0 Bewertungen0% fanden dieses Dokument nützlich (0 Abstimmungen)
39 Ansichten11 Seiten
This paper presents data from several applications of SFRA in the field. Results have been used to support decisions relating to transformer health and viability. A good test procedure is key to making good, reliable and repeatable measurements.
This paper presents data from several applications of SFRA in the field. Results have been used to support decisions relating to transformer health and viability. A good test procedure is key to making good, reliable and repeatable measurements.
This paper presents data from several applications of SFRA in the field. Results have been used to support decisions relating to transformer health and viability. A good test procedure is key to making good, reliable and repeatable measurements.
This paper presents data from several applications of SFRA in the field where results have been used to support decisions relating to transformer health and viability. It is not the aim of this paper to discuss in detail the basic theory of SFRA as this has been covered in several previous papers [1-14].
We should perhaps reiterate the need in SFRA measurements to gather results which are of sufficient quality as to provide suitable data to make decisions. This means that the results are repeatable and independent of test operator, test equipment and lead arrangement; a good test procedure is key to making good, reliable and repeatable measurements [9,10].
Null results
An SFRA measurement is a trace which shows resonances at a number of different frequencies. These resonances are due to combinations of inductances and capacitances in the complex network which makes up the transformer: series and parallel resonances between windings, between layers within windings, between windings and ground, and so on. Clearly if the complex network does not change, then the SFRA trace should not change.
We can use that information in the reverse manner no change in the SFRA trace means that it is unlikely that there has been any change in the network being tested. Such a result is called a null result.
Small variations often do exist between successive traces, but if they can be attributed to simple and well understood causes such as remnant magnetization or stray impedance at test lead terminals then they do not present a problem. It is important in SFRA to take in to account the whole picture, and view data as one element in the analysis of a transformer.
Relocation of a transformer is a simple example where data may be taken:
before the transformer is moved for example, in the factory after the transformer has been moved say at the substation
In this case we expect a null result. FIGURE 1 shows the SFRA results from a Generator Step Up transformer before relocation and then, some months later, after it has arrived on site. J ust one winding, the 2005 Doble Engineering Company All Rights Reserved
1 LV, and one phase is shown, but the results are typical of all of the SFRA tests performed on this transformer.
Generator Transformer 23.5/432 kV 800 MVA a to b LV winding 0 0.5 1 1.5 2 -40 -30 -20 -10 0 Frequency (MHz) Amplitude (dB) Scotland 9/1/00
England 10/4/00
Typical SFRA Traces before and after relocation of a Generator Step Up Transformer FIGURE 1
Clearly there are no new resonances or shifted resonances the results are acceptable. Small variations in response at higher frequencies are not uncommon and are associated with stray impedance in the test lead connections.
FIGURE 2 shows typical results from the HV winding of a distribution transformer before and after relocation. There is a small offset to the results at low frequencies, below 1 kHz which is associated with remnant magnetism in the core. The remainder of the traces overlay almost perfectly, and these results are typical for the two tests on the transformer. This is strong evidence that nothing has moved within the transformer.
2005 Doble Engineering Company All Rights Reserved
2
HV Winding 45 MVA Transformer before and After Relocation FIGURE 2
In both cases, the null result is useful in deciding whether anything has moved inside the transformer as a result of relocation.
Null results with no reference results?
It is clearly not possible to have a null result without reference results. However, it is possible to use results from sister units or similar units to provide an indication of the expected form of results.
FIGURE 3 shows the results for three phases of a GSU after a bushing failed and had been replaced. The failed bushing was on H3 and it is this phase which shows some small variations at high frequencies, above 1 MHz. Higher frequency variations are related to smaller objects with the transformer and the variation shown here could relate to lead displacement between the winding and the bushing.
HV Results from GSU after bushing replacement FIGURE 3 2005 Doble Engineering Company All Rights Reserved
3 There were no previous results from this transformer, but a sister unit in known good condition was available to act as a reference. FIGURE 4 shows the results of the H3 phase overlaid on the results from the same phase of the sister unit. The two results are clearly identical.
H3 of GSU results compared with sister unit FIGURE 4
By comparing the other phases it was possible to conclude that the variation of the H3 phase was related to construction and manufacturing and is part of the design rather than a feature resulting from the transformer failure. The results helped support the decision to accept the transformer as healthy despite the bushing failure.
It is possible to find variation in sister units, even with results at the factory. FIGURE 5 shows variation between corresponding LV windings of transformers with successive serial numbers. The variation is small and limited to a few points around 100 kHz and should not be considered a reason to suspect either transformer.
2005 Doble Engineering Company All Rights Reserved
4
Variation in SFRA Results in Sister Units at the Factory FIGURE 5
In the case of the transformer with the failed bushing, it is the consistent similarity between all three corresponding phases which gives credibility to the idea that the variation found at high frequencies on the phase with the replaced failed bushing is not due to some mechanical movement in response to that failure.
Clearly Identifiable Problems
There are some transformer failure modes which result in such clear SFRA trace formats that no reference results are required. One such failure mode is a shorted turn on a winding. The effect of the shorted turn is to remove the inductive effect of that core limb, resulting in a response which is similar to a standard SFRA short circuit response. This test allows for direct comparison between results by shorting out the LV windings while measuring the HV side in a manner akin to leakage reactance.
The series winding results for the 200 MVA shell form autotransformer in FIGURE 6 are typical of a shorted turn. The responses from the two outer limbs are almost what we would expect, except that there is only one downward resonance near 100 Hz where we would normally expect two. The center phase has the shorted turn, resulting a response which rolls off as per a short circuit test.
2005 Doble Engineering Company All Rights Reserved
5
Results indicating a shorted turn FIGURE 6
The SFRA results produce a relatively quick and simple diagnosis, or confirmation, of a severe problem.
Winding Movement: A Suspected Case with References
Previous papers have given examples of axial collapse of a winding and compressive failure of a winding [2,7]. Two similar sets of results are presented here.
In FIGURE 7 are three responses from the low voltage windings of a transformer they follow the expected form up to about 100 kHz and above 1 MHz. From 100 kHz to 12 MHz, however, there seems to be a difference for the X3-X0 phase.
Low Voltage Responses for a Suspect Transformer FIGURE 7
Clearly, in 8, the resonances for the X3-X0 phases have shifted to higher frequencies when compared to X1-X0 and X2-X0. Such a shift represents a reduction in the 2005 Doble Engineering Company All Rights Reserved
6 capacitance-inductance combination for that resonance. This presents a problem why would one phase be so different to the other two? It is often the case that the center phase has some slight differences when compared to the outer phases, explained through symmetry arrangements of the windings, but it is unlikely that one outer phase would differ so consistently when compared to the other two.
Detail of Low Voltage Responses for a Suspect Transformer FIGURE 8
A similar set of results were found for a transformer which had suffered axial collapse of one winding. The results shown in FIGURE 9 are for the transformer in 1994; the three phases are very consistent across the frequency range, having similar shape and occasional dB variations. -60 -50 -40 -30 -20 -10 0 0 0.5 Frequency in MHz A m p l i t u d e
i n
d B 1
Previous Example of Results Shifting to Higher Frequencies FIGURE 9
2005 Doble Engineering Company All Rights Reserved
7 After an incident in 2001 the transformer was retested, giving the results shown in FIGURE 10. These are quite different for one phase, though the differences are predominantly above about 300 kHz, as with the suspect transformer. This transformer was dismantled and the winding collapse found on the suspect phase.
-70 -60 -50 -40 -30 -20 -10 0 0 0.5 Frequency in MHz A m p l i t u d e
i n
d B 1
Results after Axial Collapse of Winding FIGURE 10
At the time of writing the transformer with the new results has not been dismantled; this may be the subject of a future paper.
SFRA Results Indicating a Resistance Issue
A distribution transformer had suffered a number of faults and was showing a rising DGA trend. Power factor and capacitance tests were inconclusive, as were excitation and leakage reactance. SFRA tests were performed to try and identify minor winding movement.
The results were acceptable for open circuit tests, but the short circuit tests indicated a problem at low frequencies. FIGURE 11 shows the results below 3 kHz for all three phases.
2005 Doble Engineering Company All Rights Reserved
8
Short Circuit Results for Suspect Transformer FIGURE 11
Clearly the results show the expected form with a resistive section close to 0 dB and an inductive roll off at about 20 dB per decade. This is the advantage of the short circuit test all three phases should look very similar and have an expected form. In some cases the winding inductance is so large that there is no clear resistive section, but all three windings should look the same.
Zooming in on the inductive section showed all three results within 0.1 dB which is acceptable. The resistive section, however, showed variation for all three phases, as shown in FIGURE 12. The effect is small, but the close pattern of the inductive roll off is not reflected in the resistive section.
Resistive Component of Short Circuit Test Results FIGURE 12
2005 Doble Engineering Company All Rights Reserved
9 What does this variation mean? As we use a reliable test instrument, we can deduce that something in the measurement circuit is adding resistance to that phase; this could be something in the transformer or it could be a result of the shorting leads. All shorting leads and connections were checked and tightened, cleaned and reapplied. The results remained the same. Consequently the variation is due to the transformer in some way. A DC resistance set was obtained and measurements made which confirmed the indications of the SFRA results right down to which winding had the lowest resistance and which had the highest. On inspection, the transformer was found to have coking on the tap changer which had lead to the increased resistance.
No significant winding movement and/or distortion was found.
In this case SFRA was useful in confirming that the transformer was probably mechanically sound, but indicated a need for further testing to removed the resistance issue.
CONCLUSIONS
Use of SFRA for decision support in factory and field applications is increasing. It is informative to discuss results and learn from them where possible so that knowledge generated may be applied in other cases. Results presented here are from practical application and we believe they will be both useful and informative.
ACKNOWLEDGEMENTS
This work is published with permission of the Doble Engineering Company. The assistance of colleagues both within Doble and within the industry is acknowledged and greatly appreciated.
REFERENCES
1. "Transformer Diagnostic Testing by Frequency Response Analysis" Dick, E. P. and Erven, C. C, IEEE Trans PAS-97, No. 6, pp 2144-2153, 1978.
2. Substation Diagnostics with SFRA: Transformers, Line Traps and Synchronous Compensators Phil Prout & Matt Lawrence, National Grid USA; Charles Sweetser & Tony McGrail, Doble Engineering, USA 2004 EPRI Substations and Diagnostics Conference, New Orleans, LA
3. Transformer Winding Movement Detection by Frequency Response Analysis J ohn Lapworth & Tony McGrail 1999 Annual Conference of Doble Clients, Boston MA
4. Developments in Substation SFRA Application Greg Bennett & J ack Eitzel, Xcel Energy; Tony McGrail & Charles Sweetser, Doble 2005 Doble Engineering Company All Rights Reserved
10 Engineering 2005 EPRI Substations and Diagnostics Conference, New Orleans, LA
5. SFRA: An Efficient Tool for Decision Making Harry Fridman, Elco Industries Ltd., Israel 2004 Annual Conference of Doble Clients, Boston MA
6. Experience with SFRA for Transformer Diagnostics Tony McGrail, Doble Engineering Company 2004 Annual Conference of Doble Clients, Boston MA
7. Transformer Fails Seven Years After Close Up Faults - FRA Diagnoses the Problem J ohn Lapworth, National Grid 2002 Annual Conference of Doble Clients, Boston MA
8. The Need for and Use of Techniques to Assess the Mechanical Integrity of Transformer Windings Alan Wilson, Doble Engineering Company; Tony McGrail, National Grid 2002 Annual Conference of Doble Clients, Boston MA
9. Experimental Investigations of the Repeatability of FRA Measurements: Experience with Sweep Frequency Response Analysis Measurements Charles L. Sweetser, Doble 2002 Annual Conference of Doble Clients, Boston MA
10. Testing Practices for Frequency Response Analysis Charles L. Sweetser, Doble 2001 Annual Conference of Doble Clients, Boston MA
11. Recent Developments Relating to the Detection of Winding Movement in Transformers by Frequency Response Analysis J ohn Lapworth, National Grid 2001 Annual Conference of Doble Clients, Boston MA
12. ESBI Experiences with SFRA Tim Noonan, ESBI 2001 Annual Conference of Doble Clients, Boston MA
13. Frequency Response Analysis of the Leakage Impedance Used as a Power Transformer Diagnostic Tool Librado Magallanes R., Ernesto Lpez Azamar, Isa Gallardo F., CFE 2001 Annual Conference of Doble Clients, Boston MA
14. Experience in the Application Of Frequency Response Analysis Sokom An, BPA 1999 Annual Conference of Doble Clients, Boston MA
2005 Doble Engineering Company All Rights Reserved