RULES FOR

CLASSIFICATION OF
DET NORSKE VERITAS
Veritasveien 1, N-1322 Hvik, Norway Tel.: +47 67 57 99 00 Fax: +47 67 57 99 11
SHIPS
NEWBUILDINGS
MACHINERY AND SYSTEMS
MAIN CLASS
PART 4 CHAPTER 10
FIRE SAFETY
JANUARY 2001
CONTENTS PAGE
Sec. 1 General Requirements ................................................................................................................ 5
Sec. 2 Fire Pumps and Fire Main ......................................................................................................... 9
Sec. 3 Fixed Gas Fire Extinguishing System ..................................................................................... 13
Sec. 4 Fire Extinguishers .................................................................................................................... 18
Sec. 5 Fire Extinguishing Arrangement in Machinery Spaces ........................................................... 19
Sec. 6 Fixed Foam and Pressure Water Spraying Fire Extinguishing Systems .................................. 21
Sec. 7 Special Arrangements in Machinery Spaces ........................................................................... 24
Sec. 8 Automatic Sprinkler, Fire Detection and Fire Alarm Systems ............................................... 25
Sec. 9 Fixed Fire Detection and Fire Alarm Systems ........................................................................ 27
Sec. 10 Ventilation Systems ................................................................................................................. 30
Sec. 11 Fireman's Outfit ....................................................................................................................... 32
Sec. 12 Miscellaneous Items ................................................................................................................. 33
Sec. 13 Arrangement for Helicopter Decks .......................................................................................... 34
Sec. 14 Fire Control Plans and Drills ................................................................................................... 35
Sec. 15 Fire Safety Measures for Cargo Ships ..................................................................................... 36
Sec. 16 Fire Safety Measures for Cargo Ships less than 500 Gross Tonnage ...................................... 42
Sec. 17 Fire Safety Measures for Fishing Vessels ............................................................................... 43
CHANGES IN THE RULES
Comments to the rules may be sent by e-mail to rules@dnv.com
For subscription orders or information about subscription terms, please use distribution@dnv.com
Comprehensive information about DNV and the Society's services is found at the Web site http://www.dnv.com
Det Norske Veritas
Computer Typesetting (FM+SGML) by Det Norske Veritas
Printed in Norway by GCS AS.
If any person suffers loss or damage which is proved to have been caused by any negligent act or omission of Det Norske Veritas, then Det Norske Veritas shall pay compensation to such person
for his proved direct loss or damage. However, the compensation shall not exceed an amount equal to ten times the fee charged for the service in question, provided that the maximum compen-
sation shall never exceed USD 2 million.
In this provision "Det Norske Veritas" shall mean the Foundation Det Norske Veritas as well as all its subsidiaries, directors, officers, employees, agents and any other acting on behalf of Det
Norske Veritas.
General
The present edition of the rules includes additions and amendments
decided by the Board as of December 2000 and June 2001, and super-
sedes the July 1998 edition of the same chapter.
The rule changes come into force 1 January 2002.
This chapter is valid until superseded by a revised chapter. Supple-
ments will not be issued except for an updated list of minor amend-
ments and corrections presented in Pt.0 Ch.1 Sec.3. Pt.0 Ch.1 is
normally revised in January and July each year.
Revised chapters will be forwarded to all subscribers to the rules.
Buyers of reprints are advised to check the updated list of rule chap-
ters printed Pt.0 Ch.1 Sec.1 to ensure that the chapter is current.
Main changes
General
The New Machinery Project called for restructuring of the ma-
chinery chapters in Pt.4. As a result of this restructuring, Ch.6 has
been renumbered to read Ch.10.
The amendments are based on updated requirements adopted by
IMO and IACS.
Sec.1 General Requirements
Items A104 and C206 have been added. Previous items C206 to
C209 have been renumbered C207 to C210.
Sec.2 Fire Pumps and Fire Main
Item B204 has been expanded with IACS UI SC23 and item
B208 has been added.
Items C201 and C401 have been expanded.
Sec.3 Fixed Gas Fire Extinguishing System
Item A206, A213, A214 and B305 have been expanded.
Sec.4 Fire Extinguishers
Item A103 has been expanded.
Sec.5 Fire Extinguishing Arrangement in Machinery Spaces
Item A101 has been expanded with a Guidance note.
Sec.11 Fireman's Outfit
Item A101 has been expanded.
Sec.12 Miscellaneous Items
Item A801 has been expanded with a Guidance note.
Sec.13 Arrangement for Helicopter Decks
Previous item A103 on requirements from national authority has
been deleted.
Sec.15 Fire Safety Measures for Cargo Ships
Item B604 has been expanded to cover that watertight doors are
to be made of steel.
Item B802 has been expanded with IACS UI SC127.
Sec.16 Fire Safety Measures for Cargo Ships less than 500
Gross Tonnage
Item B401 has been expanded.
Corrections and Clarifications
In addition to the above stated rule amendments, some detected errors
have been corrected, and some clarifications have been made in the
existing rule wording.
Rules for Ships, January 2001
Pt.4 Ch.10 Contents Page 3
DET NORSKE VERITAS
CONTENTS
SEC. 1 GENERAL REQUIREMENTS .......................... 5
A. Scope.......................................................................................5
A 100 Adopted International Maritime Standards.......................5
B. Classification..........................................................................5
B 100 Application........................................................................5
B 200 Rule references..................................................................5
C. Definitions ..............................................................................5
C 100 Ship type definitions and size ...........................................5
C 200 Fire technical definitions...................................................5
C 300 Space definitions...............................................................6
C 400 Definitions on equipment, control stations and
hydrostatic terms..............................................................7
C 500 System definitions.............................................................7
D. Documentation ......................................................................7
D 100 Plans and particulars .........................................................7
SEC. 2 FIRE PUMPS AND FIRE MAIN ...................... 9
A. General...................................................................................9
A 100 Application .......................................................................9
B. Fire Pumps.............................................................................9
B 100 Capacity of fire pumps......................................................9
B 200 Arrangement and number of fire pumps...........................9
C. Water Distribution System.................................................11
C 100 Diameter of and pressure in the fire mains .....................11
C 200 Number and position of hydrants....................................11
C 300 Pipes and hydrants ..........................................................11
C 400 Fire hoses ........................................................................11
C 500 Nozzles............................................................................12
C 600 International shore connection........................................12
C 700 Pump arrangement for other fire systems .......................12
SEC. 3 FIXED GAS FIRE EXTINGUISHING
SYSTEM ............................................................. 13
A. General.................................................................................13
A 100 Application......................................................................13
A 200 General requirements ......................................................13
B. Carbon Dioxide Systems.....................................................14
B 100 General requirements for CO
2
fire extinguishing
systems ............................................................................14
B 200 CO
2
fire extinguishing systems for cargo holds .............14
B 300 CO
2
high pressure fire extinguishing systems for
machinery spaces ............................................................14
C. Low Pressure CO
2
Systems................................................15
C 100 General ............................................................................15
C 200 Vessels and relevant devices...........................................15
C 300 Refrigerating plant ..........................................................16
C 400 Pipes and fittings.............................................................16
C 500 Control of smothering system operation.........................16
C 600 Release control................................................................16
C 700 Testing.............................................................................16
D. Halogenated Hydrocarbon Systems ..................................16
D 100 Application......................................................................16
E. Steam Systems .....................................................................16
E 100 General ............................................................................16
F. Other Gas Systems..............................................................17
F 100 General ............................................................................17
SEC. 4 FIRE EXTINGUISHERS ................................. 18
A. General.................................................................................18
A 100 General requirements for all extinguishers .....................18
B. Portable Foam Applicator................................................. 18
B 100 Definition........................................................................ 18
B 200 Requirement.................................................................... 18
C. Portable Fire Extinguishers in Accommodation, Service
Spaces and Control Stations.............................................. 18
C 100 Requirement.................................................................... 18
D. Fire Extinguishers in Machinery Spaces ......................... 18
D 100 Requirement.................................................................... 18
SEC. 5 FIRE EXTINGUISHING ARRANGEMENT IN
MACHINERY SPACES ................................... 19
A. Spaces Containing Oil-fired Boilers or Oil Fuel Units ... 19
A 100 General ............................................................................19
B. Spaces Containing Internal Combustion Machinery ..... 19
B 100 General ............................................................................19
C. Spaces Containing Both Oil Fired Boilers and Internal
Combustion Machinery ..................................................... 19
C 100 General ............................................................................19
D. Spaces Containing Steam Turbines or Other Enclosed
Steam Engines .................................................................... 19
D 100 General ............................................................................19
E. Fire-extinguishing Appliances in other Machinery
Spaces .................................................................................. 19
E 100 General ............................................................................19
F. Fixed Fire-extinguishing Systems not required by this
Chapter................................................................................ 20
F 100 General ............................................................................20
G. Machinery Spaces of Category A in Passenger Ships..... 20
G 100 Fixed fire-extinguishing systems .................................... 20
G 200 Fire-extinguishing appliances ......................................... 20
SEC. 6 FIXED FOAM AND PRESSURE WATER
SPRAYING FIRE EXTINGUISHING
SYSTEMS ........................................................... 21
A. General ............................................................................... 21
A 100 Application......................................................................21
B. Fixed Low-Expansion Foam Fire - Extinguishing Systems
in Machinery Spaces .......................................................... 21
B 100 General ............................................................................21
C. Fixed High-Expansion Foam Fire - Extinguishing Systems
in Machinery Spaces .......................................................... 21
C 100 General ............................................................................21
C 200 Arrangement ...................................................................21
C 300 Capacity .......................................................................... 22
C 400 Foam generator ............................................................... 22
C 500 Foam generator room......................................................22
D. Pressure Water-Spraying Systems in Machinery Spaces22
D 100 General ............................................................................22
E. Pressure Water Spraying Systems for Special Category
Spaces in Passenger Ships ................................................. 22
E 100 General ............................................................................22
SEC. 7 SPECIAL ARRANGEMENTS IN
MACHINERY SPACES ................................... 24
A. General ................................................................................ 24
A 100 Application......................................................................24
A 200 General requirements ......................................................24
Rules for Ships, January 2001
Pt.4 Ch.10 Contents Page 4
DET NORSKE VERITAS
SEC. 8 AUTOMATIC SPRINKLER, FIRE
DETECTION AND FIRE ALARM
SYSTEMS ........................................................... 25
A. General ................................................................................ 25
A 100 Application......................................................................25
A 200 General ............................................................................25
A 300 Arrangement....................................................................25
A 400 Capacity ..........................................................................25
A 500 Pumps and piping system................................................25
A 600 Power sources .................................................................25
A 700 Testing.............................................................................26
SEC. 9 FIXED FIRE DETECTION AND FIRE ALARM
SYSTEMS ........................................................... 27
A. Fire Detection and Fire Alarm Systems ........................... 27
A 100 General ............................................................................27
A 200 Installation.......................................................................28
A 300 Design .............................................................................28
B. Sample Extraction Smoke Detection Systems.................. 28
B 100 General ............................................................................28
B 200 Installation.......................................................................28
B 300 Design .............................................................................29
SEC. 10 VENTILATION SYSTEMS ............................. 30
A. General ................................................................................ 30
A 100 General requirements ......................................................30
SEC. 11 FIREMAN'S OUTFIT ...................................... 32
A. General ................................................................................ 32
A 100 Extent of outfit ................................................................32
A 200 Number of outfits ............................................................32
SEC. 12 MISCELLANEOUS ITEMS............................. 33
A. General ................................................................................ 33
A 100 Division penetrations ......................................................33
A 200 Pipe materials ..................................................................33
A 300 Electric radiators .............................................................33
A 400 Cellulose-nitrate based films...........................................33
A 500 Waste-receptacles............................................................33
A 600 Insulation surface ............................................................33
A 700 Paint lockers and flammable liquid lockers ....................33
A 800 Seismic cables containing flammable liquids .................33
A 900 Use of asbestos................................................................33
SEC. 13 ARRANGEMENT FOR HELICOPTER
DECKS................................................................. 34
A. General ................................................................................ 34
A 100 Arrangement....................................................................34
SEC. 14 FIRE CONTROL PLANS AND DRILLS ....... 35
A. General ................................................................................ 35
A 100 Fire control plans ............................................................35
A 200 Maintenance and operation instructions .........................35
A 300 Plans outside deckhouse..................................................35
A 400 Fire drills .........................................................................35
SEC. 15 FIRE SAFETY MEASURES FOR CARGO
SHIPS .................................................................. 36
A. General................................................................................. 36
A 100 Application......................................................................36
A 200 Rule references................................................................36
B. Fire Protection and Means of Escape ............................... 36
B 100 Structure ..........................................................................36
B 200 Bulkheads within the accommodation and service
spaces .............................................................................36
B 300 Fire integrity of bulkheads and decks .............................36
B 400 Means of escape ..............................................................38
B 500 Protection of stairways and lift trunks in accommodation
spaces, service spaces and control stations .....................39
B 600 Doors in fire resisting divisions ......................................39
B 700 Ventilation systems .........................................................39
B 800 Restricted use of combustible materials..........................39
B 900 Details of construction ....................................................39
C. Arrangements for Gaseous Fuel for Domestic Purposes 40
C 100 General ............................................................................40
D. Fixed Fire Detection and Fire Alarm Systems. Automatic
Sprinkler, Fire Detection and Fire Alarm Systems ......... 40
D 100 General ............................................................................40
E. Fire Protection Arrangements in Cargo Spaces .............. 40
E 100 General ............................................................................40
E 200 Ro-ro cargo spaces ..........................................................40
E 300 Cargo spaces, other than ro-ro cargo spaces, intended for
the carriage of motor vehicles .........................................41
SEC. 16 FIRE SAFETY MEASURES FOR CARGO
SHIPS LESS THAN 500 GROSS TONNAGE 42
A. General................................................................................. 42
A 100 Application......................................................................42
B. Fire Extinction .................................................................... 42
B 100 Fire pumps.......................................................................42
B 200 Water distribution system ...............................................42
B 300 Portable fire extinguishers ..............................................42
B 400 Non-portable fire extinguishers ......................................42
B 500 Fireman's outfit ...............................................................42
SEC. 17 FIRE SAFETY MEASURES FOR FISHING
VESSELS ............................................................ 43
A. General................................................................................. 43
A 100 Application......................................................................43
B. Fire Safety Measures .......................................................... 43
B 100 Fire pumps and water distribution system ......................43
B 200 Fire safety arrangements in machinery spaces................43
B 300 Fireman's outfit ...............................................................43
B 400 Fire protection of bulkheads and decks...........................43
B 500 Portable fire extinguishers ..............................................43
Rules for Ships, January 2001
Pt.4 Ch.10 Sec.1 Page 5
DET NORSKE VERITAS
SECTION 1
GENERAL REQUIREMENTS
A. Scope
A 100 Adopted International Maritime Standards
101 The requirements of this chapter cover the fire technical
regulations of SOLAS 74 Chapter II-2 including later amend-
ments as in force per 1 July 1998.
The International Association of Classification Societies'
(IACS) interpretations of SOLAS have further been incorpo-
rated into the rule text in this chapter.
Fire technical requirements in SOLAS, compulsory to specific
types of vessel, are covered by the Part and Chapter for the rel-
evant additional class notation, as referred to in B105.
102 With reference to Pt.1 Ch.1 Sec.3, plan approval and
survey with subsequent issuance of relevant SOLAS Certifi-
cates, if carried out by a recognised SOLAS contracting gov-
ernment in which the vessel is registered, may be accepted as
basis for the requirements to fire safety for the class.
103 Text quoted from SOLAS is printed in italics.
For the application of these rules, wherever the term Adminis-
tration is quoted, this is to read as the Society.
104 IMO MSC/Circ.847, Interpretations of vague expres-
sions and other vague wording in SOLAS Chapter II-2 is to
be regarded as part of the rules, although the entire text of this
IMO Circular is not included in the rules.
B. Classification
B 100 Application
101 The requirements in this chapter apply to all ships as-
signed main class, except as specified in 102.
102 The present regulations, unless expressly provided oth-
erwise, do not apply to:
ships of war and troopships
cargo ships less than 500 gross tonnage
ships not propelled by mechanical means
wooden ships of primitive build
pleasure yachts not engaged in trade
fishing vessels.
(SOLAS Reg. I/3)
See also 105 concerning cargo ships less than 500 gross ton-
nage and fishing vessels.
103 Consideration will be given to ships classed for restrict-
ed or special service.
104 The Administration of a State may, if it considers that the
sheltered nature and conditions of the voyage are such as to
render the application of any specific requirements of this
Chapter unreasonable or unnecessary, exempt from those re-
quirements individual ships or classes of ships entitled to fly the
flag of that State which, in the course of their voyage, do not
proceed more than 20 miles from the nearest land.
(SOLAS Reg. II-2/1.4.1)
105 The requirements may also be applicable to other ships
than specified in 102. Such applications will be stated in con-
nection with additional classes. For cargo ships less than 500
gross tonnage Sec.16 will apply. For fishing vessels Sec.17
will apply.
106 Consideration will be given to ships not covered by 102
and 105.
B 200 Rule references
201 Special requirements applicable to additional class nota-
tions are placed under:
C. Definitions
C 100 Ship type definitions and size
101 A "passenger" is every person other than:
the master and the members of the crew or other persons
employed or engaged in any capacity on board a ship on
the business of that ship; and
a child under one year of age.
(SOLAS Reg. I/2(e))
102 A "passenger ship" is a ship which carries more than
twelve passengers.
(SOLAS Reg. I/2(f))
103 A "cargo ship" is any ship which is not a passenger ship.
(SOLAS Reg. I/2(g))
104 A "tanker" is a cargo ship constructed or adapted for the
carriage in bulk of liquid cargoes of an inflammable nature.
(SOLAS Reg. I/2(h))
105 A "fishing vessel" is a vessel used for catching fish,
whales, seals, walrus or other living resources of the sea.
(SOLAS Reg. I/2(i))
C 200 Fire technical definitions
201 "Non-combustible material" is a material which neither
burns nor gives off flammable vapours in sufficient quantity for
self-ignition when heated to approximately 750C, this being
determined in accordance with the Fire Test Procedures Code.
Any other material is a combustible material.
(SOLAS Reg. II-2/3.1)
202 "A standard fire test" is one in which specimens of the rel-
evant bulkheads or decks are exposed in a test furnace to tem-
peratures corresponding approximately to the standard time-
temperature curve. The test methods shall be in accordance
with the Fire Test Procedures Code.
(SOLAS Reg. II-2/3.2)
203 " 'A' class divisions" are those divisions formed by bulk-
heads and decks which comply with the following:
.1 they shall be constructed of steel or other equivalent mate-
rial;
.2 they shall be suitably stiffened;
.3 they shall be so constructed as to be capable of preventing
the passage of smoke and flame to the end of the one-hour
standard fire test;
Passenger Ships Pt.5 Ch.2
Oil Carriers Pt.5 Ch.3
Chemical Carriers Pt.5 Ch.4
Liquefied Gas Carriers Pt.5 Ch.5
Fishing Vessels Sec.17
Fire Fighter I (or II or III) Pt.5 Ch.7
Additional Fire Protection (F-AMC) Pt.6 Ch.4
Dangerous Goods Pt.5 Ch.11
Rules for Ships, January 2001
Pt.4 Ch.10 Sec.1 Page 6
DET NORSKE VERITAS
.4 they shall be insulated with approved non-combustible ma-
terials such that the average temperature of the unex-
posed side will not rise more than 140C above the original
temperature, nor will the temperature, at any one point, in-
cluding any joint, rise more than 180C above the original
temperature, within the time listed below:
class "A-60" 60 minutes
class "A-30" 30 minutes
class "A-15" 15 minutes
class "A-0" 0 minutes.
.5 the Administration shall require a test of a prototype bulk-
head or deck in accordance with the Fire Test Procedures
Code to ensure that it meets the above requirements for in-
tegrity and temperature rise.
(SOLAS Reg. II-2/3.3)
204 " 'B' class divisions" are those divisions formed by bulk-
heads, decks, ceilings or linings which comply with the follow-
ing:
.1 they shall be so constructed as to be capable of preventing
the passage of flame to the end of the first half hour of the
standard fire test;
.2 they shall have an insulation value such that the average
temperature of the unexposed side will not rise more than
140C above the original temperature, nor will the temper-
ature at any one point, including any joint, rise more than
225C above the original temperature, within the time list-
ed below:
class "B-15" 15 minutes
class "B-0" 0 minutes.
.3 they shall be constructed of approved non-combustible
materials and all materials entering into the construction
and erection of "B" class divisions shall be non-combusti-
ble, with the exception that combustible veneers may be
permitted provided they meet other requirements of this
Chapter;
.4 the Administration shall require a test of a prototype divi-
sion in accordance with the Fire Test Procedures Code to
ensure that it meets the above requirements for integrity
and temperature rise.
(SOLAS Reg. II-2/3.4)
205 " 'C' class divisions" are divisions constructed of ap-
proved non-combustible materials. They need meet neither re-
quirements relative to the passage of smoke and flame nor
limitations relative to the temperature rise. Combustible ve-
neers are permitted provided they meet other requirements of
this Chapter.
(SOLAS Reg. II-2/3.5)
206 A division consisting of a non-combustible core and
combustible veneers may be accepted as a B or C class divi-
sion, provided that the non-combustible core is tested in ac-
cordance with the Fire Test Procedures Code, part 1, that the B
class division is tested in accordance with the Fire Test Proce-
dures Code, part 3, and that the veneers mounted to the non-
combustible core are tested in accordance with the Fire Test
Procedures Code, part 5 and part 2 if applicable.
(IACS UI SC125)
207 "Continuous 'B' class ceilings or linings" are those "B"
class ceilings or linings which terminate only at an "A" or "B"
class division.
(SOLAS Reg. II-2/3.6)
208 "Steel or other equivalent material". Where the words
"steel or other equivalent material" occur, "equivalent material"
means any non-combustible material which, by itself or due to
insulation provided, has structural and integrity properties
equivalent to steel at the end of the applicable exposure to the
standard fire test (e.g. aluminium alloy with appropriate insula-
tion).
(SOLAS Reg. II-2/3.7)
209 "Low flame spread" means that the surface thus de-
scribed will adequately restrict the spread of flame, this being
determined in accordance with the Fire Test Procedures Code.
(SOLAS Reg. II-2/3.8)
210 Primary deck covering is a deck covering which will not
readily ignite or give rise to toxic or explosive hazards at ele-
vated temperatures. Testing is to be based on IMO Res.
A.687(17) or an equivalent test procedure.
C 300 Space definitions
301 "Main vertical zones" are those sections into which the
hull, superstructure, and deckhouses are divided by 'A' class di-
visions, the mean length and width of which on any deck does
not in general exceed 40 m.
(SOLAS Reg. II-2/3.9)
302 "Accommodation spaces" are those spaces used for
public spaces, corridors, lavatories, cabins, offices, hospitals,
cinemas, games and hobbies rooms, barber shops, pantries
containing no cooking appliances and similar spaces.
(SOLAS Reg. II-2/3.10)
303 "Public spaces" are those portions of the accommodation
which are used for halls, dining rooms, lounges and similar per-
manently enclosed spaces.
(SOLAS Reg. II-2/3.11)
304 "Service spaces" are those spaces used for galleys, pan-
tries containing cooking appliances, lockers, mail and specie
rooms, store-rooms, workshops other than those forming part
of the machinery spaces, and similar spaces and trunks to such
spaces.
(SOLAS Reg. II-2/3.12)
305 "Cargo spaces" are all spaces used for cargo (including
cargo oil tanks) and trunks to such spaces.
(SOLAS Reg. II-2/3.13)
306 "Ro-ro cargo spaces" are spaces not normally subdivid-
ed in any way and extending to either a substantial length or the
entire length of the ship in which goods (packaged or in bulk, in
or on rail or road cars, vehicles (including road or rail tankers),
trailers, containers, pallets, demountable tanks or in or on sim-
ilar stowage units or other receptacles) can be loaded and un-
loaded normally in a horizontal direction.
(SOLAS Reg. II-2/3.14)
307 "Open ro-ro cargo spaces" are ro-ro cargo spaces either
open at both ends, or open at one end and provided with ade-
quate natural ventilation effective over their entire length
through permanent openings in the side plating or deckhead to
the satisfaction of the Administration.
(SOLAS Reg. II-2/3.15)
308 "Closed ro-ro cargo spaces" are ro-ro cargo spaces
which are neither open ro-ro cargo spaces nor weather decks.
(SOLAS Reg. II-2/3.16)
309 "Weather deck" is a deck which is completely exposed to
the weather from above and from at least two sides.
(SOLAS Reg. II-2/3.17)
310 "Special category spaces" are those enclosed spaces
above or below the bulkhead deck intended for the carriage of
motor vehicles with fuel in their tanks for their own propulsion,
into and from which such vehicles can be driven and to which
passengers have access.
(SOLAS Reg. II-2/3.18)
Rules for Ships, January 2001
Pt.4 Ch.10 Sec.1 Page 7
DET NORSKE VERITAS
311 "Machinery spaces of category A" are those spaces and
trunks to such spaces which contain:
.1 internal combustion machinery used for main propulsion;
or
.2 internal combustion machinery used for purposes other
than main propulsion where such machinery has in the ag-
gregate a total power output of not less than 375 kW; or
.3 any oil-fired boiler or oil fuel unit.
(SOLAS Reg. II-2/3.19)
Spaces which contain oil fired equipment other than boilers,
such as inert gas generators, incinerators, waste disposal units
etc., are to be considered as machinery spaces of category A.
(IACS UR F35 / UI SC15)
312 "Machinery spaces" are all machinery spaces of catego-
ry A and all other spaces containing propulsion machinery, boil-
ers, oil fuel units, steam and internal combustion engines,
generators and major electrical machinery, oil filling stations,
refrigerating, stabilizing, ventilation and air conditioning ma-
chinery, and similar spaces, and trunks to such spaces.
(SOLAS Reg. II-2/3.20)
C 400 Definitions on equipment, control stations and
hydrostatic terms
401 "Oil fuel unit" is the equipment used for the preparation of
oil fuel for delivery to an oil-fired boiler, or equipment used for
the preparation for delivery of heated oil to an internal combus-
tion engine, and includes any oil pressure pumps, filters and
heaters dealing with oil at a pressure of more than 0.18 N/mm
2
.
(SOLAS Reg. II-2/3.21)
Oil fired inert gas generators are to be defined as 'Oil fuel unit'.
(IACS UI SC16)
402 "Control stations" are those spaces in which the ship's ra-
dio or main navigating equipment or the emergency source of
power is located or where the fire recording or fire control equip-
ment is centralized.
(SOLAS Reg. II-2/3.22)
'Control stations' are spaces containing emergency sources for
emergency lighting, wheel house and chartroom, spaces con-
taining the ship's radio equipment, fire extinguishing rooms.
Spaces containing the following battery sources are to be re-
garded as control stations regardless of battery capacity:
.1 emergency batteries in separate battery room for power
supply from blackout till start of emergency generator;
.2 emergency batteries in separate battery room as reserve
source of energy to radiotelegraph installation;
.3 batteries for start of emergency generator;
.4 and in general, all emergency batteries required in pursu-
ance of Ch.8 Sec.2 C.
(IACS UI SC17)
403 "Central control station" is a control station in which the
following control and indicator functions are centralized:
.1 fixed fire detection and alarm system;
.2 automatic sprinklers, fire detection and alarm system;
.3 fire door indicator panels;
.4 fire door closures;
.5 watertight door indicator panels;
.6 watertight door closure;
.7 ventilation fans;
.8 general/fire alarms;
.9 communication systems including telephones; and
.10 microphones to public address systems.
(SOLAS Reg. II-2/3.22-1)
404 "Continuously manned central control station" is a central
control station which is continuously manned by a responsible
member of the crew.
(SOLAS Reg. II-2/3.22-2)
405 Rooms containing furniture and furnishings of restricted
fire risk are, for the purpose of regulation 26 (Pt.5 Ch.2 Sec.2
E700) those rooms containing furniture and furnishings of re-
stricted fire risk (whether cabins, public spaces, offices or other
types of accommodation) in which:
.1 all case furniture such as desks, wardrobes, dressing ta-
bles, bureaux, dressers, is constructed entirely of ap-
proved non-combustible materials, except that a
combustible veneer not exceeding 2 mm may be used on
the working surface of such articles;
.2 all free-standing furniture such as chairs, sofas, tables, is
constructed with frames of non-combustible materials;
.3 all draperies, curtains and other suspended textile materi-
als have qualities of resistance to the propagation of flame
not inferior to those of wool of mass 0.8 kg/m, this being
determined in accordance with the Fire Test Procedures
Code;
.4 all floor coverings have low flame characteristics;
.5 all exposed surfaces of bulkheads, linings and ceilings
have low flame-spread characteristics; and
.6 all upholstered furniture has qualities of resistance to the
ignition and propagation of flame, this being determined in
accordance with the Fire Test Procedures Code;
.7 all bedding components have qualities of resistance to the
ignition and propagation of flame, this being determined in
accordance with the Fire Test Procedures Code.
(SOLAS Reg. II-2/3.23)
406 "Bulkhead deck" is the uppermost deck up to which the
transverse watertight bulkheads are carried.
(SOLAS Reg. II-2/3.24)
407 "Deadweight" is the difference in tonnes between the dis-
placement of a ship in water of a specific gravity of 1.025 at the
load water-line corresponding to the assigned summer free-
board and the lightweight of the ship.
(SOLAS Reg. II-2/3.25)
408 "Lightweight" is the displacement of a ship in tonnes with-
out cargo fuel, lubricating oil, ballast water, fresh water and
feedwater in tanks, consumable stores, and passengers and
crew and their effects
(SOLAS Reg. II-2/3.26)
409 "Fire Test Procedures Code" means the International
Code for Application of Fire Test Procedures, as adopted by the
Maritime Safety Committee of the Organization by resolution
MSC.61(67), as may be amended by the Organization, provid-
ed that such amendments are adopted, brought into force and
take effect in accordance with the provisions of article VIII of the
present Convention concerning the amendment procedures
applicable to the Annex other than chapter I.
(SOLAS Reg. II-2/3.35)
C 500 System definitions
501 A total flooding fire-extinguishing system is a perma-
nently fixed system designed for extinguishing in the complete
volume of an enclosure.
502 Local application fire-extinguishing system is a perma-
nently fixed system designed for extinguishing of local out-
breaks.
D. Documentation
D 100 Plans and particulars
101 In cases where the National Authorities do not survey
the ship, as specified in A102, the following plans and partic-
ulars are to be submitted for approval:
fire pumps and fire main including emergency fire pump
and number and positions of hydrants and hoses
capacity calculation for fire pumps
Rules for Ships, January 2001
Pt.4 Ch.10 Sec.1 Page 8
DET NORSKE VERITAS
fixed fire extinguishing arrangement in engine and boiler
room. Specification and location of equipment and calcu-
lation of discharge capacities, if required
fixed fire extinguishing arrangement in cargo spaces.
Specification and location of equipment and calculation of
discharge capacities, if required
fire control plan. Equipment according to Sec.14 is to be
included on the plan in addition to details of fire items not
shown on other drawings
automatic sprinkler, fire alarm and fire detection system.
Sprinklers grouped into sections, specification and loca-
tions of pumps, tanks, alarms and activators, if applicable
for fixed fire detection and alarm systems in accommoda-
tion spaces, service spaces, machinery spaces and cargo
spaces, if required: Specification and location of detectors,
alarm devices and call points, and cable routing layout
drawing
ventilation systems. Layout, dimensions and penetrations
of ducts through fire divisions and details of fire dampers
penetration of cables and pipes through fire divisions
arrangement of means of control for closure of openings,
stop of ventilation fans and stop of fuel oil pumps in ma-
chinery spaces of category A.
Cargo ships
ventilation systems in cargo spaces
structural fire protection drawings showing method of
construction, key numbers according to Sec.15 B300 for
all rooms, the fire insulation and draught stops. Details of
insulation and specification of materials. Doors in fire di-
visions
means of escape from different compartments
fire extinguishing system for cargo spaces
protection of ro-ro cargo spaces and cargo spaces intended
for carriage of motor vehicles with fuel in their tanks for
their own propulsion with ventilation system, fire main,
fire extinction and precautions against ignition of flamma-
ble vapours, if applicable.
102 Fire fighting equipment required to be of an approved
type, such as hoses, extinguishers, gas cylinders, emergency
pumps, breathing apparatuses etc. are to be approved by the
Society or a recognised SOLAS contracting government ad-
ministration.
Documentation verifying approval is in such cases to be sub-
mitted.
103 For instrumentation and automation, including compu-
ter based control and monitoring, see Ch.9 Sec.1.
Rules for Ships, January 2001
Pt.4 Ch.10 Sec.2 Page 9
DET NORSKE VERITAS
SECTION 2
FIRE PUMPS AND FIRE MAIN
A. General
A 100 Application
101 Every ship is to be provided with fire pumps, fire mains,
hydrants and hoses complying as applicable with the require-
ments of this regulation.
(SOLAS Reg. II-2/4.1)
B. Fire Pumps
B 100 Capacity of fire pumps
101 The required fire pumps shall be capable of delivering for
fire-fighting purposes a quantity of water, at the pressure spec-
ified in paragraph 4 (C100), as follows:
.1 Pumps in passenger ships, not less than two thirds of the
quantity required to be dealt with by the bilge pumps when
employed for bilge pumping; and
.2 pumps in cargo ships, other than any emergency pump,
not less than four-thirds of the quantity required under
Regulation II-1/21 to be dealt with by each of the independ-
ent bilge pumps in a passenger ship of the same dimen-
sion when employed in bilge pumping, provided that in no
cargo ship need the total required capacity of the fire
pumps exceed 180 m
3
/hour.
(SOLAS Reg. II-2/4.2.1)
102 Each of the required fire pumps (other than any emer-
gency pump required in paragraph 3.3.2 (203.2) for cargo
ships) shall have a capacity not less than 80% of the total re-
quired capacity divided by the minimum number of required fire
pumps but in any case not less than 25 m
3
/hour and each such
pump shall in any event be capable of delivering at least the two
required jets of water. These fire pumps shall be capable of
supplying the fire main system under the required conditions.
Where more pumps than the minimum of required pumps are
installed the capacity of such additional pumps shall be to the
satisfaction of the Administration.
(SOLAS Reg. II-2/4.2.2)
B 200 Arrangement and number of fire pumps
201 Ships shall be provided with independently driven fire
pumps as follows:
.1 Passenger ships of 4,000 gross tonnage and upwards at
least three.
.2 Passenger ships of less than 4,000 gross tonnage and car-
go ships of 1,000 gross tonnage and upwards at least two
.3 Cargo ships of less than 1,000 gross tonnage to the satis-
faction of the Administration.
(SOLAS Reg. II-2/4.3.1)
.4 Cargo ships of less than 1000 gross tonnage but above 500
gross tonnage are to be provided with not less than two
power fire pumps, one of which is to be an independently
driven pump.
(IACS UI SC18)
202 Sanitary, ballast, bilge or general service pumps may be
accepted as fire pumps, provided that they are not normally
used for pumping oil and that if they are subject to occasional
duty for the transfer or pumping of oil fuel, suitable change-over
arrangements are fitted.
(SOLAS Reg. II-2/4.3.2)
203 The arrangement of sea connections, fire pumps and
their sources of power shall be such as to ensure that:
.1 In passenger ships of 1,000 gross tonnage and upwards,
in the event of a fire in any one compartment all the fire
pumps will not be put out of action.
.2 In cargo ships of 1,000* gross tonnage and upwards if a
fire in any one compartment could put all the pumps out
of action there shall be an alternative means consisting of
a fixed independently driven emergency pump which
shall be capable of supplying two jets of water to the sat-
isfaction of the Administration. The pump and its location
shall comply with the following requirements:
.2.1 The capacity of the pump shall not be less than
40% of the total capacity of the fire pumps re-
quired by this Reg. and in any case not less than
25 m
3
/hour.
.2.2 When the pump is delivering the quantity of water
required by paragraph 3.3.2.1 (203.2.1) the pres-
sure at any hydrant shall be not less than the min-
imum pressures given in paragraph 4.2 (C102).
.2.3 Any diesel driven power source for the pump shall
be capable of being readily started in its cold con-
dition down to a temperature of 0C by hand (man-
ual) cranking. If this is impracticable, or if lower
temperatures are likely to be encountered, consid-
eration is to be given to the provision and mainte-
nance of heating arrangements, acceptable to the
Administration, so that ready starting will be as-
sured. If hand (manual) starting is impracticable
the Administration may permit other means of
starting. These means shall be such as to enable
the diesel driven power source to be started at
least 6 times within a period of 30 minutes, and at
least twice within the first 10 minutes.
For diesel engines above 15 kW, the engine is to
be equipped with an approved auxiliary starting
device, e.g. starting battery, independent hydrau-
lic system, or independent air system.
.2.4 Any service fuel tank shall contain sufficient fuel to
enable the pump to run on full load for at least
three hours and sufficient reserves of fuel shall be
available outside the main machinery space to en-
able the pump to be run on full load for an addition-
al 15 hours.
For ships below 2000 gross tonnage the total run-
ning time may be reduced to 3 hours.
.2.5 The total suction head and the net positive suction
head of the pump shall be such that the require-
ments of paragraphs 3.3.2 (203.2), 3.3.2.1
(203.2.1), 3.3.2.2 (203.2.2) and 4.2 (C102) of this
regulation shall be obtained under all conditions of
list, trim, roll and pitch likely to be encountered in
service.
A condition of service is to be based upon a min-
imum draft for self propulsion of the ship. The
emergency fire pump not installed at an adequate
depth below water line, is to be of a self-priming
type.
Rules for Ships, January 2001
Pt.4 Ch.10 Sec.2 Page 10
DET NORSKE VERITAS
204 The arrangements for the ready availability of water sup-
ply shall be:
.1 In passenger ships of 1,000 gross tonnage and upwards
such that at least one effective jet of water is immediately
available from any hydrant in an interior location and so as
to ensure the continuation of the output of water by the au-
tomatic starting of a required fire pump.
Only one of the required fire pumps needs to be provided
with automatic starting.
(IACS UI SC23)
.2 in passenger ships of less than 1,000 gross tonnage and
in cargo ships to the satisfaction of the Administration
.3 in cargo ships with a periodically unattended machinery
space or when only one person is required on watch there
shall be immediate water delivery from the fire main sys-
tem at a suitable pressure, either by remote starting of one
of the main fire pumps with remote starting from the navi-
gating bridge and fire control station, if any, or permanent
pressurization of the fire main system by one of the main
fire pumps, except that the Administration may waive this
requirement for cargo ships of less than 1,600 gross ton-
nage if the arrangement of the machinery space access
makes it unnecessary
.4 In passenger ships, if fitted with periodically unattended
machinery spaces in accordance with regulation II-1/54,
the Administration shall determine provisions for fixed wa-
ter fire-extinguishing arrangement for such spaces equiva-
lent to those required for normally attended machinery
spaces.
(SOLAS Reg. II-2/4.3.4)
205 Relief valves shall be provided in conjunction with all fire
pumps if the pumps are capable of developing a pressure ex-
ceeding the design pressure of the water service pipes, hy-
drants and hoses. These valves shall be so placed and
adjusted as to prevent excessive pressure in any part of the fire
main system.
(SOLAS Reg. II-2/4.3.5)
206 Where centrifugal fire pumps are used, a non-return
valve is to be fitted to the pump.
207 In tankers isolation valves shall be fitted in the fire main
at poop front in a protected position and on the tank deck at in-
tervals of not more than 40 m to preserve the integrity of the fire
main system in case of fire or explosion.
(SOLAS Reg. II-2/4.3.6)
208 For ships with class notation ICE, at least one of the fire
pumps is to be connected to a sea chest, which is in compliance
with Pt.5 Ch.1 Sec.2 C300.
(IACS UR F41)
.2.6 When the emergency fire pump is electrically
driven, the power is to be supplied by a source
other than that supplying the main fire pumps.
The relevant electric cables are not to pass
through the compartment containing the main fire
pump. This source is to be located outside the
space containing the main fire pumps and their
source of power and is to be insulated to a stand-
ard of structural fire protection equivalent to a
control station in Sec.15 B300.
.2.7 No direct access shall be permitted between the
machinery space and the space containing the
emergency fire pump and its source of power.
When this is impracticable an Administration may
accept an arrangement where the access is by
means of an airlock, each of the two doors being
self-closing, or through a watertight door capable
of being operated from a space remote from the
machinery space and the space containing the
emergency fire pump and unlikely to be cut off in
the event of fire in those spaces. In such cases a
second means of access to the space containing
the emergency fire pump and its source of power
shall be provided.
.2.8 Ventilation arrangements to the space containing
the independent source of power for the emergen-
cy fire pump shall be such as to preclude, as far as
practicable, the possibility of smoke from a ma-
chinery space fire entering or being drawn into that
space.
If the room is to be mechanically ventilated the
power is to be supplied by the emergency source.
The room where the emergency fire pump prime
mover is located is to be illuminated from the
emergency source of supply and is to be well ven-
tilated.
.2.9 The space containing the fire pump shall not be
contiguous to the boundaries of machinery spaces
of category A or those spaces containing main fire
pumps. Where this is not practicable, the common
bulkhead between the two spaces shall be insulat-
ed to a standard of structural fire protection equiv-
alent to that required for a control station in
regulation 44 (Sec.15 B300).
Where an emergency fire pump is required ac-
cording to 203.2, the fire pump and its source of
power are to be outside the space containing the
main fire pumps. Sea water inlet, suction and de-
livery pipes are to be outside the space containing
the main fire pumps except for short lengths of
pipe enclosed in substantial steel casing. If sea
chest is located inside the space containing main
fire pump, the sea chest valve is to be operable
from a position close to the pump.
2.10 If water is needed for any fixed fire extinguishing
system provided to protect the space where the
main fire pumps are located, the capacity of the
emergency fire pump is to be sufficient for simul-
taneously supplying water to this and the fire
main.
.2.11 The emergency fire pump may also be used for
other suitable purposes subject to approval in
each case.
.2.12 Upon completion of the emergency fire pump in-
stallation, a running test of 4 hours duration is to
be carried out. This test is to be a full load trial,
and the water pressure in the fire main is to be
checked.
.3 In passenger ships of less than 1,000 gross tonnage and
cargo ships of less than 1000* gross tonnage, if a fire in
any one compartment could put all the pumps out of ac-
tion the alternative means of providing water for fire-fight-
ing purposes are to the satisfaction of the Administration.
.3.1 The alternative means to be provided in accord-
ance with the provisions of paragraph 3.3.3
(203.3) shall be an independently driven, power-
operated emergency fire pump and with its source
of power and sea connection located outside the
machinery space.
.4 In addition, in cargo ships where other pumps, such as
general service, bilge and ballast, etc., are fitted in a ma-
chinery space, arrangements shall be made to ensure
that at least one of these pumps, having the capacity and
pressure required by paragraphs 2.2 (102) and 4.2
(C102), is capable of providing water to the fire main.
(SOLAS Reg. II-2/4.3.3, * IACS UR F30, IACS UI SC19)
Rules for Ships, January 2001
Pt.4 Ch.10 Sec.2 Page 11
DET NORSKE VERITAS
C. Water Distribution System
C 100 Diameter of and pressure in the fire mains
101 The diameter of the fire main and water service pipes
shall be sufficient for the effective distribution of the maximum
required discharge from two fire pumps operating simultane-
ously, except that in the case of cargo ships the diameter need
only be sufficient for the discharge of 140 m
3
/hour.
(SOLAS Reg. II-2/4.4.1)
102 With the two pumps simultaneously delivering through
nozzles specified in paragraph 8 (500) the quantity of water
specified in paragraph 4.1 (101), through any adjacent hy-
drants, the following minimum pressures shall be maintained at
all hydrants:
(SOLAS Reg. II-2/4.4.2)
For passenger ships, see Pt.5 Ch.2.
103 The maximum pressure at any hydrant shall not exceed
that at which the effective control of a fire hose can be demon-
strated.
(SOLAS Reg. II-2/4.4.3)
C 200 Number and position of hydrants
201 The number and position of hydrants shall be such that
at least two jets of water not emanating from the same hydrant,
one of which shall be from a single length of hose, may reach
any part of the ship normally accessible to the passengers or
crew while the ship is being navigated and any part of any cargo
space when empty, any ro-ro cargo space or any special cate-
gory space in which latter case the two jets shall reach any part
of such space, each from a single length of hose. Furthermore,
such hydrants shall be positioned near the accesses to the pro-
tected spaces.
(SOLAS Reg. II-2/4.5.1)
When calculating the number of hydrants, the length of the wa-
ter jet is to be ignored.
202 In the accommodation, service and machinery spaces of
passenger ships the number and position of hydrants shall be
such that the requirements of paragraph 5.1 (201) may be com-
plied with when all watertight doors and all doors in main verti-
cal zone bulkheads are closed.
(SOLAS Reg. II-2/4.5.2)
203 Where, in a passenger ship, access is provided to a ma-
chinery space of category A at a low level from an adjacent
shaft tunnel, two hydrants shall be provided external to, but
near the entrance to that machinery space. Where such access
is provided from other spaces, in one of those spaces two hy-
drants shall be provided near the entrance to the machinery
space of category A. Such provision need not be made where
the tunnel or adjacent spaces are not part of the escape route.
(SOLAS Reg. II-2/4.5.3)
C 300 Pipes and hydrants
301 Materials readily rendered ineffective by heat shall not be
used for fire mains and hydrants unless adequately protected.
The pipes and hydrants shall be so placed that the fire hoses
may be easily coupled to them. The arrangement of pipes and
hydrants shall be such as to avoid the possibility of freezing. In
ships where deck cargo may be carried, the positions of the hy-
drants shall be such that they are always readily accessible and
the pipes shall be arranged as far as practicable to avoid risk of
damage by such cargo. Unless one hose and nozzle is provid-
ed for each hydrant in the ship, there shall be complete inter-
changeability of hose couplings and nozzles.
(SOLAS Reg. II-2/4.6.1)
302 A valve shall be fitted to serve each fire hose so that any
fire hose may be removed while the fire pumps are at work.
(SOLAS Reg. II-2/4.6.2)
303 Isolating valves to separate the section of the fire main
within the machinery space containing the main fire pump or
pumps from the rest of the fire main shall be fitted in an easily
accessible and tenable position outside the machinery spaces.
The fire main shall be so arranged that when the isolating
valves are shut all the hydrants on the ship, except those in the
machinery space referred to above, can be supplied with water
by a fire pump not located in this machinery space through
pipes which do not enter this space. Exceptionally, the Admin-
istration may permit short lengths of the emergency fire pump
suction and discharge piping to penetrate the machinery space
if it is impracticable to route it externally provided that the integ-
rity of the fire main is maintained by the enclosure of the piping
in a substantial steel casing.
(SOLAS Reg. II-2/4.6.3)
304 Pipe wall thicknesses are to be in accordance with Ch.6
Sec.6 and material quality in accordance with Pt.2 Ch.1.
305 All water pipes for fire extinguishing are to be provided
with means for draining to avoid damage due to frost.
C 400 Fire hoses
401 Fire hoses shall be of non-perishable material approved
by the Administration and shall be sufficient in length to project
a jet of water to any of the spaces in which they may be required
to be used. Fire hoses of non-perishable material shall be pro-
vided in ships constructed on or after 1 February 1992, and on
ships constructed before 1 February 1992 when the existing fire
hoses are replaced. Their maximum length shall be to the sat-
isfaction of the Administration. Each hose shall be provided
with a nozzle and the necessary couplings. Hoses specified in
this Chapter as "fire hoses" shall together with any necessary
fittings and tools be kept ready for use in conspicuous positions
near the water service hydrants or connections. Additionally in
interior locations in passenger ships carrying more than 36 pas-
sengers fire hoses shall be connected to the hydrants at all
times.
(SOLAS Reg. II-2/4.7.1)
Fire hoses should have a length of:
at least 10 m
not more than 15 m in machinery spaces
not more than 20 m for other spaces and open decks
not more than 25 m for open decks on ships with a maxi-
mum breadth in excess of 30 m.
(MSC/Circ.847)
Guidance note:
Fire hoses should be of dimension 38 mm (1.5'') in accommoda-
tion and 51 mm (2'') in other areas.
---e-n-d---of---G-u-i-d-a-n-c-e---n-o-t-e---
402 Ships shall be provided with fire hoses the number and
diameter of which shall be to the satisfaction of the Administra-
tion.
(SOLAS Reg. II-2/4.7.2)
403 In passenger ships there shall be at least one fire hose
for each of the hydrants required by paragraph 5 (200) and
these hoses shall be used only for the purposes of extinguish-
ing fires or testing the fire-extinguishing apparatus at fire drills
and surveys.
(SOLAS Reg. II-2/4.7.3)
404 In cargo ships of 1,000 gross tonnage and upwards the
number of fire hoses to be provided shall be one for each 30 m
length of the ship and one spare but in no case less than five in
all. This number does not include any hoses required in any en-
gine or boiler room. The Administration may increase the
number of hoses required so as to ensure that hoses in suffi-
Cargo ships:
6,000 gross tonnage and upwards 0.27 N/mm
2
1,000 gross tonnage and upwards but
under 6,000 gross tonnage
0.25 N/mm
2
Under 1,000 gross tonnage To the satisfaction of
the Administration
Rules for Ships, January 2001
Pt.4 Ch.10 Sec.2 Page 12
DET NORSKE VERITAS
cient number are available and accessible at all times, having
regard to the type of ship and the nature of trade in which the
ship is employed.
(SOLAS Reg. II-2/4.7.4.1)
405 In cargo ships of less than 1,000 gross tonnage the
number of fire hoses to be provided shall be to the satisfaction
of the Administration.
(SOLAS Reg. II-2/4.7.4.2)
The number of fire hoses shall be one for each 30 m length of
the ship and one spare but not less than 3 in all.
C 500 Nozzles
501 For the purposes of this chapter, standard nozzle sizes
shall be 12 mm, 16 mm and 19 mm or as near thereto as pos-
sible. Larger diameter nozzles may be permitted at the discre-
tion of the Administration.
(SOLAS Reg. II-2/4.8.1)
502 For accommodation and service spaces, a nozzle size
greater than 12 mm need not be used.
(SOLAS Reg. II-2/4.8.2)
503 For machinery spaces and exterior locations, the nozzle
size shall be such as to obtain the maximumdischarge possible
from two jets at the pressure mentioned in paragraph 4 (100)
from the smallest pump, provided that a nozzle size greater
than 19 mm need not be used.
(SOLAS Reg. II-2/4.8.3)
504 All nozzles shall be of an approved dual purpose type
(i.e. spray/jet type) incorporating a shut-off.
(SOLAS Reg. II-2/4.8.4)
C 600 International shore connection
601 Ships of 500 gross tonnage and upwards shall be provid-
ed with at least one international shore connection, complying
with provisions of paragraph 3 (603).
(SOLAS Reg. II-2/19.1)
602 Facilities shall be available enabling such a connection to
be used on either side of the ship.
(SOLAS Reg. II-2/19.2)
603 Standard dimensions of flanges for the international
shore connection shall be in accordance with the following ta-
ble:
(SOLAS Reg. II-2/19.3)
604 The connection shall be of steel or other suitable material
and shall be designed for 1.0 N/mm
2
services. The flange shall
have a flat face on one side and on the other shall be perma-
nently attached to a coupling that will fit the ship's hydrant and
hose. The connection shall be kept aboard the ship together
with a gasket of any material suitable for 1.0 N/mm
2
services,
together with four 16 mm bolts, 50 mm in length and eight
washers.
(SOLAS Reg. II-2/19.4)
C 700 Pump arrangement for other fire systems
701 Pumps required for the provision of water for other fire-
extinguishing systems required by this chapter, their sources of
power and their controls shall be installed outside the space or
spaces protected by such systems and shall be so arranged
that a fire in the space or spaces protected will not put any such
system out of action.
(SOLAS Reg. II-2/4.9)
DESCRIPTION DIMENSION
Outside diameter 178 mm
Inside diameter 64 mm
Bolt circle diameter 132 mm
Slots in flange 4 holes 19 mm in diameter spaced equidis-
tantly on a bolt circle of the above diame-
ter, slotted to the flange periphery
Flange thickness 14.5 mm minimum
Bolts and nuts 4, each of 16 mm diameter, 50 mm in
length.
Rules for Ships, January 2001
Pt.4 Ch.10 Sec.3 Page 13
DET NORSKE VERITAS
SECTION 3
FIXED GAS FIRE EXTINGUISHING SYSTEM
A. General
A 100 Application
101 The requirements in this section applies to ships and
spaces where fixed gas fire extinguishing systems are required
or fitted.
A 200 General requirements
201 The use of a fire-extinguishing medium which, in the
opinion of the Administration, either by itself or under expected
conditions of use gives off toxic gases in such quantities as to
endanger persons shall not be permitted.
(SOLAS Reg. II-2/5.1.1)
202 The necessary pipes for conveying fire-extinguishing
medium into protected spaces shall be provided with control
valves so marked as to indicate clearly the spaces to which the
pipes are led. Suitable provision shall be made to prevent inad-
vertent admission of the medium to any space. Where a cargo
space fitted with a gas fire-extinguishing system is used as a
passenger space the gas connection shall be blanked during
such use.
(SOLAS Reg. II-2/5.1.2)
203 The piping for the distribution of fire-extinguishing medi-
um shall be arranged and discharge nozzles so positioned that
a uniform distribution of medium is obtained.
(SOLAS Reg. II-2/5.1.3)
204 Means shall be provided to close all openings which may
admit air to or allow gas to escape from a protected space.
(SOLAS Reg. II-2/5.1.4)
205 Where the volume of free air contained in air receivers in
any space is such that, if released in such space in the event of
fire, such release of air within that space would seriously affect
the efficiency of the fixed fire-extinguishing system, the Admin-
istration shall require the provision of an additional quantity of
fire-extinguishing medium.
(SOLAS Reg. II-2/5.1.5)
206 Means shall be provided for automatically giving audible
warning of the release of fire-extinguishing medium into any
space in which personnel normally work or to which they have
access. The alarm shall operate for a suitable period before the
medium is released.
(SOLAS Reg. II-2/5.1.6)
The alarm shall be automatically activated by opening of re-
lease cabinet door. The alarm is to operate as long as doors to
release boxes or master valves are kept open. The alarm is to
operate for a suitable period before the medium is released, and
for this purpose an automatic time delay device is to be fitted
to ensure that the alarm operates for a period of time necessary
to evacuate the space but not less than 20 s.
The time delay unit to be equipped with an override valve to-
gether with a signboard describing emergency operating in-
structions.
Guidance note:
In case of electric time delay, a dedicated battery (UPS) may be
accepted as an alternative to the override valve.
---e-n-d---of---G-u-i-d-a-n-c-e---n-o-t-e---
Ordinary cargo holds need not comply with this requirement.
However, ro-ro cargo spaces and other spaces where personnel
can be expected to enter and where the access is therefore fa-
cilitated by doors or manway hatches are to comply.
Small spaces, such as small compressor rooms, paint lockers,
lamp stores and similar spaces where release is situated imme-
diately outside entrance to such space need not be provided
with automatic audible warning.
(IACS UI SC25)
207 Alarms are to be pneumatically or electrically operated.
If electrically operated, the alarm is to be supplied with power
from the main and emergency source of electrical power. If
pneumatically operated, the air supply is to be taken from the
starting air receivers. Any stop valve fitted in the air supply
line is to be sealed in open position.
208 The means of control of any fixed gas fire-extinguishing
system shall be readily accessible and simple to operate and
shall be grouped together in as few locations as possible at po-
sitions not likely to be cut off by a fire in a protected space. At
each location there shall be clear instructions relating to the op-
eration of the system having regard to the safety of personnel.
(SOLAS Reg. II-2/5.1.7)
209 Automatic release of fire-extinguishing medium shall not
be permitted, except as permitted by paragraph 3.3.5 and in re-
spect of local automatically operated units referred to in para-
graphs 3.4 and 3.5.
(SOLAS Reg. II-2/5.1.8)
210 Where the quantity of extinguishing medium is required
to protect more than one space, the quantity of medium availa-
ble need not be more than the largest quantity required for any
one space so protected.
(SOLAS Reg. II-2/5.1.9)
211 Except as otherwise permitted by paragraphs 3.3, 3.4 or
3.5 pressure containers required for the storage of fire- extin-
guishing medium, other than steam, shall be located outside
protected spaces in accordance with paragraph 1.13 (214).
(SOLAS Reg. II-2/5.1.10)
212 Means shall be provided for the crew to safely check the
quantity of medium in the containers.
(SOLAS Reg. II-2/5.1.11)
For this purpose the arrangement of bottles is to be such as to
provide access for the necessary checking.
213 Containers for the storage of fire-extinguishing medium
and associated pressure components shall be designed to
pressure codes of practice to the satisfaction of the Administra-
tion having regard to their locations and maximum ambient
temperatures expected in service.
(SOLAS Reg. II-2/5.1.12)
Unless otherwise specified, the maximum ambient tempera-
ture is to be understood as 55C. Certification of the bottles is
to be carried out according to Ch.7 Sec.1 D as for CO
2
bottles.
214 When the fire-extinguishing medium is stored outside a
protected space, it shall be stored in a room which shall be sit-
uated in a safe and readily accessible position and shall be ef-
fectively ventilated to the satisfaction of the Administration. Any
entrance to such a storage room shall preferably be from the
open deck and in any case shall be independent of the protect-
ed space. Access doors shall open outwards, and bulkheads
and decks including doors and other means of closing any
opening therein, which form the boundaries between such
rooms and adjoining enclosed spaces shall be gastight. For the
purpose of the application of the integrity tables in Regulations
26 (Pt.5 Ch.2 Sec.2 E700), 27 (Pt.5 Ch.2 Sec.2 E800), 44 (Sec
15 B300) and 58 (Pt.5 Ch.3 Sec.7 B400), such storage rooms
shall be treated as control stations.
(SOLAS Reg. II-2/5.1.13)
Rules for Ships, January 2001
Pt.4 Ch.10 Sec.3 Page 14
DET NORSKE VERITAS
Small local extinguishing systems, like for instance extin-
guishing systems in galley exhaust ducts, where the amount of
gas volume is small in proportion to the space where the bottles
are stored, need not comply with this requirement.
215 Spare parts for the system shall be stored on board and
be to the satisfaction of the Administration.
(SOLAS Reg. II-2/5.1.14)
216 On completion, the system is to be function tested. Sys-
tems of new design are to be function tested according to an ap-
proved test program.
B. Carbon Dioxide Systems
B 100 General requirements for CO
2
fire extinguishing
systems
101 For cargo spaces the quantity of carbon dioxide available
shall, unless otherwise provided, be sufficient to give a mini-
mum volume of free gas equal to 30% of the gross volume of
the largest cargo space so protected in the ship.
(SOLAS Reg. II-2/5.2.1)
See Sec.15 and Pt.5 Ch.2 Sec.2 G for additional requirements
for ro-ro cargo spaces and spaces carrying vehicles with fuel in
their tanks for their own propulsion.
102 For machinery spaces the quantity of carbon dioxide car-
ried shall be sufficient to give a minimum volume of free gas
equal to the larger of the following volumes, either:
.1 40%of the gross volume of the largest machinery space so
protected, the volume to exclude that part of the casing
above the level at which the horizontal area of the casing
is 40% or less of the horizontal area of the space con-
cerned taken midway between the tank top and the lowest
part of the casing; or
.2 35% of the gross volume of the largest machinery space
protected, including the casing; provided that the above-
mentioned percentages may be reduced to 35% and 30%
respectively for cargo ships of less than 2,000 gross ton-
nage; provided also that if two or more machinery spaces
are not entirely separate they shall be considered as form-
ing one space.
(SOLAS Reg. II-2/5.2.2)
103 For the purpose of this paragraph the volume of free car-
bon dioxide shall be calculated at 0.56 m
3
/kg.
(SOLAS Reg. II-2/5.2.3)
The necessary amount (kg) of CO
2
related to the protected vol-
ume (m
3
) is to be calculated as:
30% CO
2
= 0,54 kg CO
2
per m
3
35% CO
2
= 0,63 kg CO
2
per m
3
40% CO
2
= 0,71 kg CO
2
per m
3
45% CO
2
= 0,80 kg CO
2
per m
3
.
104 For machinery spaces the fixed piping system shall be
such that 85%of the gas can be discharged into the space with-
in 2 minutes.
(SOLAS Reg. II-2/5.2.4)
With reference to Table B2, calculations according to a recog-
nised standard (NFPA 12, ISO/DIS 6183 or equivalent) are to
be performed.
105 Carbon dioxide systems installed on or after 1 October
1994 shall comply with the following requirements:
.1 Two separate controls shall be provided for releasing car-
bon dioxide into a protected space and to ensure the activ-
ities of the alarm. One control shall be used to discharge
the gas from its storage containers. A second control shall
be used for opening the valve of the piping which conveys
the gas into the protected space.
.2 The two controls shall be located inside a release box
clearly identified for the particular space. If the box contain-
ing the controls is to be locked, a key to the box shall be in
a break-glass type enclosure conspicuously located adja-
cent to the box.
(SOLAS Reg. II-2/5.2.5)
.3 There is to be a release box for each protected space in
which personnel normally work or to which they have ac-
cess. The space served is to be identified at the release
box. These requirements apply for all CO
2
-systems.
Guidance note:
Concerning application of requirement for CO
2
release alarm for
cargo holds and small spaces, see A206.
---e-n-d---of---G-u-i-d-a-n-c-e---n-o-t-e---
Guidance note:
Opening of the valves to the pilot cylinders is not regarded as one
separate control .
---e-n-d---of---G-u-i-d-a-n-c-e---n-o-t-e---
B 200 CO
2
fire extinguishing systems for cargo holds
201 Requirements in 303 to 316 are to be complied with.
202 The internal diameter of the pipes is not to be less than
19 mm. Branch pipes leading to the various nozzles may have
an internal diameter of 13 mm. At suitable points, the pipeline
is to have facilities for drainage and cleaning.
203 CO
2
pipes connected to the valve register are to be led
such that they are as visible and accessible as possible. The
pipeline is not to be fitted behind ceiling or lining in the accom-
modation, unless the ceiling and lining are made detachable by
fitting of separate cover plates.
Pipes passing through accommodation spaces are to be seam-
less. The number of joints is to be kept to a minimum. Joints
are to be of welded design.
204 The pipelines to cargo spaces are as far as practicable to
be fitted below the weather deck and are to be laid as straight
as possible. Branch pipes leading to the various nozzles are to
be symmetrically installed. All piping is to be properly
clamped and, where necessary, protected against external dam-
age.
205 The CO
2
piping system is to have a blowing-through
connection for drying and checking purposes.
B 300 CO
2
high pressure fire extinguishing systems for
machinery spaces
301 The number of nozzles is to be sufficient to provide an
even distribution of CO
2
gas throughout the space. The total
sectional area of the nozzles in engine or boiler room is not to
be greater than 85% or less than 50% of the total sectional area
of the CO
2
bottle valves intended for the respective rooms.
Where oil separators are installed in a separate room, addition-
al nozzles for CO
2
are to be fitted in this room. For purifier
rooms, see Ch.1 Sec.3 A400.
302 Approximately 90% of the total quantity of CO
2
for en-
gine and boiler rooms is to be discharged above, and approxi-
mately 10% below the floor.
303 In cases where the CO
2
room is readily accessible, one
release station may be acceptable. One master valve for each
of the protected spaces is to be fitted to the piping system of the
Total Flooding System. The operation of those valves is to be
controlled from the position where the CO
2
system is released.
This is to be arranged, if possible, by interlocking devices on
the control handles, so that any fault in the sequence of opera-
tion does not prevent the release of CO
2
gas. The master valve
is to be manually operable even with maximum CO
2
pressure
acting on it. For the release of the system, see 105.
Rules for Ships, January 2001
Pt.4 Ch.10 Sec.3 Page 15
DET NORSKE VERITAS
304 The CO
2
bottle valves are to be of a type which makes it
possible to close the bottles after testing the release system
without emptying the CO
2
content.
305 Bottles are not to contain more than 45 kg of CO
2
and
the ratio of charge is not to exceed 0,67 kg/litre. The company
charging the bottles is to issue a certificate for the ratio of
charge.
Bottles of sizes up to 53.3 kg (80 litre) may be approved case
by case based on satisfactory handling arrangements. All bot-
tles are to be of the same size.
306 The connection between the bottle-valve and the mani-
fold for the CO
2
battery is normally to be flexible high pressure
hose of approved type. Other types of connections which are
considered equivalent may be accepted.
307 Non-return valves are to be fitted between the separate
bottles and the manifold, in order that a bottle, if necessary, can
be disconnected from the battery without putting the whole in-
stallation out of action. The non-return valve is to be fitted to
the manifold. If the non-return valve is fitted in the upper por-
tion of the bottle valve, a notice is to be posted, which clearly
states that the upper portion of the valve is to remain attached
to the manifold, even if the appropriate bottle has been tempo-
rarily removed.
308 The CO
2
pipes connecting the manifold to the valves are
to be steel pipes, the wall thickness of which is to be at least as
given in Table B1. The pipes are to comply with the require-
ments specified in Pt.2 Ch.1 or other recognised standard, and
are to be certified by the Society. Fittings used as pipe joints in
this part of the CO
2
line are to be of steel or equivalent materi-
al.
309 Master valves are to be of steel or equivalent material
and are to comply with PN 100 (nominal pressure). In systems
where valve arrangements introduce sections of closed piping
manifolds, such sections are to be equipped with pressure re-
lief devices.
310 The wall thickness of CO
2
pipes fitted between valves
and nozzles is at least to comply with Table B1. Fittings used
to join this part of the CO
2
pipes may be of malleable cast iron
or nodular cast iron.
311 The portion of the piping fitted outside the engine and
boiler rooms is to be protected internally against corrosion.
312 In order to reduce the pipe resistance, the pipes are to be
laid as straight as possible and to follow the shortest way to the
nozzles. Connecting pieces are not to be fitted in such a way
that the pipe threads are exposed to corrosion. All pipes intend-
ed to carry CO
2
are to be free from burs, rust and scale.
313 The diameter of CO
2
pipes is to be based on the quantity
of CO
2
they are intended to carry. The maximum quantity of
CO
2
which may be carried through any pipeline is given in Ta-
ble B2. Deviations from the table may be accepted when doc-
umented by calculations, see 104.
314 Regarding manufacture, workmanship, inspection and
testing of pipes, see Ch.6 Sec.7. For CO
2
-manifolds the test
pressure may be accepted as 1,25 times design pressure.
315 The distribution manifolds and the pipes between the
cylinders and the manifolds are to be subject to a pressure test
of at least 1,25 times the relief valve setting, or minimum 125
bar prior to installation. After installation, pipe sections be-
tween cylinders and master valves as well as any release line
incorporated in the system are to be pneumatically pressure
tested to at least 50 bar. All piping from master valves to noz-
zles are to be tightness tested.
316 A function test of the system is to be carried out to verify
correct operating of release gear and alarms. The part of the gas
distribution piping that runs through accommodation spaces
are to be designed and tested in accordance with IMO MSC/
Circ.847, 5.1.2. All other piping is to be tested to ensure that it
is free from obstructions. As far as practicable, the function
testing is to be performed in the most realistic manner.
C. Low Pressure CO
2
Systems
C 100 General
101 The rated amount of carbon dioxide, time of discharge
into the protected space, location of nozzles in the protected
spaces and signals warning that the smothering system is acti-
vated are to comply with the requirements relating to CO
2
high-pressure systems specified in B100.
102 Vessels, refrigerating plants, control devices and other
equipment of the smothering system is to be located in CO
2
rooms which are to comply with the requirements for such
rooms of CO
2
high-pressure systems.
C 200 Vessels and relevant devices
201 The rated amount of liquid carbon dioxide is to be stored
in vessel(s) under the working pressure in the range of 18 to 22
bar.
Table B1 Minimum wall thickness for steel pipes for fire
extinguishing CO
2
pipes
External diameter D (mm) From CO
2
bot-
tles to valves
(mm)
From valves to
nozzles
(mm)
21,3 - 26,9 3,2 2,6
30,0 - 48,3 4,0 3,2
51,0 - 60,3 4,5 3,6
63,5 - 76,1 5,0 3,6
82,5 - 88,9 5,6 4,0
101,6 6,3 4,0
108,0 - 114,3 7,1 4,5
127,0 8,0 4,5
133,0 - 139,7 8,0 5,0
152,4 - 168,3 8,8 5,6
Remarks to the table:
1) The external diameter and thicknesses are in accordance with ISO Rec-
ommendations R 336 for welded and seamless steel pipes. For pipes
covered by other standards, thickness slightly less may be accepted.
2) The minimumwall thickness for larger diameters will be subject to spe-
cial consideration.
3) In general, the minimum wall thickness is the nominal wall thickness,
and no allowance need be made for negative tolerance and reduction in
thickness due to bending.
4) The minimumwall thickness for threaded pipes is to be measured at the
bottom of the thread.
Table B2 Maximum quantity of CO
2
which may be carried
through any pipeline
Maximum quantity of CO
2
Internal diameter of pipeline
45 kg 13 mm
100 kg 19 mm
135 kg 25 mm
275 kg 32 mm
450 kg 38 mm
1100 kg 50 mm
2000 kg 76 mm
3250 kg 89 mm
4750 kg 101 mm
6800 kg 114 mm
9500 kg 127 mm
15250 kg 152 mm
Rules for Ships, January 2001
Pt.4 Ch.10 Sec.3 Page 16
DET NORSKE VERITAS
The normal liquid charge in the container is to be limited to
provide sufficient vapour space to allow for expansion of the
liquid under the maximumstorage temperatures that can be ob-
tained corresponding to the setting of the pressure relief
valves, but is not to exceed 95% of the volumetric capacity of
the container.
202 The vessel(s) is to be designed, constructed and tested in
accordance with the requirements of the Society for liquefied
gas vessels under pressure, see Pt.5 Ch.5. For this purpose the
design pressure is to be taken not less than the relief valve set-
ting. Besides, provision is to be made for:
pressure gauge
high pressure alarm at 22 bar
low pressure alarm at 18 bar
diaphragm bleed valve
branch pipes with stop valves for filling the vessel
discharge pipes
liquid CO
2
level indicator, fitted on the vessel(s), and re-
mote level indicator located in the fire extinguishing sta-
tion
two safety relief valves arranged so that either valve can be
shut off while the other is connected to the vessel.
The setting of the relief valves is to be not less than 22 bar.
The capacity of each valve is to be such to discharge, with not
more than 20% rising pressure above the setting pressure, the
vapours generated under fire condition. The fire exposure fac-
tor F to be taken as 0,2 (see Pt.5 Ch.5 Sec.9 B216). The dis-
charge from the safety valves is to be led to the open.
203 The vessel and outgoing pipes permanently filled with
carbon dioxide are to have thermal insulation preventing the
operation of the safety valve in 24 hours after de-energizing the
plant, at ambient temperature of 45C.
C 300 Refrigerating plant
301 The vessel(s) is to be serviced by two automated com-
pletely independent refrigerating units solely intended for this
purpose, each comprising a compressor and the relevant prime
mover, evaporator and condenser.
302 The refrigerating plant is to comply with the require-
ments given in Pt.5 Ch.10 to the extent these are applicable.
The refrigerating capacity and the automatic control of each
unit are to be so as to maintain the required temperature under
conditions of continuous operation during 24 hours at the sea
temperature up to 32C and ambient air temperature up to
45C.
303 In the event of failure of either one of the refrigerating
units, the other is to be actuated automatically. Provision is to
be made for local manual control of the refrigerating plant.
304 Each electric refrigerating unit is to be supplied from the
main switchboard busbars by a separate feeder.
305 Cooling water supply to the refrigerating plant (where
required) is to be provided from at least two circulating pumps,
one of which being used as a standby. The standby pump may
be used for other services as long as its use for cooling would
not interfere with any other essential service of the ship.
C 400 Pipes and fittings
401 The pipes, valves and fittings are to be in accordance
with the requirements of the Society for a design pressure not
less than the design pressure of the CO
2
vessels.
402 Safety relief devices are to be provided in each section
of pipe that may be isolated by block valves and in which there
could be a build-up of pressure in excess of the design pressure
of any of the components.
403 The piping system is to be designed in such a way that
the CO
2
flows through in liquid phase up to the discharge noz-
zles. To this end the pressure at the nozzles are not to be less
than 10 bar.
C 500 Control of smothering system operation
501 The fire control station and the engineer's quarters are to
be equipped with audible and visual alarms activated when:
the pressure in the vessel(s) reaches the low and high val-
ues as per 202
any one of the refrigerating units fails to operate
the lowest permissible level of the liquid in the vessel is
reached
the release of CO
2
has been activated.
C 600 Release control
601 The release of CO
2
is to be manually initiated.
602 If a device is provided which automatically regulates the
discharge of the rated quantity of carbon dioxide into the pro-
tected spaces, it is also to be possible to regulate manually the
discharge.
C 700 Testing
701 The pipes, valves and fittings and assembled systems are
to be tested to the satisfaction of the Society.
702 In particular, the pipes from the vessel(s) to the release
valves on the distribution manifold are to be submitted to hy-
draulic test at pressure 1,5 times the design pressure.
703 All piping, after having been assembled on board, is to
be tested for tightness and free flow of the CO
2
.
704 The refrigerating plant, after having been fitted on
board, is to be checked for its proper operation.
705 At judgment of the Society, a discharge test may be re-
quired to check the fulfilment of the requirements of 403.
(IACS UR F34)
D. Halogenated Hydrocarbon Systems
D 100 Application
101 New installation of halogenated hydrocarbon systems
shall be prohibited on all new ships.
(SOLAS Reg. II-2/5.3.1)
Guidance note:
Gas fire-extinguishing systems for replacing or as an alternative
to Halon have been type approved by the Society, and tentative
rules for such systems are available upon request.
---e-n-d---of---G-u-i-d-a-n-c-e---n-o-t-e---
E. Steam Systems
E 100 General
101 In general, the Administration shall not permit the use of
steam as a fire-extinguishing medium in fixed fire-extinguishing
systems. Where the use of steam is permitted by the Adminis-
tration it shall be used only in restricted areas as an addition to
the required fire-extinguishing mediumand with the proviso that
the boiler or boilers available for supplying steam shall have an
evaporation of at least 1.0 kg of steam per hour for each 0.75
m
3
of the gross volume of the largest space so protected. In ad-
dition to complying with the foregoing requirements the sys-
tems in all respects shall be as determined by, and to the
satisfaction of, the Administration.
(SOLAS Reg. II-2/5.4)
Superheated steam will not be accepted.
Rules for Ships, January 2001
Pt.4 Ch.10 Sec.3 Page 17
DET NORSKE VERITAS
F. Other Gas Systems
F 100 General
101 Where gas other than carbon dioxide or halogenated hy-
drocarbons, or steam as permitted by paragraph 4 (E100) is
produced on the ship and is used as a fire-extinguishing medi-
um, it shall be a gaseous product of fuel combustion in which
the oxygen content, the carbon monoxide content, the corro-
sive elements and any solid combustible elements have been
reduced to a permissible minimum.
(SOLAS Reg. II-2/5.5.1)
102 Where such gas is used as the fire-extinguishing medium
in a fixed fire-extinguishing system for the protection of machin-
ery spaces it shall afford protection equivalent to that provided
by a fixed system using carbon dioxide as the medium.
(SOLAS Reg. II-2/5.5.2)
103 Where such gas is used as a fire-extinguishing medium
in a fixed fire-extinguishing system for the protection of cargo
spaces, a sufficient quantity of such gas shall be available to
supply hourly a volume of free gas at least equal to 25% of the
gross volume of the largest space protected in this way for a pe-
riod of 72 hours.
(SOLAS Reg. II-2/5.5.3)
Rules for Ships, January 2001
Pt.4 Ch.10 Sec.4 Page 18
DET NORSKE VERITAS
SECTION 4
FIRE EXTINGUISHERS
A. General
A 100 General requirements for all extinguishers
101 All fire extinguishers shall be of approved types and de-
signs.
(SOLAS Reg. II-2/6.1)
102 The capacity of required portable fluid extinguishers shall
be not more than 13.5 l and not less than 9 l. Other extinguish-
ers shall be at least as portable as the 13.5 l fluid extinguisher
and shall have a fire-extinguishing capability at least equivalent
to that of a 9 l fluid extinguisher.
(SOLAS Reg. II-2/6.1.1)
103 The Administration shall determine the equivalents of fire
extinguishers.
(SOLAS Reg. II-2/6.1.2)
Each powder or carbon dioxide extinguisher should have a ca-
pacity of at least 5 kg, and each foam extinguisher a capacity
of at least 9 litre.
(MSC/Circ. 847)
104 Spare charges shall be provided in accordance with re-
quirements to be specified by the Administration.
(SOLAS Reg. II-2/6.2)
A spare charge is to be provided for each required, portable fire
extinguisher which can be readily charged on board. If this
cannot be done, duplicate extinguishers are to be provided.
105 Fire extinguishers containing an extinguishing medium
which, in the opinion of the Administration, either by itself or un-
der expected conditions of use gives off toxic gases in such
quantities as to endanger persons shall not be permitted.
(SOLAS Reg. II-2/6.3)
106 The fire extinguishing medium in the extinguishers are
to be suitable for the potential fire hazards in the protected
spaces.
107 Fire extinguishers shall be periodically examined and
subjected to such tests as the Administration may require.
(SOLAS Reg. II-2/6.5)
Fire extinguishers are subject to periodical inspection in ac-
cordance with Pt.7 Ch.2 Sec.2.
108 One of the portable fire extinguishers intended for use in
any space shall be stowed near the entrance to that space.
(SOLAS Reg. II-2/6.6)
B. Portable Foam Applicator
B 100 Definition
101 A portable foam applicator unit shall consist of an air-
foam nozzle of an inductor type capable of being connected to
the fire main by a fire hose, together with a portable tank con-
taining at least 20 l of foam-making liquid and one spare tank.
The nozzle shall be capable of producing effective foam suita-
ble for extinguishing an oil fire, at the rate of at least 1.5 m
3
/
minute.
(SOLAS Reg. II-2/6.4)
B 200 Requirement
201 Number of required foam applicators are regulated in
Sec.5.
C. Portable Fire Extinguishers in Accommoda-
tion, Service Spaces and Control Stations
C 100 Requirement
101 Accommodation spaces, service spaces and control sta-
tions shall be provided with portable fire extinguishers of appro-
priate types and in sufficient number to the satisfaction of the
Administration. Ships of 1,000 gross tonnage and upwards
shall carry at least five portable fire extinguishers.
(SOLAS Reg. II-2/6.7)
In ships of less than 1000 gross tonnage, at least three portable
fire extinguishers are to be provided.
D. Fire Extinguishers in Machinery Spaces
D 100 Requirement
101 Number of requiredextinguishers are regulatedinSec.5.
Rules for Ships, January 2001
Pt.4 Ch.10 Sec.5 Page 19
DET NORSKE VERITAS
SECTION 5
FIRE EXTINGUISHING ARRANGEMENT IN MACHINERY SPACES
A. Spaces Containing Oil-fired Boilers or Oil
Fuel Units
A 100 General
101 Machinery spaces of category A containing oil-fired boil-
ers or oil fuel units shall be provided with any one of the follow-
ing fixed fire-extinguishing systems:
.1 a gas system complying with the provisions of Regulation
5 (Sec.3);
.2 a high expansion foam system complying with the provi-
sions of Regulation 9 (Sec.6);
.3 a pressure water-spraying system complying with the pro-
visions of Regulation 10 (Sec.6).
In each case if the engine and boiler rooms are not entirely sep-
arate, or if fuel oil can drain from the boiler room into the engine
room, the combined engine and boiler rooms shall be consid-
ered as one compartment.
(SOLAS Reg. II-2/7.1.1)
Guidance note:
Alternatively a type approved system complying with IMO
MSC/Circ.848 or IMO MSC/Circ.668 may be used.
---e-n-d---of---G-u-i-d-a-n-c-e---n-o-t-e---
102 There shall be in each boiler roomat least one set of port-
able foam applicator unit complying with the provisions of Reg-
ulation 6.4 (Sec.4 B).
(SOLAS Reg. II-2/7.1.2)
103 There shall be at least two portable foamextinguishers or
equivalent in each firing space in each boiler room and in each
space in which a part of the oil fuel installation is situated. There
shall be not less than one approved foam type extinguisher of
at least 135 l capacity or equivalent in each boiler room. These
extinguishers shall be provided with hoses on reels suitable for
reaching any part of the boiler room. In the case of domestic
boilers of less than 175 kW in cargo ships the Administration
may consider relaxing the requirements of this paragraph.
(SOLAS Reg. II-2/7.1.3)
50 kg dry powder or 45 kg CO
2
is considered as equivalent to
135 l foam liquid.
104 In each firing space there shall be a receptacle contain-
ing sand, sawdust impregnated with soda, or other approved
dry material in such quantity as may be required by the Admin-
istration. An approved portable extinguisher may be substituted
as an alternative.
(SOLAS Reg. II-2/7.1.4)
B. Spaces Containing Internal Combustion
Machinery
B 100 General
101 Machinery spaces of category A containing internal com-
bustion machinery shall be provided with:
.1 One of the fire-extinguishing systems required by para-
graph 1.1 (A101).
.2 At least one set of portable air-foam equipment complying
with the provisions of Regulation 6.4 (Sec.4 B).
.3 In each such space approved foam type fire extinguishers,
each of at least 45 l capacity or equivalent, sufficient in
number to enable foam or its equivalent to be directed on
to any part of the fuel and lubricating oil pressure systems,
gearing and other fire hazards. In addition, there shall be
provided a sufficient number of portable foam extinguish-
ers or equivalent which shall be so located that no point in
the space is more than 10 m walking distance from an ex-
tinguisher and that there are at least two such extinguish-
ers in each such space. For smaller spaces of cargo ships
the Administration may consider relaxing this requirement.
(SOLAS Reg. II-2/7.2)
25 kg dry powder or 20 kg CO
2
is considered as equivalent to
45 l foam liquid.
C. Spaces Containing Both Oil Fired Boilers and
Internal Combustion Machinery
C 100 General
101 In the case of machinery spaces containing both boilers
and internal combustion engines, both A100 and B100 must be
complied with, except that one of the foam fire-extinguishers
of at least 45 l capacity or equivalent (required in B101.3) may
be omitted on the condition that the 135 l foam extinguisher
(required in A103) can protect efficiently and readily the area
covered by the 45 l extinguisher. Only one portable foam ap-
plicator is required.
D. Spaces Containing Steam Turbines or Other
Enclosed Steam Engines
D 100 General
101 In spaces containing steam turbines or enclosed steam
engines used either for main propulsion or for other purposes
when such machinery has in the aggregate a total power output
of not less than 375 kW there shall be provided:
.1 Approved foam fire extinguishers each of at least 45 l ca-
pacity or equivalent sufficient in number to enable foam or
its equivalent to be directed on to any part of the pressure
lubrication system, on to any part of the casings enclosing
pressure lubricated parts of the turbines, engines or asso-
ciated gearing, and any other fire hazards. However, such
extinguishers shall not be required if protection at least
equivalent to that required by this sub-paragraph is provid-
ed in such spaces by a fixed fire-extinguishing system fit-
ted in compliance with paragraph 1.1 (A101).
.2 A sufficient number of portable foam extinguishers or
equivalent which shall be so located that no point in the
space is more than 10 m walking distance from an extin-
guisher and that there are at least two such extinguishers
in each such space, except that such extinguishers shall
not be required in addition to any provided in compliance
with paragraph 1.3 (A103).
.3 One of the fire-extinguishing systems required by para-
graph 1.1 (A101), where such spaces are periodically un-
attended.
(SOLAS Reg. II-2/7.3)
E. Fire-extinguishing Appliances in other
Machinery Spaces
E 100 General
101 Where, in the opinion of the Administration, a fire hazard
exists in any machinery space for which no specific provisions
for fire-extinguishing appliances are prescribed in paragraphs
1, 2 and 3 (A to D), there shall be provided in, or adjacent to,
that space such a number of approved portable fire extinguish-
Rules for Ships, January 2001
Pt.4 Ch.10 Sec.5 Page 20
DET NORSKE VERITAS
ers or other means of fire extinction as the Administration may
deem sufficient.
(SOLAS Reg. II-2/7.4).
F. Fixed Fire-extinguishing Systems not required
by this Chapter
F 100 General
101 Where a fixed fire-extinguishing system not required by
this Chapter is installed, such a system shall be to the satisfac-
tion of the Administration.
(SOLAS Reg. II-2/7.5)
G. Machinery Spaces of Category Ain Passenger
Ships
G 100 Fixed fire-extinguishing systems
101 When systems (such as purifiers) for preparing flamma-
ble liquids for use in boilers and machinery and separate oil
systems with working pressures above 15 bar and which are no
part of the main engines, boilers or auxiliary engines etc. are
placed in a separate roomenclosed by steel bulkheads and self-
closing door, a fixed fire-extinguishing system capable of be-
ing operated from outside that space is to be provided.
102 A local fixed fire-extinguishing unit is to be provided
for:
a) Separated oil systems referred to in 101 which, for practi-
cal reasons, cannot be located in a separated room.
b) Fuel installations which are not promptly accessible (e.g.
burners area of top-fired boilers, auxiliary boilers on plat-
forms or decks, etc.).
G 200 Fire-extinguishing appliances
201 In passenger ships carrying more than 36 passengers
each machinery space of category A is to be provided with at
least two suitable water fog applicators.
(SOLAS Reg. II-2/7.6)
Guidance note:
A water fog applicator might consist of a metal L-shaped pipe,
the long limb being about 2 m in length capable of being fitted to
a fire hose and the short limb being about 250 mmin length fitted
with a fixed water fog nozzle or capable of being fitted with a wa-
ter spray nozzle.
---e-n-d---of---G-u-i-d-a-n-c-e---n-o-t-e---
Rules for Ships, January 2001
Pt.4 Ch.10 Sec.6 Page 21
DET NORSKE VERITAS
SECTION 6
FIXED FOAM AND PRESSURE WATER SPRAYING FIRE EXTINGUISHING
SYSTEMS
A. General
A 100 Application
101 The requirements in this section apply to ships where a
fixed foam or pressure water spraying system is fitted in ma-
chinery spaces, special category spaces or in other spaces.
B. Fixed Low-Expansion Foam Fire - Extin-
guishing Systems in Machinery Spaces
B 100 General
101 Where in any machinery space a fixed low-expansion
foam fire-extinguishing system is fitted in addition to the re-
quirements of Regulation 7 (Sec.5), such system shall be capa-
ble of discharging through fixed discharge outlets in not more
than five minutes a quantity of foam sufficient to cover to a
depth of 150 mm the largest single area over which oil fuel is
liable to spread. The system shall be capable of generating
foam suitable for extinguishing oil fires. Means shall be provid-
ed for effective distribution of the foam through a permanent
system of piping and control valves or cocks to suitable dis-
charge outlets, and for the foam to be effectively directed by
fixed sprayers on other main fire hazards in the protected
space. The expansion ratio of the foamshall not exceed 12 to 1.
(SOLAS Reg. II-2/8.1)
102 The means of control of any such systems shall be read-
ily accessible and simple to operate and shall be grouped to-
gether in as few locations as possible at positions not likely to
be cut off by a fire in the protected space.
(SOLAS Reg. II-2/8.2)
103 The foam-forming liquid is to be of approved type.
C. Fixed High-Expansion Foam Fire - Extin-
guishing Systems in Machinery Spaces
C 100 General
101 Any required fixed high-expansion foam system in ma-
chinery spaces is to consist of components which are perma-
nently installed.
102 High-expansion foam generators are to be of approved
types.
103 The Administration may permit alternative arrangements
and discharge rates provided that it is satisfied that equivalent
protection is achieved.
(SOLAS Reg. II-2/9.1.2)
104 The foam-forming liquid is to be of an approved type.
C 200 Arrangement
201 The foam generator, its sources of power supply, foam-
forming liquid and means of controlling the system shall be
readily accessible and simple to operate and shall be grouped
in as few locations as possible at positions not likely to be cut
off by a fire in the protected space.
(SOLAS Reg. II-2/9.4)
202 The foam generator with equipment is to be placed in a
special room, safely separated from all the rooms to be protect-
ed in order to minimise the risk of damage to the generators
and ducts in event of fire or explosion in the rooms to be pro-
tected.
203 The arrangement of the foam generator is to permit test-
ing of the foam production without leading any foam to the
rooms to be protected, e.g. by providing means that permit
foam to pass overboard or to open deck.
204 Supply ducts for delivering foam, air intakes to the foam
generator and the number of foam-producing units shall in the
opinion of the Administration be such as will provide effective
foam production and distribution.
(SOLAS Reg. II-2/9.2)
205 The arrangement of the foam generator delivery ducting
shall be such that a fire in the protected space will not affect the
foam generating equipment.
(SOLAS Reg. II-2/9.3)
206 The high expansion foam is to be distributed to the re-
spective rooms by means of ducts that are led to at least the
lower edge of the casing. The ducts are to be dimensioned ac-
cording to the size of the foam generator's outlet, and are to be
so located that an even distribution of foam is obtained
throughout the room to be protected.
Where the engine room is divided into separate spaces (engine
room, boiler room, auxiliary engine room, separator room,
etc.) the foam is to be distributed to each separate space.
207 The ducts leading from the generators to the rooms to be
protected, are to be made of steel. They are to be dimensioned,
stiffened and fastened such that they can withstand the normal
mechanical and thermal strain they may be exposed to.
208 To avoid damage to the foam generators, open duct con-
nections from these to the rooms to be protected are not al-
lowed. Where the ducts leave the generator room, they are to
be provided with a closing appliance which is normally shut
and cannot be opened until the foam production has started. If
the closing appliance (the flap valve) is arranged for automatic
release, a manual release is also to be arranged. The closing ap-
pliance is to be of non-combustible material.
209 The arrangement in the engine room is to be such that
any possible overpressure in the room, caused by fire, can be
relieved when the room is being filled with foam. If this is
achieved by means of a skylight or ventilating aperture, a no-
tice plate stating that this is to be kept open whilst foam is be-
ing produced, is to be put up in the generator room. This will
be considered by the Society in each case.
210 The foam-forming liquid is to be stored in a special tank
and fed to the foam generator by a suitable system, which is to
be permanently adjusted for seawater consumption. The tank
is to be equipped with a level gauge of approved type. Foam-
forming liquid tanks are to be protected against inside corro-
sion.
211 The water tank for the first action (see 305) is to be
placed not lower than the foam generator. The arrangement is
to allow filling of the water tank from the fire pumps in the en-
gine room and also from the emergency fire pump. The water
tank is to be fitted with a level gauge of approved type and is
to be protected against inside corrosion.
212 For testing and drying purposes the piping system is to
be fitted with connection for blowing through with compressed
air.
Rules for Ships, January 2001
Pt.4 Ch.10 Sec.6 Page 22
DET NORSKE VERITAS
C 300 Capacity
301 Any required fixed high-expansion foam system in ma-
chinery spaces shall be capable of rapidly discharging through
fixed discharge outlets a quantity of foam sufficient to fill the
greatest space to be protected at a rate of at least 1 m in depth
per minute. The quantity of foam-forming liquid available shall
be sufficient to produce a volume of foamequal to five times the
volume of the largest space to be protected. The expansion ra-
tio of the foam shall not exceed 1,000 to 1.
(SOLAS Reg. II-2/9.1.1)
The largest space is to include casing if applicable, and the rate
of at least 1 m in depth per minute shall be calculated with re-
spect to maximum horizontal area of the room, without reduc-
tion for engines, boilers, loose tanks, etc.
The capacity is to be sufficient to fill the whole roomto the lev-
el of the main deck in the course of maximum 10 minutes.
302 In engine rooms where air intakes for auxiliary engines
are fitted with suitable filters enabling the engines to run whilst
immersed in foam, the capacity mentioned in 301 is to be in-
creased according to the air consumption of the respective en-
gines.
303 Engine and boiler rooms not completely separated, or
where fuel oil may pass from the boiler to the engine room, are
to be regarded as one room.
304 The quantity of foam forming liquid available is to be
sufficient to produce a volume of foam equal to five times the
volume of the largest space to be protected including casing.
305 Sufficient water is to be stored to produce a foam depth
of at least 7 m in the largest space to be protected.
306 The emergency fire pump is to have enough capacity to
supply the foam generators with sufficient water for maximum
foam production and, in addition, to supply 25 m
3
/h at the re-
quired pressure head to the fire main pipeline for ordinary fire
hose purposes.
C 400 Foam generator
401 The generator engine is to be certified by the Society.
402 The sources of power supply for the foam generator in-
cluding pumps, etc. are to be supplied independently of ma-
chinery or electrical installations located in the rooms to be
protected.
403 Foam generators are to be so constructed and assembled
that maintenance and replacement of essential parts can easily
be effected. The system is to be so arranged that nozzles and
pipes can easily be rinsed and drained.
404 All electrical components in connection with the foam
generator are to be totally enclosed.
405 Foam generators are to be made of corrosion resistant
materials. In this connection, stringent requirements will be
made regarding nozzles, pipes, fittings and filters coming into
direct contact with the foam-forming liquid.
406 The foam generator nozzles are to have as large open-
ings as possible. The nozzles are to be so constructed that they
have the least possible chance of getting choked.
407 The foam-forming net is to be made of a durable, non-
shrinking material that is rot- and heat-resistant.
408 The foam generator is to be supplied with a special air
intake dimensioned according to the air consumption of the
generator.
C 500 Foam generator room
501 Bulkheads and decks in the foam generator room adja-
cent to the rooms to be protected, are to have A-60 class di-
vision.
502 The generator room is to have a heating system which
can keep the room permanently free from frost.
503 The foam generator room is to have separate mechanical
ventilation for overpressure.
D. Pressure Water-Spraying Systems in Machin-
ery Spaces
D 100 General
101 Any required fixed pressure water-spraying fire-extin-
guishing system in machinery spaces shall be provided with
spraying nozzles of an approved type.
(SOLAS Reg. II-2/10.1)
102 The number and arrangement of the nozzles shall be to
the satisfaction of the Administration and shall be such as to en-
sure an effective average distribution of water of at least 5 l/m
2
per minute in the spaces to be protected. Where increased ap-
plication rates are considered necessary, these shall be to the
satisfaction of the Administration. Nozzles shall be fitted above
bilges, tank tops and other areas over which oil fuel is liable to
spread and also above other specific fire hazards in the ma-
chinery spaces.
(SOLAS Reg. II-2/10.2)
103 The system may be divided into sections, the distribution
valves of which shall be operated from easily accessible posi-
tions outside the spaces to be protected and will not be readily
cut off by a fire in the protected space.
(SOLAS Reg. II-2/10.3)
104 The system shall be kept charged at the necessary pres-
sure and the pump supplying the water for the system shall be
put automatically into action by a pressure drop in the system.
(SOLAS Reg. II-2/10.4)
105 The pump shall be capable of simultaneously supplying
at the necessary pressure all sections of the system in any one
compartment to be protected. The pump and its controls shall
be installed outside the space or spaces to be protected. It shall
not be possible for a fire in the space or spaces protected by the
water-spraying system to put the system out of action.
(SOLAS Reg. II-2/10.5)
106 The pump may be driven by independent internal com-
bustion machinery but, if it is dependent upon power being sup-
plied from the emergency generator fitted in compliance with
the provisions of Regulation II-1/44 (Ch.8 Sec.2 C) or Regula-
tion II-1/45 (Pt.5 Ch.2 Sec.2 D), as appropriate, that generator
shall be so arranged as to start automatically in case of main
power failure so that power for the pump required by paragraph
5 (105) is immediately available. When the pump is driven by
independent internal combustion machinery it shall be so situ-
ated that a fire in the protected space will not affect the air sup-
ply to the machinery.
(SOLAS Reg. II-2/10.6)
107 Precautions shall be taken to prevent the nozzles from
becoming clogged by impurities in the water or corrosion of pip-
ing, nozzles, valves and pump.
(SOLAS Reg. II-2/10.7)
E. Pressure Water Spraying Systems for Special
Category Spaces in Passenger Ships
E 100 General
101 The nozzles are to be of an approved full bore type. They
are to be arranged so as to secure an effective distribution of
water in the spaces which are to be protected. For this purpose,
the system is to be such as will provide water application at a
rate of at least 3,5 litres/m
2
/minute for spaces with a deck
height not exceeding 2,5 m and a capacity of at least 5 litres/
m
2
/minute for spaces with a deck height of 2,5 m or more.
Rules for Ships, January 2001
Pt.4 Ch.10 Sec.6 Page 23
DET NORSKE VERITAS
102 The water pressure is to be sufficient to secure an even
distribution of water.
103 The system is normally to cover the full breadth of the
vehicle deck and may be divided into sections provided they
are of at least 20 m in length, except that in ships where the ve-
hicle deck space is subdivided with longitudinal A Class di-
visions forming boundaries of staircases, etc., the breadth of
the sections may be reduced accordingly.
104 The distribution valves for the system are to be situated
in an easily accessible position adjacent to but outside the
space to be protected which will not readily be cut off by a fire
within the space. Direct access to the distribution valves from
the vehicle deck space and from outside that space is to be pro-
vided. Adequate ventilation is to be fitted in the space contain-
ing the distribution valves.
105 The water supply to the system is to be provided by a
pump or pumps other than the ship's required fire pumps which
are additionally to be connected to the system by a lockable
non-return valve which will prevent a back-flow from the sys-
tem into the fire main.
106 The principal pump or pumps are to be capable of pro-
viding simultaneously at all times a sufficient supply of water
at the required pressure to all nozzles in the vehicle deck or in
at least two sections thereof.
107 The principal pump or pumps are to be capable of being
brought into operation by remote control (which may be man-
ually actuated) from the position at which the distribution
valves are situated.
Rules for Ships, January 2001
Pt.4 Ch.10 Sec.7 Page 24
DET NORSKE VERITAS
SECTION 7
SPECIAL ARRANGEMENTS IN MACHINERY SPACES
A. General
A 100 Application
101 The provisions of this Regulation shall apply to machin-
ery spaces of category A and, where the Administration consid-
ers it desirable, to other machinery spaces.
(SOLAS Reg. II-2/11.1)
A 200 General requirements
201 The number of skylights, doors, ventilators, openings in
funnels to permit exhaust ventilation and other openings to ma-
chinery spaces shall be reduced to a minimum consistent with
the needs of ventilation and the proper and safe working of the
ship.
(SOLAS Reg. II-2/11.2.1)
202 Skylights shall be of steel and shall not contain glass
panels. Suitable arrangements shall be made to permit the re-
lease of smoke in the event of fire, fromthe space to be protect-
ed.
(SOLAS Reg. II-2/11.2.2)
Existing exhaust ventilation systems may be accepted as ar-
rangements for permitting the release of smoke.
203 Hatches to engine room for transport of goods are to be
weather-tight. Where remote control for closing of the hatch is
not provided, signboard to the effect that the hatch-cover is to
be closed at all times except during transfer of goods, shall be
posted.
204 In passenger ships, doors other than power-operated
watertight doors, are to be so arranged that positive closure is
assured in case of fire in the space, by power-operated closing
arrangements or by the provision of self-closing doors capable
of closing against an inclination of 3,5 opposing closure and
having a fail-safe hook-back facility, provided with a remotely
operated release device.
(SOLAS Reg. II-2/11.2.3)
205 Windows shall not be fitted in machinery space bounda-
ries. This does not preclude the use of glass in control rooms
within the machinery spaces.
(SOLAS Reg. II-2/11.3)
206 Means of control shall be provided for:
.1 opening and closure of skylights, closure of openings in
funnels which normally allow exhaust ventilation, and clo-
sure of ventilator dampers;
.2 permitting the release of smoke;
.3 closing power-operated doors or actuating release mech-
anism on doors other than power-operated watertight
doors;
.4 stopping ventilating fans; and
.5 stopping forced and induced draught fans, oil fuel transfer
pumps, oil fuel unit pumps and other similar fuel pumps.
(SOLAS Reg. II-2/11.4)
207 The controls required in paragraph 4 (206) and in Regu-
lation 15.2.5 (Ch.6 Sec.5 D501) shall be located outside the
space concerned, where they will not be cut off in the event of
fire in the space they serve. In passenger ships such controls
and the controls for any required fire-extinguishing system are
to be situated at one control position or grouped in as few posi-
tions as possible. Such positions are to have a safe access
from the open deck.
(SOLAS Reg. II-2/11.5)
208 When access to any machinery space of category A is
provided at a low level froman adjacent shaft tunnel, there shall
be provided in the shaft tunnel, near the watertight door, a light
steel fire-screen door operable from each side.
(SOLAS Reg. II-2/11.6)
209 For periodically unattended machinery spaces in cargo
ships, the Administration shall give special consideration to
maintaining fire integrity of the machinery spaces, the location
and centralization of the fire-extinguishing system controls, the
required shut-down arrangements (e.g. ventilation, fuel pumps,
etc.) and may require additional fire- extinguishing appliances
and other fire-fighting equipment and breathing apparatus. In
passenger ships these requirements are to be at least equiva-
lent to those of machinery spaces normally attended.
(SOLAS Reg. II-2/11.7)
210 A fixed fire detection and alarm system complying with
the provisions of Regulation 14 (Sec.9) shall be fitted in any ma-
chinery space:
.1 where the installation of automatic and remote control sys-
tems and equipment has been approved in lieu of continu-
ous manning of the space; and
.2 where the main propulsion and associated machinery in-
cluding sources of main electrical supply are provided with
various degrees of automatic or remote control and are un-
der continuous manned supervision from a control room.
(SOLAS Reg. II-2/11.8)
211 Materials used in machinery spaces are not normally to
have properties increasing the fire potential of these rooms.
212 Neither combustible nor oil-absorbing materials are to
be used as flooring, bulkhead lining, ceiling or deck in the con-
trol room, machinery spaces, shaft tunnel or rooms where oil
tanks are located. Where penetration of oil products is possi-
ble, the surface of the insulation is to be impervious to oil or oil
vapours.
Rules for Ships, January 2001
Pt.4 Ch.10 Sec.8 Page 25
DET NORSKE VERITAS
SECTION 8
AUTOMATIC SPRINKLER, FIRE DETECTION AND FIRE ALARM SYSTEMS
A. General
A 100 Application
101 The requirements in this section apply to ships where au-
tomatic sprinkler, fire detection and fire alarm systems are re-
quired to protect accommodation spaces, service spaces and
control stations.
A 200 General
201 Any required automatic sprinkler, fire detection and fire
alarm system shall be capable of immediate operation at all
times and no action by the crew shall be necessary to set it in
operation. It shall be of the wet pipe type but small exposed
sections may be of the dry pipe type where in the opinion of the
Administration this is a necessary precaution. Any parts of the
system which may be subjected to freezing temperatures in
service shall be suitably protected against freezing. It shall be
kept charged at the necessary pressure and shall have provi-
sion for a continuous supply of water as required in this Regu-
lation.
(SOLAS Reg. II-2/12.1.1)
202 Each section of sprinklers shall include means for giving
a visual and audible alarm signal automatically at one or more
indicating units whenever any sprinkler comes into operation.
Such alarm systems shall be such as to indicate if any fault oc-
curs in the system. Such units shall indicate in which section
served by the system fire has occurred and shall be centralized
on the navigation bridge and in addition, visible and audible
alarms from the unit shall be located in a position other than on
the navigation bridge, so as to ensure that the indication of fire
is immediately received by the crew.
(SOLAS Reg. II-2/12.1.2)
A 300 Arrangement
301 Sprinklers shall be grouped into separate sections, each
of which is to contain not more than 200 sprinklers. In passen-
ger ships any section of sprinklers shall not serve more than
two decks and shall not be situated in more than one main ver-
tical zone. However, such a section of sprinklers may be per-
mitted to serve more than two decks or be situated in more
than one main vertical zone, if it is satisfied that the protection
of the ship against fire will not thereby be reduced.
(SOLAS Reg. II-2/12.2.1)
302 Each section of sprinklers shall be capable of being iso-
lated by one stop valve only. The stop valve in each section
shall be readily accessible and its location shall be clearly and
permanently indicated. Means shall be provided to prevent the
operation of the stop valves by any unauthorized person.
(SOLAS Reg. II-2/12.2.2)
303 A gauge indicating the pressure in the system shall be
provided at each section stop valve and at a central station.
(SOLAS Reg. II-2/12.2.3)
304 The sprinklers shall be resistant to corrosion by marine
atmosphere. In accommodation and service spaces the sprin-
klers shall come into operation within the temperature range
from68 to 79C, except that in locations such as drying rooms,
where high ambient temperatures might be expected, the oper-
ating temperature may be increased by not more than 30C
above the maximum deckhead temperature.
(SOLAS Reg. II-2/12.2.4)
305 A list or plan shall be displayed at each indicating unit
showing the spaces covered and the location of the zone in re-
spect of each section. Suitable instructions for testing and
maintenance shall be available.
(SOLAS Reg. II-2/12.2.5)
A 400 Capacity
401 Sprinklers shall be placed in an overhead position and
spaced in a suitable pattern to maintain an average application
rate of not less than 5 l/m
2
/minute over the nominal area cov-
ered by the sprinklers. However, the Administration may permit
the use of sprinklers providing such an alternative amount of
water suitably distributed as has been shown to the satisfaction
of the Administration to be not less effective.
(SOLAS Reg. II-2/12.3)
402 A pressure tank having a volume equal to at least twice
that of the charge of water specified in this sub-paragraph shall
be provided. The tank shall contain a standing charge of fresh
water, equivalent to the amount of water which would be dis-
charged in one minute by the pump referred to in paragraph 5.2
(502), and the arrangements shall provide for maintaining an air
pressure in the tank such as to ensure that where the standing
charge of fresh water in the tank has been used the pressure
will be not less than the working pressure of the sprinkler, plus
the pressure exerted by a head of water measured fromthe bot-
tom of the tank to the highest sprinkler in the system. Suitable
means of replenishing the air under pressure and of replenish-
ing the fresh water charge in the tank shall be provided. A glass
gauge shall be provided to indicate the correct level of the water
in the tank.
(SOLAS Reg. II-2/12.4.1)
403 Means shall be provided to prevent the passage of sea-
water into the tank.
(SOLAS Reg. II-2/12.4.2)
A 500 Pumps and piping system
501 An independent power pump shall be provided solely for
the purpose of continuing automatically the discharge of water
from the sprinklers. The pump shall be brought into action au-
tomatically by the pressure drop in the systembefore the stand-
ing fresh water charge in the pressure tank is completely
exhausted.
(SOLAS Reg. II-2/12.5.1)
502 The pump and the piping system shall be capable of
maintaining the necessary pressure at the level of the highest
sprinkler to ensure a continuous output of water sufficient for
the simultaneous coverage of a minimum area of 280 m
2
at the
application rate specified in paragraph 3 (401).
(SOLAS Reg. II-2/12.5.2)
503 The pump shall have fitted on the delivery side a test
valve with a short open-ended discharge pipe. The effective
area through the valve and pipe shall be adequate to permit the
release of the required pump output while maintaining the pres-
sure in the system specified in paragraph 4.1 (402).
(SOLAS Reg. II-2/12.5.3)
504 The sea inlet to the pump shall wherever possible be in
the space containing the pump and shall be so arranged that
when the ship is afloat it will not be necessary to shut off the
supply of sea-water to the pump for any purpose other than the
inspection or repair of the pump.
(SOLAS Reg. II-2/12.5.4)
505 The sprinkler pump and tank shall be situated in a posi-
tion reasonably remote from any machinery space of category
A and shall not be situated in any space required to be protect-
ed by the sprinkler system.
(SOLAS Reg. II-2/12.6)
A 600 Power sources
601 In passenger ships there shall be not less than two sourc-
es of power supply for the seawater pump and automatic alarm
and detection system. Where the sources of power for the
Rules for Ships, January 2001
Pt.4 Ch.10 Sec.8 Page 26
DET NORSKE VERITAS
pump are electrical, these shall be a main generator and an
emergency source of power. One supply for the pump shall be
taken from the main switchboard, and one from the emergency
switchboard by separate feeders reserved solely for that pur-
pose. The feeders shall be so arranged as to avoid galleys, ma-
chinery spaces and other enclosed spaces of high fire risk
except in so far as it is necessary to reach the appropriate
switchboards, and shall be run to an automatic change-over
switch situated near the sprinkler pump. This switch shall per-
mit the supply of power from the main switchboard so long as a
supply is available therefrom, and be so designed that upon fail-
ure of that supply it will automatically change over to the supply
from the emergency switchboard. The switches on the main
switchboard and the emergency switchboard shall be clearly la-
belled and normally kept closed. No other switch shall be per-
mitted in the feeders concerned. One of the sources of power
supply for the alarmand detection system shall be an emergen-
cy source. Where one of the sources of power for the pump is
an internal combustion engine it shall, in addition to complying
with the provisions of paragraph 6 (505), be so situated that a
fire in any protected space will not affect the air supply to the
machinery.
(SOLAS Reg. II-2/12.7.1)
602 In cargo ships there shall not be less than two sources of
power supply for the sea-water pump and automatic alarm and
detection system. If the pump is electrically driven it shall be
connected to the main source of electrical power, which shall be
capable of being supplied by at least two generators. The feed-
ers shall be so arranged as to avoid galleys, machinery spaces
and other enclosed spaces of high fire risk except in so far as it
is necessary to reach the appropriate switchboards. One of the
sources of power supply for the alarm and detection system
shall be an emergency source. Where one of the sources of
power for the pump is an internal combustion engine it shall, in
addition to complying with the provisions of paragraph 6 (505),
be so situated that a fire in any protected space will not affect
the air supply to the machinery.
(SOLAS Reg. II-2/12.7.2)
603 The sprinkler system shall have a connection from the
ship's fire main by way of a lockable screw-down non-return
valve at the connection which will prevent a backflow from the
sprinkler system to the fire main.
(SOLAS Reg. II-2/12.8)
A 700 Testing
701 A test valve shall be provided for testing the automatic
alarm for each section of sprinklers by a discharge of water
equivalent to the operation of one sprinkler. The test valve for
each section shall be situated near the stop valve for that sec-
tion.
(SOLAS Reg. II-2/12.9.1)
702 Means shall be provided for testing the automatic opera-
tion of the pump on reduction of pressure in the system.
(SOLAS Reg. II-2/12.9.2)
703 Switches shall be provided at one of the indicating posi-
tions referred to in paragraph 1.2 (202) which will enable the
alarm and the indicators for each section of sprinklers to be
tested.
(SOLAS Reg. II-2/12.9.3)
704 Spare sprinkler heads shall be provided for each section
of sprinklers to the satisfaction of the Administration.
(SOLAS Reg. II-2/12.10)
Rules for Ships, January 2001
Pt.4 Ch.10 Sec.9 Page 27
DET NORSKE VERITAS
SECTION 9
FIXED FIRE DETECTION AND FIRE ALARM SYSTEMS
A. Fire Detection and Fire Alarm Systems
A 100 General
101 For instrumentation and automation, including compu-
ter based control and monitoring, the requirements in this
chapter are additional to those given in Ch.9.
102 Any required fixed fire detection and fire alarm system
with manually operated call points shall be capable of immedi-
ate operation at all times.
(SOLAS Reg. II-2/13.1.1)
103 Power supplies and electric circuits necessary for the op-
eration of the system shall be monitored for loss of power or
fault conditions as appropriate. Occurrence of a fault condition
shall initiate a visual and audible fault signal at the control panel
which shall be distinct from a fire signal.
(SOLAS Reg. II-2/13.1.2)
104 There shall be not less than two sources of power supply
for the electrical equipment used in the operation of the fire de-
tection and fire alarm system, one of which shall be an emer-
gency source The supply shall be provided by separate feeders
reserved solely for that purpose. Such feeders shall run to an
automatic change-over switch situated in or adjacent to the
control panel for the fire detection system.
(SOLAS Reg. II-2/13.1.3)
The main (respective emergency) feeder shall run from the
main (respective emergency) switchboard to the change-over
switch without passing through any other distribution switch-
board. (IACS UI SC35)
105 Detectors and manually operated call points shall be
grouped into sections. The activation of any detector or manu-
ally operated call point shall initiate a visual and audible fire sig-
nal at the control panel and indicating units. If the signals have
not received attention within two minutes an audible alarmshall
be automatically sounded throughout the crew accommodation
and service spaces, control stations and machinery spaces of
category A. This alarm sounder system need not be an integral
part of the detection system.
(SOLAS Reg. II-2/13.1.4)
The audible alarm is to be continuous and clearly distinguish-
able from other sound sources.
106 The control panel shall be located on the navigating
bridge or in the main fire control station.
(SOLAS Reg. II-2/13.1.5)
107 Indicating units shall, as a minimum, denote the section
in which a detector or manually operated call point has operat-
ed. At least one unit shall be so located that it is easily accessi-
ble to responsible members of the crew at all times, when at
sea or in port, except when the ship is out of service. One indi-
cating unit shall be located on the navigating bridge if the con-
trol panel is located in the main fire control station.
(SOLAS Reg. II-2/13.1.6)
108 Clear information shall be displayed on or adjacent to
each indicating unit about the spaces covered and the location
of the sections.
(SOLAS Reg. II-2/13.1.7)
109 Where the fire detection system does not include means
of remotely identifying each detector individually, no section
covering more than one deck within accommodation, service
and control stations shall normally be permitted except a sec-
tion which covers an enclosed stairway. In order to avoid delay
in identifying the source of fire, the number of enclosed spaces
included in each section shall be limited as determined by the
Administration. In no case shall more than fifty enclosed spaces
be permitted in any section. If the detection system is fitted with
remotely and individually identifiable fire detectors, the sections
may cover several decks and serve any number of enclosed
spaces.
(SOLAS Reg. II-2/13.1.8)
110 In passenger ships, if there is no fire detection systemca-
pable of remotely and individually identifying each detector, a
section of detectors shall not serve spaces on both sides of the
ship nor on more than one deck and neither shall it be situated
in more than one main vertical zone except that the Administra-
tion, if it is satisfied that the protection of the ship against fire will
not thereby be reduced, may permit such a section of detectors
to serve both sides of the ship and more than one deck. In pas-
senger ships fitted with individually identifiable fire detectors, a
section may serve spaces on both sides of the ship and on sev-
eral decks but may not be situated in more than one main ver-
tical zone.
(SOLAS Reg. II-2/13.1.9)
111 A section of fire detectors which covers a control station,
a service space or an accommodation space shall not include
a machinery space of category A.
(SOLAS Reg. II-2/13.1.10)
112 Detectors shall be operated by heat, smoke or other
products of combustion, flame, or any combination of these fac-
tors. Detectors operated by other factors indicative of incipient
fires may be considered by the Administration provided that
they are no less sensitive than such detectors. Flame detectors
shall only be used in addition to smoke or heat detectors.
(SOLAS Reg. II-2/13.1.11)
113 Suitable instructions and components spares for testing
and maintenance shall be provided.
(SOLAS Reg. II-2/13.1.12)
114 The function of the detection system shall be periodically
tested to the satisfaction of the Administration by means of
equipment producing hot air at the appropriate temperature, or
smoke or aerosol particles having the appropriate range of den-
sity or particle size, or other phenomena associated with incip-
ient fires to which the detector is designed to respond. All
detectors shall be of a type such that they can be tested for cor-
rect operation and restored to normal surveillance without the
renewal of any component.
(SOLAS Reg. II-2/13.1.13)
115 The fire detection system shall not be used for any other
purpose, except that closing of fire doors and similar functions
may be permitted at the control panel.
(SOLAS Reg. II-2/13.1.14)
116 When fire detectors are provided with the means to ad-
just their sensitivity, necessary arrangements are to be ensured
to fix and identify the set point.
117 When it is intended that a particular section or detector
is to be temporarily switched off, this state is to be clearly in-
dicated. Reactivation of the section or detector is to be per-
formed automatically after a preset time.
118 Fire detection systems with a zone address identification
capability fitted on or after 1 October 1994 shall be so arranged
that
a loop cannot be damaged at more than one point by a fire;
means are provided to ensure that any fault (e.g. power
break, short circuit; earth) occurring in the loop will not
render the whole loop ineffective;
all arrangements are made to enable the initial configura-
tion of the system to be restored in the event of failure
(electrical, electronic, informatic);
Rules for Ships, January 2001
Pt.4 Ch.10 Sec.9 Page 28
DET NORSKE VERITAS
the first initiated fire alarm will not prevent any other detec-
tor to initiate further fire alarms.
(SOLAS Reg. II-2/13.1.15)
A 200 Installation
201 Manually operated call points shall be installed through-
out the accommodation spaces, service spaces and control
stations. One manually operated call point shall be located at
each exit. Manually operated call points shall be readily acces-
sible in the corridors of each deck such that no part of the cor-
ridor is more than 20 m from a manually operated call point.
(SOLAS Reg. II-2/13.2.1)
202 Smoke detectors shall be installed in all stairways, corri-
dors and escape routes within accommodation spaces. Consid-
eration shall be given to the installation of special purpose
smoke detectors within ventilation ducting.
(SOLAS Reg. II-2/13.2.2)
203 Where a fixed fire detection and fire alarm system is re-
quired for the protection of spaces other than those specified in
paragraph 2.2 (202), at least one detector complying with par-
agraph 1.11 (112) shall be installed in each such space.
(SOLAS Reg. II-2/13.2.3)
204 Detectors shall be located for optimum performance. Po-
sitions near beams and ventilation ducts or other positions
where patterns of air flow could adversely affect performance
and positions where impact or physical damage is likely shall be
avoided. In general, detectors which are located on the over-
head shall be a minimum distance of 0.5 m away from bulk-
heads.
(SOLAS Reg. II-2/13.2.4)
205 The maximum spacing of detectors shall be in accord-
ance with the table (Table A1) below:
The Administration may require or permit other spacings based
upon test data which demonstrate the characteristics of the de-
tectors.
(SOLAS Reg. II-2/13.2.5)
206 Electrical wiring which forms part of the system shall be
so arranged as to avoid galleys, machinery spaces of category
A, and other enclosed spaces of high fire risk except where it is
necessary to provide for fire detection or fire alarm in such
spaces or to connect to the appropriate power supply.
(SOLAS Reg. II-2/13.2.6)
A 300 Design
301 The system and equipment shall be suitably designed to
withstand supply voltage variation and transients, ambient tem-
perature changes, vibration, humidity, shock, impact and corro-
sion normally encountered in ships.
(SOLAS Reg. II-2/13.3.1)
302 Smoke detectors required by paragraph 2.2 (202) shall
be certified to operate before the smoke density exceeds
12.5% obscuration per metre, but not until the smoke density
exceeds 2% obscuration per metre. Smoke detectors to be in-
stalled in other spaces shall operate within sensitivity limits to
the satisfaction of the Administration having regard to the
avoidance of detector insensitivity or over sensitivity.
(SOLAS Reg. II-2/13.3.2)
303 Heat detectors shall be certified to operate before the
temperature exceeds 78C but not until the temperature ex-
ceeds 54C, when the temperature is raised to those limits at a
rate less than 1C per minute. At higher rates of temperature
rise, the heat detector shall operate within temperature limits to
the satisfaction of the Administration having regard to the
avoidance of detector insensitivity or over sensitivity.
(SOLAS Reg. II-2/13.3.3)
304 At the discretion of the Administration, the permissible
temperature of operation of heat detectors may be increased to
30C above the maximum deckhead temperature in drying
rooms and similar spaces of a normal high ambient tempera-
ture.
(SOLAS Reg. II-2/13.3.4)
B. Sample Extraction Smoke Detection Systems
B 100 General
101 Wherever in the text of this regulation the word "system"
appears, it shall mean "sample extraction smoke detection sys-
tem".
(SOLAS Reg. II-2/13-1.1.1)
102 Any required system shall be capable of continuous op-
eration at all times except that systems operating on a sequen-
tial scanning principle may be accepted, provided that the
interval between scanning the same position twice gives an
overall response time to the satisfaction of the Administration.
(SOLAS Reg. II-2/13-1.1.2)
103 Power supplies necessary for the operation of the sys-
tem shall be monitored for loss of power. Any loss of power
shall initiate a visual and audible signal at the control panel and
the navigating bridge which shall be distinct from a signal indi-
cating smoke detection.
(SOLAS Reg. II-2/13-1.1.3)
104 An alternative power supply for the electrical equipment
used in the operation of the system shall be provided.
(SOLAS Reg. II-2/13-1.1.4)
105 The control panel shall be located on the navigating
bridge or in the main fire control station.
(SOLAS Reg. II-2/13-1.1.5)
106 The detection of smoke or other products of combustion
shall initiate a visual and audible signal at the control panel and
the navigating bridge.
(SOLAS Reg. II-2/13-1.1.6)
107 Clear information shall be displayed on or adjacent to the
control panel designating the spaces covered.
(SOLAS Reg. II-2/13-1.1.7)
108 The sampling pipe arrangements shall be such that the
location of the fire can be readily identified.
(SOLAS Reg. II-2/13-1.1.8)
109 Suitable instructions and component spares shall be pro-
vided for the testing and maintenance of the system.
(SOLAS Reg. II-2/13-1.1.9)
110 The system shall be of a type that can be tested for cor-
rect operation and restored to normal surveillance without the
renewal of any component. The functioning of the system shall
be periodically tested to the satisfaction of the Administration.
(SOLAS Reg. II-2/13-1.1.10)
(See also Pt.7 Ch.2.)
111 The system shall be designed, constructed and installed
so as to prevent the leakage of any toxic or flammable sub-
stances or fire-extinguishing media into any accommodation
and service space, control station or machinery space.
(SOLAS Reg. II-2/13-1.1.11)
B 200 Installation
201 At least one smoke accumulator shall be located in every
enclosed space for which smoke detection is required. Howev-
Table A1 Maximum spacing of detectors
Type of
detector
Maximum floor
area per detec-
tor
Maximum dis-
tance between
centres
Maximum dis-
tance away
from bulkheads
Heat 37 m
2
9 m 4,5 m
Smoke 74 m
2
11 m 5,5 m
Rules for Ships, January 2001
Pt.4 Ch.10 Sec.9 Page 29
DET NORSKE VERITAS
er, where a space is designed to carry oil or refrigerated cargo
alternatively with cargoes for which a smoke sampling system
is required, means may be provided to isolate the smoke accu-
mulators in such compartments for the system. Such means
shall be to the satisfaction of the Administration.
(SOLAS Reg. II-2/13-1.2.1)
202 Smoke accumulators shall be located for optimum per-
formance and shall be spaced so that no part of the overhead
deck area is more than 12 m measured horizontally from an ac-
cumulator. Where systems are used in spaces which may be
mechanically ventilated, the position of the smoke accumula-
tors shall be considered having regard to the effects of ventila-
tion.
(SOLAS Reg. II-2/13-1.2.2)
203 Smoke accumulators shall be positioned where impact or
physical damage is unlikely to occur.
(SOLAS Reg. II-2/13-1.2.3)
204 Not more than four accumulators shall be connected to
each sampling point.
(SOLAS Reg. II-2/13-1.2.4)
205 Smoke accumulators from more than one enclosed
space shall not be connected to the same sampling point.
(SOLAS Reg. II-2/13-1.2.5)
206 Sampling pipes shall be self-draining and suitably pro-
tected from impact or damage from cargo working.
(SOLAS Reg. II-2/13-1.2.6)
B 300 Design
301 The system and equipment shall be suitably designed to
withstand supply voltage variation and transients, ambient tem-
perature changes, vibration, humidity, shock, impact and corro-
sion normally encountered in ships and to avoid the possibility
of ignition of flammable gas air mixture.
(SOLAS Reg. II-2/13-1.3.1)
302 The sensing unit shall be certified to operate before the
smoke density within the sensing chamber exceeds 6.65% ob-
scuration per metre.
(SOLAS Reg. II-2/13-1.3.2)
303 Duplicate sample extraction fans shall be provided. The
fans shall be of sufficient capacity to operate with the normal
conditions or ventilation in the protected area and shall give an
overall response time to the satisfaction of the Administration.
(SOLAS Reg. II-2/13-1.3.3)
304 The control panel shall permit observation of smoke in
the individual sampling pipe.
(SOLAS Reg. II-2/13-1.3.4)
305 Means shall be provided to monitor the airflow through
the sampling pipes so designed as to ensure that as far as prac-
ticable equal quantities are extracted from each interconnected
accumulator.
(SOLAS Reg. II-2/13-1.3.5)
306 Sampling pipes shall be a minimum of 12 mm internal di-
ameter except when used in conjunction with fixed gas fire- ex-
tinguishing systems when the minimum size of pipe should be
sufficient to permit the fire-extinguishing gas to be discharged
within the appropriate time.
(SOLAS Reg. II-2/13-1.3.6)
307 Sampling pipes shall be provided with an arrangement
for periodically purging with compressed air.
(SOLAS Reg. II-2/13-1.3.7)
Rules for Ships, January 2001
Pt.4 Ch.10 Sec.10 Page 30
DET NORSKE VERITAS
SECTION 10
VENTILATION SYSTEMS
A. General
A 100 General requirements
101 Ventilation ducts shall be of non-combustible material.
Short ducts, however, not generally exceeding 2 m in length
and with a cross-section not exceeding 0.02 m
2
need not be
non-combustible, subject to the following conditions:
.1 these ducts shall be of a material which has low flame
spread characteristics;
.2 they may only be used at the end of the ventilation device;
.3 they shall not be situated less than 600 mm, measured
along the duct, from an opening in an "A" or "B" class divi-
sion including continuous "B" class ceilings.
(SOLAS Reg. II-2/16.1)
102 Where the ventilation ducts with a free-sectional area ex-
ceeding 0.02 m
2
pass through class "A" bulkheads or decks,
the opening shall be lined with a steel sheet sleeve unless the
ducts passing through the bulkheads or decks are of steel in the
vicinity of passage through the deck or bulkhead and the ducts
and sleeves shall comply in this part with the following:
.1 The sleeves shall have a thickness of at least 3 mm and a
length of at least 900 mm. When passing through bulk-
heads, this length shall be divided preferably into 450 mm
on each side of the bulkhead. These ducts, or sleeves lin-
ing such ducts, shall be provided with fire insulation. The
insulation shall have at least the same fire integrity as the
bulkhead or deck through which the duct passes. Equiva-
lent penetration protection may be provided to the satisfac-
tion of the Administration.
.2 Ducts with a free cross-sectional area exceeding 0.075 m
2
shall be fitted with fire dampers in addition to the require-
ments of paragraph 2.1 (102.1). The fire damper shall op-
erate automatically but shall also be capable of being
closed manually from both sides of the bulkhead or deck.
The damper shall be provided with an indicator which
shows whether the damper is open or closed. Fire damp-
ers are not required, however, where ducts pass through
spaces surrounded by "A" class divisions, without serving
those spaces, provided those ducts have the same fire in-
tegrity as the divisions which they pierce.
(SOLAS Reg. II-2/16.2)
103 Ducts provided for the ventilation of machinery spaces of
category A, galleys, car deck spaces, ro-ro cargo spaces or
special category spaces shall not pass through accommodation
spaces, service spaces or control stations unless the ducts are
either:
.1 constructed of steel having a thickness of at least 3 mm
and 5 mm for ducts the widths or diameters of which are up
to and including 300 mm and 760 mm and over respective-
ly and, in the case of such ducts, the widths or diameters
of which are between 300 mm and 760 mm having a thick-
ness to be obtained by interpolation;
.2 suitably supported and stiffened;
.3 fitted with automatic fire dampers close to the boundaries
penetrated; and
.4 insulated to "A-60" standard from the machinery spaces,
galleys, car deck spaces, ro-ro cargo spaces or special
category spaces to a point at least 5 m beyond each fire
damper; or
.5 constructed of steel in accordance with paragraphs 3.1.1
(103.1) and 3.1.2 (103.2); and
.6 insulated to "A-60" standard throughout the accommoda-
tion spaces, service spaces or control stations; except that
penetrations of main zone divisions shall also comply with
the requirements of paragraph 8 (109).
(SOLAS Reg. II-2/16.3)
104 Ducts provided for ventilation to accommodation spaces,
service spaces or control stations shall not pass through ma-
chinery spaces of category A, galleys, car deck spaces, ro-ro
cargo spaces or special category spaces unless either:
.1 the ducts where they pass through a machinery space of
category A, galley, car deck space, ro-ro cargo space or
special category space are constructed of steel in accord-
ance with paragraphs 3.1.1 (103.1) and 3.1.2 (103.2) ;
.2 automatic fire dampers are fitted close to the boundaries
penetrated; and
.3 the integrity of the machinery space, galley, car deck
space, ro-ro cargo space or special category space bound-
aries is maintained at the penetrations; or
.4 the ducts where they pass through a machinery space of
category A, galley, car deck space, ro-ro cargo space or
special category space are constructed of steel in accord-
ance with paragraphs 3.1.1 (103.1) and 3.1.2 (103.2) ; and
.5 are insulated to "A-60" standard within the machinery
space, galley, car deck space, ro-ro cargo space or special
category space; except that penetrations of main zone di-
visions shall also comply with the requirements of para-
graph 8 (109).
(SOLAS Reg. II-2/16.4)
105 Ventilation ducts with a free cross-sectional area exceed-
ing 0.02 m
2
passing through "B" class bulkheads shall be lined
with steel sheet sleeves of 900 mm in length divided preferably
into 450 mm on each side of the bulkheads unless the duct is
of steel for this length.
(SOLAS Reg. II-2/16.5)
106 Such measures as are practicable shall be taken in re-
spect of control stations outside machinery spaces in order to
ensure that ventilation, visibility and freedom from smoke are
maintained, so that in the event of fire the machinery and equip-
ment contained therein may be supervised and continue to
function effectively. Alternative and separate means of air sup-
ply shall be provided; air inlets of the two sources of supply shall
be so disposed that the risk of both inlets drawing in smoke si-
multaneously is minimized. At the discretion of the Administra-
tion, such requirements need not apply to control stations
situated on, and opening on to, an open deck, or where local
closing arrangements would be equally effective.
(SOLAS Reg. II-2/16.6)
As equally effective means, in case of ventilators these are to
be fitted with fire dampers which are to be easily closed within
the control station in order to maintain the absence of smoke in
the event of fire.
107 Galley ventilation systems are to be separate from the
ventilation systems serving other spaces. When passing
through accommodation spaces, service spaces and control
stations, galley ventilation ducts are to be constructed of steel
having a thickness as in 103.1 for the entire length passing
through such spaces. (IACS UI SC65)
108 Where they pass through accommodation spaces or
spaces containing combustible materials, the exhaust ducts
from galley ranges shall be constructed of "A" class divisions.
Each exhaust duct shall be fitted with:
.1 a grease trap readily removable for cleaning;
.2 a fire damper located in the lower end of the duct;
.3 arrangements, operable from within the galley, for shutting
off the exhaust fans; and
.4 fixed means for extinguishing a fire within the duct.
(SOLAS Reg. II-2/16.7)
109 Where in a passenger ship it is necessary that a ventila-
tion duct passes through a main vertical zone division, a fail-
safe automatic closing fire damper shall be fitted adjacent to the
Rules for Ships, January 2001
Pt.4 Ch.10 Sec.10 Page 31
DET NORSKE VERITAS
division. The damper shall also be capable of being manually
closed from each side of the division. The operating position
shall be readily accessible and be marked in red light- reflecting
colour. The duct between the division and the damper shall be
of steel or other equivalent material and, if necessary, insulated
to comply with the requirements of regulation 18.1.1 (Sec.12
A101). The damper shall be fitted on at least one side of the di-
vision with a visible indicator showing whether the damper is in
the open position.
(SOLAS Reg. II-2/16.8)
110 The main inlets and outlets of all ventilation systems shall
be capable of being closed from outside the spaces being ven-
tilated.
(SOLAS Reg. II-2/16.9)
111 Power ventilation of accommodation spaces, service
spaces, cargo spaces, control stations and machinery spaces
shall be capable of being stopped from an easily accessible po-
sition outside the space being served. This position should not
be readily cut off in the event of a fire in the spaces served. The
means provided for stopping the power ventilation of the ma-
chinery spaces shall be entirely separate from the means pro-
vided for stopping ventilation of other spaces.
(SOLAS Reg. II-2/16.10)
This applies to all ventilation fans (circulation fans included).
112 The following arrangements shall be tested in accord-
ance with the Fire Test Procedures Code:
.1 fire dampers, including relevant means of operation; and
.2 duct penetrations through "A" class divisions. Where steel
sleeves are directly joined to ventilation ducts by means of
riveted or screwed flanges or by welding, the test is not re-
quired.
(SOLAS Reg II-2/16.11)
113 High risk spaces such as purifier rooms separated from
machinery spaces with steel bulkheads and self-closing doors
are to have independent mechanical ventilation (see Ch.1
Sec.3 A400 ).
Rules for Ships, January 2001
Pt.4 Ch.10 Sec.11 Page 32
DET NORSKE VERITAS
SECTION 11
FIREMAN'S OUTFIT
A. General
A 100 Extent of outfit
101 A fireman's outfit shall consist of:
Only self-contained compressed-air-operated breathing appa-
ratus will be accepted onboard ships classed with the Society,
unless otherwise enforced by the flag Administration. At least
two refills are to be available for each compressed air breathing
apparatus.
Spare charges for breathing apparatus are to be stored in the
same location as the breathing apparatus.
102 For each breathing apparatus a fireproof lifeline of suffi-
cient length and strength shall be provided capable of being at-
tached by means of a snap hook to the harness of the
apparatus or to a separate belt in order to prevent the breathing
apparatus becoming detached when the lifeline is operated.
(SOLAS Reg. II-2/17.2)
A 200 Number of outfits
201 All ships shall carry at least two fireman's outfits comply-
ing with the requirements of paragraph 1 (100).
(SOLAS Reg. II-2/17.3)
202 In addition, there shall be provided:
.1 in passenger ships for every 80 m, or part thereof, of the
aggregate of the lengths of all passenger spaces and
service spaces on the deck which carries such spaces or,
if there is more than one such deck, on the deck which has
the largest aggregate of such lengths, two fireman's outfits
and two sets of personal equipment, each set comprising
the items stipulated in paragraphs 1.1.1 (101.1.1),
1.1.2(101.1.2) and 1.1.3 (101.1.3);
In passenger ships carrying more than 36 passengers, two
additional fireman's outfits shall be provided for each main
vertical zone; however, for stairway enclosures which con-
stitute individual main vertical zones and for the main ver-
tical zones in the fore or aft end of a ship which do not
contain spaces of categories 26.2.2(6), (7), (8) or (12) (Pt.5
Ch.2 Sec.2 E 702.2 (6), (7), (8) or (12), respectively), no
additional fireman's outfits are required.
.2 in tankers, two fireman's outfits.
(SOLAS Reg. II-2/17.3.1)
203 In passenger ships carrying more than 36 passengers for
each pair of breathing apparatus there shall be provided one
water fog applicator which shall be stored adjacent to such ap-
paratus.
(SOLAS Reg. II-2/17.3.2)
204 The Administration may require additional sets of per-
sonal equipment and breathing apparatus, having due regard
to the size and type of the ship.
(SOLAS Reg. II-2/17.3.3)
205 The fireman's outfits or sets of personal equipment shall
be so stored as to be easily accessible and ready for use and,
where more than one fireman's outfit or more than one set of
personal equipment is carried, they shall be stored in widely
separated positions. In passenger ships at least two fireman's
outfits and one set of personal equipment shall be available at
any one position.
(SOLAS Reg. II-2/17.4)
.1 Personal equipment comprising:
.1.1 Protective clothing of material to protect the skin from
the heat radiating from the fire and from burns and
scalding by steam. The outer surface shall be water-
resistant.
.1.2 Boots and gloves of rubber or other electrically non-
conducting material.
.1.3 A rigid helmet providing effective protection against
impact.
.1.4 An electric safety lamp (hand lantern) of an approved
type with a minimum burning period of three hours.
.1.5 An axe to the satisfaction of the Administration.
.2 A breathing apparatus of an approved type which may be
either:
.2.1 a smoke helmet or smoke mask which shall be pro-
vided with a suitable air pump and a length of air hose
sufficient to reach from the open deck, well clear of
hatch or doorway, to any part of the holds or machin-
ery spaces. If, in order to comply with this sub-para-
graph, an air hose exceeding 36 min length would be
necessary, a self-contained breathing apparatus
shall be substituted or provided in addition as deter-
mined by the Administration; or
.2.2 a self-contained compressed air-operated breathing
apparatus, the volume of air contained in the cylin-
ders of which shall be at least 1,200 l, or other self-
contained breathing apparatus which shall be capa-
ble of functioning for at least 30 minutes. A number of
spare charges, suitable for use with the apparatus
provided, shall be available on board to the satisfac-
tion of the Administration.
(SOLAS Reg. II-2/17.1)
Rules for Ships, January 2001
Pt.4 Ch.10 Sec.12 Page 33
DET NORSKE VERITAS
SECTION 12
MISCELLANEOUS ITEMS
A. General
A 100 Division penetrations
101 Where "A" class divisions are penetrated for the passage
of electric cables, pipes, trunks, ducts, etc., or for girders,
beams or other structural members, arrangements shall be
made to ensure that the fire resistance is not impaired, subject
to the provisions of Reg. 30.5 (Pt.5 Ch.2 Sec.2 E1105).
(SOLAS Reg. II-2/18.1.1)
102 Where "B" class divisions are penetrated for the passage
of electric cables, pipes, trunks, ducts, etc., or for the fitting of
ventilation terminals, lighting fixtures and similar devices, ar-
rangements shall be made to ensure that the fire resistance is
not impaired.
(SOLAS Reg. II-2/18.1.2)
A 200 Pipe materials
201 Pipes penetrating "A" or "B" class divisions shall be of
materials approved by the Administration having regard to the
temperature such divisions are required to withstand.
(SOLAS Reg. II-2/18.2.1)
202 Where the Administration may permit the conveying of oil
and combustible liquids through accommodation and service
spaces, the pipes conveying oil or combustible liquids shall be
of a material approved by the Administration having regard to
the fire risk.
(SOLAS Reg. II-2/18.2.2)
203 Materials readily rendered ineffective by heat shall not be
used for overboard scuppers, sanitary discharges, and other
outlets which are close to the water-line and where the failure
of the material in the event of fire would give rise to danger of
flooding.
(SOLAS Reg. II-2/18.2.3)
204 For the protection of cargo tanks carrying crude oil and
petroleum products having a flashpoint not exceeding 60C,
materials readily rendered ineffective by heat shall not be used
for valves, fittings, tank opening covers, cargo vent piping, and
cargo piping so as to prevent the spread of fire to the cargo.
(SOLAS Reg. II-2/18.2.4)
A 300 Electric radiators
301 Electric radiators, if used, shall be fixed in position and so
constructed as to reduce fire risks to a minimum. No such radi-
ators shall be fitted with an element so exposed that clothing,
curtains, or other similar materials can be scorched or set on
fire by heat from the element.
(SOLAS Reg. II-2/18.3)
A 400 Cellulose-nitrate based films
401 Cellulose-nitrate based films shall not be used for cine-
matograph installations.
(SOLAS Reg. II-2/18.4)
A 500 Waste-receptacles
501 All waste-receptacles shall be constructed of non-com-
bustible materials with no openings in the sides or bottom.
(SOLAS Reg. II-2/18.5)
A 600 Insulation surface
601 In spaces where penetration of oil products is possible,
the surface of insulation shall be impervious to oil or oil vapours.
(SOLAS Reg. II-2/18.6)
A 700 Paint lockers and flammable liquid lockers
701 Paint lockers and flammable liquid lockers shall be pro-
tected by an appropriate fire-extinguishing arrangement ap-
proved by the Administration.
(SOLAS Reg. II-2/18.7)
Paint lockers and flammable liquid lockers of deck area 4 m
2
and more shall be provided with a fire-extinguishing system
enabling the crew to extinguish a fire without entering the
space. Fixed arrangements as specified below may be provid-
ed.
1) CO
2
- system, designed for 40% of the gross volume of the
space.
2) Dry-powder-system, designed for at least 0,5 kg powder/
m
3
.
3) Water spraying system, designed for 5 l/m
2
, minimum.
4) Water spraying systems may be connected to the ship's
main system.
5) Other systems than those mentioned above may be accept-
ed.
6) For lockers of deck area less than 4 m
2
CO
2
or dry-powder
fire extinguisher(s) may be accepted.
(IACS UI SC80)
A 800 Seismic cables containing flammable liquids
801 Storage space for seismic cables, gun deck and other ar-
eas where equipment containing flammable liquids are han-
dled or stored, are to be protected by a fixed fire extinguishing
system.
Special attention is to be given to seismic vessels with a wood-
en gun deck above the steel deck, allowing for flammable liq-
uid to collect in the closed space. In such cases the fixed fire
extinguishing is also to protect the space below the wooden
deck.
Guidance note:
One suitable fixed fire extinguishing system is a low expansion
foam system with the following capacity:
- 3 litre/minute/m
2
of streamer deck area
- 10 litre/minute/m
2
of cable reels area.
Sufficient foam concentrate to ensure at least 20 minutes of foam
generation.
---e-n-d---of---G-u-i-d-a-n-c-e---n-o-t-e---
A 900 Use of asbestos
901 Concerning the use of asbestos, see Ch.1 Sec.2 A200.
Rules for Ships, January 2001
Pt.4 Ch.10 Sec.13 Page 34
DET NORSKE VERITAS
SECTION 13
ARRANGEMENT FOR HELICOPTER DECKS
A. General
A 100 Arrangement
101 Provisions for helicopter facilities shall be in accordance
with the standards developed by the Organization*.
(SOLAS Reg. II-2/18.8)
* Refer to the standards developed by the Organization by res. A.855(20).
Guidance note:
For offshore support vessels the requirements of Ch. 9.11.1 in the
MODU Code may be applied.
---e-n-d---of---G-u-i-d-a-n-c-e---n-o-t-e---
Rules for Ships, January 2001
Pt.4 Ch.10 Sec.14 Page 35
DET NORSKE VERITAS
SECTION 14
FIRE CONTROL PLANS AND DRILLS
A. General
A 100 Fire control plans
101 In all ships general arrangement plans shall be perma-
nently exhibited for the guidance of the ship's officers, showing
clearly for each deck the control stations, the various fire sec-
tions enclosed by "A" class divisions, the sections enclosed by
"B" class divisions together with particulars of the fire detection
and fire alarm systems, the sprinkler installation, the fire-extin-
guishing appliances, means of access to different compart-
ments, decks, etc. and the ventilating system including
particulars of the fan control positions, the position of dampers
and identification numbers of the ventilating fans serving each
section. Alternatively, at the discretion of the Administration, the
aforementioned details may be set out in a booklet a copy of
which shall be supplied to each officer, and one copy shall at all
times be available on board in an accessible position. Plans
and booklets shall be kept up to date, any alterations being re-
corded thereon as soon as practicable. Description in such
plans and booklets shall be in the official language of the flag
state. If the language is neither English nor French, a transla-
tion into one of those languages shall be included. In addition,
instructions concerning the maintenance and operation of all
the equipment and installations on board for the fighting and
containment of fire shall be kept under one cover, readily avail-
able in an accessible position.
(SOLAS Reg. II-2/20.1)
A translation into English is to be included.
Symbols shall be in accordance with IMO resolution
A.654(16) "Graphical symbols for fire control plans".
102 In ships carrying more than 36 passengers, plans and
booklets required by this regulation are to provide the informa-
tion regarding fire protection, fire detection and fire extinction
based on the guidelines issued by IMO in res. A.756(18).
(SOLAS Reg. II-2/20.4)
A 200 Maintenance and operation instructions
201 Instructions concerning the maintenance and operation
of all the equipment and installations on board for the fighting
and containment of fire are to be kept under one cover, readily
available in an accessible position.
A 300 Plans outside deckhouse
301 In all ships a duplicate set of fire control plans or a book-
let containing such plans shall be permanently stored in a prom-
inently marked weathertight enclosure outside the deckhouse
for the assistance of shoreside fire-fighting personnel.
(SOLAS Reg. II-2/20.2)
A 400 Fire drills
401 Fire drills shall be conducted in accordance with the pro-
visions of regulation III/19 (Pt.7 Ch.3 Sec.2 C100).
(SOLAS Reg. II-2/20.3)
Rules for Ships, January 2001
Pt.4 Ch.10 Sec.15 Page 36
DET NORSKE VERITAS
SECTION 15
FIRE SAFETY MEASURES FOR CARGO SHIPS
A. General
A 100 Application
101 The requirements in this section apply to cargo ships of
and above 500 gross tonnage.
A 200 Rule references
201 Special requirements for ships carrying dangerous
goods are given in Pt.5 Ch.11.
B. Fire Protection and Means of Escape
B 100 Structure
101 Subject to the provisions of paragraph 4 (104), the hull,
superstructure, structural bulkheads, decks and deckhouses
shall be constructed of steel or other equivalent material.
(SOLAS Reg. II-2/42.1)
102 The insulation of aluminium alloy components of "A" or
"B" class divisions, except structure which in the opinion of the
Administration is non-load-bearing, shall be such that the tem-
perature of the structural core does not rise more than 200C
above the ambient temperature at any time during the applica-
ble exposure to the standard fire test.
(SOLAS Reg. II-2/42.2)
103 Special attention shall be given to the insulation of alu-
minium alloy components of columns, stanchions and other
structural members required to support lifeboat and liferaft
stowage, launching and embarkation areas, and "A" and "B"
class divisions, to ensure:
.1 that for such members supporting lifeboat and liferaft are-
as and "A" class divisions, the temperature rise limitation
specified in paragraph 2 (102) shall apply at the end of one
hour; and
.2 that for such members required to support "B" class divi-
sions, the temperature rise limitation specified in para-
graph 2 (102) shall apply at the end of half an hour.
(SOLAS Reg. II-2/42.3)
104 Crowns and casings of machinery spaces of category A
shall be of steel construction adequately insulated and open-
ings therein, if any, shall be suitably arranged and protected to
prevent the spread of fire.
(SOLAS Reg. II-2/42.4)
Crowns and casings exposed to the open air need not be insu-
lated. (IACS UI SC44)
105 One of the following methods of protection shall be
adopted in accommodation and service areas:
.1 Method IC - The construction of all internal divisional bulk-
heading of non-combustible "B" or "C" class divisions gen-
erally without the installation of an automatic sprinkler, fire
detection and fire alarm system in the accommodation and
service spaces, except as required by Regulation 52.1
(D101); or
.2 Method IIC - The fitting of an automatic sprinkler, fire de-
tection and fire alarm system as required by Regulation
52.2 (D102) for the detection and extinction of fire in all
spaces in which fire might be expected to originate, gener-
ally with no restriction on the type of internal divisional
bulkheading; or
.3 Method IIIC - The fitting of a fixed fire detection and fire
alarmsystem, as required by Regulation 52.3 (D103), in all
spaces in which a fire might be expected to originate, gen-
erally with no restriction on the type of internal divisional
bulkheading, except that in no case must the area of any
accommodation space or spaces bounded by an "A" or "B"
class division exceed 50 m
2
. Consideration may be given
by the Administration to increasing this area for public
spaces.
(SOLAS Reg. II-2/42.5)
106 The requirements for the use of non-combustible materi-
als in construction and insulation of the boundary bulkheads of
machinery spaces, control stations, service spaces, etc., and
the protection of stairway enclosures and corridors will be com-
mon to all three methods outlined in paragraph 5 (105).
(SOLAS Reg. II-2/42.6)
B 200 Bulkheads within the accommodation and service
spaces
201 All bulkheads required to be "B" class divisions shall ex-
tend from deck to deck and to the shell or other boundaries, un-
less continuous "B" class ceilings or linings are fitted on both
sides of the bulkhead in which case the bulkhead may termi-
nate at the continuous ceiling or lining.
(SOLAS Reg. II-2/43.1)
202 Method IC - All bulkheads not required by this or other
Regulations of this Part to be "A" or "B" class divisions, shall be
of at least "C" class construction.
(SOLAS Reg. II-2/43.2)
203 Method IIC - There shall be no restriction on the con-
struction of bulkheads not required by this or other regulations
of this Part to be "A" or "B" class divisions except in individual
cases where "C" class bulkheads are required in accordance
with table 44.1 (Table B1).
(SOLAS Reg. II-2/43.3)
204 Method IIIC - There shall be no restriction on the con-
struction of bulkheads not required by this Part to be "A" or "B"
class divisions except that the area of any accommodation
space or spaces bounded by a continuous "A" or "B" class divi-
sion must in no case exceed 50 m
2
except in individual cases
where "C" class bulkheads are required in accordance with ta-
ble 44.1 (Table B1). Consideration may be given by the Admin-
istration to increasing this area for public space.
(SOLAS Reg. II-2/43.4)
B 300 Fire integrity of bulkheads and decks
301 In addition to complying with the specific provisions for
fire integrity of bulkheads and decks mentioned elsewhere in
this Part, the minimum fire integrity of bulkheads and decks
shall be as prescribed in tables 44.1 and 44.2 (Table B1 and
B2).
(SOLAS Reg. II-2/44.1)
302 The following requirements shall govern application of
the tables:
.1 Tables 44.1 and 44.2 (Table B1 and B2) shall apply re-
spectively to the bulkheads and decks separating adjacent
spaces.
.2 For determining the appropriate fire integrity standards to
be applied to divisions between adjacent spaces, such
spaces are classified according to their fire risk as shown
in categories (1) to (11) below. The title of each category is
intended to be typical rather than restrictive. The number
in parentheses preceding each category refers to the ap-
plicable column or row in the tables.
1) Control stations
Spaces containing emergency sources of power and
lighting. Wheelhouse and chartroom. Spaces contain-
ing the ship's radio equipment. Fire-extinguishing
rooms, fire control rooms and fire-recording stations.
Rules for Ships, January 2001
Pt.4 Ch.10 Sec.15 Page 37
DET NORSKE VERITAS
Control room for propulsion machinery when located
outside the machinery space. Spaces containing cen-
tralized fire alarm equipment.
Navigation equipment room (radio transmitter). Bat-
tery rooms. (Requirements for location of the emer-
gency source of electrical power are further given in
Ch.8 Sec.2 C).
2) Corridors
Corridors and lobbies.
3) Accommodation spaces
Spaces as defined in Reg. 3.10 (Sec.1 C302), exclud-
ing corridors.
4) Stairways
Interior stairways, lifts and escalators (other than those
wholly contained within the machinery spaces) and en-
closures thereto. In this connection, a stairway which
is enclosed only at one level shall be regarded as part
of the space from which it is not separated by a fire
door.
5) Service spaces (low risk)
Lockers and store-rooms not having provisions for the
storage of flammable liquids and having areas less
than 4 m
2
and drying rooms and laundries.
Provision chambers are to be treated as store rooms.
Refrigerated provision chambers are considered as
category (5) Service spaces if thermally insulated with
non-combustible materials.
6) Machinery spaces of category A
Spaces as defined in Regulation 3.19 (Sec.1 C311).
7) Other machinery spaces
Spaces as defined in Regulation 3.20 (Sec.1 C312) ex-
cluding machinery spaces of category A;
Electrical equipment rooms (auto telephone ex-
change, air conditioning duct spaces).
8) Cargo spaces
All spaces used for cargo (including cargo oil tanks)
and trunkways and hatchways to such spaces.
9) Service spaces (high risk)
Galleys, pantries containing cooking appliances, paint
and lamp rooms, lockers and store-rooms having are-
as of 4 m
2
or more, spaces for the storage of flamma-
ble liquids, and workshops other than those forming
part of the machinery spaces.
Provision chambers are to be treated as store rooms.
Refrigerated provision chambers are considered as
category (9) service spaces if thermally insulated with
combustible materials.
10) Open decks
Open deck spaces and enclosed promenades having
no fire risk. Air spaces (the space outside superstruc-
tures and deck-houses).
11) Ro-ro cargo spaces
Spaces as defined in Regulation 3.14 (Sec.1 C306).
Cargo spaces intended for the carriage of motor vehi-
cles with fuel in their tanks for their own propulsion.
(SOLAS Reg. II-2/44.2, IACS UI SC45)
303 Continuous "B" class ceilings or linings, in association
with the relevant decks or bulkheads, may be accepted as con-
tributing, wholly or in part, to the required insulation and integ-
rity of a division.
(SOLAS Reg. II-2/44.3)
304 External boundaries which are required in Regulation
42.1 (101) to be of steel or other equivalent material may be
pierced for the fitting of windows and sidescuttles provided that
there is no requirement for such boundaries to have "A" class
integrity elsewhere in this Part. Similarly, in such boundaries
which are not required to have "A" class integrity, doors may be
of materials to the satisfaction of the Administration.
(SOLAS Reg. II-2/44.4)
305 The required division of steel between control stations
and open decks may in the case of an emergency generator be
provided with openings for intake of combustion air to the die-
sel engine and for intake of cooling air in the case of an air
cooled diesel engine. These openings needed not be fitted with
means for closure for fire integrity purposes, unless a fixed gas
fire fighting system for the emergency generator space is fit-
ted.
(IACS UI SC66)
Table B1 Fire integrity of bulkheads separating adjacent spaces
Spaces below above (1) (2) (3) (4) (5) (6) (7) (8) (9) (10) (11)
Control stations (1) A-0
5)
A-0 A-60 A-0 A-15 A-60 A-15 A-60 A-60 *) A-60
Corridors (2) C B-0 B-0
A-0
3)
B-0 A-60 A-0 A-0 A-0 *) A-30
Accommodation spaces (3) C
1)2)
B-0
A-0
3)
B-0 A-60 A-0 A-0 A-0 *) A-30
Stairways (4) B-0
A-0
3)
B-0
A-0
3)
A-60 A-0 A-0 A-0 *)
*)
A-30
Service spaces (low risk) (5) C A-60 A-0 A-0 A-0 *) A-0
Machinery spaces of category A (6) *) A-0 A-0
7)
A-60 *) A-
60
6)
Other machinery spaces (7) A-0
4)
A-0 A-0 *) A-0
Cargo spaces (8) *) A-0 *) A-0
Service spaces (high risk) (9) A-0
4)
*) A-30
Open decks (10) - A-0
Ro-ro cargo spaces (11) *)
8)
See notes under Table B2.
Rules for Ships, January 2001
Pt.4 Ch.10 Sec.15 Page 38
DET NORSKE VERITAS
B 400 Means of escape
401 Stairways and ladders shall be so arranged as to pro-
vide, from all accommodation spaces and from spaces in which
the crew is normally employed, other than machinery spaces,
ready means of escape to the open deck and thence to the life-
boats and liferafts. In particular the following general provisions
shall be complied with:
.1 At all levels of accommodation there shall be provided at
least two widely separated means of escape from each re-
stricted space or group of spaces.
.2 Below the lowest open deck the main means of escape
shall be a stairway and the second escape may be a trunk
or a stairway.
.3 Above the lowest open deck the means of escape shall be
stairways or doors to an open deck or a combination there-
of.
.4 Exceptionally the Administration may dispense with one of
the means of escape, due regard being paid to the nature
and location of spaces and to the numbers of persons who
normally might be quartered or employed there.
.5 No dead-end corridors having a length of more than 7 m
shall be accepted. A dead-end corridor is a corridor or part
of a corridor from which there is only one escape route.
.6 The width and continuity of the means of escape shall be
to the satisfaction of the Administration.
.7 If a radiotelegraph station has no direct access to the open
deck, two means of access to or egress from such station
shall be provided, one of which may be a porthole or win-
dow of sufficient size or other means to the satisfaction of
the Administration, to provide an emergency escape.
(SOLAS Reg. II-2/45.1)
402 In all ro-ro cargo spaces where the crew is normally em-
ployed the number and locations of escape routes to the open
deck shall be to the satisfaction of the Administration, but shall
in no case be less than two and shall be widely separated.
(SOLAS Reg. II-2/45.2)
403 Except as provided in paragraph 4 (404), two means of
escape shall be provided from each machinery space of cate-
gory A. In particular, one of the following provisions shall be
complied with:
.1 two sets of steel ladders as widely separated as possible
leading to doors in the upper part of the space similarly
separated and from which access is provided to the open
deck. In general, one of these ladders shall provide contin-
uous fire shelter from the lower part of the space to a safe
position outside the space. However, the Administration
may not require the shelter if, due to the special arrange-
ment or dimensions of the machinery space, a safe escape
route from the lower part of this space is provided. This
shelter shall be of steel, insulated, where necessary, to the
satisfaction of the Administration and be provided with a
self-closing steel door at the lower end; or
.2 one steel ladder leading to a door in the upper part of the
space from which access is provided to the open deck and
additionally, in the lower part of the space and in a position
well separated from the ladder referred to, a steel door ca-
pable of being operated from each side and which pro-
vides access to a safe escape route from the lower part of
the space to the open deck.
(SOLAS Reg. II-2/45.3)
404 In a ship of less than 1,000 gross tonnage, the Adminis-
tration may dispense with one of the means of escape required
under paragraph 3 (403), due regard being paid to the dimen-
sion and disposition of the upper part of the space.
(SOLAS Reg. II-2/45.4)
405 From machinery spaces other than those of category A,
escape routes shall be provided to the satisfaction of the Ad-
ministration having regard to the nature and location of the
space and whether persons are normally employed in that
space.
(SOLAS Reg. II-2/45.5)
406 Lifts shall not be considered as forming one of the re-
quired means of escape required by this Regulation.
(SOLAS Reg. II-2/45.6)
Table B2 Fire integrity of decks separating adjacent spaces
Spaces below above (1) (2) (3) (4) (5) (6) (7) (8) (9) (10) (11)
Control stations (1) A-0 A-0 A-0 A-0 A-0 A-60 A-0 A-0 A-0 *) A-60
Corridors (2) A-0 *) *) A-0 *) A-60 A-0 A-0 A-0 *) A-30
Accommodation spaces (3) A-60 A-0 *) A-0 *) A-60 A-0 A-0 A-0 *) A-30
Stairways (4) A-0 A-0 A-0 *) A-0 A-60 A-0 A-0 A-0 *) A-30
Service spaces (low risk) (5) A-15 A-0 A-0 A-0 *) A-60 A-0 A-0 A-0 *) A-0
Machinery spaces of category A (6) A-60 A-60 A-60 A-60 A-60 *) A-60
9)
A-30 A-60 *) A-60
Other machinery spaces (7) A-15 A-0 A-0 A-0 A-0 A-0 *) A-0 A-0 *) A-0
Cargo spaces (8) A-60 A-0 A-0 A-0 A-0 A-0 A-0 *) A-0 *) A-0
Service spaces (high risk) (9) A-60 A-0 A-0 A-0 A-0 A-60 A-0 A-0 A-0
4)
*) A-30
Open decks (10) *) *) *) *) *) *) *) *) *) - *)
Ro-ro cargo spaces (11) A-60 A-30 A-30 A-30 A-0 A-60 A-0 A-0 A-30 *) *)
8)
To be applied to both Tables B1 and B2, as appropriate.
1) No special requirements are imposed upon bulkheads in methods IIC and IIIC fire protection.
2) In case of method IIIC B class bulkheads of B-0 rating shall be provided between spaces or groups of spaces of 50 m
2
and over in area.
3) For clarification as to which applies, see 200 and 500.
4) Where spaces are of the same numerical category and superscript 4) appears, a bulkhead or deck of the rating shown in the tables is only required when
the adjacent spaces are for a different purpose, e.g. in category (9). A galley next to a galley does not require a bulkhead but a galley next to a paint room
or a galley next to a provision store requires an A-0 bulkhead.
5) Bulkheads separating the wheelhouse, chartroom and radio room from each other may be B-0 rating.
6) A-0 rating may be used if no dangerous goods are intended to be carried or if such goods are stowed not less than 3 m horizontally from such bulkhead.
7) Cargo spaces in which dangerous goods are intended to be carried will be specially considered.
8) Bulkheads and decks separating ro-ro cargo spaces shall be capable of being closed reasonably gastight and such divisions shall have A class integrity
in so far as is reasonable and practicable.
9) Fire insulation need not be fitted if the machinery space in category (7) has little or no fire risk.
* Where an asterisk appears in the tables, the division is required to be of steel or other equivalent material but is not required to be
of A class standard.
Rules for Ships, January 2001
Pt.4 Ch.10 Sec.15 Page 39
DET NORSKE VERITAS
B 500 Protection of stairways and lift trunks in accom-
modation spaces, service spaces and control stations
501 Stairways which penetrate only a single deck shall be
protected at least at one level by at least "B-0" class divisions
and self-closing doors. Lifts which penetrate only a single deck
shall be surrounded by "A-0" class divisions with steel doors at
both levels. Stairways and lift trunks which penetrate more than
a single deck shall be surrounded by at least "A-0" class divi-
sions and be protected by self-closing doors at all levels.
(SOLAS Reg. II-2/46.1)
Dumb waiters are to be regarded as lifts. (IACS UI SC46)
502 On ships having accommodation for 12 persons or less,
where stairways penetrate more than a single deck and where
there are at least two escape routes direct to the open deck at
every accommodation level, consideration may be given by the
Administration to reducing the "A-0" requirements of paragraph
1 (501) to "B-0".
(SOLAS Reg. II-2/46.2)
503 All stairways shall be of steel frame construction except
where the Administration sanctions the use of other equivalent
material.
(SOLAS Reg. II-2/46.3)
B 600 Doors in fire resisting divisions
601 The fire resistance of doors shall, as far as practicable,
be equivalent to that of the division in which they are fitted.
Doors and door frames in "A" class divisions shall be construct-
ed of steel. Doors in "B" class divisions shall be non-combusti-
ble. Doors fitted in boundary bulkheads of machinery spaces of
category A shall be reasonably gastight and self-closing. In
ships constructed according to method IC, an Administration
may permit the use of combustible materials in doors separat-
ing cabins fromindividual interior sanitary accommodation such
as showers.
(SOLAS Reg. II-2/47.1)
602 Doors required to be self-closing shall not be fitted with
hold-back hooks. However, hold-back arrangements fitted with
remote release devices of the fail-safe type may be utilized.
(SOLAS Reg. II-2/47.2)
603 In corridor bulkheads ventilation openings may be per-
mitted only in and under the doors of cabins and public spaces.
The openings shall be provided only in the lower half of a door.
Where such opening is in or under a door the total net area of
any such opening or openings shall not exceed 0.05 m
2
. When
such opening is cut in a door it shall be fitted with a grille made
of non-combustible material.
(SOLAS Reg. II-2/47.3)
Ventilation openings may also be permitted in "B" class doors
leading to lavatories, offices, pantries, lockers, store rooms etc.
(IACS UI SC67)
604 Watertight doors need not be insulated.
(SOLAS Reg. II-2/47.4)
Watertight doors in fire resisting divisions are to be made from
steel.
B 700 Ventilation systems
701 The ventilation systems of cargo ships shall be in compli-
ance with the provisions of Regulation 16, except paragraph 8
(Sec.10 except A109).
(SOLAS Reg. II-2/48.1)
B 800 Restricted use of combustible materials
801 All exposed surfaces in corridors and stairway enclo-
sures and surfaces including grounds in concealed or inacces-
sible spaces in accommodation and service spaces and control
stations shall have low flame-spread characteristics *. Exposed
surfaces of ceilings in accommodation and service spaces and
control stations shall have low flame-spread characteristics.
(SOLAS Reg. II-2/49.1)
* Refer to the Guidelines on the evaluation of fire hazard properties
of materials adopted by IMO by resolution A.166(ES.IV) and to the
Recommendation on improved fire test procedures for surface
flammability of bulkhead, ceiling and deck finish materials adopted
by IMO by resolution A.653(16).
802 Paints, varnishes and other finishes used on exposed in-
terior surfaces shall not be capable of producing excessive
quantities of smoke and toxic products, this being determined
in accordance with the Fire Test Procedures Code.
(SOLAS Reg. II-2/49.2)
These regulations only apply to accommodation spaces, serv-
ice spaces and control stations.
(IACS UI SC127)
803 Primary deck coverings, if applied within accommodation
and service spaces and control stations, shall be of approved
material which will not readily ignite, or give rise to toxic or ex-
plosive hazards at elevated temperatures, this being deter-
mined in accordance with the Fire Test Procedures Code.
(SOLAS Reg II-2/49.3)
804 Bulkheads, ceiling and linings are to comply with 801
and 802 regardless of the type of materials used. 800 applies
regardless of the type of materials. Other finishes used in ex-
posed interior surfaces other than decking are to comply with
802. Finishes such as plastic tile and latex as primary deck
covering are to comply with 803 and IMO Res. A.687(17).
(IACS UI SC47)
B 900 Details of construction
901 Method IC - In accommodation and service spaces and
control stations all linings, draught stops, ceilings and their as-
sociated grounds shall be of non-combustible materials.
(SOLAS Reg. II-2/50.1)
902 Methods IIC and IIIC - In corridors and stairway enclo-
sures serving accommodation and service spaces and control
stations, ceilings, linings, draught stops and their associated
grounds shall be of non-combustible materials.
(SOLAS Reg. II-2/50.2)
903 Methods IC, IIC and IIIC
.1 Except in cargo spaces or refrigerated compartments of
service spaces, insulating materials shall be non-combus-
tible. Vapour barriers and adhesives used in conjunction
with insulation, as well as the insulation of pipe fittings, for
cold service systems, need not be of non-combustible ma-
terials, but they shall be kept to the minimumquantity prac-
ticable and their exposed surfaces shall have low flame
spread characteristics.
.2 Where non-combustible bulkheads, linings and ceilings
are fitted in accommodation and service spaces they may
have a combustible veneer with a calorific* value not ex-
ceeding 45 MJ/m
2
of the area for the thickness used.
3 The total volume of combustible facings, mouldings, deco-
rations and veneers in any accommodation and service
space bounded by non-combustible bulkheads, ceilings
and linings shall not exceed a volume equivalent to a 2.5
mmveneer on the combined area of the walls and ceilings.
4 Air spaces enclosed behind ceilings, panellings, or linings,
shall be divided by close-fitting draught stops spaced not
more than 14 m apart. In the vertical direction, such air
spaces, including those behind linings of stairways, trunks,
etc., shall be closed at each deck.
(SOLAS Reg. II-2/50.3)
Rules for Ships, January 2001
Pt.4 Ch.10 Sec.15 Page 40
DET NORSKE VERITAS
* The gross calorific value measured in accordance with ISO 1716 -
"Building Materials - Determination of Calorific Potential", should be
quoted.
C. Arrangements for Gaseous Fuel for Domestic
Purposes
C 100 General
101 Where gaseous fuel is used for domestic purposes the
arrangements for the storage, distribution and utilization of the
fuel shall be such that, having regard to the hazards of fire and
explosion which the use of such fuel may entail, the safety of
the ship and the persons on board is preserved.
(SOLAS Reg. II-2/51)
D. Fixed Fire Detection and Fire Alarm Systems.
Automatic Sprinkler, Fire Detection and Fire
Alarm Systems
D 100 General
101 In ships in which method IC is adopted, a fixed fire detec-
tion and fire alarm system of an approved type complying with
the requirements of regulation 13 (Sec.9 A) shall be so installed
and arranged as to provide smoke detection and manually op-
erated call points in all corridors, stairways and escape routes
within accommodation spaces.
(SOLAS Reg. II-2/52.1)
102 In ships in which method IIC is adopted, an automatic
sprinkler, fire detection and fire alarm system of an approved
type complying with the relevant requirements of regulation 12
(Sec.8) shall be so installed and arranged as to protect accom-
modation spaces, galleys and other service spaces, except
spaces which afford no substantial fire risk such as void spac-
es, sanitary spaces, etc. In addition, a fixed fire detection and
fire alarm system of an approved type complying with the re-
quirements of regulation 13 (Sec.9 A) shall be so installed and
arranged as to provide smoke detection and manually operated
call points in all corridors, stairways and escape routes within
accommodation spaces.
(SOLAS Reg. II-2/52.2)
103 In ships in which method IIIC is adopted, a fixed fire de-
tection and fire alarm system of an approved type complying
with the requirements of regulation 13 (Sec.9 A) shall be so in-
stalled and arranged as to detect the presence of fire in all ac-
commodation spaces and service spaces, except spaces which
afford no substantial fire risk such as void spaces, sanitary
spaces, etc.
(SOLAS Reg. II-2/52.3)
E. Fire Protection Arrangements in Cargo
Spaces
E 100 General
101 Except for cargo spaces covered in paragraphs 2 and 3
(200 and 300), cargo spaces of ships of 2,000 gross tonnage
and upwards shall be protected by a fixed gas fire-extinguishing
system complying with the provisions of Regulation 5 (Sec.3) or
by a fire-extinguishing system which gives equivalent protec-
tion.
(SOLAS Reg. II-2/53.1.1)
Ships of less than 2000 gross tonnage carrying petroleum prod-
ucts having a flash point exceeding 60C (closed cup test) are
not required to be fitted with a fixed fire-extinguishing system.
(IACS UI SC48)
102 Notwithstanding the provisions of paragraph 1.1 (101),
any ship engaged in the carriage of dangerous goods on deck
or in cargo spaces shall be provided with a fixed gas fire-extin-
guishing system complying with the provisions of Regulation 5
(Sec.3) or with a fire-extinguishing system which, in the opinion
of the Administration, gives equivalent protection for the car-
goes* carried.
(SOLAS Reg. II-2/53.1.2)
* For cargoes for which a fixed gas fire-extinguishing system is ineffec-
tive, refer to the list of cargoes in table 2 of MSC/Cir.671.
This only applies to ships above 500 gross tonnage engaged in
the carriage of dangerous goods.
(IACS UI SC49)
103 The Administration may exempt fromthe requirements of
paragraphs 1.1 (101) and 1.2 (102) cargo spaces of any ship if
constructed and solely intended for the carriage of ore, coal,
grain, unseasoned timber, non-combustible cargoes or cargoes
which, in the opinion of the Administration, constitute a low fire
risk.*
Such exemptions may be granted only if the ship is fitted with
steel hatch covers and effective means of closing all ventilators
and other openings leading to the cargo spaces* *.
When such exemptions are granted, the Administration shall is-
sue an Exemption Certificate, irrespective of the dated of con-
struction of the ship concerned, in accordance with regulation I/
12(a)(vi), and shall ensure that the list of cargoes the ship is
permitted to carry is attached to the Exemption Certificate.
(SOLAS Reg. II-2/53.1.3)
* For cargoes considered to be non-combustible or which constitute a low
fire risk, refer to the list of cargoes in table 1 of MSC/Circ.671.
** Refer to Code of Safe Practice for Solid Bulk Cargoes - Emergency
schedule B 14, entry for coal.
E 200 Ro-ro cargo spaces
201 There shall be provided a fixed fire detection and fire
alarm system complying with the requirements of regulation 13
(Sec.9 A). The fixed fire detection system shall be capable of
rapidly detecting the onset of fire. The type of detectors and
their spacing and location shall be to the satisfaction of the Ad-
ministration taking into account the effects of ventilation and
other relevant factors. After being installed the system shall be
tested under normal ventilation conditions and shall give a sat-
isfactory overall response time to the satisfaction of the Admin-
istration.
(SOLAS Reg. II-2/53.2.1)
202 Ro-ro cargo spaces capable of being sealed shall be fit-
ted with a fixed gas fire-extinguishing system which shall com-
ply with the provisions of regulation 5 (Sec.3), except that:
.1 if a carbon dioxide system is fitted, the quantity of gas
available shall be at least sufficient to give a minimum vol-
ume of free gas equal to 45% of the gross volume of the
largest such cargo space which is capable of being sealed,
and the arrangements shall be such as to ensure that at
least two thirds of the gas required for the relevant space
shall be introduced during 10 min;
.2 a halogenated hydrocarbon system may be used only for
spaces designated only for vehicles which are not carrying
any cargo;
.3 any other fixed gas fire-extinguishing system or fixed high
expansion foam fire-extinguishing system may be fitted
provided the Administration is satisfied that an equivalent
protection is achieved;
.4 as an alternative, a system meeting the requirements of
regulation 37.1.3 (Sec.6 E) may be fitted. However, the
drainage and pumping arrangements shall be such as to
prevent the build-up of free surfaces. If this is not possible
the adverse effect upon stability of the added weight and
free surface of water shall be taken into account to the ex-
tent deemed necessary by the Administration in its approv-
al of the stability information. Such information shall be
included in the stability information supplied to the master
as required by regulation II-1/22 (Pt.3 Ch.4).
(SOLAS Reg. II-2/53.2.2.1)
Rules for Ships, January 2001
Pt.4 Ch.10 Sec.15 Page 41
DET NORSKE VERITAS
203 Ro-ro cargo spaces not capable of being sealed shall be
fitted with a system meeting the requirements of regulation
37.1.3 (Sec.6 E). However, the drainage and pumping arrange-
ments shall be such as to prevent the build-up of free surfaces.
If this is not possible the adverse effect upon stability of the add-
ed weight and free surface of water shall be taken into account
to the extent deemed necessary by the Administration in its ap-
proval of the stability information. Such information shall be in-
cluded in the stability information supplied to the master as
required by regulation II-1/22. (Pt.3 Ch.4)
(SOLAS Reg. II-2/53.2.2.2)
204 There shall be provided for use in any ro-ro cargo space
such number of portable fire extinguishers as the Administra-
tion may deem sufficient. At least one of these portable fire ex-
tinguishers shall be located at each access to such a cargo
space.
(SOLAS Reg. II-2/53.2.2.3)
There is to be provided for use in any ro-ro cargo space at each
level portable fire extinguishers spaced not more than 20 m
apart on both sides of the ship.
(IACS UI SC73)
205 Each ro-ro cargo space intended for the carriage of mo-
tor vehicles with fuel in their tanks for their own propulsion shall
be provided with:
.1 at least three water fog applicators;
.2 one portable foam applicator unit complying with the provi-
sions of regulation 6.4 (Sec.4 B) provided that at least two
such units are available in the ship for use in such ro-ro
cargo spaces.
(SOLAS Reg. II-2/53.2.2.4)
206 Closed ro-ro cargo spaces shall be provided with an ef-
fective power ventilation system sufficient to provide at least six
air changes per hour based on an empty hold. Ventilation fans
shall normally to be run continuously whenever vehicles are on
board. Where this is impracticable, they shall be operated for a
limited period daily as weather permits and in any case for a
reasonable period prior to discharge, after which period the ro-
ro cargo space shall be proved gas-free. One or more portable
combustible gas detecting instruments shall be carried for this
purpose. The system shall be entirely separate from other ven-
tilating systems. Ventilation ducts serving ro-ro cargo spaces
capable of being effectively sealed shall be separated for each
cargo space. The Administration may require an increased
number of air changes when vehicles are being loaded or un-
loaded. The system shall be capable of being controlled from a
position outside such spaces.
(SOLAS Reg. II-2/53.2.3.1)
207 The ventilation shall be so arranged as to prevent air
stratification and the formation of air pockets.
(SOLAS Reg. II-2/53.2.3.2)
208 Means shall be provided to indicate any loss of the re-
quired ventilating capacity on the navigating bridge.
(SOLAS Reg. II-2/53.2.3.3)
The requirement to indicate any loss of ventilation capacity is
considered complied with by an alarm on the bridge, initiated
by fall-out of starter relay of fan motor.
(IACS UI SC75)
209 Arrangements shall be provided to permit a rapid shut-
down and effective closure of the ventilation system in case of
fire, taking into account the weather and sea conditions.
(SOLAS Reg. II-2/53.2.3.4)
210 Ventilation ducts, including dampers, shall be made of
steel and their arrangement shall be to the satisfaction of the
Administration.
(SOLAS Reg. II-2/53.2.3.5)
211 Closed ro-ro cargo spaces carrying motor vehicles with
fuel in their tanks for their own propulsion shall comply with the
following additional provisions:
.1 Except as provided in paragraph 2.4.2 (211.2), electrical
equipment and wiring shall be of a type suitable for use in
explosive petrol and air mixtures.
The electrical equipment shall be of certified safe type
suitable for use in Zone 1 as defined in IEC 79 (Gas Group
II A and Temperature class T3).
.2 Above a height of 450 mm from the deck and from each
platform for vehicles, if fitted, except platforms with open-
ings of sufficient size permitting penetration of petrol gases
downwards, electrical equipment with enclosure of a type
so enclosed and protected as to prevent the escape of
sparks shall be permitted as an alternative on condition
that the ventilating system is so designed and operated as
to provide continuous ventilation of the cargo spaces at the
rate of at least ten air changes per hour whenever vehicles
are on board.
The enclosure for electrical equipment shall be at least of
type IP 55.
.3 Other equipment which may constitute a source of ignition
of flammable vapours shall not to be permitted.
.4 Electrical equipment and wiring in an exhaust ventilation
duct shall be of a type approved for use in explosive petrol
and air mixtures and the outlet from any exhaust duct shall
be sited in a safe position, having regard to other possible
sources of ignition.
The electrical equipment shall be of certified safe type ac-
cording to 211.1.
.5 Scuppers shall not be led to the machinery or other spaces
where sources of ignition may be present.
.6 All electrical circuits terminating in the cargo holds are to
be provided with multipole linked isolating switches situ-
ated outside the cargo holds, and accessible only to au-
thorized personnel. Provision is to be made for isolation,
and for locking in the off position, of the means of control
of such circuits. However, this requirement does not apply
in respect of safety devices such as fire, smoke or gas de-
tectors.
.7 If electrical circuits of the gas detection system are located
in the cargo hold, the system is to be of the certified safe
type (see Ch.8).
.8 No smoking notices are to be posted in way of all accesses
to these compartments.
(SOLAS Reg. II-2/53.2.4, IACS UI SC42 and SC43)
212 Permanent openings in the side plating, the ends or
deckhead of open and closed ro-ro cargo spaces shall be so sit-
uated that a fire in the cargo space does not endanger stowage
areas and embarkation stations for survival craft and accom-
modation spaces, service spaces and control stations in super-
structures and deckhouses above the cargo spaces.
(SOLAS Reg. II-2/53.2.5)
E 300 Cargo spaces, other than ro-ro cargo spaces,
intended for the carriage of motor vehicles
301 Cargo spaces, other than ro-ro cargo spaces, intended
for the carriage of motor vehicles with fuel in their tanks for their
own propulsion, shall comply with the requirements of para-
graph 2 (200) except that in lieu of the requirements of para-
graph 2.1 (201) a sample extraction smoke detection system
complying with the requirements of regulation 13-1 (Sec.9 B)
may be permitted and paragraph 2.2.4 (205) need not be com-
plied with.
(SOLAS Reg. II-2/53.3)
302 For vessels other than ro-ro carriers and car carriers, in-
tended for the carriage of motor vehicles with fuel in their
tanks, class notation PET will be given.
Rules for Ships, January 2001
Pt.4 Ch.10 Sec.16 Page 42
DET NORSKE VERITAS
SECTION 16
FIRE SAFETY MEASURES FOR CARGO SHIPS LESS THAN 500 GROSS TON-
NAGE
A. General
A 100 Application
101 The requirements in this section apply to cargo ships be-
low 500 gross tonnage assigned main class. See also Sec.1 A,
B, C and D.
B. Fire Extinction
B 100 Fire pumps
101 Cargo ships above 150 but below 500 gross tonnage are
to be provided with at least one independent driven fire pump.
102 Cargo ships of less than 150 gross gross tonnage are to
have at least one fire pump which may be driven by the main
engine.
103 The main fire pumps referred to in 101 and 102 are to
have capacities according to Sec.2 B101.2.
104 In every such ship provided with machinery space of
category A there is to be provided in a position outside this
space a power or hand operated pump in addition to the pumps
required in 101 and 102. The pump is to have sufficient capac-
ity and pressure to provide a 6 m jet throw with nozzles not less
than 10 mm diameter. The jet throw is to be capable of being
directed on to any part of the ship.
105 In cargo ships of less than 50 gross tonnage the pumps
referred to above may be substituted by other approved equip-
ment.
B 200 Water distribution system
201 Every such ship is to have fire hydrants of sufficient
numbers and so located that at least one powerful jet of water
can reach any part of the vessel accessible to persons on board.
At least one hydrant to be provided in machinery space.
202 The fire main is to have a diameter of sufficient size to
maintain a steady distribution and pressure.
203 Materials used for the fire main are to be steel or equiv-
alent material.
204 Pipe wall thicknesses are to be in accordance with Ch.6
and material quality to be in accordance with Pt.2 Ch.1.
205 Such ships are to be provided with one fire hose com-
plete with coupling and nozzle for each 30 m of the ship, but in
no case less than three in all. The hose length is not to exceed
15 m.
206 The nozzles are to be of an approved dual purpose type
(spray/jet) with 12 mm diameter and an integrated shut-off
valve. Other diameters may be considered.
207 For smaller vessels the water distribution system may be
substituted by other approved equipment.
B 300 Portable fire extinguishers
301 Every such ship is to be provided with at least three ap-
proved portable fire extinguishers so situated as to be readily
available for use in the accommodation and service spaces.
302 In each boiler room and in each space which contains
any part of any oil fuel installation there is to be provided at
least two approved portable fire extinguishers suitable for ex-
tinguishing oil fires.
303 In each machinery space of category A containing inter-
nal combustion type machinery there is to be provided one ap-
proved foam or powder type extinguisher suitable for oil fires
for each 750 kW or part thereof of such machinery. Not less
than two such extinguishers are to be provided.
304 Smaller ships will be subjected to special consideration.
B 400 Non-portable fire extinguishers
401 In cargo ships above 150 but below 500 gross tonnage
for unrestricted service there is to be provided in machinery
spaces of category A one approved foam type extinguisher of
at least 45 litre capacity or equivalent. CO
2
extinguisher of at
least 16 kg is considered equivalent.
Alternatively, a fixed fire extinguishing system may be provid-
ed for machinery spaces of category A, in lieu of the foam type
extinguisher.
B 500 Fireman's outfit
501 Cargo ships of above 150 but below 500 gross tonnage
for unrestricted service are to be provided with at least two sets
of fireman's outfit complying with Sec.11.
Rules for Ships, January 2001
Pt.4 Ch.10 Sec.17 Page 43
DET NORSKE VERITAS
SECTION 17
FIRE SAFETY MEASURES FOR FISHING VESSELS
A. General
A 100 Application
101 The requirements in this section apply to fishing vessels
assigned main class. See also Sec.1 A, B, C and D.
102 Fishing vessels of less than 500 gross tonnage or less
than 45 m length (L) are to comply with the requirements for
cargo ships in Sec.16 and to B402 and B403.
103 Fishing vessels of 500 gross tonnage and above, or 45 m
length (L) and above are to comply with the requirements spec-
ified below.
Guidance note:
For fishing vessels - which are to comply with the applicable
parts concerning fire safety as laid down in the Torremolinos In-
ternational Convention for the Safety of Fishing Vessels, 1977,
as modified by the Torremolinos Protocol of 1993 - these recom-
mendations may be accepted as equivalent to the rule require-
ments as given in 102 and 103. Inquiry regarding use of the
Torremolinos 1993 as an alternative to classification rules should
be indicated on the request for classification.
---e-n-d---of---G-u-i-d-a-n-c-e---n-o-t-e---
B. Fire Safety Measures
B 100 Fire pumps and water distribution system
101 Fire pumps and water distribution system are to comply
with the requirements of Sec.2 as applicable to cargo ships.
B 200 Fire safety arrangements in machinery spaces
201 The arrangement of fire protection and fire-extinguish-
ing appliances in machinery spaces are to comply with the re-
quirements of Sec.5, Sec.7 and Sec.9 as applicable to cargo
ships.
B 300 Fireman's outfit
301 Fishing vessels above 150 gross tonnage are to be pro-
vided with at least two sets of fireman's outfit complying with
Sec.11.
B 400 Fire protection of bulkheads and decks
401 Structural fire protection is to comply with Sec.12 and
Sec.15 as applicable to cargo ships.
402 Combustible insulation materials are accepted in com-
partments for stowage of fish provided low ignitability and low
flame spread properties are documented. Testing is to be car-
ried out in accordance with a recognised standard, e.g. DIN
4102.1 B2 or equivalent. The test method chosen is to be suit-
able for the type of foam in question.
403 Combustible insulation as accepted by 402 is to be pro-
tected by close-fitting cladding. Acceptable cladding is steel
sheet and marine plywood. Surface coatings are to have low
flame spread properties.
B 500 Portable fire extinguishers
501 Portable fire extinguishers are to be provided in accord-
ance with Sec.4.
Rules for Ships, January 2001
Pt.4 Ch.10 Sec.17 Page 44
DET NORSKE VERITAS