Sie sind auf Seite 1von 4

Clean Room Specifications

AIR-CONDITIONING SYSTEM
i)

AIR CONDITIONING SYSTEM


Brand
: SAIVER / DUNHAM BUSH
Type
: AIR COOLED DUCTED SYSTEM

ii)

DUCT WORK
To supply and install TDC Joint & Slip Joint For Supply Air Duct, Return Air
Duct c/w 1" PE insulation
a) Low Level Return Air Grille c/w damper
b) Copper pipe c/w R22 Gas filling for Indoor & Outdoor unit.
Control Panel C/W Wiring 800 Amps / 3 phase ( Incoming Power Supply By
c) Others )

iii)

HEPA FILTER HOUSING


1.5mm thk Electrogalvanised Steel c/w Epoxy Powder
Material
: Baked
Finishing
: Epoxy Powder Baked
Internal Size
: 685(W) x 685(D) x 300(H)mm

iv)

HEPA FILTER
Brand
Frame
Efficiency
Air Velocity
Size

v)

SECONDARY
FILTER
Brand
Model
Efficiency
Size

vi)

:
:
:
:
:

CAMFILFARR / AAF
Aluminium
99.99% on 0.3 micron
920 cfm
610(W) x 610(D) x 150(H)mm

:
:
:
:
:

CAMFILFARR / AAF
Rigidpleat
99% on Arrestance on 0.5 micron
90 - 95% on Dust Spot
24" x 24" x 12"

PRIMARY FILTER
Brand
: CAMFILFARR / AAF
Model
: Superpleat
Efficiency
: 92% on Arrestance on 0.5 micron
: 25 - 30% on Dust Spot
Size
: 24" x 24' x 2"

CEILING PANEL SYSTEM

i)

AIR TIGHT PU CEILING ( CONSEALED TYPE )


0.55mm thick Electrogalvanised Steel c/w
Material
: powderbaked
Infill
: 50mm thick polyurethane
Density
: 40 - 45 kg/m3
Size
: 1200mm (W) x 3000mm (L)
Colour
: White
Joint System
: Aluminium Consealed Ceiling Tee
Caulking
: Anti - Fungus Neutral Cure Sealent
Hanging System
: Dia. 10mm threaded rod c/w turnbuckle
Price Including : Hole Opening for Low Level Return, Hepa Housing &
Lighting ~ 170 nos

C WALL PANELLING SYSTEM


i)

PU WALL PANELLING
0.55mm thick Electrogalvanised Steel c/w
Material
: powderbaked
Infill
: 50mm thick polyurethane
Density
: 40 - 45 kg/m3
Size
: 1200mm (W) x 2500mm (L)
Colour
: White
Joint System
: Tongue And Groove
Caulking
: Anti - Fungus Neutral Cure Sealent

ii)

VIEWING GLASS WINDOW


Normal 5mm thick clear glass c/w slope aluminium
Material
: window frame
Size
: 900mm (W) x 1200mm (H)

iii)

BOX UP LOW LEVEL RETURN


Size
: 500mm (W) x 200mm (H)
Size
: 300mm (W) x 200mm (H)

D FLOORING SYSTEM
i)

NORMAL VINYL FLOOR SHEET


Brand
: GERFLOR
Model
: MIPOLAM 180
Thickness
: 2mm
Joint System
: Welded Rod
Colour
: To Be Advised
Price Including
: Floor Screeding

ii)

100MM (H) COVE SKIRTING


Material Used
: PVC Cove Former And 100mm Bend Up Vinyl Sheet

LIGHTING SYSTEM C/W WIRING POINT


i)

PHARMA GRADE BOX LIGHTING


Lighting Tube
: Philips 36/54 ( 2 tubes x 36watts )
Lighting Tube
: Philips 36/54 ( 3 tubes x 36watts )
Casing
: Powderbaked Steel
Size
: 600mm (W) x 600mm (L)

ii)

SINGLE PHASE 13 Amps POWER POINT (Including Spare)

iii)

THREE PHASE 16 Amps POWER POINT C/W ISOLATOR

DOOR SYSTEM
i)

POLYURETHANE HALF GLASS SINGLE LEAF SWING DOOR


0.55mm thick Electrogalvanised Steel c/w
Material
: powderbaked
Infill
: 40mm thick polyurethane
Size
: 1000mm x 2100mm

ii)

INTERLOCKING SYSTEM FOR 21 DOORS

G CLEANROOM EQUIPMENTS
i)

PASSBOX
Material
Internal Size
External Size

: 1.5mm thk Electrogalvanised Steel c/w Powderbaked


: 600mm(W) x 600mm(D) x 600mm(H)
: 785mm(W) x 600mm(D) x 690mm(H)

H BUILDING AUTOMATION SYSTEM (BAS)


MONITORING AND CONTROL FOR 5 AHUs
i) Air conditioning - temperature, relative humidity,
ii) Filtration - pressure differential for HEPA filter life span ( 5 points )
iii) All critical lab equipments - on/off signal
Fire Fighting - monitoring only signal rooping from Control Office - Signal
iv) given by HMS
v) Room Pressure Monitoring for Cleanroom 1, 2 & 3 only
vi) Oxygen & Liquid Nitrogen Level monitoring only. - Signal given by Intran
Monitoring - Temperature sensor for 3 refrigerators and 3 freezers - Signal
vii) given by Intran
Monitoring - Temperature, Humidity & Co2 concentration for at least 6
viii) Incubator - Signal given by Intran
BAS is included software and hardware for all data retrieving and processing
components such as sensors.
I

THIRD PARTY TESTING AND VALIDATION

i)

Testing , Commissioning and validation comply to NEBB testing procedure


Scope of work
: i) Scan Test
"- To determine any leakages from HEPA Filter and
: Housing
: ii) Airflow Velocity Test
"- To determine the air velocity from air supply to table
: level
: iii) Particle Count Test
: "- To determine cleanliness level at table top level.
: iv) Temp. and RH Test
: "- To determine clean room thermal condition
: v) Room Pressurization Test
: "- To determine any cross contamination between room
vi) Air Change Calculation
"- To determine clean room cleanliness level

Testing, Commissioning and validation comply to NEBB testing procedure during


ii) warranty period.

Das könnte Ihnen auch gefallen