A simulated process input should be connected to the transmitter and checked as per attached form #J 001 and results recorded. SAES-J -904 Sec 13 A5 CONTRACTOR personnel performing test and calibrations shall be trained per applicable international or manufacturer requirements.
A simulated process input should be connected to the transmitter and checked as per attached form #J 001 and results recorded. SAES-J -904 Sec 13 A5 CONTRACTOR personnel performing test and calibrations shall be trained per applicable international or manufacturer requirements.
A simulated process input should be connected to the transmitter and checked as per attached form #J 001 and results recorded. SAES-J -904 Sec 13 A5 CONTRACTOR personnel performing test and calibrations shall be trained per applicable international or manufacturer requirements.
FF Differential Transmitter: With all devices in the same segment
connected, a simulated process input should be connected to the transmitter and checked as per attached form #J 001 and results recorded. SAES-J -904 Sec 13 B3 FF Flow Transmitter: With all devices in the same segment connected, a simulated process input should be connected to the transmitter and checked as per attached form #J 001 and results recorded. SAES-J -904 Sec 13 A5 CONTRACTOR personnel performing test and calibrations shall be trained per applicable international or manufacturer requirements. Schedule Q, Att. IV, Sec.6.2. B2 FF Pressure Transmitter: With all devices in the same segment connected, a simulated process input should be connected to the transmitter and checked as per attached form #J 001 and results recorded. SAES-J -904 Sec 13 B. TEST PROCEDURE AND CHECK LIST B1 All fieldbus cables shall be megger tested after glanding but before terminating. Each megger test certificate is to be recorded on the megger test certificate and witnessed by inspection SAES-J -904 Sec 13 A4 CONTRACTOR shall provide backup equipment when the primary equipment is being calibrated or tested. Schedule Q, Att. IV, Sec.6.1. A3 Calibration shall be performed at established periods as specified in the most stringent of SAUDI ARAMCO standards, other applicable standards, or manufacturer recommendations; if no standards apply, the calibration cycle shall not exceed six months. Schedule Q, Att. IV, Sec.6.1. A2 The CONTRACTOR shall identify, maintain, control, adjust, and calibrate all tools, gauges, instruments and other measuring and testing devices used for controlling quality. Schedule Q, Att. IV, Sec.6.1. A1 Specific tools and equipment shall be identified to make and perform tests in the field with instructions for their use, calibration, and storage. Schedule Q, Att. IV, Sec.6.1. A Certification SAUDI ARAMCO TIP NUMBER SAUDI ARAMCO ACTIVITY NUMBER WORK PERMIT REQUIRED? SAUDI ARAMCO INSPECTION LEVEL CONTRACTOR INSPECTION LEVEL TRAVEL TIME SAUDI ARAMCO USE ONLY SCHEDULED TEST DATE & TIME ACTUAL TEST DATE & TIME QUANTITY INSP. MH's SPENT LAYOUT DRAWING NUMBER REV. NO. PURCHASE ORDER NUMBER EC / PMCC / MCC NO. PLANT NO. EQUIPMENT ID NUMBER(S) EQUIPMENT DESCRIPTION EQPT CODE SYSTEM ID. PROJ ECT TITLE WBS / BI / J O NUMBER CONTRACTOR / SUBCONTRACTOR FOUNDATION Fieldbus Instruments and Accessories Field Calibration and Testing SATR-J-6913 1-Oct-05 INST SAUDI ARAMCO ID/PID - 4/14/05 - REV 0 (Standards Cutoff - August 2004) SAUDI ARAMCO TEST REPORT SATR NUMBER DATE APPROVED QR NUMBER FAIL N/A RE-TEST DATE ITEM No. TEST PROCEDURE ACCEPTANCE CRITERIA REFERENCE PASS Page 1 of 6 2. 100/250V Megger Tester 3. Oscilloscope 4. Labeled - Equipment or materials to which has been attached a label, symbol, or other identifying mark of an approved qualified organization 5. Remarks: - The attached forms to be modified and used based on requirements. Work Verified NOTES: or services, that maintains periodic inspection of production of listed equipment or materials or periodic evaluation of services, and whose listing that the equipment, material, or services either meets appropriate designated standards or has been tested and found suitable for a specified with product evaluation, that maintains periodic inspection of production of labeled equipment or materials, and by whose labeling the 2. Identified - Recognizable as suitable for the specific application by a qualified testing laboratory (i.e., listing and/or labeling). Technician Performing Test* Saudi Aramco Work / Rework May Proceed Name, Initials and Date: QC Inspector PID Representative QC Record Reviewed Work Verified T&I Witnessed Name, Title, Department, Company, Initials and Date: Contractor / Third-Party QC Record Reviewed indicates compliance with appropriate standards or performance in a specified manner. Test Performed Successfully and Results are Acceptable: Name, Initials and Date: PMT Representative T&I Witnessed ATTACHMENTS: 1. Attachment 1 Fieldbus Checkout Form REFERENCE DOCUMENTS: 1. Schedule G -- Material, Tools and Equipment (Pro Forma MP-IK-LS Contract), J uly 1993 4. SAES-J -904 FOUNDATION Fieldbus Systems, 31J uly 2004 2. Schedule Q -- Quality Requirements (Pro Forma Contract), November 2003 3. SA Pre-Commissioning Forms #J -015 Instrument and Control 10/97 5. SA Pre-Commissioning Forms #J -007 (9/05)- Thermocouples 6. SA Pre-Commissioning Forms #J -002- Transducers 3. Listed - Equipment and materials included in a list published by an approved qualified organization concerned with evaluation of products RE-TEST DATE D1 Test results are acceptable and in accordance with Saudi Aramco Engineering Standards and contractual requirements. 1. Approved - Acceptable to the authority having jurisdiction (i.e., Saudi Aramco ID). Work Verified Name, Sign and Date: Quality Record Approved: Name, Organization, Initials and Date: T&I Witnessed QC Supervisor Proponent and Others Name, Initials and Date: Witnessed Test Y =YES N =NO F =FAILED *Person Responsible for Implementation of Test and Analysis of Results ITEM No. TEST RESULTS ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A QC Record Reviewed SAUDI ARAMCO ID/PID - 4/14/05 - REV 0 (Standards Cutoff - August 2004) SAUDI ARAMCO TEST REPORT SATR NUMBER DATE APPROVED QR NUMBER PROJ ECT TITLE WBS / BI / J O NUMBER CONTRACTOR / SUBCONTRACTOR FOUNDATION Fieldbus Instruments and Accessories Field Calibration and Testing SATR-J-6913 1-Oct-05 INST C. TEST EQUIPMENT ITEM No. TEST RESULTS ACCEPTANCE CRITERIA REFERENCE PASS B5 RE-TEST DATE FAIL N/A B6 FF Valve Positioners: With all devices in the same segment connected, a simulated process input should be connected to the transmitter via thermocouple cable and checked as per attached Form #J 002 and results recorded. (Atttachment 3) SAES-J -904 Sec 13 FF Temperature Transmitter: With all devices in the same segment connected, a simulated process output should be connected to the transducer and the output checked as per Form #J 007 and results recorded. (Atttachment 2) SAES-J -904 Sec 13 2. Attachment 2- Thermocouple -Temperature Pre com Form J #007 3. Attachment 3- Transducer's Pre com Form J #002 D. CONCLUSIONS Test Records and Receipt documents are to be carefully presented in original. SAES-J -904 Sec 13 B7 1. Plant Resource Manager or Third party test equipment REMARKS: Page 2 of 6 Error Out Put Equipment Type: User Reference: Equipment Tag No: Description: BI/JO No: Plant No Ref. Drawings and Documents Description Manufacturer : Model No Serial No Commissioning Date: PASS FAIL N/A RE-INSP DATE Resistance Insulation Resistance SAUDI ARAMCO - FOUNDATION Fieldbus Instruments Test Record -Form #J 01 Input % Simulated Input Process Input Range: Signal Output Range: External Span: Zero Adjustment: Zero Elevation: Zero Suppression:
0% SAUDI ARAMCO ID/PID - 4/14/05 - REV 0 (Standards Cutoff - August 2004) SAUDI ARAMCO TEST REPORT SATR NUMBER DATE APPROVED QR NUMBER SATR-J-6913 1-Oct-05 Attachment 1 FOUNDATION Fieldbus Instrument's Test Record FOUNDATION Fieldbus Instruments and Accessories Field Calibration and Testing INST ACCEPTANCE CRITERIA RESULTS ITEM No. 25% 50% 75% 100% 75% 25% 0% Ambient: 17. CONCLUSIONS Notes: a. Indicate in 1 report all instruments of a skid tested and passed . b. Rejected items should be listed in another report, unless they were corrected within the calibration period. c. Instruments repaired shall be indicated "Repaired and Accepted" in the test report. After successful completion of each calibration, the instrument shall be marked with a colored label bearing date of the calibration and the initials of the witnessing party The color code shall be as follows: Blue- Pre Calibration Tested. Yellow - Installed & Pressure Tested. Green- cables or tubing tested. Red- Loop Check completed. Is the IAMS / PRM / AMS configuration Completed ? IAMS=Instrument Asset Management System PRM =Plant Resource Manager and AMS=Asset Management System 18. REMARKS Note: The above form to be modified to suit the site requirements No Yes N/A Page 3 of 6 FOUNDATION Fieldbus Instruments and Accessories Field Calibration and Testing SATR-J-6913 1-Oct-05 INST Attachment 2- Thermocouple -Temperature Pre com Form # J 007 SAUDI ARAMCO ID/PID - 4/14/05 - REV 0 (Standards Cutoff - August 2004) SAUDI ARAMCO TEST REPORT SATR NUMBER DATE APPROVED QR NUMBER PROJ ECT TITLE WBS / BI / J O NUMBER CONTRACTOR / SUBCONTRACTOR Page 4 of 6 FOUNDATION Fieldbus Instruments and Accessories Field Calibration and Testing SATR-J-6913 1-Oct-05 INST Attachment 2- Thermocouple -Temperature Pre com Form # J 007 SAUDI ARAMCO ID/PID - 4/14/05 - REV 0 (Standards Cutoff - August 2004) SAUDI ARAMCO TEST REPORT SATR NUMBER DATE APPROVED QR NUMBER PROJ ECT TITLE WBS / BI / J O NUMBER CONTRACTOR / SUBCONTRACTOR Page 5 of 6 SAUDI ARAMCO ID/PID - 4/14/05 - REV 0 (Standards Cutoff - August 2004) SAUDI ARAMCO TEST REPORT SATR NUMBER DATE APPROVED QR NUMBER PROJ ECT TITLE WBS / BI / J O NUMBER CONTRACTOR / SUBCONTRACTOR FOUNDATION Fieldbus Instruments and Accessories Field Calibration and Testing SATR-J-6913 1-Oct-05 INST Attachment 3- Transducers's Pre com Form J #002 Page 6 of 6