Beruflich Dokumente
Kultur Dokumente
QUADRANT 2200 RC
Technical Systems
Electric System
Electric System Quadrant 2200 TIC
TIC Quadrant 2200 Electric System
Layout of electric circuit All electric circuits are shown in individual circuit diagrams.
diagrams Some explanations are given below to illustrate the layout.
Potentials
Connections
- The description provided inside the circle (e.g. „H44”) defines the
connection.
- Numbers next to the circle (e.g. „1a”) describe the continuation of
the cabling in accordance with the circuit diagram numbering which
can The circuit diagram numbering be taken from the cover sheet or
from the footer.
Designations
A- Terminal / module
B- Sensor
E- Lighting
F- Fuse
G- Voltage source
H- Signalling device / lamp
K- Relays
M- Electric motor
P- Gauge
R- Potentiometer / resistor
S- Switches - Cab operation
T- Switches - Terminal operation
U- Switches - External operation
V- Electronic component
W- Antenna
X- Connector
Y- Solenoid coil
Z- Actual value function switch
Contents
01a - Main power supply (with central terminal compartment) ................................. 01a-2
01c - Main power supply (with CCU and Communicator) ........................................ 01c-2
06a - CAN bus, module power supply (with central terminal compartment)............. 06a-2
06b - CAN bus, module power supply (with CCU and CCT) .................................... 06b-2
06c - CAN bus, module power supply (with CCU and Communicator) .................... 06c-2
08c - Automatic cutting frame (with CCU and CCT) ................................................ 08c-2
11a - Wrapping release, knotter cleaning (with central terminal compartment) ........11a-2
11c - Wrapping release, knotter cleaning (with CCU and CCT) ...............................11c-2
Index ......................................................................................................................index-3
Electric System Quadrant 2200 TIC
Central terminal compartment (4 modules)
Electric System Quadrant 2200 TIC
! - Option
Module A20 -1
Module A20 -2
Module A20 -3
Module A20 -4
Description of function:
Main power supply During normal operation, power supply from the tractor to the baler is via
connector XV1. On the tractor, this power supply must be protected by a
25 A max. fuse (see wiring loom A).
Emergency operation After actuating emergency operation switch U5, the baler can be
operated in emergency operating mode without CCT terminal A30.
In emergency operating mode, power supply from the tractor may also be
via connector XV2.
For machine emergency operation see Operator's Manual.
- with CCU
Electric System Quadrant 2200 TIC
Description of function:
Main power supply Power supply from the tractor to the baler is via connector XV1. On the
tractor, this power supply must be protected by a 25 A max. fuse (see
wiring loom E).
Connector XV1
XT2 - 1 1.5 bk
XT2 - 2 1.5 bk-rd
XT2 - 3 1.5 br-rd
XT2 - 15 1.5 br
K 90 Relay ............................................................................Switchbox
Description of function:
Main power supply Power supply from the tractor to the baler is via connector XV.
Emergency operation After actuating emergency operation switch U5, the baler can be operated
in emergency operating mode without terminal A30.
Connector XT2
Interconnection list:
U5 - 1 0.5 br/wh
U5 - 2 0.5 rd
U5 - 3 1.5 bk
U5 - 5 1.5 br/rd
U5 - 6 1.5 br
XT1 - 3 0.5 bk
XT1 - 6 0.5 br
XT1 - 8 0.5 rd
XT1 - 9 0.5 bk
XT2 - 1 4 br
XT2 - 3 4 bk
XT2 - 6 0.5 rd
XT2 - 7 0.5 bk
XV1 - 15/30 4 bk
XV1 - 31 4 br
Master valve
Description of function:
Master valve To be able to build up the working pressure necessary for many hydraulic
control systems, the neutral hydraulic circulation must be blocked (see
chapter "Hydraulic system"). In this case, solenoid coil Y77 is actuated by
module A 20 -1 in parallel to the function.
Socket Y77
Y77 - 1 2.5 br
Y77 - 2 1.0 gr-ye
Master valve
- with CCU
Electric System Quadrant 2200 TIC
Description of function:
Master valve To be able to build up the working pressure necessary for many hydraulic
control systems, the neutral hydraulic circulation must be blocked (see
chapter "Hydraulic system"). In this case, solenoid coil Y77 is actuated by
module A 20 in parallel to the function.
Socket Y77
Terminal
Description of function:
Terminal
Description of function:
Terminal Buzzer H 44 is actuated from module A 20, in order to inform the driver
about the respective operating conditions and alarms.
06a - CAN bus, module power supply (with central terminal compartment)
Description of function:
The XD-1 and XD-2 sockets serve for diagnosis with the Claas diagnosis
system CDS.
The performance data (total number of bales, operating hours, ...) are
saved in modules A 20-1 to A 20-4.
Each module assumes a part of the baler functions (see diagram).
Module A 20 - 1 assumes the control.
Communication between the modules and with the CCT terminal A30 is via
the CAN bus.
! - Option
CAN bus Data exchange between electronic components via a serial network.
(Controller Area Network)
- Measured value table CAN high (Ueff) CAN low (Ueff) Diagnosis
CAN bus
2.52 V ± 0.1 V 2.49 V ± 0.1 V System OK
2.50 V 2.50 V Short circuit CAN high to CAN low
12 V >2.50 V Short circuit CAN high to +12 Volt
0V <2.5 V Short circuit CAN high to earth
>2.50 V 12 V Short circuit CAN low to +12 Volt
<2.50 V 0V Short circuit CAN low to earth
06b - CAN bus, module power supply (with CCU and CCT)
Description of function:
The XD connectors serve for diagnosis with the CDS Claas Diagnosis
system.
The performance data (total number of bales, operating hours, ...) are
saved in module A 20.
Communication between the module and the CCT terminal A30 is via the
CAN bus.
CAN bus Data exchange between electronic components via a serial network.
(Controller Area Network)
- Measured value table CAN high (Ueff) CAN low (Ueff) Diagnosis
CAN bus
2.52 V ± 0.1 V 2.49 V ± 0.1 V System OK
2.50 V 2.50 V Short circuit CAN high to CAN low
12 V >2.50 V Short circuit CAN high to +12 Volt
0V <2.5 V Short circuit CAN high to earth
>2.50 V 12 V Short circuit CAN low to +12 Volt
<2.50 V 0V Short circuit CAN low to earth
XD - 1 0.5 wh
XD - 2 0.75 wh
XD - 3 0.75 wh
XD - 4 0.5 wh-br
XD - 5 0.5 wh-bk
XD - 6 0.5 bk-rd
XD - 7 0.5 br-rd
06c - CAN bus, module power supply (with CCU and Communicator)
Description of function:
The XD connector serves for diagnosis with the CDS Claas Diagnosis
system.
The performance data (total number of bales, operating hours, ...) are
saved in module A 20. The CDS diagnosis system allows reading out these
data.
Communication of this module with terminal A30 is via the CAN bus.
CAN bus Data exchange between electronic components via a serial network.
(Controller Area Network)
- Measured value table CAN high (Ueff) CAN low (Ueff) Diagnosis
CAN bus
2.52 V ± 0.1 V 2.49 V ± 0.1 V System OK
2.50 V 2.50 V Short circuit CAN high to CAN low
12 V >2.50 V Short circuit CAN high to +12 Volt
0V <2.5 V Short circuit CAN high to earth
>2.50 V 12 V Short circuit CAN low to +12 Volt
<2.50 V 0V Short circuit CAN low to earth
Connector XT2
Interconnection list:
XD - 1 0.5 wh
XD - 2 0.5 wh
XD - 3 0.5 wh
XD - 4 0.5 gn
XD - 5 0.5 ye
XD - 6 1.5 bk
XD - 7 0.5 bk
XT1- 2 0.5 gn
XT1- 7 0.5 ye
XT2 - 8 0.5 ye
XT2 - 9 0.5 gn
X14 - 10 0.5 gn
X14 - 11 0.5 wh/bk
Rotocut
Description of function:
Rotor plugged When the rotor is plugged in automatic mode, the knives are moved out
(drive speed > 500 rpm), the cutting frame is possible opened, depending
on the configuration, and then closed (see "Rotor plugged" sequence
diagram, circuit diagram 8a).
Feed rake plugged In case of feed rake standstill, the rotor drive is additionally disconnected
via the solenoid Y 58 (see "Feed rake plugged" sequence diagram, circuit
diagram 8a).
Rotocut
- with CCU
Electric System Quadrant 2200 TIC
Description of function:
When the rotor is plugged in automatic mode, the knives are moved out
(drive speed > 500 rpm), the cutting frame is possible opened, depending
on the configuration, and then closed (see "Rotor plugged" sequence
diagram, circuit diagram 8c).
Y55- 1 0.75 br
Y55 - 2 0.75 bl-gn
Y63 - 1 0.75 br
Y63 - 2 0.75 rd-wh
Y64 - 1 0.75 br
Y64 - 2 0.75 gn-bl
08a - Automatic cutting frame (with central terminal compartment, with 5 V cutting frame position sensor)
Description of function:
The electronic unit monitors the following in order to control the automatic
functions:
- Drive speed
- Feed rake speed
- Rotor speed
- Knives IN position
- Opening angle of cutting frame
Rotor plugged When the rotor is plugged in automatic mode (drive speed > 500 rpm),
the knives are moved out, the cutting frame is possibly opened,
depending on the configuration, and then closed (see "Rotor plugged"
sequence diagram).
Feed rake plugged In case of feed rake standstill, the rotor drive is additionally disconnected
via the solenoid Y 58 (see "Feed rake plugged" sequence diagram).
Voltage regulator V15 The cutting frame position sensor B 67 is supplied with a 5 V voltage by
voltage regulator V 15.
Note: For cabling of the corresponding solenoid valves see circuit diagram 7a.
Sensor settings
(see also "Diagnosis"
chapter)
- Speed sensors The clearance between the magnetic pick-ups and the tooth top should
(B9, B23, B24) be approx. 0.75 mm.
At a drive speed of approx. 350 rpm, the speed values should be
displayed correctly in the service menu of terminal A30.
- HALL sensor (B67) The cutting frame angle is displayed in service menu 8/2 of terminal A30.
When the cutting frame is closed, the displayed value must be -2°.
- ROTOCUT knives IN Set the switch so that it can be pressed 5 mm max. A signal change (O-I)
actual value switch is displayed in service menu 8/2 of terminal A30.
(Z49)
Actuator settings
Step Action
Rotor standstill (with drive speed above 500 rpm) Rotor fault
Rotor coupling disengaged
until at least 2.5 s. after signal from Rotocut knives IN switch Z49
Cutting frame angle larger than 20° (10°), cutting fr. cyl. stroke approx. 100mm (50mm)
Reduce speed
Increase speed
10 Knives swing in
End
Step Action
Reduce speed
Increase speed
Feed rake must rotate for more than 6.5 s. at drive speed above 500 rpm.
until at least 2.5 s. min. after the signal from the Rotocut knives IN switch Z49
Cutting frame angle above 20° (10°), cutting fr. cyl. stroke approx. 100mm (50mm)
Reduce speed
Increase speed
10 Knives swing in
End
Y58 - 1 1.0 br
Y58 - 2 1.0 bk-gn
08b - Automatic cutting frame (with central terminal compartment, with 12 V cutting frame position sensor)
Description of function:
The electronic unit monitors the following in order to control the automatic
functions:
- Drive speed
- Feed rake speed
- Rotor speed
- Knives IN position
- Opening angle of cutting frame
Rotor plugged When the rotor is plugged in automatic mode (drive speed > 500 rpm),
the knives are moved out, the cutting frame is possibly opened,
depending on the configuration, and then closed (see "Rotor plugged"
sequence diagram).
Feed rake plugged In case of feed rake standstill, the rotor drive is additionally disconnected
via the solenoid Y 58 (see "Feed rake plugged" sequence diagram).
Note: For cabling of the corresponding solenoid valves see circuit diagram 7a.
Sensor settings
(see also "Diagnosis"
chapter)
- Speed sensors The clearance between the magnetic pick-ups and the tooth top should
(B9, B23, B24) be approx. 0.75 mm.
At a drive speed of approx. 350 rpm, the speed values should be
displayed correctly in the service menu of terminal A30.
- HALL sensor (B67) The cutting frame angle is displayed in service menu 8/2 of terminal A30.
When the cutting frame is closed, the displayed value must be -2°.
- ROTOCUT knives IN Set the switch so that it can be pressed 5 mm max. A signal change (O-I)
actual value switch is displayed in service menu 8/2 of terminal A30.
(Z49)
Actuator settings
Rotor standstill (with drive speed above 500 rpm) Rotor fault
Rotor coupling disengaged
until at least 2.5 s. after signal from Rotocut knives IN switch Z49
Cutting frame angle larger than 20° (10°), cutting fr. cyl. stroke approx. 100mm (50mm)
Reduce speed
Increase speed
10 Knives swing in
End
Step Action
Reduce speed
Increase speed
Feed rake must rotate for more than 6.5 s. at drive speed above 500 rpm.
until at least 2.5 s. min. after the signal from the Rotocut knives ON switch Z49
Cutting frame angle above 20° (10°), cutting fr. cyl. stroke approx. 100mm (50mm)
Reduce speed
Increase speed
10 Knives swing in
End
Y58 - 1 1.0 br
Y58 - 2 1.0 bk-gn
Description of function:
The electronic unit monitors the following in order to control the automatic
functions:
- Drive speed
- Feed rake speed
- Rotor speed
- Knives IN position
- Opening angle of cutting frame
Rotor plugged When the rotor is plugged in automatic mode (drive speed > 500 rpm),
the knives are moved out, the cutting frame is possibly opened,
depending on the configuration, and then closed (see "Rotor plugged"
sequence diagram).
Feed rake plugged In case of feed rake standstill, the rotor drive is additionally disconnected
via the solenoid Y 58 (see "Feed rake plugged" sequence diagram).
Note: For cabling of the corresponding solenoid valves see circuit diagram 7b.
Sensor settings
(see also "Diagnosis"
chapter)
- Speed sensors The clearance between the HALL sensors and the tooth top should be
(B9, B23, B24) approx. 1.5 ± 0.25 mm (Thread lead of sensors: 1 mm).
At a drive speed of approx. 350 rpm, the speed values should be
displayed correctly in the service menu of terminal A30.
- HALL sensor (B67) The cutting frame angle is displayed in service menu 8/2 of terminal A30.
When the cutting frame is closed, the displayed value must be -2°.
- ROTOCUT knives IN Set the switch so that it can be pressed 5 mm max. A signal change (O-I)
actual value switch is displayed in service menu 8/2 of terminal A30.
(Z49)
Actuator settings
Rotor standstill (with drive speed above 500 rpm) Rotor fault
Rotor coupling disengaged
until at least 2.5 s. after signal from Rotocut knives IN switch Z49
Cutting frame angle larger than 20° (10°), cutting fr. cyl. stroke approx. 100mm (50mm)
Reduce speed
Increase speed
10 Knives swing in
End
Reduce speed
Increase speed
Feed rake must rotate for more than 6.5 s. at drive speed above 500 rpm.
until at least 2.5 s. min. after the signal from the Rotocut knives IN switch Z49
Cutting frame angle above 20° (10°), cutting fr. cyl. stroke approx. 100mm (50mm)
Reduce speed
Increase speed
10 Knives swing in
End
Connector B9, B23, B24 Socket B9, B23, B24 Socket B67
B9 - 1 0.5 br-rd
B9 - 2 0.5 br-gr
B9 - 3 0.5 bk-rd
Y58 - 1 1.0 br
Y58 - 2 1.0 bk-gn
Description of function:
The electronic unit monitors the following in order to control the automatic
functions:
- Drive speed
- Feed rake speed
- Rotor speed
- Knives IN position
- Opening angle of cutting frame
Rotor plugged When the rotor is plugged in automatic mode (drive speed > 500 rpm), the
knives are moved out, the cutting frame is possibly opened, depending on
the configuration, and then closed (see "Rotor plugged" sequence
diagram).
Feed rake plugged In case of feed rake standstill, the rotor drive is additionally disconnected
via the solenoid Y 58 (see "Feed rake plugged" sequence diagram).
Note:
For cabling of the corresponding solenoid valves see circuit diagram 7b.
Sensor settings
(see also "Diagnosis"
chapter)
- Speed sensors The clearance between the HALL sensors and the tooth top should be
(B9, B23, B24) approx. 1.5 ± 0.25 mm (Thread lead of sensors: 1 mm).
At a drive speed of approx. 350 rpm, the speed values should be
displayed correctly in the CDS disgnosis system.
- HALL sensor (B67) The cutting frame angle can be read out using the CDS diagnosis system.
When the cutting frame is closed, the displayed value must be -2°.
Step Action
Rotor standstill (with drive speed above 500 rpm) Rotor fault
Rotor coupling disengaged
until at least 2.5 s. after signal from Rotocut knives IN switch Z49
Cutting frame angle larger than 20° (10°), cutting fr. cyl. stroke approx. 100mm (50mm)
Reduce speed
Increase speed
10 Knives swing in
End
Step Action
Reduce speed
Increase speed
Feed rake must rotate for more than 6.5 s. at drive speed above 500 rpm.
until at least 2.5 s. min. after the signal from the Rotocut knives IN switch Z49
Cutting frame angle above 20° (10°), cutting fr. cyl. stroke approx. 100mm (50mm)
Reduce speed
Increase speed
10 Knives swing in
End
Socket Z49
Interconnection list:
B9 - 1 0.5 br-rd
B9 - 2 0.5 br-gr
B9 - 3 0.5 bk-rd
Y58 - 1 1.0 br
Y58 - 2 1.0 bk-gn
Description of function:
Pressure control The set pressure of the baling chamber cylinders 334 is pre-selected in
terminal A 30, regulated by solenoid valves Y 50 / 51 and monitored by
sensor B 56 (see "Hydraulic system" chapter).
The master valve Y77 is connected in parallel with the solenoid valve
Y50 since pressure build-up within the system is required for this
function.
Baling pressure overload Activation of the baling pressure overload valve 610 due to excessive
friction forces in the baling chamber is recognized by the electronic unit
as a pressure drop at sensor B 56. This process generates the
„Overload“ error in terminal A 30. After a delay of approx. 6 seconds, the
pre-selected set pressure is built up again in the baling chamber
cylinders 334 (see "Hydraulic system" chapter).
Y50 - 1 0.75 br
Y50 - 2 1.0 bk-rd-wh
Y51 - 1 0.75 br
Y51 - 2 1.0 wh-gn
Description of function:
Pressure control The set pressure of the baling chamber cylinders 334 is pre-selected in
terminal A 30, regulated by solenoid valves Y 50 / 51 and monitored by
sensor B 56 (see "Hydraulic system" chapter).
The master valve Y77 is connected in parallel with the solenoid valve
Y50 since pressure build-up within the system is required for this
function.
Baling pressure overload Activation of the baling pressure overload valve 610 due to excessive
friction forces in the baling chamber is recognized by the electronic unit
as a pressure drop at sensor B 56. This process generates the
„Overload“ error in terminal A 30. After a delay of approx. 6 seconds, the
pre-selected set pressure is built up again in the baling chamber
cylinders 334 (see "Hydraulic system" chapter).
Y50 - 1 0.75 br
Y50 - 2 0.75 bk-rd-wh
Y51 - 1 0.75 br
Y51 - 2 0.75 wh-gn
Description of function:
Pressure control The set pressure of the baling chamber cylinders 334 is pre-selected in
terminal A 30, regulated by solenoid valves Y 50 / 51 and monitored by
sensor B 56 (see "Hydraulic system" chapter).
The master valve Y77 is connected in parallel with the solenoid valve Y50
since pressure build-up within the system is required for this function.
Baling pressure overload Activation of the baling pressure overload valve 610 due to excessive
friction forces in the baling chamber is recognized by the electronic unit as
a pressure drop at sensor B 56. This process generates the „Overload“
error in terminal A 30. After a delay of approx. 6 seconds, the pre-selected
set pressure is built up again in the baling chamber cylinders 334 (see
"Hydraulic system" chapter).
Interconnection list:
Y50 - 1 0.75 br
Y50 - 2 0.75 bk-rd-wh
Y51 - 1 0.75 br
Y51 - 2 0.75 wh-gn
Description of function:
Bale length The desired bale length is pre-selected in terminal A 30. The metering
wheel / bale length sensor B 69 detects the bale length. Both values are
compared in module A20-1. When they are identical, wrapping is
released.
Wrapping monitoring Generates the „Wrapping fault“ error in terminal A 30 if the wrapping
system monitoring switch Z 63 is actuated without a wrapping command
(from module A20-1) at a drive speed of > 500 rpm. Wrapping is now
electronically blocked (see Wrapping fault sequence diagram).
Knotter cleaning Depending on the blowing duration set in terminal A 30 and the time
needed for producing a bale, the knotter cleaning solenoid coil Y 31 is
activated by the electronic unit (see Knotter cleaning control table).
Knotter cleaning control Time between two Baling duration per Duration of blowing pulse
blowing pulses bale [ts in sec.]
[T in sec.] [B in sec.]
19 38 0.00
32 64 0.25
35 70 0.31
45 90 0.49
60 120 0.78
75 150 1.06
90 180 1.34
105 210 1.62
120 240 1.90
135 270 2.18
150 300 2.46
Sensor settings
(see "Diagnosis" chapter)
- Wrapping system Set the switch so it can be pressed 5 mm max. A signal change (O-I) is
monitoring actual displayed in service menu 8/1 of terminal A30.
value switch Z63
Step Action
20 Basic position (waiting)
yes
Does knotter shaft rotate ? Step 27:
(Wrapping system monitoring Wrapping fault
switch Z63 closes) Wrapping release locked
no
25
M1 - 31 1.0 br
M1 - 31b 1.0 br-bl
M1 - 53 1.0 br-bl
M1 - 53a 1.0 bk-wh
X14 - 4 1.5 br
X14 - 5 1.5 br
X14 - 6 1.5 br
X14- 7 1.5 bk-rd
X14 - 8 1.5 br-rd
X14 - 9 1.5 bk-wh
X14 - 12 0.5 br-bl
X14 - 21 0.5 br-ye
X14 - 22 0.5 bl-ye
X14 - 33 1.0 gn
X15 - 1 2.5 br
X15 - 3 0.5 br-rd
X15 - 4 0.5 bk-rd
X15 - 5 1.0 gn
X15 - 6 0.5 br-bl
X15 - 12 2.0 bk-wh
Y31 - 1 1.0 br
Y31 -2 1.0 ye-bk
Description of function:
Bale length The desired bale length is pre-selected in terminal A 30. The metering
wheel / bale length sensor B 69 detects the bale length. Both values are
compared in module A20-1. When they are identical, wrapping is
released.
Wrapping monitoring Generates the „Wrapping fault“ error in terminal A 30 if the wrapping
system monitoring switch Z 63 is actuated without a wrapping command
(from module A20-1) at a drive speed of > 500 rpm. Wrapping is now
electronically blocked (see Wrapping fault sequence diagram).
Knotter cleaning Depending on the blowing duration set in terminal A 30 and the time
needed for producing a bale, the knotter cleaning solenoid coil Y 31 is
activated by the electronic unit (see Knotter cleaning control table).
Sensor settings
(see "Diagnosis" chapter)
- Wrapping system Set the switch so it can be pressed 5 mm max. A signal change (O-I) is
monitoring actual displayed in service menu 8/1 of terminal A30.
value switch Z63
Step Action
20 Basic position (waiting)
yes
Does knotter shaft rotate ? Step 27:
(Wrapping system monitoring Wrapping fault
switch Z63 closes) Wrapping release locked
no
25
Socket Y 31 Socket Z 63
M1 - 31 1.0 br
M1 - 31b 1.0 br-bl
M1 - 53 1.0 br-bl
M1 - 53a 1.0 bk-wh
X14 - 4 1.5 br
X14 - 5 1.5 br
X14 - 6 1.5 br
X14- 7 1.5 bk-rd
X14 - 8 1.5 br-rd
X14 - 9 1.5 bk-wh
X14 - 12 0.5 br-bl
X14 - 21 0.5 br-ye
X14 - 22 0.5 bl-ye
X14 - 33 1.0 gn
X15 - 1 2.5 br
X15 - 3 0.5 br-rd
X15 - 4 0.5 bk-rd
X15 - 5 1.0 gn
X15 - 6 0.5 br-bl
X15 - 12 2.0 bk-wh
Y31- 1 1.0 br
Y31-2 1.0 ye-bk
Description of function:
Bale length The desired bale length is pre-selected in terminal A 30. The metering
wheel / bale length sensor B 69 detects the bale length. Both values are
compared in module A20. When they are identical, wrapping is released.
Wrapping monitoring Generates the „Wrapping fault“ error in terminal A 30 if the wrapping
system monitoring switch Z 63 is actuated without a wrapping command
(from module A20) at a drive speed of > 500 rpm. Wrapping is now
electronically blocked (see Wrapping fault sequence diagram).
Knotter cleaning Depending on the blowing duration set in terminal A 30 and the time
needed for producing a bale, the knotter cleaning solenoid coil Y 31 is
activated by the electronic unit (see Knotter cleaning control table).
Knotter cleaning control Time between two Baling duration per Duration of blowing pulse
blowing pulses bale [ts in sec.]
[T in sec.] [B in sec.]
19 38 0.00
32 64 0.25
35 70 0.31
45 90 0.49
60 120 0.78
75 150 1.06
90 180 1.34
105 210 1.62
120 240 1.90
135 270 2.18
150 300 2.46
Sensor settings
(see "Diagnosis" chapter)
- Wrapping system Set the switch so it can be pressed 5 mm max. A signal change (O-I) is
monitoring actual displayed in service menu 8/1 of terminal A30.
value switch Z63
Wrapping sequence and fault monitoring Q2200 with CCT and CCU ( 835 166.2 V4.0)
Step Action
20 Basic position (waiting)
yes
Does knotter shaft rotate ? Step 27:
(Wrapping system monitoring Wrapping fault
switch Z63 closes) Wrapping release locked
no
wait for 2s
yes
24
wait for 2s
yes
25
When a fault has occurred, steps 26, 27, 28 and 29 can be read out as follows:
1. Press plus key (to switch off the warning tone)
2. Press and hold the main menu, plus and minus keys at the same time (entry of service menu 8/1)
3. Read line P1 while keeping keys pressed.
The fault steps 27, 28 and 29 may be deleted using the minus key (back to step 20)
Socket Y 31 Socket Z 63
M1 - 31 1.0 br
M1 - 31b 1.0 br-bl
M1 - 53 1.0 br-bl
M1 - 53a 1.0 bk-wh
X14 - 4 1.5 br
X14 - 5 1.5 br
X14 - 6 1.5 br
X14- 7 1.5 bk-rd
X14 - 8 1.5 br-rd
X14 - 9 1.5 bk-wh
X14 - 12 0.5 br-bl
X14 - 21 0.5 br-ye
X14 - 22 0.5 bl-ye
X14 - 33 1.0 gn
X15 - 1 2.5 br
X15 - 3 0.5 br-rd
X15 - 4 0.5 bk-rd
X15 - 5 1.0 gn
X15 - 6 0.5 br-bl
X15 - 12 2.0 bk-wh
Y31- 1 1.0 br
Y31-2 1.0 ye-bk
- up to 2005 model
11d - Wrapping release, knotter cleaning (with CCU and Communicator) - up to 2005 model
Description of function:
Bale length The desired bale length is pre-selected in terminal A 30. The metering
wheel / bale length sensor B 69 detects the bale length. Both values are
compared in module A20. When they are identical, wrapping is released.
Wrapping monitoring Generates the „Wrapping fault“ error in terminal A 30 if the wrapping
system monitoring switch Z 63 is actuated without a wrapping command
(from module A20) at a drive speed of > 500 rpm. Wrapping is now
electronically blocked (see Wrapping fault sequence diagram).
Knotter cleaning Depending on the blowing duration set in terminal A 30 and the time
needed for producing a bale, the knotter cleaning solenoid coil Y 31 is
activated by the electronic unit (see Knotter cleaning control table).
Knotter cleaning control Time between two Baling duration per Duration of blowing pulse
blowing pulses bale [ts in sec.]
[T in sec.] [B in sec.]
19 38 0.00
32 64 0.25
35 70 0.31
45 90 0.49
60 120 0.78
75 150 1.06
90 180 1.34
105 210 1.62
120 240 1.90
135 270 2.18
150 300 2.46
Wrapping system Set the switch so it can be pressed 5 mm max. A signal change (O-I) is
monitoring actual value displayed in the CDS diagnosis system.
switch Z63
Wrapping sequence and fault monitoring Q2200 with CCU and Communicator
Step Action
20 Basic position (waiting)
yes
Does knotter shaft rotate ? Step 27:
(Wrapping system monitoring Wrapping fault
switch Z63 closes) Wrapping release locked
no
wait for 2s
yes
24
wait for 2s
yes
25
When a fault has occurred, steps 26, 27, 28 and 29 can be read out with the CDS diagnosis system.
The fault steps 27, 28 and 29 may be deleted by fault acknowledgement (back to step 20)
Interconnection list:
M1 - 31 1.0 br
M1 - 31b 1.0 br-bl
M1 - 53 1.0 br-bl
M1 - 53a 1.0 bk-wh
X14 - 4 1.5 br
X14 - 5 1.5 br
X14 - 6 1.5 br
X14- 7 1.5 bk-rd
X14 - 8 1.5 br-rd
X14 - 9 1.5 bk-wh
X14 - 12 0.5 br-bl
X14 - 21 0.5 br-ye
X14 - 22 0.5 bl-ye
X14 - 33 1.0 gn
X15 - 1 2.5 br
X15 - 3 0.5 br-rd
X15 - 4 0.5 bk-rd
X15 - 5 1.0 gn
X15 - 6 0.5 br-bl
X15 - 12 2.0 bk-wh
Y31- 1 1.0 br
Y31-2 1.0 ye-bk
11e - Wrapping release, knotter cleaning (with CCU and Communicator) – from 2005 model
Description of function:
Bale length The desired bale length is pre-selected in terminal A 30. The Metering
wheel / Bale length sensor B69 detects the bale length. Both values are
compared in module A20. Wrapping is released if the values are identical.
Wrapping monitoring Generates the “Wrapping fault” error in terminal A 30 if at a drive speed >
500 rpm, the wrapping system monitoring switch Z63 is actuated without a
wrapping command (from module A 20). After this, the wrapping is
electronically locked.
(see net wrapping fault diagram).
Knotter cleaning As a function of the blowing duration set in terminal A 30 and the time
needed for producing a bale, the knotter cleaning solenoid coil Y 31 is
controlled by the electronic unit.
(see knotter cleaning control table)
Knotter cleaning control Time between two Baling duration per Duration of blowing pulse
blowing pulses bale [ts in sec.]
[T in sec.] [B in sec.]
19 38 0.00
32 64 0.25
35 70 0.31
45 90 0.49
60 120 0.78
75 150 1.06
90 180 1.34
105 210 1.62
120 240 1.90
135 270 2.18
150 300 2.46
Wrapping system Set the switch so that it can be pushed by 5 mm max. The signal change
monitoring actual value (O-I) is displayed in the CDS diagnosis system.
switch Z63
Wrapping sequence and fault monitoring Q2200 with CCU and Communicator
Step Action
20 Basic position (waiting)
yes
Does knotter shaft rotate ? Step 27:
(Wrapping system monitoring Wrapping fault
switch Z63 closes) Wrapping release locked
no
wait for 2s
yes
24
wait for 2s
yes
25
When a fault has occurred, steps 26, 27, 28 and 29 can be read out with the CDS diagnosis system.
The fault steps 27, 28 and 29 may be deleted by fault acknowledgement (back to step 20)
Interconnection list:
M1 - 31 2.5 br
M1 - 31b 2.5 br-bl
M1 - 53 1.0 br-bl
M1 - 53a 1.0 bk-wh
X14 - 4 1.5 br
X14 - 5 1.5 br
X14 - 6 1.5 br
X14 - 7 1.5 bk-rd
X14 - 8 1.5 br-rd
X14 - 9 1.5 bk-wh
X14 - 12 0.5 br-bl
X14 - 21 0.5 br-ye
X14 - 22 0.5 bl-ye
X14 - 33 1.0 gn
X15 - 1 2.5 br
X15 - 3 0.5 br-rd
X15 - 4 0.5 bk-rd
X15 - 5 1.0 gn
X15 - 6 0.5 br-bl
X15 - 12 2,0 bk-wh
Y31 - 1 1.0 br
Y31 - 2 1.0 ye-bk
Eject bale
Description of function:
Ejecting bales To actuate the bale ejector cylinder (307), either switch U1 or switch U2
(Extend / retract bale ejector) must be actuated. Module A20-2 energizes
the corresponding solenoid valve Y11/ Y12 (Extend / retract bale ejector).
In parallel with this process, the master valve Y77 is actuated since
pressure build-up in the system is required for these functions.
Bale length The bale length determined by the metering wheel upon bale ejection is
saved in module A20-2, but not directly displayed in terminal A30.
In the next use, the saved value is added to the following bale and will
then be displayed in terminal A30. This value remains saved even after
switching off terminal A30.
Socket Y11, 12
Eject bale
Description of function:
Ejecting bales To actuate the bale ejector cylinder (307), either switch U1 or switch U2
(Extend / retract bale ejector) must be actuated. Module A20 energizes
the corresponding solenoid valve Y11/ Y12 (Extend / retract bale ejector).
In parallel with this process, the master valve Y77 is actuated since
pressure build-up in the system is required for these functions.
Bale length The bale length determined by the metering wheel upon bale ejection is
saved in module A20, but not directly displayed in terminal A30.
In the next use, the saved value is added to the following bale and will
then be displayed in terminal A30. This value remains saved even after
switching off terminal A30.
Socket U1, U2
Y11 - 1 0.75 br
Y11 - 2 0.75 gn-rd
Y12 - 1 0.75 br
Y12 - 2 0.75 ye-bk
Eject bale
Description of function:
Ejecting bales To actuate the bale ejector cylinder (307), either switch U1 or switch U2
(Extend / retract bale ejector) must be actuated. Module A20 energizes
the corresponding solenoid valve Y11/ Y12 (Extend / retract bale ejector).
In parallel with this process, the master valve Y77 is actuated since
pressure build-up in the system is required for these functions.
Bale length The bale length determined by the metering wheel upon bale ejection is
saved in module A20, but not directly displayed in terminal A30.
In the next use, the saved value is added to the following bale and will
then be displayed in terminal A30. This value remains saved even after
switching off terminal A30.
Interconnection list:
Y11 - 1 0.75 br
Y11 - 2 0.75 gn-rd
Y12 - 1 0.75 br
Y12 - 2 0.75 ye-bk
Machine monitoring
(twine break, flywheel brake)
Description of function:
Twine break monitoring Upon actuation of the twine break left / right switch Z11, an earth signal is
connected to module A20-1. The fault is displayed in terminal A 30.
Flywheel brake monitoring Upon actuation of the flywheel brake switch Z 56 an earth signal is
connected to module A20-2. The fault is displayed in terminal A 30.
Socket Z56
Machine monitoring
(twine break, flywheel brake)
Description of function:
Twine break monitoring Upon actuation of the twine break left / right switch Z11, an earth signal is
connected to module A20. The fault is displayed in terminal A 30.
Flywheel brake monitoring Upon actuation of the flywheel brake switch Z 56 an earth signal is
connected to module A20. The fault is displayed in terminal A 30.
Socket Z56
Machine monitoring
(twine break, flywheel brake)
Description of function:
Twine break monitoring Upon actuation of the twine break left / right switch Z11, an earth signal is
connected to module A20. The fault is displayed in terminal A 30.
Flywheel brake monitoring Upon actuation of the flywheel brake switch Z 56 an earth signal is
connected to module A20. The fault is displayed in terminal A 30.
Socket Z56
Interconnection list:
Operating displays
(bale discharge, baling ram load indicator,
crop moisture)
Description of function:
Moisture monitoring According to the measured resistance of the crop at the sensor, crop
moisture sensor B 38 transmits a frequency signal to module A20-4. This
value is displayed in terminal A 30.
Baling ram left / right load The measured values of the baling ram load indicator are detected by the
indicator inductive baling ram load indicator proximity sensors B57 / B58.
During the baling process, the change of distance between the main
drive crank arms and the baling ram load indicator sensors B57 / B58 is
measured and transmitted as a signal into module A20-2. This signal is
displayed in terminal A30 as a bar chart. This allows the operator to
achieve optimum baler filling.
Baling ram load indicator The baling ram load indicator sensors B57 / B58 must be set to a
sensor adjustment distance of approx. 4 mm from the ram crank arms.
Fine adjustment should be carried out by measuring the signal voltage of
the sensors. Adjust the sensors so that the signal voltage from the
sensors into the module A20-2 is approx. 70 - 400 mV.
When the adjustment is complete, the baling ram sensors B57 / B58
must be balanced (run empty baler at nominal speed, push "Sub-menu"
key and „Plus key” on terminal A30 at the same time).
Bale discharge monitoring When the finished bale leaves the bale chute, the bale discharge sensor
B101 transmits a signal to module A20-2. This process is displayed in
terminal A30.
Operating displays
(bale discharge, baling ram load indicator,
crop moisture)
Description of function:
Moisture monitoring According to the measured resistance of the crop at the sensor, crop
moisture sensor B 38 transmits a frequency signal to module A20. This
value is displayed in terminal A 30.
Baling ram left / right load The measured values of the baling ram load indicator are detected by the
indicator inductive baling ram load indicator proximity sensors B57 / B58.
During the baling process, the change of distance between the main
drive crank arms and the baling ram load indicator sensors B57 / B58 is
measured and transmitted as a signal into module A20. This signal is
displayed in terminal A30 as a bar chart. This allows the operator to
achieve optimum baler filling.
Baling ram load indicator The baling ram load indicator sensors B57 / B58 must be set to a
sensor adjustment distance of approx. 4 mm from the ram crank arms.
Fine adjustment should be carried out by measuring the signal voltage of
the sensors. Adjust the sensors so that the signal voltage from the
sensors into the module A20 is approx. 70 - 400 mV.
When the adjustment is complete, the baling ram sensors B57 / B58
must be balanced (run empty baler at nominal speed, push "Sub-menu"
key and „Plus key” on terminal A30 at the same time).
Bale discharge monitoring When the finished bale leaves the bale chute, the bale discharge sensor
B101 transmits a signal to module A20. This process is displayed in
terminal A30.
Operating displays
Bale discharge, baling ram load indicator,
crop moisture
Description of function:
Moisture monitoring According to the measured resistance of the crop at the sensor, crop
moisture sensor B 38 transmits a frequency signal to module A20. This
value is displayed in terminal A 30.
Baling ram left / right load The measured values of the baling ram load indicator are detected by the
indicator inductive baling ram load indicator proximity sensors B57 / B58.
During the baling process, the change of distance between the main drive
crank arms and the baling ram load indicator sensors B57 / B58 is
measured and transmitted as a signal into module A20. This signal is
displayed in terminal A30 as a bar chart. This allows the operator to
achieve optimum baler filling.
Baling ram load indicator The baling ram load indicator sensors B57 / B58 must be set to a distance
sensor adjustment of approx. 4 mm from the ram crank arms.
Fine adjustment should be carried out by measuring the signal voltage of
the sensors. Adjust the sensors so that the signal voltage from the
sensors into the module A20 is approx. 70 - 400 mV.
Bale discharge monitoring When the finished bale leaves the bale chute, the bale discharge sensor
B101 transmits a signal to module A20. This process is displayed in
terminal A30.
Socket Z56
Interconnection list:
Description of function:
Automatic central At a drive speed of > 500 rpm, the automatic lubrication system is
lubrication system activated by module A20-2 according to the programmed lubricating and
pre-set interval periods. The operating status is displayed in terminal
A30.
Socket M25
- with CCU
Electric System Quadrant 2200 TIC
Description of function:
Automatic central At a drive speed of > 500 rpm, the automatic lubrication system is
lubrication system activated by module A20 according to the programmed lubricating and
pre-set interval periods. The operating status is displayed in terminal
A30.
Socket M25
Socket X25
Additional sockets
X15 - 1 2.5 br
X15 - 2 2.5 bk
X20 - 1 4.0 br
X20 - 2 4.0 bk
XS - 1 1.0 bk
XS - 2 2.5 br
Additional sockets
- with CCU
Electric System Quadrant 2200 TIC
X15 - 1 2.5 br
X15 - 2 2.5 bk
XS - 1 1.0 bk
XS - 2 2.5 br
Key to diagram: B57 Baling ram left load indicator sensor ................................... 27a
B58 Baling ram right load indicator sensor ................................ 27a
X13 Connector............................................................................... 7a
X16 Connector............................................................................... 8a
X21 Connector .............................................................................. 7a
X22 Connector .............................................................................. 7a
X23 Connector............................................................................. 13a
X16 Connector............................................................................... 8a
A Acoustic warning 5
Additional sockets 40
B Bale chute 27
Bale discharge 27
Bale ejector 13
Bale length / metering wheel 11
Bale ramp 13
Baling pressure 10
Baling ram load indicator 27
Brake light 32
Buzzer 11
C CAN bus 6
Central lubrication system 29
Central lubrication system motor 29
Communicator 1, 6
Crop humidity 27
Cutting frame 8
D Diagnosis plug 6
Diode 1, 11
E Electronics earth 6
Electronics plus 6
F Feed rake 8
Flywheel brake 26
H Horn 5
Humidity sensor 27
K Knives In/Out 7
Knotter blowing valve 11
Knotter cleaning 11
L Left/right display 27
M Machine monitoring 26
Main power supply 1
Main switch 1
Master valve 4
Metering wheel 11
Metering wheel / Bale length 11
Module power supply 6
Modules 6
O Operating displays 27
P Pick-up 20
Pin assignment in modules ZE
Pressure sensor 10
R Ramp 27
Reverse polarity protection (diode) 1, 12
ROTOCUT 7, 8
ROTOCUT knives In 8
Rotor 8
Rotor lock solenoid 8
Rotor stop solenoid 8
S Sensor drive 8
Service socket outlet 40
Side light 32
Sockets (additional) 40
Speed sensor 8
Steering axle lock 28
T Taillight 32
Terminal 5
Terminating resistor 6
Turn flasher system 32
Twine 26
Twine break 26
Twine monitoring 26
V Voltage controller 8
W Wrapping release 11
Wrapping release motor 11
Wrapping system monitoring 11
0299 250.2
SYS-E QUADRANT 2200/2200RC
EN - 04.05 - NF
Printed in Germany