Doc Ref: LMAN009_R2V2

16 Digital Inputs (PNP), 16 Digital Outputs


Relay PLC, 7 colour TFT Touch Screen - 220VAC
16 Digital Inputs, 16 Digital Outputs
Transistor PLC, 7 colour TFT Touch Screen - 220VAC
XMP2-32R-E
XMP2-32T-E
XMP2-32T-C
16 Digital Inputs(PNP), 16 Digital Outputs
Relay PLC, 7 colour TFT Touch Screen - 24VDC
16 Digital Inputs, 16 Digital Outputs
Transistor PLC, 7 colour TFT Touch Screen - 24VDC
XMP2-32R-C
XMP2-32 Series Combined HMI/PLC Unit MANUAL

XMP2-32 Combined Unit Manual Page 2 of 36 LMAN009_R2V2


XMP2-32 with colour touch screen

Index Page

Chapter 1 XMP2-32R/T introduction


1-1 Performance and characteristics 4
1-2 Specs
1-2-1 General specs 5
1-2-2 HMI specs 6
1-2-3 PLC specs 7
1-3 Part name
1-3-1 LED display 9
1-3-2 Download port 9
1-3-3 Com port 9
1-3-4 Port A and B 9
1-4 Dimensions 10

Chapter 2 In/out specs and external layout
2-1 Input specs and layout 12
2-2 Output specs and layout 13

Chapter 3 PLC function and use
3-1 PLC instructions 16
3-2 Soft component range 18
3-3 Build a project 20
3-4 Communication function
3-4-1 Com port 23
3-4-2 Communication parameters 24
3-4-3 Communication mode 25

Chapter 4 HMI function and use
4-1 Online 28
4-2 Build a project 30

Chapter 5 The extension ability
5-1 Summarization 32
5-2 Extend MA model
3-4-1 Summarization 33
3-4-2 Model specs 34
3-4-3 Model connection 35

XMP2-32 Combined Unit Manual Page 3 of 36 LMAN009_R2V2


1XMP2-32 Introduction


XMP2-32R/T introduction

Model Function
XMP2-32R-E 16 DI, 16 DO Relay PLC, with a 7" colour TFT touch screen and
26 function keys, AC220V
XMP2-32R-C 16 DI, 16 DO Relay PLC, with a 7" colour TFT touch screen and
26 function keys, DC24V
XMP2-32T-E 16 DI, 16 DO Transistor PLC, with a 7" colour TFT touch screen
and 26 function keys, AC220V
XMP2-32T-C 16 DI, 16 DO Transistor PLC, with a 7" colour TFT touch screen
and 26 function keys, DC24V






























1-1 Performance and characteristics
1-2Specs
1-3 Parameters
1-4 Dimensions

XMP2-32 Combined Unit Manual Page 4 of 36 LMAN009_R2V2













XMP2-32 family is PLC+HMI integrators. This family has 4 models as listed above. The 4 models
have the same aspect. Besides fulfilling the control requirements, XMP2-32 models can replace
the common HMI and PLC in the control system. The compact shape saves space and also
convenient for the maintenance engineer.

XMP2-32 MP760-T + XC2-32.
Integrate logic control, analogue input/output, HMI in one body
Digital Input: 16 points.
Digital Output: 16 points.
Brief and simple program interface.
HMI Part: 7" touch screen, true colour TFT, 256 colour, 480234 pixel, LCD life can reach
50,000 hours.
26 Function Keys, sensitive and precise.
Supports high speed count, high speed pulse, external interruption.
Multi-function download port: Uses the same cable to download HMI and PLC
program.
Waterproof level: IP20.
Compact size, saves space in the electric control cabinet.




















1-1 Performance and characteristics

XMP2-32 Combined Unit Manual Page 5 of 36 LMAN009_R2V2










1-2-1 General specs





















Input Voltage AC220V
Power Consumption Less than 10W (TYP2.0W)
Momentary Power-Off
Allowance
Less than 20ms
Voltage Endurance AC1000V-10mA 1minute (between signal and ground)
Insulated Impedance DC500V about 10M (between signal and ground)
Operating Temperature 0~50
Storage Temperature 10~60
Ambient Temperature 20~85% (No Dew)
Vibration 10~25Hz (X, Y, Z each direction 30 minutes 2G)
Anti-interference Voltage Noise: 1000Vp-p
Ambient Condition No corrosive gas
Protection Level IP20

1-2 Installation steps

XMP2-32 Combined Unit Manual Page 6 of 36 LMAN009_R2V2






1-2-2 HMI specs








Screen Property

Type TFT 256-colour LCD
Screen Dimension 7 inch

Use Life
Over 50000 hours, 25, 24 hours
running
Display Area 480*234
Contrast Not modifiable
Character setting English, Japanese,
Character size Free size and font
Touch mode Digital mode touch

Register
Picture 8KB
Data 4KB
























XMP2-32 Combined Unit Manual Page 7 of 36 LMAN009_R2V2






1-2-3 PLC specs

Item
Specs
XMP2-32R/T-E
Program executing format Loop scan format, time scan format
Program format Instruction, C language and ladder chart
Processing speed 0.5us
Power -off Retentive Use Flash ROM and Li battery
User programs capacity 128KB
I/O points 16 digital input, 16 digital output
Internal coil (M) number 8512

Timer (T)
Points 640
Specs
100mS timerSet time 0.1~3276.7 seconds
10mS timerSet time 0.01~327.67 seconds
1mS timerSet time 0.001~32.767 seconds

Counter (C)
Points 640
Specs
16 bits counterset value K0~32767
32 bits counterset value -2147483648~2147483647
Data Register (D) 2512 words
Flash ROM Register (FD) 512 words
High speed processing function High speed countpulse outputexternal interrupt
Time Scan Interval Setting 0~99mS
Password protection 6 bits ASCII
Self-diagnose function Power on self-diagnoseMonitor timergrammar check








XMP2-32 Combined Unit Manual Page 8 of 36 LMAN009_R2V2

























1-3 Part names


Function keys
Display and
touch area
Number keys
Power point
Product label
Input point Output point
Com Port
Download Port
USB CJ45 port

XMP2-32 Combined Unit Manual Page 9 of 36 LMAN009_R2V2






1-3-1 LED display

PWR: Power supply light
RUN: program control light
STOP: program control light


1-3-2 Download port

The port is RS-232 standard and able to download PLC program and HMI screen.

Pin2 RXD
Pin3 TXD
Pin5 GND

Used as RS-485 com port: for HMI connecting with slave device











Cable connection figure:


Attention:
1 Do not switch off when downloading, or you have to download again
2 The cable for downloading the HMI screen is the same as downloading PLC program
3 Do not download when XCPPro and TP software are both open
RS-232 download port is only used to download


1-3-3 Com port

The port is RS-232 standard, is used to connect PC and HMI.

Pin2 RXD
Pin3 TXD
Pin5 GND

1-3-4 Port A and B

The port is RS-485 standard, is used to connect meter, inverter, extension model, etc.

Pin1 A
Pin9 B
Pin6
PRT (when HMI connecting with slave device, short pin
5&6)
Pin8
DOWNLOAD (short pin 5&8 to force-download HMI
screen)

XMP2-32 Combined Unit Manual Page 10 of 36 LMAN009_R2V2



Attention:
A, B port and RS-232 COM port is the same port, and cannot be used at the same time.






Outline dimension (mm):



Install dimension (mm):









1-4 Open and close XCP Pro

XMP2-32 Combined Unit Manual Page 11 of 36 LMAN009_R2V2



2In/out specs and external layout




















































2-1 Input specs and layout
2-2Output specs and layout

XMP2-32 Combined Unit Manual Page 12 of 36 LMAN009_R2V2









Input specs:



















Input connection figure:



Input point arrangement:















Input signal voltage DC24V10%
Input signal current 7mA/DC24V
Input ON current Above 4.5mA
Input OFF current Below 1.5mA
Input response time About 10ms
Input signal format Point input or NPN collector
open transistor
Circuit insulation Photoelectric coupling
isolation

2-1 Input specs and layout

XMP2-32 Combined Unit Manual Page 13 of 36 LMAN009_R2V2








Relay output:
Internal power Below AC250VDC30V
Circuit insulation Machine insulation
Action indication LED light

Max load
Resistor load 3A
Induction load 80VA
Light load 100W
Open circuit current No
Minimum load DC5V 2mA

Response time
OFFON 10ms
ONOFF 10ms



Transistor output:





























Internal power Below DC5~30V
Circuit insulation Optical coupling insulation
Action indication LED light

Max load
Resistor load 0.8A
Induction load 12w/DC24V
Light load 1.5W/DC24V
Open circuit current < 0.1 mA
Minimum load DC5V 2mA

Response time
OFFON 0.2ms
ONOFF 0.2ms

2-2 Output specs and layout

XMP2-32 Combined Unit Manual Page 14 of 36 LMAN009_R2V2



Output connection figure:
Relay output:


Transistor output connection


Output point arrangement:








XMP2-32 Combined Unit Manual Page 15 of 36 LMAN009_R2V2



3PLC functions and use




















































3-4 Communication function
3-1 PLC instructions
3-2Soft component range
3-3 Build a project

XMP2-32 Combined Unit Manual Page 16 of 36 LMAN009_R2V2









XMP2-32R/T-E series product uses XC2 series PLC (the PLC instructions are the same as XC2-
32). It contains SFC instructions, applied instructions and special function instructions. Please
refer to XC Series PLC Operating Manual:

I/O point definition and distribution.

1. High speed count


(1) Increment mode: 5 channels

Channel Input Counter Highest frequency
CHL1 X0 C600 80KHZ
CHL2 X1 C602 80KHZ
CHL3 X3 C604 10KHZ
CHL4 X6 C606 10KHZ
CHL5 X11 C608 10KHZ



(2) Pulse + direction mode: 3 channels

Channel Input
Pulse Direction
Counter Highest frequency
CHL1 X0 X1 C620 80KHZ
CHL2 X3 X4 C622 10KHZ
CHL3 X6 X7 C624 10KHZ


(3) AB phase mode: 3 channels

Channel
Input
Phase B Phase A Counter Highest frequency
CHL1 X0 X1 C630 80KHZ
CHL2 X3 X4 C632 5KHZ
CHL3 X6 X7 C634 5KHZ

3-1 PLC instructions

XMP2-32 Combined Unit Manual Page 17 of 36 LMAN009_R2V2




2. High speed pulse output
a) T type: Y0, Y1 available, the highest frequency is 400KHz
b) RT type: Y0, Y1 available, the highest frequency is 400KHz
c) R type: unavailable

3. Interrupt function

Channel Input Pointer tag Disable interruption
instruction
Rising interruption Falling interruption
CHL1 X2 I0000 I0001 M8050
CHL2 X5 I0100 I0101 M8051
CHL3 X10 I0200 I0201 M8052

4. Frequency measurement
The point is X1, X11, and X12.

5. Pulse width modulation
The point is Y0, Y1.
1T type: Y0, Y1 available
2RT type: Y0, Y1 available
3R type: unavailable

6. Precision timer
32-bit precise timer, the timer range is T600 to T618, matching with 10-interruption tag.
























XMP2-32 Combined Unit Manual Page 18 of 36 LMAN009_R2V2










Soft component Name Range Point
X Input point X000~X017 (octal) 16
Y Output point Y000~Y017 (octal) 16
M Auxiliary relay
M0~ M2999
M3000~M7999
8000
M8000~M8511 512
S Status
S0~ S511
S512~M1023
1024
T Timer
T0~T99100ms not accumulation
40
T100~T199100ms accumulation
T200~T29910ms not accumulation
T300~T39910ms accumulation
T400~T4991ms not accumulation
T500~T5991ms accumulation
T600~T6181ms with interruption precise time
T620~T639vacant
C Counter
C0~C29916 bits forward counter
640
C300~C31832 bits forward/back counter
C320~C59832 bits forward/back counter
C600~C618one phase high speed counter
C620~C628Pulse + direction high speed
counter
C630~C638AB phase high speed counter
D Data register
D0~D999
D4000~D4999
2000
For special using D8000~D8511 512
FD
Flash ROM
Register
FD0~FD255 256
For special use
FD8000~FD8255
256


NOTE:
The memory area in is the defaulted power failure retentive area, the power failure
retentive area of soft components D, M, S, T, C can be set via FD register. For details,
please see the following table.

Flash ROM register neednt be set for power failure retentive area,

The serial number of input coil and output relay are octal data, other memory number are all
decimal data.

3-2 Soft component range

XMP2-32 Combined Unit Manual Page 19 of 36 LMAN009_R2V2





Address
type
Area Function Default value
Power failure memory
area
D FD8202
First address of the power
failure memory area of D
4000 D4000~D4999
M FD8203
First address of the power
failure memory area of M
3000 M3000~M7999
T FD8204
First address of the power
failure memory area of T
640 No set
C FD8205
First address of the power
failure memory area of C
320 C320~C639
S FD8206
First address of the power
failure memory area of S
512 S512~S1023

NOTE:
Users can set the power failure memory area.



































XMP2-32 Combined Unit Manual Page 20 of 36 LMAN009_R2V2









XMP2-32R/T-E series products are integrated with XC series PLC and HMI. When editing the
PLC program, please use XCP Pro software, which is the same as XC series PLC.

1. Select the product type
Open XCPPro, click file---change PLC model:


Select XMP2-32:


2. Editing the PLC program
After selecting the type, user can edit the program in the software. The editing specs and
operating details please refer to XC Series PLC Edit Software XCPPro Manual.
The interface of software is as below:











3-3 Build a project

XMP2-32 Combined Unit Manual Page 21 of 36 LMAN009_R2V2



3. Download program
After editing and saving the program, the user needs to download them to the XMP. Before
downloading, ensure the XMP has connected with computer successfully. Click to open
software serial port configuration



When below window shows, it means the connecting is successful. Click OK to continue.




If the connection is not successful, the window will show communication error. Please check the
serial port and the cable.




After successful connection, click to download the PLC program. If the PLC is running, it will
pop up the stop running window. Click OK to continue downloading.

XMP2-32 Combined Unit Manual Page 22 of 36 LMAN009_R2V2





After downloading, click to run the PLC program.


4. Upload the program
If you want to check the PLC program in XP/XMP, click to upload the program to the PC.
Then click to save the program.
































XMP2-32 Combined Unit Manual Page 23 of 36 LMAN009_R2V2










XMP2-32R/T series supports Modbus and free format communication.
For instructions please refer to XC Series PLC User Manual.


3-4-1 Com port

XMP2-32R/T series product has program port (DB9 pins port), RS-232 COM port (DB9 pins port)
and RS-485 COM port (A and B point). Program port can only be used to download PLC program
and HMI pictures. However, RS-232 and RS-485 COM port can be used to communicate with
other devices. The communication parameters (baud rate, data bit, etc) can be set via software.
RS-485 COM port point A means + signal, point B means - signal.

Attention:
RS-485 and RS-232 COM port are the same; do not use them at the same time.































3-4 Communication function

XMP2-32 Combined Unit Manual Page 24 of 36 LMAN009_R2V2





3-4-2 Communication parameters

Communication parameters of RS-232 and RS-485 COM port can be set via FLASH register in
the XMP.
The defaulted parameters:
Station 1, baud rate 19200bps, 8 data bits, 1 stop bit, even check

Station No. Modbus station No.: 1-254, 255(FF) is for free format
communication
Baud rate 300bps~115.2Kbps
Data bit 8 or 7 bits
Stop bit 2 or 1 bits
Check Even, odd, no check

Communication parameters setting are as below table:

Note:
After changing the parameters in Flash register, a reboot is required

.




COM Port
Number Function Description
FD8220

Communication mode
(Station number)
255 is free format,
1~254 is modbus station number
FD8221 Communication format Baud rate, data bit, stop bit, check
FD8222 ASC timeout judgment time Unit: ms, 0 means no timeout waiting
FD8223 Reply timeout judgment time Unit: ms, 0 means no timeout waiting
FD8224 Start symbol High 8 bits invalid
FD8225 End symbol High 8 bits invalid
FD8226 Free format setting
8/16 bits cushion,
With/without start bit,
With/without stop bit











XMP2-32 Combined Unit Manual Page 25 of 36 LMAN009_R2V2



08bits data
17bits data
02 stop bits
21stop bit
0No check
1Odd
check
2Even
check
0:8 bits communication
1:16 bits communication
0: without start symbol
1: with start symbol
0: without end symbol
1: with end symbol
Reserved
0300bps
1600bps
21200 bps
32400 bps
44800 bps
59600 bps
619.2K bps
738.4K bps
857.6K bps
9115.2K bps
Setting up communication


FD8221:























FD8226:




























15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

XMP2-32 Combined Unit Manual Page 26 of 36 LMAN009_R2V2




3-4-3 Communication mode

Modbus communication
XMP series product support master and slave mode of Modbus communication.
Master format: When PLC is set to be master station, PLC sends request to other slave station
devices via Modbus instructions, other devices respond to the master station.
Slave format: When PLC is set to be slave station, it can only respond to other master devices.
The defaulted status of XMP is Modbus slave mode.


Communication address
The internal soft units numbers of XMP correspond with Modbus station address numbers.
Please see the following table:

Coil space: (Modbus address prefix is 0x )
Bit component address Modbus address (Decimal K) Modbus address (Hex H)
M0~M7999 0~7999 0~1F3F
X0~X511 16384~16895 4000~41FF
Y0~Y511 18432~18943 4800~49FF
S0~S1023 20480~21503 5000~53FF
M8000~M8511 24576~25087 6000~61FF
T0~T618 25600~26218 6400~666A
C0~C634 27648~28282 6C00~6E7A


Register space: (Modbus address prefix is 4x )
Word component address Modbus address (Decimal K) Modbus address (Hex H)
D0~D7999 0~7999 0~1F3F
TD0~TD618 12288~12906 3000~326A
CD0~CD634 14336~14970 3800~3A7A
D8000~D8511 16384~16895 4000~41FF
FD0~FD5000 18432~23432 4800~5B88
FD8000~FD8511 26624~27135 6800~69FF


Free format communication

Free format communication transfer data in the format of data block, each block can transfer 128
bytes at most. Meanwhile each block can set a start symbol and an end symbol.
When communicating in free format mode, FD8220 should be 255.

XMP2-32 Combined Unit Manual Page 27 of 36 LMAN009_R2V2



4HMI function and use




















































4-1HMI function
4-2 Building a project

XMP2-32 Combined Unit Manual Page 28 of 36 LMAN009_R2V2








The HMI part of XMP2-32R/T-E series product is integrated with MP-760T touch screen.
The faceplate key-presses are as below:

Key Function

Running the program, LED indication light

Stop running the program, LED indication light

Default main menu or most used screen.

Turn the screen to the last page

Turn the screen to the next page

Inquiry, jump to the user appointed screen

To write the modified value in the register and continue
modifying next register.

Alarming list key. After setting the function of alarming list,
press this key to jump to the alarm list screen.

Clear the selected area when modifying the register data.

Set the positive or negative of the data when modifying the
register data.

Number key 0-9.

Function key F1-F6

NOTE:
Besides the function listed in the previous table, all the keys can be defined as the function of
force ON, force OFF, reverse or momentary ON.




4-1 HMI function

XMP2-32 Combined Unit Manual Page 29 of 36 LMAN009_R2V2



Please see below picture. Open TouchWin software, put a button or function button in the
screen. Press, enter in the window, all the key-presses can be found in this menu. The user can
set the key function as they need.



























XMP2-32 Combined Unit Manual Page 30 of 36 LMAN009_R2V2








Use the Touchwin software.
1. Open the software, click File New or click to build a new project.
2. Choose MP760-T (XMP-32) in the panel window:
3. Click next; choose XC Series for PLC port device:
4. Click next; choose XC Series for download port device:


Click next to complete the building.


The editing interface is as below:


Note:
For software user details please refer to TP Touch Screen User Manual.



After completing the project editing and saving, connect the download port of the XMP and
computer serial port with the downloading cable. Make sure the XMP power is on. Click or
File Download to start downloading data, the download window is as below:



If it appears the item connection overtime, check cable, please download again.





4-2 Building a project

XMP2-32 Combined Unit Manual Page 31 of 36 LMAN009_R2V2



The downloading is completed when it shows the below window:



Attention:
(1) Do not cut the power when downloading, or you have to download again.
(2) The downloading cable for the TouchWin screen is the same as the downloading PLC
program.
(3) Do not download when XCPPro and TouchWin software are both open.








































XMP2-32 Combined Unit Manual Page 32 of 36 LMAN009_R2V2



5The extension ability

















XMP2-32R/T series product cannot extend BD board.
For extending other devices, use RS-232 or RS-485 (point A and B) COM port.
RS-232 COM port can connect with the computer, HMI to monitor the program.
RS-485 COM port can connect with meter, inverter, function model, etc. It can extend 32 external
devices at most.

Attention:
The connection method is Bus mode, transmission line should start from station 1 to station 2,
and then from station 2 to station 3connect in this sequence until the last station. Star mode or
ring mode connections are not permitted.










5-1 Summarization
5-1 Summarization
5-2Extend MA model

XMP2-32 Combined Unit Manual Page 33 of 36 LMAN009_R2V2










XMP2-32R/T series product can extend MA model via RS-485 COM port (A and B point) in order
to control and measure analog signals.
The type and specs of MA model are as below:


5-2-1 MA model type

Type Function
MA-8DA 8 channels analog output, voltage 0-5V or 0-10V, current 0-20mA or 4-20mA
MA-7PT-P 7 channels PT100 temperature measurement control, PID adjustment inside
MA-8TC-P 8 channels K type thermocouple temperature measurement control, PID
adjustment




































5-2 Extend MA model

XMP2-32 Combined Unit Manual Page 34 of 36 LMAN009_R2V2



5-2-2 MA model specs

MA-8DA:
Item Voltage Output Current Output
Analogue input range DC0~5V0~10V
(External load resistor
2K~1M)
DC0~20mA4~20mA
(External load resistor less than
500)
Digital output range 10 bits binary data
Resolution 1/1024(10 bits)
Integrated Precision 0.8%
Scan speed 2ms per channel
COM port RS-485
Power supply for
analogue usage
DC24V10%, 100mA
Insulation Format DC/DC convert, optical coupling insulation
Installation format Can fix with M4 screw or install on DIN46277 (width: 35mm) track
Dimension 140W73H90D


MA-7PT-P:
Item Content
Analogue input signal Pt100 platinum resistor
Temperature
measurement range
-100~350
Digital output range -1000~3500, 16 bits with symbol, binary
Control precision 0.5
Accuracy 0.1
Integrated precision 0.8% (relative max value)
Scan speed 100ms7 channels
Power supply for analog DC24V10%50mA
Installation Format Fix with M4 screws or install on DIN46277 (width 35mm) track
Dimension 63mm102mm73.3mm

XMP2-32 Combined Unit Manual Page 35 of 36 LMAN009_R2V2



MA-8TC-P:
Item Content
Analogue input signal K type thermocouple
Temperature measurement range 0~1000
Digital output range 0~1000016 bits with symbol, binary
Control precision 0.5
Accuracy 0.1
Integrated precision 0.8% (relative max value)
Scan speed 100ms8 channels
Power supply for analog DC24V10%50mA
Installation Format Fix with M3 screws or install on DIN46277 (width 35mm) track
Dimension 63mm102mm73.3mm



5-2-3 MA model connection

XMP2-32R/T product can connect with MA model via RS-485 COM port (A and B point). It can
extend 8 MA models via setting DIP switches.

Please see the connection figure:


The details and method please refer to MA Model Manual.


XMP2-32 Combined Unit Manual Page 36 of 36 LMAN009_R2V2









Documentation Reference

Document Number

Revision Date
LMAN 009 R2 V2 17/07/2012

XINJE IS A REGISTERED TRADEMARK OF XINJE ELECTRICAL CO.LTD.
REPLICATION OF THE INFORMATION CONTAINED WITHIN THIS DOCUMENT
WITHOUT PRIOR NOTIFICATION AND AGREEMENT IS PROHIBITED.







For help and support regarding your XINJE products visit the online
Support Centre or contact us on: support@listo-ltd.com.





www.listo-ltd.com
www.xinje-support-centre-listo.com







International partners with:



Contact us
Listo Ltd.
25B Antrim Business Park
Enkalon Industrial Estate
Antrim
Co.Antrim
Northern Ireland
BT41 4LD
+44 (0)28 944 64968
info@listo-ltd.com
www.xinje-support-centre-listo.com
UK & Ireland Distributors for