Sie sind auf Seite 1von 38

AmerTex

R-Serie
G Exclusive bonding
technology provides
cleaner air
G Low resistance to airflow
G High dust holding
capacity
G Available in synthetic
and natural executions
G Washable
R-series air filter media is made of
synthetic fibres, except type R20
Natural, which is made of natural fibres.
An exclusive bonding technology
ensures a high number of fibres per
square metre for a given weight.
All AmerTex R series media is white
coloured. No colour pigments are
needed to create a distinction between
the various media. The name of each
product together with its classification
according to EN779 is printed at
regular intervals on the air leaving side
of each media roll, permitting easy
product identification. R-Series media is
characterized by a relatively low
resistance to airflow and a high dust
holding capacity.
Applications
Synthetic filter media.
The R15 Economy and R17 Durable
media are recommended for use in low
pressure forced air convectors, window
ventilation units, fan coils and as
prefilter in paintspray cabins.
The R29 Standard media is for use in
room air conditioning units, hot air
generators, air conditioning installations,
home kitchen hoods and as prefilter in
paint spray cabins.
The R50 Super media is suitable for use
in air conditioning installations in the
food industry, kitchen hoods, industrial
ventilation systems and as prefilter in
paintspray cabins.
Natural filter media
The R20 Natural media, consisting of
latex coated natural fibres structured
into a porous and dense media, is
recommended for use in severe
operating conditions.
Cleaning
Types R15 and R29 are washable to a
limited extent. Types R17, R50 and R20
are fully washable.
The R-series media can be cleaned:
G in warm water (30 - 40C) with
addition of a household detergent,
if necessary. Drying should be done
on a flat surface. Do not rub or
wring.
G by blowing with compressed air in
opposite direction of filter airflow.

Synthetic and natural filter media


B E T T E R A I R I S O U R B U S I N E S S
AmerTex

R-Serie
RA-2-504-IN-4-0198
Technical Data
Type R15 Economy R17 Durable R29 Standard R50 Super R20* (30 mm)
Recommended face velocity (m/s) 1.5 1.5 1.5 1.5 2.0
Rated capacity (m
3
/h/m
2
) 5400 5400 5400 5400 7200
Rated initial resistance (Pa) 17 17 26 42 80
Recommended final resistance (Pa) 130 130 200 200 250
Average arrestance (%) 75 - 80 75 - 80 80 - 85 87 - 92 80
EN 779 classification G 2 G 2 G 3 G 4 G 3
Roll size (m) 2 x 20 2 x 20 2 x 20 2 x 20 Pads only
1 x 20 1 x 20 1 x 20 1 x 20
Packing polyethylene bags
Media colour white white white white brown
Flame retardancy according to DIN 53438 F1 F1 F1 F1 -
Max. operating temperature (C) 100 100 100 100 65
Washability limited good limited good good
* R20 media is also available in 20, 40 and 50 mm thicknesses
Airflow Resistance
0 1.0 2.0 3.0 4.0
0
10
30
50
20
60
70
80
40
R17, R15
R29
R50 R20
Face Velocity (m/s)
I
n
i
t
i
a
l

R
e
s
i
s
t
a
n
c
e


(
P
a
)
1998 AAF International
AAF has a policy of continuous product research and improvement and reserves the right to change design and
specifications without notice.
AAF-International B.V.
P.O. Box 7928
1008 AC Amsterdam
The Netherlands
Tel.: + 31 20 549 44 11
Fax: + 31 20 644 43 98
International AAF Offices:
Vienna (A), Montreal (CDN), Dortmund (D),
Vitoria (E), Paris (F), Cramlington (GB),
Athens (GR), Milan (I), Riyadh (KSA),
Mexico (Mex), Amsterdam (NL), Singapore,
Istanbul (TR), Louisville, Ky (USA)
AAF Agents:
Copenhagen (DK), Bangalore (IND)
Oslo (N), Lisbon (P), Johannesburg (RSA),
Dalsjfors (S), Malm (S), Helsinki (SF)
AmWash
Pleated Washable Filter
Washable
High dust holding capacity and long service life
Reduce the risk of fire
Low initial resistance
Lightweight and easy to install
Choice of media in the classification range G3 to F5 (EN779)
AmWash is specially designed for application in industrial and
commercial heating, ventilation and air conditioning systems. For
example like:
AmWash is a lightweight panel filter with several special features
like reusable aluminum steel frame, made of synthetic fiber and
characterized by a relatively low resistance to airflow, reduce risk of
fire, washable and easy to install. Filter media with the thickness of
10mm and 20mm ensure high dust holding capacity.
Advantages
AmWash is available with 3 classifications: G3, F4 and F5 in
accordance with EN779.
Choice of Media
Owing to the excellent dust holding capacity, AmWash can be used
as prefilter to higher efficiency filters or as main filters. As prefilter,
AmWash protect more expensive main filters from premature
replacement while as main filter it improves the quality of indoor air.
High dust holding capacity
Easy to install
AmWash has a sturdy, long lasting galvanized steel frame which
offers great resistance in harsh operating conditions. Due to its light
weight and compact size (only 46mm depth), it is relatively
inexpensive to ship and easy to handle and install. If required,
AmWash can be supplied with a stainless steel or aluminum frame
and can be manufactured to any size.
Cleanable
AmWash can be blow cleaned with compressed air, but only once
or twice during its natural lifetime. AmWash can also be cleaned
with a solution of water and detergent on a limited basis.
Aluminumframe
Filter media
Supporting grid
1) Offices, convention centers, meeting rooms, hospitals,
shopping malls, sport centers, airports and other buildings
with HVAC systems.
2) Normal industrial area with central air ventilation system.
3) Prefilter for central ventilation system for CleanRoom.
AmWash
Tel: 03-5569 2633 / Fax: 03-5569 3633
No. 9 (Lot 136), Jalan Juru Ukur U1/19,
Hicom-Glenmarie Industrial Park, 40150
Shah Alam, Selangor Darul Ehsan, Malaysia.
www.aafasia.com
ISO-9001 Certified Firm
2006 AAF Malaysia
AMWASH-01-MAL/OCT 06
AAF has a policy of continuous product research
and improvement and reserves the right to change
design and specifications without notice.
Product Information
Technical Specification
G3
G3
G3
G3
G4
610 x 610 x 51
305 x 610 x 51
610 x 610 x 102
305 x 610 x 102
610 x 610 x 51
65
65
55
55
85
G4 305 x 610 x 51 85
G4 610 x 610 x 102 80
G4 305 x 610 x 102 80
90
90
75
75
110
110
105
105
35
35
30
30
50
50
45
45
Class
70% 100% 120%
Nominal Size
WxHxD (mm)
595 x 595 x 46
290 x 595 x 46
595 x 595 x 96
290 x 595 x 96
595 x 595 x 46
290 x 595 x 46
595 x 595 x 96
290 x 595 x 96
Actual Size
WxHxD (mm)
3400
1700
3400
1700
3400
1700
3400
1700
Rated Airflow
Capacity (m
3
/h)
Initial Resistance (Pa)via Rated Airflow
Maximum Operating Temperature : 93C (200F)
Media : Synthetic fiber
Support grid : Wire grid
Frame :
Corner bracket :
Aluminum Frame
Rigid steel bracket
Airflow Resistance
Face Velocity, (m/s)
0
25
50
75
100
170
120
200
150
0 1 2 3 4 5
I
n
i
t
i
a
l
R
e
s
i
s
t
a
n
c
e
(
P
a
)
Initial Resistance vs Face Velocity
AmAir

300
B E T T E R A I R I S O U R B U S I N E S S

High Quality Prefilters


G Excellent media perfor-
mance in high humidity
conditions
G High tensile strength
media
G Environment-friendly
materials
G Sturdy, reliable
construction
High performance, environment
friendly media
With the new AmAir 100 and 300
series of prefilters AAF has risen to
the challenge of designing an
environment-friendly product with
the necessary performance charac-
teristics built-in. These filters feature
a new 100% synthetic media pack
which provides excellent perfor-
mance in conditions of high relative
humidity and moisture. When the
media becomes wet, resistance may
rise temporarily only to subside when
the media starts to dry. The synthetic
media displays great tensile strength,
reducing the chance of damage
during handling and operation. The
media is environment and user
friendly: it does not contain any
harsh resins or artificial colouring. It
can therefore be readily disposed of
by landfill or incineration.
Sturdy, reliable construction
The pleated media pack of both
range of filters is housed within a
sturdy double walled, die cut box,
beverage board frame. To ensure the
media pack does not rack or
deteriorate under difficult operating
conditions, it is bonded to the inside
of its frame at all points of contact
and retained in position by retainers
at the air leaving and air entering
sides. On the air leaving side of the
media pack a wiremesh pleat support
grid maintains equidistant spacing
between pleats, ensuring that dust is
collected evenly over the entire
surface of the media. Media usage is
maximized resulting in a more
gradual rise in resistance, which in
turn has a positive effect on energy
consumption and service life.
Applications
Classified G4 in accordance with
EN 779, AmAir 100 and 300 are
ideal for protecting more expensive
secondary air filters from premature
dust loading and replacement. As
primary filters, they will also help
reduce HVAC maintenance costs by
preventing unnecessary dust build-up
on coils, fans and duct work.
AmAir

300
RA-2-509-IN-1-0798 1998 AAF International
AAF hasa policy of continuousproduct research and improvement and reservesthe right to change design and
specificationswithout notice
FireClassification:
a) Both filtersare Class2 approved and listed according to UL Standard 900.
b) PET media isclassified M2 according to NF P92-503, 504 and 505.
Standard Dimensions Airflow Resistance
Nominal Size
1,3)
(inches)
W x H
12 x 24
16 x 20
16 x 25
20 x 20
20 x 25
24 x 18
24 x 20
24 x 24
14
1
/ 2 x 26
3
/ 4
Actual Size
2,3)
(mm)
W x H
290 x 595
392 x 494
392 x 621
494 x 494
494 x 621
595 x 445
595 x 494
595 x 595
355 x 665
Airflow
at 2.5 m/s
(m
3
/h)
1700
1870
2380
2380
2975
2550
2850
3400
2260
Notes:
1) Width and height dimensionsare interchangeable.
Filtersmay be installed with the pleatsin the
vertical or horizontal position. The pleatsare always
parallel to the longest cell side unlessexplicity
specified otherwise.
2) Other sizesand air filtersin 21 mm (1 inch
nominal) depth are available upon request.
3) SeeTechnical Data Tablefor filter depths.
Technical Data
Type 100 - 2 100 - 4 300 - 2 300 - 4
Actual Depth (mm) 48 95 48 95
Rated Face Velocity (m/s) 1.5 - 2.5 1.5 - 3.2 1.5 - 2.5 1.5 - 3.2
Average Arrestance
1)
(%) 90 - 95 90 - 95 90 - 95 90 - 95
Efficiency
1)
(%) - - - -
EN779 Classification G4 G4 G4 G4
Rated Initial Resistance
1)
(Pa) 45 - 85 40 - 100 33 - 76 31 - 91
Recomm. Final Resistance
2)
(Pa) 250 250 250 250
Temperature Limits(C) 90 90 90 90
(continuousoperation)
1) All data based on EN779.
2) Recommended final resistance not to be exceeded.
1.0 1.5 2.0 2.5 3.0 3.2 0
0
20
60
100
40
120
140
160
80
1. AmAir 300 (48 mm), 2. AmAir 300 (95 mm)
1.
2.
Rated Velocity (m/s)
I
n
i
t
i
a
l

R
e
s
i
s
t
a
n
c
e

(
P
a
)
AAF-International B.V.
P.O. Box 7928
1008 AC Amsterdam
The Netherlands
Tel.: + 31 20 549 44 11
Fax: + 31 20 644 43 98
International AAF Offices:
Vienna (A), Montreal (CDN), Dortmund (D),
Vitoria (E), Paris (F), Cramlington (GB),
Athens (GR), Milan (I), Riyadh (KSA),
Mexico (Mex), Amsterdam (NL), Singapore,
Istanbul (TR), Louisville, Ky (USA)
AAF Agents:
Copenhagen (DK), Bangalore (IND)
Oslo (N), Lisbon (P), Johannesburg (RSA),
Dalsjfors (S), Malm (S), Helsinki (SF)
DriPak

2000
G Filter classes F5 - F8 for
applications requiring
cleaner air
G Mechanically strong with
a high abrasional
resistance
G Operational reliability in
high airflow and high
dust loading conditions
G Excellent performance in
high moisture conditions
Mechanically Strong and Robust
DriPak 2000 pocket filters are made of
high quality synthetic media. They are
renowned for their high performance
characteristics in applications requiring a
high dust holding capacity and higher air
cleaning capacity. Built from strong,
robust materials they display excellent
abrasional resistance and perform well in
100% relative humidity and in high
airflow and heavy dust loading
conditions. Since their introduction they
have proven a resounding success with the
pharmaceutical, food processing and
automotive industries.
Microfine Synthetic Fibres
Provide Cleaner Air
DriPak 2000 pocket media comprises a
unique matrix of primary and secondary
synthetic fibres with a thin layer of high
strength spunbond scrim on the air
leaving side to increase filter stability and
prevent particle migration. This dual
media design ensures a low initial pressure
drop, a high dust holding capacity and a
long filter service life.
Efficiency Ranges
DriPak 2000 is available in four
efficiencies. For easy identification, each
efficiency has its own colour coded media
scheme:
Final Resistance
DriPak 2000 filters are tested in
accordance with EN779. The
recommended final resistance is 450 Pa.
Temperature limits
DriPak 2000 synthetic filters are designed
for a continuous operating temperature
up to 70C. The filters should not be
stored or transported in conditions where
temperatures exceed 60C.
B E T T E R A I R I S O U R B U S I N E S S

Superfine Synthetic Fibres Provide Cleaner Air


Efficiency EN 779 Media Colour
90 - 95% F8 Yellow
80 - 85% F7 Red
60 - 65% F6 Green
DriPak

2000
RA-2-542-IN-2-0999 1999 AAF International
AAF has a policy of continuous product research and improvement and reserves the right to change design and
specifications without notice.
0 1.0 0.5 1.5 2.0 2.5 3.0
0
50
25
75
100
125
200
225
150
175
DriPak 2000 90%
0 1.0 0.5 1.5 2.0 2.5 3.0
0
50
25
75
100
125
200
225
150
175
DriPak 2000 80%
0 1.0 0.5 1.5 2.0 2.5 3.0
0
30
60
120
90
DriPak 2000 60%
0 1.0 0.5 1.5 2.0 2.5 3.0
0
30
60
120
90
DriPak 2000 50%
Notes:
1) Filters can be operated at 67% to 133% of rated face velocity.
2) All performance data based on EN779 1993 standard (ASHRAE 52.1-1992 test method).
3) The recommended final resistance is 450 Pa.
4) The DriPak 2000 filter sizes fit into frame sizes 610 x 610, 305 x 610 and 508 x 610 mm.
5) Filters are also available in other sizes and with 25 and 20 mm headers.
3.2
2.5
1.25
592x592x700
287x592x700
490x592x700
592x592x635
287x592x635
490x592x635
592x592x508
287x592x508
490x592x508
9
4
7
8
4
6
6
3
5
8.0
3.6
6.2
6.7
3.3
5.0
4.1
2.0
3.4
4250
2125
3550
3400
1700
2850
1700
850
1400
160
160
160
135
135
135
90
90
90
Rated
Face
Velocity
1)
(m/s)
Actual
Size
4/5)
(wxhxd)
(mm)
Number
of
Pockets
Gross
Media
Area
(m
2
)
Rated
Airflow
Capacity
(m
3
/h)
Rated
Initial
2/3)
Resistance
(Pa)
90-95% Average Efficiency
2)
- F 8
80-85% Average Efficiency
2)
- F 7
60-65% Average Efficiency
2)
- F 6
3.2
2.5
1.25
592x592x700
287x592x700
490x592x700
592x592x635
287x592x635
490x592x635
592x592x508
287x592x508
490x592x508
9
4
7
8
4
6
6
3
5
8.0
3.6
6.2
6.7
3.3
5.0
4.1
2.0
3.4
4250
2125
3550
3400
1700
2850
1700
850
1400
105
105
105
80
80
80
60
60
60
3.2
2.5
592x592x700
287x592x700
490x592x700
592x592x635
287x592x635
490x592x635
9
4
7
8
4
6
8.0
3.6
6.2
6.7
3.3
5.0
4250
2125
3550
3400
1700
2850
75
75
75
65
65
65
2.5
2.5
2.5
592x592x635
287x592x635
490x592x635
592x592x508
287x592x508
490x592x508
592x592x305
287x592x305
490x592x305
6
3
5
6
3
5
6
3
5
5.0
2.5
4.3
4.1
2.0
3.4
2.5
1.2
2.0
3400
1700
2850
3400
1700
2850
3400
1700
2850
55
55
55
60
60
60
65
65
65
50-55% Average Efficiency
2)
- F 5
Resistance Curves and Selection Chart Data
I
n
i
t
i
a
l

R
e
s
i
s
t
a
n
c
e

(
P
a
)
I
n
i
t
i
a
l

R
e
s
i
s
t
a
n
c
e

(
P
a
)
I
n
i
t
i
a
l

R
e
s
i
s
t
a
n
c
e

(
P
a
)
I
n
i
t
i
a
l

R
e
s
i
s
t
a
n
c
e

(
P
a
)
Face Velocity (m/s)
Face Velocity (m/s)
Face Velocity (m/s)
Face Velocity (m/s)
AAF-International B.V.
P.O. Box 7928
1008 AC Amsterdam
The Netherlands
Tel.: + 31 20 549 44 11
Fax: + 31 20 644 43 98
International AAF Offices:
Vienna (A), Montreal (CDN), Dortmund (D),
Vitoria (E), Paris (F), Cramlington (GB),
Athens (GR), Milan (I), Riyadh (KSA),
Mexico (Mex), Amsterdam (NL), Singapore,
Istanbul (TR), Louisville, Ky (USA)
AAF Agents:
Copenhagen (DK), Bangalore (IND)
Oslo (N), Lisbon (P), Johannesburg (RSA),
Dalsjfors (S), Malm (S), Helsinki (SF)
VariCel

High and Medium Efficiency


Extended Surface
Supported Pleat Air Filters
VariCel

with Intersept

IAQ Engineered Media Treated


with Intersept

Antimicrobial
High Temp Series VariCel filters are designed for sys-
tems operating from 350- 900F. Constructed of alu-
minized steel, High Temperature VariCel filters offer
rated efficiency with proven reliability over the life of the filter.
See page 4 for models and temperature limits.
Type NH Series VariCel filters are designed for special
sizes and applications, including incineration and
compaction disposal systems. Manufactured of fire-
retardant, 34" thick, heavy wall particle board, Type NH VariCel
filters (U.L. Class 1) are operable at temperatures up to 200F.
The filters are constructed without headers and cell sides are
flush with front face dimensions.
VariCel

and
VariCel

with
Intersept

Extended Surface
Supported Pleat Filters
Available In Three Efficiencies 90-95% (MERV 14),
80-85% (MERV 13), 60-65% (MERV 11)
Available with Intersept

in 90-95% & 60-65%


efficiency
U. L. Class 1
Ideal For Difficult Operating Conditions
- Variable air volume
- Turbulent airflow
- Repeated fan shutdown
- High temperature operation
- High humidity
- Intermittent exposure to water
such as seacoast installations
VariCel filters with Intersept

antimicrobial are designed specifical-


ly to improve Indoor Air Quality (IAQ). Air filters are designed to
trap and concentrate particulate air contaminants including viable
fungal and bacterial spores. The presence of Intersept

antimico-
bial preservative in the filter media is intended to preserve the in-
tegrity of the media throughout the useful life of the filter.
Antimicrobial preservatives are not meant to increase the efficiency
of the filter, nor to kill microorganisms "on the fly" as they pass
through a filter. Intersept

is EPA registered and environmentally


safe.
Engineered For A Variety Of Applications
Designed To Improve Indoor Air Quality
Type SH Single Header VariCel filters are designed for
systems originally supplied by AAF International. A
unique
13
16" flanged header on the air entering side al-
lows the filter to be easily inserted and latched into front and
side access systems.
Type DH Double Header VariCel filters are designed to
upgrade air cleaning performance and reliability. Two
13
16" thick flanged headers make the filters compatible
with the holding frames and latching devices of various manu-
facturers, including rear access systems.
XL Series VariCel filters, single header (XL-S) and double header
(XL-D), contain up to 67% more media and offer more than twice the
service life of standard single and double header models.
Corrugated Aluminum Separators
with Rolled Edges maintain uniform
pleat spacing for optimum air flow. The
separators are rolled to eliminate
sharp edges, preventing media dam-
age during shipping and personal in-
jur y during installation.
Crimped Rear Flanges (SH) are rolled
over and riveted to add strength, elimi-
nate sharp edges, and prevent bypass
leakage.
Media Pack Restraint
Steel brace on air leaving
side adds support to the
media pack.
Media Pack Sealant A layer
of high efficiency media seals the
media pack into the cell sides.
The media sealant prevents by-
pass leakage and damage to the
media and separators during
shipping and handling. By allow-
ing slight movement of the media
pack when the filter is jarred, the
cushioning sealant helps prevent
tears and punctures to the media.
VariCel media is manufactured
with two layers of glass fibers:
coarser fibers on the air entering
side and finer fibers on the air
leaving side.
Our dual density design allows
dirt particles to be collected
throughout the entire depth of
the filter utilizing the full clean-
ing potential of the media. Maximum dust holding capacity ex-
tends the life of the filter, minimizing operating costs.
The water resistant media can withstand intermittent exposure to
water, making VariCel filters ideal for installations in humid areas
or where the filters are exposed to moisture.
DUAL DENSITY MEDIA
REDUCES OPERATING COSTS
FINER FIBERS
Air leaving side
COARSE FIBERS Air entering side
AIRFLOW
VariCel's rigid construction
with supported pleat media
pack maintains a compact,
unitized structure even under
tough operating conditions.
Variable air velocity and re-
peated fan shutdown do not
compromise performance.
Unitized Construction
Interlocked header and cell
sides, along the entire length
of each side, provide maxi-
mum sealing. Competitive fil-
ters are designed with loose
fitting headers which allow
greater potential for bypass
leakage.
BUILT RUGGED FOR DEPENDABLE PERFORMANCE
Pleats and Separators
Bonded For Strength
During the pleating process,
spots of glue are applied to
bond each separator to the ad-
jacent pleat. This solidifies the
media pack to minimize move-
ment and prevent media dam-
age. Burst strength is
increased to prevent the filter
from blowing out under vari-
able air volume conditions or
unusually high resistance.
Galvanized steel headers and
cell sides resist damage during
shipping and handling, and
prevent corrosion over long
service life. (HT VariCel filters
are constructed of aluminized
steel.)
Easy Installation
Rigid construction and mini-
mum depth make VariCel fil-
ters easy to install in all types
of systems.
VariCel
Construction
Header
Cell Side
Header
Cell Side
Potential Leak Path
Typical
Competitive
Construction
10
20
30
50
40
60
70
80
100
90
.1 .2 .4 .6 .8 1 2 4 6 8 10
0
Efficiency by Particle Size*
PARTICLE SIZE (MICRONS)
E
F
F
I
C
I
E
N
C
Y

(
%
)
80-85%
VARICEL

/VARICEL

with Intersept

OPERATING DATA
12" Deep Filters 6" Deep Filters
FILTER FACE VELOCITY (FPM)
I
N
I
T
I
A
L

R
E
S
I
S
T
A
N
C
E

(
I
N
.

W
G
)
Initial Resistance vs. Filter Face Velocity Operating Temperature Limits
VariCel Model Temperature Limit
Types SH, DH, XL 350F 177C
Type HT-500 500F 260C
Type HT-725 750F 385C
Type HT-900 900F 482C
Type NH 200F 93C
Underwriters Laboratories Inc. Classification: All VariCels are Class1.
Testing was per formed according to U.L. Standard 900 and CAN 4-S111.
OPTIONS
VariCel filters can be ordered with faceguards
made of flattened, expanded, aluminized
steel on one or both sides of the filter.
Factory installed gaskets are available on the
front or back of the header.
Vinyl Coated Separators are available for cor-
rosive conditions.
1
1
8" Single Header VariCels, designed for
other manufacturers' equipment, are also
available.
90-95%
90-95% XL/ 80-85%
60-65%
60-65% XL
90-95%
60-65%
PREFILTERS CAN DOUBLE VARICEL LIFE
Using prefilters, such as AAF's PerfectPleat

pleated fil-
ters or 5700 panel filters, will greatly extend the life of
VariCel filters.
12" deep filters are rated at 500 FPM filter face velocity.
6" deep filters are rated at 250 FPM filter face velocity.
Recommended final resistance for all VariCel filters is 1.2" wg.
* Tested in accordance with ASHRAE standards 52.2-1999

AFP-1-158P DEC '03 MP 10M


For Additional Information On AAF Products,
Call Customer Ser vice
888. AAF. 2003
2003 AAF INTERNATIONAL
10300 ORMSBY PARK PL STE 600
LOUISVILLE KY 40223-6169
P O BOX 35690
LOUISVILLE KY 40232-5690
www.aafintl.com
90-95% (MERV 14)
60-65% (MERV 11)
80-85% (MERV 13)
VariCel

II
B E T T E R A I R I S O U R B U S I N E S S

Low Depth Compact Filter


For Commercial and Industrial HVAC Systems
G Low depth saves space
G Classification ranges
F6 and F8
G Lightweight and
easy-to-install
G Economic to transport
G High dust holding
capacity
When installation space is limited and high
quality air filtration is required, VariCel II
is the solution. This low depth, lightweight
filter is available in EN779 classification
ranges F6 and F8. It displays low media
resistance which means low energy
consumption. Due to its lightweight and
low depth it is economic to ship compared
to other heavier, bulkier types of filter.
VariCel II is suitable for use in front, rear
and side access HVAC installations.
The filter is also suitable for use in variable
air volume systems and can withstand
repeated fan shut down and turbulent
airflow. VariCel II has a high dust holding
capacity and long service life. It can resist
intermittent exposure to water and
provides excellent performance in
conditions of high relative humidity.
0 1.0 2.0 3.0 4.0
0
50
75
25
100
125
175
225
200
150
60%
90%
2.5
I
n
i
t
i
a
l

R
e
s
i
s
t
a
n
c
e

(
P
a
)
Face Velocity (m/s)
Initial Resistance vs Face Velocity
VariCel

II
RA-2-599-IN-1-0198 1998 AAF International
Maximum operating temperature : 65 C
Media : Dual density glass fibre
Filter frame : Natural kraft pine and hardwood fibre
Disposal : Municipal incinerator
Specification
Underwriters Laboratories Inc. Listing
VariCel II filters are Class 2 approved according to U.L. Standard 900.
1) Width and height dimensions are interchangeable. VariCel II filters can be installed horizontally or vertically.
2) All performance data based on ASHRAE 52: 1.1992. Classification in accordance with EN779.
For maximum service life, VariCel II filters should always be operated with a prefilter.
3) Available for side access installations designed with a 18 mm or 22 mm or customized wide stationary track.
Technical Data
AAF has a policy of continuous product research and improvement and reserves the right to change design and
specifications without notice
11.80
10.31
9.85
8.18
8.83
8.18
6.50
5.85
2.97
3400
2975
2805
2380
2550
2380
1870
1700
850
0.944
0.826
0.780
0.661
0.708
0.661
0.519
0.472
0.236
0.944
0.826
0.780
0.661
0.708
0.661
0.519
0.472
0.236
170
170
170
170
170
170
170
170
170
100
100
100
100
100
100
100
100
100
594x594x97
492x619x97
492x594x97
492x492x97
441x594x97
391x619x97
391x492x97
289x594x97
289x289x97
24x24x4
3)
20x25x4
20x24x4
3)
20x20x4
18x24x4
16x25x4
16x20x4
12x24x4
3)
12x12x4
24x24x4
3)
20x25x4
20x24x4
3)
20x20x4
18x24x4
16x25x4
16x20x4
12x24x4
3)
12x12x4
Nominal
Size
1)
(wxhxd)
(inches)
Actual
Size
1)
(wxhxd)
(mm)
Gross
Media
Area
(m
2
)
Rated
Air Flow
Capacity
2)
(m
3
/h) (m
3
/s)
Rated
Initial
2)
Resistance
(Pa)
90% Average Efficiency - F 8
11.80
10.31
9.85
8.18
8.83
8.18
6.50
5.85
2.97
3400
2975
2805
2380
2550
2380
1870
1700
850
594x594x97
492x619x97
492x594x97
492x492x97
441x594x97
391x619x97
391x492x97
289x594x97
289x289x97
60% Average Efficiency - F 6
AAF-International B.V.
P.O. Box 7928
1008 AC Amsterdam
The Netherlands
Tel.: + 31 20 549 44 11
Fax: + 31 20 644 43 98
International AAF Offices:
Vienna (A), Montreal (CDN), Dortmund (D),
Vitoria (E), Paris (F), Cramlington (GB),
Athens (GR), Milan (I), Riyadh (KSA),
Mexico (Mex), Amsterdam (NL), Singapore,
Istanbul (TR), Louisville, Ky (USA)
AAF Agents:
Copenhagen (DK), Bangalore (IND)
Oslo (N), Lisbon (P), Johannesburg (RSA),
Dalsjfors (S), Malm (S), Helsinki (SF)
VariPak

B E T T E R A I R I S O U R B U S I N E S S

Multi-Purpose High Efficiency Compact Filter


G For use as prefilter or fine
filter
G F6, F7 and F8 classified
according to EN779
G Various media pack depths
and cell side combinations
available
G Low resistance = long
service life
G Maximum operating
temperature 70C
Applications
VariPak is a multi-purpose air filter.
It can be used as a prefilter to a
HEPA filter operating at low face
velocity or as a fine filter in
commercial HVAC systems at a
recommended face velocity of 1.0 -
1.5 m/s. The filter is available in the
classification ranges F6, F7 and F8 in
accordance with EN779.
The Filter
Depending on the application,
VariPak can be supplied in a wide
variety of mini-pleat media pack
depths and cell side configurations,
including non-shedding MDF,
die-cut, extruded aluminium and
aluminized U-profile. The ultra fine
glass fibre media pack features
thermoplastic separators which
maintain uniform spacing between
pleats and ensure low media
resistance: low media resistance
translates into low energy
consumption and long service life.
The filter can be supplied with or
without a one-piece gasket and in
certain configurations with a
faceguard.
0 0.2
0
150
250
200
100
50
0.6 0.8 0.4 1.0 1.2 1.4 1.6 1.8 2.0
VariPak 80%
Face Velocity m/sec.
I
n
i
t
i
a
l

R
e
s
i
s
t
a
n
c
e

P
a
1
2
3
4
5
0
0
150
250
200
100
50
1.0 0.5 1.5 2.0
VariPak 90%
Face Velocity m/sec.
I
n
i
t
i
a
l

R
e
s
i
s
t
a
n
c
e

P
a
1
2
3
4
5
0 0.5
0
60
100
80
90
40
20
50
70
30
10
1.0 1.5 2,0
VariPak 60%
Face Velocity m/sec.
I
n
i
t
i
a
l

R
e
s
i
s
t
a
n
c
e

P
a
5
4
3
2
1
1: 25 mm 1.0 m/s 3: 48 mm 1.3 m/s 5: 96 mm 1.5 m/s
2: 35 mm 1.0 m/s 4: 72 mm 1.5 m/s
1: 25 mm 1.0 m/s 3: 48 mm 1.3 m/s 5: 96 mm 1.5 m/s
2: 35 mm 1.0 m/s 4: 72 mm 1.5 m/s
1: 25 mm 1.0 m/s 3: 48 mm 1.3 m/s 5: 96 mm 1.5 m/s
2: 35 mm 1.0 m/s 4: 72 mm 1.5 m/s
VariPak

RA-2-509-IN-1-0699 1999 AAF International


AAF has a policy of continuous product research and improvement and reserves the right to change design and
specifications without notice
AAF-International B.V.
P.O. Box 7928
1008 AC Amsterdam
The Netherlands
Tel.: + 31 20 549 44 11
Fax: + 31 20 644 43 98
International AAF Offices:
Vienna (A), Montreal (CDN), Dortmund (D),
Vitoria (E), Paris (F), Cramlington (GB),
Athens (GR), Milan (I), Riyadh (KSA),
Mexico (Mex), Amsterdam (NL), Singapore,
Istanbul (TR), Louisville, Ky (USA)
AAF Agents:
Copenhagen (DK), Bangalore (IND)
Oslo (N), Lisbon (P), Johannesburg (RSA),
Dalsjfors (S), Malm (S), Helsinki (SF)
How to Order
Below a typical example of the Style Code for a standard VariPak filter using the
Component Definition Code System.
Item Component Component Code Definition
A Filter Type VP = VariPak
B Efficiency 6 = 60 - 65%
9 = 80 - 85%
10 = 90 -95%
C Cell sides 10 = die - cut, 11 = Aluminium extrusion
72 = MDF
89 = Aluminized steel
99 = Aluminium extrusion
90 = Aluminium extrusion with 20 mm flange for 3 media
D Pack Depth P = 25 mm R = 35 mm
K = 48 mm M = 96 mm
L = 72 mm
E Bond 9 = Polyurethane
2 = polyurethane flame retandant
0 = none on filters with die-cut cell sides
F Gasket type S = foamed polyurethane
P = No gasket
T = neoprene 6 mm
A = special
G Gasket location 0 = none 2 = air leaving side
1 = air entering side 3 = both sides
H Faceguard P = none A = Aluminium
E = epoxy coated steel U = Aluminized expanded metal
Z = special
I Faceguard location 0 = none 1 = Air leaving side
2 = Air entry side 3 = Both sides
Item A B C D E F G H I
Component
Definition VP 6 72 K 9 S 2 P 0
Standard Sizes and Ratings
Size in mm Nominal
without gasket airflow
H W D m
3
/h m
3
/s
96 mm pack
610 610 292 2000 0,55
610 610 149 2000 0,55
72 mm pack
610 610 292 2000 0,55
610 610 149 2000 0,55
48 mm pack
610 610 78 1740 0,48
610 610 149 1740 0,48
35 mm pack
610 610 78 1340 0,37
610 610 56 1340 0,37
25 mm pack
610 610 78 1340 0,37
610 610 56 1340 0,37
x x
x x
x x
x x
x x
x x
x x
x x
x x
x x
x x
Operating Temperature
VariPak air filters have a maximum
operating temperature of 70C.
Disposal
MDF and die-cut versions can be
disposed of by incineration. Products
with metal parts can be landfilled.
Recommended Final Resistance
The recommended final resistance is
450 Pa.
VariCel V
G Lightweight and
easy to install
G Classification ranges
F6, F7, F8 and F9
G Excellent performance
in difficult operating
conditions
G High air volume capacity:
upto 5000 m
3
/h
G High dust holding
capacity
VariCel V are lightweight compact filters
designed for use in industrial and
commercial HVAC installations.
Available in the EN779 classification range
F6 - F9, their rigid design and pleated
media pack with thermoplastic separators
ensure they deliver the desired air quality
when used in variable air volume systems
and subjected to repeated fan shutdown,
high relative humidity and intermittent
exposure to water.
Due to their 5000m
3
/h capacity, VariCel V
offer many cost saving benefits. In new
installations fewer filters are needed to
handle the same volume of air compared
to filters of the same size with a lower
capacity. Fewer filters mean less installation
space for the filtration system. They can
also be used in existing systems to increase
the air capacity. VariCel V display low
media resistance and have a high dust
holding capacity and long service life.
B E T T E R A I R I S O U R B U S I N E S S

Lightweight Compact Filters For Commercial and


Industrial HVAC Systems
Airflow Resistance
VV6-series
200
175
150
125
100
75
50
25
0
95%
80%
60%
0 1.0 2.0 3.0 4.0
90%
I
n
i
t
i
a
l

R
e
s
i
s
t
a
n
c
e

(
P
a
)
Face Velocity (m/s)
Varicel V
RA-2-08-IN-4-0198 1999 AAF International
AAF has a policy of continuous product research and improvement and reserves the right to change design and
specifications without notice.
Specifications
Maximum operating temperature : 70 C
Media : Ultra fine glass fibres woven into mat
Separators : Thermoplastic
Cell Sides : Recycled polystyrene
VV6- 6-24.24-12
4)
VV6- 6-20.24-12
4)
VV6- 6-12.24-12
4)
VV6- 9-24.24-12
VV6- 9-20.24-12
VV6- 9-12.24-12
VV6-10-24.24-12
VV6-10-20.24-12
VV6-10-12.24-12
VV6-11-24.24-12
VV6-11-20.24-12
VV6-11-12.24-12
592 x 592 x 292
490 x 592 x 292
287 x 592 x 292
592 x 592 x 292
490 x 592 x 292
287 x 592 x 292
592 x 592 x 292
490 x 592 x 292
287 x 592 x 292
592 x 592 x 292
490 x 592 x 292
287 x 592 x 292
5000
4165
2500
5000
4165
2500
5000
4165
2500
5000
4165
2500
1,39
1,15
0,69
1,39
1,15
0,69
1,39
1,15
0,69
1,39
1,15
0,69
4250
3540
2125
4250
3540
2125
4250
3540
2125
4250
3540
2125
1,18
0,98
0,59
1,18
0,98
0,59
1,18
0,98
0,59
1,18
0,98
0,59
60-65
60-65
60-65
80-85
80-85
80-85
90-95
90-95
90-95
> 95
> 95
> 95
6
6
6
7
7
7
8
8
8
9
9
9
600
600
600
600
600
600
600
600
600
600
600
600
Type Size
1)
(mm)
HxWxD
Airflow
Maximum Nominal
m
3
/h m
3
/h m
3
/s
Average
Efficiency
2)
%
EN
779
Class
2
Initial
Resistance
at Nominal
Airflow (Pa)
Final
Resistance
3)
(Pa)
m
3
/s
1) Width and height are interchangeable, pleats can be either vertical or horizontal without affecting performance.
2) All performance data based on EN779.
3) Recommended maximum value. Filters can be operated to a lower final resistance without materially effecting filter efficiency.
4) Suffix "C" denotes cellulose media option.
110
110
110
125
125
125
145
145
145
180
180
180
Technical Data
AAF-International B.V.
P.O. Box 7928
1008 AC Amsterdam
The Netherlands
Tel.: + 31 20 549 44 11
Fax: + 31 20 644 43 98
International AAF Offices:
Vienna (A), Montreal (CDN), Dortmund (D),
Vitoria (E), Paris (F), Cramlington (GB),
Athens (GR), Milan (I), Riyadh (KSA),
Mexico (Mex), Amsterdam (NL), Singapore,
Istanbul (TR), Louisville, Ky (USA)
AAF Agents:
Copenhagen (DK), Bangalore (IND)
Oslo (N), Lisbon (P), Johannesburg (RSA),
Dalsjfors (S), Malm (S), Helsinki (SF)
BioCel

I
G Airflow range:
500 - 2000 m
3
/h
G Classified H11 in
accordance with EN1822
G Benefits in existing and
new installations
G Lower energy costs
As a H11 EN1822 classified filter,
BioCel I is the ideal choice for customers
wishing to upgrade a non-HEPA
installation to a HEPA installation. With
an airflow range of 500 - 2000 m
3
/h,
BioCel I is ideally suited for variable air
volume and turbulent air flow systems.
BioCel I displays low media resistance
which results in lower energy costs and
longer service life. The filter is designed
for use in clean areas in the pharma-
ceutical, microelectronic, semi-conductor
and healthcare industries in which high
efficiency air filtration on fine particulates
is required. Temperature limit: 90C.
B E T T E R A I R I S O U R B U S I N E S S

High Quality HEPA Filter For Use In Clean Zones


Resistance vs Face Velocity
0 1.87 1.5 1.13 2.25 0.37 0.75
0
150
250
200
100
50
149 mm 292 mm
I
n
i
t
i
a
l

R
e
s
i
s
t
a
n
c
e

(
P
a
)
Face Velocity (m/s)
BioCel

I
RA-2-527-IN-1-0897 1997 AAF International
AAF has a policy of continuous product research and improvement and reserves the right to change design and
specifications without notice.
Size Classification Low Airflow Initial High Airflow Initial Efficiency* Media Area
(mm) EN1822 m
3
/h Resistance (Pa) m
3
/h Resistance (Pa) % @ 0.3 m m
2
610 x 610 x 292 H11 2000 165 3000 250 98 14.6
610 x 610 x 149 H11 1000 165 1500 250 98 6.8
Technical Data
Technical Data Standard Execution
Dimensions : 610 x 610 x 292 mm, 610 x 610 x 149 mm
Media : Submicron glass fibres formed into high density paper
Cell sides : MDF
Separators : Corrugated aluminium
Bond : Cold cured resin
Gasket : One piece gasket
Disposal : Landfill
Temperature limit : 90 C
Style code : D72J9S2F
Note: Non-standard sizes and executions available upon request
* Efficiency % @ MPPS > 95%
AAF-International B.V.
P.O. Box 7928
1008 AC Amsterdam
The Netherlands
Tel.: + 31 20 549 44 11
Fax: + 31 20 644 43 98
International AAF Offices:
Vienna (A), Montreal (CDN), Dortmund (D),
Vitoria (E), Paris (F), Cramlington (GB),
Athens (GR), Milan (I), Riyadh (KSA),
Mexico (Mex), Amsterdam (NL), Singapore,
Istanbul (TR), Louisville, Ky (USA)
AAF Agents:
Copenhagen (DK), Bangalore (IND)
Oslo (N), Lisbon (P), Johannesburg (RSA),
Dalsjfors (S), Malm (S), Helsinki (SF)
BioPak

G H11 classified in
accordance with EN1822
G Recessed pack ensures
easy handling
G Non-shedding
MDF cell sides
G Low resistance ensures
low energy consumption
G One-piece gasket
provides leaktight seal
BioPak filters are classified H11 in
accordance with EN1822. They are the
ideal solution for upgrading an existing
non-HEPA HVAC installation into a
HEPA installation. Their recessed mini-
pleat media pack make BioPak filters easy
to handle and install while high quality
MDF cell sides ensure a smooth non-
shedding construction. The filter can be
installed with the pleats in the vertical or
horizontal position.
BioPak filters offer low media resistance
which results in low energy consumption
and long service life. A one-piece gasket
around the perimeter of the filter ensures
leaktight installation. The filters are made
of fully incinerable materials.
Temperature limit: 70C.
B E T T E R A I R I S O U R B U S I N E S S

High Quality HEPA Filters


Resistance vs Face Velocity
0 0.30
0
150
250
200
100
50
149 mm
292 mm
0.45 0.60 0.75 0.90 1.05 1.20 1.37 1.50
I
n
i
t
i
a
l

R
e
s
i
s
t
a
n
c
e

(
P
a
)
Face Velocity (m/s)
BioPak

RA-2-539-IN-1-0897 1997 AAF International


AAF has a policy of continuous product research and improvement and reserves the right to change design and
specifications without notice.
Size Classification Low Airflow Initial High Airflow Initial Efficiency* Media Area
(mm) EN1822 m
3
/h Resistance (Pa) m
3
/h Resistance (Pa) % @ 0.3 m m
2
610 x 610 x 78 H11 600 90 1000 120 98 8.8
610 x 610 x 149 H11 1000 120 1500 180 98 8.8
610 x 610 x 292 H11 1000 90 2000 250 98 17.5
Technical Data
Technical Data Standard Execution
Dimensions : 610 x 610 x 292 mm, 610 x 610 x 149 mm,
610 x 610 x 78 mm
Media : High density paper made from ultra-fine glass fibres
Cell sides : MDF
Separators : Thermoplastic ribbon
Bond : Cold cured resin
Gasket : One piece gasket
Disposal : Incineration or landfill
Temperature limit : 70 C
Style code : D72M9S2F for 292 mm depth
D72K9S2F for 149 and 78 mm depth*
Note: Non-standard sizes and executions available upon request
* Efficiency % @ MPPS > 95%
* Specify depths acquired
AAF-International B.V.
P.O. Box 7928
1008 AC Amsterdam
The Netherlands
Tel.: + 31 20 549 44 11
Fax: + 31 20 644 43 98
International AAF Offices:
Vienna (A), Montreal (CDN), Dortmund (D),
Vitoria (E), Paris (F), Cramlington (GB),
Athens (GR), Milan (I), Riyadh (KSA),
Mexico (Mex), Amsterdam (NL), Singapore,
Istanbul (TR), Louisville, Ky (USA)
AAF Agents:
Copenhagen (DK), Bangalore (IND)
Oslo (N), Lisbon (P), Johannesburg (RSA),
Dalsjfors (S), Malm (S), Helsinki (SF)
BioCel

V
G H10 classification in
accordance with EN1882
G High air capacity:
3000 m
3
/h
G Reduced energy costs
and long service life
G Lightweight and
easy to install
BioCel V is designed for industrial
HVAC installations in which HEPA
quality air filtration is required. As a H10
EN1882 classified air filter, BioCel V is
ideal for upgrading an existing
non-HEPA HVAC installation to a
HEPA installation. The filters mini-pleat
media provides high quality filtration on
fine particulate matter removing tiny dust
particles from the airstream efficiently.
Because of its 3000 m
3
/h air capacity,
BioCel V is an ideal choice in new
installations as fewer filters are needed to
handle the same volume of air compared
to HEPA filters of the same size with a
lower capacity. Fewer filters means less
installation space. The filter displays low
media resistance which results in low
energy costs and long service life.
Lightweight, BioCel V is easy to handle
and install. Temperature limit: 70C.
B E T T E R A I R I S O U R B U S I N E S S

High Quality Compact HEPA Filter for HVAC Systems


Resistance vs Face Velocity
0 1.87 1.5 1.13 2.25 0.37 0.75
0
120
200
160
80
40
20
140
180
100
60
I
n
i
t
i
a
l

R
e
s
i
s
t
a
n
c
e

(
P
a
)
Face Velocity (m/s)
BioCel

V
RA-2-541-IN-2-0899 1999 AAF International
AAF has a policy of continuous product research and improvement and reserves the right to change design and
specifications without notice.
Size Classification Low Airflow Initial High Airflow Initial Efficiency* Media Area
(mm) EN1822 m
3
/h Resistance (Pa) m
3
/h Resistance (Pa) % @0.3 m m
2
592 x 592 x 292 H10 2000 120 3000 200 95 20.4
287 x 592 x 292 H10 1000 120 1500 250 95 9.0
Technical Data
Technical Data Standard Execution
Dimensions : 610 x 610 x 292 mm, 292 x 610 x 292 mm,
Media : Ultra-fine glass fibres formed into a high density paper
Cell sides : Polystyrene
Separators : Thermoplastic ribbon
Disposal : Landfill or incineration
Temperature limit : 70 C
Style code : BV6-2424-12 resp. BV6-1224-12
Note: Non-standard sizes and executions available upon request
* Efficiency % @ MPPS > 85%
AAF-International B.V.
P.O. Box 7928
1008 AC Amsterdam
The Netherlands
Tel.: + 31 20 549 44 11
Fax: + 31 20 644 43 98
International AAF Offices:
Vienna (A), Montreal (CDN), Dortmund (D),
Vitoria (E), Paris (F), Cramlington (GB),
Athens (GR), Milan (I), Riyadh (KSA),
Mexico (Mex), Amsterdam (NL), Singapore,
Istanbul (TR), Louisville, Ky (USA)
AAF Agents:
Copenhagen (DK), Bangalore (IND)
Oslo (N), Lisbon (P), Johannesburg (RSA),
Dalsjfors (S), Malm (S), Helsinki (SF)
AstroCel

I
G Filter class H13 and H14
according to EN1822
G Non-shedding
construction
G Improves quality of
manufacturing processes
and products
AstroCel I filters owe their excellent air
cleaning efficiency to their advanced
design. High quality MDF cell sides
ensure a smooth, non-shedding
construction, while a rigid pleated media
pack with aluminium separators provides
high efficiency air filtration on fine
particulates at the lowest possible
resistance. Galvanized steel and stainless
steel cell sides are also available.
AstroCel I filters are classified H13 and
H14 in accordance with EN1822.
Additional benefits include:
G Factory tested to meet the most
stringent legal and industry
requirements.
G Easy to install.
B E T T E R A I R I S O U R B U S I N E S S

High Efficiency Particulate Air Filter (HEPA)


Resistance vs Face Velocity
0 1.0 1.25 1.5 1.75 2.0 0.25 0.50 0.75 2.25
0
100
50
150
400
350
300
200
250
1 2 3 4
1. 292 mm, H13 3. 149 mm, H13
2. 292 mm, H14 4. 149 mm, H14
I
n
i
t
i
a
l

R
e
s
i
s
t
a
n
c
e

(
P
a
)
Face Velocity (m/s)
AstroCel

I
RA-4-701-IN-3-1299 1999 AAF International
AAF has a policy of continuous product research and improvement and reserves the right to change design and
specifications without notice.
How to Order
Below a typical example of how to order a standard AstroCel I filter using
the Component Code Definition System.
An AstroCel I can be ordered using the following Component Code Definition System.
Use the table to specify a product suitable to your application requirements.
Selection Table Standard Sizes and Ratings
Item Component Component Code Definition*
A Media A = Waterproof glass fibre
E = Waterproof glass fibre
B Cell Sides 24 = Galvanized steel
26 = Stainless steel
72 = MDF
C Separators J = Aluminium
D Bond 5 = Silicone
9 = Cold cured resin
E Gasket P = No gasket
S = 7 mm, half round profile, one piece foamed
T = 6 mm, flat profile
Y = 6,5 mm, silicone rubber
F Gasket Location 0 = No gasket
2 = One face
3 = Both faces
G Acceptance Level H = H13 99.95% @ MPPS, acc. to EN1822
R = H14 99.995% @ MPPS, acc. to EN1822
Size in mm Nominal
without gasket
1)
airflow
H W D m
3
/h m
3
/s
610 305 149 500 0.14
610 610 149 1000 0.28
610 762 149 1250 0.35
610 305 292 1000 0.28
610 610 292 2000 0.56
610 762 292 2500 0.69
Item A B C D E F G
Component
Definition A 72 J 9 S 2 H
* Bold typeface: standard execution
1) The H (Height) dimension also indicates
the vertical position of the separators.
AstroCel I filters should always be
installed with the separators in the vertical
position.
2) Other sizes available on request.
Notes:
- Initial resistance at nominal airflow is:
250 Pa for H13 filters
320 Pa for H14 filters.
- Recommended final resistance is 750 Pa.
- Temperature limit: 90C.
(200C for A 24 J 5 Y 2 R,
260C for A 26 J 5 Y 2 R.)
Efficiency
Efficiency Efficiency EN1822
@ 0.3 m @ MPPS
99.997% H13 99.95%
99.999% H14 99.995%
AAF-International B.V.
P.O. Box 7928
1008 AC Amsterdam
The Netherlands
Tel.: + 31 20 549 44 11
Fax: + 31 20 644 43 98
International AAF Offices:
Vienna (A), Montreal (CDN), Dortmund (D),
Vitoria (E), Paris (F), Cramlington (GB),
Athens (GR), Milan (I), Riyadh (KSA),
Mexico (Mex), Amsterdam (NL), Singapore,
Istanbul (TR), Louisville, Ky (USA)
AAF Agents:
Copenhagen (DK), Bangalore (IND)
Oslo (N), Lisbon (P), Johannesburg (RSA),
Dalsjfors (S), Malm (S), Helsinki (SF)
AstroCel

I HC
G High air volume filter:
3000 m
3
/h
G Classified H12, H13 and
H14 according to
EN1822
G Space saving design
G Saves energy in existing
installations
AstroCel I High Capacity are classified
H12, H13 and H14 in accordance with
EN1822 and are designed for
applications in which a high volume of
air has to be throughput. Because of their
high capacity, fewer filters are needed to
handle the same volume of air compared
to other HEPA filters of the same size.
AstroCel I HC filters owe their high
capacity to a unique separator design
which allows denser packing of the filter
media. The benefits to the customer are
numerous:
G In new installations, fewer filters mean
less costly installation space is
necessary.
G In existing installations, low pressure
drop means lower energy costs and
longer service life.
G Standard individually tested.
B E T T E R A I R I S O U R B U S I N E S S

High Quality HEPA Filter


Resistance vs Face Velocity
0 1.0 1.25 1.5 1.75 2.0 0.25 0.50 0.75 2.25
0
100
50
150
400
350
300
200
250
1
2
1. 292 mm, H12 / H13
2. 292 mm, H14
Face Velocity (m/s)
I
n
i
t
i
a
l

R
e
s
i
s
t
a
n
c
e

(
P
a
)
AstroCel

I HC
RA-4-721-IN-3-1299 1999 AAF International
AAF has a policy of continuous product research and improvement and reserves the right to change design and
specifications without notice.
How to Order
Below a typical example of how to order a standard AstroCel I HC filter using the
Component Code Definition System.
An AstroCel I HC can be ordered using the following Component Code Definition System.
Use the table to specify a product suitable to your application requirements.
Selection Table Standard Sizes and Ratings
Item Component Component Code Definition*
A Media A = Waterproof glass fibre
E = Waterproof glass fibre
B Cell Sides 24 = Galvanized steel
26 = Stainless steel
72 = MDF
C Separators H = Aluminium (HC pleat)
D Bond 9 = Cold cured resin
E Gasket P = No gasket
S = 7 mm, half round profile, one piece foamed
T = 6 mm, flat profile
F Gasket Location 0 = No gasket
2 = One face
3 = Both faces
G Acceptance Level G = H12 99.5% @ MPPS acc. to EN1822**
H = H13 99.95% @ MPPS acc. to EN1822
R = H14 99.995% @ MPPS acc. to EN1822
Size in mm Nominal
without gasket airflow
H W D m
3
/h m
3
/s
610 305 292 1500 0.42
610 610 292 3000 0.83
610 762 292 3750 1.04
Item A B C D E F G
Component
Definition A 72 H 9 S 2 H
* Bold typeface: standard execution
** Non leaktested filter
1) The H (Height) dimension also indicates
the vertical position of the separators.
AstroCel I HC filters should always be
installed with the separators in the vertical
position.
Notes:
- Initial resistance at nominal airflow is:
300 Pa for H12 / H13 filters
350 Pa for H14 filters.
- Recommended final resistance 750 Pa.
- Temperature limit: 90C.
(200C for A 24 H 5 Y 2 G),
(260C for A 26 H 5 Y 2 G).
Efficiency
Efficiency Efficiency EN1822
@ 0.3 m @ MPPS
99.99% H12 99.5%
99.997% H13 99.95%
99.999% H14 99.995%
AAF-International B.V.
P.O. Box 7928
1008 AC Amsterdam
The Netherlands
Tel.: + 31 20 549 44 11
Fax: + 31 20 644 43 98
International AAF Offices:
Vienna (A), Montreal (CDN), Dortmund (D),
Vitoria (E), Paris (F), Cramlington (GB),
Athens (GR), Milan (I), Riyadh (KSA),
Mexico (Mex), Amsterdam (NL), Singapore,
Istanbul (TR), Louisville, Ky (USA)
AAF Agents:
Copenhagen (DK), Bangalore (IND)
Oslo (N), Lisbon (P), Johannesburg (RSA),
Dalsjfors (S), Malm (S), Helsinki (SF)
AstroPak

G Non-shedding
construction
G Leakfree construction
G Filter class H13 and H14
according to EN1822
AstroPak filters owe their excellent air
cleaning efficiency to their advanced
design. High quality MDF cell sides
ensure a smooth, non-shedding
construction, while a rigid mini-pleat
media pack with thermoplastic separators
provides high efficiency particulate air
filtration at the lowest possible resistance.
AstroPak filters are classified H13 and
H14 in accordance with EN1822.
Additional benefits include:
G Fully incinerable.
G Recessed pack ensures easy handling.
G Installation with pleats in vertical or
horizontal position.
G Also available with metal cell sides.
B E T T E R A I R I S O U R B U S I N E S S

High Efficiency Particulate Air Filter


0 1.0 1.25 1.5 1.75 0.25 0.50 0.75
0
100
50
150
400
350
300
200
250
Face Velocity (m/s)
I
n
i
t
i
a
l

R
e
s
i
s
t
a
n
c
e


(
P
a
)
2
1
1. 292 mm, H13
2. 78 and 149 mm, H13
Resistance vs Face Velocity
AstroPak

RA-3-535-IN-3-1299 1999 AAF International


AAF has a policy of continuous product research and improvement and reserves the right to change design and
specifications without notice.
How to Order
Below a typical example of how to order a standard AstroPak filter using
the Component Code Definition System.
An AstroPak can be ordered using the following Component Code Definition System.
Use the table to specify a product suitable to your application requirements.
Selection Table Standard Sizes and Ratings
Item Component Component Code Definition*
A Media A = Waterproof glass fibre
E = Waterproof glass fibre
B Cell Sides 24 = Galvanized steel**
72 = MDF
C Media pack K = 2 deep - 48 mm.
M = 4 deep - 96 mm
D Bond 9 = Cold cured resin
E Gasket P = No gasket
S = 7 mm, half round profile, one piece foamed
T = 6 mm, flat profile
F Gasket Location 0 = No gasket
2 = One face
3 = Both faces
G Acceptance Level H = H13 Min. 99.95% @ MPPS, acc. to EN1822
R = H14 Min. 99.995% @ MPPS, acc. to EN1822
1) AstroPak filters can be installed with the
separators in either the horizontal or
vertical position.
2) Always minimal 20 mm difference
between packdepth and filterdepth.
Notes:
- Initial resistance at nominal airflow is:
250 Pa for H13
320 Pa for H14
- Temperature limit: 70C
- Final resistance 500 - 750 Pa
Item A B C D E F G
Component
Definition A 72 K 9 S 2 H
* Bold typeface: standard execution
** Cell sides with code number 24 is only available in a limited size range
Size in mm Nominal Pack
without gasket
1)
airflow Depth
H W D m
3
/h m
3
/s mm
240 240 56 155 0.04 48
610 305 56 500 0.14 48
490 490 56 650 0.18 48
610 610 56 1000 0.28 48
305 305 78 250 0.07 48
457 457 78 570 0.16 48
305 610 78 500 0.14 48
610 610 78 1000 0.28 48
203 203 149 110 0.03 96
305 305 149 250 0.07 96
610 305 149 500 0.14 96
457 457 149 570 0.16 96
610 610 149 1000 0.28 96
610 762 149 1250 0.35 96
610 915 149 1500 0.42 96
610 1220 149 2000 0.56 96
610 1524 149 2500 0.69 96
610 1830 149 3000 0.83 96
762 762 149 1600 0.44 96
762 915 149 1900 0.53 96
762 1220 149 2500 0,69 96
762 1524 149 3150 0.88 96
762 1830 149 3800 1.06 96
915 915 149 2250 0.63 96
915 1220 149 3000 0.83 96
915 1524 149 3800 1.06 96
915 1830 149 4550 1.26 96
305 305 292 500 0.14 96
610 305 292 1000 0.28 96
610 610 292 2000 0.56 96
610 762 292 2500 0.69 96
Efficiency
Efficiency Efficiency EN1822
@ 0.3 m @ MPPS
99.997% H13 99.95%
99.999% H14 99.995%
AAF-International B.V.
P.O. Box 7928
1008 AC Amsterdam
The Netherlands
Tel.: + 31 20 549 44 11
Fax: + 31 20 644 43 98
International AAF Offices:
Vienna (A), Montreal (CDN), Dortmund (D),
Vitoria (E), Paris (F), Cramlington (GB),
Athens (GR), Milan (I), Riyadh (KSA),
Mexico (Mex), Amsterdam (NL), Singapore,
Istanbul (TR), Louisville, Ky (USA)
AAF Agents:
Copenhagen (DK), Bangalore (IND)
Oslo (N), Lisbon (P), Johannesburg (RSA),
Dalsjfors (S), Malm (S), Helsinki (SF)
AstroCel

III 3400 MDF


G H12 and H13 in
accordance with EN1822
G 3400 m
3
/h air volume
saves space
G Low energy consumption
G Non-shedding
construction
AstroCel III is classified H12 or H13 in
accordance with EN1822. The filter
displays excellent efficiency on fine
particulate matter and is designed for use
in high air volume applications upto
3400 m
3
/h. Due to its high capacity the
filter has several benefits: in new
installations, fewer filters are required to
handle the same volume of air compared
to HEPA filters of the same size with a
lower capacity. As a result, less
installation space is required and
installation time is significantly reduced.
In existing installations, the filter's high
media area ensures a low pressure drop
which reduces energy costs. Other
benefits include:
G high quality MDF cell sides ensure a
smooth, non-shedding construction
G easy installation
B E T T E R A I R I S O U R B U S I N E S S

High Efficiency Particulate Air Filters


Resistance vs Face Velocity
0 0.50 3.00 2.00 2.50 1.50 1.00
0
100
50
150
200
300
250
I
n
i
t
i
a
l

R
e
s
i
s
t
a
n
c
e

(
P
a
)
Face Velocity (m/s)
AstroCel

III 3400 MDF


RA-4-139-IN-3-1299 1999 AAF International
AAF has a policy of continuous product research and improvement and reserves the right to change design and
specifications without notice.
An AstroCel III 3400 can be ordered using the following Component Code Definition System.
Use the table to specify a product suitable to your application requirements.
How to Order
Below a typical example of how to order a standard AstroCel III 3400 filter using
the Component Code Definition System.
Selection Table Standard Sizes and Ratings
Item Component Component Code Definition*
A Type of Filter A39 = AstroCel III
B Media A = Waterproof glass fibre
C Cell Sides** 72 = MDF
D Separators C = Thermoplastic
E Bond 9 = Polyurethane cold cured resin
F Gasket P = No gasket
S = Polyurethane foam, half round profile, one piece
G Gasket Location 0 = No gasket
2 = One face
H Acceptance Level G = H12 Min. 99.5% @ MPPS acc. to EN1822 **
H = H13 Min. 99.5% @ MPPS acc. to EN1822
I Faceguard Location 0 = No faceguard
K Options Consult local sales office
Item A B C D E F G H I K
Component
Definition A39 A 72 C 9 S 2 G 0 -
Size in mm Nominal
without gasket airflow
H W D m
3
/h
610 305 292 1500
610 610 292 3400
Notes:
- Recommended final resistance 750 Pa.
- Temperature limit 70C.
- Initial resistance at nominal airflow: 250 Pa.
* Bold typeface: standard execution
** Non leaktested filter
For 4000 and NG execution consult specification sheets RA-3-129 en RA-3-124.
Efficiency
Efficiency Efficiency EN1822
@ 0.3 m @ MPPS
99.97% H12 99.5%
99.99% H13 99.95%
AAF-International B.V.
P.O. Box 7928
1008 AC Amsterdam
The Netherlands
Tel.: + 31 20 549 44 11
Fax: + 31 20 644 43 98
International AAF Offices:
Vienna (A), Montreal (CDN), Dortmund (D),
Vitoria (E), Paris (F), Cramlington (GB),
Athens (GR), Milan (I), Riyadh (KSA),
Mexico (Mex), Amsterdam (NL), Singapore,
Istanbul (TR), Louisville, Ky (USA)
AAF Agents:
Copenhagen (DK), Bangalore (IND)
Oslo (N), Lisbon (P), Johannesburg (RSA),
Dalsjfors (S), Malm (S), Helsinki (SF)
Non-Laminar Flow Cleanrooms
Basic Design and Operating Considerations
B E T T E R A I R I S O U R B U S I N E S S

In a non-laminar cleanroom or, to use its


official name, non-unidirectional airflow
cleanroom, air enters the room via filters
in the ceiling, and is exhausted via grilles
in the wall close to the floor.
The principle of this technique is based
on allowing air to flow along irregular,
random paths in a turbulent way.
The success of this technique hinges on
optimizing the mixing of clean incoming
air with dust laden air in the room and
thereby diluting the contamination level
in the cleanroom and lowering the
number of particles per m
3
. The supply
of clean air is therefore the factor which
determines the success of this technique.
In general, the greater the frequency with
which the air is renewed the lower the
contamination build-up in the room and
the greater the rate with which
impurities are diluted. On an hourly
basis, the number of air changes in a
room can vary between 10 and 50,
depending on the type of work and the
achievable Class of the room.
Although more unpredictable than
laminar airflow cleanrooms, in many
applications a non-laminar flow room
can be a cost effective solution, especially
when local laminar flow work stations
are operational in the room.
Non-Laminar Flow Cleanrooms
AAF has a policy of continuous product research and improvement and reserves the right to change design and
specifications without notice.
CR-2-741-IN-0896 1996 AAF International
Achievable Class* 1,000 (M4.5) 10,000 (M5.5) 100,000 (M6.5) Avoid
Room size (m
2
) 100 300 500
Room aspect ratio Narrow 3:1 2:1 Large square room
Room height (m) min. 3 min. 2.75 min 2.25
Area per occupant (m
2
) 20 10 5
Equipment in room Minimum 30% Floor 50% Floor
Occupant activity Sedentary Occasional movement Constant activity Frivolous activities
Traffic in/out per hour 1-2 2-6 More than 6
Occupants properly attired Full gowns Smocks Smocks Street clothes
Particle generation in room Miniature Slight Considerable
Thermal updrafts None Slight Considerable
Housekeeping Meticulous Good Mediocre
Room Pressure (Pa) 10-15 10-15 5-10 None
Air changes per hour 40-120 20-40 10-20
Airlock Adequate Small None
Clean air inlets as % of ceiling area 20-50 10-20 5-10
Clean air inlet locations Ceiling Ceiling Ceiling or high sidewall Floor
Terminal velocity at clean air inlet (m/s) 0.15-0.45 0.15-0.45 0.15-0.45
Return locations Low level or floor Low sidewall Sidewall Ceiling
Wall return spacing Continuous on all Intermittent on long Non-uniform Single
4 walls walls
Max. horizontal distance to return (m) 3 6 9
Return face velocity (m/s) 0.5-1 1-2.5 2.5
Prefilters
- First Stage** 50% dust spot eff. 90% arrestance 80% arrestance Doors open
F5 G4 G4
- Second Stage** 90% dust spot eff. 80-90% dust spot eff. 80-90% dust spot eff.
F8 F7 F7
Prefilter maintenance and inspection Quarterly Semi-annual Annual No schedule
Final Filters** min.99.999% @ 0.3 m min. 99.99% @ 0.3 m min. 95% @ 0.3 m
H14 H13 H10
Routine particle count interval Monthly Monthly Quarterly
Basic design and operating considerations
* Class according to US Federal Standard 209E (between brackets in SI)
** G and F classification in accordance with EN779. H classification in accordance with draft EN1822.
AAF-International B.V.
P.O. Box 7928
1008 AC Amsterdam
The Netherlands
Tel.: + 31 20 549 44 11
Fax: + 31 20 644 43 98
International AAF Offices:
Vienna (A), Montreal (CDN), Dortmund (D),
Vitoria (E), Paris (F), Cramlington (GB),
Athens (GR), Milan (I), Riyadh (KSA),
Amsterdam (NL), Singapore,
Istanbul (TR), Louisville, Ky (USA)
AAF Agents:
Copenhagen (DK), Oslo (N),
Lisbon (P), Johannesburg (RSA),
Dalsjfors
(S), Malm (S), Helsinki (SF)
Laminar Flow Cleanrooms
The principle of laminar airflow or, to
be more precise, unidirectional airflow
cleanrooms is based on air moving along
parallel streamlines at a uniform velocity
of 0.3 to 0.45 m/s with as little
turbulence as possible between the place
where the air enters and exits the room.
The principle is based on expelling any
dust in the airflow by the shortest route.
Basically, there are two types of laminar
airflow cleanroom:
a) Vertical downflow
b) Horizontal crossflow
Vertical Downflow
In a vertical downflow cleanroom, air
enters the room via filters in the ceiling
surface and is exhausted via a perforated
floor. This downward aiflow flushes
contaminated air particles out of the
room via the floor, thus preventing a
build-up of contaminated particles.
Particles generated at one work station
are therefore removed before they have
the chance to migrate. The air velocity
in this type of cleanroom is usually 0.3
to 0.45 m/s.
Horizontal Crossflow
In a horizontal crossflow cleanroom, the
direction of airflow is from left to right
or right to left across the room. Air
enters the room via filters in one wall
and is exhausted and/or recirculated via
a bank of filters and perforated panels in
the opposite wall. The air velocity has to
be established at a sufficiently high level,
usually 0.45 m/s, to counter the effects
of upward thermal movement of
particles. In work stations close to the
high efficiency filter wall, Class 100 or
better is possible.
Since the flow of particles in this type of
cleanroom is in the horizontal direction,
the particle contamination generated at
one work station can be transported to
work stations further downstream of the
filters. This, however, is dependent on
the type of work or the process(es) being
carried out in the cleanroom. Horizontal
crossflow is nevertheless a very practical
and cost effective system, particularly in
cleanrooms which have to be built in
existing spaces with limited ceiling
height.
B E T T E R A I R I S O U R B U S I N E S S

Basic Design and Operating Considerations


Laminar Flow Cleanrooms
CR-2-740-IN-0896 1996 AAF International
AAF-International B.V.
P.O. Box 7928
1008 AC Amsterdam
The Netherlands
Tel.: + 31 20 549 44 11
Fax: + 31 20 644 43 98
International AAF Offices:
Vienna (A), Montreal (CDN), Dortmund (D),
Vitoria (E), Paris (F), Cramlington (GB),
Athens (GR), Milan (I), Riyadh (KSA),
Mexico (Mex), Amsterdam (NL), Singapore,
Istanbul (TR), Louisville, Ky (USA)
AAF Agents:
Copenhagen (DK), Bangalore (IND)
Oslo (N), Lisbon (P), Johannesburg (RSA),
Dalsjfors (S), Malm (S), Helsinki (SF)
AAF has a policy of continuous product research and improvement and reserves the right to change design and
specifications without notice.
Achievable Class* 1 and 10 (M1.5 and M2.5) 100 (M3.5)
Area per occupant 40 m
2
30 m
2
Occupants properly attired Full gowns Full gowns
Occupant activity Minimum Minimum
Equipment in room Minimum Minimum
Housekeeping Meticulous Meticulous
Room pressurized 15 Pa 15 Pa
Air changes per hour 500-600 500
Air lock Yes Yes
Clean air inlets as % of ceiling area 90-100% 90%
Clean air inlet locations Ceiling Ceiling (wall)
Terminal velocity at clean air inlet 0.3 - 0.45 m/s 0.3 - 0.45 m/s
Return air location Perforated floor Low level or floor
(opposite wall, 0.45 m/s)
Prefilters:
- First stage** 30% dust spot efficiency 50% dust spot efficiency
F5 F5
- Second stage** 95% @ 0.3 m 90% dust spot efficiency
H10 F9
Prefilter maintenance and inspection Monthly Monthly
Final filters** Min. 99.9995% on 0.12 m (for Class 10) Min. 99.999% @ 0.3 um
U15 H14
Min. 99.99995% on 0.12 m (for Class 1)
U16
Routine particle count interval Daily Weekly
* Class according to US Federal Standard 209E (between brackets in SI)
** G and F classification in accordance with EN779. H and U classification in accordance with draft EN1822.
Basic design and operating considerations
EN779
B E T T E R A I R I S O U R B U S I N E S S

New European Standard for Coarse and Fine Filters


In 1993, the European Committee
for Standardization, Technical
Committee 195, Work Group 1
(CEN/TC195-WG1) established a
new standard for general ventilation
filters. With the introduction of this
standard under document name EN
779, member countries of the
European Union are obliged to issue
their own national version of this
standard within the existing
framework of their own national
standards organizations.
For example, BS EN 779 in the U.K.
and DIN EN 779 in Germany.
EN 779 is based on existing
documents such as EUROVENT
4/5, and ASHRAE 52.1:1992, but is
in fact more stringent than either of
these standards. The standard
incorporates a new system of
classification for Coarse and Fine
filters based on an average dust spot
efficiency at a specified final pressure
drop.
Filters with an initial dust spot
efficiency below 20% are classified as
Arrestance Filters (Coarse Filters) in
the range G1 - G4. Final pressure
drop for certification is specified at
250 Pa maximum. Filters with an
initial dust spot efficiency above 20%
are classified as Efficiency Filters
(Fine Filters) in the range F5 - F9.
The final pressure drop for
certification is set at 450 Pa
maximum.
The table summarizes the
classification of the EN 779 for
general ventilation filters.
Filter
Classification
G1
G2
G3
G4
F5
F6
F7
F8
F9
Initial Dust Spot
Efficiency E
o
Average Arrestance
Am (%)
A
m
< 65
65 A
m
< 80
80 A
m
< 90
90 A
m
-
-
-
-
-
E
o
< 20%
Average Efficiency
E
m
(%)
-
-
-
-
40 E
m
< 60
60 E
m
< 80
80 E
m
< 90
90 E
m
< 95
95 E
m
E
o
20%
Note:
For your information, the CEN/TC 195 Work Group 1 will continue to upgrade its standardization for general ventilation filters.
To this end, EUROVENT has produced a particle count method under document name EUROVENT 4/9 which will form the
basis for a future new standard. WG 1 has also expressed its intention to work in closer liaison with ASHRAE on this subject.
CR-3-1167-IN-0896
AAF-International B.V., P.O. Box 7928, 1008 AC Amsterdam, The Netherlands
Tel.:
+
31 20 549 44 11, Fax:
+
31 20 644 43 98
G On a flat sheet of media, the MPPS is determined
for the given media velocity. This can be done
with a laser spectrometer or a combination of
electrostatic classifier and CNC (Condensed
Nucleus Counter).
G The filter is assembled with the specified media
grade and amount of media to comply with the
defined media velocity.
G The filter is challenged with an aerosol and at the
MPPS both the local and overall efficiency is
determined with either a CNC or laser
spectrometer.
G Leaks are specified as maximum allowable local
penetration at the MPPS and must not exceed
5 x the overall penetration.
G The filter is classified according to the test results
in the range H10 - H14 for HEPA,
U15 - U17 for ULPA.
Penetration vs Particle Size
Particle Size (microns)
P
e
n
e
t
r
a
t
i
o
n

(
%
)
Face Velocity 5.00 cm/s
(Resistance = 36.36 mm)
(MPPS = 0.134 m)
Minimum
Efficiency
Face Velocity 3.50 cm/s
(Resistance = 26.05 mm)
(MPPS = 0.146 m)
Face Velocity 2.50 cm/s
(Resistance = 18.70 mm)
(MPPS = 0.159 m)
Face Velocity 1.70 cm/s
(Resistance = 9.65 mm)
(MPPS = 0.172 m)
Face Velocity 1.30 cm/s
(Resistance = 9.65 mm)
(MPPS = 0.189 m)
Face Velocity 0.90 cm/s
(Resistance = 6.75 mm)
(MPPS = 0.212 m)
Filter
Classification
H 10
H 11
H 12
H 13
H 14
U 15
U 16
U 17
Overall Value
= > 85
= > 95
= > 99.5
= > 99.95
= > 99.995
= > 99.9995
= > 99.99995
= > 99.999995
Local Value
-
-
-
99.75
99.975
99.9975
99.99975
99.9999
Overall Penetration
15
5
0.5
0.05
0.005
0.0005
0.00005
0.000005
Local Penetration
-
-
-
0.25
0.025
0.0025
0.00025
0.0001
Efficiency (%) at the MPPS Penetration (%) at the MPPS
Notes:
Filters in the class H10, H11 and H12 do not require verification of local penetration.
Filters in the classification H13 and H14 may, as an alternative, be verified with the visual oil-smoke test (previously known as DIN 24.184),
which is accepted as equal or more searching than the specified local penetration.
U17 is an exception to the rule. In this case local penetration may not exceed 20 x the overall penetration value.

CR-2-489-IN-1-0398
B E T T E R A I R I S O U R B U S I N E S S
AAF-International B.V., P.O. Box 7928, 1008 AC Amsterdam, The Netherlands
Tel.:
+
31 20 549 44 11, Fax:
+
31 20 644 43 98
1998 AAF International
EN1822
New European Standard for HEPA & ULPA Filters
Procedure