Beruflich Dokumente
Kultur Dokumente
\
|
+
=
=
T
p
k
k k
kV V
d
o
273
293
760
by, given , density air of function a is where
d
k
d
0.70 0.75 0.80 0.85 0.90 0.95 1.0 1.05 1.10 1.15
k
0.72 0.77 0.82 0.86 0.91 0.95 1.0 1.05 1.09 1.12
Dr. MMY 2012
87
HIGH VOLTAGE TESTING TECHNIQUES HIGH VOLTAGE TESTING TECHNIQUES
I VAT I VAT I VATUTM UTM
4.0 DIAGNOSTIC TESTING OF INSULATION
The purpose of diagnostic testing is to estimate the importance
of any deterioration.
Diagnostic testing can use measurements of;
Non-electrical properties
Breakdown strength
Conductivity/Resistivity
Loss tangent
Partial discharges
Dr. MMY 2012
88
HIGH VOLTAGE TESTING TECHNIQUES HIGH VOLTAGE TESTING TECHNIQUES
I VAT I VAT I VATUTM UTM
Loss Tangent (tan o)
Figure 1.1
V
I
o
u
I
V
I
V R
p
C
p
I
R
I
C
I
C
I
o
u
I
R
V
Figure1.2 : Parallel model
tan =
I
I
R
C
o tan =
V / R
V C
p
p
o
e
tan =
1
C R
p p
o
e
Dr. MMY 2012
89
HIGH VOLTAGE TESTING TECHNIQUES HIGH VOLTAGE TESTING TECHNIQUES
I VAT I VAT I VATUTM UTM
I
V
R
V
C
R
s
C
s
V
V
R
V
C
I
V
o
u
Figure 1.3: Series model
R =
R
1 + C R
s
p
2
p
2
p
2
e
C = C +
1
C R
s p
2
p p
2
e
tan =
V
V
=
I R
I
1
C
R
C
s
s
o
e
tan o =eC
s
R
s
Dr. MMY 2012
90
HIGH VOLTAGE TESTING TECHNIQUES HIGH VOLTAGE TESTING TECHNIQUES
I VAT I VAT I VATUTM UTM
Measurement of tan o (dissipation factor), resistance and capacitance of
the sample are often made using a.c. bridges.
The commonbridge circuits used in power frequencyhigh voltages are:
Schering Bridge
Transformer ratio-arm
AC
A
B D
C
detector
Z
1
Z
2
Z
3
Z
4
Figure 2.1
At balanced condition
Z
1
Z
4
=Z
2
Z
3
Dr. MMY 2012
91
HIGH VOLTAGE TESTING TECHNIQUES HIGH VOLTAGE TESTING TECHNIQUES
I VAT I VAT I VATUTM UTM
The Schering Bridge
AC
C
r
R
3
C
2
R
4
C
4
Figure 2.2: Schering Bridge
(r - j / C)
R
1
j C
R +
1
j C
=
R
j C
4
4
4
4
3
2
e
e
e
e
r = R
C
C
and C = C
R
R
3
4
2
2
4
3
tan o =eC
4
R
4
Dr. MMY 2012
92
HIGH VOLTAGE TESTING TECHNIQUES HIGH VOLTAGE TESTING TECHNIQUES
I VAT I VAT I VATUTM UTM
The Transformer Ratio-arm Bridge
AC
A
B
C
D
N
1
N
2
I
1
I
2
detector
Z
1
Z
2
Figure 2.3: Transformer Ratio-ArmBridge
Z
Z
=
N
N
1
2
1
2
Dr. MMY 2012
93
HIGH VOLTAGE TESTING TECHNIQUES HIGH VOLTAGE TESTING TECHNIQUES
I VAT I VAT I VATUTM UTM
5.0 HIGH VOLTAGE TESTING OF ELECTRICAL APPARATUS
Impulse testing on transformer
According to BS 171: Part 3. Carried out at room temperature with the
transformer not energized.
Used standard impulse waveshapes. Full and chopped waves.
During the tests, impulse voltage and current are recorded.
Failure detection (Insulation failure)
A change in the waveshape of the voltage and current both before and
after the chopped waves have been applied.
The existing of acoustic noise.
Visual signs of flashover
Failure location : Voltage waveform propagation may provide clue to the
position of a breakdown.
Dr. MMY 2012
94
HIGH VOLTAGE TESTING TECHNIQUES HIGH VOLTAGE TESTING TECHNIQUES
I VAT I VAT I VATUTM UTM
Testing on switchgear or circuit breaker
According to BS 5227: Part 2, IEC 56.
Conducted in two conditions:
Circuit breaker closed (ON position)
Circuit breaker opened (OFF position)
15 negative and positive standard lightning impulse are applied.
Test on one phase, the other two phases and structure of the panel is
connected to earth.
Routine and Type test on cables
According to BS 923: Part 2, IEC 60-2, IEC 55-1, IEC 230 and BS 6480.
PD, Power frequency, conductor resistance, direct current and impulse
voltage tests.
Dr. MMY 2012
95
TRANSFORMER STANDARD
TESTING PROCEDURE
Routine Tests
Tests required for each individual
transformer such as resistance
measurements, voltage ratio and loss
measurement.
Dr. MMY 2012
96
TRANSFORMER STANDARD
TESTING PROCEDURE
Type- or design tests :
Conducted on a transformer which is
representative of other transformers to
demonstrate that these transformers
comply with specified requirements not
covered by routine tests, eg.
temperature rise test and lightning
impulse test.
97
TRANSFORMER STANDARD TRANSFORMER STANDARD
TESTING PROCEDURE TESTING PROCEDURE
Special- or other tests :
Tests other than type- or routine
tests agreed to by the
manufacturer and the purchaser,
eg.measurement of zero-sequence
impedance and sound level
measurement.
Dr. MMY 2012
98
Lightning Impulse Test
Low Low--frequency tests alone are not frequency tests alone are not
adequate to demonstrate the dielectric adequate to demonstrate the dielectric
strength of transformers. strength of transformers.
The impulse voltage stress imposed on The impulse voltage stress imposed on
windings by lightning phenomena can be windings by lightning phenomena can be
very different from the low frequency very different from the low frequency
voltage distribution. voltage distribution.
The lightning impulse test is performed The lightning impulse test is performed
to prove the transformers ability to to prove the transformers ability to
withstand transient voltages withstand transient voltages
Dr. MMY 2012
99
Lightning Impulse Test
The basic waveshapes have been defined The basic waveshapes have been defined
and the impulse voltage levels, referred to and the impulse voltage levels, referred to
as the basic lightning impulse insulation as the basic lightning impulse insulation
level (BIL), have been established for level (BIL), have been established for
respective standardized voltage classes. respective standardized voltage classes.
By defining amplitudes and waveshapes, By defining amplitudes and waveshapes,
however, a minimum impulse dielectric however, a minimum impulse dielectric
strength is established which the strength is established which the
transformer should meet. transformer should meet.
Dr. MMY 2012
Dr. MMY 2005 100
Lightning Impulse Test
-Test Waveshape
101
Lightning Impulse Test
- Test Connection
The voltage is applied to each The voltage is applied to each
line terminal in succession. line terminal in succession.
All other terminals shall All other terminals shall
nominally be earthed directly or nominally be earthed directly or
through low through low--ohmic current ohmic current
shunts. shunts.
Dr. MMY 2012
102
Lightning Impulse Test
- Test Connection
Dr. MMY 2012
103
Lightning Impulse Test
- Test Sequence
The test sequence consists of one
reference impulse(RW) at 60% of full
amplitude (FW):
1RW 50 -70% amplitude
1 FW 100 amplitude
1RCW 50-70% amplitude
2 CW 100% amplitude
2 FW 100% amplitude
Dr. MMY 2012
104
Lightning Impulse Test
- Failure Indications
Detection of faults at impulse testing
is based on comparison of voltage
and current records obtained at
reduced and full amplitudes
The two traces should have a perfect
match to constitute evidence that the
insulation has passed the test
Dr. MMY 2012
Dr. MMY 2005 105
HIGH VOLTAGE TESTING TECHNIQUES HIGH VOLTAGE TESTING TECHNIQUES
I VAT I VAT I VATUTM UTM
Dr. MMY 2005 106
TESTING ACTIVITIES AT IVAT TESTING ACTIVITIES AT IVAT
High voltage AC withstand test on 11
kV XLPE single core cable
(TOPLINK SDN BHD)
High voltage lightning impulse test on
cast resin transformer
(LKH POWER TRANSFORMER SDN BHD)
High voltage lightning impulse test on 11 kV switchgear
(MAHKOTA MANUFACTURING SDN BHD)
Dr. MMY 2005 107
TESTING ACTIVITIES AT IVAT TESTING ACTIVITIES AT IVAT
Impulse Withstand Test on 630 kVA,
11/0.433 kV (top) and
20 MVA, 33/11.5 kV (bottom) Three
Phase Power Transformer
(MALAYSIAN TRANSFORMER
MANUFACTURING SDN BHD)
Cable jointing works for preparation of
high voltage withstand test
(TOPLINK SDN BHD)