Site Name March Crematorium

Contract Number C4???


Tag No DB
Use Distribution board Incomer
Supply fault rms current level (KVA) 349 (taken from FGT short circuit calculations)
% Reactance 1
Protective device MGI125N
Range 125 125
Short circuit rating 25 kA
Short circuit release 10 * Range max
Max energy let through 75 KA
2
s
Max short circuit setting 1250 Amps
Operating voltage 400 V
Tripping time 25 milliseconds
Phases 3
Panel symmetrical fault level 349 KVA
Conductor
Copper Y
Insulation
Tri Rated Y
Mineral N
Table 43A "k" value 143
Temperature coefficient 143.00
Conductor
csa mm2 Maximum current available Current Voltage drop
35 151117 Passed Passed
Heating time (t) seconds = (k2*s2)/I2
16.0320 Seconds
16032.02 milliseconds
Conductor energy let through capability
25050025 A
2
s
25050.03 KA
2
s
Conductor short circuit energy capability Passed
Device tripping speed Passed
Note device OK
Short circuit protection calculations
Cable test
Page 1 of17 230419818.xls.ms_office
(taken from FGT short circuit calculations)
Page 2 of17 230419818.xls.ms_office
Site Name March Crematorium
Contract Number C4???
Tag No EES166201
Use No1 Coanda Fan
Supply fault rms current level (KVA) 349
% Reactance 1
Protective device MG18463 C60HC316
Range 16 16
Short circuit rating 20 kA
Short circuit release 10 * Range max
Max energy let through 60 KA
2
s
Max short circuit setting 160 Amps
Operating voltage 400 V
Tripping time 25 milliseconds
Phases 3
Panel symmetrical fault level 111 KVA
Conductor
Copper Y
Insulation
Tri Rated Y
Mineral N
Table 43A "k" value 143
Temperature coefficient 143.00
Conductor
csa mm2 Maximum current available Current Voltage drop
2.5 47997 Passed Passed
Heating time (t) seconds = (k2*s2)/I2
4.9924 Seconds
4992.43 milliseconds
Conductor energy let through capability
127806.25 A
2
s
127.81 KA
2
s
Conductor short circuit energy capability Passed
Device tripping speed Passed
Note device OK
Short circuit protection calculations
Cable test
Page 3 of17 230419818.xls.ms_office
Site Name March Crematorium
Contract Number C4???
Tag No EES266201
Use No2 Coanda Fan
Supply fault rms current level (KVA) 349
% Reactance 1
Protective device MG18463 C60HC316
Range 16 16
Short circuit rating 20 kA
Short circuit release 10 * Range max
Max energy let through 60 KA
2
s
Max short circuit setting 160 Amps
Operating voltage 400 V
Tripping time 25 milliseconds
Phases 3
Panel symmetrical fault level 111 KVA
Conductor
Copper Y
Insulation
Tri Rated Y
Mineral N
Table 43A "k" value 143
Temperature coefficient 143.00
Conductor
csa mm2 Maximum current available Current Voltage drop
2.5 47997 Passed Passed
Heating time (t) seconds = (k2*s2)/I2
4.9924 Seconds
4992.43 milliseconds
Conductor energy let through capability
127806.25 A
2
s
127.81 KA
2
s
Conductor short circuit energy capability Passed
Device tripping speed Passed
Note device OK
Short circuit protection calculations
Cable test
Page 4 of17 230419818.xls.ms_office
Site Name March Crematorium
Contract Number C4???
Tag No EES126101
Use No1 Combustion Fan
Supply fault rms current level (KVA) 349
% Reactance 1
Protective device MG18463 C60HC316
Range 16 16
Short circuit rating 20 kA
Short circuit release 10 * Range max
Max energy let through 60 KA
2
s
Max short circuit setting 160 Amps
Operating voltage 400 V
Tripping time 25 milliseconds
Phases 3
Panel symmetrical fault level 111 KVA
Conductor
Copper Y
Insulation
Tri Rated Y
Mineral N
Table 43A "k" value 143
Temperature coefficient 143.00
Conductor
csa mm2 Maximum current available Current Voltage drop
2.5 47997 Passed Passed
Heating time (t) seconds = (k2*s2)/I2
4.9924 Seconds
4992.43 milliseconds
Conductor energy let through capability
127806.25 A
2
s
127.81 KA
2
s
Conductor short circuit energy capability Passed
Device tripping speed Passed
Note device OK
Short circuit protection calculations
Cable test
Page 5 of17 230419818.xls.ms_office
Site Name March Crematorium
Contract Number C4???
Tag No EES226101
Use No2 Combustion Fan
Supply fault rms current level (KVA) 349
% Reactance 1
Protective device MG18463 C60HC316
Range 16 16
Short circuit rating 20 kA
Short circuit release 10 * Range max
Max energy let through 60 KA
2
s
Max short circuit setting 160 Amps
Operating voltage 400 V
Tripping time 25 milliseconds
Phases 3
Panel symmetrical fault level 111 KVA
Conductor
Copper Y
Insulation
Tri Rated Y
Mineral N
Table 43A "k" value 143
Temperature coefficient 143.00
Conductor
csa mm2 Maximum current available Current Voltage drop
2.5 47997 Passed Passed
Heating time (t) seconds = (k2*s2)/I2
4.9924 Seconds
4992.43 milliseconds
Conductor energy let through capability
127806.25 A
2
s
127.81 KA
2
s
Conductor short circuit energy capability Passed
Device tripping speed Passed
Note device OK
Short circuit protection calculations
Cable test
Page 6 of17 230419818.xls.ms_office
Site Name March Crematorium
Contract Number C4???
Tag No EES132002
Use No1 Analytical supply
Supply fault rms current level (KVA) 349
% Reactance 1
Protective device MG19270 C60HC116
Range 16 16
Short circuit rating 20 kA
Short circuit release 10 * Range max
Max energy let through 20 KA
2
s
Max short circuit setting 160 Amps
Operating voltage 230 V
Tripping time 25 milliseconds
Phases 1
Panel symmetrical fault level 37 KVA
Conductor
Copper Y
Insulation
Tri Rated Y
Mineral N
Table 43A "k" value 143
Temperature coefficient 143.00
Conductor
csa mm2 Maximum current available Current Voltage drop
1.5 27712 Passed Passed
Heating time (t) seconds = (k2*s2)/I2
1.7973 Seconds
1797.28 milliseconds
Conductor energy let through capability
46010.25 A
2
s
46.01 KA
2
s
Conductor short circuit energy capability Passed
Device tripping speed Passed
Note device OK
Short circuit protection calculations
Cable test
Page 7 of17 230419818.xls.ms_office
Site Name March Crematorium
Contract Number C4???
Tag No EES11001
Use No1 Cremator panel supply
Supply fault rms current level (KVA) 349
% Reactance 1
Protective device MG19270 C60HC116
Range 16 16
Short circuit rating 20 kA
Short circuit release 10 * Range max
Max energy let through 20 KA
2
s
Max short circuit setting 160 Amps
Operating voltage 230 V
Tripping time 25 milliseconds
Phases 1
Panel symmetrical fault level 37 KVA
Conductor
Copper Y
Insulation
Tri Rated Y
Mineral N
Table 43A "k" value 143
Temperature coefficient 143.00
Conductor
csa mm2 Maximum current available Current Voltage drop
1.5 27712 Passed Passed
Heating time (t) seconds = (k2*s2)/I2
1.7973 Seconds
1797.28 milliseconds
Conductor energy let through capability
46010.25 A
2
s
46.01 KA
2
s
Conductor short circuit energy capability Passed
Device tripping speed Passed
Note device OK
Short circuit protection calculations
Cable test
Page 8 of17 230419818.xls.ms_office
Site Name March Crematorium
Contract Number C4???
Tag No EES21001
Use No2 Cremator panel supply
Supply fault rms current level (KVA) 349
% Reactance 1
Protective device MG19270 C60HC116
Range 16 16
Short circuit rating 20 kA
Short circuit release 10 * Range max
Max energy let through 20 KA
2
s
Max short circuit setting 160 Amps
Operating voltage 230 V
Tripping time 25 milliseconds
Phases 1
Panel symmetrical fault level 37 KVA
Conductor
Copper Y
Insulation
Tri Rated Y
Mineral N
Table 43A "k" value 143
Temperature coefficient 143.00
Conductor
csa mm2 Maximum current available Current Voltage drop
1.5 27712 Passed Passed
Heating time (t) seconds = (k2*s2)/I2
1.7973 Seconds
1797.28 milliseconds
Conductor energy let through capability
46010.25 A
2
s
46.01 KA
2
s
Conductor short circuit energy capability Passed
Device tripping speed Passed
Note device OK
Short circuit protection calculations
Cable test
Page 9 of17 230419818.xls.ms_office
Site Name March Crematorium
Contract Number C4???
Tag No EES101
Use No1 Control panel isolator
Supply fault rms current level (KVA) 37
% Reactance 1
Protective device PKZM0-16
Range 16 16
Short circuit rating 25 kA
Short circuit release 10 * Range max
Max energy let through 25 KA
2
s
Max short circuit setting 160 Amps
Operating voltage 230 V
Tripping time 25 milliseconds
Phases 1
Panel symmetrical fault level 37 KVA
Conductor
Copper Y
Insulation
Tri Rated Y
Mineral N
Table 43A "k" value 143
Temperature coefficient 143.00
Conductor
csa mm2 Maximum current available Current Voltage drop
1.5 27712 Passed Passed
Heating time (t) seconds = (k2*s2)/I2
1.7973 Seconds
1797.28 milliseconds
Conductor energy let through capability
46010.25 A
2
s
46.01 KA
2
s
Conductor short circuit energy capability Passed
Device tripping speed Passed
Note device OK
Short circuit protection calculations
Cable test
Page 10 of17 230419818.xls.ms_office
Site Name March Crematorium
Contract Number C4???
Tag No MCB 1
Use PLC and Instrument supplies
Supply fault rms current level (KVA) 37
% Reactance 1
Protective device MG19264
Range 6 6
Short circuit rating 10 kA
Short circuit release 8 * Range max
Max energy let through 10 KA2s
Max short circuit setting 48 Amps
Operating voltage 230 V
Tripping time 25 milliseconds
Phases 1
Terminal symmetrical fault level 11 KVA
Conductor
Copper Y
Insulation
Tri Rated Y
Mineral N
Table 43A "k" value 143
Temperature coefficient 143.00
Conductor
csa mm2 Maximum current available Current Voltage drop
1.5 8314 Passed Passed
Heating time (t) seconds = (k2*s2)/I2
19.9697 Seconds
19969.73 milliseconds
Conductor energy let through capability
46010.25 A
2
s
46.01 KA
2
s
Conductor short circuit energy capability Passed
Device tripping speed Passed
Note device OK
Short circuit protection calculations
Cable test
Page 11 of17 230419818.xls.ms_office
Site Name March Crematorium
Contract Number C4???
Tag No MCB 2
Use Underpressure and sockets
Supply fault rms current level (KVA) 37
% Reactance 1
Protective device MG19264
Range 6 6
Short circuit rating 10 kA
Short circuit release 8 * Range max
Max energy let through 10 KA2s
Max short circuit setting 48 Amps
Operating voltage 230 V
Tripping time 25 milliseconds
Phases 1
Terminal symmetrical fault level 11 KVA
Conductor
Copper Y
Insulation
Tri Rated Y
Mineral N
Table 43A "k" value 143
Temperature coefficient 143.00
Conductor
csa mm2 Maximum current available Current Voltage drop
1.5 8314 Passed Passed
Heating time (t) seconds = (k2*s2)/I2
19.9697 Seconds
19969.73 milliseconds
Conductor energy let through capability
46010.25 A
2
s
46.01 KA
2
s
Conductor short circuit energy capability Passed
Device tripping speed Passed
Note device OK
Short circuit protection calculations
Cable test
Page 12 of17 230419818.xls.ms_office
Site Name March Crematorium
Contract Number C4???
Tag No MCB 3
Use Burner supplies
Supply fault rms current level (KVA) 37
% Reactance 1
Protective device MG19264
Range 6 6
Short circuit rating 10 kA
Short circuit release 8 * Range max
Max energy let through 10 KA2s
Max short circuit setting 48 Amps
Operating voltage 230 V
Tripping time 25 milliseconds
Phases 1
Terminal symmetrical fault level 11 KVA
Conductor
Copper Y
Insulation
Tri Rated Y
Mineral N
Table 43A "k" value 143
Temperature coefficient 143.00
Conductor
csa mm2 Maximum current available Current Voltage drop
1.5 8314 Passed Passed
Heating time (t) seconds = (k2*s2)/I2
19.9697 Seconds
19969.73 milliseconds
Conductor energy let through capability
46010.25 A
2
s
46.01 KA
2
s
Conductor short circuit energy capability Passed
Device tripping speed Passed
Note device OK
Short circuit protection calculations
Cable test
Page 13 of17 230419818.xls.ms_office
Site Name March Crematorium
Contract Number C4???
Tag No MCB 4
Use 230/24V Transformer supply
Supply fault rms current level (KVA) 37
% Reactance 1
Protective device MG19264
Range 6 6
Short circuit rating 10 kA
Short circuit release 8 * Range max
Max energy let through 10 KA2s
Max short circuit setting 48 Amps
Operating voltage 230 V
Tripping time 25 milliseconds
Phases 1
Terminal symmetrical fault level 11 KVA
Conductor
Copper Y
Insulation
Tri Rated Y
Mineral N
Table 43A "k" value 143
Temperature coefficient 143.00
Conductor
csa mm2 Maximum current available Current Voltage drop
1.5 8314 Passed Passed
Heating time (t) seconds = (k2*s2)/I2
19.9697 Seconds
19969.73 milliseconds
Conductor energy let through capability
46010.25 A
2
s
46.01 KA
2
s
Conductor short circuit energy capability Passed
Device tripping speed Passed
Note device OK
Short circuit protection calculations
Cable test
Page 14 of17 230419818.xls.ms_office
Site Name March Crematorium
Contract Number C4???
Tag No MCB 5
Use Analytical supply
Supply fault rms current level (KVA) 37
% Reactance 1
Protective device MG19266
Range 10 10
Short circuit rating 10 kA
Short circuit release 8 * Range max
Max energy let through 10 KA2s
Max short circuit setting 80 Amps
Operating voltage 230 V
Tripping time 25 milliseconds
Phases 1
Terminal symmetrical fault level 18 KVA
Conductor
Copper Y
Insulation
Tri Rated Y
Mineral N
Table 43A "k" value 143
Temperature coefficient 143.00
Conductor
csa mm2 Maximum current available Current Voltage drop
1.5 13856 Passed Passed
Heating time (t) seconds = (k2*s2)/I2
7.1891 Seconds
7189.10 milliseconds
Conductor energy let through capability
46010.25 A
2
s
46.01 KA
2
s
Conductor short circuit energy capability Passed
Device tripping speed Passed
Note device OK
Short circuit protection calculations
Cable test
Page 15 of17 230419818.xls.ms_office
Site Name March Crematorium
Contract Number C4???
Tag No EES14101
Use Insertion door supply
Supply fault rms current level (KVA) 37
% Reactance 1
Protective device MG19266
Range 10 10
Short circuit rating 10 kA
Short circuit release 8 * Range max
Max energy let through 10 KA2s
Max short circuit setting 80 Amps
Operating voltage 230 V
Tripping time 25 milliseconds
Phases 1
Terminal symmetrical fault level 18 KVA
Conductor
Copper Y
Insulation
Tri Rated Y
Mineral N
Table 43A "k" value 143
Temperature coefficient 143.00
Conductor
csa mm2 Maximum current available Current Voltage drop
1.5 13856 Passed Passed
Heating time (t) seconds = (k2*s2)/I2
7.1891 Seconds
7189.10 milliseconds
Conductor energy let through capability
46010.25 A
2
s
46.01 KA
2
s
Conductor short circuit energy capability Passed
Device tripping speed Passed
Note device OK
Short circuit protection calculations
Cable test
Page 16 of17 230419818.xls.ms_office
Site Name March Crematorium
Contract Number C4???
Tag No EES13101
Use Deash door supply
Supply fault rms current level (KVA) 37
% Reactance 1
Protective device MG19266
Range 10 10
Short circuit rating 10 kA
Short circuit release 8 * Range max
Max energy let through 10 KA2s
Max short circuit setting 80 Amps
Operating voltage 230 V
Tripping time 25 milliseconds
Phases 1
Terminal symmetrical fault level 18 KVA
Conductor
Copper Y
Insulation
Tri Rated Y
Mineral N
Table 43A "k" value 143
Temperature coefficient 143.00
Conductor
csa mm2 Maximum current available Current Voltage drop
1.5 13856 Passed Passed
Heating time (t) seconds = (k2*s2)/I2
7.1891 Seconds
7189.10 milliseconds
Conductor energy let through capability
46010.25 A
2
s
46.01 KA
2
s
Conductor short circuit energy capability Passed
Device tripping speed Passed
Note device OK
Short circuit protection calculations
Cable test
Page 17 of17 230419818.xls.ms_office