Beruflich Dokumente
Kultur Dokumente
BCS
"'
Model SLBC
nsta I lat
ion
3-
3. INSTALLATIOI{.
For general information regarding installation of
manual
3-1
iring.
The terminal board is located on the rear of the controller housing. Remove the cover of the terminal board., and connect external signal wires to the (lvt+ size) screw terminals. After wiring, be sure to
replace the cover. (See Figures 3- l - l and 3- l -2.)
'J
-\ ,,'
Tables 3- l - l and 3- 1-2 show the terminal designations and signals to be connected for the -200.4 and -300*A versions of the controller respectiveli'. Figure 3-l-1. Terminal La1rout.
I Terntinal Wiring
Terminal
lJesrgnatton
i
I
Table 3-1-f
DescriPtion
SLBC-200*
Terminal
B.
Designatiort
\ i\*.-
t L I
\ ./
-
(Note
1)
\compensatron _/ 1 to 5 V DC
input
7 B
10
|+ i -S
+
tto*-i"tpur-lroSVDC
Master pacing inPut
(-
terminal)
---->
l1
12 13 14
15
Hl
M N
output (+ terminal)
16
: L
K
I. | --I
l*.-
(See Sections 5'1'2 and 5-3-21' Note 1: Change wire conneclion according to the type of transmitier used' Type 3-wire 2-wire TyPe Contact or Voltage Termtnal Power Supply" Power SuPPIY' ' Voltage level pulse: external disLevel Pulse' Designation
1
2 3
:>Transmitter
Sig...
tributor.
Transmitter
\ tr"nsmitter +r/
"
,{
s:.
tM 18483-01E
r.
}f
.:
3-2
nstallation
Model SLBC
Description
Terminal Designation
17
Description
2 3
18
19
:>
Communications {Note 2)
pulse flow signal input
4
tr
Bl
input
20
21
sJ
10 11
8J
tJ
:JRrD
+\
Process variable input, or auxiliary
Fail output
(-
terminal)
AJ BJ
c
D
F H J
Manipulated output, 4 to 20 mA DC
J J
12J
13
14 15 16
J
+
+
output (+ terminal)
L
M
terminall
-l
Vcc
Q)
Each status and voltage input must be as per SLBC specifications. Note the limits on conduc-
t,*
q ( q l d cl c{
tor resistance, voltage drop in conductors, and voltage (high/low) levels. (Refer to the SLBC General Specification at the back of ' this
manual.)
-i
(3) The fail and digital outputs are transistor contact signals (isolated from power suppli'and other internal circuitry). When connecting external devices, pay attention to the following: (See
Figure 3-l-3.) O Observe correct polarity of status output ter-:./
Vcc
IL_\Ai/a
d o( d cl cl
o(
minals.
Vcc
\lS"'--
nega-
L*
l
d
ot
O When connecting a relay or other such inductive device, connect a surge absorber
c (
cl ca
N egaUve
(protective diode Figure 3- 1-3., CR circuit,, etc.) in parallel with the load. Note that status outputs cannot be connected
directly to an AC circuit. Use a relay to switch an AC circuit. o Do not connect any load which exceeds the contact rating. (Max. 30V DC' 200 mA). (4) Use shielded twisted-pair SCCD cable for communication lines (tern.Y 's 17., l8).
elay
AC load
circuilj
AC power supply
*:,
rM 184E3-O1E
Aug. 1984
r-.
Model SLBC
Principles of
OPeration 4-l
4. PRII{CIPLES OF OPERATION.
This chapter outlines some major features of the SLBC Batch Controller that are used daily in operating, the system. For further details, read TI l84A30l E "YewSeries System"
BCS Batch-Blending
Control
.--:'
Totahrer Functrons Eatch Flow Totahrer Curnulattve {wrth aclded/ sublracted tlow signall
Pulsc rnput
lr
Kf
Flow TotSlrzer
rl
rl
process vanable
1
r;o? r* Ir"*
il
Kt
<
Adocd
Torahzer
Batch Flow
'\*
Totahzer
ffi
ilow span
aata
xq
Flow P19"-*:
vanaol
Total-
*t;":::.'
tpin-
h or mtn
(putse srgnall
Flepeiter *t
KJ
Alarm Outgut
Srgnal
<
Repealer Pulse
Addedi .t Torat- Rcpaater t::t11"1'' r pursc ed tlow -',1!,1 SCalC soan .tacror Kfactor
ho
h or mrn
rnrn
(for loss of flow pulse srgnal, laakego {low} Flow Srgnal @ Repeatcr rrr (1 | io 5V!
Tr
Ftow
l)
r flow Proct3s
vanlble
K factor lor
@ co*-unrcattons
Tz
Added,' Totahrcr X factor tor subtrrctcdrscaleraddcd;sub' factor tractcd lloYv llow si'an
Pcnod ol rnput Pulcs
Cornpensatton computatlon
Start Stop
Reset
M . i(4to20mAl
@ ral
{
Signat
Master Pacrng (o
Reset Signal
added/subtracted flow signal, 8nd compensation computation. output e.g. demand )..' The Epan of Pulse i to 5 V analog Output (and the input to Pl algorithm,-disolay and repeiter) ars also adiustable when au-*iliary iadCed/subtracted) f low input is used. .r. Main data (see Ssction 5-1-1 ).
'With
r'
i:g$r<
4-], Totalizer
Functions.
addirion/subtraction
compensation.
of auxiliary input
and
Totalizers are essential in Batch-Blending Conrrol. The SLBC permits the tollowing five totalizetJ values to be displayed- (See Figure 4- l- l-)
(
added/
t)
-plo-.
,Cumulative totalieer value for uncompensated flow process variable after addition/
subtraction of auxiliary input.
-'-
tion
(5) Cumuiative flow totalizer value (with added/ 'Subtracfed flou' signal alld compensation compu rario n )
(3) Barctr flow rotaiizer value (with acjded/ subtracted flow signal ald compensation computation)
variable signal-
Cumulatiye totalizer value for flow process variable after addition/subtraction of flow signal tnd compensation computation.
,,5
s:"
r'*
/
4-2
\
Principles of OPeration
Model SLBC
41. Alarm
detection
leakage
Func-tions.
totalizer values are 6-digits [ong, and Lh"g*q-U:Xtgl.*!Xg* and 119*,d1;preye=* ;ffiIff; of the display. urpper and.,lgy_qf:ections the using "l *b -Th . ;-"itu * n ffi;- ffi"*iln"ilx, r
;'tffi-T,ffiffi
.
Alarm functions that are peculiar to SLBC are of missing pulse input and detection of
-"mg*,
totalizer value (with added/subtracted flow signal iiiput, and compensation computation) is used as main data for batch processing, and is displayed as 'the SUM on "-front panel. The other four totalizer
, r:.
_. i , i, ,B}}&ej-^"*
Figure 4-1-l shows the relationship between the alarm functions and batch sequence. (l) Detection of loss of pulse input. If between the time flow should have reached high limit setting and pre-batch'end the process variable flow input signal level remains below O.7 \Vo of span, the input signal is considered to be missing: the ALM lamp lights and
velfr
ffi*a;ET?64tffi as
au
xil
iarf data.
(2)
tion)".
'
\-
4-3' {lqLQPntrPl
fun
'
the alarm output contact opens. Detection of leakage. The leakage during the period between batch end and resetting is rneasured. If the leakage equals or exceeds a preset value (auxiliary data setting)., the ALM lamp lights and the alarm output contact opens.
This controller performs Pl control so that the flow with added/subtracted auxiliary signal and after gompensation agrees with the flowt set value
indieb-ieaTi*ffih;i,m%*ai_qpilr*ro"*i+iq*r:*:sna:<';":;';';"!!''*i'{s
"Reset" resets the detected leakage value, but leakage detection continues until "Starl". ,
programmed by the batch sequence. The PI constants necessary for control are set and
lntegral time
(l): I to 9999
sec.
Start
transfer
T ime
Figure 4-4-1.
'.\."."'
1i.
:!-
*:.
tM 184E3-O1E
october 1982
/'#
Model SLBC
peration 5-
5. OPERATION.
5-1. Front- and Side-Penel Features.
5-1-1. f:gnJ*fsnnl.
Batch Controller.
Srll-dlegnortrc .l.rm bmpt
Frequently-used
items
such as set value fiA pril;;; variable value shorvn in the main data list on the front panel),
such
as
computational constants and control constants shown on the side panel data label) are displal'ed on this data display according to the sel-
selector
Nrm@lrtr
(Trg teottl LOAD PFE EIIO
ALII
FAIL.
s?op
con+- Soourrrct troi mrtcho , lnrttntrnoorrt+tlorrv
,q F-.r t=t F- ef
cllrphy
I
drtr lcmpr
Srlcctrrl-
l-
I
_1
Ef _tJ ;7't
AATCH
,? n Lt U
OATA
I I
:,
-t lt
c J 6
?rtr.rrtttne +. - rwrtcn6
r
drtr llrt+l
Mrin
switch (FRONT P./SIDE P.) located on the side pane!. (See itern (6) of 5-l-2.) t g,ljo..$ ., . $_sf ?Ul tl e . p.tgin a ly_"* t{l,,," s e l e q l 9 r (q*il with this setdata).* P, lWjJSh".I-e-*-t$O,NT, ting, th:.jlper s::li".',.1. the disrff,f. :.oltaig J the batch set value, and'"Tnelower iection of the di5play coniains one of the main data items as selected by the data display seiector swilches ifl . A selected-data lamp lights to indicHffi lVl ffi "fvhich data item is selected. (See Figure 5- l -2.) r *r' I"*e' ,E- ffio display auxiliary data items, st the FRONT \ P./SIDE P. lelecror switch tolJp!*P,t(auxiliary ffi+ ff; ;;;ion or the
.._o_p_g ,"..".1
'
.lrDrrr dtrol.Y rr' lactor fl rutcnaa for corf" licbntr tnd rnginoring untrr +Control moda r.Specr
_9jXH_J9
--i6d
lactor rwitchcr
oiti
The
o G"p"l
.4.ttg.
The desired item can be selected using the (See cisplay selector switches nE
lory_gl_ da-ta -d"isplay,
un
rtrrI
r rt r I I t l l lt t t t
swE
Mrnurl lrvlr control
Figure.
(I
5-l-1. Front
Panel.
ISETI ,
[m}J
.,
Q)
Sequence status lamps (LOAD, PRE' END). D5n i 4i !h 9- .,t ! g.lll,'E. "9 {,Jh e, ba 9 h' 9' 9 q, ts n r;.c . Self-diagnostic alarm lamps. FAIL lamp (red): Lights if the controller lails.
1
status.
t}"y*
jq
p"
ggltg} )'
L igh
ls,
lg_*1*n9i*-q,*[g*.alarm
!
o a
a !
This lamp flashes il' the data memory backup battery is not installed. or when its voltage is
low.
(3
I i- f :' :,
FFIONT
f :l
EArcH
t-,-t -'i u
rJ
t-t
1rI I
/; i i
Mlrn detr S.l*t.ddttt
55
lrtnot
la-SIDE
P
pgy*ej.t3.p-"S"ggtto
These switches are used to sj**. r*--e_,set an-d stop the batch sequence. The batch sequence can be
t :*
i-t-c.Ig s .
controlled
inputs.
by these switches or by
contact
(4)
(5
Instantaneous-florv disPlaYT.f
O SUU (Bttcn totrlkrr vrlur) O BATCH (8rtcn lordrr rtttng| O FLOW LlMlT (Flow high limit) O FLOW (lnttrntrnrour flow) Oltr dlplrv rl'qlor Mran dltr tvltchor
ffir
Ev
Aurilirry clrte
gliPh consisting
by
Figure 5-l-2. Functions of Data Display. (Main data display shown.)
Data
disPlaY'
The data disphy is divided into t\r'o sections. upper and lower, each of which displays six
digits.
*:"
lM
B4E 3.31
.r"
gE.
"
,ts
f,,
;&
!r*'
i i:
5-2
Operation
Model SLBC
(10)Space units.
(l I ) C/ AlM control mode selector switches. These switches select the control mode. The
lamp inside the selected mode switch lights. C mode: Automatic mode (batch control). The #}Y*l:" system may be monitored and settings may be changed from a supervisorY computer. Automatic mode (batch control). A I....''.,.;, qt+:i- s,p.dg; M''ilode: Manual mode. The control output sigb;:.::..'',' , '"' nal can be increased or decreased by the manual control lever. ( l2) Manipulated variable output indicator. Indicates the current output signal. Left end 4 mA DC; right end 20 mA DC'
(
O SUU (grtch totdtz.t vrlurl O AATCH (Brtctr lod.t rtllng) O FLOw LlttiltT-(Flow high llrnit) O FLOw ( lnit ntrne(xrr flow) Ortr dlrplly rl.ctor Mrln dtt nithaa
AurilbrY drtr
\
(E!'fl).
l3)
Used for adjusting the control output signai ol the controller in manual (M) mode.
,cpilrol lever.
Action:
signal output decreases as lever
toward left
.
is'.,
desired display the data using selected be data item can selector switches.
nroved nroved
is
Main data:
SUM
BATCH......
FLOW LIMIT
. . Batch
totalizer value
FLOW
(9)
Selected-data larnPs.
..lnstantaneous flow
sec.
nroyenlent
b-v
ot'
One of these lamps lights to indicate the main data item selected by the data display seiector
switches.
u.l'ii,.
i\
r"
b-.
rM 1 B4E3-O1E
..:.;':ffi
. '''': .
Model SLBC
iT
s
:E
.#. 4::
-F*)
,-*i
Operation 5-3
(l) Transmitter power supply selector
'
'...1
'd 't
.:.]
.t
.!
a:1
{i
5-1-2.
panel.
tm-t*g*:*-SMg*md.,
:.i :lt1
"i1t :i
switch
Figure
5-l'4
shows details
of the SLBC
side
uto;Gryffr
,-"--.----=\-
\'-*t''
above), the load resistance (200 O ,, 5 l0 O or- I k O ) is selected by these switches. One of these switches turns the input filter On or On (3) Control action selector switch (ACTION). This switch is used to select the control action: DIR (Direct action): lf the process variable value is higher than the set value. the output increases. PV (process variable value) -"' MV (control output) increases.
RVS (Reverse action): If the process variable value is hlgher than the set value, the output decreases. PV (process variable value)
.
""'..
MV (control output)
decreases.
(EN ABLE/
This switch is used to enable or inhibit data setting by the front panel switches.
8i*afrl@'qtkswlt4'4gs#
2av oc
-_\
iEll
rlY
lU
:i -,--:
xY*,::
L':?
oc
This switch is usecl for setting the decimal point position o[ the set data. With this switch set to DP, the decimal point can be set using the front panel switches (SHIFT. SET).
switch
(FRONT P./SIDE P.) This switch designates the data to be displayed on the front panel data display as either main data or auxiliary data. FRONT P.: Main dara is disPlayed SIDE P.: Auxiliary data is displayed
&"
tM 184e3-O1'E
.. .:t _i.
[tr'
5--4
Operation
Model SLBC
(7) Data
label.
The data label lists auxiliary data such as K factors and other computational constants, control
constants and function-specifying data. Write data values in the data field. Table 5-1-l shows the data labei.' and Table 5-1-
shows details of the auxiliary data function specification items (item Nos. l7 and l8)' For further details of the data label, refer to TI
B4A3-
auxiliary data, and data label/work sheet writing procedure" and TI lB4A3-0lE "YewSeries BCS Batch-Blending Control System".
Controller
Tag No'
lr'-'-'-'-'-'-':'-" " 'r " r""""""""":""':"':i
(11 (21
|,i:i:i:i,:,:.:i:::i:::::.... ., ,, . l;;:::::::i:::i:::i:::i:::i
19 2A
rprn
uJ i
i
i
(comprrrrrtdl
i':':':':':':':':':':':':':':':':':':':i ol:l:l:l'l:l'l'l:l'i:l:l'l'l'l'l'l'l'l'lr
I
: : ::::::::::::
I.
-i
r
^.t vrri$lr inout L frcror lor rddrtsirbltrclGt -AA aJ K llo- input 24 i Totalizer rcala factor
i i
limit
07) Prebatch -t
sat
value value
i i
t t
08i Prcdictad
i
leakaga
09
I
I
:.:ilfnrrtion
nfrnncl ttme''
i
.t
loc
l
,fii
-l
sec
I
-ua
29
Compensation factor
14 15
eirnt 0
grnitY
o/o
t6 Measured temperature
' *,th
aOdeO/suOtracted
f
"c
tec
E9712EA
low srgnal
Function specification
Operation,mode
Batch
switch
function
0:
1: 2: Provided Providad
Supervisory sVstem backup functton Manuai backu Automatrc backul Manual backu
3:
Automatic backu
C D
Flow signal r@eEter Pulse width 0: DutV cYcle 5O% 1: 2O ms 3: 50 ms 4: lOO mr 2: 33 mr Communicatlons write inhibit switch
0: 1: Enable Fu nction specification ( 2 ) lGmTl_fl KiLl G Time unit of flow 0: '/h 1:'/min H Flow signal/simulation
specrf
O: All
values reset.
Repeater & nondisPlaved totalizer digrts Preserved. 2z Like 1, but least*ignrf icant tota' lizer display digit also preserved. 3: Like 1, but wvo least-srgnrf icant totalizer display digtts also pre'
rerved.
Cocrgrnlat ton cclmoutNtlon provrded lor
1:
ication
Proccr
j laoco/r,ru"
trlctGd
rnPUl
0: 1:
va?rable rnOut i
0: OFF 0: COLD
1:
ON
3: Simulation MV inhibit, DIO enable 4: Simulation MV enable, D/O inhibit 5: Simulation MV enable, D/O enable I
Added/subtracteo flow signal
O:
None
1: 2: 3: 4:
Master pacing
1: 2: 3: 4:
Pt 100a.
analog, subtracted
ASTM method with I to 5 V tem' psrature input. General quadrauc lormula using 1 to 5 V ternperature inPut. General compensation with 1 to 5 V signal.
$:'
tM 184E3-O1b
#$
'.tE ''!
Model SLBC
n Jperation
5-5"
5-7. Preparation of Data LabelBefore using the SLBC controller, the required values of auxiliary data items such as function specifying data. K factors and other computational and control constants must be decided and input, and these values should also be writtbn on the data
label (see note )
.
the
in Figure 5 -3-2.
When preparing the data label, refer to Tl I84A3-I IE "YewSeries BCS Explanation of auxiliary data, and data label/work sheet writing procedure" and Tl I B4A3-01 E "YewSeries BatchBlending Controi System". NOTE order time, the faclI option/DL is specified at or, on the data label tory will write data values o belore shipping the controller.
\"--'
5-3. Preparation for Operation.
Perlorm preparul ion wirh the controller installed in lhe panel. or renrovecl and placed on a work table. (Suppose that the instrument module is in the
housing).
instrument
module. The instrument module is now separated from the housing. (Figure 5-3-3).
p the stopper. lclcuted below the front ol the instrument nrodule. to remove it. W hcn it is druwn out hallway, lhe instrurneRt
Push
u
panel
(Figurc
5-i-i).
Housing
Connector
lnstrument
mod u le
Check to See that the fuse and data memor,v backup battery are installed. If not., refer to Chapter 6 Muintenance" for installation procedure.
5-3-2. Setting Side Panel
Stopper
(I
switch
(TRANSM ITTER PW R SPLY ) For pulse type process variabie input signals (two-wire distributcr type or three-wire distributor type. see Table 3- I - l. note * I ) a distributor in the SLBC unit supplies 12 or 24V DC ;
tM 18483-O1b
5-6
Operation
Model SLBC
s-3-3.
d;i?J
set
before com-
O When gl.Ug a*!wo,rvi1e pulse transmilter with the distribulof in the SLBC unit., the switc! .o.t. responding to.![e desired load rsistance should
be turned ON, When using any other type o-f transmitter. be sure to turn all of the resistance
mencing operation. Batch set value (BATCH ) Flow high rrmir set value (FLOW LIMIT) ( I ) Setting the data. main data/auxiliary Tg1!--gg $-q-Pg-*er'" set the data selecror switch on the side panel togsgl-
ffi;'selecto,
switghes OFF.
Fl LTER
P.(mai'l..--dara)position'setthedata/decimal switch to '-31T,5 then select the dara item to be set ariffiisbluy it on the lower secrion ol the displal'using the data display selecror switches Eg". Next, perform the
lollowing openltions.
,,#
L-'*
Select an appropriate time-constant from zeto (0) to ninety nine (99) seconds and set it into the auxiliary data item 33 "Pulse Input Filter", when the displayed value of instantaneous flow (or analog flow repeater signal) wavers owing to the irregularity of input pulse signal. As for setting operation to instrument, refer to Chapter 5-34 (Setting Auxiliary Data)'
(3) control acrion selector switch (ACTION ). set to the desired control action position. (4) Data setting enable/inhibit switch (EN ABLE/
X-
PARAMETER
ENABLE OP SIDE P
THHH
Figure 5-3-5.
IExanrple
INHIBIT)
value)l
--9-u"$ns
normal(
selector
switch
D. P./
operatron
oescnptron
nor.il.a.! .opera-
switch
isHII'r
INCR
I
f
I.l
i
i set value or an already set ; vaiue rs rndtcateo. lffre most significant drgrt Itnat may be set flashes.
I
ra1tg-n'-
.r
TRANSMITTER
P WR SP LY
2g
PU LSE INP UT
FILTER 2OO Qr
llsHtnr>
llrNCR
.__.,
I
;
I
next step.
I
I I
I
idigrt flashes
data. i Set the desrred
I
c
I
lf::=f
tEit
IUJ
c
OFF ON
5to a I uolo
l__, a
rrnJ
ll
3t
r-rl":
l#
't
I
I
ACTION
DIR
PARAMETER
SIOE
P
ENAELE DP
TXXTAIT
ATA
FRONT
l; l*
i Repeat
580
00
the above settrng operatron to the least srgwhole data thus set
lnificant digrt
I
51000c
5JCC0C
tl
ifn"
I
I
I
flashes
i
I
I
I
indicates flashing
of data
display
rM 184E3-O1
t#
tT*wrModel SLBC
Operation 5*7
[Decimal point position setting examplel
Switch operation
(2) Setting the decimal Point. The batch set value decimal point position is automatically set to coincide with the decimal point position of the cumulatively totalized value of auxiliary data item 04. Similarly., the decimal Doint position of the flow high limit set value is automatically set to coincide with the
process variable flow t9.
A c co rd
@sP*
Display 0owerl
span
-9.i
tmt
lsHrr>l
{Note 1}
fl-Tl
The decimal point of the initial value flashes. When the SHIFT switch is held depressed, the decimal point'position changes digit by digit and the decimal point position flashes. When the decimal Point reaches the desired Position, release the switch. The entire disPlaY flashes.
ng
y,
t h.
-e-
-.
de
qn --need*
not bg-Je.L:uberuselhsg'
the"
rnain dam*
5-3-1,
au xiliary data values with the data on the data must be set to correspond
(Note 2)
n.rn
[.-,
,"ah*-=
con troller has been ordered with data (option /DL), the clata has already been label according to the data label factory set at the
I
th
is
Note 1 : The * mark indicates a flashing decimal point. Note 2: The shaded portion t3 indicates flashing digit-
preparecl by YEW. Before starting operation., be sure to check that each data item has been set correctly (to correspond with the label) .
(2)M -the--main
Tet
setting
NOTE
Auxiliary datit
sho
ld
be 04
set
in the sequence
I 6.
to SI,DE P, (auxiliary data). set the datal(decimal point selector switch to AATA, and set the data setring enable/inhibit switch to el!A!LE. Then select the clata item to be set and display it on the lower display section using the data display selector switches trM . Next set the data. The data is set in the Same way'as for rnain data. Refer to the main data setting example of par.
5-3-3.
thru
0)
t-d
r't clirta selector switch P.. (auxiliary data) panel to SIDE on the side poin t selector rjata/decimal position, set the the data setposition, set then switch to the p.f to ting enable/inhibit switch ENAp,LF,..Using rhe dera rJisplay selector switches trE , select the data whose clecimal point is to be set, and display'it on the lower section of rhe display. Next perlorm the following operations:
PA RA METE
ENABLE DP SIDEP
Tffi H ffi
INHIBIT
D
ATA
FRONT
M'
After completing data setting, set the data setting enable/inhibit switch to IN F{ IBIT so as to
prevent accidental (erroneous) setting.
PA RA METER
* 'ExlBLE
j
i -.*
slDE
Tffiffiffi
INHIB
according
P
IT
ATA
FRONT
Auxiliar,v data that is not being used to the function specification can also be "displayed" and "set". However, the
Settings of such unuscd data iterns does not affect computation and control
Figure 5-3-6.
ii,
"
lM 184E3-O1E \
t
*j# :s
dR:
..;j :.:':.':.1::.-:"r,_i.:f.)l.t:,!b:*il1
5-8
Operation
Model SLBC
5-3-5. Simulation. After setting the main and auxiliary data, check the operation of the batch and cgntrol functions using the simulation function of this controller(Refer to TI I 84A3-01 E.) Set auxiliary data item
3-e). Match the label location with the action (normal or reverse action) of the control valve The labels can be removed using tweezers or
l8 [function specification (2) I H Process variable flow signal/simulation specification to simulation mode., and check the
operation (refer
op-
finger nails. CLOSE (Control valve closing direction). OPEN (Control valve opening direc-
E E
tion
Table 5-3-1.
iu*iii"r,
Item.
ffi
I
2:
MV inhibit, D/O inhibit MV inhibit, DIO enable MV enable, D/O inhibit MV enable, Di O enable
5-4. Operation and Handling5-4-1. Batch Loading (Batch Operation)After Setting nrain clata and auxiliury'dut1. start up the controller as describecl bclow. ll'thc integrll tinre aniJ proportitinail band har c alreudl' bcctl scl (thar is, for daily start up). Steps r2' arrd (-6) ;irc
,,
u n n ecessa ry
Choose suitable coefflcient and engineering units labels from those supplied with the controller, and stick them in the appropriate place on the front panel. (See Figure 5-3-8') If 'A''suitable label is missing, use a blank label and write the necessary coefTicient or units on it'
Spaca f or sticking coeff icienV
u
Figure 5-4-2 shows the batch sequence oper:,ttitln. flow characteristics. status input/output operation
and lamp disPlaY.
Note that the operations required to start punlps and other devices are not described in this nlanuul' e Turn on the power to the instrument'
ilnd set
thc
nits labels
integral time to 9999 sec. Set thc proportional bancl to a sulllciently large value'
ffiffir ffiflv
+
@ lg1!
to enable Set the control mode to tr, or system lromsupervisory control setting and set the control mode to tgj th9 r:se1 tlsnll (front panel R h'SET
The batch totalizer value will be reset. If the stop status input is oN, the instrument is ready to start. Note that the instrument cannot be restarted immediately after normal batch end without first resetting it. An interlock function of this instrument disables the reset signal during
a batch sequence-l
tnrlrrlrltlltllllr
Figure 5-3-8-
rM 184E3-O1E
lff
'
,'.,r:'TtFES
Model SLBC
Turn the start signal (front panel START switch or status input) ON. This controller operates automatically according to the batch sequence, and stops automatically when the totalized flow reaches the batch loader set value. Figure 5-4-2 shows the change in the flow during the batch cycle.
@ Set the integral time and proportional band according to the procedure described in 54-3 @
"Automatic control". To stop operation in the middle of a batch cycle, press the front panel stop switch, or t#:*_.Jn_g_* stgp tjalus TP$*9FF. The flow ramps down to the flow low limit in a preset time, and then
goes to zero
LOAO PRE E}IO
.
o'aooo
START
ALll
FAIL
mmm
NESE?
STOP
@ To resume operation after stopping in lhe middle of a batch cycle, turn ON the start signal
without resettirrg.The remaining quantity
is
then loaded, so that the totalized flow coincides -with the batch loader set value. To restart the batch cycle, begin with step (4) above.
Total
b
Figure 5-4-1.
itrr r.trt
rtop
Emrrgoncy
Flrrtrrt
Mrrto
trecing
Brtch
cnd
rc3at
Totrlirrr
Stert
Power
supply
ON OFF
switch or con-
(front panel
Reset signal
ON
OF F
(front panel
StoP
ON
(front panel
signal
Orv
OFF
switch)
Stop signal
{status
input}
ON OFF ON OFF
inbut)
Pre-batch
Clorect Oocn
output
Batch end
L---
output
Reset
output
Clorrd Oorn
F low characteristics of
t\
,,
\l
:etpoint
I
I
rlt r-J
(Noto 2)
L
I
Lamp drrglrv
Note 1: Th SESET and START 3t tu3 inputs ur non-locking contacts which ar "rs3t" or "3tart" in th. ON stlt (minimum ON timo at lcan 4OO mr)' Nota 2: Flsher onlv whon ttop ttrtul input 3i9nrl is OFF.
lr
,i
5-10
Operation
Model SLBC
After setting main data and auxiliary data, start up the controller as described below. If the integral time and proportional band have already been set (that is. for daily start up), steps @ and '@ are
un
necessary.
Figure 54-3 shows the sequence operation, flow characteristics., status input/output operation
and lamp display.
stop status input is ON, the instrument is ready to start. If resetting is unnecessary, skip step @ and go to step @. @ Turn the start signal (front panel START switch or status input) ON. This controller operates automatically according to the sequence. Figure 54-3 shows the change in the flow during the batch cYcle.
@
Note that the operations required to start pumps and other devices are not described in this manual. O Turn on the power to the instrument.
@ Set the control mode to M , and set the ,integral time to 9999 sec. Set the proportional
@ @
band to a sufficiently large ,value to enable Set the control motJe to tr, ot setting and control from a supervisory system set the control mode to E. Turn ON the reset signal (front panel RESET switch or status inPut).
o
@
Set the integral time and proportional band according to the procedure described in 5-4-3 "Automatic control". To stop operation, press the front panel stop switch, or turn the stop status input OFF. T[e flow ramps down to the flow low limit in a
preset time, and then goes to zero.
If
the
Marter
p.clng ON OFF
Power
supply
(front panel
Reret signal
ON OFF
(front panel
oN oFF
(front panel
I
signal
ON
oFF
srvitch
Stop tignal
(status
inPut)
ON
oFF oN
Master pacing
oFF
Pre-batch
output
Batch end
Cloro
Oprn
output
Reret o.utput
Clo..d
Oprn
I
usa non-locking contacts which aro "reset''or ,,staft,, in the ON stata (mrnimum ON time at least 4OO ms).
(
rM 184E3-O1E
JO
?'
Model SLBC
Operation s-tt
The procedure for setting controller integral time and proportional band is explained below. In general. if a small change in the controller output causes a large fluctuation in the process variable value, the width of the proportional band must be increased (the gain must be reduced) to. assure statility. ln the converse case, the proportional band
must be narrowed. For a process'which responds quickly to a change
Set the control mode to M , and tbe integral time to 9999 sgc. Set the proportional band to a sufficiently large value., and then set the control
mode to
value for the proporperform the following operations: tional band, Decrease the value of proportional band from its initial large value in steps (for example, from 100'X, to 50'X, to 2A"1,) - Take a sufficiently long time for each step, so that the state of control can be observed fully. Continue this operation un til the control loop begins cycling. (Cycling
means periodic (cyclic) oscillation of the process variable pointer around the set point, and this phenomenon is caused by setting the proportional band narrower (setting the gain higher)
tr
) Of the C/A/M mode selector switches, select M. (The lamp inside the pushbutton lights.)
(Figure 514). Move the manual control "lever to lefL (or right) to adjust the output signal. (f igure 5-4-5).
?
Q)
Manual control
lever
than the optintunt value for the process. ) ll'cycling occurs, increuse the width of'the proportional band until the nleter indication stabilizes.
(3
Decrease
point. decreasing the integral time improves the speed of response of the controller. but if the integral time is shortened too far. cycling is caused due to dead tinte in the process. In such a case. increase the integral time gradually until
the cycling disappears.
hT; ;T;' c h e cr operation is manual o'p-Jiirion, tpu t returns insthe and ou automatically stopped,
b a rc fi
*iffi
anywhe"r.e-*-Igtwes4l
-a,i
The control ntode of the controller can be changed freelv by depressing the C/A/M pushbutton switches. (Figure 544). (Npje*"hs@kect
balanc-
5-4-6. Resetting Cumulative Totalizer Value. The cumulative totalizer values contained in auxiliary data items 04 and 05 are not reset b"v the reset signal. lf resetting is needed. set this auxiliarl'data to. zero using the data setting srvitches. For the setting procedure., reler to 5-3-4 "setting of auxiliary
data".
,'1
{tr
"
lM 184E3-OlE
"H/
5-12
Operation
Model SLBC
5-5-4. Alarm (ALM) Codes and their Meanings. The alarm codes and their meaning are listed
below,
Code i
0000
ooo
1
Lamp Normal
Meaning
*,,
FAIL
ooo2
ooo4
oooS
5-5-1. Action to be Taken when FAIL Larnp Lights. When the FAIL lamp ligfuts and the FAIL contact output opOns, this indicates that a serious fault has occurred inside the instrument. (l) Monitor the current output signal, and set it to a sale level using the manual control lever.
oo10
oo20
Error in compensation computation Data memory backuP batterY not installed, or low battery voltage
oo40
oo80
0100
0200 o400 0800
Control output open circuit RAM memory data lost Process variable input signal out of range or missing Pulse inPut Added/subtracted input signal out of
range
ALM
Q)
to.Ihe auxiliary data position to indicate the alarm (ALM) contents of auxiiiary data item 0l
on the data display., and check the cause of the
ALM
Flow signal out of range (fcr Pl control input, analog display and flow signal repeater span) after acidition/subtraction
2000
ALlvl ALM
appropriate
Repeater internal data overflow Data setting out of range Power failure
4000
8000
action to correct the fault. If the data display does not function normally, it can be presumed that the microprocessor is not
operating.
ALM
It two or
IExa m plel
5-5-2. Action to be Taken when ALM Lamp Lights. The ALM lamp lights il the high or low limit alarms of the contrOller operate. or when inpr'rt-output signals are disconnected. Display the alarm (ALlvl
contents
ol
auxiiiar-v
data item 0i on the data display, and examine the cause of the fault. (See 5-5-4.) Take appropriate
action corresponding to the cause of the fault.
030C
5-5-3. Action to be Taken when ALI\{ Lamp F'lashes. The ALM lamp begins flashing il the voltage df the data memory backup battery is lorv. Replace the battery with a new one. (See section 6-4 for repiacement procerJtire.)
process
addcd/
during
The diagnostic alarnr codc displal reverts to zero and the ALM lanrp turns ol'l'when the cause of the fautt is removed. except for the lollowing items. Select these items using the data selector switches
E E and reset them using the m keY. (l) Use the m pushbutron switch to erase alarm
. indication tll': ;o Repeater internal data overflorv o Data setting our of range
Q) The flashing of the ALM lamp has precedence over its continuous lighting. lamp is flashing.
Thus,
o Power failure (2) Use data selector switch.s EE,o erase alarm indication ol o RAM mernor!' data lost. (The alarm indication is erased when a new data setting is
t
:.
input.)
C:;.
tM 184E3-O1E
Aus. 1984
:e
Model SLBC
Main*.nrn.. 6-l
6. MAINTENANCE.
This chapter explains the indicator adjustment
and parts replacement procedures.
6-l-l).
Figure
6-2-t
Replacing Nameplate.
ooooo
OBB
6-3. Replacing Fuse. If it seems that the fuse may be faulty, check the inside of the fuse holder lor contaminatiqn or poor ', contact with fuse ( I ) To remove the fuse, unscrew the fuseholder cap (turn it in the direction of the arrow marked on the cap counterclockwise); the cap and fuse
Q,
may then be removed lnstall a new fuse of the correct rating. Tighten the cap llrmly. '
llo
*'
Figure
: Rating :
G9OO
1ZF
1A
5l
)v
IM 184E3-O1E
..1
6-2
Maintenance
Model SLBC
lPrecautions
data
lf the ALM
out delay. NOTE Leave power applied to the instrument while replacing the battery. lf the battery is removed while the power is off' data (parameter) settings may be lost
(2)
in plastic plug-in
package).
(l)
Draw out the controller module a little from the housing, and remove the battery cover and battery. (See Figures 6-4-1 and 6-4-?.)
secu
(4)
use a high impedance voltmeter. Do trot attempt to measure the voltage using a circuit tester or the like. Cautions in handling batteries a Do not charge the batteries. o Do not heat or put into a fire.
poles
FqB
,4
S,.
tM 18483-01E
March 1982
ry '1{
.:1? ..1
I
,'.i
BATCH CONTROLLER
The SLBC Batch Controller co^bines main functions
of
.sBsD Barih ser unit and |LCD Indicating controller. It con be used on irs own in Batch Loader loops, or can be used with'the |LCC Blending controller in high-resolution in-line batch blending systems. The controller functions include:
o scaling, addition or subtraction of flow signals, instantaneous flow display, repeater fo, a !'low o
sig na I.
o Flow program o o
to design into a system, it can cornmunicate with o central operator station or supervisory computer.
STANDARD SPECIFICATIONS
Input/Output Signals
Process Variable. Pulse
::j::
span at
least 0.24 Hz. zero elevation not possible. Make-to-Break Ratio: Between 35Vo and 65% at the 6 kHz maximum input frequency. ON time lv{ake-to-Break Ratio = X lo07o ON time + OFF time
frequency. (See above for definition of make-to-break ratio). Analog ,.Input Signals (Process variable or Auxiliary Flow and Compensation Signals): I to 5 V DC, input
resistance I MQ Analog Input Conversion Accuracy: t0 .2% of span. compensation)
Pulse Specifications: voltage or contact pulse input; two-wire or three-wire transmitter may also be used distributor in SLBC supplies l2Vl24V (switch
\.-
se le cta ble )
Input Filter (e.g. for contact pulse input): Time constant l0 ms. Filter ONIOFF switch. Two-wire Transmitter: Load resistance switch selectable - 200Q.510O or I kQ.
RTD: JIS specification Pt l00Q 3-wire type. Lead Wire Resistance: Up to l0 Qlwire. Ternperature Compensation Accuracy: t0 .2% of span. Output Signals:
Pulse Output Signal (flow signal repeater): Transistor contact signal, rating 30 V DC, 200 mA.
Frequency : 0 to I kHz. S pan at least A .24 Hz whe.n repeater pulse width duty 5A%. Status Output Signals (for signal input abnormal (miss-
Voltage Level Pulse: From two-wire or three-wire transmitter. Distributor voltage + I 2 v DC or +24 Y
DC !10%, current at least 30 mA. Voltage LOW Level (Er-): -l V to +8 V DC. Voltage HIGH Level (EH): +3 V to 24V DC. Amplitude of Pulse Signal (EH - El): At least 3 V. Input Resistance: At least l0 kO. Contact Pulse: Relay/switch contact or transistor switch. Contact ON: Source resistance up to 200 Q. Contact OFF: Source resistance at least 100 kQ. Contact Rating. At least 30 V DC, 30 mA. Auxiliarv Pulse Input Sienal (Added to/Subtracted from Process Variable), and Status Inputs: Voltage (level) or contact signals. Voltage (Level) Input: Voltage LOW Level (Et-): -l V to +l V DC. Voltage HIGH Level (Es): +4.5 V to 25 V DC.
and fail signals * five points): Transistor contact signais, rating 30 V DC, 200 mA Analog Output Signal (flow signal repeater): I to 5 V
Isolation: Both analog and contact (status/pulse) rlo signals are isolated from the power supply. Contacr l/O signals are isolated from internal circuitry. Pulse UO signals are. also isolated from each other. Analog U O, status inputs and status output*," use
separate common negative lines.
9-32, Nakacho 2chome, Musashino-shi, Tokyo, 180 JAPAN Phone: Tokyo 0422-54-1 111 Telex: A2822-327 y EW MT J
t rL
GS 1B4E3.E
4ttr Edition: March 1984(5)
@ Coovright: Jan. 1983(Y)
,t
ts
r*
Input Processing Functions Process variable and' auxiliary flow inputs may be either voltage or pulse signals, compensation input may be either a voltage or RTD signal' Input Cutoff : Analcg flow input signals less than A.787o of span, and pulse flow input signals less than A'24H2, Voltage Flow'signal Processing: Span corresponding to input signal range of 1 to 5 V DC (4-disit fixed point number). Totalizer Scale Factors: Scaler for pulse signal input (constant K number of pulses for every flow unit
are ignored.
Pulse Output: Output pulse rate may be scaled by a factor K'. K' (Kl , Ke ) are S-dieit fixed point numbers, of maximum value 29999. Pulse Output ON Tkne: Selectable one of 20,33, 50
or duty cycle of Savo (for YewSeries BCS Instruments: up to ten may be connected in
or
100
ms
Totalizer Functions
three 6-digit batch Five totalizers are built in totalizers: (cumulative) totalizers and two 8-digit
totalized). Totalizer scaie factor for analog signal input. K (Kr , Kz) are S-rjigit fixed point numbers, of maximum value 29999 Auxiiiary Flow-signal Processing: Auxiliary flow signal can be added to or subtracted from process variable signal. Range of analog output ( to PI algorithm,
-
o o
Batch flow totalizer (process variable only). Batch flow totalizel (process variable, with compensation computation). Batch flow totalizer (process variable, with auxiliary
and
compensation are also possible (see below). Temperature ComPensation : Input signal: Platinum RTD (Pt 100 Q) or I to5VDC. Temperature Range: for platinum RTD (Pr r 00 Q);
compensation computation: can compensate the process variable and auxiliary flow signals for liquid density changes with temperature. other types of
is
bdjustabte'
(process variable, with auxiliary floy signal added to or subtracted from it). Cumulative flow totalizer (process variable, with
and compensation computation)
Cumulative flow totalizer r filEY be reset maqually by entering other data for totalizer value '
Data Display and Data Setting Functions Data Display: upper display is batch loader setting, 6 digits. Lower display is selectable data, 6 digits.
'
general
nsift
Vl\l
+ a)
Vo-Vl,(l+a){l+P(r-re)X
Vg '. Yolumetric
l0-2 +7(
tg : Reference
ASTM.
tenlPerature
("C), tg = l5oC
for
Selectable data (displayed in lower dispiay) may be major data itern or auxiliary data item: Major Data ltem: Displayed data type is indicated by lamp ne xt to data itegr iabei on froni panel' Value of batch flow totalizer ( for process variable with auxiliary flow signal added to or subtractec from
r a
p : First
to
-0.9999 to *0.9999).
to +0.9999).
^l : Second ' p
:
(-0 .9999
+0 .9999),
Specific gravity, (0.5000 to l '2000)' coeffiNote: For density (specific granty ) compensation' to tlow volumetric convert p to used are and cients t
ASTM standard conditions tu = 15"C'
compensation computation), batch loader set value, instantaneous flow high linrit and instan' taneous flow may be disPlaYed' Auxiliary Data ltem: Displayed data type is indicared by code displayed in upper display' Auxiliary data hrcludes the other four totalizer values, pre-batch alarm settirtg, progrem set parameters and control parameters. A table of data that may be displayed
it, and
is on the instntment side Panel' lnstantaneous Flow Display: 5-segment bar graph' Data Setting:
computation Format: vo =
v(c
+ 0.5), c
ranges from
. 0 to I - its value
Displayed Data Seiection: Selected by push buttonsOne switch (on side panel) changes from major data displaY to auxiliary data disPiaY' Data setting: uses push button switches. Data setting may be inhibited (disabied) by an inhibit/enable
switch on the side Panel
the
Outputs puirr process variable input ( the instrument can also add or subtract an auxiliary flow signal input in this dispiay case. the span of analog output (to PI algorithm,
and repeater) is acljustable).
GS 1ts483.E
Jd
SLBC Modes
Control Functions
modes:
Batch loader (combination of batch set station and PI controller) or c PI controller (standalone controller, or master controller in a blending control system). o SPC or DDC modes are also possible. Batch Loader: One SLBC mode is batch loader (batch set station plus PI controller). (See batch sequence in table, and flow setpoint program in figure below). Program is started by start status inpu t or start
pushbutton on front panel.
(These
correspond to SPC and DDC respectively in computer (rernote setting) mode). Auto Mode: PI control. Proportional band 6.3 to 999.9Vo. Integration time constant I to 9999 sec. Manual Mode: Two speed operation. Slow - 40 sec./full span change. Fast - 4 sec.lfull sp an change. Control Mode Transfer: Bumpless and balanceless AIM
transfer.
'
'
PI Controller: Another S LBC mode is PI controller (standalone controller, or master controller in a blending control system demand pulse ogtput, using flow signal repeater, and master pacing input provided). loader or PI con troller modes (see above) using stopistart status inputs. Ramp change in output between high and low flow limits, step change in output between low flow limit and zero. Master Pacing Input: Changes (ONIOFF or OFF/ON) cause the output to rampl between high and low flow limits. Useful when SLBC is used as a blending master or used in a blending batch loader system (the SLBC can provide a demand pulse signal to a slave conEmergency Stop/Ristart (see figure): Provided for batch
Manipulated Variable Output Indication: Horizontal scale 3 9 mm long, one pointer, with two memory
indexes and valve open/close direction marks.
Indicator Accuracy !2.57o of span. Control Period : 0 .2 sec. Alarm Functions De tects loss of
flow process variable input signal between the tinre flow should have reached high limit
output contact opens. _ Leakage Detection: Detects leakage flow between"batch end and reset. ALM lamp lights, alarm\output contact
ope ns.
'
troller such
Controller).
Communication
super-
Batch Functions
Batch Sequence:
Batch status
visory computer via Field Control Unit (UFCU). Illaximum Distance between UFCU and SLBC: 100 m.
Lamp END Load
Status
lit
Status outpr, t
input/
output
Pushbutton
LOAD, PRE,
Reset
Start
Pre-
or status input
Batch end
pre -alarm
lit
oN*
ON to OFF OFF
ON
batch
Batch end
PR
E Iit
ON
Data Transmitted: Instantaneous flow, batch flow totalizer value (process variable, with auxiliary flow signal added to or subtracted from it, and compensation corn p u ta tion, , barch loacier se tting, initiai tjow setting, initial totalized-flow limit setting, high flow limit setting, manipulated variable output, control mode, batch status, alarm status, cornpensation
coefficients.
output
Batch end
output
Pushbutton
ON to OFF
ON
Data with Remote Setting: Batch loader setting, batch flow totalizer value (process variable, with auxiliary
Reset
or status input
Pushbutton
off . LOAD
f
OFF
OFF
(rno
lashing
men-
tary OFF ON to
LOAD'*,
PRE, END
f lash
Stop
or status input
ing
OFF**
pensation computation), initial flow setting, initial totalized-flow limit setting, high flow limit setting, manipulated variable output (in manual or DDC modes), control mode, batch sequence status, com-
below) is reached.
status input is turned OFF or RESET status input is turned ON. Qgntact opens after program ramps flow set point down to
pensation coefficients. Remote parame ter setting may be inhibited; if parame ter setting is enabled, the mode or any of these data can be changed from
the supervisory computer or operator console. Computeri Auto/lllanual (C/A/M) Mode Switches on
S
Batch Computation Period: 0.04 seconds. Setpoint Program: I l"* H ish Limit Setting
LBC Front Panel: Lamps in these switches indicate 'instrument mode. The mode (ComputerlAuto
Manual) can be checked and changed by a supervisory computer or from a remote operator station.
i
Pre-Batch-End Alarm
Leakage
During SPCiDDC operation from a supervisory computer, only the 3'C" (Computer) lamp is lit. During local operation or remote operation from the YEWPACK UOPC console, the (6A" or 53M"
lamps are lit.
-i t'
I
Start
R
I
ise Time
GS 1B4E3.E
)t
J?
Power Fail/Restart Functions Totalizer Value: Not changed by power failure. Batch and Control Functions:
Simulation Functions
For a power failure of up to approximately 2 seconds instrument status may remain norrnal (as if there were no break), or revert to that after an emergency
shut down (either action selectable) For a power failure of more than 2 seconds - instrument status reverts to that after an emergency shut down. Dbta Mernory Backup During Power Failure: By internal battery. All contact outputs are OFF during a power failure. Life of Backup Battery (temperature up to 45oC): At least 5 years (normal operation), At least I year (backup operation). Self-Diagnostic Func tions
The cause of an alarm if, indicated as a numeric code. Computation and Control Circuit Abnormal Alarm: FAIL lamp lights and fail contact output opens-
V" (standard) or
Version
1OOV
22OV
DC (polarity 11v_glsiblgl_ t__.4 tg 1:o v _* i *120 to.340 v - I-eo i" rga t--i--1 38 264 v Ac (4? *Gt
[;t
540 mA
56O mA
22.7 V A 23.3 VA
28.5 VA 29.5 VA
Power Failure, Pulse Repeater Overflow, Data Setting Overrange: ALM lamP lights
Insulation Resistance : Between I/O Terminals and Ground: l00Ma/500 V DC. Between Power and Cround: 100 MA/500 U,?a.
Dielectric Strength:
Ground:
500
V AC for
I minute.
Tota[rer Funclrons rl
i
;
Cumulattve
Process Vanable lnput (pulse srgnall Process Varrable lnput or Added, Suolracted
Fto*
(l to svl
iil
lnstantaneous Ftow Drsolav
Flow Srgnal
Repeater
tt
rtorr, Srgnat
computatron
1 (1 to 5V)
@ co--unrcatrons
Manroulated OutPut
Farl Srgnal
Starr Stop
Reset
(4 to 2O mA)
c omDensatton cornputatton
Master Pacrng
Reset Signat
" e.g. ciemand puise output '. The span of 1 to 5 V analog output (and the input to
computation.
Pl
algorithm, display and repeater) are also adiustable when auxiliary (addedrsubtractsd) f low input rs used.
GS 184E3-E
JF.
Between Power and Ground: 1000 v Ac for I minute ( 100 V version). 1500 v Ac for I minute QzA V version).
ACCESSORIES
Wiring:
Power and Ground Wiring: with earthing 100 v version: JIS c 9303-two-pin plug
Suffix Code
contact. (IEC A5-l 5, UL498) plug' 220 V version: CEE 7 VII (CENELEC standard)
Cable Length: 300 mm.
Batch Controller
with
CompGnsa-
-2 -3
to 5V DC
Mounting:
Flush panel mounting. lnstnrments are in housings, and may be mounted individually or side-by-side. Rear of instrument may be up to 7 5" below front' rows each up
tion lnput
Pt lOO O RTD
stvrr coJt-l .e
Option
loo
Always 0O
Style
/DL
/AzER /MTS
to
14 Common Options
/scFuM
/NHS
/NP /NPE
Without housing
Nameplate lettering Nameplate engraving
t.,
((D): Housing Dimensions: 182.5 (H) X 87 (W) X 480 depth behind Panel surface) ( mm) '
l'Yeight:
OPTIONS
/MTS: Supplied
ilzrn:
label attached' IDL: With data For ..22A V version" power supply.
mounting.
Formountingingroups,seeGSlB4Fl.E. change from /scF-GnM: Mounting kit bezel color from set of color (black). choose standard color color -E Specify F 1 I 2D (see 2 )' GS optional colors
module only' /NHS: No housing, plug-in instrument
code in sPace
[.
See
GslB4Fl.Etoorderhousingseparately.
/NP: Lettering on front panel nameplate' panel nameplate. /NPE: Letter! engraved on front
d:,
GS 18483-E
TERMINAL CONNECTIONS
Terminal Designation
1
Description
Terminal Designation
17 18
Description
2
3
Communications "2
19
4
5
:l
6
7
lSRrD
+ -,
+
inPut
\compensation input,
s
2A
21
I
9 10
11
-);;"
Dc*4
(-
terminal)
2O
A
B
Manipulated output, 4 to
mA DC
c
o
F H
J
output (+ terminall
12 13 14 15 16
*f
-
lL I l,Common
I
lllst"einput
pre.{catch
K L M
* -l -1 | - I t
output
Batch end output eommon (& reset output, Contact, or VoltageLevel Pu lse
:>
+
r
terminal)
Terminal No.
1
2-wire
3-wire
Transmitter's
Transmitter'5
Sigt.
2 3
:>Transmitter
Transmitter
\ rr"nsmitter +/
Use shielded twisted-pair cabf (SCCD see GS 3485K3{2E}. For Model SLBC-3OO only. For Model SLBC-2OO onty.
12V
bu
124
V distributor f or traltsmitter
.,,
l.
1
When ordering, specify the following: Model, suffix and option codes.
Nameplate marking,
/NPE).
if
and
be mounted individually.
. . .
. See
GS 3485C2-01E
See GS
34B5K3-028
labels
.
GS 1B4E3.E
3o
vewSERIEs
BCS
Drawings
li
80 t0.5
UN!T: mm
3.2 to 20
PANEL THICKNESS
otr
PANEL CUTOUT
RECOMIIIENDED POSITION
h
'3
I
#
oiie"i.i"" I C D
F !l ., J K A B
Trrminrl Drristion
TERMINAL CONNECTIONS
Trrmiml Drdgnrtion Drrcriptbn
t
2 3 a
5
.riarrl-l
14
Trtrnirul
r5
16
Orrcrigfton
+ +
t""rured
Putrc lnput .1
6 7 8 9 10
I
19 20
tl
Snn lnput
Rrrct lnput
Stop lnput
Comrnon
|+
-./
;
N
l:>Ararm
|+
output
12 13
Hotrc '1
Drrignrtion
1
Trminrl
2
Contret or Voltrgr.
Weight
2-Wiru Oirtributor
Lrvrl Pult
3-Win Dirrributor
Sig.r
: >'Trenrmittcr
SCCD
:>
rransmitrar
) Transmitter
l;
'2 Ur
'3
cabtc. Cablc lcngth: 3OO. Plug dimenrion: Sec the below drawing.
$ieldcd twirtcd.prir
Ar for depth dimencion, povwr connection and vrcight for option ',lLH,, reter to SD 1g4Fl -128.
r.5i0.
4.610,2
t5
l;Kb-N
%\-j \
JIS C 8303
EARTHING CONTACT
REMARKS
CEE PUELICATION 7 STANDARD SHEET VII 10/164 25OV IWO.POLE PLUG WITH OUAL.E,ARTHING CONTACTS
EARTH CONTACTS
SD
184E3-O1E
"-
36
*frtE
Drawings
HOU:SI-NG KtT (roo
L|NE
vrwSERtEs Bo
HOUSINGI
't
UNIT I nm
t\ l/--
t, tl tl ,
I t
;t
520-
360
l
a O. a
fi
.a
,
1777t
\
n
-l "rJ al
E0t0.
*rl
-f
-. I el
I
TERMINAL
BOAR,D
Terminel
Dcg:gnction
L1
De*ription
I'2
:>
',
*:.
\__
srzE
fiilileil
Fornr
Y
A4
-24A-2
fiTltr ffi
tct<ocAwA I'tctq.]st{tx EtEcrntc
A A A
FCI-XJYS80.010g
p-,37
198 4-04-20
,rl '
'!
c\l
o
Ll.t
I
E
.o
f:.
(o
; I I
I I I
(J
o
J lr,
z
o.
/?o
i*.j
,\