TTC-1000 Transformer Temperature Controller

DESCRIPTION The Transformer Temperature Controller (TTC) is a full feature single or dual temperature measurement and control device for the management of transformer cooling and Load Tap Changer (LTC) conditioning monitoring applications. A significant advantage of the TTC is it does not require calibration. calibration Because the accuracy is guaranteed over the entire temperature range, the temperature probes are interchangeable and can be installed up to 250 feet from the controller. There are no maintenance items such as potentiometers or batteries. Just set it and go. The TTC has four programmable output relays with Trip Duty rated form C contacts. The built-in programmable scheme logic provides the ability to: Control Fans and Pumps Provide high temperature alarms Generate Trip signals Provide LTC Condition Alarm Periodic exercising of fan banks

The TTC also includes an RS-232 communications interface for settings and status that uses the terminal emulation software installed on your PC and does not require special software. Setting files can be either uploaded or downloaded. There are many additional features available including analog outputs and time stamped min/ max temperature display all with a Life Time Warranty at an affordable price and now with DNP3.0 communications . Advanced Power Technologies

FEATURES The TTC-1000 is an advanced microprocessor based transformer temperature controller that contains a full compliment of programmable features:

Dual universal temperature probes measure temperature from 0 to 160 C, Without Calibratio n. Contains no maintenance items and does not require calibration. Four independent temperature set points per temperature probe with settable pickup and drop out temperatures for hysteresis. Built-in LTC condition monitoring. Mag mount probe available. AUX CT input for winding hot spot temperature measurement based on top oil temperature. Clip on CT provided. Dual load pickup set points for transformer pre-cooling. Built-in fan bank alternate feature. Three independent time set points for daily fan exercising. Programmable scheme logic with four programmable form C relay outputs. Dedicated form B Device Alarm Relay with built in self check. Minimum and maximum temperature display time stamped with date and time. DNP3.0 Level 1 Communications, read all binary and analog outputs and command cooling remotely (optional). Dual analog outputs programmable to 0 to 1 or 4 to 20 mA (optional). Dual optically isolated inputs for remote cooling control or reporting liquid level or sudden pressure alarms through DNP3.0 (optional). Operates over a wide voltage range of 38 to 160 VDC or 120 VAC. Mounting available in a NEMA 4X enclosure, heater option available. Substation hardened to ANSI Fast Transient and Surge Withstand of C37.90.1 and RFI/EMI requirements of C37.90.2. Lifetime Warranty

CTS

RTS

N/C

N/C

DB-9, RS-232 TTC-1000-XXX


TB4

N/C

CONNECTION DIAGRAM

GROUND

Rx

Tx

2-Wire RS-485 1 DNP 3.0 2 Interface


COM TMP REF TMP REF

DO/ RI DO/ RI

TB3
12 11 10 9 8 7 6 5 4 3 2 1

COM

TB1 TB2
6 5 4 3 2 1 4 3 2 1

12

11

10

COM

COM

COM

COM

Analog Output, A2 (optional)

Analog Output, A1 (optional)

COM

NO

NO

NO

NO

NC

NC

NC

NC

NC

CHASSIS GROUND

OUT4

OUT3

OUT2

OUT1

WHT RED

BLK

ALARM

Aux CT Input (010A) Power In


38 to 160VDC or 120VAC

WHT

RED BLK

Probe #2 (optional)
Temperature Probe TTC-PROBE-01-XXX

MOUNTNG
Probe #1

Temperature Probe TTC-PROBE-01-XXX

7.00

5.00

Oblong 0.312 X 0.500

12.75

Lexan Window

Liquid-Tight Cable Strain Reliefs


3.312

1/2 - NPT Cable Fitting Ground Stud 1/4-20x1/2


1.500

3/4 - NPT Cable Fittings

0.000 0.000 1.750 3.500 5.25

SPECIFICATIONS
Power Supply Input Ope ra ting Range : 38 VDC to 160 VDC or 120 VAC +/- 10%, 3 Watts Max. O pe r a ting Te mpe r a tur e Ra nge : -35 C to +85 C, 95% Relative Humidity (non condensing) Te mpe r a tur e M e a s ur e me nt Ra nge : 0 C to +160 C LTC Diffe r e ntia l M e a s ur e me nt Ra nge : -20 to +20 C Te mper a tur e M ea s ur e me nt Accur a cy: Avg error over entire measurement range 1 C. Absolute error at any temperature 1.5 C. O utput Conta ct Ra ting: 30 amps make for 250 msec, 10 amps continuous at 250VAC. O ptica lly Isolate d Inputs : Operates from 38 to 160VDC. External wetting voltage required. Ala r m Conta ct Ra ting: 0.15 amp continuous at 160VDC Ana log O utput: Selectable, 0 to 1 mA or 4 to 20 mA. Maximum load 9,500 ohms (0 to 1mA), 450 ohm (4 to 20 mA). Communica tions Inte r fa ce s : Front Panel Mounted RS-232 DB-9 Null Modem Interface SCADA Inte r fa ce : DNP3.0 Level 1 Protocol using half duplex RS-485 interface. AUX CT Input: 0 to 10A Pa ne l M ount V e r s ion Dime ns ions : 5.32 W x 2.61 H x 6 D N EM A 4 Enclos ur e V e r s ion Dime ns ions : 10 H x 6 W x 3 D Sur ge Withsta nd/F as t Tr a nsie nt: Relay outputs and station battery inputs: ANSI C37.90.1 EM I Withs ta nd: ANSI C37.90.2 Die le ctr ic Withs ta nd: 3000 VDC for 10 seconds
TTC1000w x y z 4 form C 1 6 form C 2 4 form C 3 6 form C 0 2 3 5 1 2 3 4 Outputs, Outputs, Outputs, Outputs, No inputs No inputs 2 inputs 2 inputs

ORDERING INFORMATION

Panel Mounting 0 NEMA 4X Enclosure 3 NEMA 4X w/Heater 4

No telemetry outputs Single analog output Dual analog output RS485w/Dnp3 Level 1

Single Probe Dual Probe AUX CT, Single Probe AUX CT, Dual Probe
1 2

TTC-

PROBE-

-zzz

Universal Thermowell Probe Magnetic Surface Mount Probe

Probe lead length, 10 to 250 ft

Advanced Power Technologies

Advanced Power Technologies, LLC 240 Dr. MLK Jr. Blvd Newark, NJ 07102 Phone: (973) 621-6600 Fax: (973) 621-6625 web: www.advpowertech.com