EXCOUNT-A Accessories

Surge Counter EXCOUNT-A


Highest personnel safety
• Explosion-proof for short-circuit currents
up to 80 kA.
• Same safe performance as arresters.

Negligible residual voltage


• Does not reduce protection margins.
• Reduces risk against accidental contact
during surges.

Long life
• Moulded components, non-sensitive to
humidity or temperature variations.
• Verified by tests per IEC 60068.

Universal application
• All makes and types of surge arresters.
• All weather and temperature conditions.

For gapless surge arresters, surge coun- The principle of operation is shown in
ters are used only to obtain information figure 1 on next page.
regarding surge activities in the corre-
sponding surge arrester and its location. Performance
Surge counter, EXCOUNT-A is designed The design of the secondary circuit ensu-
therefore, to withstand the same severe res that the counting relay is not energised
conditions as the arresters without failure. for low lightning current impulses which
are insignificant to the arrester capability
Design features and life. The stepping criteria are given in
EXCOUNT-A comprises basically of an figure 2 on next side. The current trans-
impulse current transformer with a single- former secondary output is sufficient for
turn primary in the form of an insulated driving the counter and external supply
stranded-copper cable to be connected in source is not needed.
the earth circuit of an arrester. The cable is The single-turn primary ensures that the
provided at both ends with tinned-copper voltage drop across the counter, even at
cable shoes. the highest impulse currents encountered
The secondary circuit consists of a rec- in service, is negligible, leading to added
tifier, capacitor and an electronic switch personnel safety and no increase in the
connected to a mechanical counting relay protection level of the arrester.
and is totally moulded in plastic which Since no gaps or series impedance
makes it ideal for exposed installation. The are used, there is no risk of internal
complete assembly is then housed in an arcing and consequent explosive faillure
elegant vented aluminium casing. A suita- in the event of a short-circuit following
ble-angled window permits easy reading an arrester failure.
of the 6-digit cyclometer-typ counter.

S-1 Edition 5, 2004-10 ABB Surge Arresters — Buyer’s Guide


Accessories EXCOUNT-A

Type tests Routine tests


EXCOUNT-A has been subjected to severe All surge counters are routine-tested
electrical, mechanical and climate tests: with a sufficient number of impulses in a
pass/no pass test prior to despatch from
the factory.
Shock test, 15 g IEC 60068-2-27

Vibration test IEC 60068-2-6 Packing, installation and


maintenance
Temperature test IEC 60068-2-14 Counters are packed in cases together
(-55°C/+70°C) with arresters. For separate supply, they
are packed in cartons.
Humidity test IEC 60068-2-30 Detailed instructions are enclosed with
each counter. However, the following may
Salt fog test DIN 50021 be noted.
(500h, +35°C, The counter must be placed at a suit
95%RH, 5% salt) able height for easy reading. The electri-
Impulse tests IEC 60099-4 cal lead between the earth terminal and
the counter should be insulated and its
Short-circuit test IEC 60099-4 length kept to a minimum. If the length is
(full asymmetry of 2.6) too long, the counter may not register for
very steep impulses when the inductive
voltage between the earth terminal and
At 65 kA, there were no damages at all. the counter exceeds the lightning impulse
At 80 kA, the insulation of the primary withstand level of the insulating base.
conductor was burnt. The counters are maintenance-free.
However, the counter function was not Refer to assembly instructions for
impaired and no pieces were ejected. more details.

Fig. 1 Schematic diagram

Fig. 2 Stepping criteria Fig. 3 Dimensions

ABB Surge Arresters — Buyer’s Guide Edition 5, 2003-10 S-2