED. These are basic configurations that are normally configured only once and then settled. The IED configures itself during startup according to the given configuration parameter values.
5.2.2
Setting parameter
Setting parameter (short form: setting) is a parameter that can be changed in the IED at runtime.
5.2.3
Setting group
Nearly all settings used by the IED for protection application functions are organized into a group of settings. Up to four setting groups can be configured with different values. The IED supports the selection of a setting group at runtime.
5.2.4
60
1MRS757306 B
5.3
GUID-D8D20AEC-3B57-4094-9D1B-657F7EE83997 V1 EN
Figure 40:
A binary input channel can be connected to one or several function block inputs.
61
1MRS757306 B
A binary output channel can only be activated from one function block output. Connections made with the Signal Matrix tool are automatically also shown in the Application Configuration tool.
GUID-3848DA0B-7F15-4A35-9D0F-6F35FCD80805 V1 EN
GUID-86387094-8AF6-4376-B183-416DE0B35A31 V1 EN
Figure 41:
Signal Matrix tool: a connection between binary input channels to binary input signals
Depending on the IED capability, the Signal Matrix tool has a separate sheet for each possible combination. The possible sheets are: Binary inputs Binary outputs GOOSE
62
1MRS757306 B
Section 6
LHMI engineering
For information on LED operation modes supported by 615 series, see technical manual.
6.1
6.1.1
63
1MRS757306 B
GUID-165E4FDC-7342-4A39-9E63-58BA77AF1E99 V1 EN
Figure 42:
The Graphical Display Editor has a fixed symbol library window on the left side of the view. The presentation is empty when no page exists for the IED. A default singleline diagram presentation is displayed if standard configurations are used.
6.1.1.1
6.1.1.2
Symbol library
The Symbol Library view contains panes that include drawing symbols or elements for creating a single-line diagram, measurements and texts onto a page. Panes can be opened by clicking the name bar of the selected element.
64
1MRS757306 B
The library shows the symbols either in the ANSI standard or IEC standard. The standard is selected from the list located on top of the window. When changing to another library standard, Graphical Display Editor changes the symbols according to the selected new standard and redraws the single-line diagram in the window. To change the symbol format used in the IED, select Main menu/ Configuration/HMI/SLD symbol format and choose IEC or ANSI.
To become familiar with the available symbols, select the different panes and their symbols.
6.1.1.3
Isolator Bad (faulty) position Isolator motor operated Intermediate position Isolator motor operated Open position Isolator motor operated Closed position Isolator motor operated Bad (faulty) position Circuit breaker Intermediate position
Table continues on next page Breaker Integrated Protection RBX615 Engineering Manual 65
1MRS757306 B
ANSI representation
Current transformer
Voltage transformer
Star Point
Capacitor
Surge arrestor
Reactor Motor
66
1MRS757306 B
Coil
Fuse
Resistor
Fieldwinding
Rectifier
Earthing transformer
6.1.1.4
6.1.1.5
Text handling
The raster switches when text is selected in a raster of 9 x 14 (columns x rows). A text element must be placed in the position of the raster. The name and the unit of a measurement or text symbol can be changed by double-clicking the symbol or via the Object Properties view.
67
1MRS757306 B
GUID-865B99B4-378B-406E-8AEF-D379F7CA6ACA V1 EN
Figure 43:
2.
Edit the text in the Name field in the Object Properties view, or alternatively double-click the text to edit it.
6.1.1.7
Adding a measurand
1. Place a Measurand object into a raster box by dragging-and-dropping.
GUID-3C8B2B22-705B-46EE-8F95-7666CA8296B4 V1 EN
Figure 44:
2.
In the Objects Properties view, edit the name, unit and the number of decimals. Unit text specifies the default text used for the measurement's unit. If Unit text is not empty, the unit in the IED is updated dynamically and the unit from the Graphical Display Editor is used by default. If the Unit text is empty in the Graphical Display Editor, no unit is shown. The Scale factor parameter is not used.
68
1MRS757306 B
6.1.1.8
GUID-706B5CBE-21D8-4129-8428-9361D51FFCD5 V1 EN
Figure 45:
Graphical Display Editor: adding single-line diagram symbols into display page
6.1.1.9
69
1MRS757306 B
GUID-0F2660C5-2AF0-4FFD-8D74-C228885657F3 V1 EN
Figure 46:
5. 6.
Draw all line elements that are necessary. To finish the line drawing, click Select on the menu bar.
6.1.2
6.1.2.1
70
1MRS757306 B
6. 7. 8. 9.
Place measurements when needed. Edit the name, unit and the number of the measurements' decimals. Select each object that has a dynamic link and make the link to the corresponding process object. Check that you have selected the correct function block. Function blocks of the same type can have different instance numbers.
GUID-A066255E-E058-42AA-A6D4-5498C46FCE58 V1 EN
Figure 47:
Ensure that all links are done. Save the complete picture. Write to the IED. Validate the single-line diagram on the IED.
6.1.2.2
71
1MRS757306 B
Application Configuration tool for programming the application function block for the apparatus and/or measurements Parameter Setting tool for adapting the settings and/or configuration parameters of the application function block Graphical Display Editor for establishing the link to update the selected data attribute in the HMI of the application function block
The following application function blocks are used to deliver the needed information: Switch controller (of type CSWI) for an apparatus All configured function blocks with measurements (of type MMXU) for the measurements
1. 2. 3. 4.
Right-click the apparatus symbol and select Select Input Signal. A list of engineered switch control application function blocks opens. Select the switch control application function block that corresponds to the selected apparatus. Right-click the measurement symbol and select Select Input Signal. A list of the engineered measurement application function blocks opens. Select the measurement application function block that corresponds to the selected symbol.
72
1MRS757306 B
GUID-20060033-738D-4807-9D6A-14347B1EBE02 V1 EN
Figure 48:
The ordering number in the selection window of the process objects corresponds to the number given in the Parameter Setting tool tree and to the application function block in the Application Configuration tool. Only the apparatus and measurements that are configured in the application configuration program are displayed.
73
1MRS757306 B
GUID-9157BA8E-8804-41D8-9F4C-EA2A7CB1A42B V1 EN
GUID-1B944E54-11FE-4788-BCE7-936A97E0D73C V1 EN
Figure 49:
74
1MRS757306 B
Section 7
7.1
7.2
75
Section 7 IEC 61850 communication engineering 7.2.1 IEC 61850 interface in the IED
GOOSE interf.
FBs FBs GOOSE GOOSE Receive Receive
1MRS757306 B
LN part
Commands
FB AFL
LN part
FB AFL LN part
IEC08000364.vsd
IEC08000364 V1 EN
Figure 50:
IEC 61850 has as a concept for the identification of all signals for communication that belongs to a function by a logical node as a place holder. All signal information in the command and monitoring direction, that belongs to a function, is available within the logical node. Whenever a function block is instantiated in the Application Configuration tool, PCM600 automatically generates the corresponding logical node data. In the figure above this is shown by two parts per function block. The upper part is the visible function block in the Application Configuration tool and the lower part is the logical node data for the function block.
7.2.1.1
76
FB AFL
1MRS757306 B
Receive
Receive
Receive
Receive
Receive
LN LN LN LN LN
Data-set
LN LN LN
Data-set
LN LN LN LN
Data-set
LN LN LN
IED 1
IEC05000830 V1 EN
IED 2
IED 3
en05000830.vsd
Figure 51:
IEC 61850: horizontal communication principle, an example of three IEDs where each IED communicate with all others
When a GOOSE message is to be sent, it is defined by configuring the data set with the defined trigger option and GoCB. This engineering process is done in a station configuration tool, for example, CCT600. The task involves configuring lists with the signal, value and quality (data attributes) that belong to the GOOSE message data set. In the opposite direction, the standard only defines the IED as a receiver of a GOOSE message. How the GOOSE input signals are handled must be defined in the IED application configuration. The SCD file generated by CCT600 (or any other station configuration tool) contains the GOOSE data sets as input data. The input data must be connected to the function block inputs in the Signal Matrix tool.
7.2.2
7.2.3
Receive
Send
Send
Send
1MRS757306 B
Capability description of the IED in logical nodes and their data. No information about, for example, the communication configuration is included. An IED is already extended by default data sets and report control blocks. They are predefined by ABB. Changes or additional data sets, for example, have to be done with CCT600. A complete configuration description of all IEDs in a station and the full engineering of process signals and communication structure is included. This includes all the needed data sets and control blocks. The CID file contains the information needed for configuring one specific IED. The CID file contains the complete configuration description of one specific IED. This includes the configured IED name, communication part, data sets and all control blocks.
The uploading of IEC 61850 communication configuration is not supported when reading a configuration from an online IED.
7.3
When exporting a SCL file from PCM600, the tool builds a default substation structure and creates default data sets and control blocks for vertical communication between the substation client and IEDs. For more information, see the IEC 61850 standards. In the following example, it is assumed that PCM600 and CCT600 are used as the system configuration tools.
78
1MRS757306 B
1. 2. 3.
SCL files are exported from PCM600. In this case, a SCD file. It is also possible to export other SCL file types. Horizontal and vertical communication is configured using the station configuration tool, for example, CCT600. SCL files are imported to a PCM600 project. In this case, it is the updated SCD file.
CCT600 (2) create project import SCD file configure data sets configure Report CBs configure GOOSE CBs export SCD file
SCD file
SCD file
PCM600 (3) import SCD file link GOOSE input data Write to IED
IED 1
IED 2
IED n-1
IED n
IEC08000413.vsd
IEC08000413 V1 EN
Figure 52:
IEC 61850: signal engineering procedure flow when a complete station is exported as a SCD file
7.3.1
7.3.1.1
79
1MRS757306 B
GUID-07274DBE-81C6-47C4-A9E7-A268C1813A74 V1 EN
Figure 53:
2. 3. 4.
Right-click the station and select Export. From the open standard Windows dialog box, select the location to store the file and name it. Click Save. The SCL Export Options dialog box opens.
GUID-501CC322-0643-41DE-8A7D-E2F1EFACAA6F V1 EN
Figure 54:
5.
Click OK to export the project to the SCD file. A progress window shows the ongoing export of the station.
80
1MRS757306 B
7.3.1.2
GUID-B48B9B77-2399-4B43-B8B0-CD91EEA6EAC2 V1 EN
Figure 55:
4. 5.
Click Save. The SCL Export Options dialog box opens. Select the exportation method. Export Private Sections Export As SCL Template Include Goose Sending IEDs
81
1MRS757306 B
GUID-86EAC57A-A639-49D6-ABB0-08012B19B9B8 V1 EN
Figure 56:
6.
Click Export.
7.3.2
GUID-BDE141C0-124E-4565-AB1B-927CEA1114A5 V1 EN
Figure 57:
3.
82
1MRS757306 B
GUID-BBF30767-A389-4EC8-AD28-83D68121F1E2 V1 EN
Figure 58:
3.2. Configure and/or re-configure the default data sets. Reporting data sets can only contain data intended to be used by clients, for example, for event handling.
The data set for GOOSE may contain signals on data attribute level. 3.3. Configure additional Report Control Blocks when needed for each data set used for vertical communication. Up to five report clients can be configured.
3.4. Link the IED clients to the Report Control Blocks. 4. Conduct horizontal communication engineering. 4.1. Configure GOOSE control blocks for each data set configured for GOOSE messages. One data must be included only once in the GOOSE data set. 4.2. Define the client IEDs for each GOOSE control block. 4.3. Link the IEDs to the GOOSE control block that is to receive the GOOSE control block. 5. 6. Update the data flow. Export the updated SCD file.
83
1MRS757306 B
All data sets, Report Control Blocks and GOOSE control blocks must be located in LLN0.
7.3.3
7.3.3.1
GUID-212ABAE9-A822-4CD0-BC82-9EDCDD2D268F V1 EN
Figure 59:
4.
In the SCL Import Options dialog box, select how to handle the file during the import.
84
1MRS757306 B
5. 6.
Click Don't import IEDs of unknown type to protect the existing IEDs in case the SCD file does not match the original configuration in PCM600. Click Replace unknown if it is known that the file includes additional IEDs that are needed. The IED of type Generic IEC 61850 IED is used to integrate these kinds of IEDs into the plant structure, for example. Click Ignore PCM Object Type to update the IED object(s) in PCM600 from the IED type(s) in the SCD file, whether or not the IED type(s) in the SCD file matches the IED object(s) in PM600. Click Ignore Substation Section to not import the SSD file part of the SCD file.
7.
Click Import when the file definition has been completed. A progress view displays the importing procedure. Make connections from the sending IEDs to the receiving function blocks with the Signal Matrix tool. Make connections between the signals that the server is sending and the function blocks on the receiver's side. Write the configuration to the IED. In the Plant Structure view, select the IED, right-click and select Write to IED.
85
1MRS757306 B
GUID-4C60D783-8EE5-4186-8A0E-7923E7E3D465 V1 EN
Figure 60:
The engineered data is written to the IED when executing a common Write to IED operation.
7.3.3.2
86
1MRS757306 B
3.
The SCL Import Option dialog box opens. In the SCL Import Option dialog box, select how the file is to be handled during the import.
GUID-9455B65D-993A-492E-A26B-B652842C0538 V1 EN
Figure 61:
4.
Don't import protects the existing IEDs in case the SCD file does not match the original configuration in PCM600. Replace unknown can be used when it is known that the file includes additional IEDs that are needed. The IED of type Generic IEC 61850 IED is used to integrate these kinds of IEDs into, for example, the plant structure. Ignore PCM Object Type updates the IED object(s) in PCM600 from the IED type(s) in the SCD file, discarding whether or not the IED type(s) in the SCD file matches the IED object(s) in PM600. Ignore Substation Section does not import the SSD file part of the SCD file.
Click Import when the definition has been completed. A progress view displays the importing procedure.
87
88
1MRS757306 B
Section 8 Glossary
Section 8
Glossary
615 series
Series of numerical IEDs for low-end protection and supervision applications of utility substations, and industrial switchgear and equipment Application Configuration tool in PCM600; Trip status American National Standards Institute Communication Configuration tool in PCM600 Configured IED description Communication Management tool in PCM600
COMTRADE Common format for transient data exchange for power systems. Defined by the IEEE Standard. CT DU EMC Ethernet FTP GDE GoCB GOOSE HMI HW I/O ICD IEC IEC 61850 IED Instance Current transformer Docking unit Electromagnetic compatibility A standard for connecting a family of frame-based computer networking technologies into a LAN File transfer protocol Graphical Display Editor in PCM600 GOOSE control block Generic Object-Oriented Substation Event Human-machine interface Hardware Input/output IED capability description International Electrotechnical Commission International standard for substation communication and modeling Intelligent electronic device Identical protection function blocks available in a standard configuration. By setting the application-specific parameters of an instance, a protection function stage can be established. A set of four numbers between 0 and 255, separated by periods. Each server connected to the Internet is assigned a
89
IP address
Section 8 Glossary
1MRS757306 B
unique IP address that specifies the location for the TCP/IP protocol. LAN LED LHMI MV NCC PCM600 PST RJ-45 SCD SCL SMT TCP UDP VT WAN WHMI Local area network Light-emitting diode Local human-machine interface Medium voltage Network control center Protection and Control IED Manager Parameter Setting tool in PCM600 Galvanic connector type Substation configuration description XML-based substation description configuration language defined by IEC 61850 Signal Matrix tool in PCM600 Transmission Control Protocol User datagram protocol Voltage transformer Wide area network Web human-machine interface