One (1) No. Digital multifuction meter with RS-485 port for
measurement of voltages, currents, powerfactor,
frequency, power (kVA, kVAR, kW) and energy (kVAH,
kVARH, KWH).
One (1) set of IDMTL over current and earth fault relay
complete with set of 15VA, class 5 P 10 cast resin CT of
ratio 100/5A with high set instantaneous earth fault and
O/C relay (CDG-61 of Areva or equivalent).
Setting Range
Notes :
1 Any other components not specifically mentioned but
required for trouble free operation shall be included.
Rating : 1000KVA
Cable Arrangement: -
SCHEDULE OF QUANTITIES
P & C FOR LIVING QUARTERS AT BHOGAT, GUJARAT (INDIA) PROJECT
Notes :
1 Before quoting the prices for the job and designing the
Transformer, Vendor/Contractor has to survey the site
conditions.
2 Space for fixing of cast resin CT of 1600/1 A on neutral
terminal shall be left. Cost of CT not to be included.
However the CT shall be fixed by manufacturer on the
terminal on supply of same by the contractor.
E 3.1.1 Underground:
Set 1
E 4.2 Design, manufacture, assembly & supply, installation,
testing and commissioning of suitable float cum boost
battery charger and necessary distribution board with 6
Nos. 16A outgoing feeders, instrument panel, Amp, Volts
meter, interconnections etc. power supply 230 V, 1 phase,
50 Hz ± 10%. Charger trouble annunciation shall be
provided through potential free contacts.
Set 1
TOTAL OF BATTERY & BATTERY CHARGER CARRIED
OVER TO SUMMARY
E 5.0 SUB STATION SAFETY EQUIPMENT :
E 5.1 Supplying and fixing 1000 mm x 900 mm wide checkered
rubber matting conforming to IS 15652-2006 complete as
required.
SCHEDULE OF QUANTITIES
P & C FOR LIVING QUARTERS AT BHOGAT, GUJARAT (INDIA) PROJECT
E 6.0 DG SET :
Notes :
Exhaust Piping :
Set 2
E 6.2.2 Fuel Oil Piping :
Supply, installation, testing and commissioning of medium
class MS piping conforming to IS-1239 for fuel piping
complete with all necessary fittings and valves between
day oil storage tanks and DG sets/priming motor including
jointing of pipes, painting with 2 coats of red oxide and two
coats of enamel paint.
a) 20 mm dia RM 15
b) 25 mm dia RM 15
NOTES :
1 The BOQ shall be read inconjunction with general notes,
specification and Single Line Diagram (attached for Ref.).
Incase of any discrepancy between specification, BOQ and
SLD, the same shall be brought to the notice of
Client/Consultant before quoting the rates, otherwise
stringent condition shall be deemed to have been
considered.
20. All bus bar shall be insulated with coloured PVC Sleeve i.e.
RYB,BK as per colour code.
21 Internal wiring of panel shall be with size 2.5sqmm Flexible
Copper Conductor for CT circuit and control wiring with 1.5
sqmm.
22 All Lift Panels transport section should not be more then
1000 mm.
23 In soft starter Vender should supply power contactor with
aux. Contactor & All necessary accessories required etc .
(As per BOQ & specification )
c) One (1) No. under voltage (CDG-13) and one no. over
voltage relay (CDG-11) with 415 /110V, 100 VA / phasePT
& Control MCB in incoming and outgoing side of PT.
Any Auxiliary relay if required shall be provided with in the scope of item.
Required interlock should be provided so that transformer and DG supply are not paralleled.
viii) Busbar :
1600A, 50kA TPN Cu. Bustbar insulated with heat
shrinkable sleeves and shall be colour coded.
Notes:
1 Each capacitor bank should have its individual MCCB &
Contactor suitable for capacitor duty including fuses for
each capacitor unit.
2 Enclosure of capacitor panel shall be liberally designed to
take care of internal heat emission by capacitor unit without
forced cooling and to limit the temperature rise with in
permissible limit. However, louvers are allowed to facilitate
extra cooling.
Outgoing :
- All outgoing shall be 35KA breaking capacity and shall be
provided with ON/OFFTrip indication lamps.
Busbar :
500A TPN Cu busbar.
Outgoing :
SCHEDULE OF QUANTITIES
P & C FOR LIVING QUARTERS AT BHOGAT, GUJARAT (INDIA) PROJECT
Outgoing:-
- Three (3) Nos. 20A DP MCB (10KA) with 20A contactor
(AC-3 Cat with 230V control coil)
- Nine (9) Nos. 40A DP MCBs (10KA)
- Three (3) Nos. 63A TPN MCBs (10KA)
- Three (3) Nos. 24 hours double dial programmable time
switch on auto mode arrangement for Auto/Manual
Selection, A/M Selector switch ON/OFF push buttons
indication lamps and control MCB etc as required.
Set 4
E 7.6 Distribution Board
MCB distribution board double door type pre-wired
complete with din rail, top and bottom grand plates, knock
outs, separate neutral and earth terminal for each phase as
required comprising of following:-
SCHEDULE OF QUANTITIES
P & C FOR LIVING QUARTERS AT BHOGAT, GUJARAT (INDIA) PROJECT
b) Bus Bar
100A TPN Cu. Busbar.
(The rate for point wiring (using 2.5 Sqmm 1100 V grade
FR PVC insulated copper wires) shall include the circuit
wiring (using 2 Nos. 2.5 Sqmm & 1 No. 2.5 (for earth),
1100 V grade FR PVC insulated copper wires) from the
DB/Dimmer panel up to the Junction box/ first light/fan/6 A
convenience socket outlet control switch on wards to light/
fan then the looping between switches /lights/fans/6 A
socket etc. The circuit wiring will not be paid separately.
However where the lights are controlled directly from DB
without local control switch, the quoted rates shall not
include cost of switches/MCB etc.
SCHEDULE OF QUANTITIES
P & C FOR LIVING QUARTERS AT BHOGAT, GUJARAT (INDIA) PROJECT
Wiring for a call bell and buzzer point with 2.5 Sqmm PVC
insulated copper conductor wires in recessed/ surface MS
conduit including providing, fixing suitable size of GI box,
bell push with PVC insulated 2.5 Sqmm copper conductor
wire for earthing, cutting, filling chases, providing saddles
including circuit wiring complete with all accessories as
required.
Point 50
E 9.2 Power Socket Wiring
SCHEDULE OF QUANTITIES
P & C FOR LIVING QUARTERS AT BHOGAT, GUJARAT (INDIA) PROJECT
E 9.4 Conduits
E 9.3.3 Same as Item No. 9.3.1 but in Polycarbonate enclosure
with IP-66 Protection.
a) 32A 3 Pin Socket with 32A DP MCB. Nos. 12
Supply and installation of following size of PVC conduit
pipe in recess or on surface including all accessories
MS/CI pull/junction boxes, GI fish wire, fixing hardware etc
including chasing the walls/floor and plastering the chased
portion and making good the damages etc, complete as
required.
25 mm dia
a) RM 275
32 mm dia
b) RM 100
E 9.5 Sub-mains Wiring
Supply and drawing of following sizes of FR PVC insulated
stranded copper conductor wires of 650/1100 Volts grade
in existing conduit pipe /wire ways including connection
/terminations etc as required.
a) 100x50x2mm thick RM 50
Notes :
1)
In false ceiling areas the work is to be co-ordinate with
respect to ID work and rate for point wiring shall include
flexible conduit/fixing nipples/couplers etc from the junction
box up to the fitting.
.
2)
Point on the same switch board shall include providing and
fixing 3 pin 6A switch socket outlet including connection
from the same switch board.
.
TOTAL OF WIRING CARRIED OVER TO SUMMARY
NOTE
1 Running meters (RM) for the cable/conduit is approximate. The contractor shall measure the running
meter (RM) & procurement order shall be placed accordingly. The quantities shall be confirmed before
start of work to the Engineer-In charge.
2 The scope includes the designing of the cable TV network for the Living Quarters. Above quantities are
approx. and one to be adjusted as per the requirements. Bidders may quote any left over item which is
required but not included above.
GENERAL NOTES
1. All the shop drawings, fabrication drawings, drawings for supports and cable laying alongwith cable tray
& conduit etc shall be prepared by the contractor & prior approval shall be taken for the construction of
Electrical Works.
SCHEDULE OF QUANTITIES
P & C FOR LIVING QUARTERS AT BHOGAT, GUJARAT (INDIA) PROJECT
AMOUNT (Rs.)
S.NO. DESCRIPTION
Supply Erection
1.0 6.6 KV SWITCHGEAR:
2.0 TRANSFORMER:
3.0 H T CABLING :
4.0 BATTERY & BATTERY CHARGER :
5.0 SUB STATION SAFETY EQUIPMENT :
6.0 DG SET :
7.0 M.V. SWITCH GEARS & DISTRIBUTION BOARDS:
8.0 CABLES, SUB MAINS & CABLE TRAYS:
9.0 WIRING :
10.0 LIGHTING FIXTURES & FANS:
11.0 EARTHING & LIGHTNING PROTECTION :
CONDUITING CABLING & WIRING FOR COMPUTER
12.0
DATA/IP TELEPHONE :
13.0 CONDUITING, CABLING & WIRING FOR TV SYSTEM :
TOTAL
Grand Total (Supply + Erection)