Sie sind auf Seite 1von 31

Micrologic control units

2.0 A, 5.0 A, 6.0 A and 7.0 A


Low Voltage Products
User manual
We do more with electricity.
Micrologic A Schneider Electric 1
Discovering your control unit 2
Identifying your control unit 2
Overview of functions 4
Setting your control unit 10
Selecting the type of neutral protection 10
Setting procedure 11
Setting the Micrologic 2.0 A control unit 12
Setting the Micrologic 5.0 A control unit 13
Setting the Micrologic 6.0 A control unit 14
Setting the Micrologic 7.0 A control unit 15
Fault and status indications 16
Resetting the fault indications
and checking battery status 16
Testing the ground-fault
and earth-leakage functions 17
Menus 18
Accessing the menus 18
Measuring phase currents 19
Displaying the maximum current values 20
Resetting the maximum current values 21
Viewing the settings 22
Setting up the Modbus communications option 23
Technical appendix 24
Tripping curves 24
Changing the long-time rating plug 26
Zone selective interlocking (ZSI) 27
Digital display 28
Thermal memory 29
Micrologic control units
2.0 A, 5.0 A, 6.0 A and 7.0 A
Micrologic A Schneider Electric 2
Discovering your
control unit
E
5
1
3
8
4
A
E
5
1
4
5
0
A
All Compact NS800-3200 and Masterpact
NT and NW circuit breakers are equipped
with a Micrologic control unit
that can be changed on site.
Control units are designed to protect
power circuits and connected loads.
Identifying your control unit
Designations
E
5
1
3
5
2
A
X: type of protection
c 2 for basic protection
c 5 for selective protection
c 6 for selective + ground-fault protection
c 7 for selective + earth-leakage protection
Y: version number
identification of the control-unit generation.
"0" signifies the first generation.
Z: type of measurement
c A for "ammeter"
c P for "power meter"
c H for "harmonic meter"
c no indication: no measurements
Micrologic 2.0 A: basic protection and ammeter
Long time + Instantaneous
Micrologic 5.0 A: selective protection and ammeter
Long time + Short time + Instantaneous
E
5
1
3
8
5
A
E
5
1
3
5
4
A
0 Ir Isd I
t
0 Ir I
t
Ii Isd
Micrologic 6.0 A: selective + ground-fault protection and
ammeter
E
5
1
3
8
7
A
E
5
1
3
5
4
A
E
5
1
3
9
5
A
0 Ir I
t
Ii Isd
Long time + Short time
+ Instantaneous
Ground-fault protection
Micrologic 7.0 A: selective + earth-leakage protection and
ammeter
E
5
1
3
8
8
B
E
5
1
3
5
4
A
E
5
1
4
5
2
A
0 Ir I
t
Ii Isd
Long time + Short time
+ Instantaneous
Earth-leakage protection
Micrologic 2.0 A
Y
X
Z
Micrologic 2.0 A
40
100%
%
menu
long time
alarm
instantaneous
.4
.5
.6
.7
.8
.9
.95
.98
1
Ir
x In .5
1
2
4
8
12
16
20
tr
(s)
at 6 Ir 24
x Ir
2
2.5
3 4
5
6
1.5
setting
Isd
8
10
Micrologic 5.0 A
40
100%
%
menu
delay
short time
tsd
(s)
long time
alarm tr
(s)
setting
.4
.5
.6
.7
.8
.9
.95
.98
1
Ir
x In .5
1
2
4 8 12
16
20
at 6 Ir 24
x Ir
2
2.5
3 4 5
6
8
10
Isd
1.5
on I
2
t
.2
.4 .4
.1
.3
.1
0
I i
x In
3
4
8
off 2
.3
instantaneous
.2
6
15
10
12
Micrologic 6.0 A
40
100%
%
menu
delay
short time
on I
2
t
.2
.3
.4 .4
.1
.2
.1
0
long time
alarm
ground fault
setting
4
test
.4
.5
.6
.7
.8
.9
.95
.98
1
Ir
x In .5
1
2
4
8
12
16
20
tr
(s)
at 6 Ir 24
x Ir
2
2.5
3 4 5
6
8
10
Isd
1.5
tsd
(s)
x In
3
6 8 10
12
15
off 2
B
C
D E F
G
H
I
Ig
A
on I
2
t
.2
.3
.4 .4
.1
.2
.3
.1
0
off
tg
(s)
.1
.3
instantaneous
I i
0 I
t
I
2
t off
I
2
t on
Ig
Micrologic 7.0 A
40
100%
%
menu
.98
delay
short time
off
long time
alarm
setting
earth leakage
test
.4
.5
.6
.7
.8
.9
.95
1
Ir
x In
tr
(s)
.5
1
2
4
8
12
16
20
at 6 Ir 24
x Ir
2
2.5
3 4 5
6
8
10
Isd
1.5
tsd
(s)
on I
2
t
.2
.3
.4 .4
.1
.2
.3
.1
0
x In
3
4
6 8 10
12
15
off 2
1
2
3 5 7
10
20
30 .5
In
800
I
60
140
230 350
instantaneous
I i
0 I
t
In
Micrologic A Schneider Electric 3
1 top fastener
2 bottom fastener
3 protective cover
4 cover opening point
5 lead-seal fixture for protective cover
6 long-time rating plug
7 screw for long-time rating plug
8 connection with circuit breaker
9 infrared link with communications interfaces
10 terminal block for external connections
11 housing for battery
12 digital display
13 three-phase bargraph and ammeter
Adjustment dials
14 long-time current setting Ir
15 long-time tripping delay tr
16 short-time pickup Isd
17 short-time tripping delay tsd
18 instantaneous pick-up Isd
19 instantaneous pick-up Ii
20 ground-fault pick-up Ig
21 ground-fault tripping delay tg
22 earth-leakage pick-up In
23 earth-leakage tripping delay t
Indications
24 LED indicating long-time tripping
25 LED indicating short-time tripping
26 LED indicating ground-fault
or earth-leakage tripping
27 LED indicating auto-protection tripping
28 LED indicating an overload
Navigation
29 navigation button to change menus
30 navigation button to view menu contents
31 button for fault-trip reset and battery test
Test
32 test button for ground-fault and earth-leakage
protection
33 test connector
Presentation
E
5
1
3
8
9
B
E
5
1
3
9
0
A
E
5
1
3
9
1
B
Micrologic 7.0 A Micrologic 2.0 A
Micrologic 5.0 A
E
5
1
3
9
4
A
E
5
1
3
9
3
A
Micrologic 6.0 A
E
5
1
3
9
2
A
3
2
1
10
5
.4
.5
.6
.7
.8 .9
.95
.98
1
.5
1
2
4
8 12
16
20
24
long time
alarm
Ir
tr
(s)
x In
at 6 Ir
11
12
Micrologic 7.0 A
40
100%
%
menu
31
13
30
29
7
6
4
8
9
instantaneous
long time
alarm
.4
.5
.6
.7
.8
.9
.95
.98
1
Ir
x In
.5
1
2
4
8
12
16
20
tr
(s)
at 6 Ir
24
x Ir
2
2.5
3
4
5
6
8
10 1.5
setting
Isd
14
15
18
33
28
7
Micrologic 7.0 A
40
100%
%
menu
delay
short time
I i
long time
alarm
test
800
earth leakage
1
2
3
5
7
10
20
30
I
(ms)
60 .5
140
230
350
In
(A)
setting
x Ir
2
2.5
3
4 5
6
8
10 1.5
x In
3
4
6
8
10
12
15
off 2
.5
1
2
4
8
12
16
20
tr
(s)
at 6 Ir
24 .4
.5
.6
.7
.8
.9
.95
.98
1
Ir
x In
29
15
14
17
16
23
22
30
28
7
19
33
31
12
13
27 26 25 24
tsd
(s)
on I
2
t
.2
.3
.4
.4
.1
.2
.3
.1
0
off
instantaneous
Isd
32
.95
.98
setting delay
short time
I i tsd
(s)
long time
alarm
.4
.5
.6
.7
.8
.9
1
Ir
x In
.5
1
2
4
8
12
16
20
tr
(s)
at 6 Ir
24
x Ir
2
2.5
3
4
5
6
8
10
Isd
1.5
on I
2
t
.2
.3
.4
.4
.1
.2
.3
.1
0
x In
3
4
6
8
10
12
15
off 2
14
15
16
17
19
28
7
33
instantaneous
.4
.5
.6
.7
.8
.9
.95
.98
1
delay
short time
I i tsd
(s)
on I
2
t
.2
.3
.4
.4
.1
.2
.3
.1
0
off
long time
alarm Ir
x In
ground fault
B
C
D
E
F
G
H
I
Ig tg
(s)
on I
2
t
.2
.3
.4
.4
.1
.2
.3
.1
0
off
A
.5
1
2
4
8
12
16
20
tr
(s)
at 6 Ir
24
setting
x Ir
2
2.5
3
4
5
6
8
10
Isd
1.5
x In
3
4
6
8
10
12
15
off
test
instantaneous
15
14
17
16
21
20
28
7
19
32
33
2
Micrologic A Schneider Electric 4
Discovering your
control unit
Protection settings
Depending on the type of installation, it is possible to set the tripping curve of your
control unit using the parameters presented below.
Long-time protection
The long-time protection function protects cables (phases and neutral)
against overloads. This function is based on true rms measurements.
Thermal memory
The thermal memory continuously accounts for the amount of heat in the cables,
both before and after tripping, whatever the value of the current (presence of
an overload or not). The thermal memory optimises the long-time protection
function of the circuit breaker by taking into account the temperature rise in the
cables. The thermal memory assumes a cable cooling time of approximately
15 minutes.
Long-time current setting Ir and standard tripping delay tr
E
5
1
3
5
8
A
Overview of functions
Current protection
Micrologic 2.0 A
1. current setting Ir (long time)
2. tripping delay tr (long time) for 6 x Ir
3. pick-up Isd (instantaneous)
Micrologic control unit Accuracy 2.0 A, 5.0 A, 6.0 A and 7.0 A
current setting Ir = In (*) x 0.4 0.5 0.6 0.7 0.8 0.9 0.95 0.98 1
tripping between other ranges or disable by changing rating plug
1.05 and 1.20 x Ir
time delay (s) tr at 1.5 x Ir 0 to -30% 12.5 25 50 100 200 300 400 500 600
tr at 6 x Ir 0 to -20% 0.5 1 2 4 8 12 16 20 24
tr at 7.2 x Ir 0 to -20% 0.34 0.69 1.38 2.7 5.5 8.3 11 13.8 16.6
* In: circuit breaker rating
Setting accuracy of the Ir setting may be enhanced by using a different long-time
rating plug.
See the technical appendix "Changing the long-time rating plug".
0 Ir Isd I
t
1
2
3
E
5
1
3
5
9
A
Micrologic 5.0 A, 6.0 A,
7.0 A
1
2
3
4
5
0 Ir Isd I
t
Ii
I
2
t off
I
2
t on
E
5
1
3
8
6
A
E
5
1
3
9
6
A
Micrologic 6.0 A Micrologic 7.0 A
1. current setting Ir
(long time)
2. tripping delay tr
(long time) for 6 x Ir
3. pick-up Isd (short time)
4. tripping delay tsd
(short time)
5. pick-up Ii
(instantaneous)
1. pick-up Ig (ground
fault)
2. tripping delay tg
(ground fault)
1. pick-up In
(earth leakage)
2. tripping delay t
(earth leakage)
0 I
t
1
2
I
2
t off
I
2
t on
Ig 0 I
t
In
1
2
Micrologic A Schneider Electric 5
Short-time protection
c the short-time protection function protects the distribution system against
impedant short-circuits
c the short-time tripping delay can be used to ensure discrimination with a
downstream circuit breaker
c this function carries out true rms measurements.
c the I
2
t ON and I
2
t OFF options enhance discrimination with downstream
protection devices
c use of I
2
t curves with short-time protection:
v I
2
t OFF selected: the protection function implements a constant time curve;
v I
2
t ON selected: the protection function implements an I
2
t inverse-time
curve up to 10 Ir. Above 10 Ir, the time curve is constant.
c zone selective interlocking (ZSI)
The short-time and ground-fault protection functions enable time discrimination
by delaying the upstream devices to provide the downstream devices the time
required to clear the fault. Zone selective interlocking can be used to obtain total
discrimination between circuit breakers using external wiring.
Short-time pick-up Isd and tripping delay tsd
Micrologic control unit 2.0 A, 5.0 A, 6.0 A and 7.0 A
pick-up Isd = Ir x accuracy 10 % 1.5 2 2.5 3 4 5 6 8 10
time delay settings I
2
t OFF 0 0.1 0.2 0.3 0.4
(ms) at 10 Ir I
2
t ON 0.1 0.2 0.3 0.4
I
2
t ON or tsd (max resettable time) 20 80 140 230 350
I
2
t OFF tsd (max break time) 80 140 200 320 500
Instantaneous protection
c the instantaneous-protection function protects the distribution system
against solid short-circuits. Contrary to the short-time protection function,
the tripping delay for instantaneous protection is not adjustable.
The tripping order is sent to the circuit breaker as soon as current exceeds
the set value, with a fixed time delay of 20 milliseconds.
c this function carries out true rms measurements.
Instantaneous pick-up Isd
Micrologic control unit 2.0 A
pick-up Isd = Ir x accuracy 10 % 1.5 2 2.5 3 4 5 6 8 10
Instantaneous pick-up Ii
Micrologic control unit 5.0 A, 6.0 A and 7.0 A
pick-up li = In (*) x accuracy 10 % 2 3 4 6 8 10 12 15 OFF
* In: circuit-breaker rating
For the characteristics and external wiring
of the zone selective interlocking function,
see the technical appendix on
"Zone selective interlocking".
The portable test kit can be used to test
the wiring between circuit breakers
for the zone selective interlocking function.
Micrologic A Schneider Electric 6
Discovering your
control unit
Protection of the fourth pole on four-pole circuit breakers
Protection of the neutral conductor depends on the distribution system.
There are three possibilities.
Type of neutral Description.
Neutral unprotected The distribution system does not require protection
of the neutral conductor.
Neutral protection The cross-sectional area of the neutral conductor
at 0.5 In is half that of the phase conductors.
c the long-time current setting Ir for the neutral is equal
to half the setting value
c the short-time pick-up Isd for the neutral is equal
to half the setting value
c the instantaneous pick-up Isd (Micrologic 2.0 A)
for the neutral is equal to half the setting value
c the instantaneous pick-up Ii (Micrologic 5.0 A / 6.0 A /
7.0 A) for the neutral is equal to the setting value.
Neutral protection The cross-sectional area of the neutral conductor is equal
at In to that of the phase conductors.
c the long-time current setting Ir for the neutral is equal
to the setting value
c the short-time pick-up Isd for the neutral is equal to
the setting value
c the instantaneous pick-ups Isd and Ii for the neutral
are equal to the setting value.
Overview of functions
Current protection
Ground-fault protection on Micrologic 6.0 A
c an ground fault in the protection conductors can provoke local temperature rise
at the site of the fault or in the conductors.
The purpose of the ground-fault protection function is to eliminate this type of fault.
c there are two types of ground-fault protection.
Type Description
Residual c the function determines the zero-phase sequence
current, i.e. the vectorial sum of the phase and neutral
currents
c it detects faults downstream of the circuit breaker.
Source Ground Return c using a special external sensor, this function
directly measures the fault current returning
to the transformer via the earth cable
c it detects faults both upstream and downstream
of the circuit breaker
c the maximum distance between the sensor
and the circuit breaker is ten metres.
c ground-fault and neutral protection are independent and can therefore be
combined.
Ground-fault pick-up Ig and tripping delay tg
The pick-up and tripping-delay values can be set independently and are identical
for both the residual and "source ground return" ground-fault protection functions.
Micrologic control unit 6.0 A
pick-up Ig = In (*) x accuracy 10 % A B C D E F G H I
In 400 A 0.3 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
400 A < In 1200 A 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
In > 1200 A 500 A 640 A 720 A 800 A 880 A 960 A 1040 A 1120 A 1200 A
time delay settings I
2
t OFF 0 0.1 0.2 0.3 0.4
(ms) at 10 In (*) I
2
t ON 0.1 0.2 0.3 0.4
I
2
t ON or tg (max resettable time) 20 80 140 230 350
I
2
t OFF tg (max break time) 80 140 200 320 500
* In: circuit-breaker rating
Neutral protection for three-pole devices
Neutral protection is not available on three-pole devices.
Micrologic A Schneider Electric 7
Current protection and alarms
Earth-leakage protection on Micrologic 7.0 A
c the earth-leakage protection function primarily protects people against indirect
contact because an earth-leakage current can provoke an increase in the potential
of the exposed conductive parts. The earth-leakage pick-up value In is displayed
directly in amperes and the tripping delay follows a constant-time curve
c an external rectangular sensor is required for this function
c this function is inoperative if the long-time rating plug is not installed
c d protected against nuisance tripping.
c kDC-component withstand class A up to 10 A.
Pick-up value I n and tripping delay t
Micrologic control unit 7.0 A
pick-up In accuracy 0 to - 20 % 0.5 1 2 3 5 7 10 20 30
time delay settings
(ms) t (max resettable time) 60 140 230 350 800
t (max break time) 140 200 320 500 1000
Overload LED
E
5
1
3
9
8
B
This LED signals that the long-time current setting Ir has been overrun.
Fault indications
E
5
1
3
9
9
A
E
5
1
4
0
0
A
E
5
1
4
0
1
A
E
5
1
4
0
2
A
Signals tripping due to an
overrun of the long-time
current setting Ir.
Signals tripping due
to an overrun of the
short-time pick-up Isd
or the instantaneous
pick-up Isd / Ii.
Signals tripping due to an
overrun of the ground-
fault pick-up Ig or the
earth-leakage pick-up
In.
Signals tripping due to
the auto-protection
function of the control
unit.
delay
short time
I i tsd
(s)
long time
alarm
test
800
earth leakage
1
2
3
5
7
10
20
30
t
(ms)
60 .5
140
230 350
In
(A)
setting
x Ir
2
2.5
3
4
5
6
8
10
Isd
1.5
on I
2
t
.2
.3
.4
.4
.1
.2
.3
.1
0
x In
3
4
6
8
10
12
15
off 2
.5
1
2
4
8
12
16
20
tr
(s)
at 6 Ir
24 .4
.5
.6
.7
.8
.9
.95
.98
1
Ir
x In
instantaneous
40
%
%
100
Micrologic 7.0 A Micrologic 7.0 A
Micrologic 7.0 A Micrologic 7.0 A
The auto-protection function (excessive
temperature or short-circuit higher than
circuit-breaker capacity) opens the circuit
breaker and turns on the Ap LED.
Caution.
If the circuit breaker remains closed and
the Ap LED remains on, contact the
Schneider after-sales support department.
Caution.
The battery maintains the fault indications.
If there are no indications, check the
battery.
Micrologic A Schneider Electric 8
Discovering your
control unit
Overview of functions
Ammeter measurements
c all Micrologic control units measure the true rms value of currents
c the most heavily loaded phase is continuously displayed on the digital screen
c using the navigation buttons, it is possible to display successively the I1, I2, I3,
neutral IN, Ig, IN and stored-current (maximeter) values
c the percent load on each phase is displayed. A bargraph displays the currents
measured on phases 1, 2 and 3 as a percentage of the long-time current setting Ir.
E
6
0
3
7
1
A
40
%
%
100
1.125 x Ir
1 x Ir
0.8 x Ir
0.6 x Ir
0.4 x Ir
If no information is displayed on the screen,
see the technical appendix "Digital display".
c accuracy of the current measurements
Accuracy depends on both the value displayed (or transmitted) and the circuit-
breaker rating, where:
Accuracy = 0.5% In + 1.5% reading
Example
For a circuit breaker with a 4000 A rating and a current displayed on Micrologic of
49 A, the accuracy is:
0.5% x 4000 + 1.5% x 49 = 21 A
Micrologic A Schneider Electric 9
Micrologic A Schneider Electric 10
Setting your control unit Selecting the type
of neutral protection
On four-pole circuit breakers, it is possible to select the type of neutral protection
for the fourth pole:
c neutral unprotected (4P 3D);
c neutral protection at 0.5 In (3D + N/2);
c neutral protection at In (4P 4D).
E
5
1
3
8
3
A
4P 3D
3D
+N
/2
4P 4D
Micrologic A Schneider Electric 11
Setting procedure
Setting procedure
1. Open the protective cover.
2. Select the desired
setting.
The set value is
automatically displayed
on the digital screen in
absolute value with the
relevant units.
c Current in amperes
(A and kA);
c Tripping delays in
seconds.
E
5
1
4
1
0
A
E
5
1
4
1
1
A
3. If no information is displayed, see the technical
appendix "Digital display". If no further action is taken,
after a few seconds, the display returns to the main
menu for current measurements.
4. Close the protective cover and, if necessary, install
a lead seal to protect the settings.
E
5
1
4
1
2
A
Using the portable test kit
To test the control unit, connect the portable test kit via the test connector.
1
Micrologic 7.0 A
40
100%
%
menu
Micrologic 7.0 A
40
100%
%
menu
2
A
Ir=
3
Micrologic 7.0 A
40
100%
%
menu
E
5
1
4
1
3
A
2
Micrologic 7.0 A
40
100%
%
menu
E
5
1
4
1
0
A
1
Micrologic 7.0 A
40
100%
%
menu
See the user manual for the portable
test kit
Micrologic A Schneider Electric 12
Setting your control unit Setting the Micrologic 2.0 A
control unit
Set the threshold values
E
5
1
3
6
6
A
E
6
0
3
6
5
A
Set the tripping delay
The rating of the circuit breaker
in this example is 2000 A.
See pages 4 and 5 for information
on the available settings
E
5
1
3
6
8
A
E
6
0
3
6
6
B
E
5
1
3
7
0
A
1
In = 2000 A
In = 2000 A
In = 2000 A
Ir = 0.7 x In = 1400 A
Isd = 3 x Ir = 4200 A
alarm
x Ir
2
2.5
3
4
5
6
8
10 1.5
setting
Isd
instantaneous
.4
.5
.6
.7
.8
.9
.95
.98
1
long time
Ir
x In
0 I
t
Ir
Isd
long time
alarm
.5
1
2
4
8
12
16
20
tr
(s)
at 6 Ir
24
tr = 1 s
0 I
t
tr
Micrologic A Schneider Electric 13
Setting the Micrologic 5.0 A
control unit
Set the threshold values
E
5
1
3
6
6
A
E
6
0
3
6
7
A
Set the tripping delay
The rating of the circuit breaker
in this example is 2000 A.
See pages 4 and 5 for information
on the available settings
E
6
0
3
6
8
B
In = 2000 A
Ir = 0.7 x In = 1400 A
Ii = 3 x In = 6000 A
Isd = 2 x Ir = 2800 A
.4
.5
.6
.7
.8
.9
.95
.98
1
setting
short time
I i
x Ir
2
2.5
3
4
5
6
8
10
Isd
1.5
long time
alarm Ir
x In
x In
3
4
6
8
10
12
15
off 2
instantaneous
tr = 1 s
tsd = 0.2 s
short time
long time
alarm
.5
1
2
4
8
12
16
20
tr
(s)
at 6 Ir
24
delay
tsd
(s)
on I
2
t
.2
.3
.4
.4
.1
.2
.3
.1
0
I
2
t on I
2
t off
E
5
1
3
7
2
A
E
5
1
3
7
3
A
Ir
Isd
Ii
0 I
t
Ir
Isd
Ii
0 I
t
I
2
t

ON curve
I
2
t

OFF curve
1
In = 2000 A
In = 2000 A
Thresholds
E
5
1
3
7
5
A
E
5
1
3
7
6
A
tr
tsd
0 I
t
tr
tsd
0 I
t
I
2
t

ON curve I
2
t

OFF curve
Tripping delays
Micrologic A Schneider Electric 14
Setting your control unit Setting the Micrologic 6.0 A
control unit
Set the threshold values
E
5
1
3
6
6
A
E
5
1
4
1
4
A
The rating of the circuit breaker
in this example is 2000 A.
See pages 4 to 6 for information
on the available settings.
E
5
1
3
7
3
A
E
5
1
3
7
2
A
Ir
Isd
Ii
0 I
t
Ir
Isd
Ii
0 I
t
I
2
t

ON curve I
2
t

OFF curve
Set the tripping delay
E
6
0
3
7
2
B
E
5
1
3
7
6
A
E
5
1
3
7
5
A
tr
tsd
0 I
t
tr
tsd
0 I
t
E
5
1
4
1
6
A
E
5
1
4
1
5
A
E
5
1
4
1
9
A
E
5
1
4
1
8
A
0 I
t
tg
0 I
t
tg
1
In = 2000 A
In = 2000 A
short time
long time
alarm
ground fault
setting
.4
.5
.6
.7
.8
.9
.95
.98
1
Ir
x In
x Ir
2
2.5
3
4
5
6
8
10
Isd
1.5
B
C
D
E
F
G
H
I
Ig
A
I i
x In
3
4
6
8
10
12
15
off 2
In = 2000 A
Ir = 0.7 x In = 1400 A
Ii = 3 x In = 6000 A
Isd = 2 x Ir = 2800 A
B Ig = 640 A
instantaneous
test
0 I
t
Ig
0 I
t
Ig
short time
long time
alarm
ground fault
.5
1
2
4
8
12
16
20
tr
(s)
at 6 Ir
24
delay
tsd
(s)
on I
2
t
.2
.3
.4
.4
.2
.3
.1
0
off
tg
(s)
on I
2
t
.2
.3
.4
.4
.1
.2
.3
.1
0
off
tr = 1 s
tsd = 0.2 s
tg = 0.2 s
I
2
t on I
2
t off
.1
test
Thresholds
Tripping delays
I
2
t

ON curve I
2
t

OFF curve
Micrologic A Schneider Electric 15
Setting the Micrologic 7.0 A
control unit
Set the threshold values
E
5
1
3
6
6
A
E
5
1
4
2
0
A
The rating of the circuit breaker
in this example is 2000 A.
See pages 4 to 7 for information
on the available settings.
Set the tripping delay
E
5
1
4
2
2
B
1
In = 2000 A
In = 2000 A
.4
.5
.6
.7
.8
.9
.95
.98
1
short time
I i
long time
alarm Ir
x In
setting
x Ir
2
2.5
3
4
5
6
8
10
Isd
1.5
x In
3
4
6
8
10
12
15
off 2
instantaneous
In = 2000 A
Ir = 0.7 x In = 1400 A
Ii = 3 x In = 6000 A
Isd = 2 x Ir = 2800 A
In = 1 A
1
2
3
5
7
10
20
30 .5
In
(A)
test
earth leakage
short time
long time
alarm
.5
1
2
4
8
12
16
20
tr
(s)
at 6 Ir
24
delay
tsd
(s)
on I
2
t
.2
.3
.4
.4
.1
.2
.3
.1
0
off
800
t
(ms)
60
140
230
350
tr = 1 s
tsd = 0.2 s
t = 140 ms
I
2
t on I
2
t off
test
earth leakage
I
2
t

OFF curve
E
5
1
3
7
3
A
E
5
1
3
7
2
A
Ir
Isd
Ii
0 I
t
Ir
Isd
Ii
0 I
t
I
2
t

ON curve I
2
t

OFF curve
E
5
1
3
7
6
A
E
5
1
3
7
5
A
tr
tsd
0 I
t
tr
tsd
0 I
t
E
5
1
4
2
1
A
E
5
1
4
2
3
A
Thresholds
Tripping delays
I
2
t

ON curve
0 I
t
In
0 I
t
t
Micrologic A Schneider Electric 16
Fault and status
indications
The procedure for closing the circuit
breaker following a fault trip is presented
in the circuit-breaker user manual.
Resetting the fault indications
and checking battery status
If the battery needs to be changed, order a
new battery with the Schneider catalogue
number 33593.
c lithium battery
c 1.2 AA, 3.6 V, 850 mA/h
c SAFT LS3 SONNENSCHEIN TEL-S
c service life ten years.
Resetting the fault indications
c determine why the circuit breaker tripped.
The fault indication is maintained until it is reset on the control unit.
v press the fault-trip reset button.
E
5
1
4
3
9
A
v check the parameter settings of the control unit.
Checking the battery
E
5
1
4
4
1
A
Press the battery-test button (same as the fault-trip reset button) to display
the battery status.
If no information is displayed, either:
c no battery is installed in the control unit, or;
c an auxiliary power supply is required.
See the technical appendix "Digital display".
Changing the control-unit battery
1. Remove the battery
cover.
2. Remove the battery.
E
5
1
4
4
2
A
E
5
1
4
4
3
A
3. Insert a new battery.
Check the polarity.
4. Put the cover back in
place. Press the battery-
test button to check the
new battery.
E
5
1
4
4
4
A
Micrologic 7.0 A
E
5
1
4
4
0
A
Battery fully charged
Battery half charged
Change the battery
40
100%
%
+
E
5
1
4
4
5
A
40
100%
%
Micrologic A Schneider Electric 17
Testing the ground-fault and
earth-leakage functions
Charge and close the circuit breaker.
Using a screwdriver, press the test button for ground-fault and earth-leakage
protection. The circuit breaker should open.
E
5
1
4
5
6
B
Micrologic 7.0 A
40
100%
%
menu
If the circuit breaker does not open, contact the Schneider after-sales
support department.
Micrologic A Schneider Electric 18
Accessing the menus
Symbols used:
Briefly press a key.
Press and hold a key.
E
5
1
4
0
4
A
E
5
1
4
0
5
A
It is possible at any time to stop consulting
a current measurement, a maximum
current value recorded by the maximeter or
the setting values. After a few seconds, the
Micrologic control unit automatically returns
to the main menu displaying the current
value of the most heavily loaded phase.
The protection settings can be displayed
directly on the digital display.
Three menus may be accessed on Micrologic control units, providing the following
information:
c phase current measurements I1, I2, I3, neutral IN, ground-fault current Ig on the
Micrologic 6.0 A control unit and earth-leakage current In on the Micrologic 7.0 A
control unit;
c maximeter current values for phases I1, I2, I3, neutral IN, the maximum ground-
fault current Ig on the Micrologic 6.0 A control unit and the maximum earth-leakage
current In on the Micrologic 7.0 A control unit;
c protection settings and tripping delays.
Press the "menu" button
to access the maximum
current values measured
by the maximeter.
Press the "menu" button
to access the protection
settings and tripping
delays.
Press the "menu" button
to return to the current
measurements.
E
5
1
4
0
6
A
E
5
1
4
0
7
A
E
5
1
4
0
8
A
4. The system returns
to the main
"Measurements" menu.
E
5
1
4
0
9
B
40
100%
%
A
menu
40
100%
%
A
Max
menu
40
100%
%
A
Ir=
menu
40
100%
%
A
Menus
1. Measurements 2. Maximeter 3. Settings
Micrologic A Schneider Electric 19
Current values may be read in the
"Measurements" menu, which is also the
main menu.
If no particular action is taken, the system
displays the current value of the most
heavily loaded phase.
E
5
1
4
0
9
B
Measuring phase currents
Display of current I1. Display of current I2.
E
5
1
4
2
5
A
E
5
1
4
2
6
A
Press the "arrow" button
to go on to current I2.
Press the "arrow" button
to go on to current I3.
Display of current I3.
Display of current Ig
(Micrologic 6.0 A) or
current I n
(Micrologic 7.0 A).
Press the "arrow" button
to go on to current IN if
the neutral is protected.
E
5
1
4
2
7
A
E
5
1
4
2
8
A
Display of current IN. The system returns to
the display of current I1.
E
5
1
4
2
9
A
E
5
1
4
0
9
B
40
100%
%
A
40
100%
%
A
40
100%
%
A
40
100%
%
A
40
100%
%
A
40
100%
%
A
40
100%
%
A
Press the "arrow" button
to return to current I1.
"Measurements" menu
Phase 1 is the most heavily loaded.
Press the "arrow" button
to go on to the ground-
fault current Ig or the
earth-leakage current
In.
Micrologic A Schneider Electric 20
Menus
Maximum current values may be read in
the "Maximeter" menu.
If no particular action is taken, the system
returns to the main menu.
E
5
1
4
0
7
A
Displaying the maximum
current values
Display of the
maximum I1 current.
Display of the
maximum I2 current.
E
5
1
4
3
0
A
E
5
1
4
3
1
A
Press the "arrow" button
to go on to the maximum
I2 current.
Press the "arrow" button
to go on to the maximum
I3 current.
Display of the
maximum I3 current.
Press the "arrow" button
to go on to the maximum
ground-fault current Ig
(Micrologic 6.0 A) or the
maximum earth-leakage
current In
(Micrologic 7.0 A)
Press the "arrow" button
to go on to the maximum
current IN if the neutral is
protected.
E
5
1
4
3
2
A
E
5
1
4
3
3
A
Display of the
maximum IN current.
The system returns to
the display of the
maximum I1 current.
E
5
1
4
3
4
A
E
5
1
4
3
5
A
Press the "arrow" button
to return to the maximum
I1 current.
40
100%
%
A
MAX
40
100%
%
A
MAX
40
100%
%
A
MAX
40
100%
%
MAX
A
40
100%
%
A
MAX
40
100%
%
A
MAX
40
100%
%
A
Max
menu
Display of the maximum
Ig current or the
maximum I n current.
"Maximeter" menu.
Micrologic A Schneider Electric 21
Maximum current values can be reset
using the "Maximeter" menu.
If no particular action is taken, the system
returns to the main menu.
E
5
1
4
0
7
A
Resetting the maximum current
values
Select the maximum
current value to be
reset (e.g. I2 max.).
Reset.
E
5
1
4
3
6
A
E
5
1
4
3
7
A
Press the "arrow" button
as many times as
required to select I2 max.
Press and hold the
"arrow" button down for
three to four seconds.
The current value flashes
during the reset, then
changes to the present
value (the new
maximum).
Select another value
to reset or return to
the main menu.
Press the "arrow" button
as many times as
required to select another
maximum value to reset
or return to the main
menu.
E
5
1
4
3
8
A
40
100%
%
A
Max
menu
40
100%
%
A
MAX
40
100%
%
A
MAX
40
100%
%
A
MAX
"Maximeter" menu.
Micrologic A Schneider Electric 22
Menus Viewing the settings
E
6
0
3
7
4
B
Long-time current setting Ir
Long-time tripping delay tr
Short-time pick-up Isd
Short-time tripping delay tsd
Instantaneous pick-up Isd
Instantaneous pick-up Ii
Ground-fault pick-up Ig
Earth-leakage pick-up In
Ground-fault tripping delay tg
Earth-leakage tripping delay t
Micrologic control unit
menu
A
s
tr=
A
Isd=
s
tsd=
A
Ig=
s
tg=
s
t=
A
Ir=
Ii=
Ir=
Isd=
A
A
In=
A
5.0 A 6.0 A 7.0 A 2.0 A
Select the "Settings"
menu.
The Ir value is the first
displayed.
Press the "arrow" button
to go on to the tr value.
Press the "arrow" button
to go on to the
short-time Isd value.
Press the "arrow" button
to go on to the tsd
value.
Press the "arrow" button
to go on to the
instantaneous Isd
value.
Or
Press the "arrow" button
to go on to the Ig value.
Or
Press the "arrow" button
to go on to the tg value.
Or
the t value.
Press the "arrow" button
to return to the
beginning of the menu.
the instantaneous Ii
value.
the In value.
Micrologic A Schneider Electric 23
Setting up the Modbus
communications option
When a communications option is used,
the communications parameters must be
set. Note that the COM module should be
set up only when installed. Modification of a
parameter on a system already in operation
may lead to communications faults.
The "Parameter" menu for the
communications option displays the:
c address of the communications module;
c baud rate;
c parity;
c language.
Briefly press the button to scroll through
the parameter values.
Press the button somewhat longer to go
on to the next parameter.
After selecting the language, press and
hold the button to return to the
"Metering" menu.
4. Parity
1. Metering menu
40
100%
%
A
menu
E
7
1
9
0
3
A
2. Modbus address
40
100%
%
Set the Modbus address,
40
100%
%
You are in the "Metering"
menu. Simultaneously
press the two buttons to
access the parameter
settings for the
communications option.
E
7
1
9
0
4
A
E
7
1
9
0
5
A
then go on to the next
parameter.
then go on to the next
parameter.
5. Language
Set the language, then return to the
"Metering" menu.
E
7
1
9
0
9
A
40
100%
%
E
7
1
9
1
0
A
40
100%
%
E
7
1
9
1
1
A
3. Baud rate
Set the baud rate, then go on to the next
parameter.
Set the parity.
40
100%
%
E
7
1
9
0
8
A
E
7
1
9
0
7
A
40
100%
%
E
7
1
9
0
6
A
40
100%
% 40
100%
%
40
100%
%
Micrologic A Schneider Electric 24
Technical appendix Tripping curves
Long-time and instantaneous protection (Micrologic 2.0 A)
E
6
0
3
6
9
A
.5 .7 1 2 3 4 5 7 10 20 30 50 70 100 200 300
I / Ir
10 000
5 000
2 000
1 000
500
200
100
50
20
10
5
2
1
.5
.2
.1
.05
.02
.01
.005
.002
.001
t(s)
tr = 0.524 s
Isd = 1.510 x Ir
Ir = 0.41 x In
Long-time, short-time and instantaneous protection
(Micrologic 5.0 A, 6.0 A and 7.0 A)
E
6
0
3
7
0
A
0
0.4
0.3
0.2
0.1
t(s)
.5 .7 1 2 3 4 5 7 10 20 3 5 7 10 20 30
10 000
5 000
2 000
1 000
500
200
100
50
20
10
5
2
1
.5
.2
.1
.05
.02
.01
.005
.002
.001
x In
tr = 0.524 s
Isd = 1.510 x Ir
Ir = 0.41 x In
Ii = 215 x In . OFF (1)
I
2
t OFF
x Ir
0.4
0.3
0.2
0. 1
I
2
t ON
0
Micrologic A Schneider Electric 25
Ground-fault protection (Micrologic 6.0 A)
E
4
6
2
6
6
A
Ig = AJ x In (1)
1200 A max.
t(s)
I / In
10 000
5 000
2 000
1 000
500
200
100
50
20
10
5
2
1
.5
.2
.1
.05
.02
.01
.005
.002
.001
.05.07 .1 .2 .3 .4 .5 .7 1 2 3 5 7 10 200 300
I
2
t OFF
0.4
0.3
0.2
0.1
I
2
t ON
0.4
0.3
0.2
0.1
0 0
Micrologic A Schneider Electric 26
Technical appendix
Caution.
Following any modifications to the long-
time rating plug, all control-unit protection
parameters must be checked.
Changing the long-time
rating plug
Select the long-time rating plug
A number of setting ranges for the long-time current setting are available on
Micrologic A control units by changing the long-time rating plug.
The available rating plugs are listed below.
Part number Setting range for the Ir value
33542 standard 0.4 to 1 x Ir
33543 low setting 0.4 to 0.8 x Ir
33544 high setting 0.8 to 1 x Ir
33545 without long-time protection
Ir = In for the Isd setting
Change the long-time rating plug
Proceed in the following manner.
2. Open the protective
cover of the control unit.
3. Completely remove
the long-time rating plug screw.
E
5
1
3
7
8
A
E
5
1
3
7
9
A
4. Snap out the rating
plug.
5. Clip in the new rating plug.
E
5
1
3
8
0
A
E
5
1
3
8
1
A
6. Refit the screw for the
long-time rating plug.
7. Check and/or modify the
control-unit settings.
Caution.
If no long-time rating plug is installed, the
control unit continues to operate under the
following downgraded conditions:
c the long-time current setting Ir is 0.4;
c the long-time tripping delay tr
corresponds to the value indicated by the
adjustment dial;
c the earth-leakage protection function is
disabled.
Micrologic 7.0 A
40
100%
%
menu
Micrologic 7.0 A
40
100%
%
menu
Micrologic 7.0 A
40
100%
%
menu
.4
.5
.6
.7
.8 .9
.95
.98
1
long time
alarm
Ir
x In
.5
1
2
4
8 12
16
20
tr
(s)
@ 6 Ir24
Micrologic 7.0 A
40
100%
%
menu
.4
.5
.6
.7
.8 .9
.95
.98
1
long time
alarm
Ir
x In
.5
1
2
4
8 12
16
20
tr
(s)
@ 6 Ir24
1. Open the circuit breaker.
Micrologic A Schneider Electric 27
Caution.
If the protection function is not used on
circuit breakers equipped for ZSI
protection, a jumper must be installed to
short terminals Z3, Z4 and Z5.
If the jumper is not installed, the short-time
and ground-fault tripping delays are set
to zero, whatever the position of the
adjustment dial.
Zone selective interlocking (ZSI)
Operating principle
c A fault occurs at point A.
Downstream device no. 2 clears the fault and sends a signal to upstream device
no. 1, which maintains the short-time tripping delay tsd or the ground-fault tripping
delay tg to which it is set.
c A fault occurs at point B.
Upstream device no. 1 detects the fault. In the absence of a signal from a
downstream device, the set time delay is not taken into account and the device
trips according to the zero setting. If it is connected to a device further upstream, it
sends a signal to that device, which delays tripping according to its tsd or tg setting.
Note :
On device no. 1, the tsd and tg tripping delays must not be set to zero because this
would make discrimination impossible.
E
5
1
3
9
7
B
Z1
Z2
Z3
Z4
Z5
1
Z1
Z2
Z3
Z4
Z5
Z1
Z2
Z3
Z4
Z5
Z1
Z2
Z3
Z4
Z5
tsd = 0.3
tsd = 0.2
2
downstream
circuit-breaker
point B
point A
upstream
circuit-breaker
E
7
1
9
1
2
A
Connections between control units
A logic signal (0 or 5 volts) can be used for zone selective interlocking between the
upstream and downstream circuit breakers.
c Micrologic 5.0 A, 6.0 A, 7.0 A.
c Micrologic 5.0 P, 6.0 P, 7.0 P.
c Micrologic 5.0 H, 6.0 H, 7.0 H.
An interface is available for connection to previous generations of trip units.
Wiring
c maximum impedance: 2.7 / 300 metres
c capacity of connectors: 0.4 to 2.5 mm
2
c wires: single or multicore
c maximum length: 3000 metres
c limits to device interconnection:
v the common ZSI - OUT (Z1) and the output ZSI - OUT (Z2)
can be connected to a maximum of 10 inputs;
v a maximum of 100 devices may be connected to the common ZSI - IN (Z3) and
to an input ZSI - IN CR (Z4) or GF (Z5).
Terminals Z1 to Z5 correspond to the
identical indications on the circuit-breaker
terminal blocks.
Test
The portable test kit may be used to check the wiring and operation of the zone
selective interlocking between a number of circuit breakers.
A
B 1
2
Micrologic A Schneider Electric 28
Technical appendix Digital display
c display of measurements operates without an external power supply.
The digital display goes off if the current drops below 0.2 x In (In = rated current).
An optional 24 V external power supply may be used to maintain the display of
currents.
c display back-lighting is disabled in the following situations:
v current less than 1 x In on one phase;
v current less than 0.4 x In on two phases;
v current less than 0.2 x In on three phases.
c the maximeter does not operate for currents under 0.2 x In.
The display back-lighting and the maximeter may be maintained, whatever the
current, by adding a 24 V external power supply. Even if an external power supply
is installed, the long-time, short-time, instantaneous and earth protection functions
will not use it.
For information on connecting an external
power supply, see the electrical diagrams
in the circuit-breaker user manual.
Micrologic A Schneider Electric 29
Thermal memory
Thermal memory
The thermal memory is the means to take into account temperature rise and
cooling caused by changes in the flow of current in the conductors.
These changes may be caused by:
c repetitive motor starting
c loads fluctuating near the long-time protection settings
c repeated circuit-breaker closing on a fault.
Control units with a thermal memory record the temperature rise caused by each
overload, even very short ones. This information stored in the thermal memory
reduces the tripping time.
Micrologic control units and thermal memory
All Micrologic control units are equipped as standard with a thermal memory
c for all protection functions, prior to tripping, the temperature-rise and cooling time
constants are equal and depend on the tr tripping delay:
v if the tripping delay is short, the time constant is low
v if the tripping delay is long, the time constant is high.
c for long-time protection, following tripping, the cooling curve is simulated by the
control unit. Closing of the circuit breaker prior to the end of the time constant
(approximately 15 minutes) reduces the tripping time indicated in the tripping
curves.
Short-time protection and intermittent faults
For the short-time protection function, intermittent currents that do no provoke
tripping are stored in the Micrologic memory.
This information is equivalent to the long-time thermal memory and reduces the
tripping delay for the short-time protection.
Following a trip, the short-time tsd tripping delay is reduced to the value of the
minimum setting for 20 seconds.
Ground-fault protection and intermittent faults
The ground-fault protection implements the same function as the short-time
protection.
Schneider Electric Industries SA
Designed by: HeadLines
Printed by:
As standards, specifications and designs develop from time, always ask for confirmation of the
information given in this publication.
5, rue Nadar
92506 Rueil-Malmaison Cedex
France
Tel: +33 (0)1 41 29 82 00
Fax: +33 (0)1 47 51 80 20
http://www.schneiderelectric.com
04443724AA-B 10-01
This document has been printed on ecological paper.

Das könnte Ihnen auch gefallen