ED/120637/GTP/R3

No. Description Unit of


Measurement
Details
1 Manufacturer/country of Origin TELK, KERALA, INDIA
2 Continuous maximum rating a) ONAN MVA 15
b) ONAF MVA 20
3 Voltage ratio at no-load and principal kV 11.5/33 (LV/HV)
4 Tapping range +5% to -15%
5 Size of tapping step 1.6670%
6 No. of steps 12 (13 taps)
7 Vector group YNd11
8 On-load Tap Changer
a) Manufacturer TELK
b) Type reference YE on HV Nuetral
c) HV or LV winding HV
d) Range on/off load On load
e) Type test certificate ref./date -
9 Type of cooling ONAN/ONAF
10 Winding temperature rise at CMR under
site service conditions
C 50
11 Top oil temperature rise at CMR under
site service conditions
a) ONAF rating C 40
b) ONAN rating (full rating required) C 40
12 Hot spot temperature rise C as per IEC 60076
13 Flux density (no-load) Tesla 1.6 (max.)
14 No-load loss kW 9.5 kW (max.)
15 Load loss at 75C at CMR
a) ONAF rating kW 97 kW (max.)
b) ONAN rating (full rating required) kW 54.5 kW (approx..)
16 Total loss at 75C and normal ratio at
CMR
a) ONAF rating (including aux. losses) kW 109 kW (max.)
b) ONAN rating (full rating required) kW 64kW (approx.)
TECHNICAL PARTICULARS AND GUARANTEES
20MVA 11.5/33 kV (LV/HV) TRANSFORMERS
ED/120637/GTP/R3
No. Description Unit of
Measurement
Details
TECHNICAL PARTICULARS AND GUARANTEES
20MVA 11.5/33 kV (LV/HV) TRANSFORMERS
17 Regulation at 75C and normal ratio at
CMR
a) ONAF rating % 1.27 (approx.) at upf
b) ONAN rating (full rating required) % 0.87 (approx.) at upf
18 Impedance voltage at CMR
a) ONAF rating % 12.5 (subject to IEC tolerance)
b) ONAN rating (full rating required) % 9.3 (approx.)
19 Zero sequence impedance at CMR
a) ONAF rating % 10 (approx.)
b) ONAN rating (full rating required) % 7.5 (approx.)
20 Noise level at CMR
a) ONAF rating dBA 71 (approx.)
b) ONAN rating (full rating required) dBA 65 (approx.)
21 Type of construction (shell or core) Core type
22 Winding (brazed or crimped) Winding brazed, leads crimped
23 Thickness of tank
a) sides 10 (approx.)
b) Bottom 20 (approx.)
24 No. of cooler banks 2 x 50%
25 No. of air blowers per coller bank Adequate
26 Total oil including cooling system litres 9000 (approx.)
27 Total weight of complete transformer tonne 37 (approx.)
28 Weight of transformer for transport tonne 28. 5 (approx.) [Oil filled condition]
29 Manufacturer, type and class of oil IEC 296-1982,Class1.
Apar/Savitha/Raj Lubricants
30 Transformer bushings
a) Manufacturer TELK
b) Type reference Plain Porcelain type
HV LV
c) Rated current A 630 2000
d) Lightning impulse voltage withstand kV 170 95
e) Power frequency voltage withstand kV 70 38
f) Total creepage distance of insulator mm 25mm/kV 25mm/kV
g) Type test certificate ref./date - -
ED/120637/GTP/R3
No. Description Unit of
Measurement
Details
TECHNICAL PARTICULARS AND GUARANTEES
20MVA 11.5/33 kV (LV/HV) TRANSFORMERS
31 Brief description of transformers or
parts thereof subjected to short circuit
test or for which short circuit
calculations are available
NPC35 MVA, 21/6.9 kV
32 Highest System Voltage for
a) 33kV 36kV
b) 11kV ` 12kV
33 HVN BCT Details
Core - 1
Current Ratio 400-200/1 A
Class PS
Vk 63 / 90 Volts
Rct 2 / 1 ohm
I0 20 / 50mA at Vk/2
Core -2
Current Ratio 400-200/1 A
Class 5P
ALF 20
Burden 15VA
34 overloading capability for 4 hours with
60% initial loading at specified
As per IEC 60076-7.
110% Continuous.
35 Insulation Level (Basic impulse
withstand voltage/AC withstand
HV winding kV
Peak/kVrms
170/70
LV winding kV
Peak/kVrms
75/28
36 Efficiency at full load % 99.47
37 Inrush current (HV) kA 2.5
38 Phase current
HV current A 349.9
LV current A 579.7
39 Reactance (HV) ohms 2.6 Approx.
Resistance (HV) ohms 0.11 Approx.
Zero sequence reactance % 9.98
40 Cooling System
a) No of radiator on the transformer tank 6
b) Thickness of radiator plates mm 1.2
ED/120637/GTP/R3
No. Description Unit of
Measurement
Details
TECHNICAL PARTICULARS AND GUARANTEES
20MVA 11.5/33 kV (LV/HV) TRANSFORMERS
c) Fan motor(Type/make/no of fans/motor
rating)
Propeller type
Marathon-6nos
0.37kW
** Note:- Item no.30:- Since the bushings are placed inside airfilled cable box, 25mm/kv
creepage distance is sufficient which is also as per Cl.No: 2.6 section IID of OES 6. In this
clause creepage distance of HV bushing shall be 805mm and that of LV bushing shall be
295mm,the bushings offered by us is having creepage distance of 900mm and 440mm for
HV and LV respectively.
Item no.37:- The no load current of transformer in steady state condition is very small
compared to full load current however no load current can exceed the rated current at the
time just after switching in and may last for onlyfew cycles. Hence it is very difficult to
measure and plot its value verses time manually.so plz consider the same.