FREGA TEST PROCEDURE FOR DISTANCE RELAY

OHMEGA RELAY
1. SELECT FREGA ICON

2. CLICK CONNECT THEN SELECT DISTANCE ICON

1 / 12

3. FILL IFOMATION AND SELECT PROCED

4. WAITING SOME TIME UP TO LOADING

2 / 12

5. SELECT CONFIG

6. SELECT FILE THEN NEW TEST WILL SET PREFAULT, MAX FAULT, ZONE
TIME (3ZONES) AND CONFIG CONTACT ALSO CAN SELECT COLOUR

3 / 12

7. SELECT RX RAMP

8. FROM FILE MENU SELECT NEW TEST THEN (IMPORT A REFERNCE GRAPH)

4 / 12

9. TO CREATE GRAPH SELECT EDIT / CREATE A REFERANCE GRAPH

5 / 12

10.
Should be select circle or other chart according final setting, radius, angle,
a and b(will come auto when a value enter) Then click save element , create zone
this will give you the next zone after finish click file menu , save as , enter the
name for your graph , click file menu then exit

6 / 12

Important information about graph building:

In case of phase phase graph building


Take the radius = zone setting value /2 and the angle equal line angle
In case of phase ground graph building
Take the radius = zone setting value(1+K0) / 2 and the angle equal comp. Angle
, K0= 1/3{(Z0/Z1)-1}
REF. OHMEGA MANUAL - Chapter 2 -sheet (4,5)

Must be Ke value and angle equal zero in configuration

7 / 12

Example for 132/33 kv s/s 8903 hail


al_khotta line M08
Setting from protection engineering division central:

1- For testing Z1 By FREJA Tester


line angle
EF comp. Z0/Z1 ratio
ZF comp. Angle
Z1 PF impedance
Z1 EF impedance

65
2.79
75
7.52
7.52

In freja software - graph building:


For ph ph
Radius = Z1/2 = 7.52 / 2 = 3.76
radius
a

3.76
0

Angle
b

65
7.52

For ph E
K0= 1/3{(Z0/Z1)-1} = 1/3(2.79 1) = 0.6
Radius = Z1*(1+k0)/2 =6.016
radius
a

6.016
0

Angle
b

8 / 12

75
12.032

2- For testing Z2 by FREJA Tester


Setting from protection engineering division central:
line angle
EF comp. Z0/Z1 ratio
ZF comp. Angle
Z2 PF impedance
Z2 EF impedance

65
2.79
75
11.1
11.1

In freja software - graph building:


For ph ph
Radius = Z2/2 = 11.1/ 2 = 5.55
radius
5.55
Angle
a
0
b
For ph E
K0= 1/3{(Z0/Z1)-1} = 1/3(2.79 1) = 0.6
Radius = Z2*(1+k0)/2 = 8.88
radius
8.88
Angle
a
0
b

65
11.1

75
17.76

3- For testing Z3 by FREJA Tester


Setting from protection engineering division central:
line angle
65
EF comp. Z0/Z1 ratio
2.79
ZF comp. Angle
75
Z3 type
Offset MHO
Z3 PF impedance (FWD)
22.2
Z3 PF impedance (Rev)
2.21
Z3 EF impedance (FWD)
22.2
Z3 EF impedance (Rev)
2.21

In freja software - graph building:


For ph ph
Radius ={ Z3 (FWD) +Z3(Rev) } / 2 = (22.2 +2.21) / 2 = 12.205
radius
12.205
Angle
65
a
2.21
b
22.2
For ph E
K0= 1/3{(Z0/Z1)-1} = 1/3(2.79 1) = 0.65
Radius = {Z3 (FWD) +Z3(Rev)} * (1+K0) / 2 = 19.528
a= Z3 EF (Rev) (1+k0)=3.536
, b = Z3 EF (FWD) (1+k0)= = 35.52
radius
19.528
Angle
75
a
3.536
b
35.52

11. Adjust start, stop & step for your wanted No. of RAMPS Then START

9 / 12

Time reach
In configuration screen adjust zone time tz1=0 , tz2=800msec. , tz3= 1.5 sec.

10 / 12

Go to Zt screen
Import your graph or you can make new graph like the zone reach graph

After finish ---- file save as , file exit

11 / 12

Select the phases and Click start after finish click report then print

Eng. Mohammed Deraz