Product Specification

37166C

MFR 3
Multi Function Relay
Mains & Generator
Protection & Control

APPLICATIONS

Woodward's MFR 3 Multi Function Relay incorporates
functions and features for multiple applications with up to
14 generators, each with a maximum of 16 MW. Whether
isolated or in parallel with the utility this device was
designed for generators and switchgear equipment that
require independent protection.

The MFR 3 digitally measures true RMS values ensuring
measurement accuracy maintaining integrity against
harmonics, transients or power surges. Front panel push-
buttons allow direct control of power circuit breakers,
setpoint values, and configuration of the unit.

The MFR 3 is available for one (MFR 31) or two (MFR 32)
circuit breakers. Even if the MFR 31 front panel reflects
only one circuit breaker, it may operate two.

For utility parallel applications the combined mains and
generator breaker protection offer a very compact
solution. In addition to protection the MFR 3 offers
frequency, voltage, real power and re-active power
control allowing load/var sharing.

DESCRIPTION
Features
True RMS 8 voltage (gen/bus/mains)
True RMS 4 current (gen/mains)
Battery voltage monitoring
kWh/kvarh/oper.hours/start/maintenance counter
Configurable trip/control set points
Configurable delays for each alarm
12 configurable discrete alarm inputs
7 configurable/programmable relays
2 conf. analog outputs (20 mA)
2 conf. pulse outputs for kWh/kvarh
Two-line LC display
Synchroscope
Push-buttons for direct control
CAN bus communication
Language manager (English/German preloaded)
Multi level password protection
DESCRIPTION (continued)
Protection ANSI #
Mains
Over-/undervoltage (59/27)
Over-/underfrequency (81O/U)
Phase/vector shift (78)
df/dt (ROCOF) (81RL)
Generator
Over-/undervoltage (2 steps) (59/27)
Over-/underfrequency (2 steps) (81O/U)
Overload (32)
Reverse/reduced power (32R/F)
Unbalanced load (46)
Loss of excitation (40Q)
Definite time-overcurrent (TOC) (50)
Inverse time-overc. (incl. volt. restr.) (51V)
Calculated earth fault (64)
Controller
Synchronizer for 1 or 2 breaker/s (gen/mains)
Isolated operation
Mains parallel operation
Softloading
Speed/frequency/real power
Voltage/power factor cosphi
Mains import/export power
Load/var sharing (up to 14 generators)
Remote real power setpoint (0/4 to 20 mA)
Version PSVX (additionally)
Remote power factor setpoint (0/4 to 20 mA)
5 analog measuring inputs
(1 x 0/4 to 20 mA, 4 x Pt100)
Event recorder with real time clock
Option Q (additionally)
Discrete raise/lower for n/f/V/P/Q
Analog raise/lower for n/f/V/P/Q
PWM raise/lower for n/f/P









Complete controller
with generator and
mains protection,
synchronizer, and
load/var control in one
single digital relay
True RMS sensing
Synchronization for
one/two circuit breakers
Load/var sharing for
up to 14 participants
Counters for kWh,
kvarh, engine starts,
operating hours,
maintenance call
Freely configurable
discrete and analog
alarminputs
Freely configurable
relay and analog
outputs
PC and front panel
configurable
CAN bus based
communication
Microprocessor
technology for accurate,
repeatable and reliable
operation
Programmable two step
threshold set points
with individual time
delays
CE marked
UL/cUL Listed
SPECIFICATIONS (for more see manual 37107)

Accuracy..........................................................................................Class 1
Power supply.......................................................12/24 Vdc (9.5 to 32 Vdc)
Intrinsic consumption..................................................................max. 15 W
Ambient temperature................................................................ -20 to 70 C
Ambient humidity......................................................95 %, non-condensing
Voltage Rated: [1] 57/100(120) Vac........... or [4] 230/400 Vac
VL: [1] max. 150 Vac or [4] max. 300 Vac
Setting range: [1] 50 to 125 Vac or [4] 200 to 440 Vac
Measuring frequency................................................50/60 Hz (40 to 70 Hz)
Linear measuring range up to.......................................................1.3Vrated
Input resistance.....................................................[1] 0.21 M, [4] 0.7 M
Max. power consumption per path................................................ < 0.15 W
Current..................................................................[../1] ../1 A or [../5] ../5 A
Current-carrying capacity......................................................Igen = 3.0Irated
Imains = 1.5Irated
Load.............................................................................................< 0.15 VA
Rated short-time current (1 s)...........................[../1] 50Irated, [../5] 10Irated
Discrete inputs.............................................................................. isolated
Input range....................................................................18 to 250 Vac or dc
Input resistance.....................................................................approx. 68 k
Analog input......................................................................freely scaleable
Type.............................................................................0/4 to 20 mA, Pt100
Resolution...........................................................................................10 Bit
Relay outputs................................................................................ isolated
Contact material ...............................................................................AgCdO
Load (GP)......................................................................2.00 Aac@250 Vac
2.00 Adc@24 Vdc / 0.36 Adc@125 Vdc / 0.18 Adc@250 Vdc
Pilot duty (PD)..................................................................................... B300
1.00 Adc@24 Vdc / 0.22 Adc@125 Vdc / 0.10 Adc@250 Vdc
Analog output................................................................................ isolated
Type............................................................. 0/4 to 20 mA, freely scaleable
Resolution....................................................8/12 Bit (depending on model)
Max. load 0/4 to 20 mA..................................................................... 500
Insulating voltage.........................................................................1,500 Vdc
Housing......................................................Type APRANORM DIN 43 700
Dimensions.....................................................................144144118 mm
Front cutout.......................................................... 138[+1.0]138[+1.0] mm
Connection................................................ screw/plug terminals depending
on connector 1.5 mm or 2.5 mm
Front.................................................................................insulating surface
Protection system.....................................................with proper installation
Front................................................. IP42
(sealed IP54; gasket kit = P/N 8923-1039)
Back................................................. IP21
Weight............................................ depending on version, approx. 1,000 g
Disturbance test(CE)..........tested according to applicable EN guidelines
Listings......................................... UL/cUL listed (voltages up to 300 Vac)


DIMENSIONS
136,0 mm
1
50
99 93
83
48
105 111
X5 X1
130
8,0 mm
111,0 mm
1
3
6
,
0

m
m
54
24
60
25
1
4
4
,
0

m
m
32,0 mm
4
2
,
0

m
m
1
4
4
,
0

m
m
12,0 mm

2002-11-21 | MFR 3 Dimensions r3ww-4702-ab.skf
138
113
0
Configuration plug

APPLICATION
52
52
MFR 3
CAN
RS232
0/4..20mA
I / O
G
81RL
78
90
79
47
81U
81O
59
27
25
25
27
59
81O 50
79
32 81U
32R
32F
40Q
46 39
38
12
49 55
90
74



WIRING DIAGRAM (example: MFR32; for others see manual)
P
S
V
X
P
S
V
X
G
4
0 Vdc
2004-11-17 | MFR3 Wiring Diagramr3ww-4704-ap.skf
9
6
7
8
A
B
C
5
0
5
1
5
2
2
7
2
8
4
0
1
6
1
7
5
3
5
4
2
3
2
4
4
1
1
4
1
5
3
2
5
2
6
3
9
4
2
2
9
3
0
3
1
3
2
2
0
2
1
2
2
1
1
1
2
1
3
8
9
1
0
1
0
5
1
0
6
1
0
7
1
0
8
1
0
9
1
1
0
1
1
1
1
1
2
1
1
3
X
1
X
2
X
3
X
4
X
5
1
3
0
1
3
1
1
3
2
1
3
3
0
1
2
5
6
7
3
3
3
4
3
5
3
6
6
0
6
1
6
2
6
3
6
4
6
5
6
6
6
7
6
8
6
9
7
0
7
1
7
2
7
3
1
8
1
9
7
4
7
5
7
6
7
7
7
8
7
9
8
0
8
1
8
2
8
3
9
3
9
4
9
5
9
6
9
7
9
8
9
9
1
0
0
1
0
1
1
0
2
1
0
3
1
0
4
GND
s2 (l)
s1 (k)
L1
L2
s2 (l)
s1 (k)
s2 (l)
s1 (k)
s2 (l)
s1 (k)
GND
A
I
A
I
12/24 Vdc
N
raise
lower
R
e
la
is
m
a
n
a
g
e
r
(
f
r
e
i
p
r
o
g
r
a
m
m
ie
r
b
a
r
e

R
e
la
is
)
u
p

t
o

1
4

a
d
d
i
t
i
o
n
a
l

g
e
n
e
r
a
t
o
r
s
(
e
a
c
h

v
i
a

o
n
e

M
F
R

3
)
G
A
T
E
W
A
Y
G
W

4
C
o
n
t
r
o
l

r
o
o
m
S
P
S
P
C
D
r
i
v
e
Mains current L1
or
Option IN20: 0/4 to 20 mAinput
Subject to technical mocifications.
Mains voltage L1
Mains voltage L3
Mains voltage L2
Busbar voltage
Enable GCB
raise
lower
Ready for operation
Switch setpoint 1 <--> 2
Enable monitoring
Common (terminal 3/4/5/6/53/54)
Common
Configuration blocked
Isolated operation controller ON
External acknowledgement
Common
Blocking of mains protection
Alarm input [D04]
Alarm input [D06]
Alarm input [D07]
Alarm input [D08]
Alarm input [D09]
Alarm input [D10]
Alarm input [D11]
Alarm input [D12]
Relay [R1]
Relay [R2]
Relay [R3]
Relay [R4]
Relay [R5]
Analog input 1 [T1]
0/4 to 20 mA
- Setpoint: Real power kW
Analog input 2 [T2]
0/4 to 20 mA
- Setpoint: power factor
Analog input 3 [T3]
0/4 to 20 mA
- Alarminput
Analog input 4 [T4]
Pt100
- Alarminput
Command: open GCB
Generator current L1
Generator current L2
Generator current L3
Generator voltage L1
Generator voltage L2
Generator voltage L3
SPEED / POWER
(three-position controller)
alternatively:
Analog controller output
VOLTAGE / POW. FAC.
(three-position controller)
alternatively:
Analog controller output
Analog input 5 [T5]
Pt100
- Alarminput
Analog input 7 [T7]
Pt100
- Alarminput
Analog input 6 [T6]
Pt100
- Alarminput
Analog output
0/4 to 20 mA
Command: close GCB
T
h
e

s
o
c
k
e
t

f
o
r

t
h
e

P
C

c
o
n
f
ig
u
r
a
t
io
n

is

s
it
u
a
t
e
d

o
n

t
h
e
s
id
e

o
f

t
h
e

u
n
it
.
T
h
is

is

w
h
e
r
e

t
h
e

D
P
C

h
a
s

t
o

b
e

p
lu
g
g
e
d

in
.
Reply: MCB is open
Command: close MCB
Enable MCB
Command: open MCB
M
F
R

3
2

(
M
u
l
t
i

F
u
n
c
t
i
o
n

R
e
l
a
y
)
CAN bus interface
Guidance level
P
S
V
GND
CAN-H
CAN-L
Termination
Relay [R6]
3
8
3
7
Relay [R7]
4
8
4
7
Alarm input [D03] or
Switch breaker logic
3
Alarm input [D02] or
Operation mode selector locked
2
Alarm input [D01] or
Mains decoupling via MCB
1
5 Alarm input [D05]
Impulse output kvarh
Open collector
Impulse output kWh
Open collector
1
3
4
1
3
5
1
3
6
1
3
7
P
S
V
c
o
n
fig
u
r
a
b
le
d
u
r
in
g
s
e
tu
p
(
N
O
/N
C
)
#
1
#1
B
a
tte
r
y
o
r
a
n
o
th
e
r
p
o
w
e
r
s
u
p
p
ly
; te
r
m
in
a
l 6
0
is
p
o
s
. o
r
n
e
g
. s
ig
n
a
l
#
2
NO/
NC
Battery
#2
#2
Battery
Battery
#2
#1 NO/
NC
#1 NO/
NC
#1 NO/
NC
#1 NO/
NC
#1 NO/
NC
#1 NO/
NC
#1 NO/
NC
#1 NO/
NC
#1 NO/
NC
#1 NO/
NC
#1 NO/
NC
#1 NO/
NC
#1 NO/
NC
#1 NO/
NC
#1 NO/
NC
#1 NO/
NC
#1 NO/
NC
P
S
V
quasi-continuous controller
with analog outputs
DC
current
DC
voltage
PWM
9 8 10
A U GND
GND A I N/C
PWM GND
12 11 13
A U GND
GND A I N/C
P
S
V

/

Q
P
S
V
[A2]
[A1]
4Reply: GCB is open
3
/
(
4
)3
X1/S1 (K) x1/s1 (k)
X2/S2 (L) x2/s2 (l)
S1/S1 (K)
X2/S2 (L) x2/s2 (l)
X1/S1 (K) x1/s1 (k)
X2/S2 (L) x2/s2 (l)
x1/s1 (k)
L2
L1
L3
3
/
(
4
)
3
X1/S1 (K) x1/s1 (k)
X2/S2 (L) x2/s2 (l)
L1
2
M
C
B
3
/
(
4
)
G
C
B
4
3
4
4
Centralized alarm
Q Package
P
a
c
k
a
g
e
s

P
S
V

/

P
S
V
X

/

P
S
V
+
Q

/

P
S
V
X
+
Q





International
Woodward
PO Box 1519
Fort Collins CO, USA
80522-1519
1000 East Drake Road
Fort Collins CO 80525
Ph: +1 (970) 482-5811
Fax: +1(970) 498-3058

Europe
Woodward Governor Company
Leonhard-Reglerbau GmbH
Handwerkstrasse 29
70565 Stuttgart, Germany
Ph: +49 (711) 789 54-0
Fax: +49 (711) 789 54-100

Distributors &Service
Woodward has an international
network of distributors and
service facilities. For your
nearest representative, call the
Fort Collins plant or see the
Worldwide Directory on our
website.

Corporate Headquarters
Rockford IL, USA
Ph: +1 (815) 877-7441

www.woodward.com
/smart-power






















Subject to technical
modifications.

This document is distributed for
informational purposes only. It is not
to be construed as creating or
becoming part of any Woodward
Governor Company contractual or
warranty obligation unless expressly
stated in a written sales contract.

We appreciate your comments
about the content of our
publications. Please send comments
including the document number
belowto
stgt-doc@woodward.com

Woodward Governor
Company

All Rights Reserved

37166C - 05/2/S
FEATURE OVERVIEW

MFR 31 MFR 32

ANSI
P
S
V

P
S
V
+
Q

P
S
V
X

P
S
V
X
+
Q

P
S
V

P
S
V
+
Q

P
S
V
X

P
S
V
X
+
Q

Control
Breaker control logic 1 1 1 1 2 2 2 2
Synchronization 25
Isolated single-unit operation
Mains parallel operation
Softloading
Accessories
kWh counter
kvarh counter
Operation hrs./start/maintenance counter
Configuration via PC
#1

Event recorder, real time clock 50 50 50 50
Protection
Mains: over-/undervoltage 59/27
Mains: over-/underfrequency 81O/U
Mains: df/dt (ROCOF) 81RL
Mains: d/dt (phase/vector jump) 78
Gen.: Over-/undervoltage 59/27
Gen.: Over-/underfrequency 81O/U
Gen.: Overload 32
Gen.: Reverse power 32R
Gen.: Reduced power 32F/37
Gen.: Unbalanced load 46
Gen.: Loss of excitation 40Q
Gen.: Definite time-overcurrent (TOC) 50
Gen.: Inverse time-overc. (incl. volt. restr.) 51V*
Gen.: Calculated earth fault 64
Controller
Discrete raise/lower: n/f & P
#4

#4

#4

#4

Discrete raise/lower: V & Q
#4

#4

#4

#4

Analog raise/lower: n/f & P
#4

Analog raise/lower: V & Q
#4

PWM raise/lower: n/f & P
#4

Mains import/export power control
Real power setpoint 0/4 to 20 mA
Power factor setpoint 0/4 to 20 mA
Load/var sharing for 14participants
I/O's
Discrete alarm inputs (configurable) 12 12 12 12 12 12 12 12
Relay outputs (configurable) 74 7 7 7 7 7 7 7 7
Analog inputs (configurable) 5
#2
5
#2
5
#2
5
#2

Analog outputs 0/4 to 20 mA (configurab.) 2 2 2 2 2 2 2 2
Impulse output for kWh/kvarh
CAN bus communication
#3

Listings/Approvals
CE Marked
UL/cUL listed
Part numbers P/N
Measuring inputs 120 Vac, ../1 A (8440- -1628 -1730 -1731
Measuring inputs 120 Vac, ../5 A (8440- -1595 -1455 -1597 -1631 -1017 -1635 -1018 -1633
Measuring inputs 400 Vac, ../5 A (8440- -1596 -1365 -1598 -1632 -1328 -1636 -1599 -1634
* according to IEC guidelines
#1 Cable incl. software necessary (DPC)
#2 [T3] = 0/4-20 mA, [T4]-[T7] = Pt100
#3 Remote monitoring, control, configuration (GW 4 could be used for several interfaces)
#4 +/-20 mA and +/-10 Vdc and PWMsignal (type and range configurable); bias/discrete setpoint via relay manager

F
o
r

m
o
r
e

i
n
f
o
r
m
a
t
i
o
n

c
o
n
t
a
c
t
:

Das könnte Ihnen auch gefallen