MAGNETIC MOTOR STARTERS

AND MAGNETIC CONTACTORS

The lineup has been enriched with N-series which employs Safety & Speedy terminals.

series

ISO 9001

NATIONAL
ACCREDITATION
OF CERTIFICATION
BODIES

MS-New Series, Excellent Controls

Designed with Ease of Use in Mind


Easy Mounting and Wiring

Safety and Speedy Terminal Functions

MS-N series contactors, starters and relays can all be mounted on DIN rail (35mm wide). For easy wiring, coil terminals are
arranged on the upper side of the contactors. In addition, distance is unified between the DIN rail center and coil terminals
at 38.5mm. (S-N10-N21, MSO-N10-N21 and SR-N4)

Models which have finger protection provide a more safe and


speedy connection, even when using closed eyelet (ring) type
terminal lugs.
(S/SD-NooCX, TH-NooCX, SR/SRD-N4 CX)
Insert closed eyelet
connectors and push
down screw holder

Pull up
screw holder
15mm

15mm

15mm

15mm

38.5mm

15mm

Tighten
screw

Stronger Design
The molded thermo plastic provides improved barrier strength.

Easy Inspection
Contacts can be easily inspected by removing the arc cover.

Improvement of Electromagnet
The spiral kick-out spring improves the balance of moving
parts, reducing bounce, lengthening core life and stabilizing
core movement.
Electromagnet efficiency has been engineered using computer
analysis. The contactor is capable of withstanding voltage
drops up to 35% (at closing of contact).

Spiral kick-out
spring

Moving core

Built-in Surge Absorber


Built-in surge absorbers for the coil are available as an option.
(S/SD-NooSA, SR/SRD-NoSA)
Indication of absorber

Coil

Surge absorber
Stationary
core

International Standard Models


(1) Conforms to new IEC 60947-4-1
(2) Listed by UL for UL and CSA standards.
(3) Conforms to EN Standards

CONTENTS
Page
1. GENERAL PURPOSE CONTACTORS & STARTERS ..................................................Series MS-N/K
1.1 Conformity to International Standards ................................................................................................................................1
1.2 Selection Guide....................................................................................................................................................................2
1.3 The Overview (Type designation breakdown) ....................................................................................................................4
1.4 Technical Data of Series S-N/K Contactors ........................................................................................................................6
1.5 When Ordering ....................................................................................................................................................................9
1.6 Selection Table of Contactors ............................................................................................................................................10
1.7 Optional Parts and Accessories for Contactors ................................................................................................................12
1.8 Connections and Contact Arrangements ..........................................................................................................................15
1.9 Outline Dimensions............................................................................................................................................................17
2. MOTOR PROTECTION RELAYS
2.1 Thermal Overload Relays........................................................................................Series TH-N/K ..................................19
2.2 Electronic Motor Protection Relays ........................................................................Series ET-N ......................................25
3. DEFINITE PURPOSE CONTACTORS & STARTERS
3.1 DC Contactors ........................................................................................................Series DU-K/Ao ..............................28
3.2 Medium Voltage Vacuum Contactors ......................................................................Series SH-V ....................................31
3.3 Compact 3-Pole Contactor ......................................................................................Series S-No8 ..................................34
3.4 DC Interface Contactors ..........................................................................................Series SD-M ....................................35
3.5 DC Interface Modules..............................................................................................Series UN/UA-SY ............................36
4. RELAYS
4.1 Contactor Relays ....................................................................................................Series SR-N ....................................38
4.2 Pneumatic Time Delay Relays ................................................................................Series SRT-N ..................................43
TYPE REFERENCE LIST ............................................................................................................................................................44

Match with Electrical Control


for Factory Automation

Even Greater Contact Reliability


Contact reliability has been greatly improved by the bifurcated
auxiliary moving contact
Contact
spring
Bifurcated
moving
contact
Stationary
contact

DC Electromagnet with AC
Operation (Patented)
Medium-and Large-Sized Models:
S-K50~S-K800
Coil Boasts Lower Power Requirements
Coil power consumption has been greatly reduced so that MSK Series contactors can be controlled by almost any type of
relay, even small output relays in programmable controllers.

Bifurcated moving
contact

Superlative Breaking Performance


New improved arc-quenching mechanism (patented) offers
superior current-interrupting capabilities. All Mitsubishi contactors feature capacity sufficient for a 690V circuit.
Arc-Quenching Mechanism (S-K220)
Construction of Arc-Quenching Mechanism (S-K220)
Moving contact Arcing horn
Grids

Arc runner

Less Noise and Surge from Coil


When switching a coil, the energy will be dissipated within the
internal circuit of electromagnet

Humming Completely Eliminated

Stationary contact

DC excitation does not cause humming so operation is quiet.

Contactor Coils Have a Wide Range of Ratings


The number of coil types has been cut by two-thirds and there
is no need to re-wire for different frequencies. The coil also
withstands large voltage drops.
Internal circuit of the electromagnet

R
Coil

Designed with Ease of Use in Mind


1. S-N10~S-K65 units can all be mounted on DIN rail (35mm
wide).
2. A variety of blocks and optional features are available including:
Standard front clip-on auxiliary contact blocks (four pole
type and two pole type).
Low-level signal front clip-on auxiliary contact blocks.
Side clip-on auxiliary contact blocks.
Surge absorbers (varistor and CR models).
Surge absorbers with LED operating indicators.
Mechanical interlocks
3. Compact arc quenching and magnet layout greatly reduces
installation space.
4. The coil rating is displayed in a location readily visible even
after the unit is installed onto the panel.
5. Contacts are visible when the arc cover is removed, allowing them to be checked easily.

1. GENERAL PURPOSE CONTACTORS & STARTERS


11 Conformity to International Standards
Mitsubishi magnetic motor starters and contactors are designed to conform to
the relevant IEC recommendations and to the standards of as many countries as
possible. Specifically, they conform to the following:
Standards

U.S.A.

Series

IEC947-4-1
International
EN60947-4-1 Europe

VDE0660
NEMA-ICS

MS-N/K

Germany
U.S.A
Table 1.1.1

U.K.

France

Korea

Japan

Lloyds
Register of
Shipping

Bureau
Veritas

Korean
Register of
Shipping

Nippom
Kaiji
Kyokai

Canada

Type

Contactor

S-N10
S-N11
S-N12
S-N18
S-N20
S-N21
S-N25
S-N35
S-K50
S-K65
S-K80
S-K95
S-K125
S-K150
S-K180
S-K220
S-K300
S-K400
S-K600
S-K800

o
o
o
o
o
o
o
o
o
o
o
o

o
o
o
o
o
o
o
o
o
o
o
o

1
1

1
1

1
1

Thermal
overload
relay

TH-N12(KP)
TH-N18(KP)
TH-N20(KP)
TH-N20TA(KP)
TH-K60(KP)
TH-K60TA(KP)
TH-K120(KP)
TH-K120TA(KP)
TH-K220RH(KP)
TH-K220HZ(KP)
TH-K400RH(KP)
TH-K400HZ(KP)
TH-K600(KP)

o
o
o
o
o
o
o
o
o
o
o
o

o
o
o
o
o
o
o
o
o
o
o
o

Contactor
relay

SR-N4
SRD-N4

Note: Standard model is certified

Rating of
Type
A
Continuous current
open
Horsepower rating
Single phase 120V HP
Con240V HP
tactor
(open) Three phase 208V HP
240V HP
480V HP
600V HP
Type

Starter Continuous current


A
(open) Horsepower rating
Three phase 208V HP
240V HP
480V HP
600V HP
Max. rating of short
circuit protection device
Fuse class K5
A
Circuit breaker
A

and

Certified models are available

Certification not yet applied for

1 under application

Certified Models

Table 1.1.2

S-N10

S-N11
S-N12

13

20

30

30

35

40

80

95

93

93

125

150

220

220

300

400

680

910

1/2
1-1/2

1/2
1-1/2

1
3

1
3

2
3

2
5

3
7-1/2

3
10

5
15

7-1/2
15

10
20

15
25

15
30

15
40

3
3
5
5

3
3
7-1/2
7-1/2

5
5
10
10

5
5
10
10

7-1/2
7-1/2
15
15

10
10
20
20

15
15
30
30

15
20
40
40

20
25
50
50

25
30
60
60

40
40
75
75

40
50
100
100

60
60
125
125

60
75
150
150

100
100
200
200

125
150
300
300

150
200
400
400

250
300
600
600

S-N18 S-N20 S-N25 S-N35 S-K50 S-K65 S-K80 S-K95 S-K125 S-K150 S-K180 S-K220 S-K300 S-K400 S-K600 S-K800

MSO- MSO- MSO- MSO- MSO- MSO- MSO- MSO- MSO- MSO- MSO- MSO- MSO- MSO- MSO- MSON10KP N11KP N18KP N20KP N25KP N35KP K50KP K65KP K80KP K95KP K125KP K150KP K180KP K220KP K300KP K400KP
N12KP
N21KP
10

13

18

18

26

3
3
5
5

3
3
7-1/2
7-1/2

5
5
10
10

5
5
10
10

7-1/2
7-1/2
15
15

10
10
20
20

15
15
30
30

30

30

70

70

100
100

125
125

250
250

34

50

80

93

125

150

180

220

300

400

15
20
40
40

20
25
50
50

25
30
60
60

40
40
75
75

40
50
100
100

60
60
125
125

60
75
150
150

100
100
200
200

125
150
300
300

250
250

300
300

225
225

350
350

350
350

500
500

500
500

600
600

65

Notes: 1. UL listed and CSA certified types for K50 to K800 require suffix letters UL (eg. S-K65UL).
2. Time delay fuse.
3. Class L fuse.
4. UL recognized type is not available.

500
1000

800

1200

12 Selection Guide

MSO-N12

S-2xN11

S-N11

S-N21

MSO-N35

Three-phase motor

220-240V

2.5 (3-1/4)

3.5 (4-1/2)

3.5 (4-1/2)

4.5 (6)

5.5 (7-1/2)

5.5 (7-1/2)

7.5 (10)

11 (15)

ratings IEC category

380-440V

4 (5-1/2)

5.5 (7-1/2)

5.5 (7-1/2)

7.5 (10)

11 (15)

11 (15)

15 (20)

18.5 (25)

AC3

500V

4 (5-1/2)

5.5 (7-1/2)

5.5 (7-1/2)

7.5 (10)

11 (15)

11 (15)

15 (20)

18.5 (25)

660V

4 (5-1/2)

5.5 (7-1/2)

5.5 (7-1/2)

7.5 (10)

7.5 (10)

7.5 (10)

11 (15)

15 (20)

20

20

20

32

32

50

60

(standard)

1NO

1NO

1NO+1NC

1NO+1NC

2NO+2NC

2NO+2NC

2NO+2NC

(special)

25
2

kW(hp)

Rated continuous current

Ith A

Auxiliary contacts1

1NC

1NC

2NO

2NO

1NO + 1NC (front)

Number of additional

1NO + 1NC (side)

auxiliary contact

2NO + 2NC (front)

block for

Low level signal (front)


1

[1NO+1NC]
(+Standard 1NO + 1NC)]

Notes 1: Number of auxiliary contact shows that for non-reversing type. Twice of the auxiliary contacts are provided on reversing type.
2: (2NO + 2NC) 2 auxiliary contacts are provided on reversing type and no additional contact can be mounted.
3: Front clip-on and side clip-on block should not both be mounted.

Contactors
AC operated models

S-N10

S-N11

S-N12

S-N18

S-N20

S-N21

S-N25

S-N35

S-2xN10

S-2xN11

S-2xN18

S-2xN20

S-2xN21

S-2xN25

S-2XxN35

SD-N11

SD-N12

SD-N21

SD-N35

Non-reversing
Reversing

DC operated models

Thermal Overload Relays1


Three heater type with
phase failure protection
Two heater type

Heater setting range


(Ordering designation)

TH-N12KP

TH-N18KP

TH-N20KP

TH-N20TAKP

TH-N12

TH-N18

TH-N20

TH-N20TA

0.1~0.16 (0.12A)

1.7~2.5 (2.1A)

1~1.6 (1.3A)

0.2~0.32 (0.24A)

2~3 (2.5A)

18~26 (22A)

0.14~0.22 (0.17A)

2~3 (2.5A)

1.4~2 (1.7A)

0.28~0.42 (0.35A)

2.8~4.4 (3.6A)

24~34 (29A)

0.2~0.32 (0.24A)

2.8~4.4 (3.6A)

1.7~2.5 (2.1A)

0.4~0.6 (0.5A)

4~6 (5A)

30~40 (35A)4

0.28~0.42 (0.35A)

4~6 (5A)

2~3 (2.5A)

0.55~0.85 (0.7A)

5.2~8 (6.6A)

0.4~0.6 (0.5A)

5.2~8 (6.6A)

2.8~4.4 (3.6A)

0.7~1.1 (0.9A)

7~11 (9A)

0.55~0.85 (0.7A)

7~11 (9A)

4~6 (5A)

1~1.6 (1.3A)

9~13 (11A)

0.7~1.1 (0.9A)

9~13 (11A)2

5.2~8 (6.6A)

1.4~2 (1.7A)

12~18 (15A)

1~1.6 (1.3A)

7~11 (9A)

1.7~2.5 (2.1A)

16~22 (19A)3

1.4~2 (1.7A)

9~13 (11A)
12~18 (15A)

Notes 1. Saturable reactors for thermal overload relays are available as a kit or equipped with the relay.
The suffix SR following the model name of the relay indicates with saturable reactor. (ex. TH-N20KPSR*5A) (Except for type
TH-N12KP, TH-N18 and TH-N18KP)
2. Except for size N10.
3. For size N20 & N21 only.
4. For size N35 only.
2

S-K125

MSO-K150

S-K400

S-K800
Table 1.2.1

15 (20)

18.5 (25)

22 (30)

30 (40)

37 (50)

45 (60)

55 (75)

75 (100)

90 (125)

125 (170)

190 (250)

220 (300)

22 (30)

30 (40)

45 (60)

55 (75)

60 (80)

75 (100)

90 (125)

132 (180)

160 (210)

220 (300)

330 (450)

440 (600)

22 (30)

30 (40)

45 (60)

55 (75)

60 (80)

90 (125)

110 (150)

132 (180)

160 (210)

225 (330)

330 (450)

500 (670)

22 (30)

30 (40)

45 (60)

55 (75)

60 (80)

90 (125)

110 (150)

132 (180)

200 (270)

250 (330)

330 (450)

500 (670)

80

100

135

150

150

200

260

260

350

450

800

1000

2NO+2NC

2NO+2NC

2NO+2NC

2NO+2NC

2NO+2NC

2NO+2NC

2NO+2NC

2NO+2NC

2NO+2NC

2NO+2NC

2NO+2NC

2NO+2NC

S-K800

S-K50

S-K65

S-K80

S-K95

S-K125

S-K150

S-K180

S-K220

S-K300

S-K400

S-K600

S-2K50

S-2K65

S-2K80

S-2K95

SD-K50

SD-K65

SD-K80

SD-K95

SD-K125

SD-K150

SD-K220

SD-K300

SD-K400

SD-K600

SD-K800

TH-K60KP

TH-K60TAKP

TH-K120KP

TH-K120TAKP

TH-K220RHKP

TH-K400RHKP

TH-K600KP9

TH-K60

TH-K60TA

TH-K120

TH-K120TA

TH-K220RH

TH-K400RH

TH-K6009

12~18(15A)

54~80 (67A)

34~50 (42A)

85~125 (105A)

65~100 (82A)

85~125 (105A)

200~300(250A)

18~26(22A)

65~93 (82A)5

43~65 (54A)

100~150(125A)6

85~125 (105A)

100~150(125A)

260~400(330A)

24~34(29A)

85~105(95A)5

54~80 (67A)

100~150(125A)

120~180(150A)

400~600(500A)

65~100(82A)

120~180(150A)

140~220(180A)

520~800(660A)10

34~50(42A)

140~220(180A)7

200~300(250A)

43~65(54A)

170~250(210A)7

260~400(330A)8

30~40(35A)

5.
6.
7.
8.
9.
10.

For size K95 only.


For size K150 only.
For size K220 only.
For size K400 only.
TH-K600(KP) must be used with the current transformers (to be supplied by the customer.) See page 21, Table 2.1.2.
For size K800 only.

13 The Overview (Type designation breakdown)


131 Non-reversing Types
Table 131

Frame Size
Rated capacity

220-240V

Category AC3(kW)

380-440V

Number of
aux. contacts

Spec
Additional aux.
contact blocks
ACCESSORIES

N10 N11 N12 N18 N20 N21 N25 N35 K50 K65 K80 K95 K125 K150 K180 K220 K300 K400 K600 K800

CONTACTORS
Open

30

37

45

55

75

45

55

60

75

90

132 160 220 330 440

3.5

3.5

4.5

5.5

5.5

7.5

5.5

5.5

7.5

11

11

15 18.5 22

Standard

1NO 1NO 1NO1NC 1NO1NC

Special

1NC 1NC 2NO 2NO

Front-on1

11

1NO1NC2(max.)

4P

2NO2NC1
(max.)

1NO1NC2(max.)

Provided as a standard

Attachable
Attachable

125 190 220

1NO1NC2(max.)

Surge absorber3

30

90

2NO2NC

2P or 4P

Side-on

Attachable

AC operated

S-o

DC operated

SD-o

Finger protected

S(D)-o

Mechanically latched

SL(D)-o

AC operated

MSO-o

DC operated

MSOD-o

With phase failure protection

MSO-oKP

Slow trip type


with saturable reactor

MSO-oSR

MSO-oFS

MSO-oKF

Standard type

MS-o

With push button

MS-oPM

MS-oKP

Mechanical interlock unit

Quick-trip type
with 2 heater elements
with phase failure protection

Enclosed
Class IP20

STARTERS
Open

15 18.5 22

2.5

With phase failure protection


DIN rail mounting

Available

Notes: 1. Additional head-on type aux. contact blocks cannot be attached to the enclosed type, mechanically latched type and DC operated
type of size K50 & K65.
2. DC operated type cannot be supplied.
3. Surge absorber is provided as a standard on ac operated contactors and starters of sizes K50 to K800.

132 Reversing Type


Table 132

2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2
N10 N11 N18 N20 N21 N25 N35 K50 K65 K80 K95 K125 K150 K180 K220 K300
K400 K600 K800

Frame Size

220-240V

2.5

3.5

4.5

5.5

5.5

7.5

Category AC(kW)

380-440V

5.5

7.5

11

11

15 18.5 22

Number of
aux. contacts

CONTACTORS ACCESSOpen
ORIES

15 18.5 22
30

45

90

125 190 220

30

37

45

55

75

55

60

75

90

132 160 220 330 440

2NO2NC 1NO1NC
Standard
Special

Spec

STARTERS
Open
Enclosed(IP20)

11

Rated capacity

Additional aux.

Front-on1

contact blocks

Side-on

1NO1NC2

4P2
2P2

1NO1NC2

4NO4NC
2NO2NC2

4P2
2P2

1NO1NC2

Surge absorber2

4P2

3NO3NC2

1NO1NC2
Provided as a standard

AC operated

S-o

Attachable

DC operated

SD-o

Finger protected

S-o

Mechanically latched

SL(D)-o

AC operated

MSO-o

DC operated

MSOD-o

With phase failure protection

MSO-oKP

Slow trip type


with saturable reactor

MSO-oSR

Quick-trip type
with 2 heater elements
with phase failure protection

MSO-oFS

MSO-oKF

Standard type

MS-o

With phase failure protection

MS-oKP

DIN rail mounting

Available3

Notes: 1. Additional head-on type aux. contact blocks cannot be attached to the enclosed type, mechanically latched type and DC operated
type of size K50 & K65.
2. Surge absorber is provided as a standard on ac operated contactors and starters of sizes 2xK50 to 2xK800.
3. Remove a mounting plate for DIN rail mounting.

14 Technical data of series S-N and S-K contactors


141 Ratings and characteristics
Contactor
Rated insulation voltage
Rated continuous current
Rated capacity for resistive loads
3-ph, Category AC-1

Rated insulation voltage


Making & breaking
3-ph, cos = 0.35
240V/440V
Switching frequency

Control terminal
Busbar width

18(50)
30(50)
40(50)
50(50)

20(60)
35(60)
50(60)
60(60)

30(80)
50(80)
65(80)
80(80)

35(100)
65(100)
85(100)
100(100)

22
22
17
9

22
22
17
9

30
30
24
12

40
40
32
17

55
50
33
26

65
62
45
35

1.5
2.2
2.2
2.2
9

2.2
3.7
3.7
3.7
13

2.2
3.7
3.7
3.7
13

3
5.5
5.5
5.5
17

3.7
5.5
5.5
5.5
24

5.5
7.5
7.5
7.5
32

7.5
11
11
11
47

12
12
12

12
12
12

20
20
20

20
20
20

25
25
22

35
35
30

50
50
40

65
65
50

6
4
2

10
8
4

10
8
4

20
15
8

20
15
8

25
20
10

30
20
10

35
30
12

40
35
15

2.2
3.3
4
3.3
690

3
4
5
4.5
690

4
6
6
5.5
690

5.5
10
10
10
690

5.5
10
10
10
690

8.5
14
14
14
690

12
20
20
20
690

20
40
30
30
690

20
40
35
40
690

110/110
100/72
1,800
1,800
660

130/120
120/100
1,800
1,800
660

180/180
180/130
1,800
1,800
600

220/220
220/220
1,800
1,800
600

220/220
220/220
1,800
1,800
600

300/300
300/240
1,800
1,800
600

400/400
400/320
1,800
1,800
600

550/460
550/460
1,200
1,200
600

650/620
650/620
1,200
1,200
600

ms
ms
ms
ms

15
10

15
10
45
10

15
10

15
10

15
10
33
12

15
10

15
10
50
13

25
53
57
15

25
53
57
15

VA
VA
W
VA
VA

60
10
3.5

60
10
3.5
7
7

60
10
3.5

110
13
5.3
18
18

132
17
2.8
24
24

132
17
2.8
24
24

million
C
G
G
mm2

10

10

10

10

1-2.5

1-2.5

1-6

2-16

2-25

2-25

mm2
mm2
mm

1-2.5
1-2.5

1-2.5
1-2.5

1-6
1-2.5

2-16
1-2.5

2-25
1-2.5

2-25
1-2.5

690
32

7.5(20)
8.5(13)
9.5(11)
8(8)

9.5(25)
13(20)
13(16)
11(10)

12(32)
20(32)
25(32)
30(32)

11
9
7
5

13
12
9
7

18
16
13
9

0.75
1.1
1.1
1.1
6

1.1
1.5
1.5
1.5
9

A
A
A

10
8
8

48V
110V
220V

A
A
A

220-240V
380-440V
550V
690V

kvar
kvar
kvar
kvar
V

Making current
Breaking current
Category AC-1
Category AC2 & AC-3
Category AC-4

A
A
operations/hour
operations/hour
operations/hour

220-240V
380-440V
500V
690V

Closing
Opening

Coil consumption (at rated coil voltage)


AC operated
Inrush
Sealed
Watts
Inrush
DC operated
Sealed
Coil voltage tolerance
Mechanical endurance (make/break operations)
Permissible ambient temperature
Vibration (10-55 Hertz)
Shock (10 ms half sine wave)
Conductor size
Main terminal (contactor)
Main terminal (overload relay)

12(32)
20(32)
25(32)
30(32)

690
25

Ith

Operating time (at rated coil voltage)


Closing
AC operated
Opening
DC operated

S/SDK65
690
100

S/SDN21
690
32

220-240V
380-440V
500V
690V
Rated capacity for jogging of AC motors
3-ph, category AC-4
220-240V
Electrical life is ca.
380-440V
200000 operations
500V
690V
Max. current for AC-4 duty at 440V
Rated current for DC non-inductive loads
48V
Category DC-1
110V
100 operations/hour max.
220V
500,000 operations

Rated capacity for 3-ph, capacitors4


15 operations/hour max.
100,000 operations
(ambient temperature 40C)

S/SDK50
690
80

S-N20

Rated operational current


3-ph, Category AC-3

Rated Current for DC motors


Category DC-3 & DC-5
100 operations/hour max.
500,000operations

690
50

S/SDN35
690
60

S-N18

V
A

S-N10
690
20

S/SDN11 N12
690
20

kW(A)
kW(A)
kW(A)
kW(A)

7.5(20)
7(11)
7(8)
7(6)

Type

A
A
A
A
kW
kW
kW
kW
A

S-N25

110
90
90
13
15
15
5.3
5.3
5.3

16

16

0.85 to 1.1 times rated coil voltage


10
10
10
25 to +55
2
5
2-16
1-6
1-6
1-6
1-2.5

1-6
1-2.5

2-16
1-2.5

Notes: 1. 660A at ambient temperature 40-55C.


2. 800A at ambient temperature 40-55C.
3. Conductor size in parentheses indicate compression terminal style not for bare clamping.
4. The peak value of inrush current should be less than 2000% of the effective value for rated current of capacitors.
The selection is invalid for the circuit of parallel capacitors which are controlled individually.
6

Table 141

S/SDK80

S/SDK95

S/SDK125

S/SDK150

SK180

S/SDK220

S/SDK300

S/SDK400

S/SDK600

S/SDK800

690
135

690
150

690
150

690
200

1000
260

1000
260

1000
350

1000
450

1000
8001

1000
10002

130(350)
230(350)
300(350)
350(350)

170(450)
290(450)
380(450)
450(450)

250(660)
430(660)
570(660)
660(660)

300(800)
530(800)
700(800)
900(800)

50(135) 55(150) 55(150) 75(200) 95(260) 95(260)


85(135) 90(150) 90(150) 130(200) 170(260) 170(260)
110(135) 120(150) 120(150) 170(200) 220(260) 220(260)
135(135) 150(150) 150(150) 200(200) 260(260) 260(260)

Rated operating current


of auxiliary contacts
Table 142

Rated continuous current


Rated operating current
Category

85
85
75
52

105
105
85
65

125
120
90
70

150
150
140
100

180
180
180
120

250
250
200
150

300
300
250
220

400
400
350
300

630
630
500
420

800
800
720
630

AC-15

7.5
15
15
15
62

11
18.5
18.5
18.5
75

15
22
22
22
90

18.5
30
37
30
110

22
37
45
50
150

22
45
55
55
180

37
60
60
75
220

45
75
90
90
300

65
110
130
130
400

75
130
150
150
630

Category

80
80
60

93
93
70

120
100
80

150
150
150

180
180
180

220
220
220

300
300
300

400
400
300

630
630
630

800
800
800

60
50
20

90
80
50

90
80
50

130
120
80

180
150
100

220
150
100

280
200
150

280
200
150

630
630
630

630
630
630

35
60
48
50
690

35
60
60
60
690

38
65
65
65
690

50
80
80
80
690

60
120
150
150
1,000

60
120
150
150
1,000

95
150
200
200
1,000

115
200
250
200
1,000

190
350
350
400
1,000

190
350
350
400
1,000

DC-13

16

120VAC

240VAC

500VAC

660VAC

1.5

24VDC

48VDC

110VDC

1.2

0.81

0.2

220VDC

Note: 1 UN-AX2, UN-AX4,


UN-AX11

850/850 1050/1050 1250/1250 1500/1500 1800/1800 2500/2500 3000/3000 4000/4000 6500/6500 8000/8000
800/750 930/930 1000/1000 1200/1200 1450/1450 2000/2000 2400/2400 3200/3200 5040/5040 6400/6400
1,200
1,200
1,200
1,200
1,200
1,200
1,200
1,200
1,200
1,200
1,200
1,200
1,200
1,200
1,200
1,200
1,200
1,200
1,200
1,200
600
300
300
300
300
300
300
300
300
300
27
75
75
18

27
75
75
18

25
85
125
22

27
85
135
37

35
120
175
55

35
120
175
55

65
75
105
80

65
75
105
80

225
22
3.3
27
27

225
22
3.3
27
27

320
26
3.5
31
31

480
54
7.3
55
55

800
100
15
600
75

800
100
15
600
75

320
480
480
480
26
44
44
54
3.5
5
5
7.3
31

41
55
31

41
55
0.85 to 1.1 times rated coil voltage
5
5
5
5
25 to +55
2
5

2-50

2-50
(2-60)3
2-50
1-2.5
15

(6-70)3
(6-70)3
1-2.5
15

2-50
1-2.5
15

(6-95)3
(6-95)3
1-2.5
20

30
100

30
100
145
40

(10-120)3 (10-150)3 (25-240)3 (25-240)3 (70-325)3 (70-325)3


(10-120)3 (10-150)3 (25-240)3 (25-240)3

1-2.5
1-4
1-4
1-2.5
1-2.5
1-2.5
30
25
25
35
35
30

142 Performance of Series S-N/K Contactors


Electrical Life

Nr/1 + (Nr/NI -1)......................................Eq.1.1


100

where

N :
Nr :
Nl :
:

Life in the case of % jogging duty


Life in the case of normal duty
Life in the case of 100% jogging duty
Percentage of jogging duty

Fig.141

3
2
Electrical life (million of operations, average)

The electrical life of the main contacts of a contactor is determined mainly by the circuit-opening duty it will perform.
The relationship between electrical life and rated current of
Mitsubishi contactors under normal and jogging duties of
squirrel-cage motors is shown in Fig. 1.4.1 and 1.4.2
In the case of a mixture of normal and jogging duties, the
expected contactor life can be determined as follows:

220~240VAC

1.5
1
0.7
0.5
S-N18
0.3
0.2
0.15
0.1
0.07
0.05

S-K220

0.03

S-N25

0.02

S-N10

0.01
2

Electrical life versus rated operating current (Ie)


(Ie = Rated operational current.)

S-K125

S-K180

S-N20,21

S-K65 S-K95 S-K300


S-K800
S-K400
S-N11,12
S-N35
S-K600
S-K50 S-K80 S-K150
3
5 7 10 15 20 30 50 70 100 150 200 300 500 800
Rated operating current (A)

380~440VAC

Fig.142

3
2
Electrical life (million of operations, average)

Normal duty, 6 Ie on, Ie off, on-load factor 40%,


1200 operations / hour (AC3)
Jogging duty, 6 Ie on, 6 Ie off, on-load factor 7%,
600 operations / hour (AC4)-S-N10~S-K300
300 operations / hour (AC4)-S-K400~S-K600
150 operations / hour (AC4)-S-K800

1.5
1
0.7
0.5
0.3
0.2
0.15
0.1
0.07
0.05
S-K125 S-K180

0.03

S-K95
S-N25
S-K300
S-K50
S-N18
S-K150
S-K65
S-K400
S-N11,N12 S-N20,21 S-N35 S-K80 S-K220 S-K600

0.02

S-N10

0.01
2

7 10 15 20 30 50 70 100 150 200 300 500 800


Rated operating current (A)

143 Permissable Mounting of Starters and Contactors


30 30

To assure proper performance, Mitsubishi magnetic motor


starters and contactors should be mounted on a vertical supporting surface with the line terminals upwards and the load
terminals downwards. The supporting surface may have a
maximum inclination of 30 from the vertical in any direction.

30 30

Top

Bottom
Regular installation

Inclined installation

S-K800

15 When Ordering
Contactors, indicate the model name and the ordering designation of the coil.

Example: S-N20 AC230V ( 2A)


Code of arrangement, if special aux. contacts, ref. Table 154
Ordering designation of the coil
Model name
Overload relays, indicate the model name and the ordering designation of the heater setting range.

Example: TH-K400RHKP250A
Ordering designation of the heater setting range
Model name
Motor starters, indicate the model name, heater setting range, main circuit voltage, coil designation.

Example: MSO-N11KP6.6A380VAC230V
Ordering designation of the coil
Main circuit voltage
Ordering designation of the heater setting range
Model name

Note: Mark indicates a blank space.

Coil Ratings and Ordering Designations


for S-N10, -N11, -N12, -N18, -N20,
-N21, -N25, -N35 and SR-N

for S-K50~-K800
Table 151

Table 152

Rated voltage (50/60Hz)

Ordering designation

100~127V

AC100V

AC24V

200~240V

AC200V

48~50

AC48V

260~350V

AC300V

100

100~110

AC100V

380~440V

AC400V

110~120

115~120

AC120V

460~550V

AC500V

125~127

127

AC127V

Rated voltage (VAC)

Ordering designation

50Hz

60Hz

24

24

48~50

AC24V,AC48V are available for S-K50~-K150

200

200~220

AC200V

208~220

220

AC220V

220~240

230~240

AC230V

240~260

260~280

AC260V

346~380

380

AC380V

380~415

400~440

AC400V

Rated voltage (VDC)

Ordering designation

415~440

460~480

AC440V

24

DC24V

500

500~550

AC500V

48

DC48V

100

DC100V

for SD-N, SD-K, SRD-N

Table 153

110

DC110V

120~125

DC125V

200

DC200V

220

DC220V

Code of arrangement for special aux. Contacts


Table 154

Arrangement

Code

1NC

1B

2NO
A : Normally Open

2A

B : Normally Closed

16 Selection Table of Contactors


Type S-No, S-Ko, SD-No&SD-Ko

161 Non-Reversing Contactors


Ordering Designation

Model name..................................................................................................S-N10
Coil designation (See page 9)..................................................................................AC400V
If required special aux. contact (never specify for standard). ................................................1B
Complete type designation

S-N10

Note: Mark indicates


a blank space.

AC400V 1B
Table 161

Rated motor capacity


3-phase AC-2 & AC-3

Rated
operational
current AC-3
220

380

220

Model name

690V

(A)

(A)

(kW)

(kW)

(kW)

(kW)

11

2.5

AC operated DC operated
S-N10
S-N10(1B)

13
18

12
12
16

3.5
3.5
4.5

10

5.5
5.5
7.5

5.5
5.5
7.5

5.5
5.5
7.5

NO

NC

S-N11

SD-N11
S-N11(1B) SD-N11(1B)
S-N12
SD-N12
S-N12(2A) SD-N12(2A)
S-N18

S-N20

S-N20(2A)

22

22

5.5

11

11

7.5

22

22

5.5

11

11

7.5

S-N21

30

30

7.5

15

15

11

S-N25

40

40

11

18.5

18.5

15

S-N35

SD-N35

55

50

15

22

22

22

S-K50

65

62

18.5

30

30

30

S-K65

SD-K50

SD-K65

SD-N21

85

85

22

45

45

45

S-K80

SD-K80

105

105

30

55

55

55

S-K95

SD-K95

125

120

37

60

60

60

S-K125

SD-K125

150

150

45

75

90

90

S-K150

SD-K150

180

180

55

90

110

110

S-K180

250

250

75

132

132

132

S-K220

SD-K220

300

300

90

160

160

200

S-K300

SD-K300

400

400

125

220

225

250

S-K400

SD-K400

630

630

190

330

330

330

S-K600

SD-K600

800

800

220

440

500

500

S-K800

SD-K800

S-N10

Finger
protection
terminal
cover

Additional auxiliary contact block

380

240V 440V 240V 440V 500V

13

Standard
aux.
contacts

S-N21

SD-K65

Provided

Provided

Provided

Provided

Provided

Provided

Provided

Provided

Provided

Provided

Provided

Provided

Provided

Provided

UN-

UN-

UN-

AX2

AX4

AX11 AX21 AX80 AX150 AX600

UA-

UA-

UA-

UA-

1
Only for
AC operated type

Max.

Max.

S-K220

S-K400

S-K800

Type S-2xN/Ko, SD-2xN/Ko

162 Reversing Contactors


Ordering Designation

Model name ................................................................................................S-2K95


Coil designation (See page 9) ....................................................................................AC400V
Complete type designation......................................................................S-2K95

Note: Mark indicates


a blank space.

AC400V
Table 162

Rated operational
current AC-3

Rated motor capacity


3-phase AC-2 & AC-3

Model name

220

380

220

380

240V

440V

240V

440V

500V

690V

(A)

(A)

(kW)

(kW)

(kW)

(kW)

AC operated

Standard
aux.
contacts

DC operated
NO

NC

11

2.5

S-2N10

12

3.5

5.5

5.5

5.5

S-2N11

SD-2N11
SD-2N11

13

18

16

4.5

7.5

7.5

7.5

S-2N18

22

22

5.5

11

11

7.5

S-2N20

22

22

5.5

11

11

7.5

S-2N21

30

30

7.5

15

15

11

S-2N25

SD-2N35
SD-2N35
SD-2K50

SD-2K65

40

40

11

18.5

18.5

15

S-2N35

55

50

15

22

22

22

S-2K50

65

62

18.5

30

30

30

SD-2N21
SD-2N21

85

85

22

45

45

45

S-2K65
S-2K80

SD-2K80

105

105

30

55

55

55

S-2K95

SD-2K95

125

120

37

60

60

60

S-2K125

SD-2K125

150

150

45

75

90

90

S-2K150

SD-2K150

180

180

55

90

110

110

S-2K180

250

250

75

132

132

132

S-2K220

SD-2K220

300

300

90

160

160

200

S-2K300

SD-2K300

400

400

125

220

225

250

S-2K400

SD-2K400

630

630

190

330

330

330

S-2K600

SD-2K600

800

800

220

440

500

500

S-2K800

SD-2K800

S-2N11

S-2N21

S-2K220

Additional auxiliary contact block(max).

UN-

UN-

AX2

AX4 AX11 AX21 AX80 AX150

UN-

UA-

UA-

UA-

Max. 2
Only for
AC operated types

S-2K600

11

17 Optional Parts and Accessories for contactors


171 Replacement coils

Table 171

DC operated coils

AC operated coils
Contactor(s)

Part number*

S-N10, S-N11, S-N12,


S-N18, SR-N4

S-N11-COIL

Wt (kgs)

Contactor(s)

Part number*
SD-N11-COIL

DCoooV

0.23

ACoooV

0.06

SD-N11, SD-N12,
SRD-N4

Wt (kgs)

S-N20, S-N21

S-N21-COIL

ACoooV

0.08

SD-N21

SD-N21-COIL

DCoooV

0.24

S-N25, S-N35

S-N35-COIL

ACoooV

0.08

SD-N35

SD-N35-COIL

DCoooV

0.23

S-K50, S-K65

S-K50-COIL

ACoooV

0.27

SD-K50, SD-K65

SD-K50-COIL

DCoooV

0.8

S-K80, S-K95

S-K80-COIL

ACoooV

0.6

SD-K80, SD-K95

SD-K80-COIL

DCoooV

0.6

S-K125, S-K150

S-K125-COIL

ACoooV

0.46

SD-K125, SD-K150

SD-K125-COIL

DCoooV

0.9

S-K180, S-K220

S-K180-COIL

ACoooV

0.6

SD-K220

SD-K220-COIL

DCoooV

1.4

S-K300, S-K400

S-K300-COIL

ACoooV

0.9

SD-K300, SD-K400

SD-K300-COIL

DCoooV

2.0

S-K600, S-K800

S-K600-COIL

ACoooV

2.0

SD-K600, SD-K800

SD-K600-COIL

DCoooV

6.0

Note: When ordering, please specify the operating voltage according to page 9 Table 151~3.

172 Replacement contact kits


Kits of main contacts for contactors

Table 172(1)

Contactor
Kit consists of 3 moving contacts
and 6 stationary contacts (include
springs and spring supports also).

PARTS BH739N300

BH569N300

Part number

S-N10*, -N11, -N12


SD-N11, -N12
S-N18
S-N20, -N21, SD-N21
S-N25
S-N35
SD-N35
S-K50
SD-K50
S-K65
SD-K65
S-K80
SD-K80
S-K95
SD-K95
S-K125
SD-K125
S(D)-K150
S-K180
S(D)-K220
S(D)-K300
S(D)-K400
S(D)-K600
S(D)-K800

Wt (kg)

PARTS BH719N300

0.03

PARTS
PARTS
PARTS
PARTS
PARTS
PARTS
PARTS
PARTS
PARTS
PARTS
PARTS
PARTS
PARTS
PARTS
PARTS
PARTS
PARTS
PARTS
PARTS
PARTS
PARTS
PARTS

0.05
0.05
0.07
0.07
0.07
0.11
0.11
0.11
0.11
0.1
0.1
0.1
0.1
0.1
0.1
0.2
0.4
0.4
0.8
0.8
2.5
2.5

BH729N300
BH739N300
BH749N300
BH749N301
BH749N303
BH559N300
BH559N302
BH559N301
BH559N303
BH569N300
BH569N302
BH569N301
BH569N303
BH579N301
BH579N304
BH589N300
BH599N301
BH599N300
BH609N300
BH609N301
BH619N300
BH619N301

BH599N300
Table 172(2)

Kits of auxiliary contacts for contactors


Kit consists of 1 bifurcated moving
contact and 2 stationary contacts.
Kit consists of 2 bifurcated moving
contacts and 4 stationary contacts.

PARTS BH729N310

Kit consists of 4 bifurcated moving


contacts and 8 stationary contacts.

Contactor

For arrangement
1NO

Part number
PARTS BH719N310

Wt(kg)

S-N10, N11, SD-N11

1NC

PARTS BH719N311

0.01

S-N12, SD-N12

1NO+1NC

PARTS BH729N310

0.01

S-N20

1NO+1NC

PARTS BH739N310

0.02

S-N21 to S-N35,

2NO+2NC

PARTS BH739N311

0.03

PARTS BH539N315

0.02

SD-N21 to SD-N35,
S-K50 to K125
SD-K50 to K125
S-K150 to K800
SD-K150 to K800

(Use auxiliary contact blocks, see


1.7.3 Auxiliary Contact Blocks.)

12

0.01

173 Auxiliary Contact Blocks


Mounting
Front clip-on1,2

Table 173

Contactor/Relay

Type for

Contact arrangement Part Number

S-N10, -N11, -N12,

Standard

2NO

UN-AX22A

-N20, -N21, -N25,

1NO+1NC

UN-AX2 1A1B

-N35, -N18, -N28,

2NC

UN-AX2 2B

-N38, -N48

4NO

UN-AX4 4A

3NO+1NC

UN-AX4 3A1B

2NO+2NC

UN-AX4 2A2B

SD-N11, -N12, -N21,


-N35
SRD-N4

Low level signal 1NO+1NC (low level) UN-LL22


(5Vdc 5mA)
1NO+1NC (standard)

S-N10, -N11, -N20,

Standard

SR-N4

UN-AX4

UN-AX11

Side clip-on1,3

1NO+1NC

UN-AX11

4NO

UA-AX2140

2NO+2NC

UA-AX21

3NO+1NC

UA-AX2131

S(D)-K80, -K95, -K125

1NO+1NC

UA-AX80

S(D)-K150, -K180, -K220, -K300, -K400

1NO+1NC

UA-AX150

S(D)-K600, -K800

2NO+2NC

UA-AX600

-N21, -N25, -N35


SD-N11, -N21, -N35
SR-N4, SRD-N4
Front clip-on2

Side clip-on3

UA-AX150

S-K50, -K65

Note: 1 Front clip-on and side clip-on should not be mounted both.
2 Maximum 1 piece of aux. contact block can be mounted on a Contactor / Relay.
3 Maximum 2 pieces of aux. contact block can be mounted on a Contactor / Relay.

174 Mechanical interlocks

Table 174

Contactor

Part Number

S-N10, -N11, SD-N11

UN-ML11*

S-N20, -N21, -N25, -N35,

UN-ML21

-N18, -N28, -N38, -N48


SD-N21, -N35

UN-ML11

S(D)-K50, -K65

UA-ML50

S(D)-K80, -K95, -K125

UA-ML80

S(D)-K150

UA-ML150

S-K180, S(D)-K220, -K300, -K400

UA-ML220

UN-ML21

175 Connecting bar kits

UA-SD50

Table 175

For connecting reversing contactors

Contactor

Part Number

Kit consists of 3 connecting bars or


wires each for source and load side.

S-2N10, -2N11
S-2N18
S-2N18
S-2N20, -2N21
S-2N20, N2N21
S-2N25, -2N35
S-2N25, -2N35
S-2K50, -2K65
S-2K80, -2K95
S-2K125
S-2K150
S-2K180, -2K220
S-2K300, -2K400
S-2K600, -2K800

UN-SD10
UN-SD18
UN-SD18
UN-SD21
UN-SD21
UN-SD35
UN-SD35
UA-SD50
UA-SD80
UA-SD125
UA-SD150
UA-SD220
UA-SD300
UA-SD600

13

176 Surge absorbers

Table 176

Varistor type

Contactor/Relay

Applicable control voltage

Part Number

S-N10, -N11, -N12, -N18, -N20,

AC24-240V/DC24-250V

UN-SA21 AC200V

AC200-480V

UN-SA21 AC400V

AC50-240V

UN-SA22 AC200V

-N21, -N25, -N35, -N28, -N38, -N48


SD-N11, -N12, -N21, -N35
SR(D)-N4
Varistor type with operating
indicator (LED)

S-N10, -N11, -N12, -N18, -N20,


-N21, -N25, -N35, -N28, -N38, -N48

DC60-250V

SD-N11, -N12, -N21, -N35


SR(D)-N4

UN-SA13
Varistor and CR type

CR type

S-N10, -N11, -N18, -N20, -N21,

AC24-127V

-N25, -N35, -N28, -N38, -N48

DC24-125V

UN-SA25 AC100V

SD-N11, -N12, -N21, -N35

AC100-240V

SR(D)-N4

DC100-250V

S-N10, -N11, -N12, -N18, -N20,

AC24-240V

UN-SA23 AC200V

DC24-250V

UN-SA13 DC200V

UN-SA25 AC200V

-N21, -N25, -N35, -N28, -N38, -N48


SR-N4
SD-N11, -N12, -N21, -N35 SRD-N4

177 Pneumatic time delay modules

Table 177

Contactor/Relay

On delay

S-N10

UN-TR4AN

S-N11
S-N12
S-N18
SR-N4
SD-N11

UN-TR4AN

SD-N12
SRD-N4

For detail see page 43.


Note : UN-AX11 (Table 1.7.3) can not be combined to a Contactor / Relay together with UN-TR4AN.

178 DC interface modules


Direct mounting
to contactor

Table 178

Output
Contactor/Relay

Solid state

Relay

S-N10, -N11, -N12, -N18, -N20,

UN-SY21

UN-SY22

UA-SY31

UA-SY32

UA-SY11

UA-SY12

-N21, -N25, -N35, -N28, -N38,


-N48
SR-N4
S-K50
S-K65

UN-SY
Separate
mounting

For detail see page 36.

14

S-K80 to K400

18 Connections and Contact Arrangement


n S, SD-N/Ko
A2 A1

A2 A1

1/L1 3/L2 5/L3 13

2/T1 4/T2 6/T3 14

S-N10, N11(1NO)
SD-N11(1NO)

A2 A1

14 2/T1 4/T2 6/T3 24

S-N12(2NO)
S-N20(2NO)

2/T1 4/T2 6/T3 22

14 2/T1 4/T2 6/T3 22

A1 A2
43 31
/ / 13 21
a b (13) (31) 1/L1 3/L2 5/L3 (23) (41)

A1
/
a

14 22 2/T1 4/T2 6/T3 44 32


(24) (42)
(14) (32)

A2
/
b

S-N12, N20
SD-N12

1/L1 3/L2 5/L3

A2 A1 13 21 1/L1 3/L2 5/L3 43 31

2/T1 4/T2 6/T3

14 22 2/T1 4/T2 6/T3 44 32

S-N18

S-N21, N25, N35


SD-N21, N35

13 21 43 31
(13) (31) (23) (41) 1/L1 3/L2 5/L3

14 22 44 32 2/T1 4/T2 6/T3


(14) (32) (24) (42)

S-K50~K400
SD-K50~K400

A1/a

13 21 43 31
(13) (31) (23) (41) 1/L1 3/L2 5/L3

A2/b

14 22 44 32 2/T1 4/T2 6/T3


(14) (32) (24) (42)

A2 A1 13 1/L1 3/L2 5/L3 21

S-N10, N11(INC)
SD-N11(INC)

A2 A1 13 1/L1 3/L2 5/L3 23

1/L1 3/L2 5/L3 21

S-K600, K800

SD-K600, K800

15

n S, SD-2xN/Ko
BLACK
A2

A1 1/L1 3/L2 5/L3

13

2/T1 4/T2 6/T3 14

RED
R01 L01

R02

A2

L02

A1 1/L1 3/L2 5/L3 13

A2 A1 1/L1 3/L2 5/L3 53 61 71 83

A2 A1 1/L1 3/L2 5/L3 53 61 71 83

14

2/T1 4/T2 6/T3 54 62 72 84

2/T1 4/T2 6/T3 54 62 72 84

2/T1 4/T2 6/T3

S-2xN10, N11
SD-2xN11
A2 A1

S-2xN18

13 1/L1 3/L2 5/L3 21

A2 A1 13 1/L1 3/L2 5/L3 21

14 2/T1 4/T2 6/T3 22

14 2/T1 4/T2 6/T3 22

A2 A1

13 21 1/L1 3/L2 5/L3 43 31

A2 A1 13 21 1/L1 3/L2 5/L3 43 31

14 22 2/T1 4/T2 6/T3 44 32

14 22 2/T1 4/T2 6/T3 44 32

S-2xN20

S-2xN21~N35
SD-2xN21, N35

13 21 1/L1 3/L2 5/L3 43 31

A1 A2 13 21

1/L1 3/L2 5/L3 43 31

83 71

54 62 14 22 2/T1 4/T2 6/T3 44 32

14 22

2/T1 4/T2 6/T3 44 32

84 72

A1 A2 53 61

S-2xK50~K400
SD-2xK50~K150, K220~K400
A1
/
a 13 21 43 31 1/L1 3/L2 5/L3 53 61 83 71

13 21 43 31 1/L1 3/L2 5/L3 53 61 83 71

A1
/
a

A2 14 22 44 32 2/T1 4/T2 6/T3 54 62 84 72


/
b

14 22 44 32 2/T1 4/T2 6/T3 54 62 84 72 A2


/
b

S-2xK600, K800

A1/a

A1/a

13 21 43 31 1/L1 3/L2 5/L3 53 61 83 71

13 21 43 31 1/L1 3/L2 5/L3 53 61 83 71

A2/b

14 22 44 32 2/T1 4/T2 6/T3 54 62 84 72

14 22 44 32 2/T1 4/T2 6/T3 54 62 84 72

A2/b

SD-2xK600, K800

16

19 Outline Dimensions
191 Outline Dimensions of Non-Reversing Contactors

Top Hat rail


(35mm)
D
M3.5 screw

13.5

AA AB AC BB BA CC CA

D Wt (kg) T

43

78

78

35 4.5 70

50

19

10 106

S-N12

53

78

78

40 4.5

50

19

10 106

4 0.32 5

S-N18

43

79

81

30

60

13

10 109

4 0.33 5

SD-N11

43

78 110 35 4.5 70

50

19

10 138

4 0.62 5

SD-N12

53

78 110 40 4.5

50

19

10 138

4 0.64 5

0.3

AC

Note: Front clip-on and side clip-on aux. contact blocks should not
both be mounted.

AA

AB

A
S-N10,-N11
B

BB

BA

2 mtg. holes for M4 screws

CC

CA

(with side clip-on aux.


contact block)

(with front clip-on aux.


contact block)

2 mtg. holes for M4 screws


M4 screw

BB

BA

M3.5 screw

Top Hat rail


D (35mm)
CC

AA

AB
13.5

AA AB AC BB BA CC CA

81

81

54 4.5 90

S-N25,-N35

75

89

91

65

SD-N21

63

81 113 54 4.5 90

SD-N35

75

89 123 65

BB
BA

M4 screw

4 0.52 5

0.4

60

14 6.5 141

4 0.72 5

102 70

13 6.5 151

4 0.85 5

AA AB AC BB BA CC CA

P Wt (kg) T

S-K50,-K65
S-K80,-K95

88 106 106 70
100 124 127 80

9
75 15.5 10 135 4.5 M4 M6 1.1
10 128 110 7 12 M5 M6 1.8

10
10

SD-K50,-K65
SD-K80,-K95

88 110 133 70
100 134 158 80

9
75 15.5 10
10 128 110 7 12

10
10

M4 M6 2.1
M5 M6 3.3

C
CA
(with head clip-on aux.
contact block)

(with side mounted aux.


contact block)

Key to Dimensions

4 mtg. holes for M screws

S-K125
S-K150
S-K180,-K220
S-K300,-K400
S-K600,-K800

A
100
120
138
163
290

B
150
160
204
243
310

C
136
145
174
195
234

AA AB BB BA CC
90
5 125 12.5 1.6
100 10 125 17.5 1.6
120 9 190 7 1.6
145 9 225 9 2.3
250 20 250 30 10.5

CA

D
M
M4
M5
M6
M8
M10

P Wt (kg)
M8 2.5
M8 3.2
M10 5.5
M12 9.5
M16 27

T
30
30
30
50
10

SD-K125
SD-K150
SD-K220
SD-K300,-K400
SD-K600,-K800

100
120
138
163
375

150
160
204
243
310

161
170
200
220
234

90
100
120
145
250

M4
M5
M6
M8
M10

M8
M8
M10
M12
M16

30
30
30
50
10

BA

BB
B

P screw

AA
A

13 6.5 119

D
T

A
AC

102 70

Key to Dimensions

CC

2 mtg. holes for M screws

AA

14 6.5 109

Note: Front clip-on and side clip-on aux. contact blocks should not
both be mounted.

AB

D Wt (kg) T

60

CA
(with front clip-on aux.
contact block)

(with side clip-on aux.


contact block)

P screw

63

AC

A
S-N20,-21

AB

M4 screw

CC
T

5
10
9
9
20

125 12.5 1.6


125 17.5 1.6
190 7 2.0
225 9 2.3
250 30 10.5

4.3
4.3
7.5
13.5
28

17

N mtg. holes for M screws

Q screw

P screw

P screw

BA
B

BA
B

BB

Q screw

BB

192 Outline Dimensions of Reversing Contactors

4 Top Hat rail (35mm)


AB
13.5

a)

AA

AC
A

AA

CC

CC
T
T

C
CA

b)

AB
13.5

AA
A

13.5

C
CA

N mtg. holes for M screws

N mtg. holes for M screws

M16 screws
M4 screws

435

230

370

BA
B

90

20

BB

Q screw P screw

19

c)

AB

620
A

CC

AA
A

10 253
6 mtg holes for M10 screws

d) S(D)-2xK600/K800

Key to Dimensions
Type
S-2xN10/N11
S-2xN18
S-2xN20/N21
S-2xN25/N35
S-2xK50/K65
S-2xK80/K95

SD-2xN11
SD-2xN21
SD-2xN35
SD-2xK50/K65
SD-2xK80/K95

18

Fig.
a
a
a
b
b
b

A
99
96
136
160
216
270

B
78
79
81
110
115
140

C
78
109
81
97
112
137

AA
35
30
54
150
204
247

AB
4.5
3.5
4.5
15
6
11.5

AC
21
23
19

BA
50
60
60
100
100
100

BB
19
13
14
8
8
32

CC
10
10
6.5
1.6
2
10

N
4
4
4
3
3
3

M
M4
M4
M4
M4
M5
M6

P
M3.5
M4
M4
M5
M6
M6

Q
M3.5
M3.5
M3.5
M3.5
M4
M4

Wt.(kg)
0.64
0.75
0.8
1.3
2.6
4.3

T
5
5
5
5
10
10

a
b
b
b
b

99
160
160
216
270

78
100
113
115
140

110
119
129
133
157

35
150
150
204
247

4.5
5
5
6
11.5

21

50
90
100
100
100

19
5
8
8
32

10
2
1.6
2
10

4
3
3
3
3

M4
M4
M4
M5
M6

M3.5
M4
M5
M6
M6

M3.5
M3.5
M3.5
M4
M4

1.3
1.7
2.0
4.5
6.4

5
5
5
10
10

2 MOTOR PROTECTION RELAYS


21 Thermal Overload Relays
TH-N Series Thermal Overload Relays Will Make a Convenient
and Safe System.

TH-N12

TH-N20

A Selection of Relays for Optimum


Motor Protection Characteristics
The thermal relay line-up includes two element units as well as
the phase failure protection type models (three-element
relays), all with the same external dimensions.
This array of protection characteristics allows you to choose
the units best suited to your motor protection needs.

TH-N12
Display and External Trip Mechanism

TH-N12(KP)
Display

When the green of the display


lever can be seen, the device
has been reset.

Display
lever

Display
window

Maintenance and Inspection Are Easy


An operation indicator makes maintenance and inspection easy.
Checks can be performed using manual operations.

External Trip
Screw driver

Display
window

Display
lever

When reset

When the green of the lever turned


in, the device has been tripped.

TH-N20(KP)~K600(KP)

1NO+1NC Contacts

Display window

When tripped

Can be tripped manually by turning in the display lever.

External Trip
Driver

Display
Display
window

95

Display window

Display
lever

97

Reset

96

Display
window

98

1 NO and 1 NC contacts can


be used independently as signals contacts.

When the display window is


green the device has been
reset.

When the display window is


white the device has been
tripped.

Tripped

Can be tripped manually by


pushing in with a screwdriver
and turning the display lever.

Switching Between Automatic and Manual Reset

TH-N12(KP)~K600(KP)
Stopper

Manual Reset Mode

Automatic Reset Mode

Rated Current Can Be Set Easily


The value of the rated current is displayed on a dial.
Simply adjust the dial to the full-load current of the motor and
motor protection is assured.

Finger Protectors
Models with finger protectors conforming to DIN VDE
0106 Part 100 (TH-No) are also available.

Switchover
plate

Switchover
plate

Switching from manual to automatic : Break the stopper off and then, slide the
switchover plate to the right (to position A) to immobilize the reset bar.
Switching from automatic to manual : Slide the switchover plate to the left (to
position H).

TH-N20(KP)~K600(KP)

Various Accessories
Independent mount adaptor for TH-N12.
: UN-HZ12
Reset release : UN-RR ooo/UA-RRooo
Trip indicating LED : UN-TLoo/UA-TL20

Trip-Free Reset Bar


Choose between automatic and manual reset. Also features
tripfree reset bar mechanism.

Switching from manual to automatic : Flip the stopper on the end


of the reset bar down and then, after pushing it all the way in,
rotate it counterclockwise 90 (to position A).
Switching from automatic to manual : Rotate the reset bar 90
clockwise (to position H) and the reset bar will pop out.

19

Series TH-N/K

211 Selection guide of thermal overload relays


Overload Relay

Max. Fuse Rating (660Vac)


IEC 269-1
(A)

Motor Capacity [kW, (hp)]


(Three phase 50/60Hz, based on four poles)

aM

gG

gM

Heater
designation

0.5

0.5

0.12A

0.1-0.16

0.5

0.17A

0.14-0.22

0.24A

0.2-0.32

0.03(1/24)

0.06(1/12)

0.06(1/12)

0.09(1/8)

0.35A

0.28-0.42

0.05(1/16)

0.09(1/8)

0.09(1/8)

0.12(1/6)

0.5A

0.4-0.6

0.06(1/12)

0.12(1.6)

0.12(1.6)

0.18(1/4)

0.7A

0.55-0.85

0.09(1/8)

0.18(1/4)

0.18(1/4)

0.25(1/3)

0.9A

0.7-1.1

0.12(1/6)

0.25(1/3)

0.25(1/3)

0.37(1/2)
0.55(3/4)
0.75(1)

Model
(TH-)

Setting range
(A)

N12

AC220-240V

AC380V

AC400-440V

AC500V

1.3A

1.0-1.6

0.18(1/4)

0.37(1/2)

1.7A

1.4-2.0

0.25(1/3)

0.55(3/4)

0.75(1)

2.1A

1.7-2.5

0.37(1/2)

0.75(1)

10

2.5A

2.0-3.0

0.55(3/4)

1.1(1-1/2)

1.1(1-1/2)

1.5(2)

10

3.6A

2.8-4.4

0.75(1)

1.5(2)

1.5(2)

2.2(3)

16

5A

4.0-6.0

1.1(1-1/2)

2.2(3)

2.2(3)

3(4)

12

20

6.6A

5.2-8.0

1.5(2)

3(4)

3,3.7(4.5)

3.7(5)

3(4)
3.7(5)

5.5(7-1/2)

N18

N20

0.37(1/2)
0.55(3/4)

1.1(1-1/2)

20

9A

7.0-11

2.2(3)

16

25

32M35

11A

9.0-13

3(4)

5.5(7-1/2)

5.5(7-1/2)

7.5(10)

3.7(5)

7.5(10)

7.5(10)
9(12.5)

9(12/5)

K60

12

3.7(5)
4(5-1/2)

32M50

15A

12-18

25

40

32M63

19A1

16-22

5.5(7-1/2)

11(15)

11(15)

11(15)

40

63

32M63

22A

18-26

5.5(7-1/2)

11(15)

11(15)

15(20)

50

80

63M80

29A

24-34

7.5(10)

15(20)

15(20)

18.5(25)

63

80

63M80

35A

30-40

9(12.5)

18.5(25)

18.5(25)

22(30)

63

100

100M100

42A

34-50

11(15)

22(30)

22(30)

30(40)

80

125

100M125

54A

43-65

15(20)

30(40)

30(40)

37(50)

100

160

100M160

67A

54-80

18.5(25)

37(50)

37(50)

45(60)

125

200

100M200

82A

65-93(65-100)5

22(30)

45(50)

45(60)

55(75)

200

100M200

95A

85-105

30(40)

55(75)

55(75)

250

200M250

105A

85-125

30(40)

55(75)

55(75)

75(100)

250

200M250

125A

100-150

37(50)

75(100)

75(100)

90(125)

315

200M315

150A

120-180

45(60)

90(125)

90(125)

110(150)

400

180A

140-220

55(75)

110(150)

110(150)

132(175)

500

75(100)

132(180)

132(180)

75(100)

132(180)
160(220)

132(180)
160(220)

160(220)

90(125)
110(150)

200(270)

200(270)

220(300)
250(340)

132(180)
160(220)

220(300)
250(340)
300(400)

220(300)
250(340)
300(400)

400(530)

200(270)
220(300)

400(530)

400(530)

500(670)

K120

K220oo

K60TA
K120TA

210A

170-250

630

250A

200-300

630

330A

260-400

800

500A

400-600

1000

660A

520-800

K600

K400oo

K220oo

K400oo

K60

32

N20TA

20

Notes: 1. For starter size N20, N21 only.


2. For starter size N35 only.
3. For starter size K95 only.
4. For starter size k220 only.
5. TH-K120KP and TH-K220KP relays have a setting range of 65-100A.
6. Selection by mounting.

20

Table 211

212 Technical data


Three heater type
Two heater type

TH-

Max. setting current


Range of setting current
Rated insulation voltage

A
A
V

Permissible ambient temperature

Table 212

N12KP

N18KP

13
0.1-13
690

18
2.8-18
690

N20KP

N20TAKP

K60KP

22
0.2-22
690

40
18-44
690

65
12-65
690

K120KP
100
34-100
690

0.9

0.8

1.4

1.7

1.8

2.2

2.2

3.5

4.9

800
200-800
690

Via CTs1

3.2

2.5

2.5

2.5

5.2

7.1

8.6

6.0

6.0

6.0

1NO+1NC
2

1
0.5

1
0.5

NC

120V

contact

240V

500V

0.5

48V

0.4

1
0.5

110V

0.2

0.2

220V

0.1

0.1

Main terminal screw size


Line side
Load side

mm
mm

Standard wire sizes


recommended
Heater designation-wire size
(mm2)

Aux. contacts

K600KP

2.5

Busbar width
Line side
Load side

400
85-400
1000

2.4

500V

Max. conductor size


Main
Line side
Load side

220
65-250
1000

Via CTs

0.8

Rated operating current of aux. contacts


Category NO
120V A
AC-15
contact
240V A

DC-13

150
85-150
690

Direct

Auxiliary contact

Category

K120TAKP K220RHKP K400RHKP

105
54-105
690
25 to`55
Types TH-N/KoooKP provide the protection.

Single phase protection


Bimetal heating
Max. heater dissipation per current path
Min. setting
W
Max. setting
W

K60TAKP

mm
mm2
mm
mm
mm2

M4

M4

M6

M6

M8

M8

M4

M3.5

M4

M4

M5

M6

M6

M8

M8

M10

M12

M4

0.24A-2

3.6A-2

0.24A-2

42A-14
54/67A-22
82A-38

105A-50
125A-60

11A-2
15A-3.5

15A-3.5
22A-5.5
29/35A-8
42A-14
54A-22

67A-22
82/95A-38

11A-2

11A-2
15A-3.5
19A-5.5

22A-5.5
29/35A-8

(2.5)2

25

38

60

2.5

25

38

38

60

150

240

16

15

20

20

15

20

20

20

25

30

2.5

Notes: 1. Used with current transformer (to be supplied by the customer). See Table 212.
2. When used with UN-HZ 12 adaptor.

21

213 Operating Characteristics of Thermal Overload Relays


(Connecting wire size: Refer Table 212)

(h)

(h)

(s)
1000
800
600
400

200

200

10
8
6
4

1.5 2

10
8
6
4

1
0.8
0.6
0.4

0.2
0.8 1

100
80
60
40
30
20

Single phasing
(TH-N12KP
Mean value)
3

4 5 6

8 10

Operating Time

With reactors
(TH-N12SR)

100
80
60
40
30
20

0.8 1

1
0.8
0.6
0.4

1.5 2

4 5 6

8 10

(h)

(h)

Amb. Temp.: 20:

0.8 1

10
8
6
4

Single phasing
(TH-N20TAKP,
Mean value)

Amb. Temp.: 20:

1
0.8
0.6
0.4

With reactors
(TH-K60SR)

10
8
6
4

Single phasing
(TH-K60(TA)KP,
Mean value)

0.8 1

1.5 2

5 6

8 10

0.8 1

15

1.5 2

(h)

5 6

8 10

5 6

8 10

15

(h)
2

Amb. Temp.: 20:

1
(s)
1000
800
600
400

With reactors
(TH-K220,
K400RHSR)

200
100
80
60
40
30
20

Operating Time

Operating Time

1.5 2

Multiples of setting current

400

Single phasing
(TH-K220RHKP,
K400RHKP,
Mean value)

200

With reactors
(TH-K600SR)

100
80
60
40
30
20
10
8
6
4
2
1
0.8
0.6
0.4

1
0.8
0.6
0.4

Single phasing
(TH-K600KP,
Mean value)

0.2

0.2
0.8 1

1.5 2

5 6

8 10

Multiples of setting current

22

Single phasing
(TH-K120(TA)KP,
Mean value)

0.8 1

(s)
1000
800
600

10
8
6
4

0.2

15

Amb. Temp.: 20:

10
8
6
4

100
80
60
40
30
20

1
0.8
0.6
0.4

TH-K600KP

With reactors
(TH-K120(TA)SR)

200

Multiples of setting current

Multiples of setting current

TH-K220RHKP
TH-K400RHKP

15

0.2

0.2

8 10

(s)
1000
800
600
400

100
80
60
40
30
20

1
0.8
0.6
0.4

5 6

Amb. Temp.: 20:

200

TH-K120KP TH-K120TAKP

Operating Time

Operating Time

100
80
60
40
30
20

(h)

With reactors
(TH-N20TASR)

1.5 2

Multiples of setting current

(s)
1000
800
600
400

200

Single phasing
(TH-N20KP,
Mean value)

0.2

15

TH-K60KPTH-K60TAKP

(s)
1000
800
600
400

Operating Time

Multiples of setting current

TH-N20TAKP

10
8
6
4

0.2

15

With reactors
(TH-N20SR)

100
80
60
40
30
20

Single phasing
(TH-N18KP
Mean value)

Multiples of setting current

Amb. Temp.: 20:

(s)
1000
800
600
400

Operating Time

Operating Time

200

Amb. Temp.: 20:

(s)
1000
800
600
400

1
0.8
0.6
0.4

(h)

Amb. Temp.: 20:

TH-N20KP

TH-N18KP

TH-N12KP

15

0.8 1

1.5

5 6

8 10

Multiples of setting current

15

214 Optional parts and accessories


Table 213
Reset release

Separate mounting adaptor

Thermal overload relay

Part number

Length (mm)

TH-N12(KP)
TH-N18(KP)

UN-RR205
UN-RR405
UN-RR555
UN-RR705

200
400
550
700

TH-N20,N20TA(KP)

UN-RR200
UN-RR400
UN-RR550
UN-RR700

200
400
550
700

TH-K60(KP),-K600(KP)

UA-RR200
UA-RR400
UA-RR550
UA-RR700

200
400
550
700

Thermal overload relay

Part number

TH-N12(KP)
TH-N12(KP)

UN-HZ12
UN-HZ12

Table 214
Connector assembly

For connection between contactor (non-reversing type) and


thermal overload relay

Overload relay

Part number

S-N20, S(D)-N21
S-N25, S(D)-N35

UN-TH20
UN-TH25

0.02
0.02

S(D)-K50, -K65

BH559N350

0.02

TH-K60(KP), -K60TA(KP)

S-K80, -K95
SD-K80, -K95

BH569N350
BH569N352

0.04
0.04

TH-K120(KP), K120TA(KP)

S(D)-K125
S(D)-K150

BH579N355
BH589N355

0.36
0.36

TH-N20(KP)
TH-N20(KP),-N20TA(KP)
TH-K60(KP)
* Connecting bars and mounting plate are included in the
OLR of TH-K220RH(KP) and
TH-K400RH(KP) for
S-K180, -K220, -K300, -K400.

Weight

Contactor

23

215 Outline Dimensions


M3.5 screws

46

65.5

55

55

Top Hat rail


(35mm)

76.5
M3.5 screws

TH-N12(KP) (Wt: 0.11kg)

4.5

35
83.5

48

TH-N12(KP) with mounting adapter UN-HZ12

59

M3.5 screws

54

80
M4 screws

BB

TH-N18(KP) (Wt: 0.14kg)

P screws

AA

AB

BA

BB

CC

TH-N20(KP)

63

51

79

19

15

33

8.5

4.5

M4 M3.5 0.14

TH-K60(KP)

89
[92]

57

83.5
[87]

70

11

45

4.5

M6

M4 0.26

TH-K120(KP)

103

67

105

75

14

50

10

M8

M4 0.48

TH-K600(KP)

63

42

83.5

19

14

33

4.5

M4

M4 0.14

AA

AB

BA

BB

CC

P(P)

Wt.
(kg)

74

72

83.5

M5 (M4)

0.2

M6 (M6)

0.32

M8 (M8)

0.75

B
BA
AB

BB

AA
A

CC
M4
screws

Wt.
(kg)

Type

B
BA

(P) screws

Type

AB

AA
A

P screws

CC

TH-N20TA(KP)

M4
screws

89

TH-K120TA(KP)

112

73.5 83.5
87

105

M4 screws

TH-K60TA(KP)

Type
P bolts

AA

AB

BA

BB

CC

Wt.
(kg)

TH-K220RH(KP)

144 114

180

M10

2.5

TH-K400RH(KP)

144 160 194

M12

2.7

AA

AB

BA

BB

CC

Wt.
(kg)

BB

Type

BA

N-fM mtg.holes

AB
P bolts

24

AA
A

M4 screws
C

CC

TH-K220HZ(KP)

144 104 167

47

48.5

62

21

18

M10

2.5

TH-K400HZ(KP)

144 173 167

47

48.5

62

55.5

18

M12

2.7

Note: Suffix HZ denotes separate mounting type.

Series ET-N

2.2 Electronic Motor Protection Relays

The MITSUBISHI series ET-N relay is an excellent relay that can protect motors electrically.
Those series ET-N relays have the following excellent features.

n Features
Selectable Protection Mode
Overload (including locked rotor condition)

Quick trip (3s.)


Fast trip (5s.)

Phase failure (including current unbalance)

ET-N60 60A

Medium trip (15s.)

Incorrect phase sequence


Excellent Wide Current Range
Easy Wiring
Easy Setting and Maintainence
Selectable Tripping Time at 600% of setting
Standard trip (7s.)

Slow trip (30s.)


Withstands High Overcurrent
Fine Indication of Trip Mode
Conformity to International Standards
Mountable onto DIN Rail (35 mm)

Type Designation

ET -

N60

8A

AC100/200V

CURRENT RANGE
1A
0.25,1A
4A
1,4A
8A
2,8A
20A
5,20A
60A
15,60A
150A
40,150A
360A
110,360A

FRAME SIZE
N60
60A frame
N150 150A frame
N360 360A frame

CONTROL VOLTAGE
AC100V
100-120V 50/60Hz
AC200V
200-240V 50/60Hz

n Specifications
Ratings and characteristics

Table 221

Frame size [Current range]

N60[1A]

N60[4A]

N60[8A]

N60[20A]

N60[60A]

N150[150A] N360[360A]

Rated insulation voltage

VAC

Adjustable setting range

0.25-1

1-4

2-8

5-20

15-60

40-150

110-360

Applicable motor
capacity
3-ph

200-240VAC
380-440VAC

kW
kW

0.03-0.2
0.05-0.4

0.2-0.75
0.4-1.5

0.4-1.5
0.75-2.2

1.5-4
2.2-7.5

3.7-11
7.5-22

11-37
22-75

30-90
55-150

200-240VAC
380-440VAC

Hp
Hp

1/16-1/4
1/8-1/2

1/4-1
1/2-2

1/2-2
1-3

2-5
3-10

5-15
10-30

15-50
30-100

40-125
75-200

Rated operating
current of aux.
contacts

Category
AC-15

120VAC
240VAC

A
A

2
1

Category
DC-13

24VDC
110VDC

A
A

1
0.2
10 to + 55/45 to 85

Permissible ambient temperature/humidity

690

C / %RH

Control circuit consumption

VA

7.5 (AC100V)/15 (AC200V)

times

0.85 to 1.1 (rated control voltage)

Overload

[minimum tripping current] 110 to 120 (at setting current)

Phase failure

more than 70 (at setting current) [Tripping time : 2-4 sec.]

Reversal phase

more than 70 (at setting current) [Tripping time : less than 0.5 sec.]

Control voltage tolerance


Tripping time

Tripping condition

See Fig. 221

VAC

2500 [1 minute]

Vibration 10-55Hz

gs

Sine wave pulse

gs

Withstand voltage
Shock resistance
Conductor size

Main terminals

mm2

Control terminals

mm2

5
2-14

3.5-22

5.5-60

14-200

1.25-2

Notes: ET-N relay cannot be used on DC circuit.


25

Characteristic Curves
Fig 221

(h)
2
1

(s)
1000
800
600
400

(min)
60
50
40
30

Tripping time

200
100
80
60

20
10
8
6
5
4
3
2

Overload
(600%)
30s

40
30
20

15s
10
8
6

7s
5s
3s

Phase failure

4
2
1
0.8
0.6

Reverse phase

0.4
0.2

0.8 1

1.5

5 6

8 10

15

Multiple of Setting current

Selection of Protection Mode & Tripping


PF

REV

0 12

20

8 9A

TEST RESET

34 5

EF

BCD

PWR OC

Protection mode

MODE

15

67

ET-N60
20A 10

RC.A
CURRENT

Current Setting

Table 222

Time
The selector switch is set at position 7 when
shipped (overload and phase failure protection
mode; standard trip type).
Reset the position of the changeover switch
according to Table 222 before installation.

reversal phase

15

30

15

Overload and phase failure


[2E]

Overload only
[1E]

Application to High Voltage or Big Motor Circuit


The high voltage current transformer (secondary current: smaller than 5A:
capacity: more than 5VA) should be connected to ET-N60*8A in the star
connection, when the load is high voltage or big AC motor.

26

Symbol on changeover switch

Overload, phase failure and

[3E]

Function Selector
Switch

Overload tripping time


at 600% of setting(s)

30

15

30

n Wiring Precautions
Indicators
LED1:Source
LED2:Overload
LED3:Phase failure
LED4:Reverse phase
Test button

MCCB
MC

1/L1 3/L2 5/L3

The control source should be


wired in the same phases as the
contactor control source.
When the load is a single phase
motor, use 1/ L1-2/T1 and 5/L36/T3 phases.
And re-set the position of
changeover switch to A to E.

Mode selection
Current setting
Reset button

LED1 LED2 LED3 LED4

RA

NC
A1

2/T1 4/T2 6/T3

A2

96

MC

95

NO
98

97

MC

ON

OFF

Control source

If capacitors are used to correct the power factor, connect the capacitor in the power source side of the ET-N relay.

n Outline Dimensions
100
92
78
68

M8 screw
32

24.5

3/L2

5/L3

50

19

95

25.5

98

63

10.5

70
M3.5 screw

100

ET-N60(1-60A) (Wt: 0.3kg)


144

6/T3

15.7

26

21.5

7
120

ET-N150 (Wt: 1.6kg)

188
62

2.5

S/3/L2

T/5/L3

A1 A2 96 95 98
A1
A2

96
95

V/4/T2

97

80.5

30

143
173

62

4/T2

M12 screw

55

U/2/T1

97
98
97

15.7 9.5

R/1/L1

95 98
96
95

2/T1

M3.5 screw

30

A2 96
A1
A2

6/T3

4/T2

2/T1

A1

97
98
97

96
95

41.5

96

5/L3

3/L2

1/L1

50

49

A2
A1
A2

48

2.5

A1

26.5
2.5

24.5
1/L1

150

4M4 mtg. hole

75
84
108

M5 screw

32

2M4 mtg. hole

9.5

98
97

W/6/T3

18
4M5 mtg. hole

47

20

158

M3.5 screw

ET-N360 (Wt: 2.5kg)

27

3 DEFINITE PURPOSE CONTACTORS & STARTERS


Series DU

31 DC Contactors
The MITSUBISHI series DU contactors are designed for DC circuits, that is variable-speed
drive-control circuits (SCR switching circuit) and DC motor control circuits.

n Features
DU-A60

Compact design
High break capacity
CSA certified models are also
available on AC operated
type, add suffix UR immediately after the Frame size.

Double break contacts


Long Life
UL recognized component
(If
marking is required add
suffix UR immediately after
the Frame size).

Type Designation

DU-K180

DU

A60

AC 200V

CONTROL TYPE
DU
DUD

AC operated
DC operated

FRAME SIZE
A30
A60
A120
K180
K260

COIL DESIGNATION

50A frame
90A frame
160A frame
260A frame
360A frame

see Table 313

Note: Mark

* indicates a blank space.

n Specifications
Number of main contacts type DU : 2NO1NC, type DUD : 2NO
Number of auxiliary contacts type DU & DUD : 2NO2NC

Ratings

Table 311

Frame size
Rated continuous current I th
Rated operating
current for SCR
switching circuit*

1-pole

Rated operating current for SCR


switching circuit

A30

1-pole
Rated operating current
category DC2 & 4

K180

K260

160

260

360

110VDC
240VDC
440VDC
500VDC

A
A
A
A

40
40
15
15

80
80
30
30

160
160
60
60

260
260
90
90

360
360
130
130

NC
contact

110VDC
240VDC
440VDC
500VDC

A
A
A
A

120
120
120
120

240
240
240
240

480
480
480
480

720
720
720
720

1.040
1.040
1.040
1.040

NO
contact

110VDC
240VDC
440VDC
500VDC

A
A
A
A

50
50
40
40

90
90
80
80

160
160
160
160

260
260
260
260

360
360
360
360

NO
contact

110VDC
240VDC
440VDC

A
A
A

30
20
7.5

60
40
15

120
80
30

180
120

260
175

NC
contact

110VDC
240VDC
440VDC

A
A
A

20
15
7.5

40
30
15

80
60
25

100
75

150
100

NO
contact

110VDC
240VDC
440VDC

A
A
A

40
30
20

80
60
40

160
120
80

240
180
120

350
260
175

Category
AC11

110VAC
240VAC

A
A

6
5

Category
DC11

110VDC
240VDC

A
A

1.2
0.2

2-pole
Rated
operating
current of
aux. contacts

50

A120

NO
contact

2-pole
Rated operating
current
category DC 2 & 4

A60
90

Note: For SCR switching, making current of NO contacts is 2 times the rated operating current and making current of NC contact is 1
times, the rated operating current which means the peak value at making. In this application NO and NC contacts do not break
any current.
28

Characteristics

Table 312

Frame size

A30

Mechanical life
Electrical life

operations
operations

Permissible ambient temperature

Coil voltage tolerance

times
Inrush
Sealed
Watts

A120

K180

K260

2.5 million
0.5 million
10 to 55
0.85 to 1.1 (rated coil voltage)

VA
VA
W

240
28
7 (26)

520
47
13 (35)

1260
100
25 (50)

480
44
5(41)

480
54
7.3(55)

Make NO contacts ON
NC contact OFF

msec
msec

15 (60)
12

20 (100)
13

20 (140)
13

30(150)
26

40(180)
37

Break NO contacts OFF


NC contact ON

msec
msec

6(18)
12

11 (27)
11 (37)
110(25)
18
18
112
4 (at the rated operating current)
4 (at the rated operating current)

125(30)
135

Coil consumption

Operating time

A60

Make and break capacity


Category DC2 & DC4

Make
Break

tmes
times

Permissible switching frequency

operations/hour

Vibration resistance
Shock resistance

10-55Hz
10 msec half sine wave

g
g

Conductor size

Main terminals

mm2

Control terminals

mm

1,200
2
5
2-25

2-35

6-70

10-150

1-4

16-185
1-2.5

Notes: Parenthesized data is for type DUD, DC operated contactors.

Coil designation
Coil
designation

Table 313

Coils for type DU-A


Applicable voltage
50Hz

Coils for type DU-K

60Hz

AC100V
AC120V
AC200V
AC230V

100VAC
110-120VAC
200VAC
220-240VAC

100-110VAC
115-120VAC
200-220VAC
230-240VAC

AC400V
AC440V
AC500V

380-415VAC
415-440VAC
500VAC

400-440VAC
460-480VAC
500-550VAC

Coils for type DUD

Coil
designation

Applicable voltage

AC100V

100-127VAC 50/60Hz

AC200V

200-240VAC 50/60Hz

AC300V
AC400V

260-350VAC 50/60Hz
380-440VAC 50/60Hz

AC500V

460-550VAC 50/60Hz

Coil
designation

Applicable
voltage

DC24V
DC48V
DC100V
DC110V 1
DC120V
DC125V
DC200V
DC220V

24VDC
48VDC
100VDC
110VDC
120VDC 2
120-125VDC
200VDC
220VDC

Notes: 1. Only for type DUD-A60


2. 125V DC for type DUD-A60

n Spare parts
Spare parts
Main contact kits for DU-o 1
Main contact kits for DUD-o 2
Auxiliary contact kits for DU(D)-Ao3
Auxiliary contact Units for DU(D)-Ko4
Coils for DU-o5
Coils for DUD-o6

Table 314
Ordering designation
MAIN KIT DU-o
MAIN KIT DUD-o
Z926783G30
UA-AX150
DU- o-COIL ACV
DUD-o-COIL DCV

Notes: 1. Contact kit of type DU consists of three moving contacts and six stationary contacts.
2. Contact kit of type DUD consists of two moving contacts and four stationary contacts.
3. Aux. contact kits of type DU(D)-Ao are all the same.
4. Aux. contact units of type DU(D)-Ko, UA-AX 150 are the same as those of the standard series S-K contactors.
5. Coils for DU-K 180/K 260 are the same as S-K220/K300 each.
6. Coil for DUD-A30 includes only one coil. Other DC operated coils of type DUD include two coils.

29

n Contact Arrangements
A1
/
a

A2
/
b

/1

13 21

14 22

/3

/2

/5

A1
/
a

43 31

/6 44 32

/4

/1

13 21

14 22

A2
/
b

/5

43 31

/6 44 32

/2

A1
/
a

A2
/
b

A2
/
b

A1
/
a

/1

13 21

14 22

/5

43 31

/6 44 32

/2

D.B. resistor
M

M
A

M
H

DU-A30, DU-A60, DU-A120

DUD-A30

DU-K180, DU-K260

DUD-K180,DUD-K260

DUD-A60, DUD-A120

Note: Values in parenthesis are shown on auxiliary terminals of DUD-A

n Outline Dimensions
P screws
AA

BA

M4 screws

CC

AA

BA

DU-A30

100

86

118

90

105.5

12.5

DU-A60

120

100

144

100

128.5

16

DU-A120

162

130

160

140

162

2.3

DU-K180

138

120

204

190

174

1.6

DU-K260

163

145

243

225

195

DUD-A30

101

86

108

90

DUD-A60

120

100

144

DUD-A120

162

130

DUD-K180

138

DUD-K260

163

Type

30

CC

Wt.(kg)

1.2

10

2.0

10

10

4.1

10

10

5.5

30

2.3

12

135.5

3.2

2.1

10

100

161.5

3.5

10

160

140

187

2.3

10

7.1

10

120

204

190

200

1.6

10

7.5

30

145

243

225

220

2.3

12

13.5

50

10

50

32 Medium Voltage Vacuum Contactors

Series SH-V

The MITSUBISHI series SH-V contactors are specially designed for the areas of mining, pumping,
sawing and other applications where voltages above 1500VAC are frequently used.

n Features
Compact design
Lightweight
Long service life

Easy inspection & maintenance


Applications over a wide range of voltage
High insulation strength

SH-V160

Type Designation

SH

CONTROL TYPE
SH
SHD

AC operated
DC operated

CONTACTOR TYPE
Non-reversing
V
2XV Reversing

160

AC200V

FRAME SIZE
160 160A frame
320 320A frame
400 400A frame
6001 600A frame

COIL DESIGNATION
See Table 333

Note: Mark
indicates
a blank space.
Note: 1. Only AC operated non-reversing type is available for Frame size 600.
SH-V600 is not presently certified by CSA.

n Specifications
Ratings

Table 321
V160

V320

V400

V600

1,500
90(320)
200(320)
315(320)
450(320)
700(320)
75(250)
150(250)
300(200)
500(200)
350

1,500
115(400)
250(400)
400(400)
550(400)
800(400)
100(300)
200(300)
300(200)
500(200)
450

1,500
160(630)
300(630)
600(600)
750(600)
1,000(600)
200(580)
400(580)

1,500
55(180)
110(180)
160(180)
225(160)
315(160)
50(150)
100(150)
250(150)
350(150)
200

200

350

450

750

Frame size
Rated insulation voltage
Three phase motor
category AC3
Rated operating
capacity
Three phase
capacitor

V
240V
440V
660V
1,000V
1,500V
240V
440V
1,000V
1,500V

Resistance load rating category AC-1


Continuous current

Ith

Short circuit interrupting current


Withstand current
for short time

Rated operating
current of
aux. contacts

kW(A)

kVar(A)

6,000

for 2 seconds

kA

for 10 milliseconds

kA

33
5
3
3

Category
AC-15

240VAC
480VAC
660VAC

Category
DC-13

110VAC
220VAC

750

1.2
0.2

Note: A surge absorber is required for motors less than 5.5kW only.

31

Characteristics

Table 322

Frame size

V320

V160

Mechanical life1.2.

operations

Electrical life3.4.(category AC3)

operations

0.5 million

Permissible ambient temperature

-10 to +55

Coil voltage tolerance

2.5 million

times

Coil consumption

VA
VA
W

550
45
5.2

1150
55
7.3

DC operated lnrush
Sealed

VA
VA

500
40

Mechanically latched lnrush

VA

550

Operating time (approx.)

msec
msec

Make and break current capacity

Make
Break

times
times

40
130
10 (at AC3 rated operating current)
8 (at AC3 rated operating current)

operations/hour

Permissible switching frequency


10-55Hz

Sine wave pulse

Vibration resistance

Conductor size

0.85 to 1.1(rated coil voltage)

AC operated lnrush
Sealed
Watts

Make
Break

Shock resistance

V600

V400

65
80

1,200
2
5

Main terminals

mm2

Control terminals

mm

5.5-100

70-325

14-200

1-2.5

Notes: 1. Mechanical life of the latched type is 0.25 million operations.


2. Mechanical life of vacuum tube is 1 million.
3. When the load is three phase capacitors, electrical life is 0.1 million operations.
4. Electrical life of the latched type is 0.25 million operations.

Designation

Table 323

Coil designation

Rated voltage

AC100V

100~127V 50/60Hz

AC200V

200~240V 50/60Hz

AC300V

260~350V 50/60Hz

AC400V

380~440V 50/60Hz

AC500V

460~550V 50/60Hz

DC100V

100-110 VDC

DC200V

200-220 VDC

Note: When ordering the latched type contactor, specify the coil
designation of the closing coil and the tripping coil.
PlaceMCbefore the closing coil designation and
placeMTbefore the tripping coil designation.

n Spare Parts & Accessories


Contactor Catalog
Number
SH-V160
SH-V320
SH-V400
SH-V600

Coil Part Number

SH-V160COIL AC ............V
SH-V600COIL AC ............V

Main Contact Part


Number
SH-V160TUBES2
SH-V320TUBES2
SH-V400TUBES2
SH-V600TUBES2

Table 324
Auxiliary Contacts Number
Replacement(1NO 1NC)
Add-on(2NO 2NC)
UA-AXVV1

Vacuum Tube Gauge


Part Number

UA-AXVV23

SH-V160 GAUGE

UA-AXVV4

SH-V600 GAUGE

Notes: 1. See Table 3.2.3 for Coil Designation.


2. Set of three vacuum bottles suppled.
3. Consists of two UA-AXVV1 contact blocks on the mounting plate. Mounts on left side of contactor.

Surge absorber
As the vacuum tubes of SH-V use a special contact material,
the surge voltage by current chopping is very small. Surge
absorbers are required only for motors smaller than 5.5kW.

32

Table 325

Applicable voltage

Ordering designation

up to 440VAC

UA-SU4

up to 550VAC

UA-SU5

up to 660VAC

UA-SU6

up to 1,000VAC

UA-SU10

up to 1,500VAC

UA-SU15

n Contact Arrangement
n Outline Dimensions

TRIPPING
CLOSING
E2

A1 A2 53 61 83 71 1/L1 3/L2 5/L3 13 21 43 31

55

13

E1 E2 55

A1 A2 53 61 83 71 1/L1 3/L2 5/L3 13 21 43 31

56

54 62 84 72 2/T1 4/T2 6/T3 14 22 44 32

54 62 84 72 2/T1 4/T2 6/T3 14 22 44 32

SHL-Vo
SHLD-Vo

SH-Vo

SH-V600 (Wt:22kg)
210

4-9
mtg
holes

25

210
90

A
10
12.5
12.5
10
12.5
12.5

190

N
M8
M10
M10
M8
M10
M10

181

10

190

210

SH-V160
SH-V320
SH-V400
SHL(D)-V160
SHL(D)-V320
SHL(D)-V400

10

210

190

KEYS

210

210
N screws

181

4-9
mtg
holes

210

190

210
N screws

25
80

SH-V160, V320, V400

11

15

290
270
40

SHL-V160, V320, V400


SHLD-V160, V320, V400

(Wt:12.5kg)

(Wt:14kg)

225
219
175

260
285

2.3

UA-AXVV1 (Wt:0.2kg)

UA-AXVV1 (Wt:0.2kg)

28

160

121

100

4- 9 MTG.
HOLES

29

49

M16 BOLTS

49

43.5

UA-AXVV2 (Wt:0.5kg)

33

Series S-N 8

33 Compact 3-Pole Contactors

The MITSUBISHI series S-No8 compact 3-pole contactors are designed for limited panel space
applications such as machine control panels.

n Features

Compact design Very limited required mounting space.


Front clip-on type auxiliary contact block can be added.
Coil surge absorbers are available. Mountable on 35mm DIN rails.

Type Designation
S

2X

REVERSING OR
NON-REVERSING
None Non-reversing
2X Reversing

AC 200V
FRAME SIZE

COIL DESIGNATION

See table 3.3.1

See Table 1.5.1 on page 9

n Specifications

Note: Mark

* indicates a blank space

Rating and characteristics

Table 331

Type
Rated insulation voltage
Rated operational current
3-ph, category AC-3

Rated continuous current lth


Electrical life
Mechanical life
Rated making current for 100,000 cycle operations
Peak let through time 0.5ms
Switching frequency(AC3)
Inrush
Sealed
Watts
Main terminal

Coil consumption
(at rated coil voltage)
Terminal screw size

S-N28

18(4.5)
16(7.5)
13(7.5)
9(7.5)
25

26(7.5)
17(7.5)
13(7.5)
9(7.5)
30

200

operations/hour
VA
VA
W

1800

50(15)
40(18.5)
32(18.5)
17(15)
80

5
300

500

1800

1800

670
1200

60
10
3

110
13
45

M4
M3.5

M5
M3.5

M4
M3.5

M5
M3.5

1~6
1~2.5

2~16
1~2.5
UN-AX2 or UN-AX4

n Outline Dimensions

n Contact Arrangement
2 mtg. holes for M4 screws
M3.5 screw

a)

4 mtg. holes for M4 screws


M3.5 screw

P screw

BA

60

BB

13

1/L1 3/L2 5/L3

2/T1 4/T2 6/T3

S-No8

39(11)
32(15)
24(15)
12(11)
60
1

Additional auxiliary contact block

A2 A1

S-N48

10

Control terminal
Main terminal
Control terminal

Conductor size
(Compression terminal size)

S-N38
AC690

V
A(kW)
A(kW)
A(kW)
A(kW)
A
operations
(million)

220-240V
380-440V
500V
690V

S-N18

AB

CC

AA
A

30

5.5

23

79

S-N48

N38

30

M4 screw

96

10
5

109

S-2xN18, N28
5

M3.5 screw
3 mtg. holes for M4 screws

A2 A1 1/L1 3/L2 5/L3 53 61 71 83

2/T1 4/T2 6/T3 54 62 72 84

2/T1 4/T2 6/T3 54 62 72 84

S-2xNo8

11

100

120

110

A2 A1 1/L1 3/L2 5/L3 53 61 71 83

M5 screw

122

1.6
5

127

S-2xN38, N48
S-N18, N28
S-N38, N48

34

Fig.
a
a

A
43
54

B
79
90

C
81
93

AA
30
40

AB
7
7

BB
60
80

BA
6
6

CC CA
10 109
7 121

D
4
4

Q Wt(kg)
P
M4 M3.5 0.33
M5 M3.5 0.4

T
5
5

Series SD-M

34 DC Interface Contactors

The MITSUBISHI series SD-M contactors are specially designed to be directly driven by the
transistor output (DC24V) of a programmable sequence controller, etc.

n Features
SD-M11

Low coil power consumption: By combining an electromagnet with permanent magnet, coil
operating current is reduced to DC24V 60mA (1.5W) for SD-M11, M12 and 75mA (1.8W) for
SD-M19.
Compact construction: Width 45mm, Height 48mm, Depth 61mm in Type SD-M11
Mountable on 35mm DIN rails Operating indicator (LED)
Coil surge absorber Bifurcated auxiliary moving contacts having high contact reliability
Safety clear terminal cover
Easy wiring: All terminals are in the same plane
Integrated reversing contactor with mechanical and electrical interlock

SD-M12

SD-MR12
Type Designation

Non-reversing types
11

SD M

Reversing type

* DC24V *

SD - MR12
SD - MR19

AUXILIARY CONTACT ARRANGEMENT

FRAME SIZE

* Standard type: SD-M11 with 1NO, SD-M12/M19 with 1NO1NC


1B Special type: SD-M11 with 1NC
2A Special type: SD-M12/M19 with 2NO

11 With 1 auxiliary contact


12 With 2 auxiliary contacts
19 With 2 auxiliary contacts

n Contact Arrangement &


Wiring Diagram

Note: Mark * indicates a blank space.

n Specifications

Type

Ratings & characteristics

Category
AC3

200-240VAC
380-440VAC

Category
AC1

200-440VAC

Rated continuous current


Rated
operating
current
Rated 3ph
motor
capacity
Coil voltage

Table 341

SD
V
A
A
A

Category
(IEC)
AC3
tolerance

200-240VAC
380-440VAC

M11,M12,MR12 M19,MR19
660
660
20
15
18
12
13
9

mm2

2/T1 4/T2 6/T3 14

Nonreversing
SD-M12
SD-M19

A1/a
(+)

1/L1 3/L2 5/L3 21

2/T1 4/T2 6/T3 22

A2/b
()

A2/b
()

Aux. 1NO1NC

Aux. 2NO

A1/a
13 1/L1 3/L2 5/L3 21 (+)

A1/a
13 1/L1 3/L2 5/L3 23 (+)

14 2/T1 4/T2 6/T3 22


A2/b
()

14 2/T1 4/T2 6/T3 24


A2/b
()

AUX. 1NO1NCX2
SD-MR12

85-110

(+)

(+)

21

13

3/L2 5/L3

1/L1 3/L2 5/L3 13

21

22

14 2/T1 4/T2 6/T3

2/T1 4/T2 6/T3 14

22

A1/a
(+)

A2/b
()

1.8
75

A1/a
(+)

()

Reversing

AUX. 1NO1NCX2

<60

()

SD-MR19

<35

(+)
21

(+)
3/L2 5/L3

22 2/T1 4/T2 6/T3

10 million

13

13

1/L1 3/L2 5/L3 21

14

14

2/T1 4/T2 6/T3 22

A1/a
(+)

A2/b
()

()

2 million
0.5 million
-10 to 55

Note: Coil terminal have polarity.

n Outline Dimensions

1800

Mtg. hole for M4 screws


M3.5 screws

1 to 6 (Main)
1 to 2.5 (Control)

B
a

1 to 2.5

SD-M11

()

%
85-110
Coil consumption
W
1.5
mA
60
Coil current
Make
mS
<50
Operating times
Break
<20
mS
Mechanical life
operations 10 million
Category AC3 operations 1 million
Electrical life
Category AC1 operations 0.5 million
Permissible ambient temperature
C
-10 to 55
operaSwitching frequency
1800
tions/hour
Conductor size

1/L1 3/L2 5/L3 13

4.5
5.5

3
4

kW
kW

Aux. 1NC

Aux. 1NO

20

15

Table 343
Special

Standard

Type
Rated insulation voltage

* DC24V
* DC24V

Ratings of auxiliary contacts


V

Rated insulation voltage

Rated
operating
current

440VAC

Small coil load(L/R=40mS) 24VDC


Resistive load
24VDC

Mechanical Endurance

operations

10 million

Electrical Endurance

operations

0.5 million

d
10

b
A

660

220VAC

Rated continuous current


Category
AC11

Table 342

(mm)

SD-M11

45

48 61 40 35

3 M3.5

0.2

SD-M12

54

48 61 40 35

3 M3.5

0.2

Wt(kg)

SD-MR12 109 63 62 50 86 6.5 11.5 5.5

4 M3.5 0.45

SD-M19

5.5 9

M4

0.34

SD-MR19 133 80 78 50 110 22 11.5 9

M4

0.73

66

58 77 50 55

35

Series UN/UA-SY

35 DC Interface Modules
The MITSUBISHI type UN/UA-SY interface module is an optional unit for S-N/K series contactors
or SR-N series relays, controlled by the transistor output of a programmable controller.

n Features
Easy mounting on the Type S-N10 to S-K65 contactors and SR-N series relays.
Separate mounting type for the Type S-K80 to S-K400 contactors.
Relay or solid state output versions are available.

Type Designation
UN-SY 1

APPLICABLE CONTACTOR OR RELAY


UN-SY2

S-N10 to N35, SR-N4

UA-SY3

S-K50 to 65
S-K80 to 400

UA-SY1

1
2

OUTPUT
Solid state relay output
Relay output

n Specifications
Type

Table 351
UN-SY21

Output

Applicable Type of
contactor or relay

Direct mounting
to contactor or
relay
Separate mounting

Rated control voltage


Input

UA-SY31

S-N10 to N35
S-K50, K65
S-N18, N28, N38,
N48

UA-SY32

S-K50, K65
S-N10 to N35
S-N18, N28, N38,
N48

S-K80 to K400

24Vdc

Min. working voltage

18Vdc

Max. breaking voltage

4Vdc

1Vdc

Power consumption

0.4W

0.24W

18Vdc

100Vac to 240Vac 50/60Hz


0.5A (category AC11)

Response time

11ms or less

OFF-state leakage current

3mA/240Vac

Mechanical life

5 million operations

Electrical life

Ambient temperature

UA-SY12

Relay

80% to 110% of rated control voltage

Rated operating current


Output

UN-SY22

24Vdc

Permissible voltage tolerance

Rated voltage

36

UA-SY11

Solid state relay

10ms or less

1 million operations
10 to 55C

S-K80 to K400

Connection
(2) Relay Output

(1) Solid State Output

DC interface module

DC interface module
100Vac
to
240Vac

100Vac
to
240Vac

A2

A1

A2

A1

MC

MC
A2(A3)

A2(A3)

A1

A1

D2(-)

Transistor
24Vdc

D2(-)

Magnetic contactor
Contactor reray

Transistor
24Vdc

D1(+)

Magnetic contactor
Contactor reray

Coil

D1(+)

UN-SY22(CX)

UN-SY21(CX)

Type UN-SY22

Type UN-SY21
100Vac
to
240Vac

DC interface module
A3

100Vac
to
240Vac

DC interface module

A2

A3

A2

MC

MC
A1

D2(-)

D2()

Magnetic contactor
Contactor reray

Transistor
24Vdc

A1

A1

A1

Magnetic contactor
Contactor reray

Coil

Transistor
24Vdc
D1(+)

D1(+)

Type UA-SY11/31

Type UA-SY12/32

n Mounting

Direct mounting Type S-N10 to S-K65 and SR-N4


Remove the coil terminal screw from the contactor or relay, then slide the tab on the interface module to the groove on the
contactor or relay. Fasten the connecting conductor with the coil terminal screw.
Separate mounting Type S-K80 to S-K400
Mount the interface module (UA-SY11/12) with screw on a panel as follows.

n Outline Dimensions
Type Number

UN-SY21/22

10

UA-SY11/12

UA-SY-31/32

8
5

30.5
39

44

M3.5 screw
4.5 mtg. hole

39

42

43

63(75/154)

20
30
S-N12
SR-N5

78

S-N20
S-N21
S-N25
S-N35
S-N38
S-N48

3.2 hole

(A2) (A1)

81(89)

S-N10
S-N11
SR-N4
SR-N8
S-N18
S-N28

78(79)

(A2) (A1)

2.5

24.5

24.5

M4 screw
(A2) (A1)

30.5
39

Mtg. hole layout for separate mounting

24.5

Coupling outline

Overall
Mounting
dimensions

39

30

8 21.5

44

23

Module
Outline
dimensions

34
44

53

37

4. RELAYS

Series SR-N

41 Contactor Relays

The MITSUBISHI series SR-N contactor relays are specially designed for use in low voltage
control circuit applications. Series SR-N have many superior features.

n Features
High reliability: By adopting bifurcated moving contacts and by improving the shape of the
contacts, contact performance has been made more reliable than ever.
Long life Mountable on 35mm DIN rails. Dust-proof construction
Easily visible coil ratings Easy wiring (self-rising terminal screws)
Various accessories common with the series S-N contactors
(Head-and side clip-on type additional aux. contact blocks, surge absorbers, safety covers)
Finger protected types are available (DIN 57106/VDE 0106 Part 100)

SR-N4

Type Designation

Standard types
SR

N4

LC

AC200V

CONTROL TYPE
SR
SRD

AC operated
DC operated

TYPE

JH

Standard type
Big capacity type

2A2B
COIL VOLTAGE2
See Table 412

CONTACT ARRANGEMENT (CODE)


See Table 415

Notes: 1. For latched type relays, JH and LC types cannot be available.


2. When ordering the latched type relays, please specify the closing coil and tripping coil voltage.
ex: SRL-N4 * MC-AC200V * MT-AC100V * 4A
closing coil tripping coil

Note: Mark * indicates a blank space.

38

n Specifications
Rating and characteristics

Table 411
SRSRD-

Type

N4
4NO (4A)
3NO+1NC (3A1B)
2NO+2NC (2A2B)

Available contact arrangements (code)

4NO (4A)
2NO+2NC (2A2B)

Rated insulation voltage

N4LC

N4JH

4NO (4A)
2NO+2NC (2A2B)

16

660
20

Category AC-15
(coil load)

110VAC
230VAC
440VAC
550VAC

A
A
A
A

6
5
3
3

10
10
5
4

Category AC-12
(resistive load)

110VAC
230VAC
440VAC
550VAC

A
A
A
A

16
12
5
5

20
16
10
10

Category DC-13
(large coil load)

24VDC
48VDC
110VDC
220VDC

A
A
A
A

5
3
0.8(2)1
0.2(0.8)1

3
2
0.5
0.1

24VDC
48VDC
110VDC
220VDC

A
A
A
A

8
3
2(4)1
0.4(1)1

5
2
1
0.2

24VDC
48VDC
110VDC
220VDC

A
A
A
A

10
8
5(8)1
1(3)1

8
5
3
0.5

lth

Rated continuous current


Rated operating current

Category DC-14

Category DC-12
(resistive load)
Mechanical life
Electrical life

Ac-operated

Inrush
Sealed
Watts

10 million (latched type 1 million)


0.5 million

C/%RH

-25 to +55/45 to 85

VA
VA
W

60
10
3

DC-operated

Watts

Coil voltage tolerance

times

Operating time
(average)

ms
ms

Make
Break

15
10

0.85 to 1.1 (rated coil voltage)


AC
50 DC
operated
10 operated

Switching frequency

operations
/hour

1,800

Vibration resistance
Shock resistance

g
g

2
5

mm2

1.0 to 2.5

10-55Hz
10 msec. half sine wave

Conductor size

(3)2
(3)2
(3)2
(3)2
16
12
5
5

Operations
Operations

Permissible ambient temperature/humidity


Coil consumption

16
6
5
3
3

Notes: 1. Parenthesized rated operating current is for switching the load in 2-pole series connection.
2. Parenthesized rated operating current is for switching of NC contact.

Coil voltage
Coil
designation
AC12V
AC24V
AC48V
AC100V
AC120V
AC127V
AC200V

Table 412
Rated voltage (AC)
50Hz

60Hz

12V
24V
48-50V
100V
110-120V
125-127V
200V

12V
24V
48-50V
100-110V
115-120V
127V
200-220V

Coil
designation
AC220V
AC230V
AC260V
AC380V
AC400V
AC440V
AC500V

Rated voltage (AC)


50Hz

60Hz

208-220V
220-240V
240-260V
346-380V
380-415V
415-440V
500V

220V
230-240V
260-280V
380V
400-440V
460-480V
500-550V

Coil
designation
DC24V
DC48V
DC100V
DC110V
DC125V
DC200V
DC220V

Rated
voltage (DC)
24VDC
48VDC
100VDC
110VDC
120-125VDC
200VDC
220VDC

Note: AC operated coils are the same as those of S-N10 etc, and DC operated coils are the same as those of SD-N11 etc.

39

n Auxiliary Contact Blocks


Type Designation

Front clip-on types


UN-AX

2A2B

POLES
4
2

CONTACT
ARRANGEMENTS

4 pole
2 pole

See Table 414

Note: Mark * indicates a blank space.

Ratings and characteristics

Table 413

Type

UN-

Applicable contact arrangements

AX4

AX11

4NO
3NO+1NC
2NO+2NC

INO+INC

LL22
1NO+1NC
[Standard]

1NO+1NC1
[Low level]

690

250

16

Category AC-15
(coil load)

110VAC
220VAC
440VAC

A
A
A

6
5
3

Category DC-13
(large coil load)

48VDC
110VDC
220VD

A
A
A

3
0.8
0.2

1
240VAC 20mA
(COS 0.95)
48VDC 100mA
(L/R 1msec)
Minimum
operating current
5VDC 5mA

Rated insulation voltage


lth

Rated continuous current


Rated
operating
current

AX2
2NO
1NO+1NC
2NC

Mechanical life
Electrical life

10 million
0.5 million

operations
operations

2.5 million
0.5 million

Permissible ambient temperature/humidity

C / %RH

25 to +55/45 to 85

Switching frequency

operations
/hour

1,800

mm

1.0 to 2.5

Conductor size

Notes: 1. Contact reliability may be decreased if it is operated more than 1 million operations.

Selection guide & contact arrangements


UN-AX2 2A

Front
clip-on
types

53

54

2NO
UN-AX4 4A

53

63

UN-AX2 1A1B

63

64

73

51

1NO+1NC
83

UN-AX4 3A1B

Table 414

53

52

61

UN-AX2 2B

63

64

73

51

52

2NC
83

UN-AX4 2A2B

53

61

UN-LL22

61

53

63

71

81

54

64

72

82

62

71

83
standard
low level

4NO

54

64

74

84

3NO+1NC

54

62

74

84

2NO+2NC

54

62

72

84

UN-AX11

Side
clip-on
types
1NO+INC

53

61

54

62

When mount on right side

Notes: Front clip-on types and side clip-on contact block should not be mounted both.
40

83

71

84

72

When mount on left side

1NO+1NC, 1NO+1NC

n Contact Arrangements of Contactor Relay

Table 415

With standard contacts


4NO
A2 A1 13

23

33

43

14

24

34

44

V 4A
V 4A

3NO
+
1NC

A2 A1 13

21

33

43

14

22

34

44

V 3A1B
V 3A1B

A2 A1 13

21

31

43

14

22

32

44

13

21

31

43

14

22

32

44

13

21

31

43

14

22

32

44

V 2A2B
V 2A2B

SR-N4 AC
SRD-N4 DC

SR-N4 AC
SRD-N4 DC

2NO
+
2NC

SR-N4 AC
SRD-N4 DC

With big capacity contacts


4NO
A2 A1

13

23

33

43

14

24

34

44

2NO
+
2NC

V 4A
V 4A

A2 A1

V 2A2B
V 2A2B

SR-N4JH AC
SRD-N4JH DC

SR-N4JH AC
SRD-N4JH DC

With late break contacts


3NO
+
1NC

A2 A1

13

21

33

43

(late break)

2NO
+
2NC

A2 A1

(late break)

14

22

34

44

V 2A2B
V 2A2B

V 3A1B
V 3A1B

SR-N4LC AC
SRD-N4LC DC

SR-N4LC AC
SRD-N4LC DC
With mechanical latching

23

33

43

55

E1

MC
14

24

34

V 4A
V 4A

SRL-N4 AC
SRLD-N4 DC

44

56

MT
E2

A2 A1

13

21

33

43

14

22

34

44

55

E1

MC

V 3A1B
V 3A1B

SRL-N4 AC
SRLD-N4 DC

56

MT
E2

CLOSING
A2 A1

13

21

31

43

14

22

32

44

55

E1

MC

V 2A2B
V 2A2B

56

MT

TRIPPING

13

TRIPPING

A2 A1

2NO
+
2NC

CLOSING

TRIPPING

3NO
+
1NC

CLOSING

E2

SRL-N4 AC
SRLD-N4 DC

41

n Spare Coils & Accessories

Spare coils and accessories are common with the series S-N contactors.
Spare coils ..............................................................................................See page 12 (except for Type SRL(D)latched relays)
Surge absorbers(suppressors) ................................................................................................................................See page 14

n Outline Dimensions
2 mtg holes for M4 screws

Key to Dimensions

M3.5 screws

19

Model

C1

C2

Wt(kg)

SR-N4

78

106

0.3

SRD-N4

110

138

0.62

SRL-N4
SRLD-N4

134

0.45

78

50

Top Hat
rail (35mm)

4
4.5
13.5

35
C1

43
70
(with side clip-on aux.
contact blocks)

10

C2
(with front clip-on aux.
contact block)

Note: Front clip-on and side clip-on contact block should not both be mounted.

42

4.2 Pneumatic Time Delay Relays


Type UA-TR pneumatic time delay modules are designed for attachment to series S-K
contactors and SR-K contactor relays.
Type Designation
UN TR4

AN

TYPE OF DELAY
AN

ON

UN-TR4AN

Applicable contactor and relay selection


Type

Type of delay

UN-TR4AN

ON delay

Table 421
Applicable contactors and relays

AC operated

S-N10, N11, N18


SR-N4(oo)

DC operated

SD-N11
SRD-N4(oo)

Note: When this module is mounted, aux. contact block should not be mounted.

n Contact arrangement

Ratings & characteristics


.......................... See delayed contacts of Table 471

ON-delay

67

55

68

56

Note: 55-56 Delayed NC contacts


67-68 Delayed NO contacts

UN-TR4AN

n Outline Dimensions
2-mtg. holes for
M4 screws

Adjustment dial

M3.5 screws

4
35
45

Manual test button

45

50
78

M3.5 screws

10

45

4.5
1

43

n 4.2 Pneumatic Time Delay Relays


Ratings & characteristics
Adjustable delay time range

sec.

Type of contacts
Rated continuous current
Rated
category
operating
current
AC-15
category
AC-12
category
DC-13
category
DC-12

Ith
110VAC
220VAC
440VAC
550VAC
110VAC
220VAC
440VAC
550VAC
24VDC
48VDC
110VDC
220VDC
24VDC
48VDC
110VDC
220VDC

Rated insulation voltage

A
A
A
A
A
A
A
A
A

10

16

5
3
1
1
6
4
1.5
1.5
1
0.5
0.3
0.15
2
1
0.6
0.3

6
5
3
3
16
12
5
5
5
3
0.8
0.2
10
8
5
1

A
A
A
A
A
A
A
A
VAC

660

operations

1 million

Electrical life

operations
%

Min. pause time


Min. energizing time

AC operated
DC operated
Permissible ambient temperature
Control coil voltage tolerance
Make and break capacity
(at rated operating current)
Average
operating
times

Make
AC
operated Break

Coil
consumption

AC
Inrush
operated Sealed
DC operated

AC
DC

DC
Make
operated Break

Switching frequency
Vibration resistance
10-55Hz
Shock resistance 10msec. half sine wave
Conductor size

1 million

0.5 million
10
500
15
30

msec.
msec.
msec.

Table 423

0.1 to 60
Instantaneous

Delayed

Mechanical life
Repeat accuracy

44

Table 422

5 to 55

85 to 110

times
times
msec.
msec.
msec.
msec.
VA
VA

11
2

11
10

45
10
50
10

operations
/hour

1,800

g
g
mm2

2
5
1.0 to 2.5

ON-delay
67
(37)

55
(25)

68
(38)

56
(26)

A1/a

13

21

31

43

A2/b

14

22

32

44

Notes: 1. 13-14,43-44 Instantaneous NO contacts.


21-22, 31-32 Instantaneous NC contacts.
25-26, 55-56 Delayed NC contacts.
37-38, 67-68 Delayed NO contacts.

TYPE REFERENCE LIST


Type

Description

Ref.Page

DU(D)-o

DC contactors

28

ET-No

Electronic motor protection relays

25

MS-N/Ko

General purpose enclosed type motor starters

MS-2XN/Ko

General purpose enclosed and reversing type motor starters

1~
5

MSO(D)-N/Ko

General purpose open type motor starters

MSO(D)-2XN/Ko

General purpose open and reversing type motor starters

S-No8

Compact 3-pole contactors

34

S(D)-N/Ko

General purpose contactors

SD-Mo

DC interface contactors

1~
35

S(D)-2XN/Ko

General purpose reversing contactors

SH(L)(D)-Vo

Medium voltage vacuum contactors

31

SH(L)(D)-2XVo

Medium voltage reversing vacuum contactors

31

SL(D)-N/Ko

Mechanically latched contactors

SL(D)-2XN/Ko

Mechanically latched reversing contactors

SR(D)-N/Ko

Contactor relays

38

TH-N/Ko

Thermal overload relays

19

UN/UA-AXo

Auxiliary contact blocks

13, 29, 40

UN/UA-CVo

Safety cover

13, 23

UN-HZo

Separate mounting adaptor for TH-N12

23

UN/UA-MLo

Mechanical interlocks

13

UN/UA-RRo

Reset release for TH-K

23

UN/UA-SAo

Surge absorbers for S-N/K and SR-N/K

13

UA-SUo

Surge absorbers for SH-V

32

UN/UA-SYo

DC interface modules for S-K

14

UN-TRo

Pneumatic time delay modules

14, 43, 44

NOTES

NOTES

Corporate Headquarters
Mitsubishi Electric Automation, Inc.
500 Corporate Woods Parkway
Vernon Hills, Illinois 60061
Phn: (847) 478-2100
Fax: (847) 478-2253
www.meau.com

Mitsubishi Electric Automation, Inc.


4299 14th Avenue
Markham, Ontario L3R 0J2
Phn: (905) 475-7728
Fax: (905) 475-7935

1999 Mitsubishi Electric Automation, Inc.

L-VH-10001
August 1999