MiCOM P441, P442 and P444

Distance Protection Relays


Expanding the MiCOM experience
The MiCOM P440 range of relays has been expanded to offer even more
solutions. In addition to the P441 and P442, the P444 provides even more
digital inputs and more relay outputs. All P440 relays now provide optional
DNP3 communication protocol as well as optional IEC60044-8 fibre optic
interface for non-conventional instrument transformer systems.
The MiCOM relays offers fast, secure
clearing for any type of fault. The
unique distance and directionalising
implementations provide an optimum
mix of speed, selectivity and security
for difficult fault types and
application situations.
In addition, the relays offer the
following benefits:
Standardised relay selection for all
applications
Simplified spares holding with dual
rated CT inputs
No need for additional equipment
Simple system integration through
a choice of communication
protocols, including Courier,
Modbus, IEC 60870-5-103 and
DNP3
Synchronisation of all protection
devices
Fast fault diagnosis with integral
fault information, disturbance and
event records
Maximise protection availability
through extensive self-monitoring
and system supervision (CT, VT, trip
circuit)
Enhanced reliability for all faults
through two different measurement
techniques
The software tools (MiCOM S1) allow
intuitive interface to the relay and
greatly lessen training and
documentation requirements for the user.
Powerful and easily implemented
scheme logic with a large choice of
gates and timers makes the relay
completely customisable with an
apropriated certification, to meet the
needs of a wide range of power
system requirements and user
preferences.
Distance Protection
One and/or three phase tripping logic
with four shot, one and/or three-pole
autorecloser and optional check
synchronising
Dual distance protection algorithms
Five independent zones of protection
Zone 1 extension scheme
Independent quadrilateral
characteristics for phase-to-phase and
phase-to-earth faults
Range of pre-programmed channel-
aided schemes and user-definable
channel-aided scheme logic
Weak-infeed and echo mode
Loss of load protection
Current reversal guard protection
Parallel line compensation
Power swing blocking
Settable Switch-on-to-fault and Trip-on-
reclose protection
Other Protection Functions
Directional/non-directional phase
overcurrent
Stub bus protection
Emergency overcurrent on VT failure
Directional/non-directional earth fault
Channel-aided directional earth fault
Directional/non-directional negative
sequence overcurrent
Under/overvoltage
Broken conductor
Circuit breaker failure
Voltage transformer supervision
Current transformer supervision
IEC 60044-8 NCIT optical fibre option
T&D
Protection & Control
Measurement and Recording
Facilities
All records are time tagged to a
resolution of 1ms.
Display of all measured and calculated
quantities.
Post Fault Analysis
Fault location
Distance to fault in miles, kilometres,
ohms or percentage of line.
Mutual compensation feature.
Event records
Up to 250 time-tagged event records in
battery backed memory.
Fault records
Last 5 faults stored in battery backed
memory.
Indication of faulted phase
Protection operation
Active setting group
Fault location
Relay and CB operating time
Currents, voltages and frequency
Disturbance records
At least 20 disturbance records in
battery backed memory:
8 analog channels
32 digital channels
1 time channel
Data is sampled 12 times a cycle
Maximum duration of each record
10.5 seconds
All channels and triggers sources user
configured
Switchgear Supervision
Trip circuit monitoring and
supervision
Monitoring of the trip circuit in both
breaker open and closed states.
Supervision of the trip circuit using the
programmable scheme logic.
Circuit breaker state monitoring
Alarm generated in case of discrepancy
between the open and closed contacts
of the circuit breaker.
Circuit breaker condition
monitoring
The circuit breaker condition monitoring
feature includes:
Monitoring the number of breaker
operations and operation time
Recording the sum of the broken
current quantity
Communications
Rear port providing remote
communications (Courier/K-Bus,
Modbus, IEC 60870-5-103 or DNP3)
Front port providing local
communications
Password Protection
Two levels of password available
Password protection independently
applied to front user interface, front
and rear communications ports
Hardware Description
A back-lit liquid crystal display
12 LEDs
RS232 port & RS485 port
Download/monitor port
Battery (supervised)
N/O & N/C watchdog contacts
Supervised 48V field voltage
1A/5A dual rated CTs or IEC 60044-
8 fibre optic input for non
conventional instrument transformers
Ratings
Inputs
AC voltage110/120V nominal ph-ph
Rated frequency 50/60Hz
Auxiliary voltage (options):
Nominal (V) Operative range (V)
dc dc ac
24 48 19 65
48 110 37 150 24 110
110 250 87 300 80 265
Ouputs
Field voltage supply 48V dc
(current limit 112mA)
21G Earth distance protection, 3 forward
elements, 1 reverse element,
1 selectable element, quadrilateral zones
21P Phase distance protection, 3 forward
elements, 1 reverse element,
1 selectable element, quadrilateral zones
85 Channel-aided protection
50 Phase overcurrent, High set, for Stub
bus application
67/46 Negative sequence overcurrent
50/27 Switch onto fault and trip on reclose
50/51 Phase overcurrent, DT or IDMT
50/51N Earth overcurrent, DT or IDMT
51FF Fuse failure overcurrent
67 Phase directional overcurrent
67N DEF, communication aided
78 Power swing detection
VTS Voltage transformer supervision
CTS Current transformer supervision
50BF Breaker failure and backtrip
46BC Broken conductor detection
25/79 Check synchroniser/Autorecloser
59 Overvoltage
27 Undervoltage
Protection & Control, 60 Route de Sartrouville, 78230 Le Pecq. France. Tel: +33 (0) 134 80 79 00 Fax: +33 (0) 134 80 79 13 www.tde.alstom.com T&D
3Y
3Y
1
Mi COM P441 / P442/ P444
5 0
B F
4 6
BC
46 5 0
50/
51
21P
85
21G 67N
50N/
51N
50/
27
78 67
VTS /
CTS
51
FF
59
27
25/
79
Optional fibre optic
Box Opto inputs Outputs or/and IRIG-B
P441 40TE 8 x UNI (1) 6 n/o, 8 c/o No
P442 60TE 16 x UNI 9 n/o, 12 c/o Yes
P444 80TE 24 x UNI 24 n/o, 8 c/o Yes
(1) Universal voltage range (24-250 Vdc) n/o - normally open c/o - change over