HECS 2 | ABB G Technical Data Generator circuit-breaker system type HECS-80 HECS-130 General Rated maximum voltage kV 23.0 25.3 25.3 Rated frequency Hz 50/60 50/60 50/60 Rated continuous current 50 Hz (HECS-S) A rms up to 8500 (HECS-M) A rms up to 10500 up to 10500 (HECS-L) A rms up to 13000 up to 13000 (HECS-Lplus) A rms up to 14500 up to 14500 Rated continuous current 60 Hz (HECS-S) A rms up to 8000 (HECS-M) A rms up to 10000 up to 10000 (HECS-L) A rms up to 12000 up to 12000 (HECS-Lplus) A rms up to 13500 up to 13500 Rated insulation level Rated power frequency withstand voltage to earth and across circuit-breaker/switch contacts kV rms 60 (80) 60 (80) 60 (80) across isolating distance of disconnector kV rms 70 (88) 70 (88) 70 (88) Rated lightning impulse withstand voltage to earth and across circuit-breaker/switch contacts kV peak 125 (150) 125 (150) 125 (150) across isolating distance of disconnector kV peak 145 (165) 145 (165) 145 (165) Circuit-breaker Rated peak withstand current kA peak 220 300 360 Rated short-time withstand current kA, 3s 80 100 130 Rated short-circuit making current kA peak 220 300 360 Rated short-circuit breaking current kA rms 80 100 130 Rated operating sequence CO - 30min - CO Opening time ms 34 5 34 5 34 5 Rated interrupting time ms 68 68 68 Mechanical endurance life CO 20000 20000 20000 Disconnector Rated peak withstand current kA peak 220 300 360 Rated short-time withstand current kA, 3s 80 100 130 Operating time s 2 2 2 Earthing Switch Rated peak withstand current kA peak 220 300 360 Rated short-time withstand current kA, 1s 80 100 130 Operating time s 2 2 2 The above data are not limiting values. Additional data on request. We reserve the right to alter data and technical details without notice. HECS-100 Equipment Options 1 Generator circuit-breaker 2 Line disconnect switch 3 Earthing switch 4 Starting switch for SFC connection 5 Manual short-circuiting connection 6 Surge capacitor 7 Current transformers 8 Voltage transformers 9 Surge arrester 10 Motor-operated short circuiting link 7 8 6 3 4 1 2 7 5 3 6 9 8 (only with generator side earthing switch) (by removal of cover) 10 ABB | 3 Dimension Drawing HECS-S / HECS-M 870 m i n .
2 2 1 0 3 4 7 0
* ) 2 2 7 0 3 0 0 0
* ) 1000 *) 1700 N(1100-1800) N(1100-1800) 610 400 *) 3710 + 2N *) Transformer Side Generator Side N = Phase distance (Standard: 1200mm / 1400mm) *) min. space required for erection and maintenance 1 3 5 0 - 1 5 0 0 4 | ABB Dimension Drawing HECS-L 870 m i n .
2 3 3 0 3 4 7 0
* ) 2 2 7 0 3 0 0 0
* ) 1000 *) 1700 N(1200-1800) N(1200-1800) 610 400 *) 3710 + 2N *) Transformer Side Generator Side N = Phase distance (Standard: 1200mm / 1400mm) *) min. space required for erection and maintenance 1 3 5 0 - 1 5 0 0 ABB | 5 Dimension Drawing HECS-Lplus 870 m i n .
2 4 0 5 3 4 7 0
* ) 2 2 7 0 3 0 0 0
* ) 1000 *) 1700 N(1200-1800) N(1200-1800) 610 400 *) 3710 + 2N *) Transformer Side Generator Side N = Phase distance (Standard: 1200mm / 1400mm) *) min. space required for erection and maintenance 1 3 5 0 - 1 5 0 0 ABB Switzerland Ltd High Voltage Products Brown Boveri Strasse 5 CH-8050 Zurich / Switzerland Phone: +41 58 588 34 24 Fax: +41 58 588 16 44 www.abb.com/gcb Contact us
2014 04 14 Veterinary Instrumentation Presented The Simon Award 2014 For Outstanding Contribution in The Field of Veterinary Surgery To Michael Guilliard MA, VetMB, CertSAO, FRCVS