410040 Rev C (April 2008) Page 1 of 58

Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document
without incurring any obligation either with respect to equipment previously sold or in the process of construction.

Capstone
Capstone Turbine Corporation 21211 Nordhoff Street Chatsworth CA 91311 USA
Phone: (818) 734-5300 Fax: (818) 734-5320 Web: www.microturbine.com
Techni c al Ref er enc e
Modbus Transl at or Modul e
Int roduct i on
This document contains the hardware and software protocol interface definition for the
ModBus Translator board, hereafter referred to as the ModBus Translator. This document is
provided as a reference for existing MicroTurbine configurations that use the Capstone
Power Server, which is no longer manufactured. The Advanced Power Server (APS),
currently supplied by Capstone, has ModBus connectivity built in and does not require the
ModBus Translator.
The ModBus Translator is an electrical device powered from a nominal 12 VDC source that
provides data exchange between the RS-232 port of a Capstone MicroTurbine System and
an RS-485 ModBus network. The ModBus uses a microprocessor to communicate with the
Capstone MicroTurbine System to provide data over a RS-485 ModBus network.
All devices on a bus must operate according to the same electrical standards (RS-232 or RS-
485, not mixed). RS-232C standards specify that only two devices may be connected to a
bus (i.e. only one slave is allowed). RS-485 specifications allow up to 32 devices (31 slaves)
on a bus.



Capstone Turbine Corporation 21211 Nordhoff Street Chatsworth CA 91311 USA
Technical Reference: ModBus Translator Module
410040 Rev C (April 2008) Page 2 of 58
Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document
without incurring any obligation either with respect to equipment previously sold or in the process of construction.
TABLE OF CONTENTS

Introduction......................................................................................................... 1
Overview.............................................................................................................. 4
Hardware Interface.............................................................................................. 7
RS-485 Connector.................................................................................................................. 7
RS232 Connector................................................................................................................... 7
LED Operation........................................................................................................................ 7
Baud Rate Selector ................................................................................................................ 8
Address Selector .................................................................................................................... 8
Specifications...................................................................................................... 9
Power Requirements.............................................................................................................. 9
Environmental Specifications................................................................................................. 9
ModBus Interface.............................................................................................. 10
Description............................................................................................................................ 10
ModBus Address.................................................................................................................. 10
Transaction Timing............................................................................................................... 10
Data Format.......................................................................................................................... 11
ModBus Protocol .............................................................................................. 12
Introduction........................................................................................................................... 12
ModBus RTU Message Framing......................................................................................... 12
ModBus RTU Message Content.......................................................................................... 12
ModBus Function and Exception Codes............................................................................. 13
Supported ModBus Commands .......................................................................................... 14
Read Holding Registers (Function Code 03) ................................................................. 14
Preset Single Register (Function Code 06).................................................................... 15
Preset Multiple Registers (Function Code 16) ............................................................... 15
Read Registers..................................................................................................................... 17
Write Registers..................................................................................................................... 42
Loopback Diagnostic Test (Function Code 08)................................................................... 50
Troubleshooting................................................................................................ 51
Test Modes........................................................................................................ 53
Golden System..................................................................................................................... 53
Unit Under Test Mode.......................................................................................................... 54
Remapping ModBus Registers........................................................................ 55
Capstone Technical Information ..................................................................... 56

Appendix A - ModBus Codeset Download ................................................... A-1
Appendix B - ASCII Chart ............................................................................... B-1
Capstone Turbine Corporation 21211 Nordhoff Street Chatsworth CA 91311 USA
Technical Reference: ModBus Translator Module
410040 Rev C (April 2008) Page 3 of 58
Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document
without incurring any obligation either with respect to equipment previously sold or in the process of construction.
LIST OF TABLES


TABLE DESCRIPTION PAGE NO.

TABLE 1 ERROR RESPONSE FUNCTION CODES........................................................................... 13
TABLE 2 - ERROR CODE VALUE DEFINITIONS................................................................................... 13
TABLE 3 FUNCTION CODE 03 COMMAND (READ HOLDING REGISTERS).................................. 14
TABLE 4 FUNCTION CODE 03 RESPONSE (READ HOLDING REGISTERS)................................ 14
TABLE 5 FUNCTION CODE 06 COMMAND AND RESPONSE (PRESET SINGLE REGISTER)... 15
TABLE 6 FUNCTION CODE 16 COMMAND (PRESET MULTIPLE REGISTERS)........................... 15
TABLE 7 FUNCTION CODE 16 RESPONSE (PRESET MULTIPLE REGISTERS).......................... 16
TABLE 8 - HOLDING REGISTERS (READ ONLY) ................................................................................. 17
TABLE 9 - HOLDING REGISTER (WRITE ONLY) .................................................................................. 43
TABLE 10 FUNCTION CODE 08 COMMAND AND RESPONSE
(LOOPBACK DIAGNOSTIC TEST)................................................................................................... 50
TABLE 11 - MODE SELECTION (ADDRESS) ......................................................................................... 53
TABLE 12 REPORTED TEST CODES.................................................................................................. 53
TABLE 13 - DEBUG RS-232 COMMANDS.............................................................................................. 54
TABLE 14 RELOCATE MODBUS REGISTER RS-232 COMMANDS................................................ 56


Capstone Turbine Corporation 21211 Nordhoff Street Chatsworth CA 91311 USA
Technical Reference: ModBus Translator Module
410040 Rev C (April 2008) Page 4 of 58
Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document
without incurring any obligation either with respect to equipment previously sold or in the process of construction.
Overvi ew
The ModBus Translator is a self-contained pre-programmed unit, designed for instant
connectivity with a Capstone MicroTurbine. There is no customer requirement to open the
unit all necessary connectors are on the exterior of the unit.
There are two steps required to prepare the ModBus Translator for use.
Step 1:
When the ModBus is first prepared for use at the Capstone factory, the ModBus codeset is
downloaded from a local PC to the ModBus using a local RS-232 connection.
NOTE
This download does not need to be performed again by the user except under
special circumstances ! If re-programming must be performed, see Appendix
A, ModBus Codeset Download, for the sequence of required steps.
The figure below shows the hardware connection sequence for ModBus codeset download:






Step 2:
Perform RS-232 connections between the ModBus Translator and the (Model C30 or
C60/C65) MicroTurbine Connection Bay. These interconnections are shown on Figures 1 and
2.




MODBUS
TRANSLATOR
RS-232
MODBUS
TRANSLATOR
RS-232
RS-485
MODBUS
NETWORK
Capstone Turbine Corporation 21211 Nordhoff Street Chatsworth CA 91311 USA
Technical Reference: ModBus Translator Module
410040 Rev C (April 2008) Page 5 of 58
Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document
without incurring any obligation either with respect to equipment previously sold or in the process of construction.

MODBUS
NETWORK
MODBUS TRANSLATOR
6
-
2
4

V
D
C

(
-
)

5

P
O
W
E
R

(
+
)

4



R
S
4
8
5

(
A
)

3



R
S
4
8
5

(
B
)

2










T
E
R
M

1
RS-232
PWR
DATA
1 2 3 4 5 6 7 8 O
N
MODBUS ID
BAUD
RATE
J8
J5 Maintenance J6 User
1
1
TB3
J15 J16
Intra-A MultiPac Intra-B
TB4
TB5
TB1
J7 J9 J14
Inter-Controller
1
1
1
TB2
RESERVED
RESERVED
MODEM 12V+
MODEM 12V-
B-START OPTO+
AI - 1
AGND
AI - 2
AGND
AI - 3
AGND
A 12V POS
A 12V NEG
Option Port
J1
J3
B-START OPTO-
CHASSIS
CHASSIS
L ESTOP RTN
L ESTOP
G ESTOP RTN
G ESTOP
BAT START
BAT START RTN
OPTO+
OPTO -
AI-4
AI-4 RTN
AI-5
AI-5 RTN
AI-6
AI-6 RTN
AI-7
AI-7 RTN
AI-8
AI-8 RTN
AI-9
AI-9 RTN
OPTO 2+
DI-1
OPTO 2-
OPTO 3+
OPTO 3-
DI - RTN
DI-2
DI-3
DI-4
DI - RTN
DI-5
DI-6
AC6-B
AC6-A
AC5-B
AC5-A
AC4-B
AC4-A
AC3-B
AC3-A
AC2-B
AC2-A
AC1-B
AC1-A
MODEL C30
MICROTURBINE
RS-232


Figure 1. ModBus Connections to MicroTurbine (Model C30)
Capstone Turbine Corporation 21211 Nordhoff Street Chatsworth CA 91311 USA
Technical Reference: ModBus Translator Module
410040 Rev C (April 2008) Page 6 of 58
Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document
without incurring any obligation either with respect to equipment previously sold or in the process of construction.

MODBUS
NETWORK
6
-
2
4

V
D
C

(
-
)

5

P
O
W
E
R

(
+
)

4



R
S
4
8
5

(
A
)

3



R
S
4
8
5

(
B
)

2










T
E
R
M

1
RS-232
PWR
DATA
1 2 3 4 5 6 7 8 O
N
MODBUS ID
BAUD
RATE
RS-232
J7 J4
J3 Maintenance
J5 User
J16
J14
1
1
1
1
1 1
J13
J12
J11
J6 J8
Intra-A MultiPac Intra-B
J10
J15
J2 J1
Ethernet
MODEL C60
MICROTURBINE
MODBUS TRANSLATOR


Figure 2. ModBus Connections to MicroTurbine (Model C60/C65)
Capstone Turbine Corporation 21211 Nordhoff Street Chatsworth CA 91311 USA
Technical Reference: ModBus Translator Module
410040 Rev C (April 2008) Page 7 of 58
Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document
without incurring any obligation either with respect to equipment previously sold or in the process of construction.
Har dware Int erface
RS-485 Connect or
Connector - Terminal with Comm A, Comm B, Shield, and GND
Communication - RTU Mode, 8 Data, 1 Stop, Even Parity, Half Duplex (Unless
otherwise noted)
Baud Rate - Selectable
Distance - less than 4000 feet

Pin# Description
1 RS-485 Termination
2 RS-485 Bus B Lead
3 RS-485 Bus A Lead
4 Positive Power Input (+6V to +24V DC)
5 Ground

RS232 Connect or
The connector between the Modbus Translator and the MicroTurbine system is a standard
9-pin straight-through serial cable.
Connector - DB 9-pin (female) following DCE standard (see diagram below)
Communication - 57,600 bps, 8 Data, 1 Stop, No Parity, Half Duplex
Distance less than 50 feet (in relatively noise-free environment)

Pin# Description
1 DCD Data Carrier Detect (output)
2 TXD Transmit Data (output)
3 RXD Receive Data (input)
4 DSR Data Set Ready (input)
5 Signal Ground
6 DTR Data Terminal Ready (output)
7 CTS Clear To Send (input)
8 RTS Request To Send (output)
9 RI Ring Indicator (not used)

LED Operat i on
The ModBus Translator is equipped with two LEDS to provide status feedback about
operation of the device. Illumination of the upper LED occurs when power is applied to the
ModBus Translator. Software shall provide a 2ms pulse on the lower LED when a successful
RS-485 ModBus communication packet is received.
1 2 3 4 5
Female
Pin-5 Pin-1
Pin-6 Pin-9
Capstone Turbine Corporation 21211 Nordhoff Street Chatsworth CA 91311 USA
Technical Reference: ModBus Translator Module
410040 Rev C (April 2008) Page 8 of 58
Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document
without incurring any obligation either with respect to equipment previously sold or in the process of construction.
1 2 3 4 5 6 7 8 O
N
Baud Rat e Sel ect or
An 8-position rotary switch is made available on the board for the purpose of selecting the
baud rate communicated on the RS-485 ModBus link. See the table below for definition of
position vs. baud rate selected. Note position 7 is no parity while all others are even parity.

Position Baud Rate (bps)
0 2400-E-8-1
1 4800-E-8-1
2 9600-E-8-1
3 14400-E-8-1
4 19200-E-8-1
5 28800-E-8-1
6 38400-E-8-1
7 9600-N-8-1

Address Sel ect or
On the side of the ModBus Translator, an 8-position DIP switch that appears as shown:







Each device in an RS-485 ModBus network must have a unique 8-bit address from 1 to 247.
To set the Capstone ModBus Translator address, set the DIP switches to a unique 8-bit
number. Flipping the switches up corresponds to a Logic-1, or ON. Flipping the switches
down corresponds to a Logic-0, or OFF.
Each of the bit positions is numbered such that switch number one is assumed to be the
MSB of the 8-bit address. Remember that for a RS-485 ModBus network to work, every
device on the bus MUST have a different 8-bit address. An example for setting a ModBus
address is shown below.
Address Switch Number (Bit)
1 (7) 2 (6) 3 (5) 4 (4) 5 (3) 6 (2) 7 (1) 8 (0)
147 (93h) ON OFF OFF ON OFF OFF ON ON
90 (5Ah) OFF ON OFF ON ON OFF ON OFF
NOTE: Baud rate is set for 28800 bps.
Capstone Turbine Corporation 21211 Nordhoff Street Chatsworth CA 91311 USA
Technical Reference: ModBus Translator Module
410040 Rev C (April 2008) Page 9 of 58
Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document
without incurring any obligation either with respect to equipment previously sold or in the process of construction.
Speci fi cat i ons
Power Requi rement s
Connector Terminal block with +PWR, -PWR and GND
Voltage Nominal 13.8 VDC (+6 TO +24V)
Amps 300 mA continuous, 500mA peak @nominal voltage

Envi ronment al Speci fi cat i ons
Temperature: -20C to +50C operating
-25C to +70C storage
Humidity: 100% Non-condensing

Capstone Turbine Corporation 21211 Nordhoff Street Chatsworth CA 91311 USA
Technical Reference: ModBus Translator Module
410040 Rev C (April 2008) Page 10 of 58
Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document
without incurring any obligation either with respect to equipment previously sold or in the process of construction.
ModBus Int erface
Descri pt i on
The ModBus network is a MASTER to SLAVE network; that is to say, one node asks a
question and a second node answers. A NODE is a ModBus device that is connected to the
network. All communication is initiated selectively by the MASTER to other nodes by
assigning each SLAVE NODE a unique address in the range of 1 to 247. Address 0 is a
BROADCAST ADDRESS that can be used with certain ModBus functions to allow the
MASTER to address all SLAVE NODES at one time. This device does not respond to
BROADCAST messages.
ModBus Address
Each ModBus device responds to a single ModBus address. The address is in the range of
1 to 247, and each device must have a unique address.
Transact i on Ti mi ng
Commands shall be processed and responded to by the ModBus Translator within 50ms.
Write commands sent to the ModBus Translator are confirmed within 50ms, but updates to
the Capstone MicroTurbine System may not occur for up to 500ms.
Read registers are updated by a polling operation in the converter. Several read registers
may be updated by the ALLDAT command and are designated with an asterisk (*) in Table 8,
RS232 Command column. ALLDAT is sent every 1 second. Other Read registers are
updated in a round robin fashion at varying time intervals designated in the following table.
Whenever a Write command is sent, the MicroTurbine will respond, causing certain Read
registers to update. This will occur within 500ms in all cases.

Read Timing:
1 Response from Translator: 50ms
2 Read Register update from MicroTurbine: See Table 8
Write Timing:
1 Response from Translator: 50ms
2 Response time from MicroTurbine: Max 500ms
3 Update to Read register in Translator Max 500ms

Capstone Turbine Corporation 21211 Nordhoff Street Chatsworth CA 91311 USA
Technical Reference: ModBus Translator Module
410040 Rev C (April 2008) Page 11 of 58
Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document
without incurring any obligation either with respect to equipment previously sold or in the process of construction.
Dat a For mat
Information regarding states and measurements made by the MicroTurbine are placed into a
set of holding registers (4XXXX).
Registers are defined as READ ONLY (less than or equal to 47999) or WRITE and READ
(greater than 48000) registers.
Both Read and Write Registers are converted to two byte values prior to transmission with
the following formula:
Register Number 40001

Example: To read Register 40008, first subtract 40001 resulting in 7. Convert this to two-
byte hex: 0007h. This is the register value transmitted.

Similarly, when reading a Write register, such as 48507, the Register number returned would
be 213Ah, which is (48507-40001 = 8506 = 213Ah)

All data from the ModBus registers is returned in either word (16-bits) or long word (32-bits)
integer format. A long word integer format containing 2 words will always be transmitted high
word first (lower address).

Integer data requires either translation or conversion to engineering units. Translations are
described as an integer value representing some state or level. Integers may be converted to
their corresponding floating-point representation with the units conversions provided.
Information to perform the translation or conversion is described for each register in the
Representation field of the tables.
Capstone Turbine Corporation 21211 Nordhoff Street Chatsworth CA 91311 USA
Technical Reference: ModBus Translator Module
410040 Rev C (April 2008) Page 12 of 58
Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document
without incurring any obligation either with respect to equipment previously sold or in the process of construction.
ModBus Prot ocol
Int roduct i on
The ModBus protocol is an open standard that defines a command-response method of
communicating digital information between a master and slave device. The electrical
connection between devices is known as a bus. In ModBus, two types of devices attach to
the bus, master and slave devices. A master device issues commands to slaves. A slave
device, such as the ModBus Translator device, issues responses to master commands that
are addressed to them. Each bus must contain exactly one master and may contain as
many slaves as the electrical standards permit.
When RS-485 ModBus queries are sent to the translator board, the board responds with data
it has buffered from the MicroTurbine system. ModBus commands to write registers in the
translator board are immediately queued up and transmitted to the MicroTurbine system over
the RS-232 network. Both origination and user responses are buffered and can be read
back.
The ModBus protocol specifications define two types of transmission modes: ASCII and
RTU. This manual describes only the more common RTU mode.
ModBus RTU Message Frami ng
Each message from either a master or slave consists of a continuous stream of characters.
A silent interval of 3.5 characters times (3.5 * 11 bits / 9600 bps = 3.5ms) or more separates
these communication streams. A typical response from this device would be:
Enable the output interface drivers (RS-485)
Wait 5 character times
Send the response as a continuous stream
Wait 3.5 character times
Disable the output interface drivers (RS-485)
ModBus RTU Message Cont ent
The ModBus RTU Message stream consists of an address byte, a function code byte, a
number of message bytes, and two check bytes. The address byte, which is in the range 1 to
247, specifies the identity of the slave device. The function code byte in a master command
indicates the operation that the slave is to perform. The function code byte in a slave
response is the same value as the master command function code if no error occurs,
otherwise it has 128 added to it.
The message bytes in a command contain additional information needed to perform the
command. Message bytes in a response contain the data requested if no error has occurred
or a one-byte exception code upon errors. The check bytes are generated using the CRC-16
polynomial generator sequence (x
16
+ x
15
+ x
2
+ 1) with the remainder pre-initialized to all 1s.
The least significant byte of the CRC is transmitted first.
Capstone Turbine Corporation 21211 Nordhoff Street Chatsworth CA 91311 USA
Technical Reference: ModBus Translator Module
410040 Rev C (April 2008) Page 13 of 58
Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document
without incurring any obligation either with respect to equipment previously sold or in the process of construction.
ModBus Funct i on and Except i on Codes
The ModBus only supports the function codes shown below. Note that the values are shown
in hexadecimal (base 16). The table below shows the value returned when an error occurs.
Table 1 Error Response Function Codes
Master
Function
Code
Slave
Error
Code
Name Meaning
03
16
83
16
Read Holding Registers Read values from system run-time data
06
16
86
16
Preset Holding Registers Set control values to command system
10
16
90
16
Preset Multiple Registers Set control values of multiple register
values

The ModBus will return exception codes back to the master upon certain conditions. All
function codes greater than 127 decimal (7F
16
) indicate a slave error response. The
message byte indicates the exception code. The table below shows error code value
definitions.
Table 2 - Error Code Value Definitions
Code Name Meaning
1 Illegal Function Master command contained an unrecognized function code.
2 Illegal Data Address Starting address is illegal. Note that some registers are read-
only.
3 Illegal Data Value Either the register count is invalid or an attempt to write an
illegal register value was found. Note this can be caused by
attempting to write fewer registers than are required for an
operation.
4 Slave Device Failure Some internal self-test of the device has failed.
6 Slave Device Busy Not communicating with MicroTurbine system
Capstone Turbine Corporation 21211 Nordhoff Street Chatsworth CA 91311 USA
Technical Reference: ModBus Translator Module
410040 Rev C (April 2008) Page 14 of 58
Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document
without incurring any obligation either with respect to equipment previously sold or in the process of construction.
Suppor t ed ModBus Commands
The ModBus supports one read and two write commands. Example transmissions are
provided with the definition of each command below.
Read Hol di ng Regi st ers (Funct i on Code 03)
This function reads a single or multiple holding register values. The command requires a
Slave Address, Function Code, Start Address, Register Count, and CRC16. Attempting to
read a non-existent or write-only register will cause an exception.
The example shown in the table below shows how to read the system Power Output value
starting at register 42107 and ending with 42108.
Table 3 Function Code 03 Command (Read Holding Registers)
Byte Name Example Notes
1 Slave Address 01
2 Function Code 03
3 Start address high 08 Power Output at register 42107 (42107-40001
= 2106 = 083Ah)
4 Start address low 3A
5 Register count high 00
6 Register count low 02 Read 2 registers total
7 CRC-16 low XX
8 CRC-16 high XX

Table 4 Function Code 03 Response (Read Holding Registers)
Byte Name Example Notes
1 Slave Address 01
2 Function Code 03
3 Byte Count 04 2 registers, 2 bytes each
4 Data high (42107) 00 Power Output = 00006AAAh = 27306 decimal
5 Data low (42107) 00 Applying the units conversion = 149,996 Watts
6 Data high (42108) 6A
7 Data low (42108) AA
8 CRC-16 low XX
9 CRC-16 high XX

Capstone Turbine Corporation 21211 Nordhoff Street Chatsworth CA 91311 USA
Technical Reference: ModBus Translator Module
410040 Rev C (April 2008) Page 15 of 58
Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document
without incurring any obligation either with respect to equipment previously sold or in the process of construction.
Preset Si ngl e Regi st er (Funct i on Code 06)
This function writes to a single register. The command requires a Slave Address, Function
Code, Start Address, Data, and CRC16. Attempting to write to a read-only register will cause
an exception. The example shown in the table below shows how to set the Time of Use
Event value at register 48507.
Table 5 Function Code 06 Command and Response (Preset Single Register)
Byte Name Example Notes
1 Slave Address 01
2 Function Code 06
3 Start address high 21 Time of Use Event at register 48507 (48507-
40001 = 8506 = 213Ah)
4 Start address low 3A
5 Data high 00 Set Event to number 5
6 Data low 05
7 CRC-16 low XX
8 CRC-16 high XX

Preset Mul t i pl e Regi st ers (Funct i on Code 16)
This function writes to one or more contiguous registers. The command requires a Slave
Address, Function Code, Start Address, Register count, Byte count, Data, and CRC16.
Attempting to write to a read-only register will cause an exception. The table below shows
how to enter a Time of Use Event value at register 48507.
Table 6 Function Code 16 Command (Preset Multiple Registers)
Byte Name Example Notes
1 Slave Address 01
2 Function Code 10
3 Start address high 21 Time of Use Event at register 48507 (48507-
40001 = 8506 = 213Ah)
4 Start address low 3A
5 Register count high 00 Writing to 6 registers (48507 48512)
6 Register count low 06
7 Byte count 0C 6 registers, 2 bytes each
8 Data high 00 Time of Use Event = 5
9 Data low 05
10 Data high 00 Event Day = 1 Sunday
11 Data low 01
12 Data high 08 Event Time = 080F hex (8:15AM)
13 Data low 0F
14 Data high 00 Start Command = 1 Start
15 Data low 01
16 Data high 00 Power Demand = 159,000 Watts = 26D18 H
17 Data low 02
Capstone Turbine Corporation 21211 Nordhoff Street Chatsworth CA 91311 USA
Technical Reference: ModBus Translator Module
410040 Rev C (April 2008) Page 16 of 58
Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document
without incurring any obligation either with respect to equipment previously sold or in the process of construction.
Table 6 Function Code 16 Command (Preset Multiple Registers) Contd
Byte Name Example Notes
18 Data high 6D
19 Data low 18
20 CRC-16 low XX
21 CRC-16 high XX

Table 7 Function Code 16 Response (Preset Multiple Registers)
Byte Name Example Notes
1 Slave Address 01
2 Function Code 10
3 Start address high 21 Time of Use Event at register 48507 (48507-
40001 = 8506 = 213Ah)
4 Start address low 3A
5 Register count high 00 Writing to 6 registers (48507 48512)
6 Register count low 06
7 CRC-16 low XX
8 CRC-16 high XX

Capstone Turbine Corporation 21211 Nordhoff Street Chatsworth CA 91311 USA
Technical Reference: ModBus Translator Module
410040 Rev C (April 2008) Page 17 of 58
Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document
without incurring any obligation either with respect to equipment previously sold or in the process of construction.
Read Regi st er s
All read registers associated with a write register shall be updated within 500ms of a
successful ModBus write operation. This provides time for the device to issue an RS-232
operation with the MicroTurbine

system and verify the change has occurred.
NOTE
Read registers which may be updated with the ALLDAT command are
indicated by an asterisk (*) following the RS232 command in Table 8.
Two ModBus Translator modes of operation are Stationary, S in Table 8, and Hybrid
Electric Vehicle (HEV), H in Table 8. These modes are mutually exclusive.
NOTE
The character H in the Mode column of Table 8 indicates both C30 and
C60/C65 HEV. If the register does not apply to C30, it is noted by N3 in
parentheses. If the register does not apply to C60/C65, it is noted by N6 in
parentheses.
Another mode of operation, for connections to a Capstone Power Server (CPS) is also
provided. By selecting either mode (Write Register 48021), the system will provide different
command options as described in the table below.
Table 8 - Holding Registers (Read Only)
Register Mode Description Representation
RS232
Command
Timing
(Sec)
General Communication Info
40001 S,H Selected Turbine
(See Write Register 48001)
0 This Turbine/Entire
System
1 Master Turbine
2 thru 10 Specific Turbine
TURBNO,0 1
40002 S,H Communication Status Bit 0 Unable to establish
communication with the
MicroTurbine system
(Error = 1)
NA NA
40003 S,H Control Access 0 Display
1 User Port
2 Maintenance Port
CNTACC 10
40004 S,H Communication
Configuration
1

Bit 0 1: Mode Bits
0 = Stationary
1 = HEV
2 = CPS
3 = Reserved
Bit 2 14: Not Used
Bit 15: Comm Timeout
Enable
NA On Reg
48021
Update

1
User selects which mode of operation the ModBus Translator operates. Setting Bit 15 Comm Timeout
Enable will cause a STRCMD=0 to be transmitted to the MicroTurbine
TM
system when a ModBus command
has not been received within time defined by the Comm Timeout Period (addr 40005) and Start Command
(addr 40101) is Start. Default setting is 0000
h
.
Capstone Turbine Corporation 21211 Nordhoff Street Chatsworth CA 91311 USA
Technical Reference: ModBus Translator Module
410040 Rev C (April 2008) Page 18 of 58
Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document
without incurring any obligation either with respect to equipment previously sold or in the process of construction.
Register Mode Description Representation
RS232
Command
Timing
(Sec)
40005 S,H
Comm Timeout Period
2

Units: 1 = 1 Seconds NA On Reg
48022
Update
40006 S,H Password Access Level 0 Base
1 Protected
NA (prompt
feedback)
NA
40007 ModBus Translator Software
Version
Encoded (xx.yy) where,
High Byte - (xx)
Low Byte - (yy)
NA NA
40008
40013
ModBus Translator Software
Part Number
Each byte represents an
ASCII character. String is
NULL terminated.
NA NA

System Controls/Settings
40101 S,H Start Command (displays
when the system is going
to start)
0 Stop, 1 Start CTRLDT(9)* 1
40102 S User Start (displays when
user has commanded a
start)
0 Stop, 1 Start USRSTR 2
40103 S,H Auto Restart 0 Disabled, 1 Enabled AUTRST 10
40104 S Restart Delay (GC) Units: 1 = 0.1 Minutes RDLYGC 10
40105 S Restart Delay (SA) Units: 1 = 0.1 Minutes RDLYSA 10
40106 S Remote Start Switch Enable 0 User
1 Remote
2 GC User/SA Remote
3 SA User/GC Remote
STRINP 10
40107 S Remote Start Input Status
(UCB Start Input)
0 Stop, 1 Start UCBSTR 10
40108 S Utility Connection 0 Invalid,
1 StandAlone,
2 Grid Connect,
3 Dual Mode
UTLCON 1
40109 S Power Enable (SA only) 0 Open, 1 Closed CTRLDT(2)* 1
40110 S Auto Load (SA only) 0 Disabled, 1 Enabled AUTOLD 10
40111
40112
S,H Power Demand Units: 1 = 1 Watt CTRLDT(7)* 1
40113
40114
S,H Store Power Demand Units: 1 = 1 Watt PWRDST 10
40115 S,H Fuel Index 1 Units: 1 = 0.01 index FUELI1 10
40116 S,H Fuel Index 2 Units: 1 = 0.01 index FUELI2 10
40117 S,H Medium BTU Switch 0 Normal
1 Medium
2 Low
MEDBTU 10
40118 S MultiPac Enable 0 Disabled, 1 Enabled MPENAB 10

2
Function is enabled when bit 15 of register 40004 is enabled. Default Comm Timeout Period is 10
seconds (can be changed at addr 48022). If the Comm Timeout Period setting exceeds 5 minutes, then the
Comm Timeout Enable function will not work.
Capstone Turbine Corporation 21211 Nordhoff Street Chatsworth CA 91311 USA
Technical Reference: ModBus Translator Module
410040 Rev C (April 2008) Page 19 of 58
Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document
without incurring any obligation either with respect to equipment previously sold or in the process of construction.
Register Mode Description Representation
RS232
Command
Timing
(Sec)
40119 S,H
(N3)
This Turbines Number Master: 1
Slave: 2 thru 10
STRBNO 10
40120 S,H
(N3)
Minimum Power Units: 1 = 1 Watt MINPWR 10
40122 S,H
(N3)
Minimum Power Timeout Units: 1 = 1 sec MPWRTO 10

Grid Connect Relays
40301 S Under Voltage (GC) Units: 1 = 1 VAC (line-to-line) UNDVLT 10
40302 S Under Voltage Time (GC) Units: 1 = 0.01 Seconds UVLTTM 10
40303 S Over Voltage (GC) Units: 1 = 1 VAC (line-to-line) OVRVLT 10
40304 S Over Voltage Time (GC) Units: 1 = 0.01 Seconds OVLTTM 10
40305 S Fast Under Voltage (GC) Units: 1 = 1 VAC (line-to-line) FSTUVL 10
40306 S Fast Over Voltage (GC) Units: 1 = 1 VAC (line-to-line) FSTOVL 10
40307 S Under Frequency (GC) Units: 1 = 0.1 Hz UNDFRQ 10
40308 S Under Frequency Time (GC) Units: 1 = 0.01 Seconds UFRQTM 10
40309 S Over Frequency (GC) Units: 1 = 0.1 Hz OVRFRQ 10
40310 S Over Frequency Time (GC) Units: 1 = 0.01 Seconds OFRQTM 10

Stand Alone Relays


40401 S Output Voltage (SA) Units: 1 = 1 VAC (line-to-line) SAVOLT 10
40402 S Voltage Start (SA) Units: 1 = 1 VAC (line-to-line) STVOLT 10
40403 S Voltage Ramp (SA) Units: 1 = 1 VAC/s (line-to-
line)
STVTRT 10
40404 S Under Voltage (SA) Units: 1 = 1 VAC (line-to-line) SAUVLT 10
40405 S Under Voltage Time (SA) Units: 1 = 0.01 Seconds SAUVTM 10
40406 S Over Voltage (SA) Units: 1 = 1 VAC (line-to-line) SAOVLT 10
40407 S Over Voltage Time (SA) Units: 1 = 0.01 Seconds SAOVTM 10
40408 S Output Frequency (SA) Units: 1 = 0.1 Hz SAFREQ 10
40409 S Frequency Start (SA) Units: 1 = 0.1 Hz STFREQ 10
40410 S Frequency Ramp (SA) Units: 1 = 1 Hz/s STFQRT 10
40411 S Under Frequency (SA) Units: 1 = 0.1 Hz SAUFRQ 10
40412 S Under Frequency Time (SA) Units: 1 = 0.01 Seconds SAUFTM 10
40413 S Over Frequency (SA) Units: 1 = 0.1 Hz SAOFRQ 10
40414 S Over Frequency Time (SA) Units: 1 = 0.01 Seconds SAOFTM 10

Load Management Settings
40501 S Load Management Mode 0 Disabled
2 Load Following
3 Time-of-Use
LMMODE 10
40502 S Meter Constant Units: 1 = 0.001 Wh/pulse LMMTRC 10
40503 S Utility Power Setpoint Units: 1 = 0.1 kW LMUTPW 10
40504 S Load Following Response
Time
Units: 1 = 1 Second LMRSPT 10
Capstone Turbine Corporation 21211 Nordhoff Street Chatsworth CA 91311 USA
Technical Reference: ModBus Translator Module
410040 Rev C (April 2008) Page 20 of 58
Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document
without incurring any obligation either with respect to equipment previously sold or in the process of construction.
Register Mode Description Representation
RS232
Command
Timing
(Sec)
40505
40506
S Minimum Power Shutoff Units: 1 = 0.1 kW LMMPWR 10
40507 S Minimum Power Shutoff
Time
Units: 1 = 1 Minute LMPWTM 10
40508 S Time of Use Event
(See Write register 48507 to
Set)
Min: 1
Max: 20
N/A On Reg
48507
Update
40509 S TOU Event Day 0 Inactive
1 Sunday
7 Saturday
LMTOUE(1) On Reg
48507
Update
40510 S TOU Event Hour High Byte Hour
Low Byte Minute
LMTOUE(2) On Reg
48507
Update
40511 S TOU Event Start Command 0 Stop, 1 Start LMTOUE(3) On Reg
48507
Update
40512
40513
S TOU Event Power Demand Units: 1 = 1 Watt LMTOUE(4) On Reg
48507
Update
40514 S Reverse Power Protect 0 Disabled, 1 Enabled LMRPFP 10
40515 S
Reverse Power Protect Time
Units: 1 = 1 Seconds LMRPTM 10
40551 S
Load Management Start/Stop
0 Stop, 1 Start LMDATA(0) 5
40552
40553
S Power Meter +Pwr Units: 1 = 1 Watt LMDATA(1) 5
40554
40555
S Power Meter Pwr Units: 1 = 1 Watt LMDATA(2) 5
40556
40557
S Power Meter +VAR Units: 1 = 1 VAR LMDATA(3) 5
40558
40559
S Power Meter VAR Units: 1 = 1 VAR LMDATA(4) 5

UCB Relays
40601 S Relay Number
(See Write register 48507 to
Set)
Min: 1
Max: 6
N/A On Reg
48601
Update
40602 S Relay Function 0 Standby
1 Run
2 Load
3 Fault
4 Standalone
5 Dual Mode
6 Disable
7 Fuel On
8 Purge
OUTRLY(1) On Reg
48601
Update
40603 S Relay Active State 0 Open, 1 Close OUTRLY(2) On Reg
48601
Update
Capstone Turbine Corporation 21211 Nordhoff Street Chatsworth CA 91311 USA
Technical Reference: ModBus Translator Module
410040 Rev C (April 2008) Page 21 of 58
Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document
without incurring any obligation either with respect to equipment previously sold or in the process of construction.
Register Mode Description Representation
RS232
Command
Timing
(Sec)
Battery Information
40701 S Battery Enabled 0 Disabled, 1 Enabled BATENA 2
40702 S Battery Auto Sleep Units: 1 = 0.1 Hours
Min: 1 = 0.1 Hours
Max: 239 = 23.9 Hours
ATOSLP 10
40703 S Battery Charge 0 Disabled, 1 Enabled BATCHG 5
40704 S Battery Recharge Enable
(SA only)
0 Disabled, 1 Enabled RCHENA 2
40705
40706
S Last Equalization Charge
Date
Word 1, High Byte Month
Word 1, Low Byte Day
Word 2 - Year
BATEQL 30
40707 S Charge Permission Day
(See Write register 48507 to
Set)
1 Sunday
2 Monday
7 Saturday
N/A On Reg
48707
Update
40708 S Charge Permission Active 0 Inactive, 1 - Active CHGEQP(1) On Reg
48707
Update
40709 S Charge Permission Start
Time
High Byte Hour
Low Byte Minute
CHGEQP(2) On Reg
48707
Update
40710 S Charge Permission End Time High Byte Hour
Low Byte Minute
CHGEQP(3) On Reg
48707
Update
40711 S Battery Temperature Units: 1 = 1 C BCDAT1(0)* 1
40712 S Battery Base SOC % Battery state of charge BCDAT1(5)* 10
40713 S Number of Equalization
Charges
Integer number BATDAT 10
40714 S, H
(N3)
BCT Heatsink Temperature Units: 1 = 1 C BCDAT1(2)* 10
40715 S, H
(N3)
Battery Average Current Units: 1 = 0.048828125 A BCDAT1(11)* 10
40716 S, H
(N3)
Battery Volts Units: 1 = 0.048828125 Vdc BCDAT1(12)* 10
40717 S, H
(N3)
BCT DC Bus Units: 1 = 0.048828125 Vdc BCDAT1(13)* 10
40718 S, H
(N3)
Battery Average Power Units: 1 = 1.220703 Watts BCDAT1(14)* 10
40719 S, H
(N3)
Battery State 0 = BATT_SA_TRANS
1 = BATT_IN_SA
2 = BATT_ENA_CHK
3 = BATT_TURN_ON
4 = BATT_WAIT_FOR_OFF
5 = BATT_TURN_OFF
6 = BATT_TURN_ON_CHG
7 = BATT_START_CHG
8 = BATT_CHARGING
9 = BATT_EQCHG_UPDATE
BCDAT1(16)* 10
Capstone Turbine Corporation 21211 Nordhoff Street Chatsworth CA 91311 USA
Technical Reference: ModBus Translator Module
410040 Rev C (April 2008) Page 22 of 58
Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document
without incurring any obligation either with respect to equipment previously sold or in the process of construction.
Register Mode Description Representation
RS232
Command
Timing
(Sec)
Hybrid Vehicle Relays
40801 H Under Voltage (HEV) Units: 1 = 1 V
DC
UNDVLT 10
40802 H Under Voltage Time (HEV) Units: 1 = 0.01 Seconds UVLTTM 10
40803 H Over Voltage (HEV) Units: 1 = 1 V
DC
OVRVLT 10
40804 H Over Voltage Time (HEV) Units: 1 = 0.01 Seconds OVLTTM 10
40805 H Fast Under Voltage (HEV) Units: 1 = 1 V
DC
FSTUVL 10
40806 H Fast Over Voltage (HEV) Units: 1 = 1 V
DC
FSTOVL 10
40807 H Battery Current Limit Units: 1 = 1 A
DC

Min: 0 = 0 A
DC

Max: 195 = 195 A
DC

BATILM 10

Capstone Power Server
(CPS)

40808 C Min Power Capacity, Grid
Connect
Units: 1 = 1 Watt
Min: 0 Watts
Max: 2,000,000,000 Watts
MPCPGC 1
40810 C Min Power Capacity, Stand
Alone
Units: 1 = 1 Watt
Min: 0 Watts
Max: 2,000,000,000 Watts
MPCPSA 1
40812 C Spinning Reserve, Grid
Connect
Units: 1 = 1 Watt
Min: 0 Watts
Max: 2,000,000,000 Watts
MPSRGC 1
40814 C Spinning Reserve, Stand
Alone
Units: 1 = 1 Watt
Min: 0 Watts
Max: 2,000,000,000 Watts
MPSRSA 1
40816 C Multipac Mode 0 Load Balancing,
1 Max Efficiency
MPMODE 1
40817 S,H System Type 0 Capstone Power Server,
1 C30 MicroTurbine,
2 C60/C65 MicroTurbine
SYSTYP 1

Data Acquisition
42001
42002
S,H System Date Word 1, High Byte Month
Word 1, Low Byte Day
Word 2 Year
ENGDT1(0)*
ENGDT1(1)*
ENGDT1(2)*
1
42003
42004
S,H System Time Word 1 Hour
Word 2, High Byte Minute
Word 2, Low Byte Second
ENGDT1(3)*
ENGDT1(4)*
ENGDT1(5)*
1
42005 S,H High Fault Identification
Number





Integer Fault Number ENGDT2(0)* 1
Capstone Turbine Corporation 21211 Nordhoff Street Chatsworth CA 91311 USA
Technical Reference: ModBus Translator Module
410040 Rev C (April 2008) Page 23 of 58
Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document
without incurring any obligation either with respect to equipment previously sold or in the process of construction.
Register Mode Description Representation
RS232
Command
Timing
(Sec)
42006 S,H System Severity Level 0 System Ok
1 Information
2 Warning
3 Shutdown
4 Inverter Loss
5 Warmdown
6 Estop
7 Disable
ENGDT2(10)* 1
42007 S,H System State and Mode Mode Bits 15-12
0 Invalid
1 Reserved
2 Standalone
3 Grid-Connect
4 Reserved
State Bits 11 0
0 Not Connected
1 StandBy
2 Prepare to Start
3 Lift-off
4 Prepare to Light
5 Start Acceleration
6 Run
7 Load
8 Re-charge
9 Cooldown
10 Warmdown
11 Re-start
12 Shutdown
13 Fault
14 Disable
15 Bad Configuration
16 Download
17 Idle Re-charge


















CTRLDT(0)* 1
Capstone Turbine Corporation 21211 Nordhoff Street Chatsworth CA 91311 USA
Technical Reference: ModBus Translator Module
410040 Rev C (April 2008) Page 24 of 58
Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document
without incurring any obligation either with respect to equipment previously sold or in the process of construction.
Register Mode Description Representation
RS232
Command
Timing
(Sec)
42008 -
42009
S,H Bitmapped System State and
Mode.
(Only 1 bit each for Mode and
State can be set at any time.
Register 42009 contains the
lower order bits Bit 0 through
Bit 15, Bits 16 31 are in
register 42008)
Mode Bits 28 - 31
Bit 28 Invalid
Bit 29 Reserved
Bit 30 Standalone
Bit 31 Grid-Connect

State Bits 0 - 27
Bit 0 Not Connected
Bit 1 StandBy
Bit 2 Prepare to Start
Bit 3 Lift-off
Bit 4 Prepare to Light
Bit 5 Start Acceleration
Bit 6 Run
Bit 7 Load
Bit 8 Re-charge
Bit 9 Cooldown
Bit 10 Warmdown
Bit 11 Re-start
Bit 12 Shutdown
Bit 13 Fault
Bit 14 Disable
Bit 15 Bad Configuration
Bit 16 Download
Bit 17 Idle Re-charge
CTRLDT(0)* 1
42010 S,H DPC / Gen Power Units: 1 = 1 Watt ENGDT1(7)* 1
42012 S,H Wenergy Units: 1 = 0.0078125 btu/sec ENGDT1(16)* 1
42013 S,H TET Setpoint Units: 1 = 0.125 C ENGDT2(3)* 1
42014
42015
S,H Combustor Time Word 1 - Hours
Word 2, High Byte - Minutes
Word 2, Low Byte - Seconds
ENGDT2(7)*
ENGDT2(8)*
ENGDT2(9)*
1
42101
42102
S Phase A Power Average Units: 1 = 2.7465820 Watts INVDT2(4)* 1
42103
42104
S Phase B Power Average Units: 1 = 2.7465820 Watts INVDT2(5)* 1
42105
42106
S Phase C Power Average Units: 1 = 2.7465820 Watts INVDT2(6)* 1
42107
42108
S,H Power Output Units: 1 = 5.4931641 Watts INVDT2(7)* 1
42109
42110
S,

H (N6)
Output Phase A Current Units: 1 = 1.8310547e-02
A
RMS

Units: 1 = 1.8310547e-02
A
DC
INVDT1(7)* 1
42111
42112
S,

H (N6)
Output Phase B Current Units: 1 = 1.8310547e-02
A
RMS

Units: 1 = 1.8310547e-02
A
DC
INVDT1(8)* 1
Capstone Turbine Corporation 21211 Nordhoff Street Chatsworth CA 91311 USA
Technical Reference: ModBus Translator Module
410040 Rev C (April 2008) Page 25 of 58
Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document
without incurring any obligation either with respect to equipment previously sold or in the process of construction.
Register Mode Description Representation
RS232
Command
Timing
(Sec)
42113
42114
S,

H (N6)
Output Phase C Current Units: 1 = 1.8310547e-02
A
RMS

Units: 1 = 1.8310547e-02
A
DC
INVDT1(9)* 1
42115
42116
S,

H (N6)
Output Neutral Current Units: 1 = 1.8310547e-02
A
RMS

Units: 1 = 1.8310547e-02
A
DC
INVDT2(0)* 1
42117
42118
S,

H (N6)
Total 3 Phase Current Units: 1 = 1.8310547e-02
A
RMS

Units: 1 = 1.8310547e-02
A
DC
Sum of
currents from
regs 42109
thru 42114
With
registers
listed
42119 S,

H (N6)
Output Phase A Voltage Units: 1 = 1.8310547e-02
V
RMS

Units: 1 = 1.8310547e-02
V
DC
INVDT2(1)* 1
42120 S,

H (N6)
Output Phase B Voltage Units: 1 = 1.8310547e-02
V
RMS

Units: 1 = 1.8310547e-02
V
DC
INVDT2(2)* 1
42121 S,

H (N6)
Output Phase C Voltage Units: 1 = 1.8310547e-02
V
RMS

Units: 1 = 1.8310547e-02
V
DC
INVDT2(3)* 1
42122 S Output AC Frequency Units: 1 = 0.0625 Hz INVDT1(3)* 1
42123 S,H Power Supply Voltage Units: 1 = 0.0625 Volts CTRLDT(8)* 1
42124 S Inverter DC Bus Units: 1 = 0.29296875 V INVDT1(0)* 1
42125 S Inverter Direct Current Units: 1 = 0.004577637 A INVDT1(1)* 1
42126 S Inverter Heat Sink
Temperature
Units: 1 = 1 C INVDT2(8)* 1
42127 S Inverter Current Limit Units: 1 = 0.29296875 A INVDT2(9)* 1
42128 S Inverter Quadrature Current Units: 1 = 0.29296875 A INVDT1(2)* 1
42129 S Phase A Volt Magnitude Units: 1 = 0.29296875 V INVDT1(4)* 1
42130 S Phase B Volt Magnitude Units: 1 = 0.29296875 V INVDT1(5)* 1
42131 S Phase C Volt Magnitude Units: 1 = 0.29296875 V INVDT1(6)* 1
42151 S,H Generator Direct Current Units: 1 = 0.29296875 A GENDT1(0)* 1
42152 S,H Generator Direct Voltage Units: 1 = 0.29296875 V GENDT1(2)* 1
42153
42154
S,H Generator Speed Command Units: 1 = 1 rpm GENDT1(4)* 1
42155 S,H Generator Quadrature
Current
Units: 1 = 0.29296875 A GENDT1(1)* 1
42156 S,H Generator Quadrature
Voltage
Units: 1 = 0.29296875 V GENDT1(3)* 1
42157 S,H Generator Voltage
Command
Units: 1 = 0.29296875 V GENDT1(5)* 1
42158 S,H Generator Current Limit Units: 1 = 0.29296875 A GENDT2(1)* 1
Capstone Turbine Corporation 21211 Nordhoff Street Chatsworth CA 91311 USA
Technical Reference: ModBus Translator Module
410040 Rev C (April 2008) Page 26 of 58
Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document
without incurring any obligation either with respect to equipment previously sold or in the process of construction.
Register Mode Description Representation
RS232
Command
Timing
(Sec)
42159 S,H Generator Heat Sink
Temperature
Units: 1 = 1 C GENDT2(2)* 1
42160 S,H Brake Temperature Units: 1 = 1 C GENDT2(3)* 1
42161
42162
S,H Generator Power Out Units: 1 = 2.746582 Watts GENDT2(5)* 1
42163
42164
S,H Generator Speed Units: 1 = 1 rpm GENDT2(6)* 1
42165 S,H Generator DC Bus Voltage Units: 1 = 0.9765625 V GENDT2(7)* 1
42166 S,H Generator Command Value Units: 1 = 0.29296875 A GENDT2(8)* 1
42201 S,H Ambient Pressure Units: 1 = 0.01 kPa ENGDT1(15)* 1
42202 S,H Compressor Inlet Temperature Units: 1 = 0.125 C ENGDT1(11)* 1
42203
42204
S,H Engine Speed Units: 1 = 1 RPM ENGDT1(6)* 1
42205 Reserved
42206 S,H Turbine Exhaust Temp Avg. Units: 1 = 0.125 C ENGDT1(10)* 1
42207 S,H Percent Fuel Command Units: 1 = 0.1% Cmd PRFUEL 2
42208 Fuel Pressure (Reserved)
42209
42210
C Present Min Power Capacity Units: 1 = 1 Watt
Min: 0 Watts
Max: 2,000,000,000 Watts
MPDAT1(0) On
Demand,
No
Refresh
42211
42212
C Present Spinning Reserve Units: 1 = 1 Watt
Min: 0 Watts
Max: 2,000,000,000 Watts
MPDAT1(1) On
Demand,
No
Refresh
42213
42214
S,
H (N6)
Inlet Fuel Pressure HP Units: 1 = 0.0625 psig SPVDAT(1)* On
Demand,
No
Refresh
42215 S,
H (N6)
SPV Injector State Model C30 MicroTurbine:
0 = Fuel Init
1 = Warm-up
2 = One Pilot
3 = Three Pilot
4 = Premix
Model C60/C65 MicroTurbine:
0 = Fuel Init
2 = Injectors 1, 2 on
3 = Injectors 1, 2, 3 on
4 = Injectors 1, 2, 3, 4 on
5 = Injectors 1, 2, 3, 4, 5 on
6 = All six injectors on
9 = Light off
SPVDAT(2)* On
Demand,
No
Refresh
42216 S,
H (N6)
SPV Temperature Units: 1 = 1 F SPVDAT(3)* On
Demand,
No
Refresh
Capstone Turbine Corporation 21211 Nordhoff Street Chatsworth CA 91311 USA
Technical Reference: ModBus Translator Module
410040 Rev C (April 2008) Page 27 of 58
Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document
without incurring any obligation either with respect to equipment previously sold or in the process of construction.
Register Mode Description Representation
RS232
Command
Timing
(Sec)
42217 S,
H (N6)
SPV Fuel Exit Pressure Units: 1 = 0.0625 psig SPVDAT(4)* On
Demand,
No
Refresh
42218 S,
H (N6)
SPV Position Command Units: 1 = 0.1% SPVDAT(0)* On
Demand,
No
Refresh
42220 S (N3) CHP Enabled 0=Disabled, 1=Enabled CHPTRU(0) 10
42221 S (N3) CHP Mode 0 = Thermal Bypass
1 = Electrical Priority
2 = Thermal Priority
CHPDAT(0)* On
Demand,
No
Refresh
42222 S (N3) CHP Water Setpoint Units: 1 = 1 F CHPDAT(2)* On
Demand,
No
Refresh
42223 S (N3) CHP State 0 = Inactive
1 = Wait State
2 = Water Temp Load
Following
3 = Electrical Load Following
4 = Max Heat Recovery
5 = Self-test Start
6 = Self-test Recovery
Direction
7 = Self-test Bypass Direction
8 = Self-test Complete
9 = Disable Wait State
CHPDAT(1)* On
Demand,
No
Refresh
42224 S (N3) CHP Water Inlet
Temperature
Units: 1 = 1 F CHPDAT(3)* On
Demand,
No
Refresh
42225 S (N3) CHP Water Outlet
Temperature
Units: 1 = 1 F CHPDAT(4)* On
Demand,
No
Refresh
42226 S (N3) CHP Board Temperature Units: 1 = 1 F CHPDAT(5)* On
Demand,
No
Refresh
42227 S (N3) CHP Bridge Current Units: 1 = 0.001 A CHPDAT(6)* On
Demand,
No
Refresh
Capstone Turbine Corporation 21211 Nordhoff Street Chatsworth CA 91311 USA
Technical Reference: ModBus Translator Module
410040 Rev C (April 2008) Page 28 of 58
Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document
without incurring any obligation either with respect to equipment previously sold or in the process of construction.
Register Mode Description Representation
RS232
Command
Timing
(Sec)
42228 S (N3) CHP Status 0 = Aux In
1 = Aux Out
2 = Flow
3 = Overtemp Core
5 = Diverter at Full Recovery
6 = Diverter at Full Bypass
7 = Moving toward Recovery
8 = Moving toward Bypass
9 = Over Current towards
Recovery
10 = Over Current towards
Bypass
11 = Under Current towards
Recovery
12 = Under Current towards
Bypass
15 = Over Current in no
motion state
28 = PIC EEPROM (PM)
CRC Error
29 = PIC ADC Conversion
Error
30 = PIC RAM
31 = PIC Communication
Timeout
CHPDAT(9)* On
Demand,
No
Refresh
42230 S (N3) CHP Temperature Feedback Units: 1 = 1 F CHPFBK(0) 5
42241 S (N6) RFC Command Units: 1 = 1 rpm RFCDAT(0)* On
Demand,
No
Refresh
42242 S (N6) RFC Mode 1 = Speed Mode
2 = Pressure Mode
RFCDAT(1)* On
Demand,
No
Refresh
42243 S (N6) RFC Pressure In Units: 1 = 0.0625 psig RFCDAT(2)* On
Demand,
No
Refresh
42244 S (N6) Fuel Outlet Pressure LP Units: 1 = 0.0625 psig RFCDAT(3)* On
Demand,
No
Refresh
42245 S (N6) HeatSink Temperature Units: 1 = 1 F RFCDAT(4)* On
Demand,
No
Refresh
Capstone Turbine Corporation 21211 Nordhoff Street Chatsworth CA 91311 USA
Technical Reference: ModBus Translator Module
410040 Rev C (April 2008) Page 29 of 58
Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document
without incurring any obligation either with respect to equipment previously sold or in the process of construction.
Register Mode Description Representation
RS232
Command
Timing
(Sec)
42246 S (N6) RFC Speed Units: 1 = 1 rpm RFCDAT(5)* On
Demand,
No
Refresh
42247 S (N6) Current Feedback Units: 1 = 1 A RFCDAT(6)* On
Demand,
No
Refresh
42248 S (N6) RFC Injector State Current injector state set for
system operation (for C30
low pressure systems only):
0 = Fuel Init
1 = Warm-up
2 = One Pilot
3 = Three Pilot
4 = Premix
RFCDAT(7)* On
Demand,
No
Refresh
42261 S,H LFC Pump Cmd - PWM Units: 1 = 0.001529% LFCDAT(0)* On
Demand,
No
Refresh
42262 S AA Pressure (psig) Units: 1 = 0.1 psig LFCDAT(1)* On
Demand,
No
Refresh
42263 S,H LFC Injector State Model C30 MicroTurbine:
0 = Fuel Init
1 = Injector 1 on
2 = Injector 2 on
3 = Injector 3 on
4 = Two injectors on
5 = All three injectors on
7 = Purge no injectors on
8 = Injectors 1 and 2 on;
injector 3 clogged
9 = Injectors 1 and 3 on;
injector 2 clogged
Model C60/C65 MicroTurbine:
0 = Fuel Init
2 = Injectors 1, 2 on
3 = Injectors 1, 2, 3 on
4 = Injectors 1, 2, 3, 4 on
5 = Injectors 1, 2, 3, 4, 5 on
6 = All six injectors on
9 = Light off
10 = Liquid fuel prime
LFCDAT(2)* On
Demand,
No
Refresh
Capstone Turbine Corporation 21211 Nordhoff Street Chatsworth CA 91311 USA
Technical Reference: ModBus Translator Module
410040 Rev C (April 2008) Page 30 of 58
Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document
without incurring any obligation either with respect to equipment previously sold or in the process of construction.
Register Mode Description Representation
RS232
Command
Timing
(Sec)
42264 S,H LFC Pressure Command Units: 1 = 0.0976562 psig LFCDAT(3)* On
Demand,
No
Refresh
42265 S,H LFC Pressure Feedback Units: 1 = 0.0976562 psig LFCDAT(4)* On
Demand,
No
Refresh
42266 S System Prime Status 0 = Not Primed
1 = Primed
LFCDAT(6)* On
Demand,
No
Refresh
42267 S LFC User Initiated Prime 0=Off, 1=User Start LFCDAT(7)* On
Demand,
No
Refresh
42268 S,H LFC Boost Pump 0=No Pump, 1=Pump
present
LFCDAT(8)* On
Demand,
No
Refresh
42269 S (N6) LFC Prime State 0 = Ready for prime
1 = Beginning line fill
2 = Filling lines into drain tank
3 = Pulsing priming solenoid
4 = Completing line fill
5 = Draining tank
6 = Verifying completion
7 = Priming sequence
complete
LFCDAT(9)* On
Demand,
No
Refresh
42270 S,H LFC Boost Pump Status 0=Off, 1=On LFCDAT(10)* On
Demand,
No
Refresh
42271 S (N6) LFC Drain Pump Status 0=Off, 1=On LFCDAT(11)* On
Demand,
No
Refresh
42272 S (N6) LFC Prime Solenoid Status 0=Close, 1=Open LFCDAT(12)* On
Demand,
No
Refresh


System Hardware
Configuration

42301 S,H System HW Part Num
Offsets 0 & 1
2 ASCII characters HWCNFG 30
42302 S,H System HW Part Num
Offsets 2 & 3
2 ASCII characters HWCNFG 30
Capstone Turbine Corporation 21211 Nordhoff Street Chatsworth CA 91311 USA
Technical Reference: ModBus Translator Module
410040 Rev C (April 2008) Page 31 of 58
Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document
without incurring any obligation either with respect to equipment previously sold or in the process of construction.
Register Mode Description Representation
RS232
Command
Timing
(Sec)
42303 S,H System HW Part Num
Offsets 4 & 5
2 ASCII characters HWCNFG 30
42304 S,H System HW Part Num
Offsets 6 & 7
2 ASCII characters HWCNFG 30
42305 S,H System HW Part Num
Offsets 8 & 9
2 ASCII characters HWCNFG 30
42306 S,H System HW Part Num
Offsets 10 & 11
2 ASCII characters (null
chars)
HWCNFG 30
42307 S,H System HW Revision Offsets
0 & 1
2 ASCII characters - (hex
0X2D), no revision letter
HWCNFG 30
42308 S,H System HW Revision Offsets
2 & 3
2 ASCII characters HWCNFG 30
42309 S,H System HW Serial Number 0 16 bit Hex word (high word) HWCNFG 30
42310 S,H System HW Serial Number 1 16 bit Hex word (low word) HWCNFG 30

Engine Hardware
Configuration

42311 S,H Engine HW Part Num Offsets
0 & 1
2 ASCII characters HWCNFG 30
42312 S,H Engine HW Part Num Offsets
2 & 3
2 ASCII characters HWCNFG 30
42313 S,H Engine HW Part Num Offsets
4 & 5
2 ASCII characters HWCNFG 30
42314 S,H Engine HW Part Num Offsets
6 & 7
2 ASCII characters HWCNFG 30
42315 S,H Engine HW Part Num Offsets
8 & 9
2 ASCII characters HWCNFG 30
42316 S,H Engine HW Part Num Offsets
10 & 11
2 ASCII characters (null
chars)
HWCNFG 30
42317 S,H Engine HW Revision Offsets
0 & 1
2 ASCII characters - (hex
0X2D), no revision letter
HWCNFG 30
42318 S,H Engine HW Revision Offsets
2 & 3
2 ASCII characters HWCNFG 30
42319 S,H Engine HW Serial Num 0 16 bit Hex word (high word) HWCNFG 30
42320 S,H Engine HW Serial Num 1 16 bit Hex word (low word) HWCNFG 30

Main CPU Hardware
Configuration


42321 S,H Main CPU HW Part Num
Offsets 0 & 1
2 ASCII characters HWCNFG 30
42322 S,H Main CPU HW Part Num
Offsets 2 & 3
2 ASCII characters HWCNFG 30
42323 S,H Main CPU HW Part Num
Offsets 4 & 5
2 ASCII characters HWCNFG 30
42324 S,H Main CPU HW Part Num
Offsets 6 & 7
2 ASCII characters HWCNFG 30
42325 S,H Main CPU HW Part Num
Offsets 8 & 9
2 ASCII characters HWCNFG 30
Capstone Turbine Corporation 21211 Nordhoff Street Chatsworth CA 91311 USA
Technical Reference: ModBus Translator Module
410040 Rev C (April 2008) Page 32 of 58
Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document
without incurring any obligation either with respect to equipment previously sold or in the process of construction.
Register Mode Description Representation
RS232
Command
Timing
(Sec)
42326 S,H Main CPU HW Part Num
Offsets 10 & 11
2 ASCII characters (null
chars)
HWCNFG 30
42327 S,H Main CPU HW Revision
Offsets 0 & 1
2 ASCII characters - (hex
0X2D), no revision letter
HWCNFG 30
42328 S,H Main CPU HW Revision
Offsets 2 & 3
2 ASCII characters HWCNFG 30
42329 S,H Main CPU HW Serial Num 0 16 bit Hex word (high word) HWCNFG 30
42330 S,H Main CPU HW Serial Num 1 16 bit Hex word (low word) HWCNFG 30

Display Hardware
Configuration

42331 S,H Display HW Part Num
Offsets 0 & 1
2 ASCII characters HWCNFG 30
42332 S,H Display HW Part Num
Offsets 2 & 3
2 ASCII characters HWCNFG 30
42333 S,H Display HW Part Num
Offsets 4 & 5
2 ASCII characters HWCNFG 30
42334 S,H Display HW Part Num
Offsets 6 & 7
2 ASCII characters HWCNFG 30
42335 S,H Display HW Part Num
Offsets 8 & 9
2 ASCII characters HWCNFG 30
42336 S,H Display HW Part Num
Offsets 10 & 11
2 ASCII characters (null
chars)
HWCNFG 30
42337 S,H Display HW Revision Offsets
0 & 1
2 ASCII characters - (hex
0X2D), no revision letter
HWCNFG 30
42338 S,H Display HW Revision Offsets
2 & 3
2 ASCII characters HWCNFG 30
42339 S,H Display HW Serial Num 0 16 bit Hex word (high word) HWCNFG 30
42340 S,H Display HW Serial Num 1 16 bit Hex word (low word) HWCNFG 30

Fuel Device Hardware
Configuration

42341 S,H Fuel Device HW Part Num
Offsets 0 & 1
2 ASCII characters HWCNFG 30
42342 S,H Fuel Device HW Part Num
Offsets 2 & 3
2 ASCII characters HWCNFG 30
42343 S,H Fuel Device HW Part Num
Offsets 4 & 5
2 ASCII characters HWCNFG 30
42344 S,H Fuel Device HW Part Num
Offsets 6 & 7
2 ASCII characters HWCNFG 30
42345 S,H Fuel Device HW Part Num
Offsets 8 & 9
2 ASCII characters HWCNFG 30
42346 S,H Fuel Device HW Part Num
Offsets 10 & 11
2 ASCII characters (null
chars)
HWCNFG 30
42347 S,H Fuel Device HW Revision
Offsets 0 & 1
2 ASCII characters - (hex
0X2D), no revision letter
HWCNFG 30
42348 S,H Fuel Device HW Revision
Offsets 2 & 3


2 ASCII characters HWCNFG 30
Capstone Turbine Corporation 21211 Nordhoff Street Chatsworth CA 91311 USA
Technical Reference: ModBus Translator Module
410040 Rev C (April 2008) Page 33 of 58
Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document
without incurring any obligation either with respect to equipment previously sold or in the process of construction.
Register Mode Description Representation
RS232
Command
Timing
(Sec)
42349 S,H Fuel Device HW Serial
Num 0
16 bit Hex word (high word) HWCNFG 30
42350 S,H Fuel Device HW Serial
Num 1
16 bit Hex word (low word) HWCNFG 30

Battery Controller
Hardware Configuration

42351
S,
H (N3)
BCT BCM HW Part Num
Offsets 0 & 1
2 ASCII characters HWCNFG 30
42352
S,
H (N3)
BCT BCM HW Part Num
Offsets 2 & 3
2 ASCII characters HWCNFG 30
42353
S,
H (N3)
BCT BCM HW Part Num
Offsets 4 & 5
2 ASCII characters HWCNFG 30
42354
S,
H (N3)
BCT BCM HW Part Num
Offsets 6 & 7
2 ASCII characters HWCNFG 30
42355
S,
H (N3)
BCT BCM HW Part Num
Offsets 8 & 9
2 ASCII characters HWCNFG 30
42356
S,
H (N3)
BCT BCM HW Part Num
Offsets 10 & 11
2 ASCII characters (null
chars)
HWCNFG 30
42357
S,
H (N3)
BCT BCM HW Revision
Offsets 0 & 1
2 ASCII characters - (hex
0X2D), no revision letter
HWCNFG 30
42358
S,
H (N3)
BCT BCM HW Revision
Offsets 2 & 3
2 ASCII characters HWCNFG 30
42359
S,
H (N3)
BCT BCM HW Serial Num 0 16 bit Hex word (high word) HWCNFG 30
42360
S,
H (N3)
BCT BCM HW Serial Num 1 16 bit Hex word (low word) HWCNFG 30

Fuel Assist Hardware
Configuration


42361
S,H
(N6)
Fuel Assist HW Part Num
Offsets 0 & 1
2 ASCII characters HWCNFG 30
42362
S,H
(N6)
Fuel Assist HW Part Num
Offsets 2 & 3
2 ASCII characters HWCNFG 30
42363
S,H
(N6)
Fuel Assist HW Part Num
Offsets 4 & 5
2 ASCII characters HWCNFG 30
42364
S,H
(N6)
Fuel Assist HW Part Num
Offsets 6 & 7
2 ASCII characters HWCNFG 30
42365
S,H
(N6)
Fuel Assist HW Part Num
Offsets 8 & 9
2 ASCII characters HWCNFG 30
42366
S,H
(N6)
Fuel Assist HW Part Num
Offsets 10 & 11
2 ASCII characters (null
chars)
HWCNFG 30
42367
S,H
(N6)
Fuel Assist HW Revision
Offsets 0 & 1
2 ASCII characters - (hex
0X2D), no revision letter
HWCNFG 30
42368
S,H
(N6)
Fuel Assist HW Revision
Offsets 2 & 3


2 ASCII characters HWCNFG 30
Capstone Turbine Corporation 21211 Nordhoff Street Chatsworth CA 91311 USA
Technical Reference: ModBus Translator Module
410040 Rev C (April 2008) Page 34 of 58
Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document
without incurring any obligation either with respect to equipment previously sold or in the process of construction.
Register Mode Description Representation
RS232
Command
Timing
(Sec)
42369
S,H
(N6)
Fuel Assist HW Serial Num 0 16 bit Hex word (high word) HWCNFG 30
42370
S,H
(N6)
Fuel Assist HW Serial Num 1 16 bit Hex word (low word) HWCNFG 30

Load Control Module
Hardware Configuration

42371 S (N3) LCM HW Part Num Offsets
0 & 1
2 ASCII characters HWCNFG 30
42372 S (N3) LCM HW Part Num Offsets
2 & 3
2 ASCII characters HWCNFG 30
42373 S (N3) LCM HW Part Num Offsets
4 & 5
2 ASCII characters HWCNFG 30
42374 S (N3) LCM HW Part Num Offsets
6 & 7
2 ASCII characters HWCNFG 30
42375 S (N3) LCM HW Part Num Offsets
8 & 9
2 ASCII characters HWCNFG 30
42376 S (N3) LCM HW Part Num Offsets
10 & 11
2 ASCII characters (null
chars)
HWCNFG 30
42377 S (N3) LCM HW Revision Offsets
0 & 1
2 ASCII characters - (hex
0X2D), no revision letter
HWCNFG 30
42378 S (N3) LCM HW Revision Offsets
2 & 3
2 ASCII characters HWCNFG 30
42379 S (N3) LCM HW Serial Number 0 16 bit Hex word (high word) HWCNFG 30
42380 S (N3) LCM HW Serial Number 1 16 bit Hex word (low word) HWCNFG 30

CHP Hardware
Configuration

42381 S (N3) CHP HW Part Num Offsets
0 & 1
2 ASCII characters HWCNFG 30
42382 S (N3) CHP HW Part Num Offsets
2 & 3
2 ASCII characters HWCNFG 30
42383 S (N3) CHP HW Part Num Offsets
4 & 5
2 ASCII characters HWCNFG 30
42384 S (N3) CHP HW Part Num Offsets
6 & 7
2 ASCII characters HWCNFG 30
42385 S (N3) CHP HW Part Num Offsets
8 & 9
2 ASCII characters HWCNFG 30
42386 S (N3) CHP HW Part Num Offsets
10 & 11
2 ASCII characters (null
chars)
HWCNFG 30
42387 S (N3) CHP HW Revision Offsets
0 & 1
2 ASCII characters - (hex
0X2D), no revision letter
HWCNFG 30
42388 S (N3) CHP HW Revision Offsets
2 & 3
2 ASCII characters HWCNFG 30
42389 S (N3) CHP HW Serial Number 0 16 bit Hex word (high word) HWCNFG 30
42390 S (N3) CHP HW Serial Number 1 16 bit Hex word (low word) HWCNFG 30



Capstone Turbine Corporation 21211 Nordhoff Street Chatsworth CA 91311 USA
Technical Reference: ModBus Translator Module
410040 Rev C (April 2008) Page 35 of 58
Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document
without incurring any obligation either with respect to equipment previously sold or in the process of construction.
Register Mode Description Representation
RS232
Command
Timing
(Sec)
Boot Software
Configuration

42401 S,H Boot SW Version 16 bit Hex word
SWCNFG
30
42402 S,H Reserved 16 bit Hex word (initialized to
0x0000)
SWCNFG
30
42403 S,H Boot SW Part Num Offsets
0 & 1
2 ASCII characters
SWCNFG
30
42404 S,H Boot SW Part Num Offsets
2 & 3
2 ASCII characters
SWCNFG
30
42405 S,H Boot SW Part Num Offsets
4 & 5
2 ASCII characters
SWCNFG
30
42406 S,H Boot SW Part Num Offsets
6 & 7
2 ASCII characters
SWCNFG
30
42407 S,H Boot SW Part Num Offsets
8 & 9
2 ASCII characters
SWCNFG
30
42408 S,H Boot SW Part Num Offsets
10 & 11
2 ASCII characters (null
chars)
SWCNFG
30
42409 S,H Boot SW Revision Offsets
0 & 1
2 ASCII characters - (hex
0X2D), no revision letter
SWCNFG
30
42410 S,H Boot SW Revision Offsets
2 & 3
2 ASCII characters
SWCNFG
30

Main CPU Software
Configuration

42411 S,H Main CPU SW Version 16 bit Hex word
SWCNFG
30
42412 S,H Reserved 16 bit Hex word (initialized to
0x0000)
SWCNFG
30
42413 S,H Main CPU SW Part Num
Offsets 0 & 1
2 ASCII characters
SWCNFG
30
42414 S,H Main CPU SW Part Num
Offsets 2 & 3
2 ASCII characters
SWCNFG
30
42415 S,H Main CPU SW Part Num
Offsets 4 & 5
2 ASCII characters
SWCNFG
30
42416 S,H Main CPU SW Part Num
Offsets 6 & 7
2 ASCII characters
SWCNFG
30
42417 S,H Main CPU SW Part Num
Offsets 8 & 9
2 ASCII characters
SWCNFG
30
42418 S,H Main CPU SW Part Num
Offsets 10 & 11
2 ASCII characters (null
chars)
SWCNFG
30
42419 S,H Main CPU SW Revision
Offsets 0 & 1
2 ASCII characters - (hex
0X2D), no revision letter
SWCNFG
30
42420 S,H Main CPU SW Revision
Offsets 2 & 3
2 ASCII characters
SWCNFG
30

Generator DSP Software
Configuration

42421 S,H GDSP SW Version 16 bit Hex word
SWCNFG
30
42422 S,H Reserved 16 bit Hex word (initialized to
0x0000)
SWCNFG
30
42423 S,H GDSP SW Part Num Offsets
0 & 1
2 ASCII characters
SWCNFG
30
Capstone Turbine Corporation 21211 Nordhoff Street Chatsworth CA 91311 USA
Technical Reference: ModBus Translator Module
410040 Rev C (April 2008) Page 36 of 58
Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document
without incurring any obligation either with respect to equipment previously sold or in the process of construction.
Register Mode Description Representation
RS232
Command
Timing
(Sec)
42424 S,H GDSP SW Part Num Offsets
2 & 3
2 ASCII characters
SWCNFG
30
42425 S,H GDSP SW Part Num Offsets
4 & 5
2 ASCII characters
SWCNFG
30
42426 S,H GDSP SW Part Num Offsets
6 & 7
2 ASCII characters
SWCNFG
30
42427 S,H GDSP SW Part Num Offsets
8 & 9
2 ASCII characters
SWCNFG
30
42428 S,H GDSP SW Part Num Offsets
10 & 11
2 ASCII characters (null
chars)
SWCNFG
30
42429 S,H GDSP SW Revision Offsets
0 & 1
2 ASCII characters - (hex
0X2D), no revision letter
SWCNFG
30
42430 S,H GDSP SW Revision Offsets
2 & 3
2 ASCII characters
SWCNFG
30

Inverter DSP Software
Configuration

42431
S,H
(N6)
IDSP SW Version 16 bit Hex word
SWCNFG
30
42432
S,H
(N6)
Reserved 16 bit Hex word (initialized to
0x0000)
SWCNFG
30
42433
S,H
(N6)
IDSP SW Part Num Offsets
0 & 1
2 ASCII characters
SWCNFG
30
42434
S,H
(N6)
IDSP SW Part Num Offsets
2 & 3
2 ASCII characters
SWCNFG
30
42435
S,H
(N6)
IDSP SW Part Num Offsets
4 & 5
2 ASCII characters
SWCNFG
30
42436
S,H
(N6)
IDSP SW Part Num Offsets
6 & 7
2 ASCII characters
SWCNFG
30
42437
S,H
(N6)
IDSP SW Part Num Offsets
8 & 9
2 ASCII characters
SWCNFG
30
42438
S,H
(N6)
IDSP SW Part Num Offsets
10 & 11
2 ASCII characters (null
chars)
SWCNFG
30
42439
S,H
(N6)
IDSP SW Revision Offsets
0 & 1
2 ASCII characters - (hex
0X2D), no revision letter
SWCNFG
30
42440
S,H
(N6)
IDSP SW Revision Offsets
2 & 3
2 ASCII characters
SWCNFG
30

Display Software
Configuration

42441 S,H Display SW Version 16 bit Hex word
SWCNFG
30
42442 S,H Reserved 16 bit Hex word (initialized to
0x0000)
SWCNFG
30
42443 S,H Display SW Part Num
Offsets 0 & 1
2 ASCII characters
SWCNFG
30
42444 S,H Display SW Part Num
Offsets 2 & 3
2 ASCII characters
SWCNFG
30
42445 S,H Display SW Part Num
Offsets 4 & 5
2 ASCII characters
SWCNFG
30
Capstone Turbine Corporation 21211 Nordhoff Street Chatsworth CA 91311 USA
Technical Reference: ModBus Translator Module
410040 Rev C (April 2008) Page 37 of 58
Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document
without incurring any obligation either with respect to equipment previously sold or in the process of construction.
Register Mode Description Representation
RS232
Command
Timing
(Sec)
42446 S,H Display SW Part Num
Offsets 6 & 7
2 ASCII characters
SWCNFG
30
42447 S,H Display SW Part Num
Offsets 8 & 9
2 ASCII characters
SWCNFG
30
42448 S,H Display SW Part Num
Offsets 10 & 11
2 ASCII characters (null
chars)
SWCNFG
30
42449 S,H Display SW Revision Offsets
0 & 1
2 ASCII characters - (hex
0X2D), no revision letter
SWCNFG
30
42450 S,H Display SW Revision Offsets
2 & 3

2 ASCII characters
SWCNFG
30
Fuel Device Software
Configuration

42451 S,H Fuel Device SW Version 16 bit Hex word
SWCNFG
30
42452 S,H Reserved 16 bit Hex word (initialized to
0x0000)
SWCNFG
30
42453 S,H Fuel Device SW Part Num
Offsets 0 & 1
2 ASCII characters
SWCNFG
30
42454 S,H Fuel Device SW Part Num
Offsets 2 & 3
2 ASCII characters
SWCNFG
30
42455 S,H Fuel Device SW Part Num
Offsets 4 & 5
2 ASCII characters
SWCNFG
30
42456 S,H Fuel Device SW Part Num
Offsets 6 & 7
2 ASCII characters
SWCNFG
30
42457 S,H Fuel Device SW Part Num
Offsets 8 & 9
2 ASCII characters
SWCNFG
30
42458 S,H Fuel Device SW Part Num
Offsets 10 & 11
2 ASCII characters (null
chars)
SWCNFG
30
42459 S,H Fuel Device SW Revision
Offsets 0 & 1
2 ASCII characters - (hex
0X2D), no revision letter
SWCNFG
30
42460 S,H Fuel Device SW Revision
Offsets 2 & 3
2 ASCII characters
SWCNFG
30

Battery Controller Software
Configuration

42461
S,
H (N3)
BCT SW Version 16 bit Hex word
SWCNFG
30
42462
S,
H (N3)
Reserved 16 bit Hex word (initialized to
0x0000)
SWCNFG
30
42463
S,
H (N3)
BCT SW Part Num Offsets
0 & 1
2 ASCII characters
SWCNFG
30
42464
S,
H (N3)
BCT SW Part Num Offsets
2 & 3
2 ASCII characters
SWCNFG
30
42465
S,
H (N3)
BCT SW Part Num Offsets
4 & 5
2 ASCII characters
SWCNFG
30
42466
S,
H (N3)
BCT SW Part Num Offsets
6 & 7
2 ASCII characters
SWCNFG
30
42467
S,
H (N3)
BCT SW Part Num Offsets
8 & 9
2 ASCII characters
SWCNFG
30
42468
S,
H (N3)
BCT SW Part Num Offsets
10 & 11 (null chars)
2 ASCII characters
SWCNFG
30
Capstone Turbine Corporation 21211 Nordhoff Street Chatsworth CA 91311 USA
Technical Reference: ModBus Translator Module
410040 Rev C (April 2008) Page 38 of 58
Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document
without incurring any obligation either with respect to equipment previously sold or in the process of construction.
Register Mode Description Representation
RS232
Command
Timing
(Sec)
42469
S,
H (N3)
BCT SW Revision Offsets
0 & 1
2 ASCII characters - (hex
0X2D), no revision letter
SWCNFG
30
42470
S,
H (N3)
BCT SW Revision Offsets
2 & 3
2 ASCII characters
SWCNFG
30

Fuel Assist Software
Configuration

42471 S (N6) Fuel Assist SW Version 16 bit Hex word
SWCNFG
30
42472 S (N6) Reserved 16 bit Hex word (initialized to
0x0000)
SWCNFG
30
42473 S (N6) Fuel Assist SW Part Num
Offsets 0 & 1
2 ASCII characters
SWCNFG
30
42474 S (N6) Fuel Assist SW Part Num
Offsets 2 & 3
2 ASCII characters
SWCNFG
30
42475 S (N6) Fuel Assist SW Part Num
Offsets 4 & 5
2 ASCII characters
SWCNFG
30
42476 S (N6) Fuel Assist SW Part Num
Offsets 6 & 7
2 ASCII characters
SWCNFG
30
42477 S (N6) Fuel Assist SW Part Num
Offsets 8 & 9
2 ASCII characters
SWCNFG
30
42478 S (N6) Fuel Assist SW Part Num
Offsets 10 & 11
2 ASCII characters (null
chars)
SWCNFG
30
42479 S (N6) Fuel Assist SW Revision
Offsets 0 & 1
2 ASCII characters - (hex
0X2D), no revision letter
SWCNFG
30
42480 S (N6) Fuel Assist SW Revision
Offsets 2 & 3
2 ASCII characters
SWCNFG
30

EUCB Software
Configuration

42481
S,H
(N6)
EUCB SW Version 16 bit Hex word
SWCNFG
30
42482
S,H
(N6)
Reserved 16 bit Hex word (initialized to
0x0000)
SWCNFG
30
42483
S,H
(N6)
EUCB SW Part Num Offsets
0 & 1
2 ASCII characters
SWCNFG
30
42484
S,H
(N6)
EUCB SW Part Num Offsets
2 & 3
2 ASCII characters
SWCNFG
30
42485
S,H
(N6)
EUCB SW Part Num Offsets
4 & 5
2 ASCII characters
SWCNFG
30
42486
S,H
(N6)
EUCB SW Part Num Offsets
6 & 7
2 ASCII characters
SWCNFG
30
42487
S,H
(N6)
EUCB SW Part Num Offsets
8 & 9
2 ASCII characters
SWCNFG
30
42488
S,H
(N6)
EUCB SW Part Num Offsets
10 & 11 (null chars)
2 ASCII characters
SWCNFG
30
42489
S,H
(N6)
EUCB SW Revision Offsets
0 & 1
2 ASCII characters - (hex
0X2D), no revision letter
SWCNFG
30
42490
S,H
(N6)
EUCB SW Revision Offsets
2 & 3
2 ASCII characters
SWCNFG
30
Capstone Turbine Corporation 21211 Nordhoff Street Chatsworth CA 91311 USA
Technical Reference: ModBus Translator Module
410040 Rev C (April 2008) Page 39 of 58
Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document
without incurring any obligation either with respect to equipment previously sold or in the process of construction.
Register Mode Description Representation
RS232
Command
Timing
(Sec)
Aux Fuel Device Software
Configuration

42491 S Aux Fuel Device SW Version 16 bit Hex word
SWCNFG
30
42492 S Reserved 16 bit Hex word (initialized to
0x0000)
SWCNFG
30
42493 S Aux Fuel Device SW Part
Num Offsets 0 & 1
2 ASCII characters
SWCNFG
30
42494 S Aux Fuel Device SW Part
Num Offsets 2 & 3
2 ASCII characters
SWCNFG
30
42495 S Aux Fuel Device SW Part
Num Offsets 4 & 5
2 ASCII characters
SWCNFG
30
42496 S Aux Fuel Device SW Part
Num Offsets 6 & 7
2 ASCII characters
SWCNFG
30
42497 S Aux Fuel Device SW Part
Num Offsets 8 & 9
2 ASCII characters
SWCNFG
30
42498 S Aux Fuel Device SW Part
Num Offsets 10 & 11
2 ASCII characters (null
chars)
SWCNFG
30
42499 S Aux Fuel Device SW
Revision Offsets 0 & 1
2 ASCII characters - (hex
0X2D), no revision letter
SWCNFG
30
42500 S Aux Fuel Device SW
Revision Offsets 2 & 3
2 ASCII characters
SWCNFG
30

Fault Information
46000
46001
S,H Fault Summary Register
(Bitmapped. Lower Order bits,
0 through 15 are contained in
register 46001 and bits 16
31 in register 46000)
Bit 0 Any System Fault
Bit 1 Category 1000 Fault
Bit 2 Category 2000 Fault

Bit 20 Category 20000
Fault
Bits 21 31 - Unused
FLTLST 10
46002
46003
S,H Faults 1000 1031 from
Fault Category 1000
Bit 0 Fault 1000
Bit 1 Fault 1001
Bit 2 Fault 1002

Bit 31 Fault 1031
FLTLST 1
46004
46005
S,H Faults 1032 1063 Bit 0 Fault 1032
Bit 1 Fault 1033

Bit 31 Fault 1063
FLTLST 1
46006
46007
S,H Faults 1064 1095 Bit 0 Fault 1064
Bit 1 Fault 1065

Bit 31 Fault 1095
FLTLST 1
46008
46009
S,H Faults 1096 1127 Bit 0 Fault 1096
Bit 1 Fault 1097

Bit 31 Fault 1127
FLTLST 1
Capstone Turbine Corporation 21211 Nordhoff Street Chatsworth CA 91311 USA
Technical Reference: ModBus Translator Module
410040 Rev C (April 2008) Page 40 of 58
Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document
without incurring any obligation either with respect to equipment previously sold or in the process of construction.
Register Mode Description Representation
RS232
Command
Timing
(Sec)
46010
46011
S,H Faults 2000 2031 from
Fault Category 2000
Similar to registers 46002
46003 for Fault Category
1000
FLTLST 1
46012
46013
S,H Faults 2032 2063 from
Fault Category 2000
Similar to registers 46002
46003 for Fault Category
1000
FLTLST 1
46014
46015
S,H Faults 2064 2095 from
Fault Category 2000
Similar to registers 46002
46003 for Fault Category
1000
FLTLST 1
46016
46017
S,H Faults 2096 2127 from
Fault Category 2000
Similar to registers 46008
46009 for Fault Category
1000
FLTLST 1
46018
46025
S,H Faults in Category 3000 Similar to registers 46002
46009 for Fault Category
1000
FLTLST 1
46026
46033
S,H Faults in Category 4000 Similar to registers 46002
46009 for Fault Category
1000
FLTLST 1
46034
46041
S,H Faults in Category 5000 Similar to registers 46002
46009 for Fault Category
1000
FLTLST 1
46042
46049
S,H Faults in Category 6000 Similar to registers 46002
46009 for Fault Category
1000
FLTLST 1
46050
46057
S,H Faults in Category 7000 Similar to registers 46002
46009 for Fault Category
1000
FLTLST 1
46058
46065
S,H Faults in Category 8000 Similar to registers 46002
46009 for Fault Category
1000
FLTLST 1
46066
46073
S,H Faults in Category 9000 Similar to registers 46002
46009 for Fault Category
1000
FLTLST 1
46074
46081
S,H
(N6)
Faults in Category 10000 Similar to registers 46002
46009 for Fault Category
1000
FLTLST 1
46082
46089
S,H Faults in Category 11000 Similar to registers 46002
46009 for Fault Category
1000
FLTLST 1
46090
46097
S,H Faults in Category 12000 Similar to registers 46002
46009 for Fault Category
1000
FLTLST 1
46098
46105
Faults in Category 13000 Similar to registers 46002
46009 for Fault Category
1000
FLTLST 1
46106
46113
C Faults in Category 14000 Similar to registers 46002
46009 for Fault Category
1000
FLTLST 1
Capstone Turbine Corporation 21211 Nordhoff Street Chatsworth CA 91311 USA
Technical Reference: ModBus Translator Module
410040 Rev C (April 2008) Page 41 of 58
Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document
without incurring any obligation either with respect to equipment previously sold or in the process of construction.
Register Mode Description Representation
RS232
Command
Timing
(Sec)
46114
46121
N/A Faults in Category 15000 Similar to registers 46002
46009 for Fault Category
1000
FLTLST 1
46122
46129
S,H Faults in Category 16000 Similar to registers 46002
46009 for Fault Category
1000
FLTLST 1
46130
46137
S (N3) Faults in Category 17000 Similar to registers 46002
46009 for Fault Category
1000
FLTLST 1
46138
46145
Faults in Category 18000 Similar to registers 46002
46009 for Fault Category
1000
FLTLST 1
46146
46153
Faults in Category 19000 Similar to registers 46002
46009 for Fault Category
1000
FLTLST 1
46154
46161
Faults in Category 20000 Similar to registers 46002
46009 for Fault Category
1000
FLTLST 1
46171-
46190
S,H Fault History (20 registers) Fault history table containing
the last 20 faults.
FLTHST 1

Warranty Information
47001
47002
S,H Commission Date Word 1, High Byte Month
Word 1, Low Byte Day
Word 2 Year
WARNTY(0) 30
47003
47005
S,H Operating Time (Hours High) Word 1 Hours High
Word 2 Hours Low
Word 3, High Byte Minute
Word 3, Low Byte Second
WARNTY(1) 30
47006
47007
S,H Number of Starts Units: 1 = 1 Start WARNTY(3) 30
47008
47010
S (N6) RFC Low psi Time Word 1 Hours High
Word 2 Hours Low
Word 3, High Byte Minute
Word 3, Low Byte - Second
WARNTY(4) 30
Capstone Turbine Corporation 21211 Nordhoff Street Chatsworth CA 91311 USA
Technical Reference: ModBus Translator Module
410040 Rev C (April 2008) Page 42 of 58
Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document
without incurring any obligation either with respect to equipment previously sold or in the process of construction.
Wri t e Regi st er s
Some write registers may be written into without entering a password. However, most do
require password access in order to change the values. Write Registers 48001, 48003
48008, and 48021 48022 may be written without password access. All other Write
Registers will require entering a valid password in register 48004 through 48008 before
modifying a value. Successful entry of the password may be verified by reading back the
value at register 40006 as 1, indicating protected password access has been granted.
The paragraph below demonstrates how to enter a user password.

Entering a User Password

Passwords may be no more than 9 characters
(see Appendix A for character - hex translation)
An additional character is required for a NULL terminator (0x00)
Two characters make up one 16-bit register location
Passwords must be entered starting in location 48004
Fill any remaining register bytes with NULL (0x00)

The example below shows how to enter the default password:

Register Location Byte Contents
48004 0x55h (U) 0x53h (S)
48005 0x52h (R) 0x31h (1)
48006 0x32h (2) 0x33h (3)
48007 0x50h (P) 0x00h (NULL)
48008 0x00 (NULL) 0x00h (NULL)

Several write registers require multiple registers to be updated simultaneously in order to
complete the operation. These registers will be identified with footnotes.
All values written into the write registers can be read back using the standard ModBus read
procedure. This allows verification that the value that was attempted to be written into a
specific register, can be read back from that register. However, this value may be different
from the value of the corresponding read register, which could happen if the host device does
not or was not able to accept the command issued to it. In that case, the command value
remains unchanged and the corresponding read register on the ModBus Translator would still
contain the old value.
WARNING
Several of the registers in this section access MicroTurbine commands that
write to Non-Volatile Memory (NVM) locations. The NVM memory device
has limited number of writes (10,000 writes) that can be executed before
the device fails. All registers that apply (see below) are denoted with an
asterisk (*) character preceding the description name.
Capstone Turbine Corporation 21211 Nordhoff Street Chatsworth CA 91311 USA
Technical Reference: ModBus Translator Module
410040 Rev C (April 2008) Page 43 of 58
Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document
without incurring any obligation either with respect to equipment previously sold or in the process of construction.
Table 9 - Holding Register (Write Only)
Register Mode Description Representation
RS232
Command
General Communication Info
48001 S Selected Turbine
3
0 This Turbine/Entire System
1 Master Turbine
2 thru 10 Specific Turbine
TURBNO,0
48002 Reserved
48003 S,H Logoff
4
Send 1 to logoff LOGOFF
48004
48008
S,H Enter Password
4,5
Each byte represents an ASCII
character for the password.
String must be NULL
terminated.
(Default: USR123P)
PSSWRD
48009
48013
S,H Change Password
6
Each byte represents an ASCII
character for the password.
String must be NULL
terminated.
CPTPSW
48014
48018
S,H *Verify Password
7
Each byte represents an ASCII
character for the password.
String must be NULL
terminated.
VPTPSW
48020 S,H Reboot Send 1 to reboot system REBOOT
48021 S,H Communication Configuration
1
Bit 0 1: Mode Bits
0 = Stationary
1 = HEV
2 = Reserved
3 = Reserved
Bit 2 14: Not Used
Bit 15: Comm Timeout Enable
NA
48022 S,H Comm Timeout Period
2
Units: 1 = 1 Seconds
Min: 1 Seconds
Max: 65535 Seconds
NA

System Controls/Settings
48101 S,H *Start Command 0 Stop, 1 Start STRCMD
48102 S *User Start 0 Stop, 1 Start USRSTR
48103 S,H *Auto Restart 0 Disabled, 1 Enabled AUTRST

3
Updating this parameter will make all registers reflect data from system number selected. All read
registers would be invalidated until the ModBus device has been able to query data from the new turbine
number.
4
Logoff command is automatically issued after 5 minutes of no ModBus communication.
5
Changes Port Access Level (see Reg 40006) so that write commands can be processed. When no
ModBus communication is received within 5 minutes, the LOGOFF command will be issued.
6
Changes the password for the Enter Password (see Reg 48004 - 48008). Must be followed by a write to
the Verify Password registers (see Reg 48014 48018) with the same password data.
7
Must follow a write to the Change Password registers (see Reg 48009 - 48013) to have the new password
(Enter Password, see Reg 48004 48008) become valid.
Capstone Turbine Corporation 21211 Nordhoff Street Chatsworth CA 91311 USA
Technical Reference: ModBus Translator Module
410040 Rev C (April 2008) Page 44 of 58
Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document
without incurring any obligation either with respect to equipment previously sold or in the process of construction.
Register Mode Description Representation
RS232
Command
48104 S *Restart Delay (GC) Units: 1 = 0.1 Minutes
Min: 0.0 Minutes
Max: 60.0 Minutes
RDLYGC
48105 S *Restart Delay (SA) Units: 1 = 0.1 Minutes
Min: 0.0 Minutes
Max: 60.0 Minutes
RDLYSA
48106 S *Remote Start Switch Enable 0 User
1 Remote
2 GC User/SA Remote
3 SA User/GC Remote
STRINP
48107 Reserved
48108 S *Utility Connection 0 Invalid,
1 Stand Alone,
2 Grid Connect,
3 Dual Mode
UTLCON
48109 S Power Enable (SA only) 0 Open, 1 Closed PWRENA
48110 S *Auto Load (SA only) 0 Disabled, 1 Enabled AUTOLD
48111
48112
S,H Power Demand Units: 1 = 1 Watt
Min: 0 Watts
Max: 2,000,000,000 Watts
PWRDMD
48113
48114
S,H *Store Power Demand
8
Units: 1 = 1 Watt
Min: 0 Watts
Max: 2,000,000,000 Watts
PWRDST
48115 S,H *Fuel Index 1 Units: 1 = 0.01 index
Min: 0.10
Max: 14.00
(see Installation Guide for
details)
FUELI1
48116 S,H *Fuel Index 2 Units: 1 = 0.01 index
Min: 0.10
Max: 2.00
(see Installation Guide for
details)
FUELI2
48117 S,H *Medium BTU Switch 0 Normal
1 Medium
2 Low
(see Installation Guide for
details)
MEDBTU
48118 S *MultiPac Enable 0 Disabled, 1 Enabled MPENAB
48119 S *This Turbines Number Master: 1
Slave: 2 thru 10
STRBNO

Grid Connect and HEV Relays
48301 S
*Under Voltage (GC)
Units: 1 = 1 VAC (line-to-line)
Min: 360 VAC
Max: 528 VAC
UNDVLT

8
For continuous power command updates use registers 48111 - 48112 Power Demand.
Capstone Turbine Corporation 21211 Nordhoff Street Chatsworth CA 91311 USA
Technical Reference: ModBus Translator Module
410040 Rev C (April 2008) Page 45 of 58
Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document
without incurring any obligation either with respect to equipment previously sold or in the process of construction.
Register Mode Description Representation
RS232
Command
48302 S
*Under Voltage Time (GC)
Units: 1 = 0.01 Seconds
Min: 0.01 Second
Max: 10.00 Seconds
UVLTTM
48303 S
*Over Voltage (GC)
Units: 1 = 1 VAC (line-to-line)
Min: 360 VAC
Max: 528 VAC
OVRVLT
48304 S
*Over Voltage Time (GC)
Units: 1 = 0.01 Seconds
Min: 0.01 Second
Max: 10.00 Seconds
OVLTTM
48305 S
*Fast Under Voltage (GC)
Units: 1 = 1 VAC (line-to-line)
Min: 0 VAC
Max: 528 VAC
FSTUVL
48306 S
*Fast Over Voltage (GC)
Units: 1 = 1 VAC (line-to-line)
Min: 360 VAC
Max: 635 VAC
FSTOVL
48307 S
*Under Frequency (GC)
Units: 1 = 0.1 Hz
Min: 45.0 Hz
Max: 65.0 Hz
UNDFRQ
48308 S
*Under Frequency Time (GC)
Units: 1 = 0.01 Seconds
Min: 0.01 Second
Max: 10.00 Seconds
UFRQTM
48309 S
*Over Frequency (GC)
Units: 1 = 0.1 Hz
Min: 45.0 Hz
Max: 65.0 Hz
OVRFRQ
48310 S
*Over Frequency Time (GC)
Units: 1 = 0.01 Seconds
Min: 0.01 Second
Max: 10.00 Seconds
OFRQTM

Stand Alone Relays
48401 S
*Output Voltage (SA)
Units: 1 = 1 VAC (line-to-line)
Min: 150 VAC
Max: 480 VAC
SAVOLT
48402 S
*Voltage Start (SA)
Units: 1 = 1 VAC (line-to-line)
Min: 0 VAC
Max: 480 VAC
STVOLT
48403 S
*Voltage Ramp (SA)
Units: 1 = 1 VAC/s (line-to-line)
Min: 3 VAC/s
Max: 6000 VAC/s
STVTRT
48404 S
*Under Voltage (SA)
Units: 1 = 1 VAC (line-to-line)
Min: 0 VAC
Max: 480 VAC
SAUVLT
48405 S
*Under Voltage Time (SA)
Units: 1 = 0.01 Seconds
Min: 0.01 Second
Max: 10.00 Seconds
SAUVTM
Capstone Turbine Corporation 21211 Nordhoff Street Chatsworth CA 91311 USA
Technical Reference: ModBus Translator Module
410040 Rev C (April 2008) Page 46 of 58
Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document
without incurring any obligation either with respect to equipment previously sold or in the process of construction.
Register Mode Description Representation
RS232
Command
48406 S
*Over Voltage (SA)
Units: 1 = 1 VAC (line-to-line)
Min: 150 VAC
Max: 528 VAC
SAOVLT
48407 S
*Over Voltage Time (SA)
Units: 1 = 0.01 Seconds
Min: 0.01 Second
Max: 10.00 Seconds
SAOVTM
48408 S
*Output Frequency (SA)
Units: 1 = 0.1 Hz
Min: 10.0 Hz
Max: 60.0 Hz
SAFREQ
48409 S
*Frequency Start (SA)
Units: 1 = 0.1 Hz
Min: 0.0 Hz
Max: 60.0 Hz
STFREQ
48410 S
*Frequency Ramp (SA)
Units: 1 = 1 Hz/s
Min: 3 Hz/s
Max: 6000 Hz/s
STFQRT
48411 S
*Under Frequency (SA)
Units: 1 = 0.1 Hz
Min: 5.0 Hz
Max: 60.0 Hz
SAUFRQ
48412 S
*Under Frequency Time (SA)
Units: 1 = 0.01 Seconds
Min: 0.01 Second
Max: 10.00 Seconds
SAUFTM
48413 S
*Over Frequency (SA)
Units: 1 = 0.1 Hz
Min: 10.0 Hz
Max: 65.0 Hz
SAOFRQ
48414 S
*Over Frequency Time (SA)
Units: 1 = 0.01 Seconds
Min: 0.01 Second
Max: 10.00 Seconds
SAOFTM

Load Management Settings
48501 S
*Load Management Mode
0 Disabled
2 Load Following
3 Time-of-Use
LMMODE
48502 S
*Meter Constant
Units: 1 = 0.001 Wh/pulse
Min: 0.000 Wh/pulse
Max: 50.000 Wh/pulse
LMMTRC
48503 S
*Utility Power Setpoint
Units: 1 = 0.1 kW
Min: -1000.0 kW
Max: +1000.0 kW
LMUTPW
48504 S
*Load Following Response Time
Units: 1 = 1 Second
Min: 1 Second
Max: 120 Seconds
LMRSPT
48505
48506
S
*Minimum Power Shutoff
Units: 1 = 0.1 kW
Min: 0.0 kW
Max: 2,000,000.0 kW
LMMPWR
Capstone Turbine Corporation 21211 Nordhoff Street Chatsworth CA 91311 USA
Technical Reference: ModBus Translator Module
410040 Rev C (April 2008) Page 47 of 58
Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document
without incurring any obligation either with respect to equipment previously sold or in the process of construction.
Register Mode Description Representation
RS232
Command
48507 S
*Minimum Power Shutoff Time
Units 1 = 1 Minutes
Min: 1 Minute
Max: 15 Minutes
LMPWTM
48508
9,10
S
Time of Use Event
Min: 1
Max: 20

Update of Holding Registers will
be delayed 1 second
N/A
48509
10
S
*TOU Event Day
0 Inactive
1 Sunday

7 Saturday
LMTOUE
48510
10
S
*TOU Event Time
High Byte Hour
Low Byte Minute
LMTOUE
48511
10
S
*TOU Event Start Command
0 Stop, 1 Start LMTOUE
48512
10

48513
S
*TOU Event Power Demand
Units: 1 = 1 Watt
Min: 0 Watts
Max: 2,000,000,000 Watts
LMTOUE
48514 S
*Reverse Power Protect
0 Disabled, 1 - Enabled LMRPFP
48515 S
*Reverse Power Protect Time
Units 1 = 1 Seconds
Min: 1 Second
Max: 120 Seconds
LMRPTM



UCB Relays
48601
11,12
S
Selected Relay Number
Min: 1
Max: 6

Update of Holding Registers will
be delayed 1 second
N/A
48602
12
S
*Relay Function
0 Standby
1 Run
2 Load
3 Fault
4 Standalone
5 Dual Mode
6 Disable
7 Fuel On
8 Purge
OUTRLY
48603
12
S
*Relay Active State
0 Open, 1 Close OUTRLY

9
Writing to only this register will query the information for a specific Time-of-Use event. Read registers
40508 through 40513 will be updated within 500ms with the requested information.
10
All of these registers must be written simultaneously to update a Time-of-Use event.
11
Writing to only this register will query the information for a specific UCB Relay. Read registers 40601
through 40603 will be updated within 500ms with the requested information.
12
All of these registers must be written simultaneously to update UCB Relay settings.
Capstone Turbine Corporation 21211 Nordhoff Street Chatsworth CA 91311 USA
Technical Reference: ModBus Translator Module
410040 Rev C (April 2008) Page 48 of 58
Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document
without incurring any obligation either with respect to equipment previously sold or in the process of construction.
Register Mode Description Representation
RS232
Command
Battery Information
48701 S Battery Enable 0 Disabled, 1 Enabled BATENA
48702 S *Battery Auto Sleep Units: 1 = 0.1 Hours
Min: 1 = 0.1 Hours
Max: 239 = 23.9 Hours
ATOSLP
48703 S Battery Charge 0 Disabled, 1 Enabled BATCHG
48704 S Battery Recharge Enable (SA only) 0 Disabled, 1 Enabled RCHENA
48705 Reserved
48706 Reserved
48707
13,14
S Selected Charge Permission Day 1 Sunday
2 Monday

7 Saturday
Update of Holding Registers will
be delayed 1 second
N/A
48708
14
S *Charge Permission Active 0 Inactive, 1 Active CHGEQP
48709
14
S *Charge Permission Start Time.
Must be earlier than 40710.
High Byte Hour (0 23)
Low Byte Minute (Ignored)
CHGEQP
48710
14
S *Charge Permission End Time.
Must be later than 40709.
High Byte Hour (0 23)
Low Byte Minute (Ignored)
CHGEQP
48711 Reserved

Hybrid Vehicle Relays
48801 H *Under Voltage (HEV) Units: 1 = 1 V
DC

Min: 40 V
DC

Max: 740 V
DC

UNDVLT
48802 H
*Under Voltage Time (HEV)
Units: 1 = 0.01 Seconds
Min: 0.01 Second
Max: 10.00 Seconds
UVLTTM
48803 H
*Over Voltage (HEV)
Units: 1 = 1 V
DC
Min: 40 V
DC

Max: 740 V
DC

OVRVLT
48804 H
*Over Voltage Time (HEV)
Units: 1 = 0.01 Seconds
Min: 0.01 Second
Max: 10.00 Seconds
OVLTTM
48805 H
*Fast Under Voltage (HEV)
Units: 1 = 1 V
DC
Min: 40 V
DC

Max: 740 V
DC

FSTUVL
48806 H
*Fast Over Voltage (HEV)
Units: 1 = 1 V
DC
Min: 40 V
DC

Max: 740 V
DC

FSTOVL

13
Writing to only this register will query the information for a specific Charge Permission Day. Read
registers 40707 through 40710 will be updated within 500ms with the requested information.
14
All of these registers must be written simultaneously to update Charge Permission Day settings.
Capstone Turbine Corporation 21211 Nordhoff Street Chatsworth CA 91311 USA
Technical Reference: ModBus Translator Module
410040 Rev C (April 2008) Page 49 of 58
Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document
without incurring any obligation either with respect to equipment previously sold or in the process of construction.
Register Mode Description Representation
RS232
Command
48807 H
*Battery Current Limit
Units: 1 = 1 A
DC

Min: 0 = 0 A
DC

Max: 195 = 195 A
DC

BATILM
Capstone Power Server
48808 C Min Power Capacity, Grid Connect Units: 1 = 1 Watt
Min: 0 Watts
Max: 2,000,000,000 Watts
MPCPGC
48810 C Min Power Capacity, Stand Alone Units: 1 = 1 Watt
Min: 0 Watts
Max: 2,000,000,000 Watts
MPCPSA
48812 C Spinning Reserve, Grid Connect Units: 1 = 1 Watt
Min: 0 Watts
Max: 2,000,000,000 Watts
MPSRGC
48814 C Spinning Reserve, Stand Alone Units: 1 = 1 Watt
Min: 0 Watts
Max: 2,000,000,000 Watts
MPSRSA
48816 C Multipac Mode 0 Load Balancing,
1 Max Efficiency
MPMODE

Data Acquisition
49001
49002
S,H *System Date Word 1, High Byte Month
Word 1, Low Byte Day
Word 2 Year
DATESC
49003
49004
S,H *System Time Word 1 Hour
Word 2, High Byte Minute
Word 2, Low Byte Second
TIMESC

Capstone Turbine Corporation 21211 Nordhoff Street Chatsworth CA 91311 USA
Technical Reference: ModBus Translator Module
410040 Rev C (April 2008) Page 50 of 58
Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document
without incurring any obligation either with respect to equipment previously sold or in the process of construction.
Loopback Di agnost i c Test (Funct i on Code 08)
This function performs a communication test. The command requires a Slave Address,
Function Code, Sub function Code, two bytes of user-supplied data bytes, and CRC16. The
entire response should be identical to the command. This command is typically used to verify
the existence of a device at a ModBus address. The example shown in the table below
shows the user data transmission to perform the Loopback communication.
Table 10 Function Code 08 Command and Response (Loopback Diagnostic Test)
Byte Name Example Notes
1 Slave Address 01
2 Function Code 08
3 Sub function high 00 Only legal sub function is 00,00
4 Sub function low 00
5 Data high 55 Any two data bytes are allowed
6 Data low AA
7 CRC-16 low XX
8 CRC-16 high XX
Capstone Turbine Corporation 21211 Nordhoff Street Chatsworth CA 91311 USA
Technical Reference: ModBus Translator Module
410040 Rev C (April 2008) Page 51 of 58
Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document
without incurring any obligation either with respect to equipment previously sold or in the process of construction.
Troubl eshoot i ng
In the event that there is a ModBus problem, attempt the following solutions provided below:
Symptom: Cannot communicate with the device through the ModBus Translator.
Solutions:
Verify that the ModBus Translator Power Indicator light is ON.
Verify that the device that the ModBus Translator is hooked to (MicroTurbine) is
powered up. This can be verified by looking for lights on the display panel.
Verify that the DB-9 serial cable from the MicroTurbine is properly plugged into both
the Turbine unit, and the ModBus Translator.
Verify that the Data Activity Indicator light on the ModBus Translator blinks
occasionally.
Verify that the RS-485 Bus wires are properly terminated, and the screws tightened
into terminals 2 and 3 of the ModBus RS-485 connector. The A-Bus wire MUST
connect to Terminal 3, and the B-Bus wire MUST connect to Terminal 2.
Change the ModBus Translator to a different address.
Change the baud rates of the entire system to a slower baud to verify. It is possible
that by adding a new node to the RS-485 system, a previously achieved baud rate
can no longer be supported. This occurs because the length of the cable and
number of nodes may have changed.
Symptom: The Power Indicator light on the ModBus Translator is not ON.
Solutions:
Verify that the power is correctly hooked to the ModBus Translator. The positive (+)
power wire MUST hook to Pin-4. The negative (-) power wire MUST hook to Pin-5.
NOTE
If these wires are hooked up backwards, permanent damage to the
ModBus Translator could occur!
Verify with a voltmeter, that the voltage at power terminals is DC, and is between
+6.0V and +25.0V.
Symptom: The Data Activity Indicator light on the ModBus Translator is not lit. This light
should never be solidly ON, but should blink ON and OFF periodically. When this light blinks,
it shows that a valid ModBus command was received on the RS-485 Bus.
Solutions:
Verify that the Power Indicator light is ON. The Data Activity light will not work if there
is inadequate power to the ModBus Translator.
Verify that the baud rate selector switch is set to the same baud rate your ModBus
master system is communicating. If data rates are not the same, bit timing will be off
and data will not be understood properly by the ModBus Translator.
If there are still communications problems, then either the address should be
changed, or the host device connected to the ModBus Translator over the DB-9
connector is not communicating.
Capstone Turbine Corporation 21211 Nordhoff Street Chatsworth CA 91311 USA
Technical Reference: ModBus Translator Module
410040 Rev C (April 2008) Page 52 of 58
Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document
without incurring any obligation either with respect to equipment previously sold or in the process of construction.
Symptom: Unable to read back value from a read register that was previously written to a
corresponding write register.
Solutions:
Note that because this is a translator, there may be a 0.5sec to 1.0sec delay before
the write operation is actually processed. Slow down the time between writing a
Write Register and trying to read back the value from the corresponding Read
Register.
Verify access to write the register has been granted by reading register 40006. If a
zero is read back, a password must first be entered by writing registers 48004
through 48008.
Verify the connected port has control access by reading register 40003.
A write operation may require update to multiple registers - rather than just one. If
only one register is written to, the entire entry may be ignored.
Capstone Turbine Corporation 21211 Nordhoff Street Chatsworth CA 91311 USA
Technical Reference: ModBus Translator Module
410040 Rev C (April 2008) Page 53 of 58
Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document
without incurring any obligation either with respect to equipment previously sold or in the process of construction.
Test Modes
Invalid address settings and the baud rate selector shall be used to place the system into
various modes. In addition to normal operation, test modes will be made available for the
Golden System board test operator and Unit-Under Test (UUT) functions.
The table below shows mode selections and corresponding address settings:
Table 11 - Mode Selection (Address)
Mode Address Setting
Normal 1 247
Unit Under Test 0 and 248-254
Golden System 255

Gol den Syst em
The Baud Rate selector switch provided on the ModBus Translator Board will determine the
RS-485 baud rate.
A Golden System (address set to 255), when powered up will:
1. Delay for 2 seconds in order for UUT to power up. The lower LED shall be ON during
this process.
2. Begin blinking lower LED 250 msec ON, then 250 msec OFF, repeatedly, to indicate
test in progress.
3. Test RS-232 communications by executing a command to the UUT.
4. Send an RS-232 command to initiate execution of a Loopback Command on the
UUT.
5. Verify RS-485 command was received from UUT address (245
d
).
6. Respond to the UUTs Loopback Command (08
h
).
7. Verify the RS-232 response contains the correct data from the Loopback Command.
8. Execute steps 4 through 7 for nine (9) more iterations to verify operation.
9. Report that the test was successful by leaving the lower LED turned ON. When a
failure has occurred, the lower LED shall be turned OFF for 2 seconds. This OFF
period will be followed by a continued blink of the lower LED to indicate the Test Code
below followed by a 2 second OFF break. The blink rate shall be 50 msec ON
followed by 250 msec OFF.
The table below shows reported test codes:
Table 12 Reported Test Codes
Test Code Description
1 Test Successfully Complete
2 RS-232 Communication Failure
3 RS-485 Communication Failure
Capstone Turbine Corporation 21211 Nordhoff Street Chatsworth CA 91311 USA
Technical Reference: ModBus Translator Module
410040 Rev C (April 2008) Page 54 of 58
Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document
without incurring any obligation either with respect to equipment previously sold or in the process of construction.
Uni t Under Test Mode
When powered up, the UUT will respond to commands issued by the Golden System, and
utilize functionality already implemented by the Debug Mode. The Baud Rate selector switch
provided on the ModBus Translator Board will determine RS-485 baud rate. The system will
be capable of receiving RS-232 commands that execute functions over the RS-485 ModBus
interface.
The table below shows RS-232 debug commands that may be performed:
Table 13 - Debug RS-232 Commands
Command Description Arguments
MBADDR
MBTEST
MBRD10
MBWR10
MBRD16
MBWR16
MBECHO

Capstone Turbine Corporation 21211 Nordhoff Street Chatsworth CA 91311 USA
Technical Reference: ModBus Translator Module
410040 Rev C (April 2008) Page 55 of 58
Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document
without incurring any obligation either with respect to equipment previously sold or in the process of construction.
Remappi ng ModBus Regi st er s
In some implementations, it may be desirable to re-map the ModBus register assignments.
This may be done to fill in the gaps in the standard table, allowing for longer multi-byte read
operations. It can be accomplished by using the following Relocate commands.
1. The commands to assign both read and write registers are MBASGN and MBSAVE and
are available at the Capstone prompt (which is enabled by setting all address dip
switches to "off" and connecting the RS232 program to the RS232 port). When new
firmware is installed, the assignments are reset. A batch file can be created to load all
the changes at once.
The command MBASGN works as follows:
MBASGN <enter>: lists all current assignments stored in memory (not NVM)
MBASGN =0 <enter>: clears all current assignments in memory (does not Write to NVM)
MBASGN =<MODBUS addr>, <capstone addr>: assigns default capstone register to new
ModBus Address
MBASGN =<ModBus addr>, 0: deletes ModBus assignment in memory restore default
MBASGN =<ModBus addr>: displays current assignment for specified ModBus Address
shows assigned default
MBSAVE: saves current assignment list to NVM to be loaded on next boot
2. When a new ModBus address is assigned to a Capstone default register, that Capstone
register will no longer be valid at its original address and may not be assigned to another
ModBus address. In other words, it is not possible to have a Capstone default register
(read or write) appear at more than one ModBus address; nor is it possible to have more
than the original number of valid registers available at one time.
3. When re-assigning multi-word registers, only the first register location needs be assigned;
the others will follow automatically. If an attempt is made to assign a register in the
middle of a multi-word bank, a warning is generated and the command is ignored. For
write registers, the multi-word banks are obvious, may be up to 6 words long, and are
indicated as such in the documentation. For the read registers, the multi-word registers
are only those returning pure 32-bit values and may only be 2 words long. To remap
multi-word registers more than 2 words long, the user needs to reassign each word of the
multi-word register. For ex., in case of the fault register, register 46002 will need to be
remapped separately from register 46000, and that separately from register 46004, etc.
4. The MBSAVE command actually writes the assignment list from RAM to flash memory.
The next time the ModBus controller is booted, the new assignments are loaded back
into RAM and used. The MBASGN=0 command can be used to clear the RAM copy of
the assignments; to reload the assignments from NVM use the REBOOT command.
5. By using the MBASGN command to list assignments and RS232 program's "W"
command to save this to disk, a verified batch file for assigning the registers in a
production situation can be created.
NOTE
A register re-assignment map may become invalid after a software upgrade.
The registers per the new software will need to be reassigned once again
after an upgrade.
Capstone Turbine Corporation 21211 Nordhoff Street Chatsworth CA 91311 USA
Technical Reference: ModBus Translator Module
410040 Rev C (April 2008) Page 56 of 58
Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document
without incurring any obligation either with respect to equipment previously sold or in the process of construction.
Table 14 Relocate ModBus Register RS-232 Commands
Command Description Arguments
MBASGN Assign new ModBus addresses See text
MBSAVE Save ModBus changes See text

Capst one Techni cal Infor mat i on
If questions arise regarding ModBus operation for your Capstone MicroTurbine, please
contact Capstone Turbine Technical Support for assistance and information.

Capst one Appl i cat i ons
Toll Free Telephone: (866) 4-CAPSTONE or (866) 422-7786
Fax: (818) 734-5385
E-mail: applications@capstoneturbine.com

Capst one Ser vi ce
Capst one Techni cal Support
Toll Free Telephone: (877) 282-8966
Service Telephone: (818) 407-3600 Fax: (818) 734-1080
E-mail: service@capstoneturbine.com

Capst one Techni cal Support (Japan)
Service Telephone: (818) 407-3700 Fax: (818) 734-1080
E-mail: servicejapan@capstoneturbine.com
Capstone Turbine Corporation 21211 Nordhoff Street Chatsworth CA 91311 USA
Technical Reference: ModBus Translator Module
Appendi x A - ModBus Codeset Downl oad
410040 Rev C (April 2008) Page A-1
Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document
without incurring any obligation either with respect to equipment previously sold or in the process of construction.
Perform the following steps to download the ModBus Codeset:
1. Copy the MODBUS software file (ex: 512620-005.crc), version 1.11, to your
hard drive, and rename the file to MODBUS.crc.
2. Ensure that the power to the MODBUS Translator Board is off.
3. The ADDRESS selector must be set with all switches in the OFF position. This
represents address 0. The position of the rotary switch does not matter.
4. Connect the MODBUS to the COM port of a PC using a straight-through
RS232 serial cable.
5. With CRMS inactive, run the RS232.exe program.
6. Within the RS232.exe interface, enter the command F1 PSSWRD=A4D5M6N!
7. Turn on power to the MODBUS translator. As soon as the Capstone Turbine
logo is seen, press the F1 key.
8. The prompt MNTADM>> should appear. If the prompt does not appear, there
is an apparent failure and earlier steps should be repeated.
9. At the prompt, type LB C:\MODBUS.CRC 70000 10000 (this will actually be the
directory of the copied crc file)
10. The next activity seen at the screen will be several lines of dots or periods;
otherwise, a series of ones and zeroes will appear. When the sequence
finishes, you will receive a 'Downloading Complete and Verified' message.
11. Enter the command DLTEST to query the checksum of this MODBUS
Application Code segment. This checksum should match that of the version
description document.
12. Enter the command DLBURN to burn the MODBUS Application Code into flash
memory.
13. Upon completion of the burn operation, type the command FLEXEC to execute
the MODBUS Application Code.
14. Upon completion of this execute operation, the message MECHO 25 is seen.
15. At this point, shut off power to the MODBUS. However, leave the RS232.exe
program active.
16. The ADDRESS selector must be set to an address in the range 1-247. The
recommended address is 55H.
17. Turn power on to the MODBUS.
18. Watch for the Capstone Turbine logo, the Boot Code version string, and the
MODBUS Application Code version string at the screen.
19. The MNT> prompt should appear.
20. Verify the Boot Code version string has the correct version number.
21. Verify the MODBUS Application Code version string has the correct version
number.
Capstone Turbine Corporation 21211 Nordhoff Street Chatsworth CA 91311 USA
Technical Reference: ModBus Translator Module
APPENDIX B ASCII Char t

410040 Rev C (April 2008) Page B-1
Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document
without incurring any obligation either with respect to equipment previously sold or in the process of construction.
Decimal Hexadecimal Character Decimal Hexadecimal Character
48 0x30 0 101 0x65 e
49 0x31 1 102 0x66 f
50 0x32 2 103 0x67 g
51 0x33 3 104 0x68 h
52 0x34 4 105 0x69 i
53 0x35 5 106 0x6A j
54 0x36 6 107 0x6B k
55 0x37 7 108 0x6C l
56 0x38 8 109 0x6D m
57 0x39 9 110 0x6E n
65 0x41 A 111 0x6F o
66 0x42 B 112 0x70 p
67 0x43 C 113 0x71 q
68 0x44 D 114 0x72 r
69 0x45 E 115 0x73 s
70 0x46 F 116 0x74 t
71 0x47 G 117 0x75 u
72 0x48 H 118 0x76 v
73 0x49 I 119 0x77 w
74 0x4A J 120 0x78 x
75 0x4B K 121 0x79 y
76 0x4C L 122 0x7A z
77 0x4D M
78 0x4E N
79 0x4F O
80 0x50 P
81 0x51 Q
82 0x52 R
83 0x53 S
84 0x54 T
85 0x55 U
86 0x56 V
87 0x57 W
88 0x58 X
89 0x59 Y
90 0x5A Z
97 0x61 a
98 0x62 b
99 0x63 c
100 0x64 d