Combination automatic motor starters with overload protection built into the circuit-breaker

D.O.L. starters, non-reversing, from 0.37 to 5.5 kW at 400/415 V, type 1 coordination


This pre-assembled combination comprises: - 1 motor circuit-breaker type GV2-ME, - 1 3-pole contactor, - 1 combination block GV2-AF01.

Characteristics
Starter type Breaking capacity (Iq) (1) To IEC-947-4-1 GV2400/415 V 440 V 500 V kA kA kA ME06K1 50 50 50 ME07K1 50 50 50 ME08K1 50 50 50 ME10K1 50 50 50 ME14K1 50 15 10 (4 kW) 6 (5.5 kW) ME16K1 15 8 6

References
D.O.L. starters, non-reversing Standard Setting power ratings range of of 3-phase thermal motors trips 50/60 Hz in AC-3 400/ 415V 440V 500V kW kW kW A 0.37 0.37 0.37 0.55 0.55 0.55 0.75 0.75 0.75 1.1 1.1 1.1 1.5 GV2-ME06K1// 2.2 3 4 5.5 2.2 3 4 5.5 3 4 5.5 7.5 46.3 78 GV2-ME10 LC1-K06 GV2-ME10K1// 0.460 1.5 1.5 2.2 11.6
810484

Fixed magnetic tripping current 13 Irth

For customer assembly Motor Contactor circuitReference breaker to be Reference completed (3)

Pre-assembled Basic reference. Complete with code indicating control circuit voltage (2)

Weight

A 22.5 GV2-ME06 LC1-K06 GV2-ME06K1//

kg 0.460

1.62.5

33.5

GV2-ME07

LC1-K06

GV2-ME07K1//

0.460

2.54

51

GV2-ME08

LC1-K06

GV2-ME08K1//

0.460

610

138

GV2-ME14

LC1-K09

GV2-ME14K1//

0.460

914

170

GV2-ME16

LC1-K12

GV2-ME16K1//

0.460

Add-on blocks Description

Sold in lots of

Unit reference GV2-AF01

Weight kg 0.020

Combination block between circuit-breaker and contactor 10

(1) The breaking performance of circuit-breakers GV2-ME can be increased by adding a current limiter GV1-L3, see page 24509/5. (2) Standard control circuit voltages (for other voltages, please consult your Regional Sales Office). Volts 24 110 220/230 230 230/240 380/400 " 50/60 Hz B7 F7 M7 P7 U7 Q7 $ (4) BW3 (3) Please consult your Regional Sales Office. (4) Coil: low consumption (1.5 W), wide range (0.71.3 Uc) with integral suppression device as standard.

Dimensions: page 24536/2 24520_Ver5.00-EN.fm/2

Schemes: page 24536/3


Schneider Electric

References

TeSys motor starters - open version


Combination automatic motor starters with overload protection built into the circuit-breaker

D.O.L. starters, reversing, from 0.37 to 5.5 kW at 400/415 V, type 1 coordination


This pre-assembled combination comprises: - 1 motor circuit-breaker type GV2-ME, - 1 3-pole reversing contactor, - 1 combination block GV2-AF01.

Characteristics
Starter type Breaking capacity (Iq) (1) To IEC-947-4-1 GV2400/415 V 440 V 500 V kA kA kA ME06K2 50 50 50 ME07K2 50 50 50 ME08K2 50 50 50 ME10K2 50 50 50 ME14K2 50 15 10 (4 kW) 6 (5.5 kW) ME16K2 15 8 6

References
D.O.L. starters, reversing Standard Setting power ratings range of of 3-phase thermal motors trips 50/60 Hz in AC-3 400/ 415V 440V 500V kW kW kW A 0.37 0.37 0.37 0.55 0.55 0.55 0.75 0.75 0.75 1.1 1.1 1.1 1.5 GV2-ME06K2// 2.2 3 4 5.5 2.2 3 4 5.5 3 4 5.5 7.5 46.3 78 GV2-ME10 LC2-K06 GV2-ME10K2// 0.460 1.5 1.5 2.2 11.6
810485

Fixed magnetic tripping current 13 Irth

For customer assembly Motor Reversing circuitcontactor breaker Reference Reference to be completed (3)

Pre-assembled Basic reference. Complete with code indicating control circuit voltage (2)

Weight

A 22.5 GV2-ME06 LC2-K06 GV2-ME06K2//

kg 0.460

1.62.5

33.5

GV2-ME07

LC2-K06

GV2-ME07K2//

0.460

2.54

51

GV2-ME08

LC2-K06

GV2-ME08K2//

0.460

610

138

GV2-ME14

LC2-K09

GV2-ME14K2//

0.460

914

170

GV2-ME16

LC2-K12

GV2-ME16K2//

0.460

Add-on blocks Description

Sold in lots of

Unit reference GV2-AF01

Weight kg 0.020

Combination block between circuit-breaker and contactor 10

(1) The breaking performance of circuit-breakers GV2-ME can be increased by adding a current limiter GV1-L3, see page 24509/5. (2) Standard control circuit voltages (for other voltages, please consult your Regional Sales Office). Volts 24 110 220/230 230 230/240 380/400 " 50/60 Hz B7 F7 M7 P7 U7 Q7 $ (4) BW3 (3) Please consult your Regional Sales Office. (4) Coil: low consumption (1.5 W), wide range (0.71.3 Uc) with integral suppression device as standard.

Dimensions: page 24536/2


Schneider Electric

Schemes: page 24536/3 24520_Ver5.00-EN.fm/3

References

TeSys motor starters - open version


Combination automatic motor starters with overload protection built into the circuit-breaker

D.O.L. starters, non-reversing, from 0.06 to 15 kW at 400/415 V, type 1 coordination


This pre-assembled combination comprises: - 1 motor circuit-breaker type GV2-ME, - 1 3-pole contactor, - 1 combination block GV2-AF3.

Characteristics
Starter type Breaking capacity (Iq) (1) To IEC-947-4-1 GV2400/415 V 440 V 500 V kA kA kA DM102 DM114 to DM110 50 50 50 50 15 10 DM116 15 8 6 DM120 15 8 6 DM121 15 6 4 DM122 15 6 4 DM132 10 6 4

References
D.O.L. starters, non-reversing (3) Standard Setting Fixed power ratings range of magnetic of 3-phase thermal tripping motors trips current 50/60 Hz 13 Irth in AC-3 400/ 415V 440V 500V kW kW kW A A
810486

For customer assembly Motor Contactor circuitReference breaker to be Reference completed (4)

Pre-assembled Basic reference. Complete with code indicating control circuit voltage (2)

Weight

kg GV2-ME02 GV2-ME03 GV2-ME04 GV2-ME05 GV2-ME06 GV2-ME07 GV2-ME08 GV2-ME10 GV2-ME14 GV2-ME16 GV2-ME20 GV2-ME21 GV2-ME22 GV2-ME32 LC1-D09// LC1-D09// LC1-D09// LC1-D09// LC1-D09// LC1-D09// LC1-D09// LC1-D09// LC1-D09// LC1-D12// LC1-D18// LC1-D25// LC1-D25// LC1-D32// GV2-DM102// GV2-DM103// GV2-DM104// GV2-DM105// GV2-DM106// GV2-DM107// GV2-DM108// GV2-DM110// GV2-DM114// GV2-DM116// GV2-DM120// GV2-DM121// GV2-DM122// GV2-DM132// Unit reference GV2-AF3 0.596 0.596 0.596 0.596 0.596 0.596 0.596 0.596 0.596 0.601 0.606 0.646 0.646 0.651 Weight kg 0.016

0.06 0.09 0.12 0.18 0.25 0.37 0.55 0.75 1.1 1.5 2.2 3 4 5.5 7.5 GV2-DM102// 9 11 15

0.06 0.09 0.12 0.18 0.25 0.37 0.37 0.55 0.55 0.75 0.75 1.1 1.1 1.5 1.5 2.2 2.2 3 3 4 4 5.5 5.5 7.5 9 11 15 7.5 9 11 15 18.5

0.160.25 0.250.40 0.400.63 0.631 11.6 1.62.5 2.54 46.3 610 914 1318 1723 2025 2432

2.4 5 8 13 22.5 33.5 51 78 138 170 223 327 327 416

Add-on blocks Description Combination block between circuit-breaker and contactor

Mounting of Sold in GV2 lots of rail 10

10 GV2-AF4 0.016 Mtg. plate LAD-31 (1) The breaking performance of circuit-breakers GV2-ME can be increased by adding a current limiter GV1-L3, see page 24509/5. (2) Standard control circuit voltages (for other voltages, please consult your Regional Sales Office). Volts 24 220 230 50/60 Hz B7 M7 P7 $ (5) BD (3) Can be combined with type 2, see page 24539/3. (4) See page 24501/2. (5) Coil with integral suppression device as standard.

Dimensions: page 24536/2 24520_Ver5.00-EN.fm/4

Schemes: page 24536/3


Schneider Electric

References

TeSys motor starters - open version


Combination automatic motor starters with overload protection built into the circuit-breaker

D.O.L. starters, reversing, from 0.06 to 15 kW at 400/415 V, type 1 coordination


This pre-assembled combination comprises: - 1 motor circuit-breaker type GV2-ME, - 1 3-pole reversing contactor, - 1 combination block GV2-AF3.

Characteristics
Starter type Breaking capacity (Iq) (1) To IEC-947-4-1 GV2400/415 V 440 V 500 V kA kA kA DM202 DM214 to DM210 50 50 50 50 15 10 DM216 15 8 6 DM220 15 8 6 DM221 15 6 4 DM222 15 6 4 DM232 10 6 4

References
D.O.L. starters, reversing (3) Standard Setting power ratings range of of 3-phase thermal motors trips 50/60 Hz in AC-3 400/ 415V 440V 500V kW kW kW A 0.06 0.09 0.12 0.18 0.25 0.37 0.55 0.75 1.1 1.5 2.2 3 4 5.5 7.5 GV2-DM202// 9 11 15 0.06 0.09 0.12 0.18 0.25 0.37 0.55 0.75 1.1 1.5 2.2 3 4 5.5 7.5 9 11 15 0.37 0.55 0.75 1.1 1.5 2.2 3 4 5.5 7.5 9 11 15 18.5 0.160.25 0.250.40 0.400.63 0.631 11.6 1.62.5 2.54 46.3 610 914 1318 1723 2025 2432 Fixed magnetic tripping current 13 Irth For customer assembly Motor Reversing circuitcontactor breaker Reference Reference to be completed (4) Pre-assembled Basic reference. Complete with code indicating control circuit voltage (2) Weight

810487

A 2.4 5 8 13 22.5 33.5 51 78 138 170 223 327 327 416 GV2-ME02 GV2-ME03 GV2-ME04 GV2-ME05 GV2-ME06 GV2-ME07 GV2-ME08 GV2-ME10 GV2-ME14 GV2-ME16 GV2-ME20 GV2-ME21 GV2-ME22 GV2-ME32 Mounting of GV2 rail LC2-D09// LC2-D09// LC2-D09// LC2-D09// LC2-D09// LC2-D09// LC2-D09// LC2-D09// LC2-D09// LC2-D12// LC2-D18// LC2-D25// LC2-D25// LC2-D32// Sold in lots of 10 GV2-DM202// GV2-DM203// GV2-DM204// GV2-DM205// GV2-DM206// GV2-DM207// GV2-DM208// GV2-DM210// GV2-DM214// GV2-DM216// GV2-DM220// GV2-DM221// GV2-DM222// GV2-DM232// Unit reference GV2-AF3

kg 0.963 0.963 0.963 0.963 0.963 0.963 0.963 0.963 0.963 0.973 0.983 1.063 1.063 1.073 Weight kg 0.016

Add-on blocks Description Combination block between circuit-breaker and contactor

10 GV2-AF4 0.016 Mtg. plate LAD-31 (1) The breaking performance of circuit-breakers GV2-ME can be increased by adding a current limiter GV1-L3, see page 24509/5. (2) Standard control circuit voltages (for other voltages, please consult your Regional Sales Office). Volts 24 220 230 50/60 Hz B7 M7 P7 $ (5) BD (3) Can be combined with type 2, see page 24540/3. (4) See page 24501/2. (5) Coil with integral suppression device as standard.

Dimensions: page 24536/2


Schneider Electric

Schemes: page 24536/3 24520_Ver5.00-EN.fm/5

References

TeSys motor starters - open version


Combination automatic motor starters with overload protection built into the circuit-breaker

D.O.L. starters, non-reversing, from 0.06 to 15 kW at 400/415 V, type 2 coordination


This pre-assembled combination comprises: - 1 motor circuit-breaker type GV2-P, - 1 3-pole contactor, - 1 combination block GV2-AF3

Characteristics
Starter type Breaking capacity (Iq) (1) To IEC-947-4-1 GV2400/415 V 440 V 500 V kA kA kA DP102 DP114 to DP110 130 130 130 130 130 50 DP116 130 50 42 DP120 50 20 10 DP121 50 20 10 DP122 50 20 10 DP132 50 20 10

References
D.O.L. starters, non-reversing Standard Setting power ratings range of of 3-phase thermal motors trips 50/60 Hz in AC-3 400/ 415V 440V 500V kW kW kW A 0.06 0.09 0.12 0.18 0.25 0.37 0.55 0.75 1.1 1.5 2.2 3 4 5.5 GV2-DP102// 7.5 9 11 15 0.06 0.09 0.12 0.18 0.25 0.37 0.55 0.75 1.1 1.5 2.2 3 4 5.5 7.5 9 11 15 0.37 0.55 0.75 1.1 1.5 2.2 3 4 5.5 7.5 9 11 15 18.5 0.160.25 0.250.40 0.400.63 0.631 11.6 1.62.5 2.54 46.3 610 914 1318 1723 2025 2432 Fixed magnetic tripping current 13 Irth For customer assembly Motor Contactor circuit Reference breaker to be Reference completed (3) Pre-assembled Basic reference. Complete with code indicating control circuit voltage (2) Weight

810488

A 2.4 5 8 13 22.5 33.5 51 78 138 170 223 327 327 416 GV2-P02 GV2-P03 GV2-P04 GV2-P05 GV2-P06 GV2-P07 GV2-P08 GV2-P10 GV2-P14 GV2-P16 GV2-P20 GV2-P21 GV2-P22 GV2-P32 LC1-D09// LC1-D09// LC1-D09// LC1-D09// LC1-D09// LC1-D09// LC1-D09// LC1-D09// LC1-D09// LC1-D25// LC1-D25// LC1-D25// LC1-D25// LC1-D32// GV2-DP102// GV2-DP103// GV2-DP104// GV2-DP105// GV2-DP106// GV2-DP107// GV2-DP108// GV2-DP110// GV2-DP114// GV2-DP116// GV2-DP120// GV2-DP121// GV2-DP122// GV2-DP132// Unit reference GV2-AF3

kg 0.686 0.686 0.686 0.686 0.686 0.686 0.696 0.736 0.736 0.741 0.736 0.741 0.741 0.741 Weight kg 0.016

Add-on blocks Description Combination block between circuit-breaker and contactor

Mounting of Sold in GV2 lots of rail 10

Mtg. plate 10 GV2-AF4 0.016 LAD-31 (1) The breaking performance of circuit-breakers GV2-P can be increased by adding a current limiter GV1-L3, see page 24509/5. (2) Standard control circuit voltages (for other voltages, please consult your Regional Sales Office). Volts 24 220 230 50/60 Hz B7 M7 P7 $ (4) BD (3) See page 24501/2. (4) Coil with integral suppression device as standard.

Dimensions: page 24536/2 24520_Ver5.00-EN.fm/6

Schemes: page 24536/3


Schneider Electric

References

TeSys motor starters - open version


Combination automatic motor starters with overload protection built into the circuit-breaker

D.O.L. starters, reversing, from 0.06 to 15 kW at 400/415, type 2 coordination


This pre-assembled combination comprises: - 1 motor circuit-breaker type GV2-P, - 1 3-pole reversing contactor, - 1 combination block GV2-AF3.

Characteristics
Starter type Breaking capacity (Iq) (1) To IEC-947-4-1 GV2400/415 V 440 V 500 V kA kA kA DP202 DP214 to DP210 130 130 130 130 130 50 DP216 130 50 42 DP220 50 20 10 DP221 50 20 10 DP222 50 20 10 DP232 50 20 10

References
D.O.L. starters, non-reversing Standard Setting power ratings range of of 3-phase thermal motors trips 50/60 Hz in AC-3 400/ 415V 440V 500V kW kW kW A 0.06 0.09 0.12 0.18 0.25 0.37 0.55 0.75 1.1 1.5 2.2 3 4 5.5 7.5 GV2-DP202// 9 11 15 0.06 0.09 0.12 0.18 0.25 0.37 0.55 0.75 1.1 1.5 2.2 3 4 5.5 7.5 9 11 15 0.37 0.55 0.75 1.1 1.5 2.2 3 4 5.5 7.5 9 11 15 18.5 0.160.25 0.250.40 0.400.63 0.631 11.6 1.62.5 2.54 46.3 610 914 1318 1723 2025 2432 Fixed magnetic tripping current 13 Irth For customer assembly Motor Reversing circuitcontactor breaker Reference Reference to be completed (3) Pre-assembled Basic reference. Complete with code indicating control circuit voltage (2) Weight

810489

A 2.4 5 8 13 22.5 33.5 51 78 138 170 223 327 327 416 GV2-P02 GV2-P03 GV2-P04 GV2-P05 GV2-P06 GV2-P07 GV2-P08 GV2-P10 GV2-P14 GV2-P16 GV2-P20 GV2-P21 GV2-P22 GV2-P32 Mounting of GV2 rail LC2-D09// LC2-D09// LC2-D09// LC2-D09// LC2-D09// LC2-D09// LC2-D09// LC2-D09// LC2-D09// LC2-D25// LC2-D25// LC2-D25// LC2-D25// LC2-D32// Sold in lots of 10 GV2-DP202// GV2-DP203// GV2-DP204// GV2-DP205// GV2-DP206// GV2-DP207// GV2-DP208// GV2-DP210// GV2-DP214// GV2-DP216// GV2-DP220// GV2-DP221// GV2-DP222// GV2-DP232// Unit reference GV2-AF3

kg 1.053 1.053 1.053 1.053 1.053 1.053 1.073 1.153 1.153 1.163 1.153 1.163 1.163 1.163 Weight kg 0.016

Add-on blocks Description

Combination block between circuit-breaker and contactor

10 GV2-AF4 0.016 Mtg. plate LAD-31 (1) The breaking performance of circuit-breakers GV2-P can be increased by adding a current limiter GV1-L3, see page 24509/5. (2) Standard control circuit voltages (for other voltages, please consult your Regional Sales Office). Volts 24 220 230 50/60 Hz B7 M7 P7 $ (4) BD (3) See page 24501/2. (4) Coil with integral suppression device as standard.

Dimensions: page 24536/2


Schneider Electric

Schemes: page 24536/3 24520_Ver5.00-EN.fm/7

Combinations for assembly TeSys motor starters - open by the customer version
D.O.L. starters with circuit-breaker and overload protection built into the circuit-breaker

0.06 to 110 kW at 400/415 V: type 1 coordination


Standard power ratings of 3-phase motors 50/60 Hz in category AC-3 400/415 V 440 V P Ie Iq (1) P Ie kW A kA kW A 0.06 0.09 0.12 0.18 0.25 0.37 0.55 0.75 1.1 1.5 2.2 3 4 5.5 7.5 9 11 15 18.5 22 30 37 37 45 55 75 90 0.22 0.36 0.42 0.6 0.88 0.98 1.5 2 2.5 3.5 5 6.5 8.4 11 14.8 18.1 21 28.5 35 42 57 69 69 81 100 135 165 50 50 50 50 50 50 50 50 50 50 50 50 50 15 15 15 15 10 35 35 35 15 25 25 25 35 35 0.06 0.09 0.12 0.18 0.25 0.37 0.55 0.75 1.1 1.5 2.2 3 4 5.5 7.5 9 11 15 18.5 22 30 37 37 45 45 50 75 90 110 0.19 0.28 0.37 0.55 0.76 0.99 1.36 1.68 2.37 3.06 4.42 5.77 7.9 10.4 13.7 16.9 20.1 26.5 32.8 39 51.5 64 64 76 76 90 125 146 178 500 V P Ie kW A 0.37 0.55 0.75 1.1 1.5 2.2 3 4 5.5 7.5 9 11 15 18.5 18.5 22 30 37 45 45 55 55 75 90 110 132 160 1 1.21 1.5 2 2.6 3.8 5 6.5 9 12 13.9 18.4 23 28.5 28.5 33 45 55 65 65 80 80 105 129 156 187 220 Circuit-breaker Reference (2) Iq (1) kA 50 50 50 50 50 50 50 10 10 6 6 4 4 4 8 8 8 8 4 18 4 18 30 30 30 30 30 GV2-ME02 GV2-ME03 GV2-ME04 GV2-ME05 GV2-ME06 GV2-ME06 GV2-ME07 GV2-ME08 GV2-ME10 GV2-ME14 GV2-ME16 GV2-ME20 GV2-ME21 GV2-ME22 GV2-ME32 GV3-ME40 GV3-ME40 GV3-ME63 GV3-ME63 GV3-ME80 GV7-RE80 GV3-ME80 GV7-RE80 GV7-RE100 GV7-RE100 GV7-RE150 GV7-RE150 GV7-RE150 GV7-RE220 GV7-RE220 Setting range of thermal trips A 0.160.25 0.250.40 0.400.63 0.631 11.6 11.6 1.6.2.5 2.54 46.3 610 914 1318 1723 2025 2432 2540 2540 4063 4063 5680 4880 5680 4880 60100 60100 90150 90150 90150 132220 132220 Contactor Reference

Iq (1) kA 50 50 50 50 50 50 50 50 50 50 50 50 15 8 8 8 6 6 25 25 25 10 25 10 25 25 35 35 35

LC1-K06 or LC1-D09 LC1-K06 or LC1-D09 LC1-K06 or LC1-D09 LC1-K06 or LC1-D09 LC1-K06 or LC1-D09 LC1-K06 or LC1-D09 LC1-K06 or LC1-D09 LC1-K06 or LC1-D09 LC1-K06 or LC1-D09 LC1-K09 or LC1-D09 LC1-K12 or LC1-D12 LC1-D18 LC1-D25 LC1-D25 LC1-D32 LC1-D38 LC1-D40 LC1-D50 LC1-D65 LC1-D65 LC1-D65 LC1-D80 LC1-D80 LC1-D95 LC1-D115 LC1-D115 LC1-D150 LC1-F185 LC1-F185 LC1-F265

110 200 35 132 215 35 GV7-RE220 132220 LC1-F225 (1) The breaking performance of circuit-breakers GV2-ME can be increased by adding a current limiter GV1-L3, see page 24509/5. (2) For reversing operation, replace the reference prefix LC1 by LC2.

24539_Ver3.20-EN.fm/2

Schneider Electric

Combinations for assembly TeSys motor starters - open by the customer version
D.O.L. starters with circuit-breaker and overload protection built into the circuit-breaker

0.06 to 110 kW at 400/415 V: type 2 coordination


Standard power ratings of 3-phase motors 50/60 Hz in category AC-3 400/415 V 440 V P Ie Iq (1) P Ie kW A kA kW A 0.06 0.09 0.12 0.18 0.25 0.37 0.55 0.75 1.1 1.5 2.2 3 4 5.5 7.5 9 11 15 15 18.5 22 30 37 45 55 75 90 0.22 0.36 0.42 0.6 0.88 0.98 1.5 2 2.5 3.5 5 6.5 8.4 11 14.8 18.1 21 28.5 28.5 35 42 57 69 81 100 135 165 130 130 130 130 130 130 130 130 130 130 130 130 130 130 50 50 50 35 70 70 70 70 70 70 70 70 70 0.06 0.09 0.12 0.18 0.25 0.37 0.55 0.75 1.1 1.5 2.2 3 2.2 3 4 4 5.5 7.5 9 11 15 15 18.5 22 30 37 45 55 75 90 110 0.19 0.28 0.37 0.55 0.76 0.99 1.36 1.68 2.37 3.06 4.42 5.77 4.42 5.77 7.9 7.9 10.4 13.7 16.9 20.1 26.5 26.5 32.8 39 51.5 64 76 90 125 146 178 500 V P Ie kW A 0.37 0.55 0.75 1.1 1.5 2.2 3 3 4 5.5 4 5.5 7.5 9 11 15 18.5 18.5 22 30 37 45 55 90 110 1 1.21 1.5 2 2.6 3.8 5 5 6.5 9 6.5 9 12 13.9 18.4 23 28.5 28.5 33 45 55 65 80 129 156 Circuit-breaker Reference (2) Iq (1) kA 130 130 130 130 130 130 50 130 10 10 50 50 42 42 10 10 10 50 50 50 50 50 50 50 50 Setting range of thermal trips A Contactor Reference (3)

Iq (1) kA 130 130 130 130 130 130 130 130 130 130 50 50 130 130 15 130 50 50 20 20 25 65 65 65 65 65 65 65 65 65 65

GV2-P02 or GV2-ME02 0.160.25 GV2-P03 or GV2-ME03 0.250.4 GV2-P04 or GV2-ME04 0.40.63 GV2-P05 or GV2-ME05 0.631 GV2-P06 or GV2-ME06 11.6 GV2-P06 or GV2-ME06 11.6 GV2-P07 or GV2-ME07 1.62.5 GV2-P08 or GV2-ME08 2.54 GV2-P10 or GV2-ME10 46.3 GV2-ME10 GV2-P10 46.3 46.3

LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D12 LC1-D25 LC1-D25 LC1-D25 LC1-D25 LC1-D32 LC1-D32 LC1-D40 LC1-D40 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D80 LC1-D115 LC1-D115 LC1-D115 LC1-D150 LC1-F185 LC1-F225 LC1-F265

GV2-P14 or GV2-ME14 610 GV2-ME14 GV2-P14 610 610

GV2-P16 or GV2-ME16 914 GV2-P20 or GV2-ME20 1318 GV2-P21 or GV2-ME21 1723 GV2-P22 or GV2-ME22 2025 GV2-P22 2025 GV2-P32 or GV2-ME32 GV7-RS40 GV7-RS40 GV7-RS40 GV7-RS50 GV7-RS80 GV7-RS50 GV7-RS80 GV7-RS80 GV7-RS80 GV7-RS80 GV7-RS80 GV7-RS100 GV7-RS150 GV7-RS220 2540 2540 2540 2540 3050 4880 3050 4880 4880 4880 4880 4880 60100 90150 132220

110 200 70 132 215 65 GV7-RS220 132220 132 187 50 160 220 50 GV7-RS220 132220 (1) The breaking performance of circuit-breakers GV2-P can be increased by adding a current limiter GV1-L3, see page 24509/5. (2) Combinations with circuit-breaker GV2-ME are type 2 coordinated only at 400/415 V and 440 V. (3) For reversing operation, replace the reference prefix LC1 by LC2.

Schneider Electric

24539_Ver3.20-EN.fm/3

Combinations for assembly TeSys motor starters - open by the customer version
D.O.L. starters with circuit-breaker and overload protection by separate thermal overload relay

0.06 to 250 kW at 400/415 V: type 1 coordination


Standard power ratings of 3-phase Circuit-breaker Contactor Thermal overload relay motors 50/60 Hz in category AC-3 Reference RatIrm Reference Reference Setting 400/415 V 440 V 500 V ing (1) (2) range P Ie Iq P Ie Iq P Ie Iq kW A kA kW A kA kW A kA A A A GV2-LE03 0.4 5 LC1-K06 LR2-K0302 0.160.23 0.06 0.22 50 0.06 0.19 50 0.09 0.28 50 GV2-LE03 0.4 5 LC1-K06 LR2-K0303 0.230.36 GV2-LE03 0.4 5 LC1-K06 LR2-K0304 0.360.54 0.09 0.36 50 0.12 0.37 50 0.12 0.42 50 GV2-LE04 0.63 8 LC1-K06 LR2-K0304 0.360.54 GV2-LE04 0.63 8 LC1-K06 LR2-K0305 0.540.8 0.18 0.6 50 0.18 0.55 50 0.25 0.76 50 GV2-LE05 1 13 LC1-K06 LR2-K0305 0.540.8 0.25 0.88 50 GV2-LE05 1 13 LC1-K06 LR2-K0306 0.81.2 0.37 1 50 0.37 1 50 0.37 1 50 0.55 1.5 50 0.55 1.36 50 0.55 1.21 50 GV2-LE06 1.6 22.5 LC1-K06 LR2-K0307 1.21.8 0.75 1.5 50 GV2-LE07 2.5 33.5 LC1-K06 LR2-K0307 1.21.8 0.75 1.68 50 0.75 2 50 GV2-LE07 2.5 33.5 LC1-K06 LR2-K0308 1.82.6 1.1 2.5 50 1.1 2.37 50 1.1 2 50 1.5 3.5 50 1.5 3.06 50 1.5 2.6 50 GV2-LE08 4 51 LC1-K06 LR2-K0310 2.63.7 GV2-LE08 4 51 LC1-K06 LR2-K0312 3.75.5 2.2 3.8 50 2.2 5 50 2.2 4.4 50 3 5 50 GV2-LE10 6.3 78 LC1-K06 LR2-K0312 3.75.5 GV2-LE10 6.3 78 LC1-K06 LR2-K0314 5.58 3 5.77 50 4 7.9 15 GV2-LE14 10 138 LC1-K09 LR2-K0314 5.58 GV2-LE14 10 138 LC1-K09 LR2-K0314 5.58 3 6.5 50 4 6.5 10 4 8.4 50 GV2-LE14 10 138 LC1-K09 LR2-K0316 811.5 GV2-LE16 14 170 LC1-K12 LR2-K0321 1014 5.5 11 15 5.5 10.4 8 7.5 12 6 7.5 13.7 8 9 13.9 6 GV2-LE16 14 170 LC1-D18 LRD-21 1218 GV2-LE20 18 223 LC1-D18 LRD-21 1218 7.5 14.8 15 9 16.9 8 9 18.1 15 11 18.4 4 GV2-LE22 25 327 LC1-D25 LRD-22 1624 GV2-LE22 25 327 LC1-D25 LRD-22 1624 11 21 15 11 20.1 6 15 23 4 15 28.5 10 15 26.5 6 18.5 26.5 4 GV2-LE32 32 416 LC1-D32 LRD-32 2332 NS80HMA 50 500 LC1-D38 LRD-35 3038 18.5 35 70 18.5 32.5 65 22 33 25 NS80HMA 50 450 LC1-D40 LRD-3355 3040 NS80HMA 50 650 LC1-D40 LRD-3357 3750 22 39 65 22 42 70 30 40 25 NS80HMA 50 650 LC1-D50 LRD-3357 3750 NS80HMA 50 880 LC1-D65 LRD-3359 4865 30 57 70 30 51.5 65 37 64 65 37 55 25 NS80HMA 80 960 LC1-D65 LRD-3359 4865 NS80HMA 80 960 LC1-D80 LRD-3361 5570 45 65 25 37 69 70 45 76 65 55 80 25 NS80HMA 80 1040 LC1-D80 LRD-3363 6380 NS100/MA (3) 100 1300 LC1-D95 LRD-3365 80104 45 81 (3) 50 90 (3) NS100/MA (3) 100 1200 LC1-D115 LRD-4365 80104 NS160/MA (3) 150 1500 LC1-D115 LRD-4367 95120 75 105 (3) 55 100 (3) NS160/MA (3) 150 1350 LC1-D115 LRD-4367 95120 NS160/MA (3) 150 1800 LC1-D150 LRD-4369 110140 75 135 (3) 75 125 (3) 90 129 (3) 90 146 (3) NS160/MA (3) 150 1950 LC1-F185 LR9-F5371 132220 NS250/MA (3) 220 2200 LC1-F185 LR9-F5371 132220 90 165 (3) 110 156 (3) 110 200 (3) NS250/MA (3) 220 2640 LC1-F225 LR9-F5371 132220 110 178 (3) NS250/MA (3) 220 2420 LC1-F225 LR9-F5371 132220 NS250/MA (3) 220 2640 LC1-F265 LR9-F5371 132220 132 187 (3) 132 215 (3) NS250/MA (3) 220 2860 LC1-F265 LR9-F5371 132220 NS400/MA (3) 320 3200 LC1-F265 LR9-F7375 200330 132 240 (3) 160 220 (3) NS400/MA (3) 320 2860 LC1-F265 LR9-F7375 200330 NS400/MA (3) 320 3520 LC1-F330 LR9-F7375 200330 160 256 (3) 160 285 (3) 200 321 (3) NS400/MA (3) 320 4160 LC1-F330 LR9-F7375 200330 NS400/MA (3) 320 3840 LC1-F330 LR9-F7375 200330 200 281 (3) 220 310 (3) NS400/MA (3) 320 4160 LC1-F400 LR9-F7379 300500 NS630/MA (3) 500 5000 LC1-F400 LR9-F7379 300500 200 352 (3) 220 353 (3) 250 401 (3) NS630/MA (3) 500 5550 LC1-F400 LR9-F7379 300500 NS630/MA (3) 500 5000 LC1-F400 LR9-F7379 300500 250 360 (3) 220 388 (3) NS630/MA (3) 500 5500 LC1-F400 LR9-F7379 300500 250 437 (3) 280 470 (3) 315 445 (3) NS630/MA (3) 500 6000 LC1-F500 LR9-F7379 300500 NS630/MA (3) 500 6500 LC1-F500 LR9-F7381 380630 355 500 (3) (1) Irm: magnetic trip setting current. (2) For reversing operation, replace the reference prefix LC1 by LC2. (3) Products marketed under the Merlin Gerin brand. Reference to be completed by replacing the (/) with the breaking performance code Breaking performance Iq (kA) NS100/MA NS160/MA and NS250/MA NS400/MA and NS630/MA 400/415 V 25 70 36 70 70 130 440 V 25 65 35 65 65 130 500 V 18 50 30 50 50 70 660/690 V 8 10 8 10 20 35 Code N H N H H L

24540_Ver2.10-EN.fm/2

Schneider Electric

Combinations for assembly TeSys motor starters - open by the customer version
D.O.L. starters with circuit-breaker and overload protection by separate thermal overload relay

0.06 to 250 kW at 400/415 V: type 2 coordination


Standard power ratings of 3-phase motors 50/60 Hz in category AC-3 Circuit-breaker Contactor Thermal overload relay Reference Reference Setting 400/415 V 440 V 500 V Reference Rating Irm P Ie Iq P Ie Iq P Ie Iq (1) (2) range kW A kA kW A kA kW A kA A A A GV2-L03 or LE03 0.4 5 LC1-D09 LRD-02 0.160.25 0.06 0.22 130 0.06 0.19 130 0.09 0.36 130 0.09 0.28 130 GV2-L03 or LE03 0.4 5 LC1-D09 LRD-03 0.250.40 0.12 0.37 130 0.12 0.42 130 0.12 0.37 130 GV2-L04 or LE04 0.63 8 LC1-D09 LRD-04 0.40.63 0.18 0.6 130 0.18 0.55 130 0.25 0.88 130 0.25 0.76 130 GV2-L05 or LE05 1 13 LC1-D09 LRD-05 0.631 0.37 0.98 130 0.37 0.99 130 GV2-L05 or LE05 1 13 LC1-D09 LRD-06 11.7 0.37 0.99 130 0.37 1 130 0.55 1.6 130 0.55 1.21 130 GV2-L06 or LE06 1.6 22.5 LC1-D09 LRD-06 11.7 0.55 1.36 130 0.75 1.5 130 0.75 2 130 0.75 1.68 130 1.1 2 130 GV2-L07 or LE07 2.5 33.5 LC1-D09 LRD-07 1.62.5 1.1 2.5 130 1.1 2.37 130 1.5 2.6 130 GV2-L08 or LE08 4 51 LC1-D09 LRD-08 2.54 1.5 3.5 130 2.2 3.8 130 GV2-L08 or LE08 4 51 LC1-D09 LRD-10 46 1.5 3.06 130 2.2 5 130 GV2-L10 or LE10 6.3 78 LC1-D09 LRD-10 46 3 5 13 2.2 4.42 50 GV2-LE10 6.3 78 LC1-D09 LRD-10 46 3 5.77 50 3 5 50 2.2 4.42 130 GV2-L10 6.3 78 LC1-D09 LRD-10 46 3 5.77 130 3 5 130 3 6.5 130 GV2-L14 or LE14 10 138 LC1-D09 LRD-12 5.58 GV2-LE14 10 138 LC1-D12 LRD-12 5.58 4 6.5 10 4 6.5 50 GV2-L14 10 138 LC1-D12 LRD-12 5.58 GV2-L14 or LE14 10 138 LC1-D09 LRD-14 710 4 8.4 130 4 7.9 15 GV2-LE14 10 138 LC1-D09 LRD-14 710 GV2-L14 10 138 LC1-D09 LRD-14 710 4 7.9 130 5.5 9 10 GV2-LE14 10 138 LC1-D09 LRD-14 710 GV2-L14 10 138 LC1-D09 LRD-14 710 5.5 9 50 5.5 11 130 5.5 10.4 50 7.5 12 42 GV2-L16 14 170 LC1-D25 LRD-16 913 GV2-L16 14 170 LC1-D25 LRD-21 1218 7.5 13.7 50 7.5 14.8 50 9 16.9 20 9 13.9 42 GV2-L20 18 223 LC1-D25 LRD-21 1218 9 18.1 50 GV2-L22 25 327 LC1-D25 LRD-22 1624 11 21 50 11 20.1 20 11 18.4 10 GV2-L22 25 327 LC1-D32 LRD-22 1624 15 23 10 GV2-L32 32 416 LC1-D40 LRD-3353 2332 15 28.5 50 15 26.5 20 18.5 28.5 10 22 33 25 NS80HMA 50 450 LC1-D40 LRD-3353 2332 NS80HMA 50 550 LC1-D40 LRD-3355 3040 18.5 35 70 18.5 32.5 65 22 42 70 22 39 65 30 45 25 NS80HMA 50 650 LC1-D50 LRD-3357 3750 30 51.5 65 NS80HMA 80 880 LC1-D65 LRD-3359 4865 30 57 70 37 64 65 37 55 25 NS100/MA (3) 100 880 LC1-D80 LRD-3359 4865 37 55 (3) 45 65 (3) NS100/MA (3) 100 960 LC1-D80 LRD-3361 5570 37 69 70 45 76 65 NS80HMA 80 1000 LC1-D80 LRD-3363 6380 NS100/MA (3) 100 1040 LC1-D80 LRD-3363 6380 55 80 (3) 45 81 (3) 55 90 (3) NS100/MA (3) 100 1300 LC1-D115 LR9-D5367 60100 NS160/MA (3) 150 1500 LC1-D115 LR9-D5369 90150 55 100 (3) 75 105 (3) NS160/MA (3) 150 1050 LC1-D115 LR9-D5369 90150 NS160/MA (3) 150 1950 LC1-D150 LR9-D5369 90150 75 135 (3) 75 125 (3) 90 146 (3) NS160/MA (3) 150 1950 LC1-D150 LR9-D5369 90150 NS160/MA (3) 150 1200 LC1-D150 LR9-D5369 90150 90 129 (3) 90 165 (3) 110 178 (3) NS250/MA (3) 220 2420 LC1-F185 LR9-F5371 132220 NS250/MA (3) 220 1540 LC1-F185 LR9-F5371 132220 110 156 (3) 110 200 (3) NS250/MA (3) 220 2860 LC1-F225 LR9-F5371 132220 NS250/MA (3) 220 2200 LC1-F265 LR9-F5371 132220 132 215 (3) 132 187 (3) 132 240 (3) 160 256 (3) NS400/MA (3) 320 3520 LC1-F265 LR9-F7375 200330 NS400/MA (3) 320 2200 LC1-F265 LR9-F7375 200330 160 220 (3) 160 285 (3) NS400/MA (3) 320 4000 LC1-F330 LR9-F7375 200330 NS400/MA (3) 320 4000 LC1-F330 LR9-F7379 300500 200 321 (3) 200 281 (3) NS400/MA (3) 320 3500 LC1-F400 LR9-F7375 200330 NS400/MA (3) 320 3500 LC1-F400 LR9-F7379 300500 220 310 (3) 220 353 (3) NS630/MA (3) 500 5500 LC1-F400 LR9-F7379 300500 200 352 (3) 250 401 (3) 250 360 (3) NS630/MA (3) 500 4500 LC1-F500 LR9-F7379 300500 315 445 (3) 220 388 (3) NS630/MA (3) 500 6250 LC1-F500 LR9-F7379 300500 250 437 (3) 355 500 (3) NS630/MA (3) 500 5000 LC1-F630 LR9-F7381 380630 (1) Irm: magnetic trip setting current. (2) For reversing operation, replace the reference prefix LC1 by LC2. (3) Products marketed under the Merlin Gerin brand. Reference to be completed by replacing the (/) with the breaking performance code: see page opposite.

Schneider Electric

24540_Ver2.10-EN.fm/3

Combinations for assembly TeSys motor starters - open by the customer version

D.O.L. starters with integral 18, 32 and 63 contactor breakers with overload protection by separate module

0.06 to 4 kW at 400/415 V (total coordination)


Standard power ratings of 3-phase motors 50/60 Hz in category AC-3 400/415 V 440 V P Ie Iq P Ie Iq kW A kA kW A kA 0.06 0.22 70 0.06 0.19 70 500 V P Ie kW A Contactor breaker Without control test function Reference LD1-LB030 With control test function Reference Protection module Reference Setting range Thermal Magnetic (2) (3) A A LB1-LB03P02 0.160.25 3.8

Iq kA

0.09 0.36 70

0.09 0.28 70

LD1-LB030 or LD1-LC030 LD1-LB030 or LD1-LC030 LD1-LB030 or LD1-LC030 LD1-LB030 or LD1-LC030 LD1-LB030 or LD1-LC030 LD1-LB030 or LD1-LC030 LD1-LB030 or LD1-LC030 LD1-LB030 or LD1-LC030 LD1-LB030 or LD1-LC030 LD1-LB030 or LD1-LC030 LD1-LB030 or LD1-LC030 LD1-LB030 or LD1-LC030 LD1-LB030 or LD1-LC030 LD1-LB030 or LD1-LC030 LD1-LB030 or LD1-LC030

LD4-LC130

LB1-LB03P03 LB1-LC03M03 LB1-LB03P03 LB1-LC03M03 LB1-LB03P04 LB1-LC03M04 LB1-LB03P04 LB1-LC03M04 LB1-LB03P05 LB1-LC03M05 LB1-LB03P06 LB1-LC03M06 LB1-LB03P06 LB1-LC03M06 LB1-LB03P07 LB1-LC03M07 LB1-LB03P07 LB1-LC03M07 LB1-LB03P08 LB1-LC03M08 LB1-LB03P08 LB1-LC03M08 LB1-LB03P10 LB1-LC03M10 LB1-LB03P10 LB1-LC03M10 LB1-LB03P13 LB1-LC03M13 LB1-LB03P13 LB1-LC03M13

0.250.4 0.250.4 0.250.4 0.250.4 0.40.63 0.40.63 0.40.63 0.40.63 0.631 0.631 11.6 11.6 11.6 11.6 1.62.5 1.62.5 1.62.5 1.62.5 2.54 2.54 2.54 2.54 46 46.3 46 46.3 610 6.310 610 6.310

6 2.44.8 6 2.44.8 9.5 3.87.6 9.5 3.87.6 15 612 24 9.519 24 9.519 37.5 1530 37.5 1530 60 2448 60 2448 90 3876 90 3876 150 60120 150 60120

0.12 0.37 70

LD4-LC130

0.12 0.42 70

0.18 0.55 70

LD4-LC130

0.18 0.6

70

LD4-LC130

0.25 0.88 70

0.25 0.76 70

0.37 1

70

LD4-LC130

0.37 1

70

0.37 1

70

0.55 1.21 70

LD4-LC130

0.55 1.5

70

0.55 1.36 70

0.75 1.5

70

LD4-LC130

0.75 2

70

0.75 1.68 70

1.1

70

LD4-LC130

1.1

2.37 70

LD4-LC130

1.1

2.5

70

1.5

2.6

70

LD4-LC130

1.5

3.5

70

1.5

3.06 70

2.2

3.8

70

LD4-LC130

2.2

70

2.2

4.42 (1)

15

LD4-LC130

5.77 (1)

LD4-LC130

6.5

70

7.9

(1)

6.5

15

LD4-LC130

8.4

70

5.5

15

LD4-LC130

(1) Iq = 40 kA for LD1-LB; Iq = 70 kA for LD/-LC. (2) Irth min to Irth max. (3) For LB1-LB, the magnetic protection is fixed, set at 15 Irth max. For LB1-LC, the magnetic protection is adjustable from 6 to 12 Irth max.

24570_Ver2.10-EN.fm/2

Schneider Electric

Combinations for assembly TeSys motor starters - open by the customer version

D.O.L. starters with integral 18, 32 and 63 contactor breakers with overload protection by separate module

5.5 to 30 kW at 400/415 V (total coordination)


Standard power ratings of 3-phase motors 50/60 Hz in category AC-3 400/415 V 440 V P Ie Iq P Ie Iq kW A kA kW A kA 5.5 11 70 5.5 10.4 (1) 500 V P Ie kW A 7.5 12 Contactor breaker Without control test function Reference LD1-LB030 or LD1-LC030 LD1-LB030 or LD1-LC030 LD1-LB030 or LD1-LC030 LD1-LB030 or LD1-LC030 LD1-LC030 With control test function Reference Protection module Reference Setting range Thermal Magnetic (3) (4) A A LB1-LB03P17 LB1-LC03M17 LB1-LB03P17 LB1-LC03M17 LB1-LB03P21 LB1-LC03M17 LB1-LB03P21 LB1-LC03M22 LB1-LC03M22 1016 1016 1016 1016 1218 1016 1218 1625 1625 240 95190 240 95190 270 95190 270 150300 150300

Iq kA (2)

LD4-LC130

7.5

14.8 70

7.5

13.7 (1)

LD4-LC130

13.9 (2)

LD4-LC130

18.1 70

16.9 (1)

LD4-LC130 LD4-LC130

11

21

70

11

20.1 70

11

18.4 20

15

23

20

LD1-LC030

LD4-LC130

LB1-LC03M22

1625

150300

15

28.5 70

15

26.5 30

18.5 28.5 15

LD1-LC030

LD4-LC130

LB1-LC03M53

2332

190380

18.5 35

70

18.5 32.8 70

22

33

35

LD1-LD030

LD4-LD130

LB1-LD03M55

2840

240480

22

39

70

LD1-LD030

LD4-LD130

LB1-LD03M55

2840

240480

22

42

70

30

45

35

LD1-LD030

LD4-LD130

LB1-LD03M57

3550

300600

30

57

70

30

51.5 40

37

55

35

LD1-LD030

LD4-LD130

LB1-LD03M61

4563

380760

33

58.5 40

LD1-LD030

LD4-LD130

LB1-LD03M61

4563

380760

(1) Iq = 40 kA for LD1-LB ; Iq = 70 kA for LD/-LC. (2) Iq = 10 kA for LD1-LB ; Iq = 25 kA for LD/-LC. (3) Irth min to Irth max. (4) For LB1-LB, the magnetic protection is fixed, set at 15 Irth max. For LB1-LC and LB1-LD, the magnetic protection is adjustable from 6 to 12 Irth max.

Schneider Electric

24570_Ver2.10-EN.fm/3

Combinations for assembly TeSys motor starters - open by the customer version
D.O.L. starters with fuse protection (NF C or DIN fuses)

0.06 to 55 kW at 400/415 V: type 1 coordination


Standard power ratings of 3-phase motors 50/60 Hz in category AC-3 400/415 V 440 V P Ie P Ie kW A kW A 0.06 0.09 0.12 0.18 0.25 0.37 0.55 0.75 1.1 1.5 2.2 3 4 5.5 7.5 9 11 15 18.5 22 30 37 (3) 45 0.22 0.36 0.42 0.6 0.88 1 1.5 2 2.5 3.5 5 6.5 8.4 11 14.8 18.1 21 28.5 35 42 57 69 81 0.06 0.09 0.12 0.18 0.25 0.37 0.55 0.75 1.1 1.5 2.2 3 4 5.5 7.5 9 11 15 18.5 22 30 37 45 55 0.19 0.28 0.37 0.55 0.76 1 1.36 1.68 2.37 3.06 4.42 5.77 7.9 10.4 13.7 16.9 20.1 26.5 32.8 39 51.5 64 76 90 500 V P kW 0.37 0.55 0.75 1.1 1.5 2.2 3 4 5.5 7.5 9 11 15 18.5 22 30 37 45 55 Fuse carrier (1) (basic block) Reference Ie A 1 1.21 1.5 2 2.6 3.8 5 6.5 9 12 13.9 18.4 23 28.5 33 45 55 65 80 LS1-D32 LS1-D32 LS1-D32 LS1-D32 LS1-D32 LS1-D32 LS1-D32 LS1-D32 LS1-D32 LS1-D32 LS1-D32 LS1-D32 LS1-D32 LS1-D32 LS1-D32 GK1-EK GK1-EK GK1-EK GK1-FK GK1-FK GK1-FK GK1-FK GK1-FK GK1-FK GK1-FK GK1-FK 10 x 38 10 x 38 10 x 38 10 x 38 10 x 38 10 x 38 10 x 38 10 x 38 10 x 38 10 x 38 10 x 38 10 x 38 10 x 38 10 x 38 10 x 38 14 x 51 14 x 51 14 x 51 22 x 58 22 x 58 22 x 58 22 x 58 22 x 58 22 x 58 22 x 58 22 x 58 22 x 58 aM fuses Size Rating A 2 2 2 2 2 2 4 4 6 8 8 12 16 16 20 25 32 40 50 80 80 80 80 100 100 125 125 LC1-K06 LC1-K06 LC1-K06 LC1-K06 LC1-K06 LC1-K06 LC1-K06 LC1-K06 LC1-K06 LC1-K06 LC1-K09 LC1-K09 LC1-K12 LC1-D18 LC1-D25 LC1-D25 LC1-D32 LC1-D40 LC1-D50 LC1-D50 LC1-D65 LC1-D65 LC1-D80 LC1-D80 LC1-D95 LC1-D115 LC1-D115 LR2-K0302 LR2-K0303 LR2-K0304 LR2-K0305 LR2-K0306 LR2-K0307 LR2-K0308 LR2-K0310 LR2-K0312 LR2-K0312 LR2-K0314 LR2-K0316 LR2-K0321 LRD-21 LRD-21 LRD-22 LRD-32 LRD-3355 LRD-3357 LRD-3359 LRD-3359 LRD-3361 LRD-3361 LRD-3363 LRD-3365 LRD-4365 LRD-4367 Contactor Reference (2) Thermal overload relay Reference Setting range A 0.160.23 0.230.36 0.360.54 0.540.8 0.81.2 1.21.8 1.82.6 2.63.7 3.75.5 3.75.5 5.58 811.5 1014 1218 1218 1624 2332 3040 3750 4865 4865 5570 5570 6380 8093 80104 95120

55 100 75 105 GK1-FK (1) For breaking under load, add a rotary switch disconnector. (2) For reversing operation, replace the reference prefix LC1 by LC2. (3) 400 V maximum.

24541_Ver3.11-EN.fm/2

Schneider Electric

Combinations for assembly TeSys motor starters - open by the customer version
D.O.L. starters with fuse protection (NF C or DIN fuses)

0.06 to 315 kW at 400/415 V: type 2 coordination


Standard power ratings of 3-phase motors 50/60 Hz in category AC-3 400/415 V 440 V P Ie P Ie kW A kW A 0.06 0.09 0.12 0.18 0.25 0.37 0.55 0.75 1.1 1.5 2.2 3 4 5.5 7.5 9 11 15 18.5 22 30 37 45 55 75 90 110 132 160 200 220 250 315 0.22 0.36 0.42 0.6 0.88 1 1.5 2 2.5 3.5 5 6.5 8.4 11 14.8 18.1 21 28.5 35 42 57 69 81 100 135 165 200 240 285 352 388 437 555 0.06 0.09 0.12 0.18 0.25 0.37 0.55 0.75 1.1 1.5 2.2 3 4 5.5 7.5 9 11 15 18.5 22 30 37 45 55 75 90 110 132 160 200 220 250 315 0.19 0.28 0.37 0.55 0.76 1 1.36 1.68 2.37 3.06 4.42 5.77 7.9 10.4 13.7 16.9 20.1 26.5 32.8 39 51.5 64 76 90 125 146 178 215 256 321 353 401 505 Switch-disconnectorfuse 500 V P kW 0.37 0.55 0.75 1.1 1.5 2.2 3 4 5.5 7.5 9 11 15 18.5 22 30 37 45 55 75 90 110 132 160 200 220 250 315 355 Ie A 1 1.21 1.5 2 2.6 3.8 5 6.5 9 12 13.9 18.4 23 28.5 33 45 55 65 80 105 129 156 187 220 281 310 360 445 500 Reference A GS1-DD GS1-DD GS1-DD GS1-DD GS1-DD GS1-DD GS1-DD GS1-DD GS1-DD GS1-DD GS1-DD GS1-DD GS1-F GS1-F GS1-F GS1-F GS1-J GS1-J GS1-J GS1-J GS1-J GS1-J GS1-J GS1-J GS1-L GS1-L GS1-N GS1-N GS1-QQ GS1-QQ GS1-QQ GS1-QQ GS1-S GS1-S GS1-S GS1-S 10 x 38 10 x 38 10 x 38 10 x 38 10 x 38 10 x 38 10 x 38 10 x 38 10 x 38 10 x 38 10 x 38 10 x 38 14 x 51 14 x 51 14 x 51 14 x 51 22 x 58 22 x 58 22 x 58 22 x 58 22 x 58 22 x 58 22 x 58 22 x 58 22 x 58 T0 T0 T1 T2 T2 T2 T2 T3 T3 T3 T3 T4 2 2 2 2 2 4 4 6 8 10 16 16 20 25 32 40 50 80 80 80 80 100 100 100 125 160 200 250 315 315 400 400 500 500 630 630 800 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D12 LC1-D18 LC1-D25 LC1-D25 LC1-D32 LC1-D40 LC1-D50 LC1-D50 LC1-D65 LC1-D65 LC1-D95 LC1-D80 LC1-D115 LC1-D95 LC1-D150 LC1-D150 LC1-F185 LC1-F225 LC1-F265 LC1-F330 LC1-F330 LC1-F400 LC1-F400 LC1-F500 LC1-F500 LC1-F630 LC1-F630 LRD-02 LRD-03 LRD-04 LRD-05 LRD-06 LRD-07 LRD-08 LRD-10 LRD-12 LRD-14 LRD-16 LRD-21 LRD-21 LRD-22 LRD-32 LRD-3355 LRD-3357 LRD-3359 LRD-3359 LRD-3361 LRD-3361 LRD-3363 LR9-D5367 LRD-3365 LR9-D5369 LR9-D5369 LR9-F5371 LR9-F5371 LR9-F7375 LR9-F7375 LR9-F7375 LR9-F7375 LR9-F7379 LR9-F7379 LR9-F7381 LR9-F7381 LR9-F7381 aM fuses Size Rating Contactor Reference (1) Thermal overload relay Reference Setting range A 0.160.25 0.250.4 0.40.63 0.631 11.7 1.62.5 2.54 46 5.58 710 913 1218 1218 1624 2332 3040 3750 4865 4865 5570 5570 6380 60100 8093 90150 90150 132220 132220 200330 200330 200330 200330 300500 300500 380630 380630 380630

355 549 400 611 400 540 GS1-V (1) For reversing operation, replace the reference prefix LC1 by LC2.

Schneider Electric

24541_Ver3.11-EN.fm/3

Combinations for assembly TeSys motor starters - open by the customer version
Star-delta starters with circuit-breaker and overload protection built into the circuit-breaker

1.5 to 110 kW at 400/415 V: type 1 coordination


Maximum operating rate: LC3-K: 12 starts/hour; LC3-D: 30 starts/hour. Maximum starting time: 30 seconds. Standard power ratings of 3-phase motors 50/60 Hz in category AC-3 400/415 V P Ie IrD (1) Iq (2) kW A A kA 1.5 2.2 3 4 5.5 7.5 9 11 15 18.5 22 30 30 37 37 45 55 75 90 110 3.5 5 6.5 8.4 11 14.8 18.1 21 28.5 35 42 57 57 69 69 81 100 135 165 200 2 2.9 3.8 4.9 6.4 8.6 10 12 17 20 24 33 33 40 40 47 58 78 95 115 50 50 50 50 15 15 15 15 10 35 35 35 25 15 25 25 25 35 35 35 Circuit-breaker Reference 440 V P kW 1.5 2.2 3 4 5.5 7.5 9 11 15 18.5 22 30 30 37 37 45 45 55 75 90 110 Ie A 3.06 4.42 5.77 7.9 10.4 13.7 16.9 20.1 26.5 32.8 39 51.5 51.5 64 64 76 76 90 125 146 178 IrD (1) Iq (2) A kA 1.8 2.6 3.3 4.6 6 7.9 9.8 12 15 19 23 30 30 37 37 44 44 52 72 84 103 50 50 50 15 8 8 8 6 6 25 25 10 25 10 25 10 25 25 35 35 35 GV2-ME08 GV2-ME10 GV2-ME14 GV2-ME16 GV2-ME20 GV2-ME20 GV2-ME21 GV2-ME22 GV2-ME32 GV3-ME40 GV3-ME40 GV3-ME63 GV7-RE80 GV3-ME63 GV7-RE80 GV3-ME80 GV7-RE80 GV3-ME80 GV7-RE80 GV7-RE100 GV7-RE150 GV7-RE150 GV7-RE220 Star-delta contactors Reference

Setting range of thermal trips A 2.54 46.3 610 914 1318 1318 1723 2025 2432 2540 2540 4063 4880 4063 4880 5680 4880 5680 4880 60100 90150 90150 132220

LC3-K06 LC3-K06 LC3-K06 LC3-K06 LC3-K09 LC3-D12A LC3-D12A LC3-D12A LC3-D18A LC3-D18A LC3-D18A LC3-D32A LC3-D32A LC3-D32A LC3-D32A LC3-D40 LC3-D40 LC3-D50 LC3-D50 LC3-D50 LC3-D80 LC3-D115 LC3-D115

132 215 124 35 GV7-RE220 132220 LC3-D150 (1) IrD: current in the motor windings in delta connection. (2) The breaking performance of motor circuit breakers GV2-ME can be increased by adding a current limiter, GV1-L3, see page 24509/5.

24542_Ver2.10-EN.fm/2

Schneider Electric

Combinations for assembly TeSys motor starters - open by the customer version
Star-delta starters with circuit-breaker and overload protection built into the circuit-breaker

1.5 to 110 kW at 400/415 V: type 2 coordination


Maximum operating rate: LC1-D: 30 starts/hour; LC1-F: 12 starts/hour. Maximum starting time: LC1-D: 30 seconds; LC1-F: 20 seconds. Standard power ratings of 3-phase motors 50/60 Hz in category AC-3 400/415 V P Ie Iq kW A kA 1.5 2.2 3 4 5.5 7.5 9 11 15 18.5 22 30 37 45 55 75 90 3.5 5 6.5 8.4 11 14.8 18.1 21 28.5 35 42 57 69 81 100 135 165 130 130 130 130 130 50 50 50 70 70 70 70 70 70 70 70 70 Circuit-breaker Reference 440 V P kW 1.5 2.2 3 4 5.5 7.5 9 11 15 18.5 22 30 37 45 55 75 90 110 Ie A 3.06 4.42 5.77 7.9 10.4 13.7 16.9 20.1 26.5 32.8 39 51.5 64 76 90 125 146 178 Iq (1) kA 130 130 130 130 50 50 20 20 65 65 65 65 65 65 65 65 65 65 GV2-P08 GV2-P10 GV2-P10 GV2-P14 GV2-P14 GV2-P16 GV2-P16 GV2-P20 GV2-P21 GV2-P22 GV7-RS40 GV7-RS40 GV7-RS40 GV7-RS50 GV7-RS80 GV7-RS80 GV7-RS80 GV7-RS100 GV7-RS100 GV7-RS150 GV7-RS150 GV7-RS220 Star-delta contactors Reference

Setting range of thermal trips A 2.54 46.3 4...6.3 610 610 914 914 1318 1723 2025 2540 2540 2540 3050 4880 4880 4880 60100 60100 90150 90150 132220

3 x LC1-D09 3 x LC1-D18 3 x LC1-D18 3 x LC1-D18 3 x LC1-D18 3 x LC1-D25 3 x LC1-D25 3 x LC1-D25 3 x LC1-D25 3 x LC1-D25 3 x LC1-D80 3 x LC1-D80 3 x LC1-D80 3 x LC1-D80 3 x LC1-D80 3 x LC1-D80 3 x LC1-D80 3 x LC1-D115 3 x LC1-D115 3 x LC1-D150 3 x LC1-D150 3 x LC1-F185

110 200 70 132 215 65 GV7-RS220 132220 3 x LC1-F225 (1) The breaking performance of motor circuit breakers GV2-P can be increased by adding a current limiter GV1-L3, see page 24509/5.

Schneider Electric

24542_Ver2.10-EN.fm/3

Combinations for assembly TeSys motor starters - open by the customer version
Star-delta starters with circuit-breaker and overload protection by separate thermal overload relay

1.5 to 315 kW at 400/415 V: type 1 coordination


Maximum operating rate: LC3-K and LC3-F: 12 starts/hour; LC3-D: 30 starts/hour. Maximum starting time: LC3-K and LC3-D: 30 seconds; LC3-F: 20 seconds. Standard power ratings of 3-phase motors 50/60 Hz in category AC-3 440 V 400/415 V P Ie IrD(1) Iq P kW A A kA kW 1.5 1.5 3.5 2 50 2.2 2.2 5 3 50 3 3 6.5 4 50 4 4 8.4 5 50 5.5 5.5 11 6 15 7.5 7.5 14.8 9 15 9 9 18.1 10 15 11 11 21 12 15 15 15 28.5 16 10 18.5 22 30 37 45 55 75 90 110 132 160 200 220 280 35 42 57 69 81 100 135 165 200 240 285 352 388 480 20 24 33 40 47 58 78 96 116 139 165 204 225 278 70 70 70 70 (3) (3) (3) (3) (3) (3) (3) (3) (3) (3) 18.5 22 30 37 45 55 75 90 110 132 160 200 220 250 Circuit-breaker Reference Ie A 3.06 4.42 5.77 7.9 10.4 13.7 16.9 20.1 26.5 32.8 39 51.5 64 76 90 125 146 178 215 256 321 353 401 IrD(1) A 1.8 3 3 5 6 8 10 12 15 19 23 30 37 44 52 72 85 103 125 148 186 204 233 Iq kA 50 50 50 50 15 8 8 8 6 65 65 65 65 65 65 (3) (3) (3) (3) (3) (3) (3) (3) Star-delta contactors Reference Thermal overload relay Reference Setting range A LC3-K06 LC3-K06 LC3-K06 LC3-K06 LC3-K06 LC3-K06 LC3-K06 LC3-K09 LC3-K09 LC3-D12A LC3-K12 LC3-K12 LC3-K12 LC3-D18A LC3-D18A LC3-D18A LC3-D18A LC3-D32A LC3-D32A LC3-D32A LC3-D40 LC3-D40 LC3-D50 LC3-D40 LC3-D80 LC3-D50 LC3-D50 LC3-D80 LC3-D115 LC3-D115 LC3-D150 LC3-D115 LC3-D150 LC3-F225 LC3-D150 LC3-F185 LC3-F225 LC3-F265 LC3-F330 LR2-K0308 LR2-K0310 LR2-K0312 LR2-K0312 LR2-K0312 LR2-K0314 LR2-K0314 LR2-K0316 LR2-K0316 LRD-16 LR2-K0316 LR2-K0321 LR2-K0321 LRD-21 LRD-21 LRD-22 LRD-22 LRD-32 LRD-32 LRD-35 LRD-3355 LRD-3357 LRD-3359 LRD-3359 LRD-3363 LRD-3357 LRD-3361 LRD-3363 LRD-4365 LRD-4365 LRD-4369 LRD-4369 LR9-D5369 LR9-F5371 LRD-4369 LR9-F5371 LR9-F5371 LR9-F7375 LR9-F7375 1.82.6 2.63.7 3.75.5 3.75.5 3.75.5 5.58 5.58 811.5 811.5 811.5 811.5 1014 1014 1218 1218 1624 1624 2332 2332 3038 3040 3750 4865 4865 6380 3750 5570 6380 80104 80104 110140 110140 90150 132220 110140 132220 132220 200330 200330 200330 200330 300500

Rating A

Irm (2) A 51 78 138 78 138 138 170 170 223 170 327 223 327 327 384 350 400 400 560 560 560 640 800 640 1200 800 1200 1200 1200 1760 1760 1760 2240 3150 2240 2560 3150 3500 4000

GV2-LE08 GV2-LE10 GV2-LE14 GV2-LE10 GV2-LE14 GV2-LE14 GV2-LE16 GV2-LE16 GV2-LE20 GV2-LE16 GV2-LE22 GV2-LE20 GV2-LE22 GV2-LE22 GV2-LE32 NS80HMA NS80HMA NS80HMA NS80HMA NS80HMA NS80HMA NS80HMA NS80HMA NS80HMA NS160/MA (3) NS100/MA (3) NS100/MA (3) NS160/MA (3) NS160/MA (3) NS250/MA (3) NS250/MA (3) NS250/MA (3) NS400/MA (3) NS630/MA (3) NS400/MA (3) NS400/MA (3) NS630/MA (3) NS630/MA (3) NS630/MA (3)

4 6.3 10 6.3 10 10 14 14 18 14 25 18 25 25 32 50 50 50 80 80 80 80 80 80 150 100 100 150 150 220 220 220 320 500 320 320 500 500 500

C801/+STR35ME 800 4000 LC3-F330 LR9-F7375 315 505 295 (3) 315 555 322 (3) 355 518 300 (3) C801/+STR35ME 800 4500 LC3-F330 LR9-F7375 C801/+STR35ME 800 5000 LC3-F400 LR9-F7379 375 575 334 (3) (1) IrD: current in the motor windings in delta connection. (2) Irm: magnetic trip setting current. (3) Products marketed under the Merlin Gerin brand. Reference to be completed by replacing the (/) with the breaking performance code NS100/MA NS160/MA NS400/MA C801/ Breaking performance Iq (kA) NS250/MA NS630/MA +STR35ME 400/415 V 25 70 36 70 70 130 70 150 440 V 25 65 35 65 65 130 65 100 Code E S E S H L H L

24543_Ver2.11-EN.fm/2

Schneider Electric

Combinations for assembly TeSys motor starters - open by the customer version
Star-delta starters with circuit-breaker and overload protection by separate thermal overload relay

1.5 to 250 kW at 400/415 V: type 2 coordination


Maximum operating rate: LC3-D: 30 starts/hour; LC3-F: 12 starts/hour. Maximum starting time: LC3-D: 30 seconds; LC3-F: 20 seconds. Standard power ratings of 3-phase motors 50/60 Hz in category AC-3 400/415 V 440 V P Ie Iq P kW A kA kW 1.5 2.2 3 4 5.5 7.5 9 11 15 18.5 22 30 37 45 55 75 90 110 132 160 3.5 5 6.5 8.4 11 14.8 18.1 21 28.5 35 42 57 69 81 100 135 165 200 240 285 130 130 130 130 50 50 50 50 70 70 70 70 70 (2) (2) (2) (2) (2) (2) (2) 1.5 2.2 3 4 5.5 7.5 9 11 15 18.5 22 30 37 45 55 75 90 110 132 160 200 Circuit-breaker Reference Ie A 3.06 4.42 5.77 7.9 10.4 13.7 16.9 20.1 26.5 32.8 39 51.5 64 76 90 125 146 178 215 256 321 Iq kA 130 130 130 20 20 20 20 20 65 65 65 65 65 65 (2) (2) (2) (2) (2) (2) (2) GV2-L08 GV2-L10 GV2-L14 GV2-L14 GV2-L16 GV2-L20 GV2-L22 GV2-L22 NS80HMA NS80HMA NS80HMA NS80HMA NS80HMA NS100/MA (2) NS160/MA (2) NS160/MA (2) NS160/MA (2) NS250/MA (2) NS250/MA (2) NS250/MA (2) NS400/MA (2) NS400/MA (2) NS400/MA (2) Star-delta contactors Reference Thermal overload relays Reference Setting range A 3 x LC1-D18 3 x LC1-D18 3 x LC1-D18 3 x LC1-D18 3 x LC1-D25 3 x LC1-D25 3 x LC1-D25 3 x LC1-D25 3 x LC1-D40 3 x LC1-D50 3 x LC1-D50 3 x LC1-D65 3 x LC1-D80 3 x LC1-D115 3 x LC1-D115 3 x LC1-D150 3 x LC1-D150 3 x LC1-F185 3 x LC1-F225 3 x LC1-F225 3 x LC1-F265 3 x LC1-F330 3 x LC1-F330 LRD-08 LRD-10 LRD-14 LRD-16 LRD-16 LRD-21 LRD-21 LRD-22 LRD-3353 LRD-3355 LRD-3357 LRD-3359 LRD-3363 LR9-D5367 LR9-D5369 LR9-D5369 LR9-D5369 LR9-F5371 LR9-F5371 LR9-F7375 LR9-F7375 LR9-F7375 LR9-F7379 2.54 46 710 913 913 1218 1218 1624 2332 3040 3750 4865 6380 60100 90150 90150 90150 132220 132220 200330 200330 200330 300500 300500 300500 300500

Rating A 4 6.3 10 10 14 18 25 25 50 50 50 80 80 100 150 150 150 220 220 220 320 320 320

Irm (1) A 51 78 138 138 170 223 327 327 300 350 400 560 640 800 1200 1200 1200 1760 1760 1760 2240 2560 2880

NS630/MA (2) 500 3150 3 x LC1-F400 LR9-F7379 200 352 (2) 220 353 (2) NS630/MA (2) 500 3500 3 x LC1-F400 LR9-F7379 220 388 (2) 250 401 (2) 250 437 (2) NS630/MA (2) 500 4000 3 x LC1-F500 LR9-F7379 (1) Irm: magnetic trip setting current. (2) Products marketed under the Merlin Gerin brand. Reference to be completed by replacing the (/) with the breaking performance code Breaking NS100/MA NS160/MA NS400/MA performance Iq (kA) NS250/MA NS630/MA 400/415 V 25 70 36 70 70 130 440 V 25 65 35 65 65 130 Code E S E S H L

Schneider Electric

24543_Ver2.11-EN.fm/3

Combinations for assembly TeSys motor starters - open by the customer version
Star-delta starters with fuse protection (NF C or DIN fuses)

1.5 to 315 kW at 400/415 V: type 1 coordination


Maximum operating rate: LC3-K and LC3-F: 12 starts/hour; LC3-D: 30 starts/hour. Maximum starting time: LC3-K and LC3-D: 30 seconds; LC3-F: 20 seconds. Standard power ratings of 3-phase motors 50/60 Hz in category AC-3 400/415 V P Ie IrD Iq (1) kW A A kA 1.5 2.2 3 4 5.5 7.5 9 11 15 18.5 22 30 37 45 55 75 90 110 132 160 220 3.5 5 6.5 8.4 11 14.8 18.1 21 28.5 35 42 57 69 81 100 135 165 200 240 285 388 2 3 4 5 6 9 10 12 16 20 24 33 40 47 58 78 95 115 139 165 225 50 50 50 50 50 50 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 Fuse carrier (basic block) Reference Ie A 3.06 4.42 5.77 7.9 10.4 13.7 16.9 20.1 26.5 32.8 39 51.5 64 76 90 125 146 178 215 256 321 IrD (1) A 2 3 3 5 6 8 10 12 15 19 23 30 37 44 52 72 84 103 124 148 185 Iq kA 50 50 50 50 50 50 50 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 LS1-D32 LS1-D32 LS1-D32 LS1-D32 LS1-D32 LS1-D32 LS1-D32 LS1-D32 GK1-EK GK1-EK GK1-EK GK1-FK GK1-FK GK1-FK GK1-FK GK1-FK GK1-FK GK1-FK GS1-K GS1-K GS1-L GS1-L GS1-N GS1-N GS1-QQ GS1-QQ GS1-QQ GS1-QQ GS1-S GS1-S GS1-S GS1-S A 10 x 38 4 10 x 38 6 10 x 38 10 x 38 10 x 38 10 x 38 10 x 38 10 x 38 8 8 12 16 16 20 LC3-K06 LC3-K06 LC3-K06 LC3-K06 LC3-K06 LC3-K06 LC3-K09 LC3-D12A LC3-D12A LC3-D18A LC3-D18A LC3-D18A LC3-D32A LC3-D32A LC3-D40 LC3-D40 LC3-D50 LC3-D50 LC3-D50 LC3-D50 LC3-D80 LC3-D115 LC3-D115 LC3-D115 LC3-D150 LC3-F185 LC3-F225 LC3-F265 LC3-F265 LC3-F330 LC3-F330 LC3-F400 LR2-K0308 LR2-K0310 LR2-K0310 LR2-K0312 LR2-K0312 LR2-K0314 LR2-K0316 LRD-16 LRD-16 LRD-21 LRD-22 LRD-22 LRD-32 LRD-32 LRD-3355 LRD-3357 LRD-3357 LRD-3357 LRD-3359 LRD-3361 LRD-3363 LRD-4365 LRD-4367 LRD-4367 LRD-4369 LR9-F5371 LR9-F5369 LR9-F7375 LR9-F7375 LR9-F7375 LR9-F7375 LR9-F7379 A 1.82.6 2.63.7 2.63.7 3.75.5 3.75.5 5.58 811.5 913 913 1218 1624 1624 2332 2332 3040 3750 3750 3750 4865 5570 6380 80104 95120 95120 110140 132220 132220 200330 200330 200330 200330 300500 aM fuses Size Rating Star-delta contactors Reference Thermal overload relay Reference Setting range

440 V P kW 1.5 2.2 3 4 5.5 7.5 9 11 15 18.5 22 30 37 45 55 75 90 110 132 160 200

14 x 51 25 14 x 51 32 14 x 51 40 22 x 58 22 x 58 22 x 58 22 x 58 22 x 58 22 x 58 22 x 58 50 50 63 80 80 80 100

22 x 58 100 22 x 58 125 T0 T0 T1 T1 T2 T2 T2 T2 T3 T3 T3 T3 160 160 200 200 250 315 400 400 500 500 630 630

250 401 233 280 480 278 100 315 505 293 315 555 322 100 355 518 300 375 575 334 (1) IrD: current in the motor windings in delta connection.

24544_Ver3.11-EN.fm/2

Schneider Electric

Combinations for assembly TeSys motor starters - open by the customer version
Star-delta starters with fuse protection (NF C or DIN fuses)

1.5 to 355 kW at 400/415 V: type 2 coordination


Maximum operating rate: LC1-D: 30 starts/hour; LC1-F: 12 starts/hour. Maximum starting time: LC1-D: 30 seconds; LC1-F: 20 seconds. Standard power ratings of 3-phase motors 50/60 Hz in category AC-3 400/415 V 440 V P Ie Iq P kW A kA kW 1.5 2.2 3 4 5.5 7.5 9 11 15 18.5 22 30 37 45 55 75 90 110 132 160 200 220 250 315 355 3.5 5 6.5 8.4 11 14.8 18.1 21 28.5 35 42 57 69 81 100 135 165 200 240 285 352 388 437 555 605 50 50 50 50 50 50 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 1.5 2.2 3 4 5.5 7.5 9 11 15 18.5 22 30 37 45 55 75 90 110 132 160 200 220 250 315 355 400 Switchdisconnectorfuse Reference GS1-DD GS1-DD GS1-DD GS1-DD GS1-DD GS1-DD GS1-F GS1-F GS1-F GS1-F GS1-J GS1-J GS1-J GS1-J GS1-L GS1-L GS1-L GS1-L GS1-N GS1-N GS1-QQ GS1-QQ GS1-QQ GS1-S GS1-S GS1-S GS1-V GS1-V aM fuses Size Rating A 10 x 38 10 x 38 10 x 38 10 x 38 10 x 38 10 x 38 14 x 51 14 x 51 14 x 51 22 x 58 22 x 58 22 x 58 22 x 58 22 x 58 T0 T0 T0 T0 T1 T1 T2 T2 T2 T3 T3 T3 T4 T4 A 4 6 8 10 16 16 25 32 40 50 80 80 80 100 125 125 160 160 200 250 315 315 400 500 500 630 800 800 3 x LC1-D09 3 x LC1-D09 3 x LC1-D09 3 x LC1-D09 3 x LC1-D12 3 x LC1-D18 3 x LC1-D25 3 x LC1-D32 3 x LC1-D40 3 x LC1-D50 3 x LC1-D65 3 x LC1-D80 3 x LC1-D80 3 x LC1-D115 3 x LC1-D115 3 x LC1-D150 3 x LC1-D150 3 x LC1-F185 3 x LC1-F185 3 x LC1-F225 3 x LC1-F265 3 x LC1-F330 3 x LC1-F330 3 x LC1-F400 3 x LC1-F500 3 x LC1-F630 3 x LC1-F630 3 x LC1-F780 LRD-08 LRD-10 LRD-12 LRD-14 LRD-16 LRD-21 LRD-22 LRD-32 LRD-3355 LRD-3357 LRD-3361 LRD-3363 LRD-3365 LR9-D5367 LR9-D5369 LR9-D5369 LR9-D5369 LR9-D5369 LR9-F5371 LR9-F5371 LR9-F7375 LR9-F7375 LR9-F7379 LR9-F7379 LR9-F7379 LR9-F7381 LR9-F7381 LR9-F7381 Star-delta contactors Reference Thermal overload relay Reference Setting range A 2.54 46 5.58 710 913 1218 1624 2332 3040 3750 5570 6380 8093 60100 90150 90150 90150 90150 132220 132220 200330 200330 300500 300500 300500 380630 380630 380630

Ie A 3.06 4.42 5.77 7.9 10.4 13.7 16.9 20.1 26.5 32.8 39 51.5 64 76 90 125 146 178 215 256 321 353 401 505 549 611

Iq kA 50 50 50 50 50 50 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100

Schneider Electric

24544_Ver3.11-EN.fm/3

Combinations for assembly TeSys motor starters - open by the customer version
D.O.L. starters with fuse protection (BS fuses)

0.06 to 375 kW at 415 V: type 2 coordination


Standard power ratings of 3-phase motors 50/60 Hz in category AC-3 415 V 440 V P Ie P Ie kW A kW A 0.06 0.09 0.12 0.18 0.25 0.37 0.55 0.75 1.5 2.2 3 4 5.5 7.5 9 11 15 22 30 45 55 80 100 110 140 160 220 0.22 0.36 0.42 0.6 0.88 1 1.5 2 3.5 5 6.5 8.4 11 14 18.1 21 28.5 42 57 81 100 138 182 196 250 285 388 0.06 0.09 0.12 0.18 0.25 0.37 0.55 0.75 1.5 2.2 3 4 5.5 7.5 9 11 15 22 30 45 55 80 100 110 140 160 220 0.19 0.28 0.37 0.55 0.76 1 1.36 1.68 3.06 4.42 5.77 7.9 10.4 13.7 16.9 20 26.5 39 51.5 76 90 132 162 178 226 256 353 500 V P kW 0.37 0.55 0.75 1.5 2.2 3 4 5.5 7.5 9 11 15 22 30 45 55 80 100 110 140 160 220 257 Switchdisconnectorfuse Reference GS1-DDB GS1-DDB GS1-DDB GS1-DDB GS1-DDB GS1-DDB GS1-DDB GS1-DDB GS1-DDB GS1-DDB GS1-DDB GS1-DDB GS1-DDB GS1-DDB GS1-GB GS1-GB GS1-GB GS1-GB GS1-GB GS1-GB GS1-GB GS1-LLB GS1-LLB GS1-LLB GS1-LLB GS1-LB GS1-LB GS1-LB GS1-MMB GS1-MMB GS1-NB GS1-NB GS1-QQB GS1-QQB GS1-QQB BS fuses Size Rating A A1 A1 A1 A1 A1 A1 A1 A1 A1 A1 A1 A1 A1 A1 A2 A2 A2 A3 A3 A3 A3 A4 A4 A4 A4 B2 B2 B2 B2 B2 B3 B3 B4 B4 B4 C2 C2 C2 NIT 2 NIT 2 NIT 2 NIT 2 NIT 4 NIT 6 NIT 10 NIT 10 NIT 16 NIT 16 NIT 20 NIT 20 NIT 20M25 NIT 20M32 TIA 32M35 TIA 32M50 TIA 32M63 TIS 63M80 TIS 63M100 TIS 63M100 TIS 63M100 TCP 100M125 TCP 100M125 TCP 100M160 TCP 100M160 TF 200 TF 200M250 TF 200M250 TF 200M250 TF 200M315 TKF 315M355 TKF 315M355 TKF 315M355 TMF 400 TMF 400M450 TTM 500 TTM 500 TTM 630 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D12 LC1-D18 LC1-D18 LC1-D25 LC1-D32 LC1-D40 LC1-D50 LC1-D50 LC1-D65 LC1-D80 LC1-D95 LC1-D115 LC1-D115 LC1-D150 LC1-D150 LC1-F185 LC1-F185 LC1-F225 LC1-F265 LC1-F265 LC1-F330 LC1-F400 LC1-F400 LC1-F500 LC1-F500 LC1-F630 LRD-02 LRD-03 LRD-04 LRD-05 LRD-05 LRD-06 LRD-07 LRD-08 LRD-08 LRD-10 LRD-12 LRD-14 LRD-16 LRD-21 LRD-21 LRD-22 LRD-32 LRD-3355 LRD-3357 LRD-3359 LRD-3359 LRD-3363 LRD-3365 LR9-D5369 LR9-D5367 LR9-D5369 LR9-D5369 LR9-F5371 LR9-F5371 LR9-F5371 LR9-F5371 LR9-F7375 LR9-F7375 LR9-F7379 LR9-F7379 LR9-F7379 LR9-F7381 LR9-F7381 Contactor Reference (1) Thermal overload relay Reference Setting range A 0.160.25 0.250.4 0.40.63 0.631 0.631 11.7 1.62.5 2.54 2.54 46 5.58 710 913 1218 1218 1624 2332 3040 3750 4865 4865 6380 8093 90150 60100 90150 90150 132220 132220 132220 132220 200330 200330 300500 300500 300500 380630 380630

Ie A 1 1.2 1.5 2.6 3.8 5 6.5 9 12 13.9 18.4 23 33 45 65 80 116 143 156 200 220 310 362

380 GS1-SB 270 257 450 257 412 270 460 270 433 GS1-SB 508 375 610 375 577 375 425 556 GS1-SB (1) For reversing operation, replace the reference prefix LC1 by LC2.

24545_Ver2.10-EN.fm/2

Schneider Electric

Combinations for assembly TeSys motor starters - open by the customer version
Star-delta starters with fuse protection (BS fuses)

1.5 to 375 kW at 415 V: type 2 coordination


Maximum operating rate: LC1-D: 30 starts/hour; LC1-F: 12 starts/hour. Maximum starting time: LC1-D: 30 seconds; LC1-F: 20 seconds. Standard power ratings of 3-phase motors 50/60 Hz in category AC-3 415 V 440 V P Ie Iq P kW A kA kW 1.5 2.2 3 4 5.5 7.5 9 11 15 22 30 45 55 80 100 110 140 160 220 257 270 375 3.5 5 6.5 8.4 11 14.8 18.1 21 28.5 42 57 81 100 138 182 196 250 285 388 450 460 610 50 50 50 50 50 50 50 50 50 50 50 50 80 80 80 80 80 80 80 80 80 80 1.5 2.2 3 4 5.5 7.5 9 11 15 22 30 45 55 80 100 110 140 160 220 257 270 375 Switchdisconnectorfuses Reference GS1-DDB GS1-DDB GS1-DDB GS1-DDB GS1-DDB GS1-DDB GS1-GB GS1-GB GS1-GB GS1-GB GS1-GB GS1-GB GS1-LLB GS1-LLB GS1-LB GS1-MMB GS1-MMB GS1-NB GS1-QQB GS1-QQB GS1-SB GS1-SB BS fuses Size Rating A A1 A1 A1 A1 A1 A1 A2 A2 A2 A3 A3 A3 A4 A4 B2 B2 B2 B3 B3 B4 C2 C2 NIT 16 NIT 16 NIT 20 NIT 20 NIT 20M25 NIT 20M32 TIA 32M35 TIA 32M50 TIA 32M63 TIS 63M80 TIS 63M100 TIS 63M100 TCP 100M125 TCP 100M160 TF 200M250 TF 200M250 TF 200M315 TFK 315M355 TFK 315M355 TMF 400M450 TTM 500 TTM 630 3 x LC1-D09 3 x LC1-D09 3 x LC1-D09 3 x LC1-D09 3 x LC1-D12 3 x LC1-D18 3 x LC1-D18 3 x LC1-D25 3 x LC1-D32 3 x LC1-D40 3 x LC1-D50 3 x LC1-D65 3 x LC1-D80 3 x LC1-D115 3 x LC1-D150 3 x LC1-F185 3 x LC1-F225 3 x LC1-F265 3 x LC1-F330 3 x LC1-F400 3 x LC1-F500 3 x LC1-F630 LRD-08 LRD-10 LRD-12 LRD-14 LRD-16 LRD-21 LRD-21 LRD-22 LRD-32 LRD-3355 LRD-3359 LRD-3359 LRD-3363 LR9-D5369 LR9-D5369 LR9-F5371 LR9-F5371 LR9-F7375 LR9-F7375 LR9-F7379 LR9-F7379 LR9-F7381 Contactor Reference Thermal overload relay Reference Setting range A 2.54 46 5.58 710 913 1218 1218 1624 2332 3040 4865 4865 6380 90150 90150 132220 132220 200330 200330 300500 300500 380630

Ie A 3.06 4.42 5.77 7.9 10.4 13.7 16.9 20.1 26.5 39 51.5 76 90 132 162 178 226 256 353 412 433 577

Iq kA 50 50 50 50 50 50 50 50 50 50 50 50 80 80 80 80 80 80 80 80 80 80

Schneider Electric

24545_Ver2.10-EN.fm/3

References

TeSys motor starters - open version


D.O.L. starters, plate mounted, for motor control 4 to 37 kW, (1), with isolating device, pre-assembled

106558_1

Utilisation category AC-3 Standard power ratings Operaof 3-phase motors tional 50/60 Hz current 220 V 380 V 660 V 440 V 230 V 400 V 415 V 440 V 500 V 690 V up to kW kW kW kW kW kW A 2.2 4 4 4 5.5 9

Fuses to be fitted by the customer Size Type aM A 12

Basic reference. Complete with code indicating control circuit voltage (2)

Weight

kg LC4-D09A// 1 0.870

10 x 38

5.5

5.5

5.5

7.5

12

10 x 38

16

LC4-D12A// 1

0.870

7.5

10

18

10 x 38

20

LC4-D18A// 1

1.150

LC4-D09A//

5.5

11

11

11

15

25

10 x 38

25

LC4-D25A// 1

1.580

7.5

15

15

15

18.5

18.5

32

14 x 51

32

LC4-D32A//

2.630

11

18.5

22

22

22

30

40

14 x 51

40

LC4-D40//

2.930

15

22

25

30

30

33

50

22 x 58

63

LC4-D50//

3.200

18.5

30

37

37

37

37

65

22 x 58

80

LC4-D65//

3.340

22

37

45

45

55

45

80

22 x 58

80

LC4-D80//

3.650

Specifications Pre-wired power and control circuit connections. 3-pole isolating device (1) Thermal overload relay to be ordered separately (see pages 24514/3 and 24515/2). (2) Standard control circuit voltages. Volts 24 42 48 110 220 230 240 380 400 50/60 Hz B7 D7 E7 F7 M7 P7 U7 Q7 V7 For other voltages, please consult your Regional Sales Office. (3) Up until this date, the products will continue to be available with LS1-D2531A65 fuse carriers.

415 N7

440 R7

1 Available 1st quarter 2002 (3)

Dimensions : page 24546/3 24546_Ver2.10-EN.fm/2

Schemes : page 24546/3


Schneider Electric

Dimensions, schemes

TeSys motor starters - open version


D.O.L. starters, plate mounted, for motor control 4 to 37 kW, (1), with isolating device, pre-assembled

D.O.L. starters Plate mounted, pre-assembled LC4-D09AD25A

LC4-D32A

98 79
33 110

173

50

63

124

36

c1

= =

55 71 86

= =

c1 = 90 165

88 =

LC4b c1 without cover or add-on blocks with cover, without add-on block with LAD-N or C (2 or 4 contacts) with LA6-DK10 with LAD-T, R, S with LAD-T, R, S and sealing cover LC4-D40D80

D09AD18A 218 94 96 127 139 147 151

D25A 221 100 102 133 145 153 157

LC4c1 without cover or add-on blocks with cover, without add-on block with LAD-N or C (2 or 4 contacts) with LA6-DK10 with LAD-T, R, S with LAD-T, R, S and sealing cover

D32A 100 102 133 145 153 157

c c1 c2

b1

G a

LC4a b c c1 without cover or add-on blocks with cover, without add-on block with LA1-DN (1 contact) with LAD-N or C (2 or 4 contacts) with LA6-DK with LAD-T, R, S with LAD-T, R, S and sealing cover c2 D.O.L. starters LC4-D09A to D80
1/L1 3/L2 5/L3

D40D65 281 143 130 124 129 149 157 169 177 181 100

D80 311 143 140 135 140 160 168 180 188 192 178

Q1
4 2 6

KM1
2 4 6

References : page 24546/2


Schneider Electric

100/110

60

24546_Ver2.10-EN.fm/3

110

Presentation

TeSys motor starters - open version


Star-delta starters for motor control

Star-delta starting
Current

This method of starting is applicable to motors on which all 6 stator terminals are accessible and whose delta connection voltage corresponds to the mains voltage and Star-delta starting should be used for motors starting on no-load or having a low load torque and gradual build-up: - the starting torque in star connection is reduced to one third of the direct starting torque, i.e. about 50% of the rated torque; - the starting current in star connection is about 1.8 to 2.6 times the rated current. The transition from star to delta connection must occur when the machine has run up to speed. A too rapid build-up in load torque would cause the stabilised run-up speed to be too low and would therefore eliminate any advantage in this method of starting: this is the case with certain machines whose load torque depends on the machine speed (a characteristic of centrifugal machines, for example). All star-delta starters are supplied with a special LA2-DS2 or LA2-KT2/ time delay relay which imposes a delay on the delta contactor during the transition period in order to allow the star contactor sufficient breaking time. For ratings D115 and D150, this function is performed by a time delay auxiliary contact block LA2-DT2 and a control relay.

1
4

2
1

0 0 0,25 0,50 0,75 1 Speed

1 Starting in direct delta connection 2 Starting in star connection

Torque

2,5

1
1,5

(1)
1

2
0,5

3
0 0 0,25 0,50 0,75 1 Speed

1 Starting in direct delta connection 2 Starting in star connection 3 Machine resistive torque

(1) Motor manufacturers generally specify machine load torques. Example: maximum resistive torque on completion of star-delta start (expressed as a proportion of the rated torque).

24547_Ver3.10-EN.fm/2

Schneider Electric

References

TeSys motor starters - open version


Star-delta starters for motor control 5.5 to 132 kW, (1), without isolating device, pre-assembled
Standard power ratings of squirrel cage motors Mains voltage delta connection 220/ 380/ 230 V 400 V 415 V 440 V kW kW kW kW Auxiliary contacts available on each contactor line delta star KM2 KM3 KM1 Star delta mechanical interlock Basic reference. Complete with code indicating control circuit voltage (2)

Weight

kg

Plate mounted
Maximum operating rate: 30 starts/hour. Maximum starting time: 30 seconds. 4 5.5 LC3-D32A// 11 15 18.5 30 37 63 75 18.5 25 37 55 75 110 132 22 30 37 59 75 110 132 22 30 37 59 75 110 147 1 1 1 1 1 1 1 1 1 1 (3) (3) (3) (3) (3) (3) (3) 1 1 1 With With Without With LC3-D18A// LC3-D32A// LC3-D40// LC3-D40//A64 LC3-D50// LC3-D50//A64 LC3-D80// LC3-D80//A64 LC3-D115// (4) LC3-D115//A64 (4) LC3-D150// (4) LC3-D150//A64 (4) 1.730 2.030 4.360 4.500 4.360 4.500 5.200 5.400 11.800 12.100 12.100 12.100 7.5 11 7.5 11 7.5 11 (3) (3) 1 1 With With LC3-D09A// LC3-D12A// 1.530 1.530

(3) Without With (3) Without With (3) Without With 1 (3) Without With

Rail mounted (35 mm


rail)
Maximum operating rate: 12 starts/hour. Maximum starting time: 30 seconds. 3 4 5.5 7.5 5.5 7.5 5.5 7.5 1 1 With With LC3-K06// LC3-K09// 0.740 0.740

Maximum operating rate: 30 starts/hour. Maximum starting time: 30 seconds. 4 5.5 11 15 7.5 11 18.5 25 7.5 11 22 30 7.5 11 22 30 (3) (3) (3) (3) 1 1 1 1 With With With With LC3-D090A// LC3-D120A// LC3-D180A// LC3-D320A// 1.530 1.530 1.730 2.030

(1) Protection must be provided by the addition of an overload relay, to be ordered separately. Select appropriate overload relay for setting at 0.58 of the full load rated motor current (see pages 24514/2 and 24514/3). (2) Standard control circuit voltages Volts " 50/60 Hz 24 36 42 48 110 220 230 240 380 400 415 440 Star-delta starters LC3-K06 and K09 Code B7 C7 D7 E7 F7 M7 P7 U7 V7 N7 R7 Star-delta starters LC3-D09A...D150, LC3-D090AD320A Code B7 D7 E7 F7 M7 P7 U7 Q7 V7 N7 R7 For other voltages, please consult your Regional Sales Office. (2) One auxiliary contact block type LAD-N can also be fitted, see page 24511/3. (3) These starters consist of contactors LC1-D115 or D150 without connectors.

Dimensions : pages 24549/2 and 24549/3


Schneider Electric

Schemes : page 24549/3

24547_Ver3.10-EN.fm/3

KM1

1b
KM3

1c

KM2 KM2 KM2

1d

1b

1c

1a

24548_Ver3.11-EN.fm/2

Schneider Electric

References

TeSys motor starters - open version


Star-delta starters, for motor control, 7.5 to 132 kW (1), without mechanical interlock, for customer assembly (on plate or on mounting rail) (2)

"

Starters for direct combination with circuit-breaker


Maximum operating rate : 30 starts/hour. Maximum starting time : 30 seconds Standard power ratings Motor Contactors (basic references to be completed of squirrel cage motors (3) thermalwith code indicating the voltage) (4) Mains voltage-delta magnetic 400/ MCB 415 V 440 V line delta star kW kW KM2 KM3 KM1 7.5 9 11 15 7.5 9 11 15 GV2-ME20 GV2-ME20 GV2-ME21 GV2-ME22 GV2-ME32 LC1-D09// LC1-D12 LC1-D12 LC1-D18 LC1-D18

// // // //

LC1-D09 LC1-D12 LC1-D12 LC1-D18 LC1-D18

// // // // //

LC1-D09 LC1-D09 LC1-D09 LC1-D09 LC1-D09

// // // // //
Weight kg 0.130

Separate parts Description

Illustration item no. a

Reference

Mounting kit comprising: power circuit connections and 1 time delay contact block LAD-S2

LAD-912GV

Starters for mounting separately from upstream protection


Maximum operating rate : 30 starts/hour. Maximum starting time : 30 seconds Standard power ratings Contactors (basic references to be completed of squirrel cage motors (3) with code indicating the voltage) (4) Mains voltage-delta 220/ 380/ 230 V 400 V 415 V 440 V line delta star kW kW kW kW KM2 KM3 KM1 4 5.5 11 15 18.5 30 37 63 75 7.5 11 18.5 25 37 55 75 110 132 7.5 11 22 30 37 59 75 110 132 7.5 11 22 30 37 59 75 110 147 LC1-D09 LC1-D12 LC1-D18 LC1-D32 LC1-D40 LC1-D50 LC1-D80 LC1-D115 LC1-D150 Separate parts (see below)

// // // // // // //// //

LC1-D09 LC1-D12 LC1-D18 LC1-D32 LC1-D40 LC1-D50 LC1-D80 LC1-D115 LC1-D150

// // // // // // //// //

LC1-D09 LC1-D09 LC1-D09 LC1-D18 LC1-D40 LC1-D40 LC1-D50 LC1-D80 LC1-D115

// // // // // // // ////

Component types D09 D12 D18 D32 D40 D50 D80 D115 (5) D150 (5)

Separate parts Description

Illustration item no.

For use on (5) D09D18

Reference

Weight kg 0.180 0.310 0.380 0.480 0.680 0.150 0.180 0.300

Mounting kit comprising : - 1 time delay contact block LAD-S2 (D09D80) (3) - power circuit connections (D09D80) - screws and clamps for fixing contactors to the plate (D40D80) - terminal block (D09D32)

LAD-91217 LAD-93217 LA9-D4017 LA9-D5017 LA9-D8017 LA9-D12974 LA9-D32974 LA9-D40973

1a D32 1b D40 1c D50 1d D80

Equipment mounting plate

D09, D12, D18 D32 D40 and D50

D80 LA9-D80973 0.300 (1) Protection must be provided by the addition of a thermal overload relay, to be ordered separately. Select appropriate overload relay for setting at 0.58 of the rated motor current, see pages 24514/2 and 24514/3. (2) For mounting, assembly and cabling : refer to installation instructions supplied with the equipment. (3) See comments on page 24547/2. (4) See page 24501/2. (5) For D115 and D150 components, see illustration and separate parts on pages 24548/4 and 24548/5.

Illustrations : page 24548/2


Schneider Electric

Dimensions : pages 24549/2 and 24549/3

Schemes : page 24549/3

24548_Ver3.11-EN.fm/3

13

12

11

10

14 6 8

24548_Ver3.11-EN.fm/4

Schneider Electric

References (continued)

TeSys motor starters - open version


Star-delta starters, for motor control, 7.5 to 132 kW (1), without mechanical interlock, for customer assembly (on plate or on mounting rail) (2)

"

Separate parts (continued)


Description Illustration For item no. use on 1 D115 (star) No. Sold in lots of 1 Unit reference LAD-N10 Weight kg 0.020

Instantaneous auxiliary contact block 1N/O Auxiliary contactor

D115, D150

CAD-N32

//

(3)

0.320

Time delay auxiliary contact blocks

D115, D150

LAD-T2

0.060

Lead sealing kit for time delay auxiliary contact blocks

D115, D150

LA9-D901

0.005

Thermal magnetic 6 circuit-breaker for control circuit (200415 V) Set of 3 connectors for 7 wider terminations (optional)

D115, D150

GB2-CB05

0.060

D115, D150

LA9-FG980

0.200

Set of power connections with fixing accessories

D115

LA9-D11517

0.800

D150

LA9-D15017

1.050

Spare volt free terminals

D115, D150

10

DZ3-HA3

0.007

10

DZ3-GA3

0.006

Lug-connector terminal block

10

D115, D150

10

AB1-BC9535

0.236

Terminal end stop

11

D115, D150

100

AB1-AB8M35

0.005

Mounting rail

35 mm

12

D115, D150

10

AM1-ED021

0.210

Pre-slotted plate

13

D115, D150

AM3-PA65

1.950

Screw with captive washer 14

D115, D150

12

100

AF1-VA618

0.006

100

AF1-VA410

0.002

(1) Protection must be provided by the addition of a thermal overload relay, to be ordered separately. Select appropriate overload relay for setting at 0.58 of the rated motor current, see pages 24514/2 and 24514/3. (2) For mounting, assembly and cabling : refer to installation instructions supplied with the equipment. (3) See page 24525/3.

Illustrations : page 124548/4


Schneider Electric

Dimensions : pages 24549/2 and 24549/3

Schemes : page 24549/3

24548_Ver3.11-EN.fm/5

General selection guide

TeSys enclosed starters

Applications

D.O.L. starters

Type

Standard starters

Starters for safety applications

Standard power ratings of 3-phase motors in AC-3 400/415 V

437 kW

0.0645 kW

0.5530 kW 0.375.5 kW

0.2545 kW

2.245 kW

0.0611 kW

Starters Manual

Auto

Isolation Switch

Circuit-breaker

Disconnector

Protection Short-circuit

/ /

/ /

/ /

/ /

/ /

Overload

Communication References Non reversing

V/F VCFN V/FX

GV2-ME GV3-CE

GV2-LC LE1-GVME LE1-M GV-NGC LE1-D LE2-K LE2-D

LE4-K LE4-D LE8-K LE8-D LE2-D


24103/2 and 24103/3

GV2-ME

Reversing

Pages

23008/2 and 23008/3

80263/2 and 80263/3

24110/2

24111/2

24101/2, 24101/3 and 24105/2

21058/2 and 21058/3

(1) Please consult your Regional Sales Office.

0243Q_Ver2.21-EN.fm/2

Schneider Electric

Soft start units

Variable speed controllers

AS-i bus starters

Standard star-delta starters

Electronic soft start soft stop units

0.069 kW

0.069 kW

0.065.5 kW

5.5 132 kW

7.5 75 kW

0.3711 kW

0.374 kW

0.7575 kW

/ (LH7-0M) / (LH7-KP)

/ /

/ /

/ /

/ (from 7.5 kW) / (up to 5.5 kW)

/ /

/ /

/ /

/ /

/ /

/ /

/ /

LG1-K LG1-D

LG7-K LG7-D LJ7-K LG8-K LJ8-K

LF1-M LF1-P LF7-P LF2-M LF2-P LF8-P

LE3-K LE3-D LE3-F (1)

LE6-D LE3-D

LH7-0 LH7-K

ATV-28E

ATV-58E

ATV-28E

ATV-58E

24026/3

24026/2 and 24026/4, 26044/2 and 26044/3

24084/2 to 24088/ 3

24106/2 24108/2 and 24106/ and 3 24108/3

24073/2 and 24073/3

(1)

Schneider Electric

0243Q_Ver2.21-EN.fm/3

Characteristics, references TeSys enclosed starters


D.O.L. starters with manual control, with magnetic circuit breaker, 0.55 to 30 kW

Characteristics (1)
Conforming to standards Degree of protection to IEC 529 Operational voltage Ue Material IEC 947-4, IEC 439-1, VDE 0660-102 and EN 60947 IP 657 GV2-LC: 690 V, GV-NGC: 500 V Polycarbonate (2)

References
Control by black rotary handle, padlockable in Off position (up to 3 padlocks with 8 shank, to be ordered separately) Rating Breaking capacity Icu Magnetic Reference Weight In conforming to IEC 947-2 tripping 220 400 current 230 V 415 V 440 V 500 V Id 20 % A kA kA kA kA A kg 1.6 GV2-LC02// 2.5 4 6.3 10 14 18 25 32 40 50 63 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 50 50 50 50 50 50 50 100 100 100 20 20 20 30 30 30 30 30 100 100 100 10 10 10 15 15 15 15 15 13 In 13 In 13 In 13 In 13 In 13 In 12 In 12 In 12 In 12 In 12 In GV2-LC0207 GV2-LC0208 GV2-LC0210 GV2-LC0214 GV2-LC0216 GV2-LC0220 GV-NGC0225 GV-NGC0232 GV-NGC0240 GV-NGC0250 GV-NGC0263 0.780 0.780 0.780 0.780 0.780 0.780 2.450 2.450 2.450 2.450 2.450 100 100 100 100 13 In GV2-LC0206 0.780

GV-NGC02//

Variant
Starters with control by red rotary handle on yellow background Add the letter R to the end of the references selected above. Example: GV2-LC0206 becomes GV2-LC0206R. Enclosure without circuit-breaker, with rotary handle mounted on cover Description Rating Reference A Black rotary handle GV2-LC02 Red rotary handle on yellow background 1.618 2563 1.618 GV2-LC02 GV-NGC02 GV2-LC02R

Weight kg 0.300 0.550 0.300

2563 GV-NGC02R 0.550 (1) Circuit-breaker characteristics: - GV2-L see pages 24523/2 and 24523/3 - NG 125L, product marketed under the Merlin Gerin, brand, please consult your Regional Sales Office. (2) Avoid placing this material in contact with harsh substances (detergents, chlorinated solvents, ketones, alcohol, aromatic hydrocarbons).

Dimensions : page 24110/3 24110_Ver2.10-EN.fm/2

Schemes : page 24110/3


Schneider Electric

Dimensions, scheme

TeSys enclosed starters


D.O.L. starters with manual control, with magnetic circuit-breaker. 0.55 to 30 kW

Dimensions GV2-LC0206 to LC0220

GV-NGC0225 to NGC0263

65

150

166

348

120 173

= 88

237

186,3

Knock-outs or blanking plugs for cable glands Type of enclosure At top PG ISO GV2-LC GV-NGC Scheme
3/L2 1/L1 5/L3

At bottom PG 2 x 13 or 2 x 16 2 x 13 or 2 x 16 or 2 x 21 or 2 x 29

ISO 2 x 20 I 2 x 20 I or 2 x 25 I or 2 x 32 I or 2 x 40 I

2 x 13 to 2 x 16 2 x 13 or 2 x 16 or 2 x 21 or 2 x 29

2 x 20 I 2 x 20 I or 2 x 25 I or 2 x 32 I or 2 x 40 I

2/T1

References : page 24110/2


Schneider Electric

4/T2

6/T3

24110_Ver2.10-EN.fm/3

167

330

Characteristics, references

TeSys enclosed starters


D.O.L. starters for motor control 2.2 to 45 kW, without isolating device
(1)

"

Characteristics
Conforming to standards Degree of protection to IEC 529 Ambient air temperature Operating positions Material IEC 947-4-1 and IEC 439-1, VDE 0660-102, EN 60947 IP 659: LE2-K, IP 657: LE /-D09 to D35 and IP 557: LE /-D405 to D955 For operation: - 5 to + 40 C Identical to positions for contactors Polycarbonate (2): LE2-K and LE/ -D09 to D35. Sheet steel: LE /-D405 to D955

References
Non-reversing starters Standard power ratings of 3-phase motors 50/60 Hz in category AC-3 220 V 380 V 660 V 230 V 400 V 415 V 440 V 500 V 690 V kW kW kW kW kW kW 2.2 LE1-D12// 3 4 5.5 7.5 11 15 18.5 22 25
810174 810173

Maximum current I the up to A 9 12 18 25 35 40 50 65 80 95

Basic reference. Complete with code indicating control Standard circuit voltage (3) voltages LE1-D09// LE1-D12// LE1-D18// LE1-D25// LE1-D35// LE1-D405// LE1-D505// LE1-D655// LE1-D805// LE1-D955//

Weight

kg F7 P7 V7 F7 P7 V7 F7 P7 V7 F7 P7 V7 F7 P7 V7 F7 P7 V7 F7 P7 V7 F7 P7 V7 F7 P7 V7 F7 P7 V7 0.920 0.920 1.015 1.015 4.320 4.820 4.850 4.850 5.140 5.440

4 5.5 7.5 11 15 18.5 22 30 37 45

4 5.5 9 11 15 22 25 37 45 45

4 5.5 9 11 15 22 30 37 45 45

5.5 7.5 10 15 18.5 22 30 37 55 55

5.5 7.5 10 15 18.5 30 33 37 45 45

Reversing starters 1.5 2.2 2.2 4 2.2 4 3 4 6 9 LE2-K065// LE2-K095// or LE2-D09// (4) LE2-D09// LE2-D12// LE2-D18// LE2-D25// LE2-D35// LE2-D405// LE2-D505// LE2-D655// LE2-D805// F7 P7 V7 F7 P7 V7 F7 P7 V7 F7 P7 V7 F7 P7 V7 F7 P7 V7 F7 P7 V7 F7 P7 V7 F7 P7 V7 F7 P7 V7 F7 P7 V7 F7 P7 V7 1.080 1.080 2.100 2.100 2.100 2.410 2.570 4.100 5.270 5.470 5.470 6.700

3 LE2-D12// 4 5.5 7.5 11 15 18.5 22

5.5 7.5 11 15 18.5 22 30 37

5.5 9 11 15 22 25 37 45

5.5 9 11 15 22 30 37 45

5.5 7.5 10 15 18.5 22 30 37 55

5.5 7.5 10 15 18.5 30 33 37 45

9 12 18 25 35 40 50 65 80

25 45 45 45 55 45 95 LE2-D955// F7 P7 V7 7.000 (1) Protection must be provided by addition of an overload relay, to be ordered separately, see pages 24514/2 and 24514/3. (2) Avoid placing this material in contact with harsh substances (detergents, chlorinated solvents, ketones, alcohol, aromatic hydrocarbons). (3) Standard control circuit voltages. Volts " 50/60 Hz 24 42 48 110 115 220 230 240 380 400 415 440 LE2-K B7 D7 E7 F7 M7 P7 U7 Q7 V7 N7 R7 LE1, LE2-D B7 D7 E7 F7 FE7 M7 P7 U7 Q7 V7 N7 R7 Other voltages: please consult your Regional Sales Office. (4) Selection according to the number of operating cycles, please consult your Regional Sales Office.

Dimensions: page 24102/2 24101_Ver3.01-EN.fm/2

Schemes: page 24102/3


Schneider Electric

References

TeSys enclosed starters


D.O.L. starters for motor control 2.2 to 45 kW, without isolating device
(1)

"

Description
810175

Standard versions comprise: / For non-reversing starters:


/ For reversing starters:

1 green Start button I , 1 red Stop/Reset button O. 1 Start button , 1 Start button , 1 red Stop/Reset button. 1 2-position spring return selector switch I-II, 1 red Stop/Reset button O. 1 blue Reset button R.

- LE2-K: LE1-D12// A04 - LE2-D09 to D35:

- LE2-D405 to D955:

Variants (pre-assembled)
810176

Description

Application

Suffix to be added to the starter reference (2) A04

No pushbuttons on cover

LE1-D09 D955 LE2-D09 D955

LE1-D12// A05

1 green Start button I 1 green Start button II 1 red Stop/Reset button O 1 blue Reset button R

LE2-D405D955 A11

LE1-D09 D955 A05 LE2-K06 and K09 LE2-D09 D35

810177

1 3-position stay put selector switch (I-O-II) (I: Automatic Start; O: Stop; II: Manual Start) 1 blue Reset button R

LE1-D09 D35

A09

LE1-D12// A09

1 2-position stay put selector switch O-I (O: Stop; I: Manual Start) 1 blue Reset button R

LE1-D09 D35

A13

1 3-position stay put selector switch O-I with spring return to centre position (I: Manual start; O: Stop, stay put) 1 blue Reset button R
810178

LE1-D09 D35

A35

1 neutral terminal Fitted as standard on LE1 and LE2-D18 to D955 starters ordered with 220 V (M7), 230 V (P7) or 240 V (U7) control supply

LE1-D09 D955 A59 LE2-K06 and K09 LE2-D09 D955

Accessory (for customer assembly)


LE1-D12// A13 Description Application Reference Weight kg 0.060

Start pushbutton latching device for stay put operation (Start-Stop) (1) See previous page. (2) Example: LE1-D09F7A04.
810178

LE1-D405D955 LA9-D09907

LE1-D12// A35

Other versions

Possible combinations of 2 variants. Please consult your Regional Sales Office.

Schemes: page 24102/3


Schneider Electric

24101_Ver3.01-EN.fm/3

Characteristics, references TeSys enclosed starters


D.O.L. starters for motor 2.2 to 45 kW, with isolating device control (1)

"

Characteristics
Conforming to standards Degree of protection to IEC 529 Ambient air temperature Operating positions Material IEC 947-4-1 and IEC 439-1, VDE 0660-102, EN 60947 IP 659 : LE/ -K, IP 657 : LE/ -D09 to D35 and IP 55 : LE /-D406 to D806 For operation : - 5 to + 40 C Identical to positions for contactors Polycarbonate (2) : LE /-K and LE/ -D09 to D35. Sheet steel : LE/ -D406 to D806

References
Non-reversing starters Standard power ratings of 3-phase Current motors 50/60 Hz in category AC-3 I the 220 V 380 V 660 V max. 230 V 400 V 415 V 440 V 500 V 690 V up to kW kW kW kW kW kW A 1.5 2.2 2.2 4 2.2 4 3 4 6 9 Fuses to be fitted by the customer Size Type aM A 10 x 38 10 10 x 38 12 or 2.2 3 LE4-D12// 4 5.5 7.5 11 15 18.5 22 4 5.5 7.5 11 15 18.5 22 30 37 4 5.5 9 11 15 22 25 37 45 4 5.5 9 11 15 22 30 37 45 5.5 7.5 10 15 18.5 22 30 37 55 18.5 30 33 37 45 9 12 18 25 35 40 50 65 80 10 x 38 12 10 x 38 16 10 x 38 20 10 x 38 25 14 x 51 32 14 x 51 40 22 x 58 63 22 x 58 80 22 x 58 80 Basic reference. Complete with code indicating control Standard circuit voltage (3) voltages LE4-K065// LE4-K095// LE4-D09// (4) LE4-D09// LE4-D12// LE4-D18// LE4-D25// LE4-D35// LE4-D406// LE4-D506// LE4-D656// LE4-D806// (5) Weight

kg F7 P7 V7 F7 P7 V7 F7 P7 V7 F7 P7 V7 F7 P7 V7 F7 P7 V7 F7 P7 V7 F7 P7 V7 F7 P7 V7 F7 P7 V7 F7 P7 V7 F7 P7 V7 1.450 1.450 1.960 1.960 1.960 2.200 2.200 5.190 5.770 6.440 6.670 7.100

Reversing starters 1.5 2.2 2.2 4 2.2 4 3 4 6 9 10 x 38 10 10 x 38 12 or 3 4 5.5 7.5 11 LE8-D12// 15 18.5 5.5 7.5 11 15 18.5 22 30 5.5 9 11 15 22 25 37 5.5 9 11 15 22 30 37 5.5 7.5 10 15 18.5 22 30 37 18.5 30 33 37 9 12 18 25 35 40 50 65 10 x 38 12 10 x 38 16 10 x 38 20 10 x 38 25 14 x 51 32 14 x 51 40 22 x 58 63 22 x 58 80 LE8-K065// LE8-K095// LE8-D09// (4) LE8-D09// LE8-D12// LE8-D18// LE8-D25// LE8-D35// LE2-D406// LE2-D506// LE2-D656// F7 P7 V7 F7 P7 V7 F7 P7 V7 F7 P7 V7 F7 P7 V7 F7 P7 V7 F7 P7 V7 F7 P7 V7 F7 P7 V7 F7 P7 V7 F7 P7 V7 1.600 1.600 3.550 3.550 3.550 3.700 4.670 5.800 14.170 14.700 14.770

LE2-D806// F7 P7 V7 16.000 22 37 45 45 55 45 80 22 x 58 80 (1) Protection must be provided by addition of an overload relay, to be ordered separately, see pages 24514/2 and 24514/3. (2) Avoid placing this material in contact with harsh substances (detergents, chlorinated solvents, ketones, alcohol, aromatic hydrocarbons). (3) Standard control circuit voltages. Volts " 50/60 Hz 24 42 48 110 115 220 230 240 380 400 415 440 LE/ -K B7 D7 E7 F7 M7 P7 U7 Q7 V7 N7 R7 LE/ -D B7 D7 E7 F7 FE7 M7 P7 U7 Q7 V7 N7 R7 Other voltages : please consult your Regional Sales Office. (4) Selection according to dimensions and number of operating cycles, please consult your Regional Sales Office. (5) Supplied with 3 cable entries. Dimensions : page 24104/2 Schemes : page 24104/3
Schneider Electric

24103_Ver4.10-EN.fm/2

References

TeSys enclosed starters


D.O.L. starters for motor 2.2 to 45 kW, with isolating device control (1)

"

Description
Standard versions comprise : / For non-reversing starters : - LE4-K and LE4-D09 to D656 :

1 green Start button I , 1 red Stop/Reset button O, no pushbuttons on cover. 1 Start button , 1 Start button , 1 red Stop/Reset button, 1 2-position spring return selector switch I II, 1 red Stop/Reset button O, no pushbuttons on cover. Power circuit 1 3-pole isolating device 1 3-pole isolating device 1 3-pole isolating device Control circuit None + 1 additional pole LA8-D254 + 1 circuit-breaker GB2-CB08

- LE4-D806 :
/ For reversing starters : - LE8-K :

- LE8-D09 to D35 : LE4-D12// A04

- LE2-D406 to D806 : Protection LE4 and LE8-K LE4 and LE8-D09 to D35 LE4 and LE2-D406 to D806

Variants (pre-assembled)
Description Application Suffix to be added to the starter reference (2) A04

No pushbuttons on cover

LE4-D09 D656 LE8-D09 D35

1 green Start button I 1 green Start button II 1 red Stop/Reset button O

LE2-D406D806 A11

1 blue Reset button R LE4-D12// A05

LE4-D09 D806 A05 LE8-K06 and K09 LE8-D09 D35 LE2-D406D806

1 neutral terminal Fitted as standard on starters LE4-D18 to D806, LE8-D18 to D35 and LE4-D406 to D806 ordered with 220 V (M7), 230 V (P7) and 240 V (U7) control supply

LE4-K06 and K09 A59 LE4-D09 D806 LE8-K06 and K09 LE8-D09 D35 LE2-D406D806

Accessories (for customer assembly)


Description Application Reference Weight kg 0.060

Start pushbutton latching device for stay put operation (Start-Stop) (1) See previous page (2) Example : LE4-D09F7A04.

LE4-D406D656 LA9-D09907

Other versions Schemes : page 24104/3


Schneider Electric

Possible combinations of 2 variants. Please consult your Regional Sales Office.

24103_Ver4.10-EN.fm/3

Characteristics, references TeSys enclosed starters


D.O.L. starters for motor control 0.25 to 7.5 kW with 3-phase thermal overload relay

Characteristics
Conforming to standards Degree of protection to IEC 529 Ambient air temperature Operating positions Material IEC 947-4-1, IEC 439-1, VDE 0660-102 and EN 60947 IP 65 For operation: - 5 to + 40 C Identical to those for k contactors Self-extinguishing ABS

References
Non-reversing starters Starter LE1-M, combined with short-circuit protection components, provides type 1 or type 2 coordination, depending on the type of devices used. Standard power ratings of 3-phase motors 50/60 Hz in category AC-3 220 V 380 V 230 V 240 V 400 V 415 V kW kW kW kW 0.12 0.18 0.25 0.37 0.55 1.1 1.5 2.2 LE1-M35//// 3 3.7 0.12 0.18 0.25 0.37 0.55 0.75 1.1 2.2 3 4 0.25 0.37 0.55 1.1 1.5 2.2 3 4 5.5 7.5 0.25 0.37 0.55 0.75 1.5 2.2 3 4 5.5 7.5 Setting range of thermal overload relay LR2-K(1) A 0.540.8 0.81.2 1.21.8 1.82.6 2.63.7 3.75.5 5.58 811.5 1014 1216 LE1-M35//05 LE1-M35//06 LE1-M35//07 LE1-M35//08 LE1-M35//10 LE1-M35//12 LE1-M35//14 LE1-M35//16 LE1-M35//21 LE1-M35//22 Basic reference. Complete with code indicating power circuit voltage (2) Weight

kg 0.600 0.600 0.600 0.600 0.600 0.600 0.600 0.600 0.600 0.600

Description
/ The standard version comprises:
- 1 green Start button I, - 1 red Stop/Reset button O/R, - 1 yellow operating indicator. / Control may be pulsed or maintained. / An earth terminal and a neutral terminal are provided on the bottom of the enclosure.

Variant
Starter without thermal overload relay LR2-K Delete the last 2 digits of the starter references selected above. Example: LE1-M35//

Spare part
Description Basic reference. Complete with code indicating power circuit voltage (2) LC1-K//A80 Weight kg 0.180

Contactor

(1) Thermal overload relay fitted as standard. (2) The contactor coil is pre-wired between 2 phases of the power circuit The codes indicated below therefore correspond to the power circuit voltage. Volts 50/60 Hz 24 220 230 240 380 400 Code B7 M7 P7 U7 Q7 V7 Example: 380/400 V 3-phase supply, 4 kW motor: LE1-M35Q716

"

415 N7

440 R7

Dimensions : page 24105/3 24105_Ver3.10-EN.fm/2

Schemes : page 24105/3


Schneider Electric

Dimensions, schemes

TeSys enclosed starters


D.O.L. starters for motor control 0.25 to 7.5 kW with 3-phase thermal overload relay

Dimensions LE1-M35 (1)

108

78

Knock-outs or blanking plugs for cable glands Enclosure type At top PG ISO

At bottom PG

ISO

LE1-M 2 x 13 to 2 x 21 2 x 20 I or 2 x 25 I 2 x 13 to 2 x 21 2 x 20 I or 2 x 25 I (1) Can be mounted on machine panel or frame. Knock-outs for 4 x 13 P cable glands. Schemes LE1-M35

Choice of type of control built into the product Control by Control by latching spring return pushbuttons pushbuttons
A A

1/L1

3/L2

A1 13 13 1 3 5 I 14 13

5/L3

L1 L2 L3

130 (5"1/8)

160

KM1

I 14

KM1

KM1

or
95
2 4 6 14 A2

O/R

96

A2

Reset/OR

KM1 A1

H1

KM1 A1
B

A2 H1

O/R

M
B

T1 T2 T3

Connections 220 V, 230 V, 240 V 380 V, 400 V, 415 V, 440 V Other voltages

A L3 L3 Terminal 1

96

95

B Neutral L1 Terminal 2

References : page 24105/2


Schneider Electric

24105_Ver3.10-EN.fm/3

Characteristics, references TeSys enclosed starters


D.O.L. starters for motor control 0.37 to 5.5 kW with thermal magnetic circuit-breaker and contactor

Characteristics
Conforming to standards Degree of protection to IEC 529 Ambient air temperature Operating positions Material IEC 947-4-1, IEC 439-1, VDE 0660-102 and EN 60947 IP 55 For operation: - 5 to + 40 C Identical to those for K contactors Polycarbonate (1)

References
Standard power ratings of 3-phase motors 50/60 Hz in category AC-3 400 230 V 415 V 440 V 500 V 690 V kW kW kW kW kW 0.18 0.25 0.37 0.55 0.37 0.55 0.37 0.55 0.75 1.1 0.75 1.1 Setting range of thermal trips A 11.6 Fixed magnetic tripping current 13 Irth A 22.5 Basic reference. Complete with code indicating control circuit voltage (2) LE1-GVME06K// Weight

kg 1.210

0.37

0.75

0.75 1.1 1.5

1.5

1.62.5

33.5

LE1-GVME07K// LE1-GVME08K// LE1-GVME10K// LE1-GVME14K// LE1-GVME16K//

1.210

0.55 0.75 1.1

1.1 1.5 2.2

1.5 2.2 3

2.2 3 4

2.54

51

1.210

2.2 3 4

46.3

78

1.210

1.5 2.2 LE1-GVME//K// 2.2 3

3 4 5.5

4 5.5 7.5

5.5 7.5 9 11

610

138

1.210

5.5 7.5

914

170

1.210

Variant
Description Suffix to be added to the starter reference (3) A59 Reference Weight kg Weight kg 0.740

Neutral terminal Description

LE1-GVMEK

Enclosure without starter, with sealing kit fitted (references of combination motor starters for customer assembly, see pages 24520/2 and 24520/3)

LE1-GVMEK

Accessories (to be ordered separately)


Description Sold in lots of Unit reference Weight kg

1 GV2-V01 0.075 Padlocking device (4) 1 to 3 padlocks with for padlocking the 4 to 8 mm shank GV2-ME operator (Padlocking is only possible in the O (Off) position) 1 GV2-K011 0.052 Mushroom Spring return (4) head Stop 1 GV2-K021 0.160 button Latching Key release (key n 455) 40 mm, (4) IP 55 Turn to release 1 GV2-K031 0.115 1 GV2-K04 (5) 0.120 red 10 GV2-E01 0.012 Sealing IP 55 10 GV2-E02 0.012 kit IP 55 for < + 5 C (1) Avoid placing this material in contact with harsh substances (detergents, chlorinated solvents, ketones, alcohol, aromatic hydrocarbons). (2) Standard control circuit voltages Volts 50/60 Hz 24 42 48 110 115 220 230 240 380 400 415 440 Code B7 D7 E7 F7 M7 P7 U7 Q7 V7 N7 R7 Other voltages: please consult your Regional Sales Office. (3) Example: LE1-GVME06KF7A59 (4) Supplied with IP 55 sealing kit. (5) Padlockable in position O, by padlock with 4 to 8 mm shank.

"

Dimensions : page 24111/3 24111_Ver3.10-EN.fm/2

Schemes : page 24111/3


Schneider Electric

Dimensions, schemes

TeSys enclosed starters


D.O.L. starters for motor control 0.37 to 5.5 kW with thermal magnetic circuit-breaker and contactor

Dimensions LE1-GVMEK

183 86 94

201

= 101

Schemes LE1-GVMEK
A
L1 L2 L3

Q1
Q1

External control

KM1

KM1

KM1

Connections 220 V, 230 V, 240 V 380 V, 400 V, 415 V, 440 V Other voltages

A L3 L3 Terminal 1

A2

A1

B Neutral L1 Terminal 2

References : page 24111/2


Schneider Electric

24111_Ver3.10-EN.fm/3

Characteristics, references TeSys enclosed starters


Star-delta starters 5.5 to 132 kW, without isolating device (1)

"

Characteristics
Conforming to standards Degree of protection to IEC 529 Ambient air temperature Operating positions Material IEC 947-4-1 and IEC 439-1, VDE 0660-102, EN 60947 IP 659: LE3-K, IP 657: LE3-D09 to D35 and IP 557: LE3-D405 to D150 For operation: - 5 to + 40 C Identical to positions for contactors Polycarbonate (2): LE3-K and LE3-D09 to D35. Sheet steel: LE3-D405 to D150

References
Standard power ratings of squirrel cage motors Mains voltage - delta connection 220 V 380 V 415 V 440 V 400 V kW kW kW kW Basic reference. Complete with code indicating control circuit voltage (3) Weight

kg

Maximum operating rate LE 3-K: 12 starts/hour and LE3-D: 30 starts/hour. Maximum starting time: 30 seconds. LE3-D: an LAD-S2 timer imposes a delay of 40 ms 15 ms on the delta contactor at the moment of changeover to ensure that the star contactor has sufficient breaking time. LE3-K065// LE3-K095// or LE3-D09// (4) 5.5 11 11 11 LE3-D12// LE3-D18// LE3-D35// LE3-D405// LE3-D505// LE3-D805// LE3-D115// LE3-D150//

5.5

5.5

5.5

1.460

4 LE3-D12//

7.5

7.5

7.5

1.460 3.650

3.650

11

18.5

22

22

3.750

15

30

30

30

5.160

18.5

37

37

37

8.160

30

55

59

59

8.150

37

75

75

75

14.000

63

110

110

110

24.500

75

132

132

147

24.500

(1) Protection must be provided by the addition of an overload relay, to be ordered separately. Select appropriate overload relay for setting at 0.58 of the full load rated motor current, see pages 24514/2 and 24514/3. (2) Avoid placing this material in contact with harsh substances (detergents, chlorinated solvents, ketones, alcohol, aromatic hydrocarbons). (3) Standard control circuit voltages. Volts 50/60 Hz 24 42 48 110 115 220 230 240 380 400 415 440 LE3-K B7 D7 E7 F7 M7 P7 U7 Q7 V7 N7 R7 LE3-D B7 D7 E7 F7 FE7 M7 P7 U7 Q7 V7 N7 R7 Other voltages: please consult your Regional Sales Office. (4) Selection according to dimensions and the number of operating cycles, please consult your Regional Sales Office.

"

Dimensions : page 24107/2 24106_Ver2.11-EN.fm/2

Schemes : page 24107/3


Schneider Electric

References

TeSys enclosed starters


Star-delta starters 5.5 to 132 kW, without isolating device

"

Description
The standard version comprises: - LE3-K and LE3-D09 to D35: 1 green Start button I 1 red Stop/Reset button O no pushbuttons on cover.

- LE3-D405 to D150:

Variants (pre-assembled)
Description Application Suffix to be added to the starter reference (1) A04

No pushbuttons on cover

LE3-D09 D35

1 green Start button I 1 red Stop/Reset button O

LE3-D405D150

A06

LE3-D12

//A04
1 blue Reset button R LE3-D09 D805 A05

1 neutral terminal Fitted as standard on starters LE3-D115 and D150

LE3-K065 and K095 LE3-D09 D805

A59

LE3-D12

//A05
Mechanical interlock Fitted as standard on starters LE3-K and LE3-D09 to D35 LE3-D405 to D150 A64

(1) Example: LE3-D09F7A04

Other versions

Possible combinations of 2 variants. Please consult your Regional Sales Office.

Schemes : page 24107/3


Schneider Electric

24106_Ver2.11-EN.fm/3

Characteristics, references TeSys enclosed starters


Star-delta starters 7.5 to 75 kW with isolating device
(1)

"

Characteristics
Conforming to standards Degree of protection to IEC 529 Ambient air temperature Operating positions Material IEC 947-4-1 and IEC 439-1, VDE 0660-102, EN 60947 IP 657: LE6-D09 to D18 and IP 557: LE3-D326 to D806 For operation: - 5 to + 40 C Identical to positions for contactors Polycarbonate (2): LE6-D. Sheet steel: LE3-D

References
Standard power ratings of squirrel cage motors Mains voltage - Delta connection 220 V 380 V 415 V 440 V 400 V kW kW kW kW Fuses to be fitted by the customer Size Type aM A Basic reference. Complete with code indicating control circuit voltage Standard (3) voltages Weight

kg

Maximum operating rate: 30 starts/hour. Maximum starting time: 30 seconds. An LAD-S2 timer imposes a delay of 40 ms 15 ms on the delta contactor at the moment of changeover to ensure that the star contactor has sufficient breaking time. LE6-D09//

7.5

7.5

7.5

10 x 38

20

F7 P7 V7

3.900

5.5 LE6-D12//

11

11

11

10 x 38

25

LE6-D12//

F7 P7 V7

3.900

11

18.5

22

22

14 x 51

40

LE6-D18//

F7 P7 V7

4.850

15

30

30

30

22 x 58

63

LE6-D326//

F7 P7 V7

7.650

18.5

37

37

37

22 x 58

80

LE3-D406//

F7 P7 V7

16.900

30

55

59

59

22 x 58

125

LE3-D506//

F7 P7 V7

17.000

37

75

75

75

160

LE3-D806//

F7 P7 V7

27.500

(1) Protection must be provided by the addition of an overload relay, to be ordered separately. Select appropriate overload relay for setting at 0.58 of the full load rated motor current, see pages 24514/2 and 24514/3. (2) Avoid placing this material in contact with harsh substances (detergents, chlorinated solvents, ketones, alcohol, aromatic hydrocarbons). (3) Standard control circuit voltages. Volts 24 42 48 110 115 220 230 240 380 400 415 440 50/60 Hz B7 D7 E7 F7 FE7 M7 P7 U7 Q7 V7 N7 R7 Other voltages: please consult your Regional Sales Office.

Dimensions : page 24109/2

Schemes : page 24109/3 :


Schneider Electric

24108_Ver2.10-EN.fm/2

References

TeSys enclosed starters


Star-delta starters 7.5 to 75 kW with isolating device

"

Description
The standard version comprises: - LE6-D09 to D18: 1 green Start button I 1 red Stop/Reset button O - LE3-D326 to D806 Protection LE6-D09 and D12 LE6-D18 to LE3-D806 no pushbuttons on cover Power circuit 1 3-pole isolating device 1 3-pole isolating device Control circuit + 1 additional pole LA8-D254 + 1 circuit breaker GB2-CB08

Variants (pre-assembled)
Description Application Suffix to be added to the starter reference (1) A04

No pushbuttons on cover

LE6-D09 D18

1 green Start button I 1 red Stop/Reset button O LE6-D12// A04

LE3-D326 to D806

A06

1 blue Reset button R

LE6-D09 LE3-D806

A05

1 neutral terminal

LE6-D09 D806

A59

LE6-D12// A05

Mechanical interlock Fitted as standard on starters LE6-D09 to D18

LE3-D326D806

A64

(1) Example: LE6-D09F7A04.

Schemes : page 24109/3


Schneider Electric

24108_Ver2.10-EN.fm/3

Selection guide

Motor starters - open version


Installation system Tego Power for motor power-starter components

Functions

Quickfit technology for assembly and connection of motor starter components without using tools with spring terminals

Types of product

Power connection kit

Power/control splitter box

Control connection module

For contactors

Model d

Type of starter

Direct and reverser

Direct

Reverser

Coil control

Yes

No

Yes

No

Use with motor power-starters

8 starters (1)

Number of motor power-starters Connecton of earth cables Connection via

2, 3, 4 limited to 63 A

HE10 connector or adaptor for comm. module

Type of connection or bus

Number of channels

References

LAD-3/

APP-2R/

APP-2D//

Pages

15022/5 (1) With LAD - 3B upstream terminal block

0124Q_Ver2.10-EN.fm/2

Schneider Electric

Assemble and connect motor power-starter components with screw terminals

Communicate with the processing part

Connection blocks

Modular sub-bases

Communication modules

Model d

Model k

Models d and k

Direct

Reverser

Direct

Reverser

Direct and Reverser

Yes

No

Yes

No

Yes

No

Yes

No

Up to 8 starters with the connection kit

2 or 4

Mounting bracket

Connector to PLCs HE 10 Terminal block AS-i bus Other buses

Screw or spring

AS-i 2 addresses

Interbus S and S optical Profibus DP and DP optical Cam Open, Device Net

8I/8O

16I/8O

8I/8O

16I/8O

32I/24O

APP-1D/

APP-1K/

APP-1B/

APP1CH
15023/3

APPAPP1CV/1CE 1CAS2

APPAPP1C//0/3 1C//2/5

15022/5

Schneider Electric

0124Q_Ver2.10-EN.fm/3

Presentation

Motor starters - open version


Installation system Tego Power for motor power-starter components

General presentation
Tego Power is a modular system which standardises and simplifies the implementation of motor power-starters with its prewired control and power circuits. Hence, installation of a motor power-starter is quick, simple, safe and flexible with no wires needed for connection. In addition, this system enables the motor power-starter to be customised at a later date. The system reduces maintenance time and optimises panel space, by reducing the number of terminals, the amount of ducting and intermediate interfaces. Two solutions are offered : / A solution using Quickfit technology for TeSys motor power-starter components with spring terminals : model d contactors (9 to 32 A) and the GV2-ME motor circuit-breaker. / A solution for TeSys motor power-starter components with screw terminals : model d (9 to 18 A) and model k (6 to 12 A) contactors and GV2 motor circuit-breakers. Tego Power Design definition software This software on CD-ROM enables the motor power-starter application to be graphically defined according to the circuitbreakers and contactors used. It determines which Tego Power products are required for the application. Referencing labels can also be created for the starters.

System for Quickfit technology TeSys motor powerstarters with spring terminals The motor power-starters concerned are those formed by combining : - GV2-M circuit-breakers - with 9 to 32 A model d (LC1) contactors. Consisting of simple parts, Tego Power Quickfit technology is used to create motor starter assemblies up to 15 kW/ 400 V. The main components which make up this range are : / For the power circuit - a power kit comprising, for each starter, a plate 1 for mounting the contactor and the circuit-breaker, and the two power connection modules 2 - a power splitter box 5 for 2, 3 or 4 starters - an upstream terminal block 6 for a power supply up to 63 A (16 mm2), - a downstream terminal block 7 for connecting the motor power supply cables and the earth cables (6 mm2). / For the control circuit - a control splitter box 3 for 2, 3 or 4 starters, with control-command data on HE 10 connector. The data on 4 to 8 starters can be fed back directly to the PLC via an 8I/8O or 16I/8O Telefast cable or to a fieldbus module (AS-i, FIP, CAN Open, Device Net, Interbus, Profibus) (see opposite page). - a control circuit connection module 4 which plugs directly into the contactor and the circuit-breaker on each starter. This module concentrates the motor starter control-command data. It integrates the circuitbreaker status data in the prewiring of the contactor control circuit. System for TeSys motor power-starters with screw terminals The motor power-starters concerned are those formed by combining : - GV2 circuit-breakers (mainly GV2-ME and GV2 P) - with 6 to 12 A model k contactors (LC1, LP1, LC2, LP2, LP4, LP5) and 9 to 18 A model d contactors (LC1). The main components which make up this range are : / modular sub-bases 1 for 2 or 4 direct or reversing contactors, consisting of a prefabricated power busbar system and a control-command circuit. These subbases can be combined to form a variable configuration of 2, 4, 6 or 8 direct starters. / the sub-base interconnection kit to interconnect the control and power circuits on two sub-bases. / connection blocks 2 and 3 which perform the following three functions : - ensure the mechanical fixing of the motor starter to the modular sub-base - connect the power terminals of the contactor and circuit-breaker - connect the auxiliary contact and A1-A2 coil terminals to the modular sub-base.

5 4 2

Selection : page 15021/4 15020_Ver2.11-EN.fm/2

Characteristics : page 15025/2

References : page 15021/5

Dimensions, schemes : pages 15026/3 and

15027/2
Schneider Electric

Presentation (continued)

Motor starters - open version


Installation system Tego Power for motor power-starter components

Communication modules
General Communication modules are used to send I/O data from a Tego Power motor power-starter configuration to the PLC. The communication modules is selected according to the type of connection required (see page 15023/2) : - in parallel mode (modules, terminal blocks or HE 10) - or in serial mode on the bus (AS-i bus, Interbus S, Profibus DP, CAN Open or Device Net modules). The communication modules are the same, whether the TeSys motor power-starter system uses spring or screw terminals.

Modules in a TeSys motor power-starter system with spring terminals 1 2 3 Motor power-starters can be connected to a PLC or a bus in two ways : - by direct connection from the control circuit splitter box 3 with 4 starters, with an HE 10 connector (8I/8O) or two HE 10 connectors (16 I and 8 O) - by a Tego Power module 1 using an APP-2CX adaptor plate 2.

Modules in a TeSys motor power-starter system with screw terminals A module 4 is mounted by direct mechanical assembly on the modular sub-base , with no screws or accessories. The electrical connection between the modular subbase and the communication module is made using an HE 10 connector.

Selection : page 15021/4


Schneider Electric

Characteristics : page 15025/2

References : page 15021/5

Dimensions, schemes : pages 15026/3 and

15027/2 15020_Ver2.11-EN.fm/3

Description

Motor starters - open version

Installation system Tego Power for motor power-starter components Components with spring terminals, using Quickfit technology

Tego Power for components with spring terminals


The motor power-starters concerned are those created by combining : - Telemecanique GV2 circuit-breakers (mainly GV2-ME and GV2-P) with an operating limit of 80% of maximum current at 60C ambient temperature, up to 690 V (see page 15025/3) - with 9 to 32 A Telemecanique model d contactors (LC1). The main components which make up this range are : / For the power part - power kits, - power splitter boxes, - upstream and downstream terminal blocks. / For the control-command part - power and control splitter boxes, - control connection modules. Used with communication modules (see pages 15020/3 and 15023/2), these motor power-starters exchange controlcommand data with PLCs or a bus. They can also communicate directly with PLCs via a Telefast HE 10 cable.

Power components / Power kits LAD-3/ Each motor power-starter requires a power kit which consists of a plate 1 and 2 Quickfit technology power connection modules 2 . The plate is used for mounting TeSys model d contactors 3, with spring terminals, direct or reversing, equipped with an a.c. or d.c. coil, 9 to 32 A, and the GV2-ME 4 circuit-breaker only. This plate is mounted on a 35 mm omega rail or screwed onto a base plate. The two power connection modules 2a and 2b are identical whatever the rating of the contactor, up to 32 A. The lower power connection module 2b connects the power between the contactor and the circuit-breaker. The upper power connection module 2a connects the power between the splitter box and the circuit-breaker. / Splitter box LAD-32/ Splitter boxes 5 are available for 2, 3 or 4 starters. They can be combined to create motor power-starters up to 63 A per power supply. A reversing starter occupies a width equivalent to that of 2 direct starters. Direct supply of power to the splitter boxes is possible up to 25 A (4 mm2). / Upstream terminal block LAD-3B The upstream terminal block 6 performs two functions : - power supply up to 63 A (16 mm2), - power supply between two connected splitter boxes. The upstream terminal block plugs into the splitter box using Quickfit technology. It is positioned on the splitter box or straddling the two splitter boxes, and takes up a width equivalent to two motor power-starters. / Downstream terminal block LAD-33 The downstream terminal block 7 performs two functions : - connects motor power supply cables up to 6 mm2, - connects the motor earth cables. In addition, the terminal block enables quick connection and disconnection for maintenance, avoiding the risk of phase reversal. The downstream terminal block plugs into the downstream spring terminals on the contactor using Quickfit technology.

Selection : page 15021/4

Characteristics : page 15025/2

References : page 15021/5

Dimensions, schemes : pages 15026/3 and 15027/2


Schneider Electric

15021_Ver3.10-EN.fm/2

Description (continued)

Motor starters - open version

Installation system Tego Power for motor power-starter components Components with spring terminals, using Quickfit technology

Components for control-command / Power and control splitter boxes APP-2R // These have the same characteristics as the power splitter box 1b described on the opposite page. They are used to gather control-command data from the motor power-starters. Power and control splitter boxes 1 for 2, 3 or 4 starters can be combined to create up to 8 starters. A reversing starter takes up the space of two direct starters. The mechanical assembly of 2 splitter boxes connects the control-command data and the power supply to the coil control. The coil control can be a.c. or d.c., up to 250 V. Three types of splitter box are available : - APP-2R/E with one 30-way HE 10 connector for connection to the APP-1C/ Tego Power communication module, using the APP-2CX adaptor plate (these splitter boxes are also available for 2 or 3 starters) - APP-2R4H1 with one HE 10 connector with 8I/8O, for direct connection to the PLC via a Telefast cable : the data communicated to the PLC for each starter is the coil control (1 output) and the contactor status (1 input), for up to 8 starters - APP-2R4H2 with two HE 10 connectors (one for 16 inputs, the other for 8 outputs) for direct connection to the PLC via a Telefast cable : the data communicated to the PLC for each starter is the coil control (1 output), the contactor status (1 input) and the circuit-breaker status (1 input), for up to 8 starters The range is completed by splitter boxes which have an APP-2R/AS AS-i bus link. Parallel link splitter boxes can be connected together up to 63 A, with no limit to the number of starters. There are 2 types : - 2 starters, 2I/1O per APP-2R2AS starter : the data communicated to the PLC for each starter is the coil control (1 output), the contactor status (1 input) and the circuit-breaker status (1 input) - 4 starters, 1I/1O per APP-2R4AS starter : the data communicated to the PLC for each starter is the coil control (1 output), the contactor status (1 input). Control splitter boxes 1b are also available on their own, as replacement parts. They are mounted, by the user, on LAD-32 / power splitter boxes. / Control circuit connection modules APP-2D // The control circuit connection module 2 plugs directly into the control terminals on the GV2 circuit-breaker and the contactor, using Quickfit technology. It connects to the control splitter box 1a via its upper part. Mechanical locking ensures good quality connections and a firm hold. It is compatible with all contactor ratings up to 32 A. These modules are available in 4 versions : with or without contactor coil control relay, and direct or reversing starter. The version without relay is designed to control the contactor coils with no interface, generally at 24 V d.c. The connection module integrates, in its lower part, the external shunt 3 for connecting an external contact in series with the contactor coil or forced local control (according to the scheme on page 15027/2). The second item of contactor status data is available on a connector 4 which is left to the choice of the user.

Selection : page 15021/4


Schneider Electric

Characteristics : page 15025/2

References : page 15021/5

Dimensions, schemes : pages 15026/3 and 15027/2

15021_Ver3.10-EN.fm/3

Selection

Motor starters - open version

Installation system Tego Power for motor power-starter components Components with spring terminals, using Quickfit technology

Selection of a power and control splitter box


Three types of splitter box are available, depending on the required connection to the PLC : / Direct connection to the PLC via HE 10 connector and Telefast cable. / Connection to the control system via Tego module. / Connection to the control system via AS-i bus. Direct connection via 8I/8O HE 10 connector An HE 10 connector, on the top of the APP-2R4H1 control splitter box 1, provides the contactor status (1 input) and the coil control (1 output) for each starter. This HE 10 connector can feed data back to up to 8 starters. The Telefast cable 3 is chosen according to the PLC environment (see pages 15024/2 and 15024/3).
8E/8S 3 HE10 1 8E/8S 3 APE1R1628 3 16E 16S 3 API API

TSX DMZ16DTK

or

ABE-1ACC02

Direct connection via 16I/8O HE 10 connectors Two HE 10 connectors, on the top of the APP-2R4H2 control splitter box 2, provide the circuit-breaker status (1 input), the contactor status (1 input) and the coil control (1 output) for each starter. These HE 10 connectors can feed data back to up to 8 starters. The Telefast cables 3 are chosen according to the PLC environment (see pages 15024/2 and 15024/3).
16E 3 HE10 2 HE10 8S 3 ABE7ACC02 16 S 3 API API

TSX DMZ64DTK

Connection via Tego module APP-1C/// The APP-2R/E control splitter boxes 1 (2, 3 or 4 starters) are connected to the PLC via a Tego module APP-1C/// 2. An APP-2CX adaptor 3 must be used to connect the module to the control splitter box. These modules can feed data back to up to 8 starters. The module is selected according to the type of connection required : terminal block, HE 10 connector or bus (see page 15023/2). The advantages of using Tego modules are : - the ability to use terminal block connection, - when connecting using an APP-1CH HE 10 connector and APP-1CAS2 AS-i connector, it is possible to choose, for each starter, feedback of the status either of the contactor, or the circuit-breaker, and to use the available I/O for external data, if there are fewer than 8 starters, or to access the Interbus S, Profibus DP, CAN Open, Device Net buses. Direct connection via AS-i bus, with no module There are two versions for direct connection of the control splitter box to the AS-i bus : - APP-2R2AS splitter box for 2 starters, providing the circuit-breaker status (1 input), the contactor status (1 input) and control of the coil (1 output) for each starter, - APP-2R4AS splitter box for 4 starters, providing the contactor status (1 input) and control of the coil (1 output) for each starter. In both cases, it is possible to connect as many starters as required, up to 63 A.

Description : pages 15021/2 and 15021/3

Characteristics : page 15025/2

References : page 15021/5

Dimensions, schemes : pages 15026/3 and 15027/2


Schneider Electric

5021_Ver3.10-EN.fm/4

References

Motor starters - open version

Installation system Tego Power for motor power-starter components Components with spring terminals, using Quickfit technology

Splitter boxes
Description Type of control-cmd No. of I/O Extension connection on per by control sys. side starter LAD-32/ No. of starters 2 3 4 4 4 2 3 4 2 4 Reference Weight kg LAD-322 LAD-323 LAD-324 APP-2R4H1 APP-2R4H2 APP-2R2E APP-2R3E APP-2R4E APP-2R2AS APP-2R4AS 0.120 0.180 0.240 0.348 0.358 0.178 0.263 0.348 0.200 0.380

63 A power splitter box 63 A power and control splitter box

1 x HE10 8I/8O 1 x HE10 16I and 1 x HE10 8O Via module APP-1C/// (2) AS-i

1I/1O (1) APP-2R/E up to 8 starters 2I/1O (1) APP-2R/E up to 8 starters APP-2R/E up to 8 starters 2I/1O 1I/1O APP-2R/AS APP-2R/AS

APP-2R4H1

Power connection components for one starter


Description Assembly and power connection kit Reversing kit (3) LAD-35 Composition of Kit 1 LAD-31 plate for GV2-ME and 2 LAD-34 power connection modules 1 set of busbars and 1 mechan. interlock Reference LAD-35 LAD-32 Weight kg 0.078 0.040

Power connection accessories for one starter


Description Upstream term. block Max. connection Use cross-section 16 mm2 Power supply of 1 or 2 power splitter boxes or power control splitter box Connection of motor cables Reference LAD-3B LAD-33 Weight kg 0.212 0.050

Dnstr.term.bl. 6 mm2 LAD-3B LAD-33

Control connection module for one starter


Description Control connection module (integrating contact block GV-AE20) Model d coil voltage " 12... 240 V or $ 24...125 V $ 24...48 V Type of coil control relay Electromechanical (4) Without relay (5) Type of starter Reference Weight kg 0.120 0.230 0.110 0.220

Direct APP-2D1 Reversing APP-2D2 Direct APP-2D1D Reversing APP-2D2D

Spare or replacement parts


Description Type of control-cmd No. of I/O connection on per control sys. side starter No. of starters 1 Sold in lots of 10 Unit reference LAD-31 Weight kg 0.042

Plate for mounting a GV2-ME circuit-breaker Power connection module Control-command splitter box (single, for mounting on a power splitter box)

1 x HE10 8I/8O 1 x HE10 16I and 1 x HE10 8O Per module APP-1C///(2) AS-i

1I/1O 2I/1O 2I/1O 1I/1O

1 4 4 2 3 4 2 4

10 1 1 1 1 1 1

LAD-34 APP-2R4H3 APP-2R4H4 APP-2R2C APP-2R3C APP-2R4C APP-2R2A APP-2R4A

0.018 0.108 0.118 0.058 0.086 0.108 0.080 0.140

APP-2D1/

Replacement electromechanical relay 1 10 APP-2ER 0.010 (for control connection module) (1) Cables with 20-way Telefast HE10 connector, in accordance with selection table on page 15024/3. (2) Connection to an APP-1C/// module via APP-2CX adaptor (see page 15023/3). (3) To create a model d reverser, use 2 LC1-D contactors, 1 assembly and power connection kit and 1 reversing kit. (4) Relay supplied mounted on the front panel of the control connection. (5) The use of model d low consumption contactors is recommended. Description : pages 15021/2 and 15021/3
Schneider Electric

Selection : page 15021/4

Characteristics : page 15025/2

Dimensions, schemes : pages 15026/3 and 15027/2

15021_Ver3.10-EN.fm/5

Presentation, description

Installation system
Tego Power for motor power-starter components

Presentation
Tego Power is a modular system which standardises and simplifies the implementation of motor power-starters with its prewired control and power circuits. Hence, installation of a motor power-starter is quick, simple, safe and flexible with no wires needed for connection. In addition, this system enables the motor power-starter to be customised at a later date. The system reduces reducing maintenance time and optimises panel space. The main components which make up this range are : - modular sub-bases - connection blocks - communication modules The motor power-starters concerned are those which combine : - Telemecanique GV2 circuit-breakers (mainly GV2-M and GV2-P) with an operating limit of 80% of maximum current at an ambient temperature of 60C, up to 690 V (see page 15013/3), - with Telemecanique contactors, series K (LC1, LP1, LC2, LP2, LP4, LP5) from 6 to 12 A and series D (LC1, LP1, LP4) from 9 to 18 A.

Description
4 1 2 3

1 Power connection 2 Contactor coil power supply 3 Protective cover 4 Mounting clips

p Tego Power Design definition software This software on CD-ROM enables the motor powerstarter application to be graphically defined depending on the circuit-breakers and contactors used. It determines which Tego Power products are required for the application. Referencing labels can also be created for the starters. p Modular sub-bases There are 3 types of Tego Power modular sub-base : - sub-bases with 2 and 4 starters, APP-1B2 and APP1B4, which can receive series K direct and -reversingcontactors, and series D direct contactors equipped with an a.c. or d.c. coil. - APP-1B1 sub-base, for a series D reversing starter. Sub-bases can be combined to form a variableconfiguration of 2, 4, 6 or 8 direct starters. One reversing starter occupies the same space on a -subbase as two direct starters. Each sub-base comprises a prefabricated busbarsystem and a control-command circuit. Busbar system A 3-phase prefabricated busbar system is integrated into the sub-base and can be used to connect the circuit-breaker to the power supply without the need for wiring simply by tightening the power screw terminals. The maximum operating currents are as follows : - 18 A per starter, - 32 A per sub-base, - 63 A per power supply 1. Protective covers 3 for power terminals, for the unused starter slots, are supplied with the sub-bases. Control-command circuit For each motor starter, a prefabricated control circuit is integrated into the sub-base and is used to send data of the following 3 types to the PLC : - circuit-breaker auxiliary contact, - contactor auxiliary contact, - contactor coil control. This I/O data is grouped on an HE 10 connector. p Sub-base interconnection kit The APP-1EL connection kit is necessary for the interconnection of the control and power circuits on two subbases. It contains the following accessories : - commoning link for the power, - commoning link for the coil control voltage, - ribbon cable with HE 10 connectors for connecting the sub-base I/O, - mechanical locking clips. p Accessories Mounting clips 4 for mounting and dismantling the sub-base fitted with motor power-starters. 2 mounting clips should be used for sub-bases with 2 starters or inverter and 4 for sub-bases with 4 starters. Fixing bracket for earth wires of motor cables. Up to 4 cables can be connected and linked in order to provide earth continuity.
Dimensions, schemes : pages 15015/2 to 15016/3
Schneider Electric

Selection : pages 15011/2 and 15011/3

Characteristics : pages 15013/2 to 15013/5

References : pages 15014/2 and 15014/3

5010 Ver4.00-EN.fm/2

Description (continued)

Installation system
Tego Power for motor power-starter components

Description (continued)
p Connection blocks
Connection blocks perform the following 3 functions : - ensure the mechanical fixing of the motor starter to the modular sub-base - connect the power terminals of the contactor 3 and circuit-breaker 4 - connect the auxiliary contact and A1-A2 coil terminals to the modular sub-base These connection blocks comprise two sub-assemblies : - an upper part 1 for connecting the circuit-breaker and contactor - a lower part 2 under the contactor. It is available for 2 types of configuration : - without interface cassette for direct connection of the contactor coil control output, - with interface cassette 6 for relaying control of the contactor coil. All lower parts of the connection block 2 integrate : - the phase wiring guide 2b, - an external shunt 2a for connecting an external contact in series with the contactor coil or forced local control (according to scheme, see page 15016/2). A set of connection blocks adapted to each contactor or reversing contactor used is available (see the selection guide on page 15011/2). 3 An additional GV2 auxiliary contact block must be mounted on each circuit-breaker, reference GV2-AE20 or GV2-AE11 5. 6

5 8

p Interface cassettes 6
Some connection blocks have an interface cassette. Its role is to provide the interface between the low voltage PLC output (c 24 V) and the contactor coil (a 24 to 240 V). These interface cassettes comprise an electromechanical relay. They can be ordered as a replacement part under the reference APP-1ER.

2a 2b

p Communication modules 7
Communication modules are used to send I/O data from a Tego Power motor power-starter configuration to the PLC. The communication module is selected depending on the type of connection required (see page 15011/3) : - in parallel mode (modules, terminal blocks or HE 10 connector) - or in series mode on the bus (AS-i bus, Interbus S, Profibus DP, CAN Open or Device Net modules). The connection between the modular sub-base and the communication module is made using an HE 10 connector 8.

Selection : pages 15011/2 and 15011/3


Schneider Electric

Characteristics : pages 15013/2 to 15013/5

References : pages 15014/2 and 15014/3

Dimensions, schemes : pages 15015/2 to 15016/3

15010 Ver4.00-EN.fm/

Selection

Installation system
Tego Power for motor power-starter components

Selecting Tego Power sub-bases

Selection of the sub-base depends on several parameters : The type of contactor The sub-bases are compatible with series D direct starter contactors and series K direct and reversing starter contactors. Series K and D contactors can be installed together on a single sub-base. A special sub-base is available for a series D reversing starter. Important : 2 direct contactors (LC1 or LP1) must be used with the integrated mechanical and electrical interlocks (LA9-D0902) to create a series D reversing starter. LC2 or LP2 reversing contactors are not suitable.

/ The number of starters to be installed / The maximum current

For a single configuration, combinations of 2, 4, 6 and 8 starters are possible by joining sub-bases together. The following maximum current restrictions must be observed : - 18 A per starter (a reverser is counted as 1 starter), - 32 A per sub-base, with either 2 or 4 starters, - 63 A per power supply. For example : a configuration with 3 sub-bases, sub-base A (4 starters), sub-bases B and C (2 starters each) : - IA, IB and IC, the current for each sub-base must not exceed 32 A, - IA + IB + IC must not exceed 63 A. Otherwise, a second power supply is required on sub-base C.

Modular sub-base selection table Type of sub-base Modular sub-base for Series D contactor direct reversing (1) APP-1B4 APP-1B2 APP-1B1 Series K contactor direct reversing APP-1B4 APP-1B2 APP-1B4 APP-1B2

Sub-base with 4 starters Sub-base with 2 starters Sub-base with D reverser

Selecting connection blocks and contactors


Selection of the breaker-contactor connection block depends on the type of contactor to be installed and, if required, on the interfacing of the contactor coil control. Connection block selection table Adaptable contactor Voltage Coil control interfacing
Connection block for

APP-1D1M APP-1D2M // Relay // // APP-1D1B APP-1D2B $ 12...250 V LP1-D0910// Relay LP1-D1210// APP-1D1BD APP-1D2BD LP1-D1810// Low LP4-D0910// Relay APP-1D1B4 APP-1D1B4D consumption LP4-D1210// $ 12...250 V LP4-D1810// " 12240 V LC1-K0610// Relay APP-1K1M LC1-K0910// LC1-K1210// APP-1K1B // Relay $ 12...250 V LP1-K0610 LP1-K0910// LP1-K1210// APP-1K1BD " 12240 V LC2-K0610// Relay APP-1K2M LC2-K0910// LC2-K1210// $ 12...250 V LP2-K0610// Relay APP-1K2B LP2-K0910// LP2-K1210// (1) To create a D reverser, 2 LC1-D or LP1-D direct contactors must be used with the integrated mechanical and electrical

" 12240 V

Reference (2) LC1-D0910 LC1-D1210 LC1-D1810

Series D contactor direct reversing (1)

Series K contactor direct reversing

interlocks (LA9-D0902). (2) Complete the reference with the compatible voltage code. Presentation, description : pages 15010/2 and 15010/3 Characteristics : pages 15013/2 to 15013/5 References : pages 15014/2 and 15014/3 Dimensions, schemes : pages 15015/2 to 15016/3

References

Installation system
Tego Power for motor power-starter components

Modular sub-bases
Description Sub-bases with 4 starters Number of protective covers supplied (1) 2 Reference APP-1B4 Weight kg 1.125

Sub-base with 2 starters

APP-1B2

0.663

Sub-base with D reverser (2)

APP-1B1

0.690

Connection blocks (3)


Description APP-1B4 Connection blocks LC1-D0910 LC1-D1210 LC1-D1810 LP1-D0910 LP1-D1210 LP1-D1810 LP4-D1210 LP4-D1810 For contactors Voltage V Type of starter Direct Coil interfacing Relay Reference Weight kg APP-1D1M 0.120

a 12240

c 12...250

Direct

Relay

APP-1D1B APP-1D1BD APP-1D1B4 APP-1D1B4D APP-1D2M

0.120 0.110 0.120 0.110 0.320

c 12...250

Direct

Relay

LC1-D0910 LC1-D1210 LC1-D1810 LP1-D0910 LP1-D1210 LP1-D1810 APP-1ppp LC1-K0610 LC1-K0910 LC1-K1210 LP1-K0610 LP1-K0910 LP1-K1210 APP-1Ep LC2-K0610 LC2-K0910 LC2-K1210 LP2-K0610 LP2-K0910 LP2-K1210

a 12240

Reversing Relay (2) Reversing Relay (2) Direct Relay

c 12...250

APP-1D2B APP-1D2BD APP-1K1M

0.350 0.340 0.100

a 12240

c 12...250

Direct

Relay

APP-1K1B

0.100

a 12240

Reversing Relay (4) Reversing Relay (4)

APP-1K2M

0.290

c 12...250

APP-1K2B

0.290

Accessories
Description Type of relay Electromechanical Sold in lots of 1 1 Unit reference APP-1ER APP-1EL Weight kg 0.017 0.055

APP-1YF1

Replacement interface cassettes Inter sub-base connection kit

Mounting clips for sub-base

APP-1YF1

0.160

Fixing bracket for earth cables

APP-1YM1

0.158

APP-1YM1

(1) Protective covers, supplied with the sub-bases, for power terminals of unused starter slots. (2) To create a D reverser, 2 LC1-D or LP1-D direct contactors must be used with the integrated mechanical and electrical interlocks (LA9-D0902). (3) A connection block comprises an upper block and a lower block. Some lower blocks have an interface cassette with a electromechanical or solid state relay. (4) Electrical locking is possible by adding front attachments to the connectors, connected to external links. Selection : pages 15011/2 and 15011/3 Characteristics : pages 15013/2 to 15013/5 Dimensions, schemes : pages 15014/2 to 15016/3
Schneider Electric

Presentation, description : pages 15010/2 and 15010/3

5014 Ver4.00-EN.fm/2

Selection (continued)

Installation system
Tego Power for motor power-starter components

Selecting Tego Power communication modules


Selection of the communication modules depends on the type of connection required : - by removable screw or spring terminal blocks, - parallel via HE 10 connector and Telefast cable, - serial via Bus (AS-i bus, Interbus S and optical S, Profibus DP and optical DP, CAN Open or Device Net modules)

/ Terminal block connection

/ Parallel connection via HE 10 connector / Serial connection via Bus //

APP-1CV and APP-1CE modules are 16 input/8 output - screw or spring - removable terminal block modules which can be used for wire-to-wire connection of data from the circuit-breaker and contactor contacts as well as the coil control outputs from each motor starter. The removable terminals are included with the modules. The APP-1CH 1 module is an 8 input/8 output module, fitted with an HE 10 connector for fast connection to PLCs using a prefabricated Telefast cable (see selection guide, page 15012/2). Connection to a TSX Micro is direct, using the 8 input/8 output module TSX DMZ16DTK 2 and the ABF-H20H 0 or TSX CDP 3 3 Telefast cable.

//

The APP-1CH (HE10 connector) and APP-1CAS2 (AS-i 8I/8O) modules are fitted with a 4-switch system providing the following selections : - switches C and D : option to feed back to the PLC, either data from the circuit-breaker contact or from the contactor on each of the 8 starters - switch E : an external input can be selected for each of the 4 end starters (no. 5 to 8), if the starter is not being used, - switch F : an external input can be selected for each of the 4 end starters (no. 5 to 8), if the starter is not being used. The position of switches C, D, E, F can be defined using Tego Power Design software. Communication module selection table Type of connection Number of I/O available for APP-1B sub-base

/ Comments on the 8I/8O modules

The APP-1CAS2 AS-i module is an 8 input/8 output module on AS-i Bus (2 addresses). The Interbus S APP-1CIB0 and optical S APP-1CIB3 , Profibus DP APP-1CPF0 and optical DP APP-1CPF3, CAN Open APP-1CCO0 and Device Net APP-1CDN0 modules are 16I/8O modules for connecting APP-1B sub-bases. The Interbus S APP-1CIB2 and optical S APP-1CIB5, Profibus DP APP-1CPF2 and optical DP APP-1CPF5, CAN Open APP-1CCO2 and Device Net APP-1CDN2 modules are 32I/24O modules in total, ie. : - 16I/8O for connecting APP-1B sub-bases with up to 8 starters, - an additional 2 x 8I/8O available on 2 HE 10 connectors 4 compatible with the Telefast cables, and therefore with the HE 10 APP-1CH module. All the optical modules (Interbus S and Profibus DP) enable connection by fibre optic.

Number of HE 10 (1) connectors

Number of I/O per HE 10

Reference module APP-1CH APP-1CV

HE 10 connector Removable screw terminal block

8I/8O 16I/8O

Removable spring terminal block AS-i bus Interbus S bus

16I/8O 8I/8O 16I/8O

0 2 0 2 0 2 0 2 0 2

8I/8O 8I/8O 8I/8O 8I/8O 8I/8O

APP-1CE APP-1CAS2 APP-1CIB0 APP-1CIB2 APP-1CIB3 APP-1CIB5 APP-1CPF0 APP-1CPF2 APP-1CPF3 APP-1CPF5 APP-1CCO0 APP-1CCO2

Interbus optical S bus APP-1CIB2 Profibus DP bus Profibus optical DP bus

16I/8O 16I/8O 16I/8O

CAN Open bus Device Net bus

16I/8O 16I/8O

0 APP-1CDN0 2 8I/8O APP-1CDN2 (1) HE 10 connector for connecting either Telefast sub-bases, APP-1CH module, or APE-1B24M Tego Dial Dialbase interface.

Presentation, description : pages 15010/2 and 15010/3

Characteristics : pages 15013/2 to 15013/5

References : pages 15014/2 and 15014/3

Dimensions, schemes : pages 15015/2 to 15016/3

References

Installation system
Tego Power for motor power-starter components

Communication modules
Description Terminal block communication modules Communication modules with connector Communication modules via bus Type of connection or Bus Screw Spring HE 10 No. of HE 10 connectors (1) Reference APP-1CV APP-1CE APP-1CH Weight kg 0.390 0.356 0.343

AS-i (2) Interbus S

2 2 2 2 2 2

APP-1CAS2 APP-1CIB0 APP-1CIB2 APP-1CIB3 APP-1CIB5 APP-1CPF0 APP-1CPF2 APP-1CPF3 APP-1CPF5 APP-1CCO0 APP-1CCO2 APP-1CDN0 APP-1CDN2

0.416 0.530 0.530 0.530 0.530 0.530 0.530 0.530 0.530 0.530 0.530 0.530 0.530

Interbus optical S APP-1CH Profibus DP

Profibus optical DP

CAN Open Device Net

Accessories for communication module


Description Characteristics Sold in lots of Reference Weight kg 0.130

Intelligent HE10 splitter box (16I/16O in 2 x 8I/8O) Self-stripping connector (for 22 units) APE-1R1628

Voltage : 24 V Ue/30 V max. 1 Type of output : 2.6 W tungsten filament pilot light 2-pin, on 5 mm pitch Wire c.s.a. : 0.75 mm2 16

APE-1R1628

APE-1PAD21

0.020

Insulation Displacement Connector (IDC) for AS-i bus

Colour : yellow

LA9-Z32825

0.100

Contact blocks for GV2 motor-circuit breaker


Description Mounting Type of contact N/O + N/C N/O + N/O Sold in lots of 10 10 Unit reference GV2-AE11 GV2-AE20 Weight kg 0.020 0.020

APE-1PAD21

Instantaneous auxiliary contacts

Front

Accessory for creating a D reverser


Description Mechanical interlock (3) Mounting Side, between 2 contactors Type of contact N/C + N/C Reference LA9-D0902 Weight kg 0.060

Tego Power Design definition software


Description Language Support Version Reference Weight kg 0.100

English and CD-Rom 01 French (1) For the connection of additional external I/O. (2) Not compatible with APP-1DppD connection blocks without relays. (3) With integrated electrical interlocking, for LC1-D and LP1-D contactors. Presentation, description : pages 15010/2 and 15010/3
Schneider Electric

Definition software

APP-1C10M

Selection : pages 15011/2 and 15011/3

Characteristics : pages 15013/2 to 15013/5

Dimensions, schemes : pages 15015/2 to 15016/3

15014 Ver4.00-EN.fm/

Choice of connection between the APP-1CH communication module and the PLC
PLC Brand Type Connection Terminal block modularity

Installation system
Tego power for motor power-starter components

Components necessary for the connection of the PLC Compatible PLC cards Communication module APP-1CH 8 I/8 O Telefast cables ABF-H20H//0 or TSX CDP //3 Splitter block APE-1R1628

Telemecanique TSX Micro

8 In + 8 Out

TSXDMZ16DTK

16 In + 16 Out

TSXDMZ64DTK

Telemecanique TSX 16 In + 16 Out Premium

TSXDEY32D2K/64D2K, TSXDSY32T2K/64T2K, TSXDEY16FK TSXBLK71 + TSXDET32// , TSXBLK91 + TSXDST3292

Telemecanique TSX 47-107

16 In + 16 Out

Modicon

Compact 16 In + 16 Out 984/A120

DA0216, DAP216/217, DE0216, DEP217/220

Modicon

Quantum 32 In + 32 Out

DDI353/853, DD0353

April

32 In + 32 Out

QPA3205

IDB3224, QDB3205, 1

Siemens

95U/100U 8 In + 8 Out (included in Telefast cable) 16 In + 16 Out 6EP5//// 1AA00

4218MA12/4318MA11 4418MA11/4518MA11

4828MA13

Siemens

115U

8 In + 8 Out 6EP5//// 1AA00 8 In + 8 Out 6EP5//// 1AA00

4207LA11, 4307LA12, 4417LA11, 4517LA11/21 4204UA14, 4304UA14, 4414UA14, 451-UA14 3211B/0/ -0AA0, 3221B/ 0/-0AA0 4211BL00-0AA0 4221BL00-0AA0 1746OB16/1746IB16

135/ 155U

Siemens

S7-300

8 In + 8 Out 6ES79213AB000AA0

S7-400

8 In + 8 Out 6ES79213AB000AA0

16 In + 16 Out

Allen Bradley

SLC500

32 In + 32 Out

1746IB32, 1746OV32, 1746OB32

15012_Ver3.00-EN.fm/2

Schneider Electric

Telefast cables for connection to the PLC ABF-H20H//0 ABFor H20H //1 TSX-CDP/// ABFH28H//0 ABFS16//H0 ABFH40H//0 H40H//1 ABFR16H //0 R16H//1 M16H //0 ABFH32H//0 ABFM32H//0 ABFA32H//0

Schneider Electric

15012_Ver3.00-EN.fm/3

Characteristics

Installation system
Tego Power for motor power-starter components

Type of sub-base

APP-1B1, APP-1B2, APP-1B4

General environment
Standard Certifications Degree of protection Resistance to incandescent wire Shock resistance Vibration resistance Conforming to IEC 529 Conforming to IEC 695-2-1 Conforming to IEC 68-2-27 Conforming to IEC 68-2-6 and BV/LR gn C IEC 439-1 UL, CSA IP 20 960 11 ms and 15 gn (half sinewave) 5300 Hz : 4 and 3100 Hz : 0.7 Level 3 V/m 10 (261000 MHz) Level 3 kV V C C C mm mm 2 in common mode, 0.6 in differential mode 10 (0.15...80 MHz) -5+60 -5+40 -40 +70 > 30 3 5 3 Nm mm2 mm2 mm2 2.2 16 25 25 2 Nm mm2 mm2 mm2 control power Nm Nm 0.8 1.5 2.5 2.5 1.2 1.7 Wave form : 1.2/50 s - 8/20 s

Withstand to electrostatic discharge Conforming to IEC 1000-4-2 Withstand to radiated fields Immunity to rapid transients Surge withstand Immunity to radio electrical fields Ambient air temperature Space required around sub-base Degree of pollution Conforming to IEC 1000-4-3 Conforming to IEC 1000-4-4 Conforming to IEC 1000-4-5 Conforming to IEC 1000-4-6 Operation in floor-standing enclosure Operation in wall-mounted enclosure Storage For cable access and heat dissipation

Mounting of sub-base using 4 screws Diameter Suitable wire cross-sections Voltage supply for power Number of wires Tightening torque Flexible cable with end Flexible cable without end Solid cable Voltage supply for control coil contactor Number of wires Tightening torque Flexible cable with end Flexible cable without end Solid cable Connection of pins to the circuit breaker or contactor terminals Tightening torque

3-phase power circuit characteristics


Maximum current per power supply per sub-base GV2 operating limit Maximum current per starter Insulation voltage Operating voltage U imp Rated frequency Conditional nominal short-circuit current Isc at 415 V Permissible nominal short time current Conforming to IEC 439-1 Conforming to IEC 439-1 A A A V V kV Hz Conforming to IEC 439-1 Conforming to IEC 439-1 kA kA 63 (single power supply to one or more sub-bases) 32 80% of Imax at 60 C ambient temp. (see table on opposite page) 18 750 690 6 50-60 50 9.1 (for 70 ms)

Control circuit characteristics


Contactor coil control voltage Presentation, description : pages 15010/2 and 15010/3 Selection : pages 15011/2 and 15011/3 V V

" $

5250 24...48 Dimensions, schemes : pages 15015/2 to 15016/3

References : pages 15014/2 and 15014/3

Characteristics (continued) Installation system


Tego Power for motor power-starter components

Table of GV2 circuit-breaker current limitation at 60 C ambient temperature with Tego Power
Circuit-breaker reference GV2-M06 and GV2-P06 GV2-M07 and GV2-P07 GV2-M08 and GV2-P08 GV2-M10 and GV2-P10 GV2-M14 and GV2-P14 GV2-M16 and GV2-P16 GV2-M20 and GV2-P20 GV2-M21 and GV2-P21 (1) Thermal release adjustment range. GV2 ratings (1) 1 - 1.6 A 1.6 - 2.5 A 2.5 - 4 A 4 - 6.3 A 6 - 10 A 9 - 14 A 13 - 18 A 17 - 23 A Maximum current of GV2 with Tego Power 1.28 A 2A 3.2 A 5A 8A 11.2 A 14.4 A 18 A

Characteristics of the interface cassette electromechanical relays


Connection block type APP-1D1 , APP-1D2 , APP-1K1B, APP-1K2B, APP-1ER

Characteristics of the electromechanical relay control circuit (PLC end)


Rated voltage at Us Energisation threshold at 40 C Drop-out voltage at 20 C Maximum operating voltage Maximum current at Us Drop-out current at 20 C Maximum power dissipated at Us Disappearance of voltage

$V $V $V $V
mA mA W ms

24 19.2 2.4 30 15 1 0.36 5

Characteristics of the electromechanical relay output circuit


Type of contact Maximum switching voltage

"V $V
Hz A

1 N/O 250 250 50/60 4

Operating current frequency Maximum current of the contact

Other characteristics of the electromechanical relay


Maximum operating time at Us (including bounce) Between coil energisation and closing of the contact Between coil de-energisation and opening of the contact Maximum switching frequency Mechanical durability Dielectric strength Rated impulse withstand voltage Primary/secondary rated insulation voltage Maximum current for 500 000 operations 24 V - DC 13 230 V - AC 15 Presentation, description : pages 15010/2 and 15010/3 Selection : pages 15011/2 and 15011/3 At no-load At Ie In millions of operating cycles V kV V A A ms 10

ms Hz Hz

5 10 0.5 20 1000 (50/60 Hz) - 1 min. 2.5 300 0.6 0.9 Dimensions, schemes : pages 15015/2 to 15016/3

References : pages 15014/2 and 15014/3

Characteristics (continued) Installation system


Tego Power for motor power-starter components

Characteristics of parallel link communication modules


Type of module Number of channels Inputs Outputs Display of supply voltages (V In, V Out) Input characteristics Supply voltage 8 8 By LED 16 8 By LED APP-1CH APP-1CV, APP-1CE

$V
mA

24 20 160

24 20 320

Max. current per channel mA Total max. current Output characteristics Operating voltage

$V
A

24 100 1 By 30-way, HE 10 connector By 20-way, HE 10 connector and Telefast cable

24 100 1 By 30-way, HE 10 connector

Max. current per channel mA Total max. current Connection to the sub-base Connection to the PLC

Connection to the 24 V supply, connection of external I/O

By removable connector at intervals of 5.08 mm Cable cross-section : 2.5 mm2 without cable end, 1.5 mm2 with cable end Tightening torque : 0.8 Nm

Presentation, description : pages 15010/2 and 15010/3

Selection : pages 15011/2 and 15011/3

References : pages 15014/2 and 15014/3

Dimensions, schemes : pages 15015/2 to 15016/3

Characteristics (continued) Installation system


Tego Power for motor power-starter components

Characteristics of communication via bus modules


Type of module Ambient air temperature C APP-1CAS2 0 C to + 55 C APP-1CIB0/3, APP-1CCO0 APP-1CPF0/3, APP-1CDN0 0 C to + 55 C APP-1CIB2/5, APP-1CCO2 APP-1CPF2/5, APP-1CDN2 0 C to + 55 C

Number of channels Inputs Outputs 8 8 16 8 16 + (2 x 8 external on HE 10) = 32 8 + (2 x 8 external on HE 10) = 24

Power supply Display Current drawn on the Bus mA

Via the AS-i bus By LED (I/O and power supply) < 280 x 2

External by removable connector at intervals of 5.08 mm By LED (I/O communication and faults)

Inputs

V mA

24 5 per input 24 50 per output relay (relay compulsory) S7.0 x 2 By 30-way, HE 10 connector 500 per output By 30-way, HE 10 connector

Outputs

V mA

AS-i profile Connection to the sub-base

Connection of external I/Os

By 2 20-way HE 10 connectors

Connection to the bus

By 2-way removable connector, at intervals of 5.08 mm

APP-1CIB0, AAP-1CIB2 : 2 shielded SUB-D 9 connectors : - male for signal input, - female for signal output. APP-1CPF0, AAP-1CPF2 : Shielded SUB-D 9 connector. APP-1CC0/, AAP-1CDN/ : 5-way connector, at intervals of 5.08 mm. APP-1CIB3, AAP-1CIB5 : Fibre optic connector F-SMA. APP-1CPF3, AAP-1CPF5 : Fibre optic connector HP-SIMPLEX.

Characteristics of the connection kit


Type of kit Commoning link for the power Operating voltage Ue V 690 32 APP-1EL

Max. current per phase A Commoning link for the coil control Operating voltage Ue V

250

Commoning link for the I/O control Operating voltage

$V

24

Presentation, description : pages 15010/2 and 15010/3

Selection : pages 15011/2 and 15011/3

References : pages 15014/2 and 15014/3