Sie sind auf Seite 1von 4

5/34

Te
5
Control units
Cam switches type K1 - K2
Characteristics
Environment
K1 K2
Conforming to standards For control circuits : IEC 947-5-1
Ambient air temperature Operation : -25+55 C. Storage : -40+70 C
Conventional thermal current Screw terminal connections : in open air Ith = 12 A Ith = 20 A
enclosed Ithe = 10 A Ithe = 16 A
Rated operational characteristics Conforming to IEC 947-5-1, BS EN 60947-5-1 230 V / 3 A ; 400 V / 2 A 230 V / 4 A ; 400 V / 3 A
c AC-15 500 V / 1 A 500 V / 2 A
Short-circuit protection Cartridge fuse 16 A gG 20 A gG
Contact operation Slow break with positive opening operation
Cabling Screw and captive cable clamp terminals.
Capacity : solid cable : 1 x 2.5 mm
2
; flexible cable, with or without cable end : 1 x 2.5 mm
2
or 2 x 1.5 mm
2
For 2 x 2.8 x 0.8 mm push on connectors, please consult your Regional customer centre.
Variations available on request (or see our pushbuttons and pilot devices catalogue)
A cam switch comprises a contact block body and an operating head.
Contact block body can either be mounted :
- from the front using a single 22 mm hole fixing or 4 hole fixing via the legend plate,
- from the rear onto a backplate or DIN mounting rail.
The body comprises stacked contact blocks (2 contacts per block).
- maximum number of contacts = 20
- maximum number of angular switch positions = 12
- operator switching positions = 30 - 45 - 60 - 90, either stay put or spring return
- screw terminal connections (2 x 2.8 x 0.8 mm push on connectors are available).
Operating heads. Wide range available to suit various application needs and aesthetics of control panel
layout. Suitable for both single 22 mm hole fixing and 4 hole fixing.
Standard handle, long handle, padlockable, stepping and key operated versions are available. Single hole
fixing has as standard IP 65 protection ; rubber seal option available to increase the degree of protection
to IP 65 when using 4 hole fixing.
Contact configurations : how to understand the conventions used
Graphic representation of switching positions and spring return to 0 position
Angular position of switch
Contact number (position)
Contact closed
Contact closed in 2 positions and maintained between the 2 positions
Sealed assembly for auto-maintain control
Overlapping contacts
Customised cam switches
Non standard switch configurations are available.
Please consult your Regional customer centre.
References :
pages 5/35 and 5/36
Dimensions :
page 5/37
0
45 315
1
2
3
4
45 0
5
6
7
8
315
9
10
5/35
Te
5
Control units
Cam switches type K1 - K2
Complete units (1)
For control circuits
References
OFF-ON switches
Marking Switch Mounting Number Thermal Reference Weight
position method of poles current (Ith)
degrees A kg
Front 2 12 K1B-1002HC 0.160
mounting
20 K2B-1002HC 0.160
3 12 K1C-003HC 0.155
20 K2C-003HC 0.155
4 12 K1D-004HC 0.160
20 K2D-004HC 0.160
Changeover switches with 0 position
Marking Switch Mounting Number Thermal Reference Weight
position method of poles current (Ith)
degrees A kg
Front 1 12 K1B-001UC 0.135
mounting
20 K2B-001UC 0.135
2 12 K1D-002UC 0.160
20 K2D-002UC 0.160
3 12 K1F-003UC 0.190
20 K2F-003UC 0.190
4 12 K1H-004UC 0.215
20 K2H-004UC 0.215
Changeover switches without 0 position
Marking Switch Mounting Number Thermal Reference Weight
position method of poles current (Ith)
degrees A kg
Front 1 12 K1B-011UC 0.135
mounting
20 K2B-011UC 0.135
2 12 K1D-012UC 0.160
20 K2D-012UC 0.160
3 12 K1F-013UC 0.190
20 K2F-013UC 0.190
4 12 K1H-014UC 0.215
20 K2H-014UC 0.215
Stepping switches (3 step), single-pole, with 0 position
Marking Switch Mounting Thermal Reference Weight
position method current (Ith)
degrees A kg
3 step + 0
Front 12 K1C-003QC 0.155
mounting
20 K2C-003QC 0.155
(1) Complete switches comprise a front mounting base/contact block and a single 22 mm hole fixing
45 x 45 mm operating head with a 34 mm long handle and markings.
To order a switch with a 37 mm long handle, suffix the references shown above with the letter T.
Example : 12 A 2-pole OFF-ON switch with 37 mm long handle : K1B-1002HCT.
0 2 1
1 2
0 1
2
3
0
45
90
135
45 315
Characteristics :
page 5/34
Dimensions :
page 5/37
0
1
0
90
0
45 315
Ki i i i i i i i i i-iiii iiii iiii iiii iiiiC
5/36
Te
5
Control units
Cam switches type K1 - K2
Complete units (1)
For control circuits
References
Stepping switches (4 step), single-pole, with 0 position
Marking Switch Mounting Thermal Reference Weight
position method current (Ith)
degrees A kg
4 step + 0
Front 12 K1D-004QC 0.160
mounting
20 K2D-004QC 0.160
Ammeter switch with 0 position
Marking Switch Mounting Thermal Reference Weight
position method current (Ith)
degrees A kg
For 3 circuits
Front 12 K1F-003MC 0.190
mounting
Voltmeter switch with 0 position
Marking Switch Mounting Thermal Reference Weight
position method current (Ith)
degrees A kg
For measurement between 3 phases and between each of the 3 phases and neutral
Front 12 K1F-027MC 0.190
mounting
Star-delta switch
Marking Switch Mounting Thermal Reference Weight
position method current (Ith)
degrees A kg
Front 20 K2H-001YC 0.215
mounting
Reversing star-delta switch
Marking Switch Mounting Thermal Reference Weight
position method current (Ith)
degrees A kg
Front 20 K2H-006YC 0.245
mounting
Pole change switch for 2-speed motors
Marking Switch Mounting Thermal Reference Weight
position method current (Ith)
degrees A kg
For motors with tapped Dahlander windings
Front 20 K2H-004PC 0.245
mounting
(1) Complete switches comprise a front mounting base/contact block and a single 22 mm hole fixing
45 x 45 mm operating head with a 34 mm long handle and markings.
To order a switch with a 37 mm long handle, suffix the references shown above with the letter T.
Example : star-delta switch with 37 mm long handle : K2H-001YCT.
0
60
120
300
240
0
1
2
3 4
0
L1 L3
L2
0
0 L1-L2
L2-L3
L3-L1
L2-L3
L1-L2
L3-L1
0
0
Tortoise
Hare
0
90
135
45
270
315
225
0
45
90
135
180
0
90
180
270
0
60
120
0
60
120
Characteristics :
page 5/34
Dimensions :
page 5/37
Ki i i i i i i i i i-iiii iiii iiii iiii iiiiC
5/37
Te
5
Control units
Cam switches type K1 - K2
Dimensions
Base/contact blocks
Front mounting
Operating heads + base/contact blocks
Base/contact block Base/contact block Operating head +
reference Front mounting Rear mounting base/contact block (front mounting)
a1 a2 a3
KiB-iiii 52.5 42.5 70.5
KiC-iiii, KiD-iiii 62.5 52.5 80.5
KiF-iiii 72.5 62.5 90.5
KiH-iiii 82.5 72.5 100.5
a3
Characteristics :
page 5/34
References :
pages 5/35 and 5/36
u45
5
0
7
8
a1

Das könnte Ihnen auch gefallen