Beruflich Dokumente
Kultur Dokumente
v
p
sign
dc
V
* *
dc
V
ref mpp
V
,
pv
P
pv
V
pv
P
~
pv
V
~
v
p
sign
dc
V
ref mpp
V
,
* *
dc
V
+
+
( ) s I
ref
g
( ) s I
g
( ) s V
inv
( ) s V
g
-
-
SCEECS 2014
which is of the form:
(1)
The controller ( ) s G
i
is responsible for reference signal
tracking. It consists of a damped generalized integrator tuned to
resonate at the grid frequency
0
W
. The structure of PR
controller is as follows:
( )
2
0 0
2
0 ir
pr i
W s 2W s
s W 2K
K s G
+ +
+ = (2)
Where the proportional gain is tuned in the same way as
that for a PI controller, and it basically determines the
dynamics of the system in terms of bandwidth, phase, and gain
margin. According to the analysis proposed in [9] it seems
reasonable to select a high value resonant gain
ir
K in order to
obtain a high attenuation of current harmonic, a low value of
in order to get a low bandwidth so that the selective harmonic
compensation is effective for PR structure shown in (2). ( )
inv
G s
is the transfer function of the inverter bridge, which is modeled
as a first order lag system with time constant equal to 1.5 times
the switching period. Fig. 5 shows the Bode plot of the inner
current loop with and without Current controller.
Fig. 5. Bode plot of inner current loop.
B. Grid Synchronizer
The grid synchronizer consists of two parts: 1) a grid
voltage estimator, and 2) an amplitude identifier [11]. The grid
voltage estimator takes the grid voltage as the input and outputs
two signals. One is aligned with the grid voltage (parallel
component), and second signal that leads the grid voltage by
(orthogonal component). The state space form of the estimator
is expressed as:
Where
2 1
, y y are the normalized parallel component and
orthogonal component of the grid voltage. A grid voltage
amplitude estimator is needed to determine the amplitude of
the grid voltage. The amplitude identifier has the form
2
2
2
1
y y V
g
+ = .
C. Voltage Controller
In general using electrolytic capacitors are less desirable for
their short operational lifetime. Hence Long lifetime film
capacitors serves as a substitute, however their high prices limit
the size that can be used in PV inverters. This causes a
significant double line frequency ripple on the DC link voltage
which may further couple through the control loop. Therefore a
band stop filter is placed on the dc voltage feedback loop to
attenuate the ripple. Fig. 6 shows the block diagram of the
outer voltage control loop. A simple PI controller is used as a
voltage controller ( ) s G
v
to regulate the dc link voltage.
Fig. 6. Block diagram of outer voltage loop.
The value of the proportional gain of the voltage controller
is selected such that the closed loop bandwidth of the voltage
control loop is about 1/150th of the closed current loop [10].
Fig .7 shows the Bode plot of the voltage control loop with and
without voltage controller.
Fig. 7. Bode plot of outer voltage loop.
IV. SIMULATION RESULTS
In order to predict the comparative performance of the
MPPT techniques, simulation studies of the single phase grid
connected PV system shown in Fig. 1 are carried out on
MATLAB/SIMULINK platform. The specifications for the
solar module used in the simulations study, corresponding to
two different irradiation levels (1000 and 600
2
W/m ) are
( )
( ) ( )s L L s R C L L s C L L
1 + s C R
s G
g i
2
d f g i
3
f g i
f d
f
+ + + +
=
ref mpp
V
,
dc
V
( ) s I
ref
g
( ) s I
g
Grid synchronization
Grid De-synchronization
SCEECS 2014
provided in Table I. The grid connected PV inverter system is
subjected to a rapid irradiation level is changed from 1000 to
600
2
W/m at t=2s and reverted back to 1000
2
W/m at 3s as
shown in Fig. 8. The temperature is considered to be constant
(
C 25
0
) during the simulation. The parameters of the grid
connected PV inverter system and the values of the control
parameters are as shown in Table II.
TABLE I
PV MODULE SPECIFICATIONS
Parameter Symbol Values
Peak power
p
P 60W 35W
Peak power voltage
mp
V 17.1V 16.8V
Current at peak power
mp
I 3.5A 2.1A
Short circuit current
sc
I 3.8A 2.3A
Open circuit voltage
oc
V 21.1V 20.4V
Solar irradiation S 1000
2
W/m 600
2
W/m
Simulation results of the RCC MPPT technique and MRCC
MPPT technique for step change in irradiation level are shown
in Fig. 9 and Fig. 11 respectively. Fig. 10 shows the
relationship curve between PV power Ppv versus PV voltage
Vpv.
TABLE II
PARAMETERS OF THE PV INVERTER SYSTEM
Parameter Symbol Value
Grid voltage(rms),frequency
g g
f , V 10V,50Hz
Rated output current(rms)
g
I 6A
Nominal DC link voltage
dc
V 21.1V
DC link capacitor
dc
C 3300F
Grid side inductor
g
L 60H
Inverter side inductor
i
L 460H
Filter capacitor
d
C 2F
Filter damping resistor
d
R 1.5
Switching frequency
sw
f 20kHz
Proportional gain of current controller
pr
K 6
Resonant gain of current controller
ir
K 100
Damping ratio of current controller
0.01
Proportional gain of voltage controller
p
K 0.5
Integral gain of voltage controller
i
K 10
Filter time constant(sec) 0.05
The curve starts from the minimum PV power point (A)
initially and moves towards the maximum power point (B)
gradually as the MPPT algorithm starts varying the reference
voltage. Fig. 9(a), 9(b) and Fig. 11(a), 11(b) shows the
variation of the PV current and PV voltage respectively. The
curves starts from the initial point and moves towards PV
current and voltage values corresponding to maximum power
operating point current and voltage corresponding to
1000
2
W/m . At t=2s the irradiation level is changed abruptly
from 1000 to 600
2
W/m during which the operating point starts
shifting from point B to point C which corresponds to the
maximum power operating point for irradiation level of
600
2
W/m . The irradiation level is maintained constant at
600
2
W/m for duration of 1s and is reverted back to 1000
2
W/m ,
which cause the drift of operating from point C towards point
B again as shown in Fig .10. From Fig. 9(a), 9(b), 9(c) and Fig.
11(a), 11(b), 11(c) the main points that emerge out for the
comparative study are the transient tracking speed, tracking
accuracy, and ripple in the PV power at MPP. These
parameters are considered as the performance indices for the
RCC-MPPT and MRCC-MPPT, which are shown in Table III.
It is observed from the simulated performance that changes in
PV current and dc-link voltage are smooth during the change in
irradiation level which implies a satisfactory transient
performance for the system. It is seen from Fig. 12(a) and Fig.
12(b) that the line current is sinusoidal and in phase with the
line voltage, which implies that the grid connected PV system
is feeding only active power to the line. The line current
produces an almost unity power factor. The grid synchronizer
is immune to the grid disturbances which make the
performance of the grid synchronizer, current controller and
voltage controller with respect to the injected grid current
appreciable.
TABLE III
PERFORMANCE COMPARISON OF RCC-MPPT AND MRCC-MPPT FOR STEP
CHANGE IN IRRADIATION
MPPT
scheme
Tracking
time (sec)
Power
ripple near
MPP(watts)
Transient
tracking
speed
Accuracy
MRCC 0.2 59.8-59.1 Fast Accurate
RCC 0.45 59.7-59.65 Slow
Not so
accurate
Fig. 12(a) and (b) shows grid current transient response for
rapid change in irradiation level and periodic grid disturbances
such as harmonics in the grid voltage, frequency deviation. The
irradiation level is maintained constant at 1000
2
W/m till t=1s
with no disturbances in the grid. Irradiation level is decreased
at t=1.2s, after which the grid current takes a very small time to
settle to new maximum power operating current value. At
t=1.6s the grid voltage is distorted with a THD of 8%. Further
grid voltage is subjected to frequency deviation of 1 Hz with a
THD of 5% and finally irradiation level is increased to
1000
2
W/m at t=1.8s with grid frequency=50 Hz.
In all the above consequences the proposed control solution
meets the requirements of grid current harmonic distortion by
keeping the each current harmonic less than the specified
distortion level. Table IV shows the variation in %THD of grid
current for various grid disturbances and varying irradiation
levels. It can be seen that the grid current harmonic distortion
increases with the increase in the grid voltage distortion and
also with deviation in the grid frequency. The PV inverter
system exhibits fast transient and steady state response even
under rapidly changing irradiation levels maintaining the
sinusoidal grid current.
SCEECS 2014
Fig.8. Step change in Irradiation level.
Fig.9.(a) Current (Ipv) Waveform of PV module with RCC-MPPT.
Fig.9.(b) Voltage (Vpv) Waveform of PV module with RCC-MPPT.
Fig.9.(c) PV Power (Ppv ) Waveform of PV module with RCC-MPPT.
Fig.12.(a) Transient response of grid current.
Fig.10. PV Power Ppv versus Vpv for step change in Irradiation.
Fig.11.(a) Current (Ipv) Waveform of PV module with MRCC-MPPT.
Fig.11.(b) Voltage (Vpv) Waveform of PV module with MRCC-MPPT.
Fig.11.(c) PV Power(Ppv) Waveform of PV module with MRCC-MPPT.
Fig.12.(b) Transient response of grid current.
B
C
A
Irradiation (0.5KW/div)
Irradiation (1KW/m
2
)
Irradiation (0.5KW/m
2
)
Vpv (5V/div)
0.5s/div
Ipv (0.5A/div)
Ppv (10W/div)
Ipv (0.5A/div)
Vpv (5V/div)
Ppv (10W/div)
Igrid (5A/div) Vgrid (5V/div) Igrid (5A/div) Vgrid (5V/div)
0.5s/div
0.5s/div
0.5s/div
0.5s/div
0.5s/div
0.05s/div 0.05s/div
0.5s/div
SCEECS 2014
TABLE IV
%THD OF GRID CURRENT FOR VARIOUS GRID VOLTAGE DISTURBANCES
Irradiation
(
2
W/m )
Grid Frequency
(Hz)
%THD of
Grid
Voltage
%THD of
Grid current
1000
49 5 3.48
50 8 3.54
51 5 3.79
600
49 5 4.32
50 8 4.40
51 5 4.62
V. CONCLUSION
In this paper, design of controllers, LCL filter for a single-
phase grid connected inverter system are presented. By
employing unipolar switching scheme for the inverter with
LCL filter, the current injected into grid is sinusoidal and
ripple free. Further, LCL filter can provide good grid
synchronization without knowledge of grid impedance.
Performance comparison of MRCC-MPPT and RCC-MPPT
are done as applied to single-phase single-stage PV inverter.
From the results, it is guaranteed that MRCC algorithm results
in higher accuracy, faster response as compared to the RCC
algorithm for generating the MPP reference voltage. A low
complexity grid synchronization method ensures that the VSI
is well synchronized and the grid current is in phase with the
grid voltage even under grid disturbances ensuring unity power
factor operation of the inverter. Simulation results confirm the
effectiveness and feasibility of the developed control scheme
and algorithm.
ACKNOWLEDGMENT
The authors would like to thank the authorities of VNIT,
Nagpur for providing facilities to carry out the research work.
REFERENCES
[1] F. Blaabjerg, R. Teodorescu, M. Liserre, and A. V. Timbus,
Overview of Control and Grid Synchronization for Distributed
Power Generation Systems, IEEE Trans. Ind. Electron., vol.
53, no. 5, pp. 1398-1409, Oct. 2006.
[2] S. B. Kjaer, J. K. Pedesen., and F. Blaabjerg, A review of
single-phase grid-connected inverters for photovoltaic
modules, IEEE Trans. Ind. Appl., vol. 4, no. 5,pp. 1292-1306,
Oct. 2005.
[3] S. Jain and V. Agarwal, Comparison of the performance of
maximum power point tracking schemes applied to single-stage
grid-connected photovoltaic systems, IET Electr.Power Appl.,
vol. 1, no. 5, pp. 753-762,Feb. 2007.
[4] D. Casadei, G. Grandi, and C. Rossi, Single-Phase Single-
Stage Photovoltaic Generation System Based on a Ripple
Correlation Control Maximum Power Point Tracking, IEEE
Trans. Energy Convers., vol. 21, no. 2,pp. 562-568, Jun. 2006.
[5] C. Boonmee and Y. Kumsuwan, Modified Maximum Power
Point Tracking Based-on Ripple Correlation Control
Application for Single-Phase VSI Grid-Connected PV Systems,
in proc. IEEE ECTI-CON., pp. 1-6, 2013.
[6] D. Marani, T. N. Sowmya, and B. C. Babu, Comparative study
between unipolar and bipolar switching scheme with LCL filter
for single-phase grid connected inverter system, in proc. IEEE
SCEECS., pp. 1-4, 2012.
[7] R. Teodorescu, F. Blaabjerg, M. Liserre, and P. C. Loh,
Proportional-resonant controllers and filters for grid-connected
voltage-source converters, IEE Proc., pp. 750-762, Mar. 2006.
[8] G. Shen, X. Zhu, J. Zhang, and D. Xu, A New Feedback
Method for PR Current Control of LCL-Filter-Based Grid-
Connected Inverter, IEEE Trans. Ind. Electron., vol. 57, no. 6,
pp. 2033-2041, Jun. 2010.
[9] M. Castilla, J. Miret, J. Matas, L. Garca de Vicuna, and J. M.
Guerrero, Control Design Guidelines for Single-Phase Grid-
Connected Photovoltaic Inverters With Damped Resonant
Harmonic Compensators, IEEE Trans. Ind. Electron., vol. 56,
no. 11, pp. 4492-4501, Nov. 2009.
[10] A. DellAquila, M. Liserre, V. Monopoli, and P. Rotondo,
Overview of PI-Based Solutions for the Control of DC Buses
of a Single-Phase H-Bridge Multilevel Active Rectifier, IEEE
Trans. Ind. Appl., vol. 44, no. 3, pp. 857-866, Jun. 2008.
[11] X. Zong and P. W. Lehn, Reactive Power Control of Single
Phase Grid Tied Voltage Sourced Inverters for Residential PV
Application, in Proc. IEEE IECON., pp. 696-707, Oct. 2012.