Sie sind auf Seite 1von 56

SCHEDULE OF QUANTITIES

P & C FOR LIVING QUARTERS AT BHOGAT, GUJARAT (INDIA) PROJECT

Contract No: RJ9TA1000009029 Revision No: C1 Date: 28.07.2009 Page No: 1


Unit Price in Indian Rupees
Item. Amount
Description Unit Qty Rate (Rs) Amount
No. (In Figures)
(In Words)
Supply Erection Supply Erection
ELECTRICAL

E1.0 6.6 KV SWITCHGEAR:

E 1.1 Design, manufacture, supply, installation, testing and


commissioning of 6.6 KV, 350 MVA, single panel, indoor,
sheet steel, floor mounted, dust, damp and vermin proof
horizontal draw out, vertical isolation, extendable on either
side fully interlocked, complete with motorized spring
closing mechanism vacuum circuit breaker panel. The
panel shall be fabricated out of 14 gauge CRCA sheet.
Sheet steel components shall be chemically pretreated by
7 tank process and powder coated with minimum coat
thickness of 60 microns. The bus bar shall be of
rectangular cross section Electrolytic copper with heat
shrinkable coloured PVC sleeve. Incoming and outgoing
feeders shall have provision for termination of 6.6 KV,
XLPE cables. The panel shall be supplied complete with
machined base frame and foundation bolts, hand closing
mechanism conforming to latest Indian standard
specification and as per single line diagram enclosed
/specified here under.
SCHEDULE OF QUANTITIES
P & C FOR LIVING QUARTERS AT BHOGAT, GUJARAT (INDIA) PROJECT

Contract No: RJ9TA1000009029 Revision No: C1 Date: 28.07.2009 Page No: 2


Unit Price in Indian Rupees
Item. Amount
Description Unit Qty Rate (Rs) Amount
No. (In Figures)
(In Words)
Supply Erection Supply Erection
E 1.1.1 Incoming/outgoing Supply :

1 No. 6.6 KV, 630A, 350 MVA, Vertical isolation, horizontal


draw out, electrically spring charge closing mechanism,
VCB complete with anti pumping and trip free mechanism 6
Nos. of auxiliary switch contacts. The incoming/outgoing
breaker shall be suitable for receiving. 6.6 KV,
3Cx300Sqmm, Copper, Armoured XLPE cable at incoming
and busbar termination on outgoing side.

One (1) Set of 630A, TP Copper bus bar with heat


shrinkable colour coaded PVC sleeve.

One (1) No. Trip-Neutral-close switch.

One (1) No. Digital multifuction meter with RS-485 port for
measurement of voltages, currents, powerfactor,
frequency, power (kVA, kVAR, kW) and energy (kVAH,
kVARH, KWH).

One (1) Set of PT 6.6 kV / √3/110V/√3, 100VA burden,


class 1.0, with control fuses.

One (1) Set of CTs 100/5A, Class 1.0, 15VA.


SCHEDULE OF QUANTITIES
P & C FOR LIVING QUARTERS AT BHOGAT, GUJARAT (INDIA) PROJECT

Contract No: RJ9TA1000009029 Revision No: C1 Date: 28.07.2009 Page No: 3


Unit Price in Indian Rupees
Item. Amount
Description Unit Qty Rate (Rs) Amount
No. (In Figures)
(In Words)
Supply Erection Supply Erection

One (1) set of IDMTL over current and earth fault relay
complete with set of 15VA, class 5 P 10 cast resin CT of
ratio 100/5A with high set instantaneous earth fault and
O/C relay (CDG-61 of Areva or equivalent).

Setting Range

IDMTL O/C - 50 - 200%


IDMTL E/F - 10 - 40%
H.S. O/C - 500 - 2000%
INST. E/F - 10 - 40%

One (1) No. VAJH13 master trip relay.

One (1) No. Trip Circuit supervision - relay.

One (1) Set of Aux. relay for transformer fault.

Indication Lamp (LED Type)

One (1) set of Phase indication lamps.

One (1) No. circuit breaker ON.

One (1) No. circuit breaker OFF.


SCHEDULE OF QUANTITIES
P & C FOR LIVING QUARTERS AT BHOGAT, GUJARAT (INDIA) PROJECT

Contract No: RJ9TA1000009029 Revision No: C1 Date: 28.07.2009 Page No: 4


Unit Price in Indian Rupees
Item. Amount
Description Unit Qty Rate (Rs) Amount
No. (In Figures)
(In Words)
Supply Erection Supply Erection
One (1) No. Auto Trip

One (1) No. Spring charge.

One (1) No. Trip circuit healthy.

One (1) Set of 4 window audio / visual alarm anunciator


system for fault on incoming and out going feeders with Set 1
accept/acknowledge push button and associated wiring.

Notes :
1 Any other components not specifically mentioned but
required for trouble free operation shall be included.

2 Before quoting the rate and designing the Panel,


Vendor/Conductor has to survey the site conditions.

TOTAL OF 6.6 KV SWITCHGEAR CARRIED OVER TO


SUMMARY
SCHEDULE OF QUANTITIES
P & C FOR LIVING QUARTERS AT BHOGAT, GUJARAT (INDIA) PROJECT

Contract No: RJ9TA1000009029 Revision No: C1 Date: 28.07.2009 Page No: 5


Unit Price in Indian Rupees
Item. Amount
Description Unit Qty Rate (Rs) Amount
No. (In Figures)
(In Words)
Supply Erection Supply Erection
E 2.0 TRANSFORMER:

Design, manufacture, supply, installation, testing and


commissioning of 6.6/0.433KV, 50 HzDelta – star DYn11
natural air cooled, double wound, copper winding, indoor
cast resin, dry type transformer with all accessories
conforming to relavant IS and as detailed here under: -

Rating : 1000KVA

Voltage Ratio : 6.6/. 433KV

Tap Capacity Range : +5% to (-) 7.5% in 2.5% steps

Accessories :As Per IS and the specification

Percentage Impedance : As Per IS

Temp Scanner : To be provided.

Cable Arrangement: -
SCHEDULE OF QUANTITIES
P & C FOR LIVING QUARTERS AT BHOGAT, GUJARAT (INDIA) PROJECT

Contract No: RJ9TA1000009029 Revision No: C1 Date: 28.07.2009 Page No: 6


Unit Price in Indian Rupees
Item. Amount
Description Unit Qty Rate (Rs) Amount
No. (In Figures)
(In Words)
Supply Erection Supply Erection
H.T. : 1No. 6.6KV,
1RX3CX300 Sqmm,
copper Armoured,
XLPE Cable

L.T : Cables Set 1

Notes :

1 Before quoting the prices for the job and designing the
Transformer, Vendor/Contractor has to survey the site
conditions.
2 Space for fixing of cast resin CT of 1600/1 A on neutral
terminal shall be left. Cost of CT not to be included.
However the CT shall be fixed by manufacturer on the
terminal on supply of same by the contractor.

TOTAL OF TRANSFORMER CARRIED OVER TO


SUMMARY
E 3.0 H T CABLING :

E 3.1 Cable laying :


SCHEDULE OF QUANTITIES
P & C FOR LIVING QUARTERS AT BHOGAT, GUJARAT (INDIA) PROJECT

Contract No: RJ9TA1000009029 Revision No: C1 Date: 28.07.2009 Page No: 7


Unit Price in Indian Rupees
Item. Amount
Description Unit Qty Rate (Rs) Amount
No. (In Figures)
(In Words)
Supply Erection Supply Erection
Supplying, laying, testing and commissioning of 6.6 KV
grade copper conductor, cross linked polyethylene (XLPE)
insulated individual core screened, flat steel/strip armoured
PVC sheathed cable suitable for earthed system complete
as follows:

E 3.1.1 Underground:

a) Supply and laying in earth at 1200 mm deep below ground, RM 1000


trench cutting, 300 mm sand cushion, brick covering with
first class bricks, back filling with riddled earth reaming
compacting and disposal of extra soil / rubbish to a place
indicated by project manager etc as required.
3C x 300 Sqmm, 6.6KV XLPE

E 3.2 End Termination (HT) :


a) Cable jointing of 6.6 KV volts grade XLPE insulated
armoured cable with suitable cable termination using Set 3
RAYCHEM/Birla 3M/MECP KITS including all accessories
i.e. Sockets, lugs, gland etc as required.
3C x 300 Sqmm, 6.6KV XLPE Copper Cable

Note: Quantity mentioned in the BOQ are tentative, however


contractor has to measure it at site before ordering the
cable.
SCHEDULE OF QUANTITIES
P & C FOR LIVING QUARTERS AT BHOGAT, GUJARAT (INDIA) PROJECT

Contract No: RJ9TA1000009029 Revision No: C1 Date: 28.07.2009 Page No: 8


Unit Price in Indian Rupees
Item. Amount
Description Unit Qty Rate (Rs) Amount
No. (In Figures)
(In Words)
Supply Erection Supply Erection
TOTAL OF H.T CABLING CARRIED OVER TO
SUMMARY
E 4.0 BATTERY & BATTERY CHARGER :
E 4.1 Design, manufacture, assembly & supply, installation,
testing and commissioning of 120 AH, capacity 24 V DC Ni-
Cadmium maintenance free batteries duly charged
complete with connecting lead as required for MV Switch
Gear and some other control loads of owners.

Set 1
E 4.2 Design, manufacture, assembly & supply, installation,
testing and commissioning of suitable float cum boost
battery charger and necessary distribution board with 6
Nos. 16A outgoing feeders, instrument panel, Amp, Volts
meter, interconnections etc. power supply 230 V, 1 phase,
50 Hz ± 10%. Charger trouble annunciation shall be
provided through potential free contacts.

Set 1
TOTAL OF BATTERY & BATTERY CHARGER CARRIED
OVER TO SUMMARY
E 5.0 SUB STATION SAFETY EQUIPMENT :
E 5.1 Supplying and fixing 1000 mm x 900 mm wide checkered
rubber matting conforming to IS 15652-2006 complete as
required.
SCHEDULE OF QUANTITIES
P & C FOR LIVING QUARTERS AT BHOGAT, GUJARAT (INDIA) PROJECT

Contract No: RJ9TA1000009029 Revision No: C1 Date: 28.07.2009 Page No: 9


Unit Price in Indian Rupees
Item. Amount
Description Unit Qty Rate (Rs) Amount
No. (In Figures)
(In Words)
Supply Erection Supply Erection
a) 6.6 KV grade size 1000 x 900 x 25 mm thick Nos. 2
b) 1100 V grade size 1000 x 900 x 15 mm thick Nos. 3
E 5.2 Supplying & fixing standard shock treatment charts in
English & Hindi and local language duly framed and
covered with glass. Nos. 3
E 5.3 Providing & fixing HT danger notice plate 200 mm x 150
mm made of mild steel atleast 2mm thick & vitreous
enameled white on both sides and with inscription in signal
red colour with skull & bone on front side as required.
No. 1
E 5.4 Supplying and erection of the following equipment at
suitable locations in the substation building as required and
as per specifications.
a) 4 1/2 kg DCP fire extinguisher (conforming to IS:2171 with Nos. 4
cylinder fully charged).
b) 4 1/2 kg CO2 type fire extinguisher (conforming to IS- Nos. 4
2878).

E 5.5 Supplying and installing at approved location approved Set 2


make 4 nos. fire buckets of 24 gauge galvanized steel,
painted white inside and red outside and black on the
bottom, inscribed with letters ”FIRE” in black and gold
including stand fabricated out of sheet metal (16 gauge)
shade, platform and associated civil works, painting etc as
approved by fire authority.
SCHEDULE OF QUANTITIES
P & C FOR LIVING QUARTERS AT BHOGAT, GUJARAT (INDIA) PROJECT

Contract No: RJ9TA1000009029 Revision No: C1 Date: 28.07.2009 Page No: 10


Unit Price in Indian Rupees
Item. Amount
Description Unit Qty Rate (Rs) Amount
No. (In Figures)
(In Words)
Supply Erection Supply Erection
E 5.6 Providing 6.6 KV tested hand gloves. Pair 2
E 5.7 Providing 6.6 KV insulated grounding rod. No. 1
E 5.8 Providing first aid box as per IS:2217. Set 1
TOTAL OF SUB STATION SAFETY EQUIPMENT
CARRIED OVER TO SUMMARY

E 6.0 DG SET :

E 6.1 Design, manufacture, assembly, testing at works, supply,


erection & testing at site as per specifications complete in
all respect of DG Sets of KVA rating as specified below :
SCHEDULE OF QUANTITIES
P & C FOR LIVING QUARTERS AT BHOGAT, GUJARAT (INDIA) PROJECT

Contract No: RJ9TA1000009029 Revision No: C1 Date: 28.07.2009 Page No: 11


Unit Price in Indian Rupees
Item. Amount
Description Unit Qty Rate (Rs) Amount
No. (In Figures)
(In Words)
Supply Erection Supply Erection
415 Volts, 3 phase, 50 Hz, 1500 RPM AC alternator
coupled with radiator cooled, Diesel Engine complete with
all accessories, like self starting device, fly wheel coupling
with guard V belts, cooling system, instrument/ control
panel comprising of switch with key, battery charging
system, (including battery charger panel for charging
batteries when DG set is in idle condition) safety control for
lub oil pressure and high cooling water temperature with
alarm and tripping etc. The alternator insulation shall be
class 'H' with temperature rise limited to class 'F' value
suitable to with stand tropical conditions and shall generally
comply with BS 5000 and IS 4722. The over load capacity
shall not be less than 110% of rated capacity for 1 hour in
every 12 hours (test certificate for the same shall be
submitted before dispatch). 24 volt chargeable lead acid
battery to be tubular type, maintenance free and fully
sealed all complete with battery leads., CT of suitable ratio
SCHEDULE OF QUANTITIES
P & C FOR LIVING QUARTERS AT BHOGAT, GUJARAT (INDIA) PROJECT

Contract No: RJ9TA1000009029 Revision No: C1 Date: 28.07.2009 Page No: 12


Unit Price in Indian Rupees
Item. Amount
Description Unit Qty Rate (Rs) Amount
No. (In Figures)
(In Words)
Supply Erection Supply Erection
& Class PS accuracy for alternator protection for all three
sets etc. as required, suitable REF terminal box for
terminating neutral cable with REF CT's as required to be
provided. DG Set shall be enclosed in an acoustic
enclosure. The enclosure shall have provision of space
required for inspection and minor maintenance.

The DG set shall be mounted on a fabricated rigid common


base frame with GERB/Dunlop make ant vibration
mounting to provide not less than 99% vibration isolation.
First filling of lube oil & HSD shall be included in the DG set
cost. The DG Set shall include all standard accessories
fittings and instruments manuals etc. complete as per
specifications. The design of DG Set shall confirm to the
requirement of CPCB for flue gas emission and noise level.

1000 kVA (with acoustic enclosure as per specification) Set 1

500 kVA (with acoustic enclosure as per specification) Set 1


SCHEDULE OF QUANTITIES
P & C FOR LIVING QUARTERS AT BHOGAT, GUJARAT (INDIA) PROJECT

Contract No: RJ9TA1000009029 Revision No: C1 Date: 28.07.2009 Page No: 13


Unit Price in Indian Rupees
Item. Amount
Description Unit Qty Rate (Rs) Amount
No. (In Figures)
(In Words)
Supply Erection Supply Erection
LOAD TESTING OF DG SETS :

The DG Sets shall be subjected to load test either at


factory or at site after installation. The rates quoted shall
include arrangement of electrical/water load required for
testing and all consumables required during trial run of DG
Sets on full load for 12 hours followed by 10% overload for
one hour as per specification and drawings.

Notes :

XLPE copper Cable termination is envisaged for


connecting DG Supply to the Main MV Switchgears.
Required terminals for AMF operation, CTs as specified are
required to be provided in the adaptor box of DG Set.
Rates shall include all these accessories.

DG Set supplier shall provide microprocessor based DG


Local Control panel mounted on the engine having, all
electrical parameters, and fault indication with provision for
its remote control.
SCHEDULE OF QUANTITIES
P & C FOR LIVING QUARTERS AT BHOGAT, GUJARAT (INDIA) PROJECT

Contract No: RJ9TA1000009029 Revision No: C1 Date: 28.07.2009 Page No: 14


Unit Price in Indian Rupees
Item. Amount
Description Unit Qty Rate (Rs) Amount
No. (In Figures)
(In Words)
Supply Erection Supply Erection

DG Supplier should provide arrangement for remote


start/stop and DG fault (LLOP, HWT over speed) etc along
with remote adjustment of voltage & speed of the engine
(Motorized/ solid state pot. may be required) & shall be
included in the quoted rates.

The neutral CTs as per specification shall be provided on


the neutral side of winding and connection brought out to a
neutral CT box to be mounted on the alternators (All the six
terminals are to be brought out and then shorted).

DG supplier / Vendor shall do necessary co-ordination with


MV SWGR panel manufacturer / vendor, required for Auto
and Manual operations / Synchronization as per the
specifications and requirement.

The Client / Consultant reserves the right for load testing


on any / all DG sets.
SCHEDULE OF QUANTITIES
P & C FOR LIVING QUARTERS AT BHOGAT, GUJARAT (INDIA) PROJECT

Contract No: RJ9TA1000009029 Revision No: C1 Date: 28.07.2009 Page No: 15


Unit Price in Indian Rupees
Item. Amount
Description Unit Qty Rate (Rs) Amount
No. (In Figures)
(In Words)
Supply Erection Supply Erection
EXHAUST SYSTEM :

Residential Type Silencer:

Supply, installation, testing & commissioning of residential


type silencers with complete insulation, supporting
arrangement suitable for the above DG Set:

Exhaust Piping :

Design, manufacture, supply, erection, testing &


commissioning of exhaust piping conforming to IS:3589,
flexible bellows, bends, load support, thermal insulated
glasswool /mineral wool, asbestos lining minimum 75 mm
thick up to silencer. Wire chicken mesh over insulation and
24 gauge Aluminium sheet wrapping over the exhaust
pipes upto residential type silencer and from silencer to
direct exhaust to atmosphere including all supports, steel
brackets etc. as required.
RM 50
500 mm dia (5 mm thick)
RM 50
200 mm dia (5 mm thick)
Nos. 2
500 mm stainless steel bellows.
SCHEDULE OF QUANTITIES
P & C FOR LIVING QUARTERS AT BHOGAT, GUJARAT (INDIA) PROJECT

Contract No: RJ9TA1000009029 Revision No: C1 Date: 28.07.2009 Page No: 16


Unit Price in Indian Rupees
Item. Amount
Description Unit Qty Rate (Rs) Amount
No. (In Figures)
(In Words)
Supply Erection Supply Erection

200 mm stainless steel bellows. Nos. 2

The Contractor shall furnish calculation for exhaust piping


sizing for approval by the Consultant. The system should
meet the performance of the engine without exceeding the
back pressure limit prescribed by engine supplier without
exceeding the back pressure limit prescribed by the Engine
supplier.

M.S. Structural Support

Self supporting structure suitable for 30 meter exhaust pipe


above the ground level. This self supporting structure shall
be complete with Aviation light with battery & battery
charger and earthing for lightning arrestor, including Guy
wire supports. This structure shall be designed for a wind
velocity prevailing at site. Including welding, cutting, 2
layers of anti-coating primer with 2 layers of silver paint etc.
complete as required. The item given indicative and
minimum to be provided. The bidder shall workout & furnish
the detail for approval in their proposal. Kg. 1500
SCHEDULE OF QUANTITIES
P & C FOR LIVING QUARTERS AT BHOGAT, GUJARAT (INDIA) PROJECT

Contract No: RJ9TA1000009029 Revision No: C1 Date: 28.07.2009 Page No: 17


Unit Price in Indian Rupees
Item. Amount
Description Unit Qty Rate (Rs) Amount
No. (In Figures)
(In Words)
Supply Erection Supply Erection
E 6.2 FUEL DAY OIL TANK :
E 6.2.1 Supply, fabrication, installation, testing & commissioning of
M.S. day oil tank of 990 litres capacity fabricated out of
min. 5mm thick M.S. sheet installed on steel frame or
masonry pedestal with all associated accessories, filters,
valves & fittings including level indicator complete as
required, float switch should be provided. The tank shall be
suitably treated with anticorrosive treatment on inside &
outside surface.

Set 2
E 6.2.2 Fuel Oil Piping :
Supply, installation, testing and commissioning of medium
class MS piping conforming to IS-1239 for fuel piping
complete with all necessary fittings and valves between
day oil storage tanks and DG sets/priming motor including
jointing of pipes, painting with 2 coats of red oxide and two
coats of enamel paint.
a) 20 mm dia RM 15
b) 25 mm dia RM 15

E 6.4.3 Oil Hand Pump :


Supply & installation of hand pump for pumping out fuel
from barrels to the day oil tank with flexible hose pipe of 5
mtr length. No. 1
SCHEDULE OF QUANTITIES
P & C FOR LIVING QUARTERS AT BHOGAT, GUJARAT (INDIA) PROJECT

Contract No: RJ9TA1000009029 Revision No: C1 Date: 28.07.2009 Page No: 18


Unit Price in Indian Rupees
Item. Amount
Description Unit Qty Rate (Rs) Amount
No. (In Figures)
(In Words)
Supply Erection Supply Erection
Notes :
1 The capacity & quantity given above are indicative and
minimum to be provided.
2 The bidder shall work out and furnish the calculation of
piping/valves PID for approval and suitable quantity shall
be included in their proposal.

TOTAL OF DG SET CARRIED OVER TO SUMMARY

E 7.0 M.V. SWITCH GEARS & DISTRIBUTION BOARDS:

Design, manufacture, supply, installation, testing and


commissioning of following MV switchgear panels suitable
for 415 V, 3 phase, 4 wire, 50 Hz power distribution
system. The panel shall be Indoor, free standing, floor
mounting, sheet metal clad, cubicle, dead front, dust and
vermin proof type compartmentalized design fabricated out
of 14 SWG sheet steel, complete with Copper bus bars,
separate earth bus bar to be provided through out the
length of the panel. The incoming and outgoing feeders
shall be accommodated in a modular multitier arrangement,
adequate size cable alley, painting, earthing, numbering,
danger plate etc as required as per specifications and
drawings shall be provided. The panel shall withstand a
fault level of as indicated on Single Line Diagram.
SCHEDULE OF QUANTITIES
P & C FOR LIVING QUARTERS AT BHOGAT, GUJARAT (INDIA) PROJECT

Contract No: RJ9TA1000009029 Revision No: C1 Date: 28.07.2009 Page No: 19


Unit Price in Indian Rupees
Item. Amount
Description Unit Qty Rate (Rs) Amount
No. (In Figures)
(In Words)
Supply Erection Supply Erection
All MCCBs shall be provided with magnetic & adjustable
thermal releases for short circuit & overload protection with
front drive kit (rotary operating handle).

NOTES :
1 The BOQ shall be read inconjunction with general notes,
specification and Single Line Diagram (attached for Ref.).
Incase of any discrepancy between specification, BOQ and
SLD, the same shall be brought to the notice of
Client/Consultant before quoting the rates, otherwise
stringent condition shall be deemed to have been
considered.

2 Fault current wherever mentioned shall be Ics value.


3 All MCCB shall be provided with door interlocked rotary
handle with ON/TRIP/OFF position indicator, continious
variable thermal magnetic O/C and S/C releases. The
MCCB above 250A rating shall be provided with
microprocessor based releases (settable at site). I/C MCCB
shall be provided with E/F release also.

4 All feeder doors shall have pad locking arrangement.

5 All TP feeders shall have solid isolable neutral link.


SCHEDULE OF QUANTITIES
P & C FOR LIVING QUARTERS AT BHOGAT, GUJARAT (INDIA) PROJECT

Contract No: RJ9TA1000009029 Revision No: C1 Date: 28.07.2009 Page No: 20


Unit Price in Indian Rupees
Item. Amount
Description Unit Qty Rate (Rs) Amount
No. (In Figures)
(In Words)
Supply Erection Supply Erection
6 All MCCB used in starter feeder shall be suitable for motor
duty application.
7 All ACB's shall be with micro processor based O/C and S/C
releases and Breaker Control Switch (BCS) having lost
motion device. I/C ACBs shall be provided with E/F release
also. Bus coupler shall be provided without O/C and S/C
releases.

8 Spare contacts of ACB/Relays/Contactor etc. shall be wired


upto terminal block.
9 All switchgear used in starter feeder shall be type-2 co-
ordinated. Manufacturer is required to submit
manufacturers type-2 co-ordination chart for the make
used.
10 Capacitor shall be heavy duty type (MPP technology).

11 All outgoing terminals (power and control) shall be brought


upto cable alley. 10% extra terminals shall be provided.

12 10% extra indicating lamp in loose shall be supplied along


with panel.
13 Removable lifting hook shall be provided in all
transportation section.
14 All CT, PT shall be cast resin.
15 All meters are digital type.
SCHEDULE OF QUANTITIES
P & C FOR LIVING QUARTERS AT BHOGAT, GUJARAT (INDIA) PROJECT

Contract No: RJ9TA1000009029 Revision No: C1 Date: 28.07.2009 Page No: 21


Unit Price in Indian Rupees
Item. Amount
Description Unit Qty Rate (Rs) Amount
No. (In Figures)
(In Words)
Supply Erection Supply Erection
16. Panel shall be powder coated of approved shade with
minimum 60 micron thickness.
17. ACB's/MCCB's in one particular panel shall be of one
similar make.
18 Size of Voltmeter / Ammeter for incomer also, 96mm x
96mm flush mounted with shrouded terminal shall be used
in the panel.
19. Bus bar chamber shall be kept at top of the all panels.

20. All bus bar shall be insulated with coloured PVC Sleeve i.e.
RYB,BK as per colour code.
21 Internal wiring of panel shall be with size 2.5sqmm Flexible
Copper Conductor for CT circuit and control wiring with 1.5
sqmm.
22 All Lift Panels transport section should not be more then
1000 mm.
23 In soft starter Vender should supply power contactor with
aux. Contactor & All necessary accessories required etc .
(As per BOQ & specification )

24 All indicating light shall be LED type .


SCHEDULE OF QUANTITIES
P & C FOR LIVING QUARTERS AT BHOGAT, GUJARAT (INDIA) PROJECT

Contract No: RJ9TA1000009029 Revision No: C1 Date: 28.07.2009 Page No: 22


Unit Price in Indian Rupees
Item. Amount
Description Unit Qty Rate (Rs) Amount
No. (In Figures)
(In Words)
Supply Erection Supply Erection
25 Each vertical section of floor mounted panel shall have
independent base frame (75mm x 40mm) size made out of
3 mm sheet steel (LT Panel & DG Panel).

26 All Energy meters shall be with RS-485 port and shall be


hooked with B.M. system.
27 Necessary inter locking shall be provided so that the
capacitor bank remains OFF incase of DG Supply.

28 Wherever only voltmeter & ammeter ars required, the same


may be provided in combined meter suitable for both
parameter.
29 All the makes shall be as per Client approved make list
only.
30 All 3P Power contactors including NIC shall be AC-3 duty.

E 7.1 MVSWGR Panel 1 & 2


i) Incomer from Transformers :
1 No. 1600A, 415 V, 50 kA four pole draw out, Electrically
operated ACB, with ON/OFF/TRIP indication lamp and
TNC control switch, under voltage & shunt trip release,
anti pumping protection with microprocessor based O/C,
S/C & E/F protection complete as required.
SCHEDULE OF QUANTITIES
P & C FOR LIVING QUARTERS AT BHOGAT, GUJARAT (INDIA) PROJECT

Contract No: RJ9TA1000009029 Revision No: C1 Date: 28.07.2009 Page No: 23


Unit Price in Indian Rupees
Item. Amount
Description Unit Qty Rate (Rs) Amount
No. (In Figures)
(In Words)
Supply Erection Supply Erection
ii) Metering & indication and Annunciation for
Transformer Supply incoming breakers :
Each transformer supply breaker shall be provided with the
following:
a) One (1) No. digital voltmeter 0-500 V, 96 x 96 mm with
control MCB and 3 way ON & OFF selector switch.

b) One (1) No. (0-1600) Amps digital Ammeter 96 x 96 mm,


with 1 Set (3 Nos) of 1600/5A, 15VA, CL 1.0 CTs. and 3-
way ON & OFF selector switch.

c) One (1) No. 3 Phase 4 wire CT operated KWH meter


suitable for unbalanced loads.

d) One set ( 3 nos.) phase indication lamps with control MCB.

e) One no. 8 window Audio/visual annunciator system


complete with hooter, Ack, test & Reset PBs for
annunciation of WTI, Protection trip & HT trip alarm etc.

iii) Protection Relays & Interlocking for transformer


breaker :
Each Transformer breaker shall be provided with the
following :
SCHEDULE OF QUANTITIES
P & C FOR LIVING QUARTERS AT BHOGAT, GUJARAT (INDIA) PROJECT

Contract No: RJ9TA1000009029 Revision No: C1 Date: 28.07.2009 Page No: 24


Unit Price in Indian Rupees
Item. Amount
Description Unit Qty Rate (Rs) Amount
No. (In Figures)
(In Words)
Supply Erection Supply Erection
a) CT operated tripple pole over current and earth fault relay
CDG-31 of Areava or equivalent make with one set (3
Nos.) 1600/5A, 5 P10, 15VA, C.T.'s.
b) One (1) no. of restricted earth fault relay similar to CAG-14
of Areava or equivalent with 4 Nos. of 1600/1A CL-PS
protection CT's (Three Nos. CTS to be fixed in the Panel
and One No. to be supplied loose for fixing on Transformer
neutral terminal).
c) One (1) No. of 1600/5A, C.L. 1.0, 15VA, CT for input to
APFCR relay.
d) One (1) no. of Master Trip relay similar to VAJH13 of
Areava or equivalent.
e) One (1) no. of Trip circuit supervision relay similar to
VAX31 of Areava or equivalent.
Note:- Operation interlocks as per specification & drawings and
sufficient nos. of potential free contacts for
interlocking/indication annunciation /control etc shall be
provided by the bidder as required.
iv) Bus coupler :
a) One (1) No. 1600A, 50 kA four pole draw out electrically
operated ACB with ON/OFF indication lamps.
SCHEDULE OF QUANTITIES
P & C FOR LIVING QUARTERS AT BHOGAT, GUJARAT (INDIA) PROJECT

Contract No: RJ9TA1000009029 Revision No: C1 Date: 28.07.2009 Page No: 25


Unit Price in Indian Rupees
Item. Amount
Description Unit Qty Rate (Rs) Amount
No. (In Figures)
(In Words)
Supply Erection Supply Erection
v) Incomer from DGs :
One (1) No. 1600A 415 V, 50 kA Three pole draw out,
Electrically operated ACB, with ON/OFF/TRIP indication
lamp and TNC control switch, 300A TP Neutral isolation
contactor, under voltage & shunt trip release, anti pumping
protection with microprocessor based O/C, S/C and E/F
protection complete as required.
- One (1) 800A 50 KA Three pole draw out, Electrically
operated ACB, with ON/OFF/TRIP indication lamp and
TNC control switch, 150A TP Neutral isolation contactor,
under voltage & shunt trip release, anti pumping protection
with microprocessor based O/C, S/C and E/F protection
complete as required.
vi) Metering & Indication for DG Supply breakers :
SCHEDULE OF QUANTITIES
P & C FOR LIVING QUARTERS AT BHOGAT, GUJARAT (INDIA) PROJECT

Contract No: RJ9TA1000009029 Revision No: C1 Date: 28.07.2009 Page No: 26


Unit Price in Indian Rupees
Item. Amount
Description Unit Qty Rate (Rs) Amount
No. (In Figures)
(In Words)
Supply Erection Supply Erection
Each DG supply breaker shall be provided with the
following:
a) One (1) No. digital voltmeter 0-500 V, 96 x 96 mm with
control MCB and 3 way ON & OFF selector switch

b) One (1) No. (0-1600A) digital Ammeter 96 x 96 mm CT.


operated, with 3-way OFF selector switch and 1 Set (3
Nos) of 1600/5A C.T's, (15VA, CL 1.0) for 1000 KVA DG
Set and (0-800A) with suitable CTs for 500 KVA DG Set.

c) One (1) No. 3 Phase 4 wire CT operated KWH meter


suitable for unbalanced loads.

d) One (1) No. KW meter.


e) One (1) No. frequency meter.
f) One (1) No. power factor meter.
g) One (1) No. hour run meter.
- One (1) Set of Phase indication lamps with control MCB.
- One (1) No. 12 window Audio / visual annuciator with test
accept and reset facility.

vii) Protection Relays & Interlocking for DG Supply


Breaker :
Each DG breaker shall be provided with the following :
SCHEDULE OF QUANTITIES
P & C FOR LIVING QUARTERS AT BHOGAT, GUJARAT (INDIA) PROJECT

Contract No: RJ9TA1000009029 Revision No: C1 Date: 28.07.2009 Page No: 27


Unit Price in Indian Rupees
Item. Amount
Description Unit Qty Rate (Rs) Amount
No. (In Figures)
(In Words)
Supply Erection Supply Erection
a) CT operated triple pole over current and earth fault relay
CDV-62 of Areava or equivalent make 50 – 200 %, IDMTL
over current, 200-1200 % for instantaneous over current,
10 – 40 % for earth fault, with1200/5A C.T.'s, (5 P10
C.T.'s) for 1000 KVA Set and 800/5A CTs for 500 KVA Set.

b) One (1) No. reverse power relay, similar to type CCUM-21


of M/s Areava or equivalent.

c) One (1) No. under voltage (CDG-13) and one no. over
voltage relay (CDG-11) with 415 /110V, 100 VA / phasePT
& Control MCB in incoming and outgoing side of PT.

d) One (1) No. of restricted earth fault relay similar to CAG-14


of Areava or equivalent with 4 nos. CT's of 1600/1A rating
CL-PS for 1000 KVA Set & 800/1A CTs for 500 KVA Set
(Three Nos. CTs to be fitted in the panel and one No to be
supplied loose for fixing on DG set neutral).

- Trip circuit supervision relay (similar to VAX -31 of Areava)

- Master trip lockout relay (similar to VAJH-13 of Areava)


SCHEDULE OF QUANTITIES
P & C FOR LIVING QUARTERS AT BHOGAT, GUJARAT (INDIA) PROJECT

Contract No: RJ9TA1000009029 Revision No: C1 Date: 28.07.2009 Page No: 28


Unit Price in Indian Rupees
Item. Amount
Description Unit Qty Rate (Rs) Amount
No. (In Figures)
(In Words)
Supply Erection Supply Erection
Note : Above BOQ is only for the purpose of scope identification. However all item required for protection interlocks as per operation scheme through
potential free contacts for operation & control shall be provided in sufficient number as required.

Any Auxiliary relay if required shall be provided with in the scope of item.

Required interlock should be provided so that transformer and DG supply are not paralleled.

viii) Busbar :
1600A, 50kA TPN Cu. Bustbar insulated with heat
shrinkable sleeves and shall be colour coded.

Separate earth busbar shall be provided.


ix) Outgoings :
a) Four (4) Nos. 800A, 50 kA, TPN MCCB.
b) One (1) No. 400A, 50 kA TPN MCCB
c) Three (3) Nos. 315A, 50 kA TPN MCCB
d) Two (2) Nos. 200A, 50 kA TPN MCCB
e) Eight (8) Nos. 100A, 50 kA TPN MCCB
f) One (1) Nos. 630A, 50 kA TPN MCCB
Notes :
1 The MV Switchgear have to operate in isolation as well as
coupled mode. When Bus coupler breaker is ON only one
of the incoming breaker can be closed in case of normal
supply.
SCHEDULE OF QUANTITIES
P & C FOR LIVING QUARTERS AT BHOGAT, GUJARAT (INDIA) PROJECT

Contract No: RJ9TA1000009029 Revision No: C1 Date: 28.07.2009 Page No: 29


Unit Price in Indian Rupees
Item. Amount
Description Unit Qty Rate (Rs) Amount
No. (In Figures)
(In Words)
Supply Erection Supply Erection
2 The protection/interlock shall be such that individual buses
can be fed either by TR or DG in all possible operating
conditions. Paralleling of transformer with DG is not
permitted.
3 Whole scheme of transformer control and DG control
should be integrated so that required operation is
accomplished.
x) MANUAL / AUTO SYNCHRONIZING AND LOAD
SHARING + AMF PANEL + LOAD MANAGEMENT(PLC
CONTROL PANEL) 1 NO. 1000 kVA AND 1 NO. 500 KVA
DG SET.

I) PLC Based DG Control :


Design, manufacture, assembly & supply of PLC based
control logic having following features :
a) AMF operation (through PLC) with all necessary feature for
manual operation to be done when PLC is not available or
out of circuit).

b) Auto Synchronisation System.


SCHEDULE OF QUANTITIES
P & C FOR LIVING QUARTERS AT BHOGAT, GUJARAT (INDIA) PROJECT

Contract No: RJ9TA1000009029 Revision No: C1 Date: 28.07.2009 Page No: 30


Unit Price in Indian Rupees
Item. Amount
Description Unit Qty Rate (Rs) Amount
No. (In Figures)
(In Words)
Supply Erection Supply Erection
c) Auto load sharing among D.G. Sets.
d) Auto load balancing and management.

Above system components shall be housed in the MV


SWGR panel complete with all accessories as per
requirement I/O racks, relay modules, 5/30 line
synchronizing module (Allen Bradley make), operation
interface with Pentium IV Computer with 40GB HDD, 14"
SVGA Color monitor, 80 column printer, 101 keys keyboard
mouse etc, communicable cable, graphic station software,
at least 1 KVA UPS 45 minutes backup by Ni-cd
maintenance free batteries, PLC to PC Communication
card. The system should be suitable for controlling Two (2)
Nos. DG breakers, One (1) No. transformer breaker, One
(1) No. bus coupler breakers. The system shall have total
manual override so that it is possible to operate the DG
Sets in the manual mode in the event of non-availability of
PLC Control. The offer shall be inclusive of all power and
control interface cabling for required I/O signals.
Notes :
1 For meeting requirement of input to PLC from various
relays, CB positions etc, suitable CTs/PTs/TBs and
interface for analog & digital input/output shall be provided
to achieve successful operation of the DG Set & system as
a whole.
SCHEDULE OF QUANTITIES
P & C FOR LIVING QUARTERS AT BHOGAT, GUJARAT (INDIA) PROJECT

Contract No: RJ9TA1000009029 Revision No: C1 Date: 28.07.2009 Page No: 31


Unit Price in Indian Rupees
Item. Amount
Description Unit Qty Rate (Rs) Amount
No. (In Figures)
(In Words)
Supply Erection Supply Erection
2 BOQ given above is for a composite panel identifying the
scope of supplies. However, bidder shall include all such
components as are necessary for a successful and safe
AMF scheme in both manual as well as on auto & PLC
mode. PLC based DG control panel shall be integrated in
the main M.V. Switch Gear.

3 Above BOQ is only for the purpose of scope identification.


However all item required for protection interlocks as per
operation scheme through potential free contacts for
operation & control shall be provided in sufficient number
as required.

Required interlock should be provided so that transformer


and DG supply are not paralleled.
xi) Manual Synchronization Panel:
Design, manufacture, assembly & supply of Manual
Synchronising Panel shall consist of :

i) One (1) No. double voltmeter.


ii) One (1) No. double frequency meter.
iii) One (1) No. synchros cope with PT & glow lamps.
iv) QDCTs for parallel operation of DGs.
v) One (1) No. Syn. Switch.
vi) One (1) No. check syn. Relay.
SCHEDULE OF QUANTITIES
P & C FOR LIVING QUARTERS AT BHOGAT, GUJARAT (INDIA) PROJECT

Contract No: RJ9TA1000009029 Revision No: C1 Date: 28.07.2009 Page No: 32


Unit Price in Indian Rupees
Item. Amount
Description Unit Qty Rate (Rs) Amount
No. (In Figures)
(In Words)
Supply Erection Supply Erection
vii) One (1) No. A/M selector switch.

MVSWGR Panel (from item i to xi) described as above Set 1


E 7.2 Capacitor Panels (400 kVAR) [To be integrated with
MVSWGR Panel]
a) Incoming :
One (1) No. 800A TPN MCCB, incomer (50 KA) with 14
steps APFC relay with Auto/Manual selector switch, timer,
aux. Contactor, louvers, Exhaust fan etc.[800 A TPN
MCCB is already inclnded in Main panel as O/G to
capacitor panel. Hence not to be included here]
b) Metering, Indication and Protection :
- One (1) No. digital voltmeter (0-500V) with selector 3 way
- ON AND OFF selector switch and control fuses.
- One (1) No. digital Ammeter (0-800A) with CTs, 800A/5A
CL-1.0, 5VA with 3 way ON and OFF selector switch.
One (1) set of RYB phase indication lamps with control
fuses.
c) Busbar :
- 1000A TPN Cu. Busbar insulated with heat shrinkable
sleeves and shall be color coded.
Separate earth bar shall be provided.
d) Outgoings :
- 400 KVAR Capacitor Panel in steps of 12 nos. of 4x2x25 + Set 1
8x1x25 kVAR banks.
SCHEDULE OF QUANTITIES
P & C FOR LIVING QUARTERS AT BHOGAT, GUJARAT (INDIA) PROJECT

Contract No: RJ9TA1000009029 Revision No: C1 Date: 28.07.2009 Page No: 33


Unit Price in Indian Rupees
Item. Amount
Description Unit Qty Rate (Rs) Amount
No. (In Figures)
(In Words)
Supply Erection Supply Erection

Notes:
1 Each capacitor bank should have its individual MCCB &
Contactor suitable for capacitor duty including fuses for
each capacitor unit.
2 Enclosure of capacitor panel shall be liberally designed to
take care of internal heat emission by capacitor unit without
forced cooling and to limit the temperature rise with in
permissible limit. However, louvers are allowed to facilitate
extra cooling.

E 7.3 SUB MAIN BOARD (SMB-1)


Location : Electrical Room Ground Floor
Incomer :
- One (1) No. 630A TPN MCCB (35KA)

- One (1) No. digital multi funciton meter for measurement of


voltage and current with selector push buttons and set of
CTs of ratio 600A/5A CL-1, 15VA.

- Three (3) Nos. phase indication lamps with control MCBs 2


Amp.

- One (1) No. earth leakage relay with suitable CBCT.

- One (1) No mushroom head type emergency stop push


button with shunt trip coil in MCCB.
SCHEDULE OF QUANTITIES
P & C FOR LIVING QUARTERS AT BHOGAT, GUJARAT (INDIA) PROJECT

Contract No: RJ9TA1000009029 Revision No: C1 Date: 28.07.2009 Page No: 34


Unit Price in Indian Rupees
Item. Amount
Description Unit Qty Rate (Rs) Amount
No. (In Figures)
(In Words)
Supply Erection Supply Erection
Busbar :
- 700A TPN Cu. busbar.

Outgoing :
- All outgoing shall be 35KA breaking capacity and shall be
provided with ON/OFFTrip indication lamps.

100A TPN MCCB - 16 Nos. Set 1


E 7.4 SUB MAIN BOARD (SMB-2)
Location : Kitchen
Incomer :
- One (1) No. 400A TPN MCCB (35KA)
- One (1) No. digital multi funciton meter for measurement of
voltage and current with selector push buttons and set of
- CTs of ratio 400A/5A CL-1, 15VA.
- Three (3) Nos. phase indication lamps with control MCBs 2
Amp.
- One (1) No. earth leakage relay with suitable CBCT.
- One (1) No mushroom head type emergency stop push
button with shunt trip coil in MCCB.

Busbar :
500A TPN Cu busbar.

Outgoing :
SCHEDULE OF QUANTITIES
P & C FOR LIVING QUARTERS AT BHOGAT, GUJARAT (INDIA) PROJECT

Contract No: RJ9TA1000009029 Revision No: C1 Date: 28.07.2009 Page No: 35


Unit Price in Indian Rupees
Item. Amount
Description Unit Qty Rate (Rs) Amount
No. (In Figures)
(In Words)
Supply Erection Supply Erection
All outgoing shall be 35KA breaking capacity and shall be
provided with ON/OFFTrip indication lamps.

- 100A TPN MCCB - 10 Nos. Set 1


E 7.5 FEEDER PILLAR (WEATHER PROOF) :
Incomer
- One (1) No. 100A TPN MCCB (35 KA)
- One (1) No. earth leakage relay with CBCT.

Busbar – 150A TPN Cu. Busbar

Outgoing:-
- Three (3) Nos. 20A DP MCB (10KA) with 20A contactor
(AC-3 Cat with 230V control coil)
- Nine (9) Nos. 40A DP MCBs (10KA)
- Three (3) Nos. 63A TPN MCBs (10KA)
- Three (3) Nos. 24 hours double dial programmable time
switch on auto mode arrangement for Auto/Manual
Selection, A/M Selector switch ON/OFF push buttons
indication lamps and control MCB etc as required.
Set 4
E 7.6 Distribution Board
MCB distribution board double door type pre-wired
complete with din rail, top and bottom grand plates, knock
outs, separate neutral and earth terminal for each phase as
required comprising of following:-
SCHEDULE OF QUANTITIES
P & C FOR LIVING QUARTERS AT BHOGAT, GUJARAT (INDIA) PROJECT

Contract No: RJ9TA1000009029 Revision No: C1 Date: 28.07.2009 Page No: 36


Unit Price in Indian Rupees
Item. Amount
Description Unit Qty Rate (Rs) Amount
No. (In Figures)
(In Words)
Supply Erection Supply Erection
E 7.6.1 LPDBs
I) 8 Way TPN MCB DB.
a) Incoming
One (1) No. 63A 4P MCB + 63A DP, ELCB (30mA) for
each phase.
b) Bus Bar
100A TPN Cu. Busbar.
c) Outgoing (10kA) comprising
6/10/16/20/32 A SP MCBs - 24 Nos. Nos. 10
II) 8 Way SPN MCB DB.
a) Incoming
One (1) No. 32A DP MCB + 32A DP, ELCB (30mA).
b) Bus Bar
100A Cu. Busbar.
c) Outgoing (10kA) comprising
6/10/16/20 A SP MCBs - 8 Nos. Nos. 54
E 7.6.2 PDBs (for Single Phase Load)
I) 6 Way TPN MCB DBs
a) Incoming
63A 4P MCB + 63A DP, ELCB (30mA) for each phase.
b) Bus Bar
100A TPN Cu. Busbar.
c) Outgoing (10kA) comprising
16/20/32 A SP MCBs - 18 Nos. Set 1
II) 12 Way TPN MCB DBs
a) Incoming
SCHEDULE OF QUANTITIES
P & C FOR LIVING QUARTERS AT BHOGAT, GUJARAT (INDIA) PROJECT

Contract No: RJ9TA1000009029 Revision No: C1 Date: 28.07.2009 Page No: 37


Unit Price in Indian Rupees
Item. Amount
Description Unit Qty Rate (Rs) Amount
No. (In Figures)
(In Words)
Supply Erection Supply Erection
63A 4P MCB + 63A DP, ELCB (30mA) for each phase.

b) Bus Bar
100A TPN Cu. Busbar.

c) Outgoing (10kA) comprising


16/20/32 A SP MCBs =36Nos. Set 4
E 7.6.3 PDBs (for Three Phase Load)
I) 8 Way TPN MCB DBs
a) Incoming
63A 4P MCB + 63A TPN, ELCB (30mA).
b) Bus Bar
100A TPN Cu. Busbar.
c) Outgoing (10kA) comprising
20/32A, TPN MCBs =8Nos. Set 2
II) 6 Way TPN MCB DBs
a) Incoming
63A 4P MCB + 63A TPN, ELCB (30mA).
b) Bus Bar
100A TPN Cu. Busbar.
c) Outgoing (10kA) comprising
20/32A, TPN MCBs = 6Nos. Set 2
TOTAL OF M.V. SWITCH GEARS & DISTRIBUTION
BOARDS CARRIED OVER TO SUMMARY
E 8.0 CABLES, SUB MAINS & CABLE TRAYS:
SCHEDULE OF QUANTITIES
P & C FOR LIVING QUARTERS AT BHOGAT, GUJARAT (INDIA) PROJECT

Contract No: RJ9TA1000009029 Revision No: C1 Date: 28.07.2009 Page No: 38


Unit Price in Indian Rupees
Item. Amount
Description Unit Qty Rate (Rs) Amount
No. (In Figures)
(In Words)
Supply Erection Supply Erection
E 8.1 Cables on Racks/Pipes/Ducts /wireways /underground
:
Supply installation, testing and commissioning of following
sizes of PVC sheathed XLPE insulated copper con-ductor
power/ multicore control armoured cable of 1.1 KV grade
on surface of wall or in existing cable tray /masonary
ducts/hume pipe with fixing hardware etc as required.
E 8.1.1 Copper Conductor Armoured cable :
1/2
a) 3 Core 300 Sqmm XLPE Cu cable RM 500
1/2
b) 3 Core 240 Sqmm XLPE Cu cable RM 200
1/2
c) 3 Core 185 Sqmm XLPE Cu cable RM 100
1/2
d) 3 Core 95 Sqmm XLPE Cu cable RM 40
e) 4 Core 25 Sqmm XLPE Cu cable RM 125
f) 4 Core 16 Sqmm XLPE Cu cable RM 425
g) 3.5 Core 50 Sqmm XLPE Cu cable RM 500
h) 3 Core 6 Sqmm XLPE Cu cable RM 300
i) 3 Core 4 Sqmm XLPE Cu cable RM 300
E 8.1.2 Laying of following sizes of PVC sheathed XLPE Insulated
power cable of 1.1KV grade in ground including excavation,
sand cushioning protective covering and refiling the trench
etc as required.
a) 3C X 6Sqmm XLPE Cu Cable RM 200
b) 3C X 4Sqmm XLPE Cu Cable RM 300
c) 3C X 2.5Sqmm XLPE Cu Cable RM 300
SCHEDULE OF QUANTITIES
P & C FOR LIVING QUARTERS AT BHOGAT, GUJARAT (INDIA) PROJECT

Contract No: RJ9TA1000009029 Revision No: C1 Date: 28.07.2009 Page No: 39


Unit Price in Indian Rupees
Item. Amount
Description Unit Qty Rate (Rs) Amount
No. (In Figures)
(In Words)
Supply Erection Supply Erection

E 8.2 Cable Termination :


Supply and making end termination with brass
compression glands for the following XLPE insulated PVC
sheathed 1100 V grade cable including cost of crimping
lugs / ferrules,compression glands, solder, cable sockets,
insulation tap etc complete as required.
E 8.2.1 Copper Conductor Cables :
(Glands suitable for following armoured cables)
1/2
a) 3 core x 300 sqmm XLPE Cu Cable Nos. 20
1/2
b) 3 core x 240 sqmm XLPE Cu Cable Nos. 12
1/2
c) 3 core x 185 sqmm XLPE Cu Cable Nos. 2
1/2
d) 3 core x 95 sqmm XLPE Cu Cable Nos. 4
1/2
e) 3 core x 50 sqmm XLPE Cu Cable Nos. 8
f) 4 core x 25 sqmm XLPE Cu Cable Nos. 8
g) 4 core x 16 sqmm XLPE Cu Cable Nos. 34
h) 3 core x 6 sqmm XLPE Cu Cable Nos. 10
i) 3 core x 4 sqmm XLPE Cu Cable Nos. 30
j) 3 core x 2.5 sqmm XLPE Cu Cable Nos. 40
Note: The cable quantities given are approximate and to cover various sizes. The contractor shall measure the cables required and procurement
order shall be placed accordingly. The quantities shall be confirmed to the engineer-in-charge before start of work.

E 8.3 Cable Trays :


SCHEDULE OF QUANTITIES
P & C FOR LIVING QUARTERS AT BHOGAT, GUJARAT (INDIA) PROJECT

Contract No: RJ9TA1000009029 Revision No: C1 Date: 28.07.2009 Page No: 40


Unit Price in Indian Rupees
Item. Amount
Description Unit Qty Rate (Rs) Amount
No. (In Figures)
(In Words)
Supply Erection Supply Erection
Supply and installation of ladder type/perforated type cable
trays of the following sizes fabricated out of perforated hot
dip galvanised MS sheets of minimum 2 mm thick with 75
mm flange to be installed horizontally or vertically. The
cable tray shall be complete including cost of bends,
elbows, cross, tees, reducers etc as per drawings/site
condition and rate shall include cost of anchor fasteners,
screws, nuts, bolts and misc. other fixing hardware painting
of support structure etc as required.
Notes :
i) Structural steel such as ISMC, ISA, flats, rods etc to be
used for cable tray/bus duct support shall be paid
separate-ly on `per kg' basis and the support arrangement
shall be as indicated in the drgs.
The contractor may refer to the tray installation
specification for this purpose and submit shop drawing
before start of work.
ii) The cable tray shall be factory built. Bidder shall include in
his price, required numbers of Tees, Crosses, Bends,
Elbows etc as required as per actual site conditions. Bidder
may refer to the drawings for estimation purpose.
iii) Earthing strip shall be paid separately under sub head
"Earthing".
E 8.3.1 Ladder Type Cable tray
a) 600 mm wide RM 50
SCHEDULE OF QUANTITIES
P & C FOR LIVING QUARTERS AT BHOGAT, GUJARAT (INDIA) PROJECT

Contract No: RJ9TA1000009029 Revision No: C1 Date: 28.07.2009 Page No: 41


Unit Price in Indian Rupees
Item. Amount
Description Unit Qty Rate (Rs) Amount
No. (In Figures)
(In Words)
Supply Erection Supply Erection
E 8.3.2 Perforated Type Cable Tray :
a) 300 mm wide RM 100
b) 150 mm wide RM 100
E 8.3.3 Cable Tray Support Structure
Supply, fabrication and installation of cable support
structure as per drawings/speci-fication/site requirement
and the direction of Construction manager /Consultant
comprising of ISMCS, ISA's flats rods, turnbuckles etc for
supporting cable trays in multitier formation. The rate shall
include painting with 2 primer coats of red oxide and two
finishing coats of approved enameled paint. Kg. 200
TOTAL OF CABLES, SUB MAINS & CABLE TRAYS
CARRIED OVER TO SUMMARY
E 9.0 WIRING :
E 9.1 Point Wiring
SCHEDULE OF QUANTITIES
P & C FOR LIVING QUARTERS AT BHOGAT, GUJARAT (INDIA) PROJECT

Contract No: RJ9TA1000009029 Revision No: C1 Date: 28.07.2009 Page No: 42


Unit Price in Indian Rupees
Item. Amount
Description Unit Qty Rate (Rs) Amount
No. (In Figures)
(In Words)
Supply Erection Supply Erection
Supplying, wiring, testing and commissioning for lights,
ceiling fans, exhaust fans and 6 A socket outlets (where 6
A socket connected to lighting circuit) using 2.5 Sqmm
stranded copper, 1100 volts grade,FR PVC insulated wires
drawn through, MS conduit including laying of conduits in a
con-cealed/ surface manner using necessary conduit
accessories, junction boxes, switch outlet boxes, switch
plates, bends, collars, clamps, ceiling roses, 6/16A, one
way/ Two way switch-es, fan regulator boxes, etc. shall be
flush mounted in brick wall or in the built up furnitures or in
floor or on the surface of wall for surface installation as
required.

(The rate for point wiring (using 2.5 Sqmm 1100 V grade
FR PVC insulated copper wires) shall include the circuit
wiring (using 2 Nos. 2.5 Sqmm & 1 No. 2.5 (for earth),
1100 V grade FR PVC insulated copper wires) from the
DB/Dimmer panel up to the Junction box/ first light/fan/6 A
convenience socket outlet control switch on wards to light/
fan then the looping between switches /lights/fans/6 A
socket etc. The circuit wiring will not be paid separately.
However where the lights are controlled directly from DB
without local control switch, the quoted rates shall not
include cost of switches/MCB etc.
SCHEDULE OF QUANTITIES
P & C FOR LIVING QUARTERS AT BHOGAT, GUJARAT (INDIA) PROJECT

Contract No: RJ9TA1000009029 Revision No: C1 Date: 28.07.2009 Page No: 43


Unit Price in Indian Rupees
Item. Amount
Description Unit Qty Rate (Rs) Amount
No. (In Figures)
(In Words)
Supply Erection Supply Erection
Also the rate shall include earthing of each light, fan outlet
boxes, switches, switch plates, switch control boxes, 6A
sockets using 2.5 Sqmm copper, FR PVC insulated wires
and flexible conduit from junction box to the fitting as
required.
E 9.1.1 Lighting Points
i) One Way Switch Controlled
a) First Point Nos. 500
b) Loop Point Nos. 291
c) Curtain/Blind Point/Controlled by Rise/Lower Switch Nos. 50
ii) Light points controlled directly by MCB from DB (Cast
of MCB not to be included)
a) First Point Nos. 23
b) Loop Point Nos. 128
E 9.1.2 Two way Switch Controlled
a) First Point Nos. 4
b) Loop Point Nos. 7
Fan Points :
E 9.1.3

Ceiling fan point wiring with 2.5 Sqmm. PVC insulated


a)
copper wires controlled by a 6A switch & electronic fan
regulator. The rate shall include G.I. fan box/ fan hook etc.
Point 90
SCHEDULE OF QUANTITIES
P & C FOR LIVING QUARTERS AT BHOGAT, GUJARAT (INDIA) PROJECT

Contract No: RJ9TA1000009029 Revision No: C1 Date: 28.07.2009 Page No: 44


Unit Price in Indian Rupees
Item. Amount
Description Unit Qty Rate (Rs) Amount
No. (In Figures)
(In Words)
Supply Erection Supply Erection
b) Exhaust fan point (Single Phase) controlled by a 5A switch
on the switch board and 5 A socket outlet near exhaust
fan. Point 54
6A Socket Points
E 9.1.4
a) 6 A shuttered type socket outlet wiring with 2 x 2.5 Sq.m +
1 x 2.5 Copper earth wire including providing 3 pin 6 A
switch. Point 466
b)
Providing and fixing 3 pin 6 Amp Shuttered socket outlet
with 6 Amp switch and lamp holder with 6Amp switch on
the same board including wiring with 2 x 2.5 sqmm + 2x2.5
sqmm PVC insulated copper wires for FCU etc complete as
required.
Nos. 100
E 9.1.5 Call Bell Point

Wiring for a call bell and buzzer point with 2.5 Sqmm PVC
insulated copper conductor wires in recessed/ surface MS
conduit including providing, fixing suitable size of GI box,
bell push with PVC insulated 2.5 Sqmm copper conductor
wire for earthing, cutting, filling chases, providing saddles
including circuit wiring complete with all accessories as
required.
Point 50
E 9.2 Power Socket Wiring
SCHEDULE OF QUANTITIES
P & C FOR LIVING QUARTERS AT BHOGAT, GUJARAT (INDIA) PROJECT

Contract No: RJ9TA1000009029 Revision No: C1 Date: 28.07.2009 Page No: 45


Unit Price in Indian Rupees
Item. Amount
Description Unit Qty Rate (Rs) Amount
No. (In Figures)
(In Words)
Supply Erection Supply Erection
E 9.2.1
Wiring for 6/16A Amp power outlet with 4 Sqmm FR PVC
insulated stranded copper conductor wires in
recessed/surface black enameled MS conduit including
cutting/filling chases, providing conduit with conduit
accessories, saddles supply and fixing of 6 pin 6/16 amps
shuttered switched socket with internal wiring in G.I. box,
earthing of 3rd pin with PVC insulated, green colour 4
Sq.mm copper wire, complete with all accessories as
required.
Point 110
E 9.2.2 Same as item above but a set of two nos. 6/16A power
outlets in one box & one switch with neon indicator(for
UPS). Set 4
INDUSTRIAL SOCKETS WITH MCBs
E 9.3
9.3.1
Point wiring same as item above but with supply and
installation of single phase, industrial type 3 pin plug and
socket outlet with SP MCB (9 KA motor duty) mounted in a
sheet steel enclosure including termination, earthing etc in
surface/recessed mounting as required.
.
a) 20/32 A Metal clad socket outlet with 20/32 A MCB. Point 52
SCHEDULE OF QUANTITIES
P & C FOR LIVING QUARTERS AT BHOGAT, GUJARAT (INDIA) PROJECT

Contract No: RJ9TA1000009029 Revision No: C1 Date: 28.07.2009 Page No: 46


Unit Price in Indian Rupees
Item. Amount
Description Unit Qty Rate (Rs) Amount
No. (In Figures)
(In Words)
Supply Erection Supply Erection
E 9.3.2
Supply and installation of single phase/three phase,
industrial type plug and socket outlet with SP/TP MCBs/
ELCB (9KA motor duty) (Bulwork of clipsal or approved
equivalent) including termination, earthing etc. in
surface/recessed mounting as required.

a) 16A 2P+E Industrial Switched socket outlet with 16A DP/


ELCB (30 mA) (Cat. No. CLIWCSDW 3166 or equivalent)
complete as required. Nos. 10
b) 32A 2P+E Industrial Switched socket outlet with 32A DP/
ELCB (30 mA) (Cat. No. CLIWCSDW 3326 or equivalent)
complete as required. Nos. 2
c)
16A 3P+N+E Industrial Switched socket outlet with 16/20A
TPN ELCB (30 mA) (Cat. No. CLIWCS DW 5166 of clipsal
or equivalent) complete as required.
Nos. 13
d)
32A 3P+N+E Industrial Switched socket outlet with 32A
TPN ELCB (30 mA) (Cat. No. CLIWCSDW 5326 of clipsal
or equivalent) complete as required.
Nos. 7
e)
63A 3P+N+E Industrial Switched socket outlet with 63A
TPN ELCB (30 mA) (Cat. No. CLIWCSDW 5636 of clipsal
or equivalent) complete as required.
Nos. 3
SCHEDULE OF QUANTITIES
P & C FOR LIVING QUARTERS AT BHOGAT, GUJARAT (INDIA) PROJECT

Contract No: RJ9TA1000009029 Revision No: C1 Date: 28.07.2009 Page No: 47


Unit Price in Indian Rupees
Item. Amount
Description Unit Qty Rate (Rs) Amount
No. (In Figures)
(In Words)
Supply Erection Supply Erection

E 9.4 Conduits
E 9.3.3 Same as Item No. 9.3.1 but in Polycarbonate enclosure
with IP-66 Protection.
a) 32A 3 Pin Socket with 32A DP MCB. Nos. 12
Supply and installation of following size of PVC conduit
pipe in recess or on surface including all accessories
MS/CI pull/junction boxes, GI fish wire, fixing hardware etc
including chasing the walls/floor and plastering the chased
portion and making good the damages etc, complete as
required.
25 mm dia
a) RM 275
32 mm dia
b) RM 100
E 9.5 Sub-mains Wiring
Supply and drawing of following sizes of FR PVC insulated
stranded copper conductor wires of 650/1100 Volts grade
in existing conduit pipe /wire ways including connection
/terminations etc as required.

a) 2 x 4.0 Sqmm + 1 No.4.0 Sqmm Copper earth wire. RM 100


b) 2 x 6.0 Sqmm + 1 No 4 Sqmm Copper earth wire. RM 20
c) 4 x 4.0 Sqmm + 2 No 4 Sqmm Copper earth wire. RM 150
d) 4 x 6.0 Sqmm + 2 No 4 Sqmm Copper earth wire . RM 100
SCHEDULE OF QUANTITIES
P & C FOR LIVING QUARTERS AT BHOGAT, GUJARAT (INDIA) PROJECT

Contract No: RJ9TA1000009029 Revision No: C1 Date: 28.07.2009 Page No: 48


Unit Price in Indian Rupees
Item. Amount
Description Unit Qty Rate (Rs) Amount
No. (In Figures)
(In Words)
Supply Erection Supply Erection
E 9.6
Supply, installation & fixing of following size powder coated
GI wireways on ceiling/ wall/floor with all associated
hardware as per approved design.

a) 100x50x2mm thick RM 50
Notes :
1)
In false ceiling areas the work is to be co-ordinate with
respect to ID work and rate for point wiring shall include
flexible conduit/fixing nipples/couplers etc from the junction
box up to the fitting.
.
2)
Point on the same switch board shall include providing and
fixing 3 pin 6A switch socket outlet including connection
from the same switch board.
.
TOTAL OF WIRING CARRIED OVER TO SUMMARY

LIGHTING FIXTURES & FANS:


E 10.0
SCHEDULE OF QUANTITIES
P & C FOR LIVING QUARTERS AT BHOGAT, GUJARAT (INDIA) PROJECT

Contract No: RJ9TA1000009029 Revision No: C1 Date: 28.07.2009 Page No: 49


Unit Price in Indian Rupees
Item. Amount
Description Unit Qty Rate (Rs) Amount
No. (In Figures)
(In Words)
Supply Erection Supply Erection
E 10.1 Supply, storing, handling, assembling, installation, testing
and commissioning of wall /ceiling, surface/ recessed,
suspended from down rod, in furniture type
fluorescent/incandescent/Halogen lamp fixtures including
making connections with 2.5 Sq.mm. PVC insulated copper
conductor wires complete including steel supports,
suspenders, fixing screws, turn buckles, bolts, nuts (down
rods ball and socket arrangement and special channel
mounting for industrial fitting/chandelier) etc, as required.
The mounting arrangement of lighting fixture shall be as
indicated in the drawings.
a) 2X3.6W FTL Fixture (TCW 596/258 Pc diffuser of Philips or
equipvalent). Nos. 42
b) 2X36W FTL Industrial ftg (TKC 202/236 HF Open of Philips
or equipvalent). Nos. 100
c) 1X36W FTL Industrial ftg (TKC 203/136 of Philips or
equivalent). Nos. 73
d) Mirror light Wipro Cat WRP-21111 or equivalent Nos. 53
e) Low Depth Recessed Down Lighter (Wipro WCP 27218 or
Equivalent) Nos. 1164
f) Night Light Floor mounted with motion sensor Nos. 75
g) Wipro Lighting Industrial fluorescent channel with stove
enameled reflector(WCF 26236SGW) or Equivalent
Nos. 18
h) Wipro Lighting Bottom opening clean room (WIP 43236) or
Equivalent Nos. 25
SCHEDULE OF QUANTITIES
P & C FOR LIVING QUARTERS AT BHOGAT, GUJARAT (INDIA) PROJECT

Contract No: RJ9TA1000009029 Revision No: C1 Date: 28.07.2009 Page No: 50


Unit Price in Indian Rupees
Item. Amount
Description Unit Qty Rate (Rs) Amount
No. (In Figures)
(In Words)
Supply Erection Supply Erection
i) Wipro Lighting Crescent : luminaire with P5 Louvers
(WVP 24236) or Equivalent Nos. 50
j) Wipro Lighting Capsule - Industrial corrosion proof IP 65
luminaire (WIF 83236) or Equivalent Nos. 59
E 10.2 External Lighting

a) Erection of Post top st light pole in cc foundation including


excavation and refilling and fitting of post top fitting
including wiring with 3X2.5mm Sq FR PVC Cu Wire
Complete as required.
Wipro Lighting FPH68150 Fantasy Pathway Luminaries for
road or Equivalent Nos. 230
b) Erection of Bollard Lights on CC Foundation including
wiring/connection etc complete as required.
Wipro Lighting FBP 32126 Integral bollard in die cast
Aluminum with Polycarbonate Diffuser for pathways or
Equivalent Nos. 150
TOTAL OF LIGHTING FIXTURES & FANS CARRIED
OVER TO SUMMARY
E 11.0 EARTHING & LIGHTNING PROTECTION :
E 11.1 Earthing Stations:
SCHEDULE OF QUANTITIES
P & C FOR LIVING QUARTERS AT BHOGAT, GUJARAT (INDIA) PROJECT

Contract No: RJ9TA1000009029 Revision No: C1 Date: 28.07.2009 Page No: 51


Unit Price in Indian Rupees
Item. Amount
Description Unit Qty Rate (Rs) Amount
No. (In Figures)
(In Words)
Supply Erection Supply Erection
E Supply, installation, testing and commissioning of copper
11.1.1 plate earthing stations making earth pits, earthing with
copper earth plate 600 mm x 600 mm x 3 mm thick
including funnel, charcoal/coke, salt, all earth work.
Providing masonry enclosure with 10 mm thick C.I. cover
plate having locking arrangement and watering pipe,
disconnecting/ testing links etc as per IS –3043 complete
as required (DG -8 Nos, Tr-4 Nos, UPS- 2 Nos., Main LT
Panel-2 and Lighting Protection-10)
Nos. 26
E Same as above but earthing with 40 dia 4.5 m long G.I.
11.1.2 earth pipe complete with masonry enclosure cover plate,
watering pipe, charcoal and salt etc. as required..
Nos. 8
E 11.2 Earthing Strip/Wires :
Supply, installation, testing and commissioning of following
sizes of Copper strip/wire clamped to walls, cable trays,
bus ducts, cables in recess or surface direct in ground etc
for equipment/ System earthing complete as required
including inter connection between length at joints, all fixing
accessories saddles, clamps etc and other fixing hardware
material as required for proper installation.
E Copper earthing strip/wire
11.2.2
a) 50 x 6 mm strip RM 200
b) 32 x 6 mm strip RM 100
c) 25 x 3 mm strip RM 100
SCHEDULE OF QUANTITIES
P & C FOR LIVING QUARTERS AT BHOGAT, GUJARAT (INDIA) PROJECT

Contract No: RJ9TA1000009029 Revision No: C1 Date: 28.07.2009 Page No: 52


Unit Price in Indian Rupees
Item. Amount
Description Unit Qty Rate (Rs) Amount
No. (In Figures)
(In Words)
Supply Erection Supply Erection

E 11.3 Air Termination


Supply and fixing of lighting conductor finals (Air
Terminations) with Copper tube 25 mm dia 300 mm long
having single prong at top with 80 mm dia 3 mm thick
Copper base plate including holes etc. complete as
required including riveting, sweating and soldering with
copper tape etc. Nos 10
E 11.4 Providing and fixing Copper tape 20mmX3mm thick on
parapet or surface of wall for lighting conductor complete
as required (for horizontal/vertical run)
Nos 1500
E 11.5 Providing fixing testing joint made of 20mmX3mm thick
Copper strip, 125mm long with 4nos. Of tinned brass bolts,
nuts, check nuts & spring washers etc complete as
required.
Nos 10
E 11.6 Providing and laying Copper tape 32mmX6mm from earth
electrode directly in ground as required.
RM 50
TOTAL OF EARTHING & LIGHTNING PROTECTION
CARRIED OVER TO SUMMARY
E 12.0 CONDUITING CABLING & WIRING FOR COMPUTER
DATA/IP TELEPHONE : .
SCHEDULE OF QUANTITIES
P & C FOR LIVING QUARTERS AT BHOGAT, GUJARAT (INDIA) PROJECT

Contract No: RJ9TA1000009029 Revision No: C1 Date: 28.07.2009 Page No: 53


Unit Price in Indian Rupees
Item. Amount
Description Unit Qty Rate (Rs) Amount
No. (In Figures)
(In Words)
Supply Erection Supply Erection
E 12.1 Supplying and installation of following sizes of PVC conduit
in recess/on surface including all accessories, GI fish wire,
fixing hardware etc including chasing the wall/floor and
plastering the chased portion and making good the
damages etc complete as required.
.
a) 20 mm dia RM 250
b) 25 mm dia RM 250
E 12.2 Supply and installation of plug in type RJ 45 computer data
outlet with dual outlet plate/single outlet plate as required
and with GI outlet box in wall/furniture/floor complete as
required (for data and voice).
Nos. 200
E 12.3 Supplying, laying, installation, testing and commissioning of
CAT-6-4 Pair UTP Data cable in existing conduits/wire
ways. RM 300
E 12.4 Supply, Installation and fixing of following size powder
coated GI Wire ways on ceiling/wall/floor with all associated
hardware as per approved design.
a) 100X50X2mm thick RM 100
b) 150X50X2mm thick RM 50
TOTAL OF CONDUITING CABLING & WIRING FOR
COMPUTER DATA CARRIED OVER TO SUMMARY
E 13.0 CONDUITING, CABLING & WIRING FOR TV SYSTEM :
.
SCHEDULE OF QUANTITIES
P & C FOR LIVING QUARTERS AT BHOGAT, GUJARAT (INDIA) PROJECT

Contract No: RJ9TA1000009029 Revision No: C1 Date: 28.07.2009 Page No: 54


Unit Price in Indian Rupees
Item. Amount
Description Unit Qty Rate (Rs) Amount
No. (In Figures)
(In Words)
Supply Erection Supply Erection
E 13.1 Supplying and installation of following sizes of PVC conduit
in recess/on surface including all accessories, M.S/C.I
Junction/pull boxes, GI fish wire, fixing hardware etc
including chasing the wall/floor & plastering the chased
portion & making good the damage etc complete as
required.
a) 25 mm dia conduit (for RG-11 cable) RM 300
b) 20 mm dia conduit (for RG-6 cable) RM 300
E 13.2 Supply, installation, testing & commissioning of following
splitter boxes :-
a) 2 way splitter No 20
b) 4 way splitter Nos 30
E 13.3 Supply, installation, testing & commissioning of line
extended amplifier 47-862 MHz with return path as per
specifications. Nos 2
E 13.4 Supply, installation, testing & commissioning of RG-11
coaxial in the existing conduits for MV TV System.
RM 500
E 13.5 Supply, installation, testing & commissioning of RG-6
coaxial cable in the existing conduits for MATV.
RM 500
E 13.6 Supplying & installation of TV outlet with grid plate in GI/MS
box including cutting, chases, fixing of GI boxes & cover
plate. Nos. 60
SCHEDULE OF QUANTITIES
P & C FOR LIVING QUARTERS AT BHOGAT, GUJARAT (INDIA) PROJECT

Contract No: RJ9TA1000009029 Revision No: C1 Date: 28.07.2009 Page No: 55


Unit Price in Indian Rupees
Item. Amount
Description Unit Qty Rate (Rs) Amount
No. (In Figures)
(In Words)
Supply Erection Supply Erection
E 13.7 Supplying & installation of set top boxes as per service
provider. Nos. 60
TOTAL OF CONDUITING, CABLING & WIRING FOR TV
SYSTEM CARRIED OVER TO SUMMARY:

NOTE

1 Running meters (RM) for the cable/conduit is approximate. The contractor shall measure the running
meter (RM) & procurement order shall be placed accordingly. The quantities shall be confirmed before
start of work to the Engineer-In charge.

2 The scope includes the designing of the cable TV network for the Living Quarters. Above quantities are
approx. and one to be adjusted as per the requirements. Bidders may quote any left over item which is
required but not included above.

 GENERAL NOTES
1. All the shop drawings, fabrication drawings, drawings for supports and cable laying alongwith cable tray
& conduit etc shall be prepared by the contractor & prior approval shall be taken for the construction of
Electrical Works.
SCHEDULE OF QUANTITIES
P & C FOR LIVING QUARTERS AT BHOGAT, GUJARAT (INDIA) PROJECT

Contract No: RJ9TA1000009029 Revision No: C1 Date: 28.07.2009 Page No: 56

SUMMARY OF COSTS FOR ELECTRICAL WORKS

AMOUNT (Rs.)
S.NO. DESCRIPTION
Supply Erection
1.0 6.6 KV SWITCHGEAR:
2.0 TRANSFORMER:
3.0 H T CABLING :
4.0 BATTERY & BATTERY CHARGER :
5.0 SUB STATION SAFETY EQUIPMENT :
6.0 DG SET :
7.0 M.V. SWITCH GEARS & DISTRIBUTION BOARDS:
8.0 CABLES, SUB MAINS & CABLE TRAYS:
9.0 WIRING :
10.0 LIGHTING FIXTURES & FANS:
11.0 EARTHING & LIGHTNING PROTECTION :
CONDUITING CABLING & WIRING FOR COMPUTER
12.0
DATA/IP TELEPHONE :
13.0 CONDUITING, CABLING & WIRING FOR TV SYSTEM :
TOTAL
Grand Total (Supply + Erection)

Das könnte Ihnen auch gefallen