0 Bewertungen0% fanden dieses Dokument nützlich (0 Abstimmungen)
50 Ansichten59 Seiten
Electrical arc short circuits in metal clad switchgear and low voltage panels may occur for many different reasons. Defective or ageing insulating materials poor bus or cable connections poor maintenance human error ingress of moisture, dust or vermin abnormal service conditions.
Electrical arc short circuits in metal clad switchgear and low voltage panels may occur for many different reasons. Defective or ageing insulating materials poor bus or cable connections poor maintenance human error ingress of moisture, dust or vermin abnormal service conditions.
Electrical arc short circuits in metal clad switchgear and low voltage panels may occur for many different reasons. Defective or ageing insulating materials poor bus or cable connections poor maintenance human error ingress of moisture, dust or vermin abnormal service conditions.
1S20 Arc Fault Monitor 1S20 Arc Fault Monitor 1S20 Arc Fault Monitor Electrical arc short circuits in metal clad switchgear and low voltage panels may occur for many different reasons. defective or ageing insulating materials poor bus or cable connections poor maintenance human error ingress of moisture, dust or vermin abnormal service conditions Arc Fault Effects and Consequences ENERGY RELEASED BY ARC FAULT ENERGY RELEASED BY ARC FAULT PRESSURE RISE TEMPERATURE RISE VISUAL & ACCOUSTIC PHENOMENA EFFECTS OF FAULT ARC CONSEQUENCES FOR PLANT MECHANICAL STRESSING OF ENCLOSURES THERMAL STRESSING, MELTING, FIRE VAPOURISATION CONSEQUENCES FOR PERSONNEL SHOCK WAVE, FLYING DEBRIS, OPENING PANELS U/V BURNS & EJECTION OF FLAMES & HOT GASES & SMOKE Switchgear Failure Effects and Consequences Switchgear Internal Fault Example FAULT TIME PROTECTION TRANSFORMER 2 secs OC-relay 110/22 kV 30 MVA Switchgear Internal Fault Example FAULT TIME PROTECTION TRANSFORMER 0.07 secs Arc protection 110/22 kV 30 MVA Variable Speed Drive Fault Example PROTECTION TRANSFORMER Earth leakage 22 kV / 690V Water Corporation Western Australia At approximately 0800 hrs on 25/2/07 No.2 VSD failed at Tamworth Pumping Station WA. The PSN electrician was called out to the fault later that same morning and found the main switch compartment of the drive badly damaged. The extent of damage is quite severe and was contained to the main switch compartment of the variable speed drive. The majority of damage appears to have been originated from the VSD main switch, then spreading upon explosion to the upper and rear of the drive and also externally through the ventilation ducts. Variable Speed Drive Fault Example The earth leakage protection on the #2 VSD 22kV / 690V feeder tripped. The O/C protection also detected a phase fault condition. #2 22kV / 690V Transformer circuit breaker was found to be in the OFF position. Judging by the extent of the damage the protection clearly did not respond quickly enough. Variable Speed Drive Fault Example Variable Speed Drive Fault Example OPERATOR HAZARD IN ADJACENT CORRIDOR Variable Speed Drive Fault Example 1S20 ARC FAULT PROTECTION INSTALLED AFTER EARLIER FAULT Variable Speed Drive Fault Example SUBSEQUENT FAULT As a result of this incident, RMS 1S20 Arc Fault Monitors and 1S30 Arc Flash Sensors were installed. Subsequently several months later another incident occurred, this time due to the failure of the IGBT board. As a consequence, the arc sensors were triggered by tripping the 22kV circuit breaker and as can be seen by the photos the damage was insignificant. 1S30 ARC SENSOR ARC FAULT Variable Speed Drive Fault Example SUBSEQUENT FAULT ARC FAULT 1S20 Arc Fault Monitor For moderate arc fault currents the trip time of the over-current stage will be too slow: For very low arc fault currents the instantaneous trip stage of a standard over-current relay cannot be set low enough. 1S20 Arc Fault Monitor The degree of damage caused by arcing depends principally on the duration of the arc. ~100ms Arc Fault Duration The switchgear needs to be checked & the insulation resistance measured before power can be re-established. ~200ms Arc Fault Duration The power supply will be interrupted; the switchgear must be checked; power is re- established only after minor repairs. 1S20 Arc Fault Monitor ~100ms Arc Fault Duration 1S20 Arc Fault Monitor The degree of damage caused by arcing depends principally on the duration of the arc. ~500ms Arc Fault Duration The supply is interrupted, metal parts of the switchgear are destroyed & poisonous gases are emitted. ~1s Arc Fault Duration Destroys most of the switchgear & may cause a fire, injury to personnel & damage to property. 1S20 Arc Fault Monitor ~500ms Arc Fault Duration 1S20 Arc Fault Monitor Arguably the greatest risk of arc fault damage exists at the CB cable termination & in the CB chamber itself due to the slow clearance times of the IDMT feeder protection. The problem of arc faults is most prevalent in older metal clad switchgear, which already has operational protection systems. The CB cable termination is particularly at risk to ingress of moisture & rodent damage. System Integration Trip on arc fault <10ms Type: 1S20K1 [C] Vx: 48V DC Serial No: 126578 1S20 Arc Fault Monitor ARC FAULT TRIP INITIATE CB ARC FAULT MONITOR SENSOR RESET / TEST System Functioning Arc Fault Trip System Ser vice DC Fail GREEN: RED: ORANGE: DARK: Single Line Diagram 1S30 1S20 Cable box only Trip on Arc Fault System Integration With current check using high speed starter element Type: 1S20K1 [C] Vx: 48V DC Serial No: 126578 1S20 Arc Fault Monitor ARC FAULT TRIP INITIATE CB ARC FAULT MONITOR SENSOR OVER-CURRENT RELAY 3 Pole OC + EF RESET / TEST System Functioning Arc Fault Trip System Service DC Fail GREEN: RED: ORANGE: DARK: Single Line Diagram 1S30 1S20 50/51 Cable box only Trip only if over current starter picked up Single Line Diagram Cable box and CT chamber 1S30 1S30 1S20 50/51 Single Line Diagram 1S20 1S30 1S30 1S30 50/51 Trip BUS CB(s) Cable box, CT and CB chamber Single Line Diagram Cable box, CB and BUS chamber 1S20 1S30 1S30 1S30 50/51 Trip BUS CB(s) Single Line Diagram BUS chamber 1S20 1S30 1S30 50/51 50/51 50/51 1S20 with 1S30 Optical Sensors 1S30 Arc Sensor Mounted in each segregated switchgear chamber Sensitivity linear in forward direction through 180 Detects reflected arc light - mounting position not critical Burden 2.5mA (quiescent) Optional rear facing sensor 1S30 Arc Sensor Installation Mounting position of the Sensor is not critical. High sensitivity in direction of View 1S20 System Testing Use camera flash to check operation of arc sensor and pick up of 1S20 trip contact. Typical operating range of flash to arc sensor is 50 to 300mm 1S20 System Testing CRO trace showing nominal operation time of the trip contacts. First contact touch at 6.25ms and fully closed by 7.25ms. 1S30 Arc Sensor Installation 1S30 shown mounted on the outside of a switchgear panel Detector oriented to look through a hole into the switchgear Switchgear panel 2 x M4 self threading mounting screws (Supplied) Sealed cable stress relief Optical detector protruding through hole in panel 1S30 Arc Sensor Installation 1S30 shown mounted on the inside of a switchgear panel Detector oriented to look out into the switchgear compartment 2 x M4 self threading mounting screws (Supplied) Optical detector facing away from panel 1S30 Arc Sensor Installation The dual optical detector version can be panel mounted to monitor two adjacent switchgear compartments simultaneously. Internal partition between switchgear compartments Optical detector protruding through compartment divider into adjacent switchgear chamber Optical detector window facing away from compartment divider 1S30 Arc Sensor Installation Right angle mounting off a surface Mount off floor or walls within switchgear / BUS bar chamber Right angle mounting bracket Optical detector window facing away from right angle mounting bracket Single optical detector Dual optical detector 1S30 Arc Sensor Installation Flush mount reinforcing plate 1.2mm zinc plated mild steel 2 x M4 self threading mounting screws (Supplied) Flush mount reinforcing plate 1S30 Arc Sensor Installation SENSOR LOCATIONS Cable Box Arc Fault 13.1kA (50mS) Fault created in Cable Box by connecting three bushing connectors with fuse wire. Sensor fitted to side of box. Cover after test Cover as new Cable Box Arc Fault Lower portion of Cover strengthened Cable Box Arc Fault Sensor location CB Chamber Arc Fault CB chamber fault at 13.1kA (50mS) Fault initiated by connecting 3 phases of circuit side of CB with fuse wire - typical of test leads used during maintenance. One ARC sensor fitted. CB Chamber Arc Fault General views after test 1S20 Does it Work WILL IT OPERATE UNDER DYNAMIC CONDITIONS? --- YES HOW FAST DOES IT REMOVE AN INTERNAL FAULT? --- 50-75ms IS IT EFFECTIVE IN ALL SWITCHGEAR CHAMBERS? --- YES HOW MUCH DAMAGE IS CAUSED TO THE SWITCHGEAR? --- Minimal DOES IT IMPROVE SAFETY? --- YES, Significantly 1S30 Arc Sensor measured current ( increase 1*In ==> 10*In) arc detection overcurrent detection trip output contact One, two or three independent arc sensor inputs Two high speed tripping duty arc sense output contacts <10ms arc fault tripping time Self supervision with fail alarm contact Push button reset & self test 1S30 Arc sensor continuous supervision Compact, economic design Simple panel mounting for retrofit applications 1S20 Summary Front Panel Indication Solid red for 2s followed by: Alternate red & green until reset. Green solid Orange solid Alternate orange & red. System healthy 1S30 Arc Sensor service 1S30 Arc Sensor continuous pick up Flash green 3 times 1S30 Power up test OK Arc fault trip Front Panel FRONT VIEW Type: 1S20K1 [C] Vx: 48V DC Serial No: 126578 1S20 Arc Fault Monitor RESET / TEST System Functioning Arc Fault Trip System Service DC Fail GREEN: RED: ORANGE: DARK: 52mm SERIAL NO. & RATING LABEL IN THIS POSITION ON REAR TERMINAL BLOCK FOR 1S20 [x][A][x] PANEL MOUNT VERSION REMOVE FOR REAR CABLE ENTRY OPTION REAR VIEW REMOVE FOR TWO M4 OR 4BA MOUNTING SCREWS 32mm TOP & BOTTOM REAR TERMINAL BLOCK RETAINING SCREWS 31 1mm ID + ( 7 5 ) 1 1 3 m m 8 5 m m (30) (30) ( 7 5 ) PANEL CUT OUT DETAIL (Minimum clearance to other devices)mm 1 S 2 0 K 2
( C A B ) A U X : 3 6 - 1 5 0 V
D C
S / N : 1 2 3 4 5 6 Panel or Surface Mounting Panel or Surface Mounting 86mm 25mm Use double sided tape supplied Top & bottom positions 24mm SIDE VIEW RELAY PANEL 3mm THICK MAXIMIUM FRONT PANEL LABEL (Supplied with module) SLIDE OUT CABLE ENTRY POINTS 3 ON ONE SIDE 1 AT EACH END TOP & BOTTOM REAR TERMINAL BLOCK RETAINING SCREWS THESE MAY BE UNSCREWED & REVERSED TO FIT FROM THE FRONT OF THE 1S20 MODULE TO ALLOW SURFACE MOUNTING RETENTION SHROUD 1S20 Arc Fault Monitor RESET / TEST System Functioning Arc Fault Trip Sensor 1 Service Sensor 2 or 3 Service Continuous Sensor P/U DC Supply Fail GREEN: RED: ORANGE SOLID: ORANGE FLASH: ORANGE / RED: NONE: S/N:123457 DIN Rail or Surface Mounting 5mm 82mm 24mm SIDE VIEW OPTIONAL DIN RAIL CLIP P/N H01180001B - DIN rail mount version DIN RAIL RELEASE LEVER SLIDE OUT CABLE ENTRY POINTS 3 ON ONE SIDE 1 AT EACH END S/N:123456 1S20K1 (CBB) ARC FAULT MONITOR DC Fail Arc Fault Trip System Functioning Sensor 1 Service Sensor 2 or 3 Service Continuous Sensor P/U AUX:36-150V DC RESET / TEST NONE: RED: GREEN: ORANGE SOLID: ORANGE FLASH: ORANGE / RED: Switch 1: Optional arc sensor 2 ON or OFF Switch 2: Arc fault trip indication LED reset Switch 3: Independent arc trip ON or OFF Switch 4: Arc fault trip output contact latch function; ON for LATCHING, OFF for self reset. Switch 5: Optional arc sensor 3 ON or OFF 1S20 Configuration Settings ON ON ON ON ON OFF OFF OFF OFF OFF 1: ARC SENSOR 2 2: LATCHING TRIP LED 3: INDEPENDENT ARC TRIP 4: LATCHING TRIP CONTACTS 5: ARC SENSOR 3 1S20 Wiring Termination 1S20 SOCKET TERMINAL LAYOUT Viewed the from front when un-plugged from the main housing (Always wire Arc Sensor 1. Arc sensor 2 & 3 optional) 2 2 1 1 3 3 4 4 5 5 6 6 8 8 9 9 12 12 11 11 10 10 1S20 Wiring Application 1S20 application diagram - Circuits shown in de-energised condition 12 8 10 9 9 or 11 5 1 3 11 6 2 4 Vx + + Fail alarm Arc 1 Arc 3 Arc 2 Arc fault trip alarm signal to protection relay status input for comms. I>start Control Protection 1S20 50/51 Overcurrent relay Arc fault relay I> CB Aux Switch Trip Coil 52 T 52 - a 1S20 Ordering Code Generate the required ordering code as follows: e.g. 1S20-CAB
1 AUXILIARY SUPPLY RANGE A 20 - 60V DC C 36 - 150V DC
2 MOUNTING A Panel mount or surface mount B DIN rail or surface mount only
3 SENSORS A Two arc sensor inputs (Default) B Three arc sensor inputs
PS5R POWER SUPPLY MODULE Use the PS5R-A24 DIN rail mount module to power a single 1 from an 85-164V AC auxiliary source. 1 2 3 1S20 Arc Fault Monitor Relay 1S30 Ordering Code Generate the required ordering code as follows: e.g. 1S30 AA
1 DETECTORS A Single through hole panel detector B Dual detectors
2 FLUSH MOUNT REINFORCING PLATE A Not required B Required 1 2 1S30 Arc Fault Sensor 1S28 Arc Fault Scheme
1S20 Additional Information Technical Bulletin User Guide Price & Availability www.rmspl.com.au/1s20.htm Test Manuals www.rmspl.com.au/search.asp Other Products www.rmspl.com.au/products.htm