Project Name : ...... Prepare by : .... Revision : .....

Location : .... Approved by : ........ Sheet No. : ..........


CHAP CHAP
REF REF


HOUR OF OPERATION
GLASS 50 SQ FT X 108.24 X 0.94 CONDITIONS DB WB % RH DP GR/LB
GLASS 50 SQ FT X 108.24 X 0.94 OUTDOOR (OA) 95 83 0 0 0
GLASS 50 SQ FT X 108.24 X 0.94 ROOM (RM) 76 50 0 0 0
GLASS 50 SQ FT X 108.24 X 0.94 DIFFERENCE 19 XXX XXX XXX 0
3

&

4
2
6
AREA OR
QUANTITY
TABLE REFERENCE
ITEM 12.00 AM
TABLE REFERENCES
FACTOR
COOLING LOAD CALCULATION SHEET
SOLAR GAIN-GLASS (Btu/hr)

16 25,436
15.00 PM ESTIMATE FOR
OUTDOOR AIR SKYLIGHT 50 SQ FT X 108.24 X 0.94

40 PEOPLE X 50 CFM/PERSON 2000
WALL 200 SQ FT X 19 X 0.32 1000 SQ FT X 5 CFM/SQ FT = 5000
WALL 200 SQ FT X 19 X 0.32 5000
WALL 200 SQ FT X 19 X 0.32


WALL 200 SQ FT X 19 X 0.32 50 12 CFM/PERSON 600
ROOF-SUN 200 SQ FT X 19 X 0.67 3 100 CFM/DOOR 300
ROOF-SHADED 200 SQ FT X 19 X 0.67 300
20 50 1000
ALL GLASS 30 SQ FT X 19 X 0.45 0
PARTITION 30 SQ FT X 19 X 0.67 5000 CFM
OA
CEILING 30 SQ FT X 19 X 0.32
FLOOR 30 SQ FT X 19 X 0.1 0.900
INFILTRATION 500 CFM X 19 X 1.08

53 53 F
PEOPLE 25 PEOPLE X 63
POWER HP OR KW X 63 0.5 76 53 11.5
LIGHT WATT X 3.4 X 12
APPLIANCE ETC. X 12 6,058 CFM
DA
ADDITIONAL HEAT GAIN X 12 11.5

8.50
6058
6,058 CFM
SA
SAFETY FACTOR 10 % 8.50
SUPPLY DUCT + SUPPLY DUCT + FAN 6058 6,058 -
HEAT GAIN % 15 LEAK LOSS % 10 10
OUTDOOR AIR 15 CFM X 19 F X 0.5
76 0.83 95 76 92

INFILTRATION 300 CFM X 15 GR/LB X 0.68 53 0.5 92 53 72
PEOPLE 30 PEOPLE X 0
STEAM 0 LB/HR X 1050 FROM PSYCH. CHART : 8 0
APPLIANCE ETC. 0 X 0
ADDITIONAL HEAT GAIN 0
VAPOR TRANS. 30 5 30
SAFETY FACTOR 10 % 1. USE DRY-BULB (DB) TEMPERATURE DIFFERENCE FROM TOP OF ESTIMATE FORM.
2. USE MOISTURE CONTENT (GR/LB) DIFFERENCE FROM TOP OF ESTIMATE FORM.
SUPPLY AIR DUCT LEAK LOSS 10 % 3. NORMALLY. USE "CFM VENTILATION" FOR "CFM OUTDOOR AIR" HOWEVER
OUTDOOR AIR 0 CFM X 0 0.5 WHEN INFILTRATION IS TO BE OFFSET, REFER TO PAGE 92 TO DETERMINE
"CFM OUTDOOR AIR."
4. WHEN INFILTRATION IS NOT TO BE OFFSET, AND "CFM VENTILATION IS LESS THAN
"CFM INFILTRATION," THEN THE EXCESS INFILTRAITON IS ACCOUNTED FORHERE.
SENSIBLE : 450 CFM X 5 0.5
LATENT : 510 CFM X 2 0.5
RETURN DUCT RETURN DUCT
HEAT GAIN % + LEAK GAIN %
HP DEHUM. &
PUMP % + PIPE LOSS % * IF THIS DIFF TEMP IS TOO HIGH, DETERMINE SUPPLY CFM FOR DESIRED DIFFERENCE BY SUPPLY
AIR QUANTITY FORMLA.
#
WHEN BYPASSING MIXTURE OF OUTDOOR AND RETURN AIR, USE SUPPLY CFM WHEN BYPASSING
RETURN AIR ONLY, USE DEHUMIFIED CFM.
55,616
50,560
83,552
SUB TOTAL 4 (Btu/hr) 2,126
10
5
10
5
GRAND TOTAL HEAT (Btu/hr) 85,677
7
8
7
ROOM LATENT HEAT (Btu/hr) 8,316
EFFECTIVE ROOM LATENT HEAT (Btu/hr) 8,316
EFFECTIVE ROOM TOTAL HEAT (Btu/hr)
5
7,560
3

&

7
8
6
EFFECTIVE ROOM SENSIBLE HEAT(Btu/hr) 75,236
SUB TOTAL 3 (Btu/hr)
7
STORAGE SQ FT X 25 2
SUB TOTAL 2 (Btu/hr)
3

&

4
6
5
8
6
3

&

7
25
2

&

3
SUPPLY AIR QUANTITY
CFM INFILTRATION
CFM OUTDOOR AIR THRU APPARATUS
APPARATUS DEWPOINT
0.4 X
50,580
NOTES


RESULTING ENT & LVG CONDITIONS AT APPARATUS
4,050
25
25
25




DEHUMIDFIED AIR QUANTITY
TRANS. GAIN-EXCEPT WALLS & ROOF (Btu/hr)
11,138
CFM VENTILATION =
9,956
SOLAR & TRANS. GAIN-WALLS & ROOF (Btu/hr)
OUTDOOR AIR HEAT 1,635
7,560 LATENT HEAT (Btu/hr)
ROOM SENSIBLE HEAT (Btu/hr)
INTERNAL HEAT (Btu/hr)
OUTDOOR AIR
SUB TOTAL 1 ( Btu/hr)
BF X 0.68
GR/LbX
=
CFM
BA
H.P.

GR/LbX
BF X 1.08
GR/Lb X (1 -
BF)X1.08
FX (1 -
%
F ,
(1 -
SQ.FTX1/100X
BF)X0.68
LOCAL TIME
SUN TIME
PEAK LOAD
LOCAL TIME
SUN TIME
VENTI-
LATION
INFIL-
TRATION
SUNGAIN OR
TEMP. DIFF
PEOPLE X
OPEN DOORS DOORS X =
EXHAUST FAN
CRACK FEET X CFM/FT =
ESHF
EFFECTIVE
SENS. HEAT
=
=
EFFECTIVE ROOM SENS. HEAT
EFFECTIVE ROOM TOTAL HEAT
=
ADP INDICATED ADP SELECTED ADP
TEMP.
RISE
BF) X (T
RM
F - T
ADP
F) = F
DEHUM.
EFFECTIVE ROOM SENS. HEAT
1.08 X F
TEMP.RISE
F
(RM-OUTLET AIR)*

ROOM SENS. HEAT
1.08 X CFM
DA 1.08 X
OUTLET
TEMP.
DIFF.
CFM
SUPPLY
CFM
BYPASS
CFM
ROOM SENS. HEAT
1.08 X F
DESIRE DIFF
=
=
=
CFM
DA CFM
SA
-

=
EDB
LDB
T
RM F +
CFM
OA
CFM+

X (T
OA
F -T
RM
F) = T
ED
F
T
ADP F + BF X (T
EDB
F -T
ADP
F) = T
LD F
T
EWB
F , T
LWB
F
SWINGING
REVOLVING DOORS
SDM#1-01 , File : 230194937.xls.ms_office Date : 5/23/2014 ,Time :2:07 PM
B10 Cell:
Solar gain-glass can Comment:
calculate by two method . First is for "With the Storage Factor",use the description of case 1. Second is for "without the Storage Factor",use the description of case 2.
C11 Cell:
Windows area , sq ft Comment:
Area of glassed structure that solar haet gain get thru at varies exposure. ( N,E,S,W,NE,SE
,SW,NW) , Chapter 3
E11 Cell:
Comment:
Solar heat gain thru glass,Btu/(hr)-(sq ft)
Case 1; With Storage factor
Multiplying of "Peak solar heat gain thru ordinary glass" (at the selected month , location ,exposure) and " Storage load factors of solar heat gain".
( Table 6, Page 29 for Peak solar heat gain thru ordinary glass and Table 7,8,9,10 or 11 ,Page 30-34 for Storage load factors of solar heat gain thruglass) :
Example : The peak solar heat gain for a west exposure
in July at 40 north Latitude = 164 Btu/hr-sqft (Tbl.6) and the
Storage load factor with internal shade = 0.66 for a west exposure at 4 pm ,the weight ~ 100 lb/sq ft. So, the
Solar heat gain thru glass for a west = 164x0.66 =
108.24 Btu/hr
Case 2 ;Without Storage factor
Solar heat gain thru ordinary glass" (at the selected month , location ,exposure) , ( Table15, Page 44-49 )
G11 Cell:
Comment:
Over all Factor for solar heat gain
Case 1: With storage factor
Factor for adjustment of the value of solar heat gain as the effect of Shading Device or Glass block . And the correction factor(Table 16,Page 52, Over all Factors for solar heat
gain thru glass , Table 17, Page 54, Solar heat gain for glass block)
Example : Factor of solar heat gain thru glassfor the Regular plate Glass = 0.94
Case 2 : Without storage factor
Correction factor on the bottom of Table 15, Page 44-49
J11 Cell:
Out door & Room condition Comment:
- Outdoor condition see Table 1-3 Page10-19
- Room Condition see Table 4-5, Page 20-23
C12 Cell:
Windows area , sq ft Comment:
Area of glassed structure that solar haet gain get thru at varies exposure. ( N,E,S,W,NE,SE
,SW,NW) , Chapter 3
SDM#1-01 , File : 230194937.xls.ms_office Date : 5/23/2014 ,Time :2:07 PM
E12 Cell:
Comment:
Solar heat gain thru glass,Btu/(hr)-(sq ft)
Case 1; With Storage factor
Multiplying of "Peak solar heat gain thru ordinary glass" (at the selected month , location ,exposure) and " Storage load factors of solar heat gain".
( Table 6, Page 29 for Peak solar heat gain thru ordinary glass and Table 7,8,9,10 or 11 ,Page 30-34 for Storage load factors of solar heat gain thruglass) :
Example : The peak solar heat gain for a west exposure
in July at 40 north Latitude = 164 Btu/hr-sqft (Tbl.6) and the
Storage load factor with internal shade = 0.66 for a west exposure at 4 pm ,the weight ~ 100 lb/sq ft. So, the
Solar heat gain thru glass for a west = 164x0.66 =
108.24 Btu/hr
Case 2 ;Without Storage factor
Solar heat gain thru ordinary glass" (at the selected month , location ,exposure) , ( Table15, Page 44-49 )
G12 Cell:
Comment:
Over all Factor for solar heat gain
Case 1: With storage factor
Factor for adjustment of the value of solar heat gain as the effect of Shading Device or Glass block . And the correction factor(Table 16,Page 52, Over all Factors for solar heat
gain thru glass , Table 17, Page 54, Solar heat gain for glass block)
Example : Factor of solar heat gain thru glassfor the Regular plate Glass = 0.94
Case 2 : Without storage factor
Correction factor on the bottom of Table 15, Page 44-49
C13 Cell:
Windows area , sq ft Comment:
Area of glassed structure that solar haet gain get thru at varies exposure. ( N,E,S,W,NE,SE
,SW,NW) , Chapter 3
E13 Cell:
Comment:
Solar heat gain thru glass,Btu/(hr)-(sq ft)
Case 1; With Storage factor
Multiplying of "Peak solar heat gain thru ordinary glass" (at the selected month , location ,exposure) and " Storage load factors of solar heat gain".
( Table 6, Page 29 for Peak solar heat gain thru ordinary glass and Table 7,8,9,10 or 11 ,Page 30-34 for Storage load factors of solar heat gain thruglass) :
Example : The peak solar heat gain for a west exposure
in July at 40 north Latitude = 164 Btu/hr-sqft (Tbl.6) and the
Storage load factor with internal shade = 0.66 for a west exposure at 4 pm ,the weight ~ 100 lb/sq ft. So, the
Solar heat gain thru glass for a west = 164x0.66 =
108.24 Btu/hr
Case 2 ;Without Storage factor
Solar heat gain thru ordinary glass" (at the selected month , location ,exposure) , ( Table15, Page 44-49 )
SDM#1-01 , File : 230194937.xls.ms_office Date : 5/23/2014 ,Time :2:07 PM
G13 Cell:
Comment:
Over all Factor for solar heat gain
Case 1: With storage factor
Factor for adjustment of the value of solar heat gain as the effect of Shading Device or Glass block . And the correction factor(Table 16,Page 52, Over all Factors for solar heat
gain thru glass , Table 17, Page 54, Solar heat gain for glass block)
Example : Factor of solar heat gain thru glassfor the Regular plate Glass = 0.94
Case 2 : Without storage factor
Correction factor on the bottom of Table 15, Page 44-49
C14 Cell:
Windows area , sq ft Comment:
Area of glassed structure that solar haet gain get thru at varies exposure. ( N,E,S,W,NE,SE
,SW,NW) , Chapter 3
E14 Cell:
Comment:
Solar heat gain thru glass,Btu/(hr)-(sq ft)
Case 1; With Storage factor
Multiplying of "Peak solar heat gain thru ordinary glass" (at the selected month , location ,exposure) and " Storage load factors of solar heat gain".
( Table 6, Page 29 for Peak solar heat gain thru ordinary glass and Table 7,8,9,10 or 11 ,Page 30-34 for Storage load factors of solar heat gain thruglass) :
Example : The peak solar heat gain for a west exposure
in July at 40 north Latitude = 164 Btu/hr-sqft (Tbl.6) and the
Storage load factor with internal shade = 0.66 for a west exposure at 4 pm ,the weight ~ 100 lb/sq ft. So, the
Solar heat gain thru glass for a west = 164x0.66 =
108.24 Btu/hr
Case 2 ;Without Storage factor
Solar heat gain thru ordinary glass" (at the selected month , location ,exposure) , ( Table15, Page 44-49 )
G14 Cell:
Comment:
Over all Factor for solar heat gain
Case 1: With storage factor
Factor for adjustment of the value of solar heat gain as the effect of Shading Device or Glass block . And the correction factor(Table 16,Page 52, Over all Factors for solar heat
gain thru glass , Table 17, Page 54, Solar heat gain for glass block)
Example : Factor of solar heat gain thru glassfor the Regular plate Glass = 0.94
Case 2 : Without storage factor
Correction factor on the bottom of Table 15, Page 44-49
C15 Cell:
Windows area , sq ft Comment:
Area of glassed structure that solar haet gain get thru the vertical exposure.; Chapter 3
SDM#1-01 , File : 230194937.xls.ms_office Date : 5/23/2014 ,Time :2:07 PM
E15 Cell:
Comment:
Solar heat gain thru glass,Btu/(hr)-(sq ft)
Case 1; With Storage factor
Multiplying of "Peak solar heat gain thru ordinary glass" (at the selected month , location ,exposure) and " Storage load factors of solar heat gain".
( Table 6, Page 29 for Peak solar heat gain thru ordinary glass and Table 7,8,9,10 or 11 ,Page 30-34 for Storage load factors of solar heat gain thruglass) :
Example : The peak solar heat gain for a west exposure
in July at 40 north Latitude = 164 Btu/hr-sqft (Tbl.6) and the
Storage load factor with internal shade = 0.66 for a west exposure at 4 pm ,the weight ~ 100 lb/sq ft. So, the
Solar heat gain thru glass for a west = 164x0.66 =
108.24 Btu/hr
Case 2 ;Without Storage factor
Solar heat gain thru ordinary glass" (at the selected month , location ,exposure) , ( Table15, Page 44-49 )
G15 Cell:
Comment:
Over all Factor for solar heat gain
Case 1: With storage factor
Factor for adjustment of the value of solar heat gain as the effect of Shading Device or Glass block . And the correction factor(Table 16,Page 52, Over all Factors for solar heat
gain thru glass , Table 17, Page 54, Solar heat gain for glass block)
Example : Factor of solar heat gain thru glassfor the Regular plate Glass = 0.94
Case 2 : Without storage factor
Correction factor on the bottom of Table 15, Page 44-49
K16 Cell:
People, Person Comment:
Amount of people in the A/C area.
M16 Cell:
Ventilation rate, CFM/Person Comment:
Ventilation rate base on the quantity of person in
conditioning space. (Table45, Page97)
C17 Cell:
Wall area , sq ft Comment:
Area of wall or roof that conducted heat gain get thru at each exposure. ( ,E,S,W,NE,
SE,SW,NW)
E17 Cell:
Equivalent temperature diff. ,Deg F Comment:
Operation of Equivalent temperature difference value (wall , roof ,Table 19, ,Page 62 ) and
SDM#1-01 , File : 230194937.xls.ms_office Date : 5/23/2014 ,Time :2:07 PM
Correction number (Table20A , Page 63,64)
G17 Cell:
Transmission Coefficient, U, (Btu/(hr)(sq ft)(deg F) Comment:
Value of Transmission Coefficient , U Value of each type of wall material (Table 21,22,23,24,25,26 ,Page 66-70 )
M17 Cell:
Ventilation rate, CFM/Sq.ft Comment:
Ventilation rate base on the size ot the
conditioning space. (Table45, Page97)
C18 Cell:
Wall area , sq ft Comment:
Area of wall or roof that conducted heat gain get thru at each exposure. ( ,E,S,W,NE,
SE,SW,NW)
E18 Cell:
Equivalent temperature diff. ,Deg F Comment:
Operation of Equivalent temperature difference value (wall , roof ,Table 19, ,Page 62 ) and
Correction number (Table20A , Page 63,64)
G18 Cell:
Transmission Coefficient, U, (Btu/(hr)(sq ft)(deg F) Comment:
Value of Transmission Coefficient , U Value of each type of wall material (Table 21,22,23,24,25,26 ,Page 66-70 )
C19 Cell:
Wall area , sq ft Comment:
Area of wall or roof that conducted heat gain get thru at each exposure. ( ,E,S,W,NE,
SE,SW,NW)
E19 Cell:
Equivalent temperature diff. ,Deg F Comment:
Operation of Equivalent temperature difference value (wall , roof ,Table 19, ,Page 62 ) and
Correction number (Table20A , Page 63,64)
G19 Cell:
Transmission Coefficient, U, (Btu/(hr)(sq ft)(deg F) Comment:
Value of Transmission Coefficient , U Value of each type of wall material (Table 21,22,23,24,25,26 ,Page 66-70 )
C20 Cell:
Wall area , sq ft Comment:
Area of wall or roof that conducted heat gain get thru at each exposure. ( ,E,S,W,NE,
SE,SW,NW)
SDM#1-01 , File : 230194937.xls.ms_office Date : 5/23/2014 ,Time :2:07 PM
E20 Cell:
Equivalent temperature diff. ,Deg F Comment:
Operation of Equivalent temperature difference value (wall , roof ,Table 19, ,Page 62 ) and
Correction number (Table20A , Page 63,64)
G20 Cell:
Transmission Coefficient, U, (Btu/(hr)(sq ft)(deg F) Comment:
Value of Transmission Coefficient , U Value of each type of wall material (Table 21,22,23,24,25,26 ,Page 66-70 )
L20 Cell:
People, Person Comment:
Amount of people in the A/C area.
M20 Cell:
Infiltration rate Comment:
Infiltration rate base on number of people , See Table41, Page 90
C21 Cell:
Wall area , sq ft Comment:
Area of wall or roof that conducted heat gain get thru at each exposure. ( ,E,S,W,NE,
SE,SW,NW)
E21 Cell:
Equivalent temperature diff. ,Deg F Comment:
Operation of Equivalent temperature difference value (wall , roof ,Table 20, ,Page 63 ) and
Correction number (Table20A , Page 63,64)
G21 Cell:
Transmission Coefficient, U, (Btu/(hr)(sq ft)(deg F) Comment:
Value of Transmission Coefficient , U Value of each type of Roof material (Table 27,28,Page 71,72 )
L21 Cell:
Door, Comment:
The numbe of open door of the A/C area.
M21 Cell:
Infiltration rate Comment:
Infiltration rate base on number of opening doors , See Table41, Page 90
C22 Cell:
Wall area , sq ft Comment:
SDM#1-01 , File : 230194937.xls.ms_office Date : 5/23/2014 ,Time :2:07 PM
Area of wall or roof that conducted heat gain get thru at each exposure. ( ,E,S,W,NE,
SE,SW,NW)
E22 Cell:
Equivalent temperature diff. ,Deg F Comment:
Operation of Equivalent temperature difference value (wall , roof ,Table 20, ,Page 63 ) and
Correction number (Table20A , Page 63,64)
G22 Cell:
Transmission Coefficient, U, (Btu/(hr)(sq ft)(deg F) Comment:
Value of Transmission Coefficient , U Value of each type of Roof material (Table 27,28,Page 71,72 )
O22 Cell:
Exhaust capacity ,CFM Comment:
Exhaust capacity of the system
C24 Cell:
Glassed area , sq ft Comment:
Heat transmission area thu glass except wall & roof.
E24 Cell:
Dry bulb temp. diff , F Comment:
Dry bulb temperature difference between outdoor temperature and air conditioning room temperature. (See the data at the top of calculation sheet)
G24 Cell:
U Value of glass ,Btu/hr-sq.ft-F Comment:
Transmission Coefficient value of Windows,
skylights, doors& Glass block (Table 33, Page 76)
C25 Cell:
Partition area , sq ft Comment:
Heat transmission area thu partition except wall & roof.
E25 Cell:
Dry bulb temp. diff , F Comment:
Dry bulb temperature difference betaween another side of partition and air conditioning room temperature.
G25 Cell:
U Value of Partition ,Btu/hr-sq.ft-F Comment:
Transmission Coefficient value of Partitions(Table 25,26, Page 69,70)
C26 Cell:
Ceiling area , sq ft Comment:
Heat transmission area thu ceilingexcept wall & roof.
SDM#1-01 , File : 230194937.xls.ms_office Date : 5/23/2014 ,Time :2:07 PM
E26 Cell:
Dry bulb temp. diff , F Comment:
Dry bulb temperature difference betaween above ceiling and air conditioning room temperature.
G26 Cell:
U Value of Partition ,Btu/hr-sq.ft-F Comment:
Transmission Coefficient value of Ceiling or floor(Table 29,30 Page 73,74)
C27 Cell:
Floor area , sq ft Comment:
Heat transmission area thu floorexcept wall & roof.
E27 Cell:
Dry bulb temp. diff , F Comment:
Dry bulb temperature difference betaween under floor temperature and air conditioning room temperature.
G27 Cell:
U Value of Partition ,Btu/hr-sq.ft-F Comment:
Transmission Coefficient value of Ceiling or floor(Table 29,30 Page 73,74)
C28 Cell:
Infiltration , cfm Comment:
Ignore this value in case of ventilation excess Infiltration of air thu window,door,crack or swinging door, (See note 4)
E28 Cell:
Dry bulb temp. diff , F Comment:
Dry bulb temperature difference between outdoor temperature and air conditioning room temperature. (See the data at the top of calculation sheet)
L30 Cell:
Apparatus dewpoint Comment:
Define from Table 65,Page or Psychrometric chart Fig 33 ,Page116
C31 Cell:
People, Person Comment:
Amount of people in the A/C area.
G31 Cell:
Heat gain from people, Btu/hr Comment:
Sensible heat release from body when they are
doing the activity (Table 48 ,Page 100)
C32 Cell:
Power, kw Comment:
Grossory of power of operating motor in the A/C area. It can generate heat to be the cooling load.
SDM#1-01 , File : 230194937.xls.ms_office Date : 5/23/2014 ,Time :2:07 PM
G32 Cell:
Heat gain from electric motor, Btu/hr Comment:
Sensible heat release from motor into the A/C
area (Table 53 ,Page 105)
C33 Cell:
Power, kw Comment:
Grossory of power of lighting in the A/C area. It can generate heat to be the cooling load.
G33 Cell:
Heat gain from light, Btu/hr Comment:
Sensible heat release from lights into the A/C
area (Table 49 ,Page 101)
D34 Cell:
Heat gain from appliance, Btu/hr Comment:
Grossory of power of appliance in the A/C area. It can generate sensible heat to be the cooling load.(Table 50,51,52 Page101,103)
G34 Cell:
Correction Factor of Appliance Comment:
Factoc of Appliance for the adjustment of each situation of cooling load.(Bottom of Table 50,51,52)
D35 Cell:
Additional heat gain, Btu/hr Comment:
Heat gain from pipe or tank located in A/C area.(Table 54-57 Page107-109)
G35 Cell:
Correction Factor of Additional heat gain Comment:
Factoc of additional heat gain for the adjustment of each situation of cooling load.(Bottom of Table 54-57)
C37 Cell:
Floor area of A/C space, sq.ft Comment:
Floor area of air conditioning space where is influenced by the temperature swing effect. The temperature swing effect will reduce the sensible heat gain. Because of some
heat gain is stored in the building .It doesn't release all of it at the peak
rate.
E37 Cell:
Desired temperature swing, F Comment:
Recommended inside design condition. The temperature swing value depend on each type of building function. (Table 4 ,Page 20)
SDM#1-01 , File : 230194937.xls.ms_office Date : 5/23/2014 ,Time :2:07 PM
G37 Cell:
Storage Factor Comment:
Factor of storage heat gain depend on the load pattern, weight of material surrounding the space and hour of operation.(Table 13,Page 37)
C40 Cell:
Safety Factor Comment:
Factor for the uncertainly of survey. The value in the range of 0%-5%.To be added to the room sensible heat. ( Chapter 7,Page112)
C43 Cell:
Heat gain to supply duct.% Comment:
Heat gain to supply duct in case of the cooled air duct go through the unconditioned space. Depend on amount of room sensible heat , type of duct insulation , distance and
temperature difference between cooled air in duct and the unconditioned space temperature.(Chart 3,Page 110)
E43 Cell:
Supply air duct leak loss,% Comment:
Average supply duct leakage from the entire length of low velocity supply duct whether large and small system is around 10% of supply air quantity. Individual workmanship is
the greatest variable and duct leakages from 5%-30%.(Chapter 7,Page 110)
G43 Cell:
Heat gain from A/C Fan,Draw thru system,% Comment:
The generated heat gain from fan motor which distribute cooled air in the A/C system. It will effect to have more sensible heat gain. And depend on the temperature difference
of room to supply air ,Fan total pressure and feature of fan installation.(Table 59,Page 111)
C44 Cell:
Outdoor air,CFM Comment:
Quantity of outdoor air make up to the A/C system. See note 3 on the bottom of this calculation sheet (Table45,Page97 and Table 43, Page92)
E44 Cell:
Dry bulb temp. diff , F Comment:
Dry bulb temperature difference betaween outdoor temperature and air conditioning room temperature. (See the data at the top of calculation sheet)
G44 Cell:
Bypass Factor Comment:
Bypass factor is a function of the physical and operating charecteristics of the conditioning apparatus (Cooling Coil) See typical Bypass Factors (Table 61,Page127)
C47 Cell:
Infiltration , cfm Comment:
SDM#1-01 , File : 230194937.xls.ms_office Date : 5/23/2014 ,Time :2:07 PM
Ignore this value in case of ventilation excess Infiltration of air thu window,door,crack or swinging door, (See note 4)
E47 Cell:
Moisture content, Gr/Lb Comment:
Moisture content difference between outdoor and room condition., (See note 2)
C48 Cell:
People, Person Comment:
Amount of people in the A/C area.
E48 Cell:
Heat gain from people, Btu/hr Comment:
Latent heat release from body when they are
doing the activity (Table 48 ,Page 100)
C49 Cell:
Steam , Lb/Hr Comment:
Amount of steam escape to conditioned space
D50 Cell:
Heat gain from appliance, Btu/hr Comment:
Grossory of power of appliance in the A/C area. It can generate latent heat to be the cooling load.(Table 50,51,52 Page101,103)
G50 Cell:
Correction Factor of Appliance Comment:
Factoc of Appliance for the adjustment of each situation of cooling load.(Bottom of Table 50,51,52)
D51 Cell:
Additional heat gain, Btu/hr-sq.ft Comment:
Heat gain from evaporation of free water surface in A/C space.(Table 58 Page109)
C52 Cell:
Moisture material area ,sq.ft Comment:
Face area of moisture material which can evaporate into A/C space.
E52 Cell:
Moisture content, Gr/Lb Comment:
Moisture content difference between outdoor and room condition., (See note 2)
G52 Cell:
SDM#1-01 , File : 230194937.xls.ms_office Date : 5/23/2014 ,Time :2:07 PM
Permeance, Btu/(hr)(100sq.ft)(Gr/Lb diff) Comment:
Diffusion of moisture material into the A/C space.(Table 40 Page84-85)
C54 Cell:
Safety Factor Comment:
Factor for the uncertainly of survey. The value in the range of 0%-5%.To be added to the room latent heat. ( Chapter 7,Page112)
E56 Cell:
Supply air duct leak loss,% Comment:
Average supply duct leakage from the entire length of low velocity supply duct whether large and small system is around 10% of supply air quantity. Individual workmanship is
the greatest variable and duct leakages from 5%-30%.(Chapter 7,Page 110)
C57 Cell:
Outdoor air ,CFM Comment:
Amount of outdoor air make up to the A/C system
can be the latent heat gain by the mixed moisture.
See note 3
E57 Cell:
Moisture content, Gr/Lb Comment:
Moisture content difference between outdoor and room condition., (See note 2)
G57 Cell:
Bypass Factor Comment:
Bypass factor is a function of the physical and operating charecteristics of the conditioning apparatus (Cooling Coil) See typical Bypass Factors (Table 61,Page127)
C61 Cell:
Outdoor air ,CFM Comment:
Amount of outdoor air make up to the A/C system
can be the sensible heat gain by the temperature difference. See note 3
E61 Cell:
Dry bulb temp. diff , F Comment:
Dry bulb temperature difference between outdoor temperature and air conditioning room temperature. (See the data at the top of calculation sheet)
G61 Cell:
Bypass Factor Comment:
Bypass factor is a function of the physical and operating charecteristics of the conditioning apparatus (Cooling Coil) See typical Bypass Factors (Table 61,Page127)
C62 Cell:
SDM#1-01 , File : 230194937.xls.ms_office Date : 5/23/2014 ,Time :2:07 PM
Outdoor air ,CFM Comment:
Amount of outdoor air make up to the A/C system
can be the latent heat gain by the mixed moisture.
See note 3
E62 Cell:
Moisture content, Gr/Lb Comment:
Moisture content difference between outdoor and room condition., (See note 2)
G62 Cell:
Bypass Factor Comment:
Bypass factor is a function of the physical and operating charecteristics of the conditioning apparatus (Cooling Coil) See typical Bypass Factors (Table 61,Page127)
C63 Cell:
Heat gain to return duct.% Comment:
Heat gain to return duct in case of the cooled air duct go through the unconditioned space. Depend on amount of room sensible heat , type of duct insulation , distance and
temperature difference between cooled air in duct and the unconditioned space temperature.(Chart 3,Page 110)
G63 Cell:
Return air duct leak gain,% Comment:
Average supply duct leakage from the entire length of low velocity supply duct whether large and small system is around 10% of supply air quantity. Individual workmanship is
the greatest variable and duct leakages from 5%-30%.(Chapter 7,Page 110)
C65 Cell:
Heat gain from dehumidifier pump,% Comment:
With dehumidifier systems, the horsepower required to pump the water adds heat to the system.This heat will be an addition to the grand total heat.(Table60 ,Page 113)
G65 Cell:
Heat gain from dehumidifier pipe,% Comment:
- Very little external piping ~1%
- Average external piping ~2%
- extensive external piping ~4%
Chapter 7,Page 113
SDM#1-01 , File : 230194937.xls.ms_office Date : 5/23/2014 ,Time :2:07 PM