Beruflich Dokumente
Kultur Dokumente
Contents Page
General Informations 2
Technical data 3
Basic designs 4 - 8
Cam Switches On-Off switches, Changeover switches 9 -12
Star-Delta switches 13 - 15
Multi speed switches 16 - 20
Control switches 21 - 23
Voltmeter selector switches, Ammeter switches 24 - 26
Gang switches 27 - 29
Multi step switches 30 - 41
Mini-Cam Switches Technical data 42
On-Off switches, Changeover switches 43
Star-Delta switches 43
Control switches 43, 44
Voltmeter selector switches, Ammeter switches 44
Gang switches, Multi step switches 44, 45
Main switches Switch disconnectors with padlock device 46 - 48
Accessories 51
Cam switches with padlock device 52
Switch On-Off switches 53
disconnectors
Load switches On-Off switches 54
Changeover switches 55
Handles and plates Operating knobs and handles 56, 57
Escutcheon plates 58 - 61
Angles of rotation 61, 62
Optional Extras Drive units 63
Door couplings 64
Key operated switches 65
Padlock devices 66
Switch interlocks, Couplings 67, 68
Accessories 69, 70
Special switches 71, 96
Technical data Cam switches 73, 74
Switch disconnectors 75
Load switches 76
Dimensions Cam switches 77 - 80
Main and Emergency-Off switches 81 - 84
Switch disconnectors, Load switches 85
Accessories 86 - 93
Representations 94, 95
and Suppliers
2 D371E
Ratings Designs
Panel moun. Single hole mount. 22,5mm Flush mount.
Protection degree from front M10H, M20 IP65 with Plate without Plate IP40
in mounted position IP40 IP65 IP65
Rated current Motor Plate
Therm. AC3 AC23
I
th
open AC21 atU
e
3~400V 3~400V
Typ A A V kW A kW mm
M4H 10 10 440 2,2 6 3 30
M4H E
M4H Z
M4H ZO
-
M10H 20 20 690 5,5 16 7,5 48
M10H E
M10H Z
M10H ZO
-
M10 20 20 440 5,5 16 7,5 48
- - - M10 UP
M20 32 32 690 11 30 15 48
M20 E
M20 Z
M20 ZO
-
N20 32 32 690 11 30 15 64
N20 E
- - N20 UP
N33F 50 50 690 15 45 22 64
N33F E
N33F Z
- -
N32 40 40 690 11 30 15 64
- - - -
N40 63 63 690 15 45 22 88
N40 E
- - -
N60 85 85 690 25 60 30 88
N60 E
- - -
N80 115 115 690 30 85 45 88
N80 E
- - -
L100 125 125 690 15 45 22 88
L100 E
- - -
L160 180 180 690 25 60 30 88
L160 E
- - -
N100 150 150 690 40 110 55 132
N100 E
- - -
N200 250 250 690 70 140 70 132
N200 E
- - -
L400 400 400 690 70 140 70 132
L400 E
- - -
L600 600 400 690 70 140 70 132
L600 E
- - -
L800 800 400 690 70 140 70 132
L800 E
- - -
L1200 1200 400 690 70 140 70 132
L1200 E
- - -
Load switch L.. 125 - 1200A
Load switches are primarily employed where resistive or slightly
inductive current loads are to be switched on and off, or switching
takes place without loading.
Load switches are assembled by parallel switching of two or more
of cam switch contacts.
With customer built main terminal protection, load switch L.. can also
be used as main switch.
Four-hole mounting
or single-hole mounting 22,5 mm
or base mounting
or DIN-rail mounting
Escutcheon frame
Handle
Latching mechanism determines
the switch position (30,45,60,90)
Up to 25
Switching cells - two poles
- double interruption per pole
Drive shaft
of solid aluminium
Escutcheon plate
. . . . E. .
. . . . Z. .
. . . . V. .
. . . . SM. .
Cam Switches 10 - 250A
Cam switches can be used for virtually all purposes, e.g. as motor,
main, control or instrument switches. Over and above the switching
programs mentioned in the list, an effectively limitless number of
special programs can be implemented.
- - Cam Switches
D371E 3
Designs
Base mounting DIN-rail Modular Plastic enclosed Motor switch Terminal box Cast enclosed
IP40 mounting IP40 ..P.. IP40 horizontal, IP65 enclosed mounting ..G.. IP40
IP40 ..PF.. IP65 IP65 IP65 ..GF.. IP65
- - - - - - - -
M10H V
M10H SM
M10H SMA
- - M10H PM
- -
- - - M10 P(F)
- - M10 KE
-
M20 V
M20 SM
M20 SMA
- - - - -
N20 V
N20 SM
- N20 P(F)
- N20 PM
N20 KE
N20 G(F)
N33F V
N33F SM
- N33F P(F)
- N33F PM
N33F KE
-
- - - - - - - N32 G(F)
N40 V
- - N40 P(F)
N40 PLF
- - -
N60 V
- - N60 P(F)
N60 PLF
- - -
N80 V
- - N80 P(F)
N80 PLF
- - -
L100 V
- - - - - - -
L160 V
- - - - - - -
N100 V
- - N100 P(F)
- - - -
N200 V
- - N200 P(F)
- - - -
L400 V
- - - - - - -
L600 V
- - - - - - -
L800 V
- - - - - - -
L1200 V
- - - - - - -
Ordering
SWITCH TYPE
DESIGN
SWITCH PROGRAM
NUMBER OF STEPS
NUMBER OF POLES
ACCESSORIES +
On-Off-switch A
M10H E A3+GFP Changeover switch with Off position U
Changeover switch without Off position W
20A Panel mounting Changeover switch with spring return to Off UR
On-Off-switch 3-pole Reversing switch WU
+ large front plate Star-Delta-switch SD
Multi speed switch P..
Start switch SE
Stop switch SA
Voltmeter selector switch V.
Ammeter selector switch M..
Gang switch GR..
Multi step switch without Off position ST
4 D371E
Switch disconnector LT.. 20 - 160A
Switch disconnectors are to be used as an ON-OFF-switch
where a high breaking capacity with high contact pressure
and in fact better short circuit behavior is necessary. These
applications are:
Main switches according to IEC/EN 60204 respectively
VDE0113 with interlocking device, terminal protection and
restrective contacts.
Switch disconnectors according to IEC/EN 60947-3 and
VDE 0660 part 107 with break distance for 690V.
Motor switches 3-pole or 4-pole; according to IEC/EN
60947-3 respectively VDE 0660 part 107, motor switches
series LT are dimensioned for switching high rated current
AC3 and AC23A.
Main switches and
Main switches with Emergency-Stop function
According to standards IEC/EN60204 or VDE0113, all electrical equip-
ment of industrial machines must be equipped with a main switch. This
must permit disconnection of all the electrical equipment during cleaning,
maintenance and repair work, and other extended periods when it is
stationary.
In case of two or more main switches, an interlock system must be used.
It is recommended to use a multiple-pole main switch (cam switch).
Main switches have to correspond to:
a) Switch disconnector according to IEC/EN 60947-3 and VDE 0660
part 107 for utilization category AC23-B or DC-23B.
b) Disconnectors are selected according to thermal rated current. They
must possess a contact that ensures load switching via the contac-
tors (see switching program A3-10). This contact must have a
sufficient AC15 switching capacity.
c) The interruption capacity of the switch must equal or exceed the
locked rotor current of the largest motor plus the total current of all
other electrical equipment in the circuit.
Requirements:
Interruption of the electrical equipment, with only on and off positions
clearly marked with O and I.
It must be lockable in the off setting.
The line terminals of the main switch must be protected according to
utilization category IP2X.
Colour of handle black or grey.
Main switches with Emergency-Off function are additional supplied
with red handles and contrasting yellow escutcheon plates.
Ratings Main Switch Emergency Stop
Panel mounting Single hole mount. Base mounting
22,5mm with door coupling
Protection degree from front IP65 IP65 adjust. installation depth
in mounted position LTS.. IP65
LT.. IP40
Rated current Motor Plate
Therm. AC3 AC23 Switch
I
th
open AC21 bei U
e
3~400V 3~400V disconnector
Type A A V kW A kW mm
LTS20 20 20 690 4 12 5,5 48
LTS20 EHN1
..
LTS20 ZHN1
..
LTS20 VZVHN4
..
LTS20 EHN4
..
LTS20 VHN4
..
LTS25 25 25 690 5,5 16 7,5 48
LTS25 EHN1
..
LTS25 ZHN1
..
LTS25 VZVHN4
..
LTS25 EHN4
..
LTS25 VHN4
..
LTS32 32 32 690 7,5 23 11 48
LTS32 EHN1
..
LTS32 ZHN1
..
LTS32 VZVHN4
..
LTS32 EHN4
..
LTS32 VHN4
..
LTS40 40 40 690 11 30 15 48
LTS40 EHN1
..
LTS40 ZHN1
..
LTS40 VZVHN4
..
LTS40 EHN4
..
LTS40 VHN4
..
LTS63 63 63 690 15 45 22 48
LTS63 EHN1
..
- LTS63 VZVHN4
..
LTS63 EHN4
..
LTS63 VHN4
..
LTS80 80 80 690 18,5 45 22 48
LTS80 EHN1
..
- LTS80 VZVHN4
..
LTS80 EHN4
..
LTS80 VHN4
..
LT80 80 80 690 22 60 30 64
LT80 EHN34
..
- LT80 VHN34
..
LT100 100 100 690 30 72 37 64
LT100 EHN34
..
- LT100 VHN34
..
LT125 125 125 690 37 85 45 88
LT125 EHN34
..
- LT125 VHN34
..
LT160 160 160 690 45 110 55 88
LT160 EHN34
..
- LT160 VHN34
..
D371E 5
Main Switch Emergency Stop Main Switch Switch Disconnectors
Base mounting w. for Distribution Plastic Panel mounting Base mounting Panel mounting for Distribution
door coupling Boards enclosed with door coupling Boards
depth not adjustable IP40 IP65 IP65 LTS.. IP65 IP65 IP40
IP65 LT.. IP40
LTS20 VZHN1
..
LTS20 SMAHN1
..
LTS20 PFHN4
..
LTS20 EH1
..
LTS20 VZVH4
..
LTS20 E
..
LTS20 SMA
..
LTS20 VZHN4
..
LTS20 EH4
..
LTS20 VH4
..
LTS25 VZHN1
..
LTS25 SMAHN1
..
LTS25 PFHN4
..
LTS25 EH1
..
LTS25 VZVH4
..
LTS25 E
..
LTS25 SMA
..
LTS25 VZHN4
..
LTS25 EH4
..
LTS25 VH4
..
LTS32 VZHN1
..
LTS32 SMAHN1
..
LTS32 PFHN4
..
LTS32 EH1
..
LTS32 VZVH4
..
LTS32 E
..
LTS32 SMA
..
LTS32 VZHN4
..
LTS32 EH4
..
LTS32 VH4
..
LTS40 VZHN1
..
LTS40 SMAHN1
..
LTS40 PFHN4
..
LTS40 EH1
..
LTS40 VZVH4
..
LTS40 E
..
LTS40 SMA
..
LTS40 VZHN4
..
LTS40 EH4
..
LTS40 VH4
..
LTS63 VZHN1
..
LTS63 SMAHN1
..
LTS63 PFHN4
..
LTS63 EH1
..
LTS63 VZVH4
..
LTS63 E
..
LTS63 SMA
..
LTS63 VZHN4
..
LTS63 EH4
..
LTS63 VH4
..
LTS80 VZHN1
..
LTS80 SMAHN1
..
LTS80 PFHN4
..
LTS80 EH1
..
LTS80 VZVH4
..
LTS80 E
..
LTS80 SMA
..
LTS80 VZHN4
..
LTS80 EH4
..
LTS80 VH4
..
- LT80 SMAHN1
..
LT80 PFHN34
..
LT80 EH34
..
LT80 VH34
..
LT80 E
..
LT80 SMA
..
- LT100 SMAHN1
..
LT100 PFHN34
..
LT100 EH34
..
LT100 VH34
..
LT100 E
..
LT100 SMA
..
- - LT125 PFHN34
..
LT125 EH34
..
LT125 VH34
..
LT125 E
..
-
- - LT160 PFHN34
..
LT160 EH34
..
LT160 VH34
..
LT160 E
..
-
Switch program
On-Off Switch 3-pole A3
On-Off Switch 4-pole A4
On-Off Switch 6-pole A6
On-Off Switch 8-pole A8
Changeover Switches 3-pole U3
Changeover Switches 4-pole U4
On-Off Switch 3-pole T300 (for LT80 - LT160)
On-Off Switch 4-pole T400 (for LT80 - LT160)
6 D371E
Panel mounting designs
Design
Description
Panel mounting
For installation in control panels, ma-
chines and equipment.
For panel thickness of over 5mm, an
extended switch shaft is required
(appendix +VW).
Protection from front:
M10H, M20 IP65
all others IP40
Central fixing 22,5mm
Switch for mounting with standard
22,5mm mounting holes and 1-4mm
panel thickness.
Protection from front: IP65
Wrench J7049 necessary
Central fixing 22,5mm
Switch without escutcheon plate,
for installation with standard 22,5mm
mounting holes and 1-4mm panel
thickness. Protection from front: IP65
Wrench J7049 necessary
Flush mounting version
Switch with cream-coloured twist knob,
cream escutcheon plate with black
markings, for installation in 65mm flush
mounting boxes and use of Unitas
plate. Supplied with flush mounting box:
appendix +UP. Maximum number of
cells with: M10
FM box 45mm deep 2
FM box 65mm deep 4
Flush mounting version
Switch without flush mounting box and
special square cover, black markings
and cream twist knob. Supplied with
flush mounting box: appendix +UP.
Max. 4 cells
Possible switch sizes
N40
Type N20 N60 N100
appendix M10H M20 N33F N80 N200 L...
E X X X X X X
Z X X X
3)
- - -
ZO X X - - - -
UP X
1)
- - - - -
UP - - X
2)
- - -
- Cam Switches
1) Switches are delivered with switch type M10
2) For switch types N20 only
3) For switch types N33F only, max. 3 poles and 3 cells
Switches of the panel mounting designs listed below have protection
from front IP40. Where a shaft seal (appendix +WD) is used, the
protection is increased to IP54. Use of a moisture proofing cap
(appendix +FR) results in an increase in rear protection to IP54. In the
standard version, the switches are delivered with a square escutcheon
plate and black twist knob. Forward mounting is possible for some of
the design E switches. The position of the terminals of the standard
switches is left and right, at switch M10H the terminals are above and
below. Where a knob insert is turned by 90(can easily be performed
after delivery), the position of the terminals can be changed.
Dimensions see page 75.
D371E 7
Base mounting designs
Design
Description
Base mounting
For screw mounting to the back wall or
floor of distributor boxes, or of applian-
ces with removable lids.
Additional it is necessary to state the
installation depth - that is the distance
between mounting level of the switch
and the inside edge of the door
(dimension T).
Door couplings see page 62
Snap-on mounting on DIN-rail
Switch with square escutcheon plate,
for snap-on mounting on standard DIN
EN 50022 rail.
Additional it is necessary to state the
installation depth - that is the distance
between mounting level of the switch
and the inside edge of the door
(dimension T).
Door couplings see page 62
Snap-on mounting on DIN-rail
with installation cover for standard
opening and toggle knob. The lay-out
of the terminals of the standard
switches is above and below.
Dimensions for Switch types
M10H SMA .. with1-3 cells
M20 SMA .. with1 or 2 cells
further dimensions see page 76
- Cam Switches
Possible switch sizes
N40
Type N20 N60 N100
appendix M10H M20 N33F N80 N200 L...
V ... +T/... X X X X X X
SM ... +T/... X X X - - -
SMA X X - - - -
Switches of the designs listed below have protection from front IP40.
When a shaft seal (appendix +WD) is used, the front protection type
is increased to IP54. In the standard version, the switches are delivered
with a square escutcheon plate and black twist knob (design SMA with
grey cover and grey toggle knob). Door couplings are advisable for
switchgear cabinets with hinged doors.
The position of the terminals of the standard switches is left and right,
at switch M10H the terminals are above and below. Where a knob insert
is turned by 90(can easily be performed after delivery), the position
of the terminals can be changed.
Dimensions see page 76.
8 D371E
Possible switch sizes
Type
appendix M10H N20 N33F N40 N60 N80 N100 N200
P X
1)
X X X X - - -
6 6 6 6 2
PF X
1)
X X X X X X X
6 6 6 6 5 5 4 3
PLF - - - X X X - -
- - - 10 6 6
G - X X
2)
- - - - -
- 6 5
GF - X X
2)
- - - - -
- 6 5
KE X
1)
X X - - - - -
12 12 12
PM - X - - - - - _
6
Plastic enclosed switches Cast aluminium enclosed switches
Design
Description
Plastic enclosure light grey
Protection class IP40
Maximum number of cells
Plastic enclosure light grey
Moisture protection
Protection class IP65
Maximum number of cells
Plastic enclosure horizontal
light grey Moisture protection
Protection class IP65
Maximum number of cells
Cast enclosure
Protection class IP40
Maximum number of cells
Cast enclosure
Moisture protection
Protection class IP65
Maximum number of cells
Terminal box mounting
Protection class IP65
These switches are front mounted on a
terminal box. The switch cells protrude
through a hole into the terminal com-
partment.
Maximum number of cells
Plastic motor switch enclosure
Moisture protection
Protection class IP65
Maximum number of cells
- Cam Switches
1) Plastic enclosed switches are delivered with switch type M10
2) Cast enclosed switches are delivered with switch type N32
The switches, which have durable plastic enclosures, are intended for
wall mounting or attachment to machines. In the standard version, they
are supplied with a light-grey enclosure, square escutcheon plate,
black markings on a silver background, and a black twist knob. Other
colours and colour combinations are available for most enclosure
types. It is not possible to mount an additional rectangular plate. The
enclosure base is equipped with 4 entry glands with heavy-gauge
conduit threads (see drawings). In all types of plastic enclosures, two
terminals that are connected and insulated from switch column can be
provided for a PE conductor (appendix +PE). In addition, 1 or 2 pilot
lamps (appendix +SL..) with neon lights can be installed.
Dimensions see page 77.
The switches with cast aluminium enclosures are intended for wall
mounting or attachment to machines, under heavy-duty operating
conditions. The switches are delivered with a square escutcheon plate,
black markings on a silver background, and a black twist knob. It is not
possible to mount an additional rectangular plate. The enclosure base
makes provision for 2 (4) entry glands with heavy-gauge conduit
threads. If a switch with an aluminium enclosure is to be mounted
directly on the terminal box of a motor, a 35mm or 50mm hole can be
made in the floor of the switch enclosure. Design PLF is the replacement
for designs G and GF at types N40 to N80.
Dimensions see page 78.
Description Wiring diagram Switching angle Number of cells Type Design Switch Escutcheon
Size see page 6-8 pro- plate
AC21 E. Z. V. SMA. P. G. gram
- Cam Switches
Switching programs
D371E 9
On-Off-switches A
1-pole 60 1 48
20A M10H . x x x x x
1)
- . A1
32A M20 . x x x x - - . A1
64
32A N20 . x - x - x x . A1
50A N33F . x x x - x x
2)
. A1
88
150A N100 . x - x - - - . A1
250A N200 . x - x - - - . A1
2-pole 60 1 48
20A M10H . x x x x x
1)
- . A2
32A M20 . x x x x - - . A2
64
32A N20 . x - x - x x . A2
50A N33F . x x x - x x
2)
. A2
88
150A N100 . x - x - - - . A2
250A N200 . x - x - - - . A2
3-pole 60 2 48
20A M10H . x x x x x
1)
- . A3
32A M20 . x x x x - - . A3
64
32A N20 . x - x - x x . A3
50A N33F . x x x - x x
2)
. A3
88
150A N100 . x - x - - - . A3
250A N200 . x - x - - - . A3
4-pole 60 2 48
20A M10H . x x x x x
1)
- . A4
4. pole early make 32A M20 . x x x x - - . A4
64
32A N20 . x - x - x x . A4
50A N33F . x - x - x x
2)
. A4
88
150A N100 . x - x - - - . A4
250A N200 . x - x - - - . A4
6-pole 60 3 48
20A M10H . x x x x x
1)
- . A6
32A M20 . x x x x - - . A6
64
32A N20 . x - x - x x . A6
50A N33F . x - x - x x
2)
. A6
88
150A N100 . x - x - - - . A6
250A N200 . x - x - - - . A6
Ordering example: AC21 250A panel mounting, On-Off-switch 6-pole, Escutcheon plate OFF - ON N200 E A6+003
1) Plastic enclosed switches are delivered with switch type M10.
2) Cast enclosed switches are delivered with switch type N32.
- Cam Switches
Description Wiring diagram Switching angle Number of cells Type Design Switch Escutcheon
Size see page 6-8 pro- plate
AC21 E. Z. V. SMA. P. G. gram
Switching programs
10 D371E
Changeover switches U
1-pole 60 1 48
20A M10H . x x x x x
1)
. U1
32A M20 . x x x x - - . U1
64
32A N20 . x - x - x x . U1
50A N33F . x x x - x x
2)
. U1
88
150A N100 . x - x - - - . U1
250A N200 . x - x - - - . U1
2-pole 60 2 48
20A M10H . x x x x x
1)
- . U2
32A M20 . x x x x - - . U2
64
32A N20 . x - x - x x . U2
50A N33F . x x x - x x
2)
. U2
88
150A N100 . x - x - - - . U2
250A N200 . x - x - - - . U2
3-pole 60 3 48
20A M10H . x x x x x
1)
- . U3
32A M20 . x x x x - - . U3
64
32A N20 . x - x - x x . U3
50A N33F . x x x - x x
2)
. U3
88
150A N100 . x - x - - - . U3
250A N200 . x - x - - - . U3
4-pole 60 4 48
20A M10H . x x x x x
1)
- . U4
4. pole early make 32A M20 . x x x x - - . U4
64
32A N20 . x - x - x x . U4
50A N33F . x - x - x x
2)
. U4
88
150A N100 . x - x - - - . U4
250A N200 . x - x - - - . U4
6-pole 60 6 48
20A M10H . x x x - x
1)
- . U6
32A M20 . x x x - - - . U6
64
32A N20 . x - x - x x . U6
50A N33F . x - x - x - . U6
88
150A N100 . x - x - - - . U6
250A N200 . x - x - - - . U6
Ordering example: AC21 250A panel mounting, changeover switch 6-pole, Escutcheon plate 1 - OFF - 2 N200 E U6+007
1) Plastic enclosed switches are delivered with switch type M10.
2) Cast enclosed switches are delivered with switch type N32.
Description Wiring diagram Switching angle Number of cells Type Design Switch Escutcheon
Size see page 6-8 pro- plate
AC21 E. Z. V. SMA. P. G. gram
- Cam Switches
Switching programs
D371E 11
Changeover switches without off W
1-pole 60 1 48
20A M10H . x x x x x
1)
- . W1
32A M20 . x x x x - - . W1
64
32A N20 . x - x - x x . W1
50A N33F . x x x - x x
2)
. W1
88
63A N40 . x - x - x - . W1
80A N60 . x - x - x - . W1
115A N80 . x - x - - - . W1
132
150A N100 . x - x - - - . W1
250A N200 . x - x - - - . W1
2-pole 60 2 48
20A M10H . x x x x x
1)
- . W2
32A M20 . x x x x - - . W2
64
32A N20 . x - x - x x . W2
50A N33F . x x x - x x
2)
. W2
88
63A N40 . x - x - x - . W2
80A N60 . x - x - x - . W2
115A N80 . x - x - - - . W2
132
150A N100 . x - x - - - . W2
250A N200 . x - x - - - . W2
3-pole 60 3 48
20A M10H . x x x x x
1)
- . W3
32A M20 . x x x x - - . W3
64
32A N20 . x - x - x x . W3
50A N33F . x x x - x x
2)
. W3
88
63A N40 . x - x - x - . W3
80A N60 . x - x - x - . W3
115A N80 . x - x - - - . W3
132
150A N100 . x - x - - - . W3
250A N200 . x - x - - - . W3
4-pole 60 4 48
20A M10H . x x x x x
1)
- . W4
4. pole early make 32A M20 . x x x x - - . W4
64
32A N20 . x - x - x x . W4
50A N33F . x - x - x x
2)
. W4
88
63A N40 . x - x - x - . W4
80A N60 . x - x - x - . W4
115A N80 . x - x - - - . W4
132
150A N100 . x - x - - - . W4
250A N200 . x - x - - - . W4
6-pole 60 6 48
20A M10H . x x x - x
1)
- . W6
32A M20 . x x x - - - . W6
64
32A N20 . x - x - x x . W6
50A N33F . x - x - x - . W6
88
63A N40 . x - x - x - . W6
80A N60 . x - x - x - . W6
115A N80 . x - x - - - . W6
132
150A N100 . x - x - - - . W6
250A N200 . x - x - - - . W6
Ordering example: AC21 250A panel mounting, changeover switch without off 6-pole, N200 E W6
1) Plastic enclosed switches are delivered with switch type M10.
2) Cast enclosed switches are delivered with switch type N32.
- Cam Switches
Description Wiring diagram Switching angle Number of cells Type Design Switch Escutcheon
Size see page 6-8 pro- plate
AC21 E. Z. V. SMA. P. G. gram
Switching programs
12 D371E
Reversing switches WU
2-pole 60 2 48
20A M10H . x x x x x
1)
- . WU2
32A M20 . x x x x - - . WU2
64
20A M10H . x x x x x
1)
- . WK2
without off 32A M20 . x x x x - - . WK2
cross switch
64
20A M10H . x x x x x
1)
- . WU2R2
with spring return from 32A M20 . x x x x - - . WU2R2
both sides to off
64
20A M10H . x x x x x
1)
- . WU2R1
position 1 latched 32A M20 . x x x x - - . WU2R1
position 2 with spring
return to off 64
20A M10H . x x x x x
1)
- . WU3
32A M20 . x x x x - - . WU3
64
20A M10H . x x x x x
1)
- . WU3R2
with spring return from 32A M20 . x x x x - - . WU3R2
both sides to off
64
20A M10H . x x x x x
1)
- . WU3R1
position 1 latched 32A M20 . x x x x - - . WU3R1
position 2 with spring
return to off 64
20A M10H . x x x x x
1)
- . SD
32A M20 . x x x x - - . SD
64
32A N20 . x - x - x x . SD
50A N33F . x - x - x x
2)
. SD
88
63A N40 . x - x - x - . SD
80A N60 . x - x - x - . SD
115A N80 . x - x - - - . SD
132
150A N100 . x - x - - - . SD
250A N200 . x - x - - - . SD
both rotary directions 45 5 48
20A M10H . x x x x x
1)
- . SDR
32A M20 . x x x x - - . SDR
64
20A M10H . x x x x x
1)
- . SRD
spring return from 32A M20 . x x x x - - . SRD
to off
64
20A M10H . x x x x x
1)
- . SDRU
with clockwise operation 32A M20 . x x x x - - . SDRU
and backswitch interlock
64
20A M10H . x x x x x
1)
- . SDU
switch 32A M20 . x x x x - - . SDU
64
20A M10H . x x x x x
1)
- . SDMO
phases for use with 32A M20 . x x x x - - . SDMO
manual motor starter
64
20A M10H . x x x x x
1)
- . SDJ1
for contactor control, 32A M20 . x x x x - - . SDJ1
without main contacts,
automatic zero setting in 64
20A M10H . x x x x x
1)
- . SDJ2
for contactor control, 32A M20 . x x x x - - . SDJ2
without main contacts,
automatic zero setting in 64
20A M10H . x x x x x
1)
- . SDB
(counter current 32A M20 . x x x x - - . SDB
braking) brake position
is a momentary 64
20A M10H . x x x x x
1)
- . HP1
single-phase motors 32A M20 . x x x x - - . HP1
with split-phase,
spring return from 64
20A M10H . x x x x x
1)
- . HP2
single-phase motors 32A M20 . x x x x - - . HP2
with split-phase,
spring return from 64
20A M10H . x x x x x
1)
- . HPR1
single-phase motors 32A M20 . x x x x - - . HPR1
with split-phase,
both rotary directions 64
20A M10H . x x x x x
1)
- . HPR2
with starting and 32A M20 . x x x x - - . HPR2
phase-shifting capacitor
64
20A M10H . x x x x x
1)
- . P61
1 rotary direction 32A M20 . x x x x - - . P61
64
20A M10H . x x x x x
1)
- . P62
1 rotary direction 32A M20 . x x x x - - . P62
64
20A M10H . x x x x x
1)
- . P61RU
1 rotary direction, 32A M20 . x x x x - - . P61RU
clockwise operation
64
20A M10H . x x x x x
1)
- . P61J
1 rotary direction, 32A M20 . x x x x - - . P61J
with auxiliary contacts
for contactor control 64
20A M10H . x x x - x
1)
- . P91
1 rotary direction 32A M20 . x x x - - - . P91
low speed with
star-delta-start 64
20A M10H . x x x x x
1)
- . P63
1 rotary direction 32A M20 . x x x x - - . P63
64
20A M10H . x x x x x
1)
- . P64
1 rotary direction 32A M20 . x x x x - - . P64
64
20A M10H . x x x x x
1)
- . P66
both rotary directions 32A M20 . x x x x - - . P66
64
20A M10H . x x x x x
1)
- . P71
1 opened 32A M20 . x x x x - - . P71
1 rotary direction
64
20A M10H . x x x - x
1)
- . P96
1 rotary direction 32A M20 . x x x - - - . P96
low speed with
star-delta-start 64
20A M10H . x x x - x
1)
- . P93
1 normal winding B 32A M20 . x x x - - - . P93
3 speeds
1 rotary direction 64
20A M10H . x x x - x
1)
- . P94
1 normal winding B 32A M20 . x x x - - - . P94
3 speeds
1 rotary direction 64
20A M10H . x x x - x
1)
- . P95
1 normal winding B 32A M20 . x x x - - - . P95
3 speeds
1 rotary direction 64
20A M10H . x x x x x
1)
- . UR1
32A M20 . x x x x - - . UR1
64
20A M10H . x x x x x
1)
- . UR2
32A M20 . x x x x - - . UR2
64
20A M10H . x x x x x
1)
- . UR3
32A M20 . x x x x - - . UR3
64
20A M10H . x x x x x
1)
- . UK1
position 1 latched 32A M20 . x x x x - - . UK1
position 2 with spring
return 64
20A M10H . x x x x x
1)
- . UK2
position 1 latched 32A M20 . x x x x - - . UK2
position 2 with spring
return 64
20A M10H . x x x x x
1)
- . UK3
position 1 latched 32A M20 . x x x x - - . UK3
position 2 with spring
return 64
20A M10H . x x x x x
1)
- . W1R
32A M20 . x x x x - - . W1R
64
20A M10H . x x x x x
1)
- . W2R
32A M20 . x x x x - - . W2R
64
20A M10H . x x x x x
1)
- . W3R
32A M20 . x x x x - - . W3R
64
20A M10H . x x x x x
1)
- . SE
32A M20 . x x x x - - . SE
64
32A N20 . x - x - x x . SE
50A N33F . x - x - x x
2)
. SE
Start-switch, 2-pole 30 1 48
20A M10H . x x x x x
1)
- . S2E
32A M20 . x x x x - - . S2E
64
20A M10H . x x x x x
1)
- . S3E
32A M20 . x x x x - - . S3E
64
20A M10H . x x x x x
1)
- . SA
32A M20 . x x x x - - . SA
64
32A N20 . x - x - x x . SA
50A N33F . x - x - x x
2)
. SA
88
63A N40 . x - x - x - . SA
Stop-switch, 2-pole 30 1 48
20A M10H . x x x x x
1)
- . S2A
32A M20 . x x x x - - . S2A
64
20A M10H . x x x x x
1)
- . S3A
32A M20 . x x x x - - . S3A
64
20A M10H . x x x x x
1)
- . SEA
1-pole 32A M20 . x x x x - - . SEA
64
20A M10H . x x x x x
1)
- . S392
1-pole 32A M20 . x x x x - - . S392
position START
with spring return to 1 64
20A M10H . x x x x x
1)
- . S2EA
1-pole for 32A M20 . x x x x - - . S2EA
reversing contactors
64
20A M10H . x x x x x
1)
- . S22
1-pole for 32A M20 . x x x x - - . S22
reversing contactors
with limit switches 64
20A M10H . x x x x x
1)
- . V3
32A M20 . x x x x - - . V3
64
32A N20 . x - x - x x . V3
50A N33F . x x x - x x
2)
. V3
3 phase voltages 45 2 48
20A M10H . x x x x x
1)
- . V0
32A M20 . x x x x - - . V0
64
32A N20 . x - x - x x . V0
50A N33F . x x x - x x
2)
. V0
3 line voltages and 30 3 48
20A M10H . x x x x x
1)
- . V1
3 phase voltages 32A M20 . x x x x - - . V1
64
32A N20 . x - x - x x . V1
50A N33F . x x x - x x
2)
. V1
2 3-phase systems 45 4 48
20A M10H . x x x x x
1)
- . V32
2 x 3 line voltages 32A M20 . x x x x - - . V32
64
20A M10H . x x x x x
1)
- . V13
1 phase voltage 32A M20 . x x x x - - . V13
64
20A M10H . x x x x x
1)
- . M11
current transformer 32A M20 . x x x x - - . M11
64
20A M10H . x x x x x
1)
- . M12
1 current transformer 32A M20 . x x x x - - . M12
or direct current
measurement 64
20A M10H . x x x x x
1)
- . M21
2 current transformers 32A M20 . x x x x - - . M21
64
20A M10H . x x x x x
1)
- . M22
2 current transformers 32A M20 . x x x x - - . M22
or direct current
measurement 64
20A M10H . x x x x x
1)
- . M31
3 current transformers 32A M20 . x x x x - - . M31
64
20A M10H . x x x x x
1)
- . M32
3 current transformers 32A M20 . x x x - - - . M32
or direct current
measurement 64
20A M10H . x x x x x
1)
- . M41
4 current transformers 32A M20 . x x x x - - . M41
64
20A M10H . x x x x x
1)
- . M42
4 current transformers 32A M20 . x x x - - - . M42
or direct current
measurement 64
20A M10H . x x x x x
1)
- . M2W
in 3-phase ystems by 32A M20 . x x x x - - . M2W
2-wattmeter method
64
20A M10H . x x x x x
1)
- . GR11
1-pole 32A M20 . x x x x - - . GR11
0 - A - A+B
64
20A M10H . x x x x x
1)
- . GR12
1-pole 32A M20 . x x x x - - . GR12
0 - A - B - A+B
64
20A M10H . x x x x x
1)
- . GR21
2-pole 32A M20 . x x x x - - . GR21
0 - A - A+B
64
20A M10H . x x x x x
1)
- . GR22
2-pole 32A M20 . x x x x - - . GR22
0 - A - B - A+B
64
20A M10H . x x x x x
1)
- . GR31
3-pole 32A M20 . x x x x - - . GR31
0 - A - A+B
64
20A M10H . x x x x x
1)
- . GR32
3-pole 32A M20 . x x x x - - . GR32
0 - A - B - A+B
64
20A M10H . x x x x x
1)
- . GR14
1-pole 32A M20 . x x x x - - . GR14
0 - A - A+B - A+B+C
64
20A M10H . x x x x x
1)
- . GR23
2-pole 32A M20 . x x x x - - . GR23
0 - A - A+B - A+B+C
64
20A M10H . x x x x x
1)
- . GR33
3-pole 32A M20 . x x x x - - . GR33
0 - A - A+B - A+B+C
64
20A M10H . x x x x x
1)
- . SP1
2-pole 32A M20 . x x x x - - . SP1
0 - A + B - A,B (parallel)
64
20A M10H . x x x x x
1)
- . SP4
2-pole 32A M20 . x x x x - - . SP4
0 - A,B (parall.) - A - A+B
64
20A M10H . x x x x x
1)
- . SP3
for 3-phase systems 32A M20 . x x x x - - . SP3
0 - A+B - A - B - A,B
64
20A M10H . x x x x x
1)
- . ST31
32A M20 . x x x x - - . ST31
64
20A M10H . x x x x x
1)
- . ST41
32A M20 . x x x x - - . ST41
64
20A M10H . x x x x x
1)
- . ST51
32A M20 . x x x x - - . ST51
64
20A M10H . x x x x x
1)
- . ST61
32A M20 . x x x x - - . ST61
64
20A M10H . x x x x x
1)
- . ST71
32A M20 . x x x x - - . ST71
64
20A M10H . x x x x x
1)
- . ST81
32A M20 . x x x x - - . ST81
64
20A M10H . x x x x x
1)
- . ST91
32A M20 . x x x x - - . ST91
64
20A M10H . x x x x x
1)
- . ST101
32A M20 . x x x x - - . ST101
64
20A M10H . x x x - x
1)
- . ST111
32A M20 . x x x - - - . ST111
64
20A M10H . x x x - x
1)
- . ST121
32A M20 . x x x - - - . ST121
64
20A M10H . x x x x x
1)
- . ST021
32A M20 . x x x x - - . ST021
64
20A M10H . x x x x x
1)
- . ST031
32A M20 . x x x x - - . ST031
64
20A M10H . x x x x x
1)
- . ST041
32A M20 . x x x x - - . ST041
64
20A M10H . x x x x x
1)
- . ST051
32A M20 . x x x x - - . ST051
64
20A M10H . x x x x x
1)
- . ST061
32A M20 . x x x x - - . ST061
64
20A M10H . x x x x x
1)
- . ST071
32A M20 . x x x x - - . ST071
64
20A M10H . x x x x x
1)
- . ST081
32A M20 . x x x x - - . ST081
64
20A M10H . x x x x x
1)
- . ST091
32A M20 . x x x x - - . ST091
64
20A M10H . x x x - x
1)
- . ST0101
32A M20 . x x x - - - . ST0101
64
20A M10H . x x x - x
1)
- . ST0111
32A M20 . x x x - - - . ST0111
64
20A M10H . x x x x x
1)
- . ST32
32A M20 . x x x x - - . ST32
64
20A M10H . x x x x x
1)
- . ST42
32A M20 . x x x x - - . ST42
64
20A M10H . x x x x x
1)
- . ST52
32A M20 . x x x x - - . ST52
64
20A M10H . x x x - x
1)
- . ST62
32A M20 . x x x - - - . ST62
64
20A M10H . x x x x x
1)
- . ST022
32A M20 . x x x x - - . ST022
64
20A M10H . x x x x x
1)
- . ST032
32A M20 . x x x x - - . ST032
64
20A M10H . x x x x x
1)
- . ST042
32A M20 . x x x x - - . ST042
64
20A M10H . x x x - x
1)
- . ST052
32A M20 . x x x - - - . ST052
64
20A M10H . x x x - x
1)
- . ST062
32A M20 . x x x - - - . ST062
64
20A M10H . x x x x x
1)
- . ST33
32A M20 . x x x x - - . ST33
64
20A M10H . x x x - x
1)
- . ST43
32A M20 . x x x - - - . ST43
64
20A M10H . x x x x x
1)
- . ST023
32A M20 . x x x x - - . ST023
64
20A M10H . x x x x x
1)
- . ST033
32A M20 . x x x x - - . ST033
64
20A M10H . x x x - x
1)
- . ST043
32A M20 . x x x - - - . ST043
64
1
) LTS20 EHN1 A3 1 0,15
25A 7,5kW 48
1
) LTS25 EHN1 A3 1 0,15
32A 11kW 48
1
) LTS32 EHN1 A3 1 0,15
40A 15kW 48
1
) LTS40 EHN1 A3 1 0,15
63A 22kW 48
1
) LTS63 EHN1 A3 1 0,17
80A 22kW 48
1
) LTS80 EHN1 A3 1 0,17
4-pole, padlock device SV1
20A 5,5kW 48
1
) LTS20 EHN1 A4 1 0,19
25A 7,5kW 48
1
) LTS25 EHN1 A4 1 0,19
32A 11kW 48
1
) LTS32 EHN1 A4 1 0,19
40A 15kW 48
1
) LTS40 EHN1 A4 1 0,19
63A 22kW 48
1
) LTS63 EHN1 A4 1 0,21
80A 22kW 48
1
) LTS80 EHN1 A4 1 0,21
3-pole, padlock device SV4(34)
20A 5,5kW 64
2
) LTS20 EHN4 A4 1 0,20
25A 7,5kW 64
2
) LTS25 EHN4 A4 1 0,20
32A 11kW 64
2
) LTS32 EHN4 A4 1 0,20
40A 15kW 64
2
) LTS40 EHN4 A4 1 0,20
63A 22kW 64
2
) LTS63 EHN4 A4 1 0,23
80A 22kW 64
2
) LTS80 EHN4 A4 1 0,23
80A 30kW 64
1
) LTS20 EH1 A3 1 0,15
25A 7,5kW 48
1
) LTS25 EH1 A3 1 0,15
32A 11kW 48
1
) LTS32 EH1 A3 1 0,15
40A 15kW 48
1
) LTS40 EH1 A3 1 0,15
63A 22kW 48
1
) LTS63 EH1 A3 1 0,17
80A 22kW 48
1
) LTS80 EH1 A3 1 0,17
4-pole, padlock device SV1
20A 5,5kW 48
1
) LTS20 EH1 A4 1 0,19
25A 7,5kW 48
1
) LTS25 EH1 A4 1 0,19
32A 11kW 48
1
) LTS32 EH1 A4 1 0,19
40A 15kW 48
1
) LTS40 EH1 A4 1 0,19
63A 22kW 48
1
) LTS63 EH1 A4 1 0,21
80A 22kW 48
1
) LTS80 EH1 A4 1 0,21
6-pole, 8-pole, padlock device SV164 on request
3-pole, padlock device SV4(34)
20A 5,5kW 64
1
) LTS20 EH4 A4 1 0,20
25A 7,5kW 64
1
) LTS25 EH4 A4 1 0,20
32A 11kW 64
1
) LTS32 EH4 A4 1 0,20
40A 15kW 64
1
) LTS40 EH4 A4 1 0,20
63A 22kW 64
1
) LTS63 EH4 A4 1 0,23
80A 22kW 64
1
) LTS80 EH4 A4 1 0,23
80A 30kW 64
1
) LTS20 VZVH4 A3 1 0,19
25A 7,5kW 64
1
) LTS25 VZVH4 A3 1 0,19
32A 11kW 64
1
) LTS32 VZVH4 A3 1 0,19
40A 15kW 64
1
) LTS40 VZVH4 A3 1 0,19
63A 22kW 64
1
) LTS63 VZVH4 A3 1 0,22
80A 22kW 64
1
) LTS80 VZVH4 A3 1 0,22
4-pole, padlock device SV4 20A 5,5kW 64
1
) LTS20 VZVH4 A4 1 0,20
25A 7,5kW 64
1
) LTS25 VZVH4 A4 1 0,20
32A 11kW 64
1
) LTS32 VZVH4 A4 1 0,20
40A 15kW 64
1
) LTS40 VZVH4 A4 1 0,20
63A 22kW 64
1
) LTS63 VZVH4 A4 1 0,26
80A 22kW 64
1
) LTS80 VZVH4 A4 1 0,26
6-pole, 8-pole on request
Main Switches, Base Mounting with Door Clutch, Padlock Device for Four-Hole Mounting
Depth X is adjustable (delivered with T
max
see below), IP65, (IP40)
3-pole, padlock device SV4(SV34) 20A 5,5kW 64
LTS20 E A3 1 0,15
25A 7,5kW 48
LTS25 E A3 1 0,15
32A 11kW 48
LTS32 E A3 1 0,15
40A 15kW 48
LTS40 E A3 1 0,15
63A 22kW 48
LTS63 E A3 1 0,17
80A 22kW 48
LTS80 E A3 1 0,17
80A 30kW 64
LTS20 E A4 1 0,18
25A 7,5kW 48
LTS25 E A4 1 0,18
32A 11kW 48
LTS32 E A4 1 0,18
40A 15kW 48
LTS40 E A4 1 0,18
63A 22kW 48
LTS63 E A4 1 0,21
80A 22kW 48
LTS80 E A4 1 0,21
80A 30kW 64
125A L100 . x x . A1
1 180A L160 . x x . A1
1 132
400A L400 . x x . A1
3 600A L600 . x x . A1
2 800A L800 . x x . A1
3 1200A L1200 . x x . A1
2-pole 60 2 88
125A L100 . x x . A2
2 180A L160 . x x . A2
2 132
400A L400 . x x . A2
3 600A L600 . x x . A2
2 800A L800 . x x . A2
3 1200A L1200 . x x . A2
3-pole 60 4 88
125A L100 . x x . A3
3 180A L160 . x x . A3
3 132
400A L400 . x x . A3
6 600A L600 . x x . A3
6 800A L800 . x x . A3
9 1200A L1200 . x x . A3
4-pole 60 4 88
125A L100 . x x . A4
4. pole early make 4 180A L160 . x x . A4
4 132
400A L400 . x x . A4
6 600A L600 . x x . A4
8 800A L800 . x x . A4
12 1200A L1200 . x x . A4
6-pole 60 6 88
125A L100 . x x . A6
6 180A L160 . x x . A6
6 132
400A L400 . x x . A6
9 600A L600 . x x . A6
12 800A L800 . x x . A6
18 1200A L1200 . x x . A6
Switch Disconnectors in Plastic Enclosure, IP65
AC21 AC23 plate Type No. Pack Weigth
690V 3x400V IP65 pcs. kg/pcs.
On-Off Switches 3-pole
20A 5,5kW 48
LTS20 PF A4 1 0,31
25A 7,5kW 48
LTS25 PF A4 1 0,31
32A 11kW 48
LTS32 PF A4 1 0,31
40A 15kW 48
LTS40 PF A4 1 0,31
63A 22kW 48
LTS63 PF A4 1 0,62
80A 22kW 48
LTS80 PF A4 1 0,62
PE
PE
D371E 55
Description Wiring diagram Switching angle Number of cells Type Design Switch Escutcheon
Size .E. .V. pro- plate
AC21 gram
Load Switches for resistive or slightly inductive loads or switching without load
Changeover switches U
1-pole 60 2 88
125A L100 . x x . U1
1 180A L160 . x x . U1
1 132
400A L400 . x x . U1
3 600A L600 . x x . U1
2 800A L800 . x x . U1
3 1200A L1200 . x x . U1
2-pole 60 2 88
125A L100 . x x . U2
2 180A L160 . x x . U2
2 132
400A L400 . x x . U2
3 600A L600 . x x . U2
4 800A L800 . x x . U2
6 1200A L1200 . x x . U2
3-pole 60 4 88
125A L100 . x x . U3
3 180A L160 . x x . U3
3 132
400A L400 . x x . U3
6 600A L600 . x x . U3
6 800A L800 . x x . U3
9 1200A L1200 . x x . U3
4-pole 60 4 88
125A L100 . x x . U4
4. pole early make 4 180A L160 . x x . U4
4 132
400A L400 . x x . U4
6 600A L600 . x x . U4
8 800A L800 . x x . U4
12 1200A L1200 . x x . U4
Changeover switches without off W
Ordering example: AC1 1200A panel mounting, changeover switch without off 4-pole L1200 E W4
1-pole 60 2 88
125A L100 . x x . W1
1 180A L160 . x x . W1
1 132
400A L400 . x x . W1
3 600A L600 . x x . W1
2 800A L800 . x x . W1
3 1200A L1200 . x x . W1
2-pole 60 2 88
125A L100 . x x . W2
2 180A L160 . x x . W2
2 132
400A L400 . x x . W2
3 600A L600 . x x . W2
4 800A L800 . x x . W2
6 1200A L1200 . x x . W2
3-pole 60 4 88
125A L100 . x x . W3
3 180A L160 . x x . W3
3 132
400A L400 . x x . W3
6 600A L600 . x x . W3
6 800A L800 . x x . W3
9 1200A L1200 . x x . W3
4-pole 60 4 88
125A L100 . x x . W4
4. pole early make 4 180A L160 . x x . W4
4 132
400A L400 . x x . W4
6 600A L600 . x x . W4
8 800A L800 . x x . W4
12 1200A L1200 . x x . W4
- Load Switches
56 D371E
Operating Knobs and Handles
All operating knobs can be moved on the hexagonal shaft, to permit
adaptation to different sheet thicknesses, etc.
Type N100
N40 N200
N60 L400
M10 N80 L600
M10H N20 L100 L800
M20 N33F L160 L1200
Knob movement mm 5 5 7 9
Hexagonal shaft dimension mm 5 7 9 12
Ordering example: Cam switch N60 V U3 with ball type handle red
Order type: N60 V U3 +B3
Dimensions see page 84
Types of handles
In the standard version, the switches are supplied with a black twist
knob or instrument knob (M10H - N33F), except for design SMA, which
has a grey toggle knob. Switches of size L, which consist of 2 or 3 switch
columns, come with a black hand wheel. If required, the switch can be
supplied with other knobs, which can later easily be exchanged.
All operating knobs have an insert, which sets the position of the knob
in relation to the switch shaft. This insert can be mounted in 8 different
positions (at intervals of 45), causing the angle of each individual
switch setting to be rotated by 45.
In the standard version, the
switch terminals are positio-
ned left and right (except
M10H). When the knob insert
is turned by 90, the lay-out
of the terminals changes to
top and bottom.
N100
N40 N200
N60 L400
M10 N80 L600
Knobs and handles Ordering M10H N20 L100 L800
Description Colour Code M20 N33F L160 L1200
Instrument knob grey +G1 X X
Standard for M10 to N33F black +G2 X X
red +G3 X X
white +G5 X X
Twist knob grey +R1 X X X X
Standard for N40 to N200 black +R2 X X X X
red +R3 X X X X
white +R5 X X X
yellow +R7 X X
Toggle knob grey +K1 X X
black +K2 X X
red +K3 X X
white +K5 X X
blue +K6 X
Ball type handle grey +B1 X X X
black +B2 X X X
red +B3 X X X
Hand wheel black +HR X
- Cam Switches
- Cam Switches
D371E 57
Escutcheon Plates
TELUX-Cam Switches in designs E, V, P, PF, SM, UP, Z and KE are
supplied with a square escutcheon plate consisting of a black frame
and plexi insert plate. The markings are printed in black are on the back
of the insert plate. To protect the markings so that they remain easy
to read, the back of the insert plate is lined with silver foil. In addition,
rectangular plates can be provided for all switch sizes, which can fitted
on all switches after mounting.
Square plate Rectangular plate
(with square plate)
TELUX-Cam Switches in design SMA, for distribution boards with
45mm inside edge of installation cover, is supplied with a grey cover
and black markings.
Special engraved markings on escutcheon plates are limited by the
available space. In the case of relatively large production runs or
frequent use of the text, we recommend ordering of a printing block.
This will be invoiced at cost price, and the engraving will not be
charged for. This investment generally pays with batches from 50
pieces upwards.
The "escutcheon plate" column of the selection and ordering tables for
switch programs indicates the standard plate and, in some cases, an
additional plate that is often used for the programs in question. If such
a plate, listed in the selection table, is desired, the appropriate code
number should be stated when ordering a switch and switch program.
Should only plates or parts of the latter be ordered, the order type is
assembled as shown by the following example.
Code letter of switch sizes
M10, M10H, M20 A
N20, N33F E
N40, N60, N80, L100, L160 H
N100, N200, L400, L600, L800, L1200 L
Ordering example: Escutcheon plate silver, complete, for cam
switch M10, marked with MAN OFF AUTO, angle of rotation 60
Order type:
However, if a switch with non-standard lettering is required, only
three-digit code number for the marking need be added to the order
type (see next page).
Dimensions see page 86
Description Order type
Switch size Plate Marking
Code letter Art.No. Code number
Escutcheon plate for designs E, V, P., Z, SM, KE and UP
Escutcheon frame black, plexi insert plate silver, markings black
Escutcheon plate complete silver A E H L .82... ... (see pp. 58-60)
Escutcheon plate complete yellow A E H L .90... ... (see pp. 58-60)
Plexi insert plate silver A E H L .85... ... (see pp. 58-60)
Plexi insert plate yellow A E H L .80... ... (see pp. 58-60)
Escutcheon frame black A E H L .8203 -
Rectangular escutcheon plate for designs E, V, Z and SM
Escutcheon frame black, plexi insert plate silver, markings black
Rectangular additional escutcheon plate complete silver A E H L .865.. ... (see pp. 58-60)
Rectangular additional escutcheon plate complete yellow A E H L .915.. ... (see pp. 58-60)
Plexi insert plate silver A E H L .885.. ... (see pp. 58-60)
Plexi insert plate yellow A E H L .895.. ... (see pp. 58-60)
Escutcheon frame black A E H L .8503 -
Installation cover for design SMA
grey cover , markings black A - - - .68... ... (see page 60)
A82088
Switch size Plate Marking
Code letter Art.No. for Code number
for M10, M10H standard plate with label
and M20 with markings, MAN OFF AUTO
complete angle of rot. 60
- Cam Switches
58 D371E
Escutcheon Plates
Code letter of switch sizes
M10, M10H, M20 A
N20, N33F E
N40, N60, N80, L100, L160 H
N100, N200, L400, L600, L800, L1200 L
Selected standard markings
The markings that are most commonly required are shown below,
together with code letters for the switch size and the code number.
Ordering example: Switch type M10H E A3 with escutcheon plate
"OFF ON" and additional rectangular escutcheon plate "PUMP"
Order type: M10H E A3 +003 +516
Blank escutcheon plates
000 001
A E H L A E H L
Switching angle 30
o
012 013 014 016 026 034 043 044 067 068
A E H A E A A A A A A A A
077 086 097 101 102 103 104 105 106 107
A A A A E H A E A E A E A E A E A
108 109 110 111 112 113 114 153 157 191
A E A E A E A A E A E A E A E
219 264 370 371 405 438 455 648 714 749
A A A E A A E A A A E E A
Switching angle 45
o
018 019 021 022 025 031 032 036 041 042
A E A E H L A E E A A E A A E
045 051 118 119 120 121 122 123 124 125
A A E A E A E E A E A E A E H L A E A E
126 127 128 129 131 160 221 243 244 247
A E A E A E A E E H A A E A E A E
- Cam Switches
D371E 59
Escutcheon Plates
Switching angle 45
o
248 249 250 303 304 336 412 421 423
A A E A E A E A A A E A E
Switching angle 60
o
002 003 004 006 007 008 009 010 011 015
A E H L A E H L A E H L A E H L A E H L A A A E H L A E H L A E
081 082 088 095 132 133 134 136 140 143
A E A E A E H A E A E H A E A E A A A
162 163 166 175 185 186 195 211 241 251
A E A E A E H L A A E E H L A A E
252 266 273 277 279 292 334 338 355 408
A A E A A A E H A A A E A A
416 417 418 419 420 422 439 446 448 489
A E A E A E A E A E A E A A E A A
634 635 636 675 699 702 706 739 798
A A A E H A A H A A A
- Cam Switches
60 D371E
Escutcheon Plates
Switching angle 90
o
028 029 030 056 083 087 089 144 145 217
A E A E A E A A E H L A E A E A E H E A
230 246 270 330
A E A E A A
Miscellaneous
020 054 071 092 147 148 149 172 225 289
E A A E A E H A E E A E A A
760
A
Rectangular additional escutcheon plates
500 501 503 504 505 506 509 519 520 524
A E H L A E A E A E A A E A E E A E
534 535 542 543 546 549 550 551 552 556
A A A E A A A A A A E E
557
A
Covers for design SMA
001 002 003 004 006 009 012 013 014 015
028 81 82 106 111 122 123 132 143 221
234 243 355 370 416 417 420 636 637 717
- Cam Switches
D371E 61
Switching angles
Arrangement of switch settings
All feasible arrangements of switch settings are shown, and defined by position numbers, in the following tables. Not only the switching angles,
but also switches with latched or momentary settings, or combinations of the two, are distinguished from one another.
Knowledge of the following variations is particularly important when planning special switches. It is necessary to state the position number when
ordering special switches, as the cheapest version will otherwise be selected.
All the switches types listed can be supplied with switching angles other than those indicated, provided that they are permitted by the switch program
(additional charge).
Switching angle 30
PN01 PN02 PN03 PN04 PN05 PN06 PN07 PN08 PN09 PN10
PN11 PN12 PN13 PN14 PN15 PN16 PN17 PN18 PN19 PN20
PN21 PN22 PN23 PN24 PN25 PN26 PN27 PN28
Switching angle 45
PN30 PN31 PN32 PN33 PN34 PN35 PN36 PN37 PN38 PN39
PN40 PN41 PN42 PN43 PN44 PN45 PN46 PN47 PN48 PN49
Switching angle 60
PN50 PN51 PN52 PN53 PN54 PN55 PN56 PN57 PN58 PN59
PN76 PN77 PN78 PN79 PN150 PN151
Switching angle 45/90
o
PN70 PN71 PN72 PN73
+) Not available for switch types M10, M10H and M20
- Cam Switches
62 D371E
Switching angles
+) Not available for switch types M10, M10H and M20
Switching angle 90
PN60 PN61 PN62 PN63 PN64 PN65 PN66 PN67 PN68 PN69
Momentary settings and special combinations
PN80 PN82 PN83 PN84 PN85 PN86 PN87 PN88 PN89 PN90
PN91 PN92 PN93 PN94 PN95 PN96 PN97 PN98 PN99 PN100
PN101 PN102 PN103 PN104 PN105 PN106 PN107 PN108 PN109 PN124
PN125 PN126 PN127 PN128 PN129 PN130 PN131
Spring return over several settings
PN110 PN111 PN112 PN113 PN114 PN115 PN116 PN117 PN118 PN119
PN120 PN121 PN122 PN123
- Cam Switches
D371E 63
Handles and drive units
Special actuating mechanisms and ancillary attachments can be
provided for many switch sizes and designs. Here, the switch type is
followed by order code for the ancillary attachment.
Dimensions see page 87
Removable knob drive
The operating knob is designed to be
removable, and can be withdrawn in any
setting. The switch shaft is covered when
the knob is withdrawn.
Removable knob drive 2
The operating knob is designed to be
removable. It can be withdrawn in one
setting, to be stated when ordering.
Roller arm
For actuation with gates, fork levers and
the like.
Roller arm 1, reinforced
with reinforced bearings on the switch
shaft and strong return spring.
Roller arm 2, reinforced
the switch rotates in intervals of 30. The
switch can only operate on conjunction
with the circular switching attachment
(+RU) and 12 switch 30settings
Eyelet lever
For cable or chain actuation.
Double arm eyelet lever cream-col.
black, red or grey availably
Eyelet lever 1, reinforced
with reinforced bearings on the switch
shaft and strong return spring.
Eyelet lever 2, reinforced
the switch rotates in intervals of 30. The
switch can only operate on conjunction
with the circular switching attachment
and 12 switch 30settings.
Footswitch drive unit
Single-arm footswitch with strong return
spring.
Stepswitch drive unit
When the footswitch is depressed, the
switch rotates in intervals of 30. The
stepswitch can only operate on conjunc-
tion with the circular switching attach-
ment (attachment +RU) and 12 switch
30settings (1 rotation).
Double arm Footswitch
Switching angle: 2 x 60
o
or 3 x 30
o
without spring return.
Ordering Suitable Suitable for
Code for designs switch type
+STGR E M10H, M20, N20, N33F
P M10, N20, N33F
+STGR2 E M10H, M20, N20, N33F
P M10, N20, N33F
+RH E, PF N20, N33F, N40, N60, N80
P N20, N33F, N40, N60
G, GF N20, N33F
1)
+RHS1 G, GF N20
+RHS2 G, GF N20
+H E, PF N20, N33F, N40, N60, N80
P N20, N33F, N40, N60
G, GF N20, N33F
1)
+H2 E,P,PF,G,GF N20, N33F
1)
+HS1 G, GF N20
+HS2 G, GF N20
+FUSS1 G, GF N20
+FUSS2 G, GF N20
+FUSS3 G, GF N20
Ordering example: Cam switch N20 GF W3R for foot operation
Order type: N20 GF W3R +FUSS1
1) Cast enclosed switches are delivered with switch type N32
- Cam Switches
64 D371E
Door couplings
Door couplings are available for switches to be installed in switchgear
cabinets or distribution boards with hinged doors. These permit the
doors to be openened without removal of the operating knobs.
Ordering example: Cam switch N100 V A3 with lockable door cou-
pling, moisture protected IP65, dimension T=580mm
Order type: N100 V A3 +TK2FR/580
Dimensions see page 88
For switches with door couplings it is necessary to state the installation
depth - that is, the distance between mounting level of the switch and
the inside edge of the door (dimension T).
Ordering Suitable Suitable for
Code for designs switch type
+TKE/... V, SM M10H, M20, N20, N33F
+TK2E/... V, SM M10H, M20, N20, N33F
+TK2Z/... V, SM M10H, M20, N20, N33F
+TK/... V N40, N60, N80, N100, N200
L100, L160, L400, L600
L800
+TKFR/... V N40, N60, N80, N100, N200
L100, L160, L400, L600
L800
+TK2/... V N40, N60, N80, N100, N200
L100, L160, L400, L600
L800
+TK2FR/... V N40, N60, N80, N100, N200
L100, L160, L400, L600
L800
Door coupling
Protection class from front: IP65
5-hole mounting
Door coupling locked
Protection class from front: IP65
5-hole mounting
Doors only open at a given switch set-
ting: unless otherwise stated, the "OFF"
setting.
Door coupling locked
Protection class from front: IP65
Central fixing 22mm
Doors only open at a given switch set-
ting: unless otherwise stated, the "OFF"
setting.
Door coupling
Protection class from front: IP40
5-hole mounting
Door coupling
Protection class from front: IP65
5-hole mounting
Door coupling locked
Protection class from front: IP40
5-hole mounting
Doors only open at a given switch set-
ting: unless otherwise stated, the "OFF"
setting.
Door coupling locked
Protection class from front: IP65
5-hole mounting
Doors only open at a given switch set-
ting: unless otherwise stated, the "OFF"
setting.
- Cam Switches
D371E 65
Lockable switches
Ordering example: Cam switch N20 E A3 key operated
Order type: N20 E A3 +SA
Dimensions see page 89 and 90
Key-operated and lockable switches are supplied with two keys. Addi-
tional keys or other types of lock on request.
Ordering Suitable Suitable for
Code for designs switch type
+SA E, V, SM M10H, M20, N20, N33F
E, V N40, N60
P M10, N20, N33F, N40, N60
SMA M10H, M20
UP M10
+SA/.
+SA Z, ZO M10H, M20
+SA/.
+SAK E M10H, M20
+SAK/.
+SASI E M10H, M20
P M10, M20
UP M10, M20
+SASO E M10H, M20
P M10, M20
UP M10, M20
Key operated switch
Lock Willenhal FT101, key removable in
all lockable settings.
Other types of lock on request.
Maximum number of cells
M10 - N33F: 6 N40, N60: 2
Key operated switch, key removable
only in some settings. Add letter of setting
where key is removable to ordering code
according to the scetch belove.
Key operated switch IP65
Lock Ronis R455, key removable in all
lockable settings.
Key operated switch, key removable
only in some settings. Add letter of setting
where key is removable to ordering code
according to the scetch above.
Key operated switch
Lock KABA8, key removable in all
lockable settings.
Key operated switch, key removable
only in some settings. Add letter of setting
where key is removable to ordering code
according the scetch belove.
Key operated switch with barrel
for special security functions
Lock EVVA EHZ50/5 Nickel matt
Special version which prevents not only
switching but also access to the cable
ends and removal of the switch when
locked.
Maximum number of cells
Design E, P: 4
Design UP : 3
Key operated switch for special
security functions without lock
for use of lock EVVA EHZ50/5 or with
same dimensions
Maximum number of cells
Design E, P: 4
Design UP : 3
- Cam Switches
66 D371E
Padlock devices
A range of padlock devices designed to prevent from being turned on
by unauthorized personnel, or during maintenance and repair work, can
be supplied.
Dimensions see page 91
Ordering example: Cam switch N33F E A3 with interlocking device
SV3 suitable for 3 padlocks
Order type: N33F E A3 +SV3
Padlock device
Description
Padlock device
Standard version black,
otherwise red,
for 1 or 2 padlocks.
Shackles up to 6mm
Standard version black 64 x 64mm,
otherwise red 64 x 64mm
Padlock device
Standard version black, otherwise
yellow insert plate and red twist knob
for 1-3 padlocks.
Shackles up to 8,5mm
Prior to insertion of the first padlock, a
red locking ledge must be depressed.
This indicates that the switch is locked.
Padlock device
Standard base grey, locking ring black,
or with yellow base and red locking
ring.
Locking ring for 1-3 padlocks.
Shackles up to 6mm
Standard base grey, locking ring
black 88 x 88mm,
or with yellow base and red locking ring
88 x 88mm
Key lock device
With a cylinder lock in the lock attach-
ment, one or more switch settings are
lockable (state when ordering). The
operating knob can only be turned when
unlocked. The key can be withdrawn
wheter locked or unlocked.
Special versions, in which the key can-
not be withdrawn when in some (unlok-
kable) settings can be supplied.
Key lock device
Special version for on-off switches, in
which it is possible to switch off without
a key.
Ordering Suitable Suitable for
Code for designs switch type
+SV1 E, V, SM M10H, M20
+SV1R P, PF M10
+SV164 E, V M10H, N20, N33F
+SV164R P, PF N20, N33F
+SV3 E, V N40, N60, N80, L100, L160
+SV3R E, V N100, N200, L400, L600,
E, V L800, L1200
PF N40, N60, N80, N100, N200
+SV4 E, V M10H, N20, N33F
+SV4R SM M10H, N20, N33F
P, PF N20, N33F
+SV488 E, V M10H, N20, N33F
E, V N40, N60, N80
+SV488R P, PF N40, N60, N80
+SZ E, V alle
SM M10H, M20, N20, N33F
+SZ2 E, V alle
SM M10H, M20, N20, N33F
- Cam Switches
D371E 67
Switch interlocks
A wide range of locks and interlocking devices, designed to prevent
accidental or hazardous switching, can be supplied.
Dimensions see page 92
Ordering example: Cam switch N20 E A3 with push button switch lock
Order type: N20 E A3 +DV
Description
Push button interlock
The switch can only be actuated when
the pushbutton is simultaneously de-
pressed (two-handed operation).
Interlock with electrical contact
The switch can only be actuated when
the pushbutton, which also operates a
make and break contact, is actuated (for
external interlocking devices or safety
measures).
Magnetic interlock
The switch can only be actuated when
an electromagnet is simultaneously ex-
cited. When ordering, voltage and per-
centage duty cycle of the magnet coll
should be stated.
Mutual interlock
Two or more switches, mounted on the
same front plate, can be mutually inter-
locked, such that one switch can only be
actuated when the other is in given
settings.
Circular switch
Switches that have the maximum num-
ber of settings for a given switching
angle can be made without a stop posi-
tion, permitting direct switching from the
last to the first setting.
Backswitch 1
Special version of the circular switch, in
which the switch can only be turned in
one direction.
Backswitch 2
Special version of the circular switch, in
which, in given positions, the switch can
only be operated in one direction.
Ordering Suitable Suitable for
Code for designs switch type
+DV E, V all
+ET E, V all
+MV E N20, N33F, N40, N60, N80
N100, N200
+GV E, V N20, N33F, N40, N60, N80
N100, N200
+RU all all
+RS1 all all
+RS2 all all
- Cam Switches
68 D371E
Couplings and stop mechanism
Description
Coupling of two columns
For simultaneous drive of two switch
columns (with very large number of
switch cells or limited installation depth).
Coupling of three columns
For simultaneous drive of three switch
columns.
Coupling of different switch sizes
For attachment of control switches (au-
xiliary contacts) to larger switches.
M10H, M20 in sizes E and H.
N20 to N80 in size L.
Delayed action switch
Using a delayed action coupling, two
switch shafts - a main shaft and delayed
shaft - can be coupled, such that the
delayed shaft is rotated together with
the main shaft once a given angle of
rotation is reached (e.g. for off-load re-
turn of switches used with pole-chan-
ging motors).
Second stop mechanism
With switches in which a large number
of contacts is simultaneously operated,
use of a second stop mechanism is
sometimes necessary, in order to ensure
precise switching to the next setting.
Metal stop mechanism
for extreme mecanical stress on the
stop mechanism, e.g. where many
contacts are switched at the same time.
Not for PN110 to PN123
Ordering Suitable Suitable for
Code for designs switch type
+ZK2 E, V all
+ZK3 E, V all
+ZWK E N40, N60, N80, L100, L160
N100, N200, L400, L600,
L800, L1200
+SK E, V N20, N33F, N40, N60, N80
G, GF N20, N32
+RW2 all all
+MRW E, V N40, N60, N80, L100, L160
E, V N100, N200, L400, L600,
E, V L800, L1200
G, GF N20, N32
A range of couplings and stop mechanisms for trouble-free operation of
switches with a very large number of contacts can be supplied.
Dimension see page 93
Ordering example: Cam switch N200 V ST0113 spread over three
columns interconnected by gears
Order type: N200 V ST0113 +ZK3
- Cam Switches
D371E 69
Special versions
A number of special versions can be supplied for adaptation of switches
to various conditions of use.
Ordering example: Cam switch M10H E U3 with pilot light for 230V
Order type: M10H E U3 +GFP +SL/230
Ordering Suitable Suitable for
Code for designs switch type
+WD E, V N20 to L1200
SM N20, N33F
+FPWD E, V, SM N20, N33F
+VW/... E, V all
SM M10H, M20, N20, N33F
+GFP E, V, SM M10H, N20, N33F
+GFPR E, V, SM M10H, N20, N33F
E all
+SLR/230 P M10, N20, N33F, N40, N60
+SLR/400 UP M10, N20
+SLG/230
+SLG/400
+GK all M10H, M20, N20, N33F
+TR all all
+FEU E N20, N33F
BK - -
Description
Switch shaft sealing
For increased front protection class on
IP54.
Front plate/switch shaft sealing
For increased front protection class on
IP65. In this version, a wider hole is
required for the shaft.
Dimensions see page 89
Extended switch shaft
For adaptation of switch designs V and
SM to the enclosure depth. State addi-
tional shaft length when ordering.
Large front plate
Switch with front plate and operating
knob of the next size (for replacement of
older, larger switches or aesthetic rea-
sons).
Large front plate + stop mechanism
Switch with front plate, stop mechanism
and operating knob of the next size
Switch with pilot lamp
lamp red, 230V
lamp red, 400V
lamp green, 230V
lamp green, 400V
Gold plated contacts
For electronic circuits with low voltages
and currents.
Tropical proof type
Neon safety switch
For all-pole switching off of neon adver-
tisement circuits by the Fire Brigade.
Dimensions see page 91
Door switch
Two-pole switch for circuit breaking when
doors to electrical operating areas are
opened.
I
th
= 20A, U
e
= 415V~
Dimensions see page 91
- Cam Switches
70 D371E
Accessories
Ordering example: Cam switch N20 E A3 with terminal cover plate
Order type: N20 E A3 +KLAD
A number of special versions can be supplied for adaptation of switches
to various conditions of use.
Dimensions see page 92
Description
Terminal cover plate
Prevents accidental touching of live ter-
minals (requirement for main switches
according to VDE 0113)
only for 2 cells
for all cells
Moisture proofing caps
Protection class from rear: IP54.
For protection of the switch from dust
and moisture (e.g. when installed in
machine pedestals). For switch moun-
ting from the front and rear. Conical
cable entry glands.
Maximum number of cells:
M10H 7
N20 5
N40 4
N60 2
Angled terminals
For easy connection of inaccessible
switches.
Unless otherwise stated, all terminals
specified with markings are equipped in
this manner.
A distinction is drawn between left and
right angled terminals. Seen from the
switch end, the left terminals are located
above left and below right; conversely,
right terminals are above right and be-
low left.
Fast-on connectors
For 6,3 x 0,8mm plugs.
Earth terminals
2 terminals, connected with one ano-
ther, insulated from switch column: for
earth conductors.
Additional rectangular
escutcheon plate 1 line
Dimensions see page 84
Big additional rectangular
escutcheon plate for 2 lines
Dimensions see page 84
Spare key for key operated switches
with Lock Willenhal FT101
Spare key for key operated switches
with Lock Ronis R455
Wrench
for switches with central fixing
Ordering Suitable Suitable for
Code for designs switch type
+KLAD E, V N20, N40, N60, N80
N100, N200
+KLAD E, V N33F
+FR E M10H, N20, N40, N60
+WK E,V M20, N20, N40, N60, N80,
N100
+AMPZ E, V M20, N20
+PE E, V, all
P, PF M10, N20, N33F, N40, N60
PF N80, N100, N200
G, GF N20, N32
SRE E, Z, V, SM all
SRE2 E, V M10H, M20, N20, N33F
J7101 E, V, P M10H, M20, N20, N33F,N40
SMA M10H, M20
B4-R455 Z, ZO M10H, M20
J7049 Z, ZO M10H, M20
D371E 71
Switching Programs to Customer Requirements
As a result of their modular construction, TELUX cam switches are
particularly suitable for manufacturing of special variants. According to
its function, each pair of contacts in the switch is adapted to the desired
program by appropriate design of the cam plate. In the case of switches
with an overall switching angle of more than 180, provision must made
for a cam plate in each switching cell, controlling two opposite, indepen-
dent contact pairs with matching programs (does not apply to M10,
M10H, M20 and N20).
Depending on the desired contact program for the special switch, it may
often be impossible to make full use of all switching cells, that is, to
include the maximum possible number of contacts. In determining the
number of cells or switch length, one-contact cells will sometimes be
resorted to.
Switch sizes M10, M10H, M20 and N20 are exceptions to this rule. Here,
two cam plates can be built into each cell, so that both contacts are
independently controlled (full use of the cells with special programs).
In all special switches with overall switching angles of less than 180,
the number of cells required is calculated by having the total number of
contacts in the switching program.
When planning for switches with special programs, choice of the
optimum switching angle thus plays an important part. The listing of all
the options for lay-out of switch settings, on pages 59 and 60, should be
an aid to planning (position numbers PN).
If special markings are to be engraved on the escutcheon plates, it is
vital to take account of the available space. It is advisable to use
abbreviations.
We provide forms (see final page) on request, free of charge, to give a
clear overview when special programs are being defined. Switch size,
design, type of operating knob and desired switching angle, as well as
the function of the contacts, are entered on these forms. Provision has
also been made in them for entry of details as to escutcheon plate
engravings or other special requirements.
Ordering Example
Order sheet A4 see last page
72 D371E
Benedikt & Jger-Low voltage switchgear are built and tested decisive
national and international specifications. All devices suit all important
specifications without any test obligation, like VDE 0660, BS 5419 and
also relative to IEC-recommendations.
That is the reason why Benedikt & Jger-Low voltage switchgear are
used all over the world. In order to provide special versions are
sometimes limitations to the max. voltages, currents and power ratings
or special markings necessary.
Kind of Category Typical Rated Test conditions for the number Test conditions for making
current fre- infre- applications operational of on-load operating cycles and breaking capacities
quent quent current (normal service) (operation in fault case)
oper- oper- Make Break Make Break
ation ation I/Ie U/Ue cos Ic/Ie Ur/Ue cos I/Ie U/Ue cos Ic/Ie Ur/Ue cos
AC20A AC20B No-load conditions all values - - - - - - - - - - - -
Alter- Switching of resistive loads
nating AC21A AC21B including moderate all values 1 1 0,95 1 1 0,95 1,5 1,05 0,95 1,5 1,05 0,95
Current overloads
Switching of mixed resistive
AC22A AC22B and inductive loads all values 1 1 0,8 1 1 0,8 3 1,05 0,65 3 1,05 0,65
including moderate overloads
Switching of motor loads 0<Ie100A 10 1,05 0,45 8 1,05 0,45
AC23A AC23B or other highly inductive all values 1 1 0,65 1 1 0,65
loads 100A<Ie 10 1,05 0,35 8 1,05 0,35
Slip-ring motors:
AC2 Starting, plugging all values 2,5 1 0,65 2,5 1 0,65 4 1,05 0,65 4 1,05 0,65
Squirrel-cage motors: 0<Ie100A Ie17A 0,65 Ie17A 0,65 0,45 0,45
AC3 Starting, switching off all values 6 1 1 0,17 10 1,05 8 1,05
motors during runing 100A<Ie Ie>17A 0,35 Ie>17A 0,35 0,35 0,35
Squirrel-cage motors: 0<Ie100A Ie17A 0,65 Ie17A 0,65 0,45 0,45
AC4 Starting, plugging, all values 6 1 6 1 12 1,05 10 1,05
inching 100A<Ie Ie>17A 0,35 Ie>17A 0,35 0,35 0,35
Control of electromagnetic
AC15 loads (> 72VA) - 10 1 0,7 1 1 0,4 10 1,1 0,3 10 1,1 0,3
I/Ie U/Ue L/R
1)
Ic/Ie Ur/Ue L/R
1)
I/Ie U/Ue L/R
1)
Ic/Ie Ur/Ue L/R
1)
DC20A DC20B No-load conditions all values - - - - - - - - - - - -
Direct Switching of resistive loads
current DC21A DC21B including moderate all values 1 1 1 1 1 1 1,5 1,05 1 1,5 1,05 1
overloads
Switching of mixed resistive
DC22A DC22B a. induct. loads incl. moderate all values 1 1 2 1 1 2 4 1,05 2,5 4 1,05 2,5
overloads (shunt motors)
Switching of highly inductive
DC23A DC23B loads (e.g. series motors) all values 1 1 7,5 1 1 7,5 4 1,05 15 4 1,05 15
Shunt-motors:
DC3 Starting, plugging, all values 2,5 1 2 2,5 1 2 4 1,05 2,5 4 1,05 2,5
inching
Series-motors:
DC5 Starting, plugging, all values 2,5 1 7,5 2,5 1 7,5 4 1,05 15 4 1,05 15
inching
Ue Rated operational voltage, U Voltage before make, Ur Recovery voltage, Ie Rated operational current, I Current made, Ic Current broken
1) Time in milliseconds (ms)
Technical Data
Note:
By plugging, is understood stopping or reversing the motor rapidly by
reversing motor primary connections while the motor is running.
By inching (jogging), is understood energizing a motor once or repeatly
for short periods to obtain small movements of the driven mechanism.
Utilization Categories
For easier choice of devices and in order to make the comparison
of different products simplier are utilization categories for cam switches
according to IEC 947-3, VDE 0660 Part 107 and auiliary contacts
according to IEC 947-5-1 and VDE 0660 Part 200 determind. The
Table below offers divers utilization catagories and assorted test
conditions.
Country Canada USA Switzer- Den- Norway Sweden Finland Poland Slowa- Czech Hun-
land mark kia garia
State deputy CSA UL UL SEV DEMKO NEMKO SEMKO SETI SEP SKTC EZU MEEI
or private examination
(state admitted)
Label marking 1)
of examination boards
Duty of approbation All switchgear or No duty of approbation since 1. 1. 1994 All All All All
Approbation Our devices are according to the harmonised switch- switch- switch- switch-
of switchgear European Standards e.g. EN 60947 gear gear gear gear
commendable (IEC 947, VDE 0660) and can be used generally
Specification UL is authorised for approbations Marking with approbation label is no longer
acc. to Canadian Standards necessary
1) CSA-approbations will be removed by UL-approbations valid for USA and Canada. On and after 1. 1. 2000 switchgear will be marked with the combined
UL-mark or only.
D371E 73
- Cam Switches
Technical Data
Data according to IEC 947-3, IEC 947-5-1, VDE 0660, EN 60947-3, EN 60947-5-1
Type M10 P M10H M20 N20 N32 G N33F N40 N60 N80 N100 N200
Rated therm. current I
th
open A 20 20 32 32 40 50 63 85 115 150 250
Rated therm. current I
the
encl. A 20 20 32 32 40 50 63 85 115 150 250
Rated operational voltage U
e
V 440 690
1)
690
1)
690
1)
690
1)
690
1)
690
1)
690
1)
690
1)
690
1)
690
1)
Disconnection property
2)
acc. to VDE, IEC up to V 440 440 440 440 440 440 690 440 440 690 690
Breaking capacity I
eff
3 x 220-440V A 160 160 220 220 260 260 380 520 740 900 1100
3 x 500V A - 100 160 160 200 200 290 380 560 680 850
3 x 660-690V A - 80 120 120 150 150 200 290 520 450 -
Utilization categ. AC21A, AC21B
Switching of resistive loads
including moderate overloads
Rated operational current I
e
A 20 20 32 32 40 50 63 85 115 150 250
Utilization categ. AC23A, AC23B
Switching of motor loads
or other highly inductive loads
Rated current I
e
400V A 16 16 30 30 30 45 45 60 85 105 135
Power rating 220-240V kW 4 4 7,5 7,5 7,5 11 15 22 30 40 40
3-phase 3-pole 380-440V kW 7,5 7,5 15 15 15 22 22 30 45 55 70
500V kW - 7,5 15 15 15 22 22 30 45 55 70
660-690V kW - 7,5 15 15 15 22 18,5 30 45 45 -
Star-Delta-Switches
for squirrel cage motors
Power rating
3-phase 3-pole 220-240V kW 3,7 3,7 7,5 7,5 7,5 8 11 15 18,5 37 40
380-415V kW 7,5 7,5 15 15 15 18,5 18,5 25 30 40 70
Utilization category AC3
Switching of three-phase motors
Rated current I
e
400V A 12 12 22 22 22 30 30 50 60 80 135
Power rating 220-240V kW 3 3 5,5 5,5 5,5 7,5 7,5 15 18,5 37 40
3-phase 3-pole 380-440V kW 5,5 5,5 11 11 11 15 15 25 30 40 70
500V kW - 5,5 11 11 13 15 15 25 30 40 70
660-690V kW - 5,5 11 11 13 15 15 25 30 40 -
Utilization category AC4
squirrel cage motors, inching
Power rating 220-240V kW 0,55 0,55 2,2 2,2 3 3,7 4 5,5 6 11 18,5
3-phase 3-pole 380-440V kW 1,5 1,5 4 4 5,5 5,5 7,5 11 15 18,5 35
500V kW - 1,5 4 4 5,5 5,5 7,5 11 15 22 35
660-690V kW - 1,5 4 4 5,5 5,5 7,5 11 15 22 -
Utilization category AC15
Control of electromagnetic loads,
contactors,
Rated current I
e
up to 240V A 6 6 12 12 16 16 - - - - -
380 -440V A 4 4 6 6 7 7 - - - - -
2-pole in series 500V A - 5 8 8 10 10 - - - - -
Utilization categ. DC21A, DC21B
Switching of resistive loads
Time constant L/R1ms
Rated current I
e
1-pole 30V A 20 20 32 32 40 40 63 80 100 150 250
60V A 4 4 6 6 20 20 30 30 30 - -
110V A 0,6 0,6 3 3 4 4 6 6 6 - -
220V A 0,3 0,3 0,8 0,8 0,8 0,8 1,3 1,3 1,3 2,5 2,5
440V A - - 0,4 0,4 0,4 0,4 0,6 0,6 0,6 0,7 0,7
Utilization category DC3 - DC5
Switching of shunt motors
and series motors
Time constant L/R15ms
Rated current I
e
1-pole 30V A 8 8 13 13 16 16 25 32 40 60 100
60V A 1 1 2,4 2,4 4 4 12 12 12 - -
110V A 0,3 0,3 0,5 0,5 1,6 1,6 2,4 2,4 2,4 - -
Protection class ot terminals IP00 IP20 IP00 IP00 - IP20 IP00 IP00 IP00 IP00 IP00
1) suitable for: earthed-neutral systems, overvoltage category I to III, pollution degree 3 (standard-industry): Uimp = 6kV. Data for other conditions on request
2) valid for lines with grounded common neutral termination, overvoltage category III , pollution degree 3.
74 D371E
Technical Data
- Cam Switches
Data according to IEC 947-3, IEC 947-5-1, VDE 0660, EN 60947-3, EN 60947-5-1
Type M10 P M10H M20 N20 N32 G N33F N40 N60 N80 N100 N200
Cable cross-sections
solid mm
2
1-2,5 1-2,5
1)
1,5-6 1,5-6 2,5-10 2,5-10 2,5-16
1)
6-25
1)
6-35 10-50
1)
50-150
flexible mm
2
0,75-2,5 0,75-2,5
1)
1-4 1-4 1,5- 6 1,5- 6 2,5-10
1)
6-25
1)
6-35 10-35
1)
35-120
flexible w. multicore cable end mm
2
0,75-2,5 0,75-1,5 1-4 1-4 1,5- 6 1,5- 6 2,5-6 6-16 6-35 10-25 -
Conductors to clamp per pole 2 2 2 2 2 2 2 1 1 1 1
Size of terminal screw M3 M3,5 M4 M4 M4 M4 M5 2xM5 2xM5 2xM6 M10
Tightening torque Nm 0,6-1,2 0,8-1,4 1,2-1,8 1,2-1,8 1,2-1,8 1,2-1,8 2,5-3 2,5-3 2,5-3 3,5-4,5 10
lb.inch 5-11 7-12 11-16 11-16 11-16 11-16 22-26 22-26 22-26 31-40 88
Short circuit protection
Max. fuse size gL (gG) A 20 20 35 35 50 50 63 100 125 160 250
Rated short-time withstand current
(1sec. current) A 250 250 400 400 500 500 800 1000 1400 1800 3000
Rated conditional
short-circuit current kAeff 10 10 10 10 10 10 10 10 10 10 10
Short-time capacity
Load duration 3s A 100 100 200 200 350 350 400 600 720 1000 2000
10s A 60 60 130 130 230 230 250 400 480 600 1200
Note: Ratings applies to 30s A 35 35 85 85 110 110 160 250 300 500 600
contacts already closed 60s A 25 25 65 65 80 80 110 200 250 370 480
Power loss at AC21A A 20 20 32 32 40 50 63 85 115 150 250
per pole W 0,6 0,5 0,9 1,1 1,5 1,9 2 2,8 4,4 5,7 21
Switching of capacitive loads
maximum making capacity
up to 500V A 140 140 300 300 350 350 400 600 700 900 1800
Data according to UL and cUL
Type M10 P M10H M20 N20 N33F N80 N100 N200 L400
Rated voltage V~ 300 600 600 600 600 600 600 600 600
Rated operational current "General Use" A 20 20 35 35 60 115 130 250 350
with jumper A 15 - 25 25 40 80 - - -
DOL-Rating 3-phase 110-120V hp 1 1 5 5 7 10 15 15 15
200-208V hp 2 2 5 5 10 15 25 25 25
220-240V hp 3 3 5 5 15 20 30 30 30
440-480V hp - 5 10 10 25 40 40 60 60
550-600V hp - 7 15 15 30 50 50 75 75
DOL-Rating 1-phase 110-120V hp 1 1 3 5 7 7 7
200-208V hp 1 1 3 3 5 7 15 15 15
220-240V hp 1 1 5 5 7 10 15 20 20
Fuse size (RK5) Manual Motor Controller A 40
2)
40 80 80 150 200 300 350 350
5kA / 600V and Motor Disconnect
Heavy pilot duty AC A300 A600 A600 A600 A600 - - - -
Cable cross sections
solid AWG 12 - 20 12 - 20 10 - 18 10 - 18 10 - 12 10 - 12 10 - 14 - -
flexible AWG 14 - 20 14 - 20 8 - 18 8 - 18 6 - 12 2 - 12 1 - 14 250kcmil 500kcmil
Tightening torque Nm 1.7 1-1.7 1.7-2.8 1.7-2.8 2.3-2.8 2.8 4.5 - -
lb.inch 15 9-15 15-25 15-25 20-25 25 40 - -
1) Maximum cable cross-section with prepared conductor
2) 5kA / 300V
D371E 75
Switch disconnectors LT
Technical Data
Data according to IEC 947-3, IEC 947-5-1, VDE 0660, EN 60947-3, EN 60947-5-1
Type LTS20 LTS25 LTS32 LTS40 LTS63 LTS80 LT80 LT100 LT125 LT160
Main contacts
Rated thermal current I
th
open A 20 25 32 40 63 80 80 100 125 160
Rated thermal current I
the
enclosed A 20 25 32 40 63 80 80/70
2)
100/80
2)
125 160
Rated insulation voltage U
i
1)
V 690 690 690 690 690 690 690 690 1000
3)
1000
3)
Rated operational current I
e
AC21A A 20 25 32 40 63 80 80 100 125 160
Making capacity I
eff
3x380-440V A 160 190 220 300 370 440 600 725 850 1050
Breaking capacity 3x220-240V A 160 180 200 250 330 380 560 700 800 900
3x380-440V A 160 180 200 250 330 380 560 650 750 850
3x660-690V A 80 110 140 170 190 220 200 280 340 340
Disconnection property performed up to V 690 690 690 690 690 690 690 690 1000
3)
1000
3)
Motor Switch AC3 3x400V A 9 12 16 23 30 37 45 60 72 85
Motor Switch AC3 3x220-240V kW 2,2 3 5,5 7,5 11 11 15 18,5 22 30
Direct switching of single motors 3x380-440V kW 4 5,5 7,5 11 15 18,5 22 30 37 45
3x660-690V kW 4 5,5 7,5 11 15 15 18,5 22 30 37
Main Switch AC23 3x400V A 12 16 23 30 45 45 60 72 85 110
Motor Switch, AC23A, 3x220-240V kW 3 4 5,5 7,5 15 15 18,5 22 30 30
Main Switch, AC23B 3x380-440V kW 5,5 7,5 11 15 22 22 30 37 45 55
Safety Switch 3x660-690V kW 5,5 7,5 11 15 18,5 18,5 22 30 37 37
Rated conditional short-circuit current kAeff 10 10 10 10 10 10 25 25 30 30
Max. fuse size gL (gG) A 25 35 40 50 63 80 80 100 125 160
Mechanical life x10
3
200 200 200 200 100 100 100 100 100 100
Rated short-time withstand current (1sec. current) A 250 300 400 500 600 850 1600 1850 2500 3000
Maximum cable cross sections
solid mm
2
10 10 10 10 25 25 35 35 95 95
AWG 8 8 8 8 4 4 2 2 3/0 3/0
flexible (+ multicore cable end) mm
2
6 6 6 6 16 16 25 25 50 50
AWG 10 10 10 10 6 6 5 5 1/0 1/0
Size of terminal screw M3,5 M3,5 M3,5 M3,5 M5 M5 - - - -
Tightening torque Nm 0,8-1,7 0,8-1,7 0,8-1,7 0,8-1,7 2-4 2-4 3 3 14 14
lb.inch 7-15 7-15 7-15 7-15 18-35 18-35 26 26 124 124
Auxiliary contacts
Rated insulation voltage U
i
1)
V 690 690 690 690 690 690 690 690 690 690
Rated thermal current I
th
, I
the
A 10 10 10 10 10 10 16 16 16 16
Switching capacity AC15 220-240V A 2,5 2,5 2,5 2,5 2,5 2,5 6 6 6 6
AC15 380-440V A 1,5 1,5 1,5 1,5 1,5 1,5 3 3 4 4
Rated conditional short-circuit current kA
eff
3 3 3 3 3 3 3 3 3 3
Max. short circuit protection gL (gG) A 10 10 10 10 10 10 16 16 16 16
Maximum cable cross sections
solid mm
2
2,5 2,5 2,5 2,5 2,5 2,5 4 4 4 4
AWG 12 12 12 12 12 12 12 12 12 12
flexible (+ multicore cable end) mm
2
2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5 2,5
AWG 14 14 14 14 14 14 14 14 14 14
Data according to UL und cUL
Type LTS20 LTS25 LTS32 LTS40 LTS63 LTS80 LT80 LT100 LT125 LT160
Rated voltage V 600 600 600 600 600 600 600 600 600 600
Ampere-Rating "General use" A 20 25 32 40 63 80 80 100 150 200
DOL-Rating 3-phase 110-120V HP 0,75 1 1.5 2 3 5 7.5 10 15 20
220-240V HP 1,5 2 3 5 7,5 10 20 25 30 40
440-480V HP 3 5 7,5 10 15 20 40 50 60 60
550-600V HP 5 7,5 10 15 20 25 50 50 60 60
DOL-Rating 1-phase 110-120V HP 0,3 0,5 0.5 1 1.5 2 3 5 - -
200-208V HP 0,5 0,75 1 2 2 3 - - - -
220-240V HP 0,7 1 1.5 3 3 5 10 15 - -
Fuse size (RK5) Manual Motor Controller A 40 50 50 70 90 110 200
4)
250
4)
350
4)
400
4)
5kA / 600V Motor Disconnect A 40 50 50 50 70 70 200
4)
250
4)
350
4)
400
4)
1) suitable for: earthed-neutral systems, overvoltage category I to III, pollution degree 3 (standard-industry): Uimp = 6kV. Data for other conditions on request
2) the values after the slash are valid for switches 6-pole or more
3) Suitable for no load applications(AC20A) above 690V
4)Fuse RK1 / 10kA / 600V
76 D371E nderungen vorbehalten
- Cam Switches
Technical Data
Data according to IEC 947-3, IEC 947-5-1, VDE 0660, EN 60947-3, EN 60947-5-1
Type L100 L160 L400 L600 L800 L1200
Rated insulation voltage U
i
V 690
2)
690
2)
690
2)
690
2)
690
2)
690
2)
Rated thermal current I
th
open A 125 180 400 600 800 1200
Rated thermal current I
the
encl. A 125 180 400 600 800 1200
busbar busbar
with conductor mm
2
50 70 40x5 40x10 2x40x10 2x50x10
Utilization category AC21A, AC21B
Switching of resistive loads,
including moderate overloads
Rated operational current I
e
A 125 180 400 400 400 400
Shot-time current-carrying capacity
Load duration 1s - - 4800 6500 8500 10000
3s 800 1200 3600 5000 6500 8000
10s 500 800 2000 3200 4000 5800
Note: Ratings applies to 30s 320 480 1200 1700 2200 3200
contacts already closed 60s 180 380 960 1300 1700 2300
Cable cross-sections
solid or stranded mm
2
25-50
1)
cable lug busbar busbar busbar busbar
flexible mm
2
25-50
1)
70 40x5 40x10 2x40x10 2x50x10
flexible with multicore cable end mm
2
25-35 - - - - -
Size of terminal screw 2xM5 M8 M12 M16 M16 M16
Number of conductors to clamp per pole 1 1 1 2 1 1
Short circuit protection
Max. fuse size slow, gL (gG) A 125 200 400 630 800 1250
1) Maximum cable cross-section with prepared conductor
2) suitable for: earthed-neutral systems, overvoltage category I to III, pollution degree 3 (standard-industry): Uimp = 6kV. Data for other conditions on request
Approvals
Country USA, Canada Switzerland Europe Russia CB/CCA-
UL SEV GOST Certificates
Type
Cam Switches (UL-Listed as MANUAL MOTOR CONTROLLER and suitable as MOTOR DISCONNECT)
M10 o o o o o
M10H o o o o o
M20 o o o o o
N20 o o o o o
N33F o o o o o
N40 - o o o o
N60 - o o o o
N80 o o o o o
N100 o o o o o
N200 o o o o o
L400 o - - -
Switch disconnectors (UL-Listed as MANUAL MOTOR CONTROLLER and suitable as MOTOR DISCONNECT)
LTS20 o o o o o
LTS25 o o o o o
LTS32 o o o o o
LTS40 o o o o o
LTS63 o o o o o
LTS80 o o o o o
LT80 o - o - o
LT100 o - o - o
LT125 o - o - -
LT160 o - o - o
o In standard version approved / No testing required CE x In test
- Not provided for test till now
D371E 77
Panel mounting E
M10 - N100 N200
Type A B C D D1 D2 D3 E G H K S Mounting holes: built in from ear
M10H 48 36 5 44
1)
5 8 - 4 3,5 9,5 19 SW5 1) 44,5 x 42
M20 48 36 5 56 5 8 57 4 3,5 12,5 19 SW5
N20 64 48 5 56 5 12 57 4,2 3 12,5 20 SW7
N33F 64 48 5 58
2)
5 12 - 4,2 3 15,5 20 SW7 2) 58 x 58
N40 86 68 7 80 6 12 82 5,2 3,5 18 24,5 SW9
N60 86 68 7 80 6 12 82 5,2 3,5 29,5 24,5 SW9
N80 86 68 7 80 6 12 82 5,2 3,5 29,5 24,5 SW9
N100 132 110 9 128 7 16 129 6,2 5 30 37 SW12
N200 132 110 9 128 7 16 - 6,2 5 40 37 SW12
Dimension L with .. cells
Type 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Mounting holes: built in from front
M10H 36,5 46 55,5 65 74,5 84 93,5 103 112,5 122 131,5 141 - - -
M20 38,5 51 63,5 76 88,5 101 113,5 126 138,5 151 163,5 176 - - -
N20 40,5 53 65,5 78 90,5 103 115,5 128 140,5 153 165,5 178 190,5 203 215,5
N33F 44 59,5 75 90,5 106 121,5 137 152,5 168 183,5 199 214,5 230 245,5 261
N40 52,5 70,5 88,5 106,5 124,5 142,5 160,5 178,5 196,5 214,5 232,5 250,5 268,5 286,5 304,5
N60 64 93,5 123 152,5 182 211,5 241 270,5 300 329,5 359 388,5 - - -
N80 64 93,5 123 152,5 182 211,5 241 270,5 300 329,5 359 388,5 - - -
N100 88 118 148 178 208 238 268 298 328 358 388 418 - - -
N200 96 136 176 216 256 296 336 376 416 456 496 536 - - -
Central fixing Z Central fixing without escutcheon plate ZO
M10H, M20, N33F M10H, M20 Mounting hole:
Further dimensions see tables above
Mini-Cam Switches M4H
Panel mounting E Central fixing Z, ZO ZO Z
Dimension L with .. cells
Type A B D M 1 2 3 4 5 6 7 8
M4H mm 30 28 29,5 12,5 38,5 50,5 62,5 74,5 86,5 98,5 110,5 122,5
- Cam Switches
78 D371E
- Cam Switches
Flush mounting UP
M10 N20 (dimensions of standard flush wall mounting box see page 90)
Base mounting V
M10H - N100 N200
Type A B D D1 D2 E G H I K K1 S Mounting holes: for escutcheon plate
M10 48 36 39 5 8 4 3,5 9,5 6 19 41 SW5
M10H 48 36 44
1)
5 8 4,2 3 9,5 6 19 41 SW5 1) 42 x 44,5
M20 48 36 56 5 8 4,2 3 12,5 6 19 47 SW5
N20 64 48 56 5 12 4,2 3 12,5 0 20 29 SW7
N33F 64 48 58
2)
5 12 4,2 3 15,5 0 20 31,5 SW7 2) 58 x 58
N40 86 68 80 6 12 5,2 3,5 18 - - 38,5 SW9
N60 86 68 80 6 12 5,2 3,5 29,5 - - 49,5 SW9
N80 86 68 80 6 12 5,2 3,5 29,5 - - 49,5 SW9
N100 132 110 128 7 16 6,2 5 30 - - 79,5 SW12
N200 132 110 128 7 16 6,2 5 40 - - 104 SW12
Dimensions L with .. cells
Type 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
M10 34,5 44 53,5 63 72,5 82 91,5 101 110,5 120 129,5 139 - - -
M10H 36,5 46 55,5 65 74,5 84 93,5 103 112,5 122 131,5 141 - - -
M20 38,5 51 63,5 76 88,5 101 113,5 126 138,5 151 163,5 176 - - -
N20 40,5 53 65,5 78 90,5 103 115,5 128 140,5 153 165,5 178 190,5 203 215,5
N33F 44 59,5 75 90,5 106 121,5 137 152,5 168 183,5 199 214,5 230 245,5 261
N40 52,5 70,5 88,5 106,5 124,5 142,5 160,5 178,5 196,5 214,5 232,5 250,5 268,5 286,5 304,5
N60 64 93,5 123 152,5 182 211,5 241 270,5 300 329,5 359 388,5 - - -
N80 64 93,5 123 152,5 182 211,5 241 270,5 300 329,5 359 388,5 - - -
N100 88 118 148 178 208 238 268 298 328 358 388 418 - - -
N200 96 136 176 216 256 296 336 376 416 456 496 536 - - -
Snap-on mounting SM Swich with installation cover SMA
M10H - N33F for 35mm DIN-rail mounting according to DIN EN 50022 M10H, M20 for 35mm DIN-rail mounting according to DIN EN 50022
Dimension X with .. cells Dimension Y with .. cells
Dimensions see tables above Type 1, 2 3 4 5 1, 2 3 4 5
M10H 44 44 61 76 60 60 75 90
M20 44 61 76 76 60 75 90 90
D371E 79
Plastic enclosed switches P, PF
M10 - N60 N100, N200
N60, N80
Dimension L with .. cells
Type A B C D E F G P 1 2 3 4 5 6
M10 66 64 50 36 5 15,5 26 M20 43 52 62 71 81 90
N20 82 78 57 53 4,5 17 35 M20 66 66 80 94 108 122
N33F 112 108 85 50 5 20 50 M25 92 92 92 110 128 146
N40 112 108 85 50 5 20 50 M25 92 92 110 128 146 164
N60 112 108 85 50 5 20 50 M25 92 110 - - - -
N60 182 180 120 120 5,5 36,5 - 1) - - 165 215 215 -
N80 182 180 120 120 5,5 36,5 - 1) 110 110 165 215 215 -
N100 210 310 165 255 6,5 52,5 - 2) 130 130 180 - - -
N200 310 310 255 255 6,5 52,5 - 3) 130 180 230 - - -
Motor terminal box mounting KE
M10 - N33F Mounting holes
Dimension L with .. cells
Type A B C D D1 D2 E F G 2 3 4 5 6
M10 66 64 58 39 4 48 3,2 24 6 22 31,5 41 50,5 60
N20 82 78 71 48 5 57 4,2 34 5 24,5 37 49,5 62 74,5
N33F 112 108 100 56 5 70 4,2 49 11 32,5 48 63,5 79 94,5
Plastic enclosed motor starter PM
N20
Dimension L with .. cells
Typ P 1 2 3 4 5 6
N20 M25 80 80 80 92,5 105 117,5
- Cam Switches
1) knock outs for M40/M32 + 4x M20 at
top and bottom
M32/M25 + 4x M20 at the right and left
hand side,
2) 2 flange plates with hole 50,5 at top and
bottom
3) 2 flange plates with hole 50,5 at top and
bottom, can also be mounted at the right
and left hand side
4) old version
80 D371E
- Cam Switches
Cast aluminium enclosed switches G, GF
N20 - N200
N20 4 x M25
N32 4 x M25
Plastic enclosure horizontal PLF (Replacement for cast aluminium enclosure G, GF)
N40, N60, N80
Type N40 1 - 6 cells N40 7 - 10 cells
N60 1 - 3 cells N60 4 - 6 cells
N80 1 - 3 cells N80 4 - 6 cells
A 182 254
B 167 239
C 120 190
D - 65
P 2 x 40,5 (M40) 4 x 40,5 (M40)
1) old version
D371E 81
Switch disconnectors LT(S)
Main Switches, Switch Disconnectors LT(S)..
Panel mounting LT(S).. E(HN)..
On-OFF Switches 3-pole, 4-pole On-OFF Switches 6-pole, 8-pole Mounting holes
Changeover Switches 3-pole, 4-pole
Single hole mounting LTS.. Z(HN).. Mounting of add-on modules
On-OFF Switches 3-pole, 4-pole Mounting holes Panel mounting, Single hole mounting
3-pole 4-pole 6-pole 8-pole aux. 4
.
pole 3-pole 6-pole
Escutch. plate or contact PE 4-pole 8-pole
Type padlock device A B B B B B1 B2 C1 D1 D2 E F G H H
LTS.. 48
64
SV1 SV164
Padlock devices
SV4 SV488 SV34
Aux. contact LH..
4. pole
PE-, N-terminal
Aux. contact LH..
82 D371E
Switch disconnectors LT(S)
Main Switches, Switch Disconnectors LT(S)..
Base mounting LTS.. VZV(HN)..
On-OFF Switches 3-pole, 4-pole 6-pole On-OFF Switches 6-pole, 8-pole Mounting
for LTS20 - 40 only Changeover Switches 3-pole, 4-pole holes
L = X - 403 L = X - 403 L = X - 603
Base mounting LT(S).. V(HN)..
On-OFF Switches 3-pole, 4-pole 6-pole On-OFF Switches 6-pole, 8-pole Mounting
for LTS20 - 40 only Changeover Switches 3-pole, 4-pole holes
L = T - 603 for LTS20 - 80 only L = X - 603 L = T - 803 for LTS20 - 80 only
Base mounting LTS.. VZ(HN)..
On-OFF Switches 3-pole, 4-pole 6-pole On-OFF Switches 6-pole, 8-pole Mounting
for LTS20 - 40 only Changeover Switches 3-pole, 4-pole holes
3-pole 4-pole 6-pole 8-pole aux. 4.Pole
Escutch. plate or contact PE
Type padlock device A B B B B B1 B2 C1 D1 D2 D3 E G K K1 J
LTS20 -40 64