Sie sind auf Seite 1von 16

1

A write up based on a substation visit Nelamangala,Banglore


NEED OF SUBSTATION
A substation is an essential component of an electrical generation transmission and distribution
system.They transforms trasnmission voltage from highlevel to low level, or the reverse,or perform any of several
other important functions.Electric power may flow through several substations at different voltage levels between
the generating station and consumer.Generally the operations in the substations is controlled remotely by a control
centre. A substation may include transformers to change voltage levels between high transmission voltages and
lower distribution voltages, or at the interconnection of two different transmission voltages. As central generation
stations became larger, smaller generating plants were converted to distribution stations, receiving their energy
supply from a larger plant instead of using their own generators. The first substations were connected to only one
power station, where the generators were housed, and were subsidiaries of that power station.

2

SUBSTATION EQUIPMENTS







Lightning arresters
Capacitive Voltage Transformers
Wave Trap
Isolators
Shunt Reactors
Bushings
Circuit Breakers
Power Transformers
Relays
Earth Mat
3

LIGHNING ARRESTOR


Fig 1.1
A lightning arrester(Fig 1.1) also known as lightning conductor, is a device used on electrical power
systems and telecommunications systems to protect the insulation and conductors of the system from the damaging
effects of lightning. The typical lightning arrester has a high-voltage terminal and a ground terminal. When a
lightning surge (or switching surge, which is very similar) travels along the power line to the arrester, the current
from the surge is diverted through the arrestor, in most cases to earth.Smaller versions of lightning arresters, also
called surge protectors, are devices that are connected between each electrical conductor in power and
communications systems and the Earth. These prevent the flow of the normal power or signal
currents to ground, but provide a path over which high-voltage lightning current flows, bypassing the connected
equipment. Their purpose is to limit the rise in voltage when a communications or power line is struck by lightning
or is near to a lightning strike.If protection fails or is absent, lightning that strikes the electrical system introduces
thousands of kilovolts that may damage the transmission lines, and can also cause severe damage to transformers
and other electrical or electronic devices. Lightning-produced extreme voltage spikes in incoming power lines can
damage electrical home appliances.There are different types of arrestors like rod gap arrestor, horn gap arrestor,
multigap arrestor, etc. Today the most commonly used arrestor is metal oxide (MOV) arrestor.The metal oxide
arresters are without gaps, unlike the silicon carbide (SIC) arrester. This gap-less design eliminates the high heat
associated with the arcing discharges. The MOV arrester has two-voltage rating: duty cycle and maximum
4

continuous operating voltage, unlike the silicon carbide that just has the duty cycle rating. A metal-oxide surge
arrester utilizing zinc-oxide blocks provides the best performance, as surge voltage conduction starts and stops
promptly at a precise voltage level, thereby improving system protection. Failure is reduced, as there is no air gap
contamination possibility; but there is always a small value of leakage current present at operating frequency.When
a metal oxide arrester is disconnected from an energized line, a small amount of static charge can be retained by the
arrester. As a safety precaution, technicians install a temporary ground to discharge any stored energy.Duty cycle
rating: The silicon carbide and MOV arrester have a duty cycle rating in KV, which is determined by duty cycle
testing. Duty cycle testing of an arrester is performed by subjecting an arrester to an AC rms voltage equal to its
rating for 24 minutes. During which the arrester must be able to withstand lightning surges at 1-minute
intervals.Maximum continuous operating voltage rating: The MOV rating is usually 80 to 90% of the duty cycle
rating.The metal oxide arrestor used in this substation is zinc oxide arrestor. It is used in 400kV line and has a
rating of 390kV.












5

CAPACITOR VOLTAGE TRANSFORMER
A capacitor voltage transformer (CVT), or capacitance coupled voltage transformer (CCVT) is a
transformer used in power systems to step down extra high voltage signals and provide a low voltage signal, for
measurement or to operate a protective relay. In its most basic form the device consists of three parts: two
capacitors across which the transmission line signal is split, an inductive element to tune the device to the line
frequency, and a transformer to isolate and further step down the voltage for the instrumentation or protective relay.
The tuning of the divider to the line frequency makes the overall division ratio less sensitive to changes in the
burden of the connected metering or protection devices.
[1]
The device has at least four terminals: a terminal for
connection to the high voltage signal, a ground terminal, and two secondary terminals which connect to the
instrumentation or protective relay. CVTs are typically single-phase devices used for measuring voltages in excess
of one hundred kilovolts where the use of wound primary voltage transformers would be uneconomical. In practice,
capacitor C
1
is often constructed as a stack of smaller capacitors connected in series. This provides a large voltage
drop across C
1
and a relatively small voltage drop across C
2
.
The CVT is also useful in communication systems. CVTs in combination with wave traps are used for
filtering high frequency communication signals from power frequency. This forms a carrier communication
network throughout the transmission network


Fig 2.1



6

WAVE TRAP
An electronic filtering device designed to exclude unwanted signals or interference from a receiver is known
as wave trap.Line trap also is known as Wave trap. Basically, it is a tuned circuit placed in the antenna path to your
rig, which traps and then dissipates the signal, or at least a bunch of it, from a station, allowing you to reduce
interference between the stations .What it does is trapping the high frequency communication signals sent on the
line from the remote substation and diverting them to the telecom/teleprotectionpanel in the substation control
room (through coupling capacitor and LMU). This is relevant in Power Line Carrier Communication (PLCC)
systems for communication among various substations withoutdependence on the telecom company network. The
signals are primarily teleprotection signals and in addition, voice and data communication signals. The Line trap
offers high impedance to the high frequency communication signals thus obstructs the flow ofthese signals in to
the substation busbars. If there were not to be there, then signal loss is more and communication will be
ineffective/probably impossible.





7


Isolator

Fig 4.1
An isolator is a switch used to isolate a section of a circuit from any energised conductors, by presenting a
visible break in the circuit. Isolators are not designed to break load currents (unless fitted with optional arc-breaking
feature) or to break fault currents. In high-voltage systems, isolators are used in conjunction with circuit breakers -
with the isolators opened after a circuit breaker has opened the circuit, and closed before the circuit breaker closes
the circuit.
For example, before one can perform maintenance work on, say, a high-voltage circuit breaker, the
following sequence is followed the circuit breaker is opened, breaking the circuit,isolators located on either side of
the circuit breaker are opened, presenting a visible break between the isolator and energised lines.
Here we are using the isolator for isolation of apparatus circuit breaker,transformers, and transmission lines,
for maintenance

8

SHUNT REACTORS

Shunt Reactor and Transformer both appear similar in construction. Reactors are also often equipped with Fans for
cooling similar to Power Transformers.However, there are major differences between the two. While a Power
Transformer is designed for efficient power transfer from one voltage system to another, a shunt reactor is intended
only to consume reactive Vars.Thus, there are more than one winding on a Power Transformer with magnetic core
which carry the mutual flux between the two. In reactor there is just one winding. The core is not therefore meant
only to provide a low reluctance path for flux of that winding to increase the Inductance.In case of a Power
Transformer, primary Ampere-Turns (AT) is sum of exciting AT and secondary AT. AT loss (in winding
resistance, eddy loss and hysteric loss) is kept to as minimum as possible. Exciting AT is small compared with the
secondary AT. Rated current is based on the load transfer requirement.

Fig 5.1




9

Bushing
An electrical bushing is an insulated device that allows the safe passage of electrical energy through an earth
field.When the conductive material is insulated and passes through any earthed material, it is known an electrical
bushing. A typical bushing design has a 'conductor', (usually of copper or aluminium, occasionally of other
conductive materials), surrounded by insulation, except for the terminal ends. In the case of a bus bar, the conductor
terminals will support the bus bar in its location. In the case of a bushing, a fixing device will also be attached to the
insulation to hold it in its location. Usually, the fixing point is integral or surrounds the insulation over part of the
insulated surface. The insulated material between the fixing point and the conductor is the most highly stressed
area. The design of any electrical bushing must ensure that the electrical strength of the insulated material is able to
withstand the penetrating 'electrical energy' passing through the conductor, via any highly stressed areas.
















10

CIRCUIT BREAKER

A circuit Breaker is a piece of equipment which can make or break a circuit either manually or by remote control
under normal condition.It also break a circuit automatically under fault condition.
Accordingly the circuit breakers are classified into
Oil circuit breaker :
This employ some insulating oil for arc extinction
Air Blast circuit breakers
In this high pressure air blast is used for extinguishing the arc
Vaccum circuit breaker
Here vaccum is used for arc extinction
Sulphur hexafluoride SF6 circuit Breaker
Sf6 gas is used as the arc quenching medium.The contacts of the breaker are opened in a high pressure flow of sf6
gas and arc is struck between them.It consists of fixed and moving contacts enclosed in a chamber containing SF6
gas.In the closed position of the breaker ,the contacts remain surrounded by the SF6 gas .When the breaker operates
the moving contact is pulled apart and arc is struck between the contacts.the high pressure flow of SF6 rapidly
absorbs the free electrons in the arc path to form immobile negative ions,then they build up high dielectric strength
and causes the extinction of arc.the pressure of sf6 gas is maintained at 14 kg/cm2.SF6 breakers have low
maintenance cost ,and minimum auxillary requirements.SF6 breakers have been developed for voltages 115kv to
230kv,power ratings 10MVA to 20MVA and interrupting time less than 3 cycles
11

The following issues are associated with SF
6
circuit breakers:
Toxic lower than order gases
When an arc is formed in SF
6
gas small quantities of lower order gases are formed. Some of these
byproducts are toxic and can cause irritation to eyes and respiratory systems.
Oxygen displacement
SF
6
is heavier than air, so care must be taken when entering low confined spaces due to the risk of oxygen
displacement.
A transformer is a static machine used for transforming power from one circuit to another without changing
frequency.





















12

Power Transformer
Generation of Electrical Power in low voltage level is very much cost effective. Hence Electrical Power are
generated in low voltage level. Theoretically, this low voltage leveled power can be transmitted to the receiving
end. But if the voltage level of a power is increased, the electric current of the power is reduced which causes
reduction in ohmic or I
2
R losses in the system, reduction in cross sectional area of the conductor i.e. reduction in
capital cost of the system and it also improves the voltage regulation of the system. Because of these, low leveled
power must be stepped up for efficient electrical power transmission. This is done by step up transformer at the
sending side of the power system network. As this high voltage power may not be distributed to the consumers
directly, this must be stepped down to the desired level at the receiving end with help of step down transformer.
These are the use of electrical power transformer in the Electrical Power System.

Fig 8.1
Two winding transformers are generally used where ratio between High Voltage and Low Voltage is greater than 2.
It is cost effective to use auto transformer where the ratio between High Voltage and Low Voltage is less than 2.
Again Three Phase Single Unit Transformer is more cost effective than a bank of three Single Phase Transformer
unit in a three phase system. But still it is preferable to use later where power dealing is very large since such large
size of Three Phase Single Unit Power Transformer may not be easily transported from manufacturer's place to
work site.

13

RELAYS
A relay is an electrically operated switch. Many relays use an electromagnet to operate a switching
mechanism mechanically, but other operating principles are also used. Relays are used where it is necessary to
control a circuit by a low-power signal (with complete electrical isolation between control and controlled circuits),
or where several circuits must be controlled by one signal. The first relays were used in long distance telegraph
circuits, repeating the signal coming in from one circuit and re-transmitting it to another. Relays were used
extensively in telephone exchanges and early computers to perform logical operations.














14

Earthmat
An earthing system has two objectives:

1. provide for a uniform potential gradient over a physical area. This is needed so that individuals who are walking
in the area are not exposed to excessive voltages across the length of a stride ('step potential') or when they touch a
metallic structure ('reach potential').

2. provide a connection to earth through which lightning or system fault current can be dissipated. In effect, this
objective amounts to managing the potential different relative to a remote location.

Earthing mats normally consist of a rectangular (or square) grid of copper wires that are buried in underground
trenches. This grid must lie underneath the entire area to be protected, and must extend beyond any security fencing
that may be present to prevent intrusion by civilians. Calculations that take into account the resistivity of the soil
and any surface treatment in the protected area (it is customary to put a layer of crushed stone over the protected
area) to achieve maximum step and reach potentials.

Earthing mats also may include driven copper rods at some or all of the grid intersections. The rods are more
required to dissipate current than to manage step and reach potentials.

In some instances, it is also necessary to treat the soil surrounding the mesh with chemicals to enhance soil
conductivity. And it may be necessary to install driven rods in bore holes that are backfilled with special chemicals.

In especially challenging applications (for example, in areas where there is a lot of granite underneath the surface
soil), it may be necessary to supplement the mesh with either metal plates that are sunk into nearby bodies of water,
or by connecting the mesh to water wells that are bored through the granite into conductive soil.




15

Onsite Recordings
Earth pit
For the entire substation we are digging out at one place and there we are putting earth mats and its nodes
are connected to earth electrodes.
Neutral earthing
The neutral should be earthed at zero potential.
Difference between isolator and circuit breaker
Isolator is used to interupt the voltage and circuit breaker is used to interupt the currents.
Floating neutral
For auxilarry purpose we are using the floating neutral.If we dont have a floating neutral it will leads to the
destruction of the equipments present in the control room.














16

Conclusions
This visit to the substation was one of the source to know about the switch yards and various equipments
that is using in the switch yards and their practical demonstrations.This visit was an extremely useful trip for us, as
it helped us to gain an idea about the basic operations and the significance of a substation.

Das könnte Ihnen auch gefallen