Beruflich Dokumente
Kultur Dokumente
s piping stress analysis software Caesar II, Version 5.0 or above shall be used
for Pipe stress analysis. Pipe thickness & material allowable stress values will be
manually fed as input.
9.0 DOCUMENT REQUIREMENT
9.1
A written report shall be submitted on the piping and equipment analysis. The report shall
include all pertinent information that shall include but not be limited to the following :
Location and type of pipe supports with loads and movements.
Location of expansion joints and movements.
Vertical and horizontal loads including moments at all support points.
Vertical and horizontal loads including moments on all equipment and vessel
connections.
Caesar II analysis report, which shall include as a minimum, restraint forces,
movements and stresses for all load cases. For flange connection, loaded with high
bending moments and/or tensile forces in piping or at equipment connections, Caesar
II flange leakage report will be provided. For piping analyzed, if subjected to hydro test,
hydro test load case will be made in Caesar II to check for loading under hydro test &
the requirement of any additional temporary supports for hydro test.
Detailed nodal model used for the stress analysis
All assumptions and limitations applied to the analysis.
9.2 All dimensions and analysis shall be performed using metric and SI units.
9.3 The final report / stress package folder shall be submitted as follows:
1. Front sheet with Approval status
2. Isometrics with Hand written following information.
Node numbers
Type of supports selected by stress engineer
Springs / Bellows data required for procurement like spring rate, loads, tide/untied
information and SM (special material) identification.
Maximum Expansion and sustain stress values with node number
Nozzle/Anchors initial movements and piping imposed forces and moments on
the same
Support loads (anchors, guides or rest) only they are above limit (The limit is
defined in the beginning of the project in consultation with civil)
Jacobs
HPCL, Mumbai Stress Design Basis Part - III
LSTK DOC NO: 44LK-5100-00/L.02/0003/A4
Section- A
44LK 5100
Sheet 10 of 15
Design and maximum operating conditions
Coordinate axis system considered for inputs
Dimensional details for piping designer to locate supports in piping model/layout.
3. Check list as per JE work instructions.
4. Following outputs
Load Cases
Restraint summary
Spring hanger report, if any
5. Stress critical line list extract for the lines analysed
6. Piping material specifications
7. Equipment drawings with allowable loads, if available
8. PID
Jacobs
HPCL, Mumbai Stress Design Basis Part - III
LSTK DOC NO: 44LK-5100-00/L.02/0003/A4
Section- A
44LK 5100
Sheet 11 of 15
ATTACHMENT 10.1
CRITERIA FOR IDENTIFING CRITICAL LINES.
Note :
1. Load sensitive equipment include fired heaters,boilers / steam generators, Reformers,lined
vessels with lining of brittle material,non-ferrous equipment,Graphite heat exchangers,plate &
frame heat exchanger,Spiral Heat Exchangers,Equipment on load Cells etc.
2. Also include lines connected to nozzles having differential settlement / Thermal displacement
more than 12 mm.
3. Delta T refers to the differential temperature between the process piping and jacket.
4. Very large diameter pipes (dia / thickness >100)and ducts need to be designed using finite
element analysis methods.
5. Category M Fluids involve toxic and harmful fluids which are identified by process.These
services are lethal and hence critical.They need mandatory flange leakage calculations. To get
the loads at flanges,a computerised stress analysis is required.
6. For critical lines in seismic prone, plants refer Attachment 10.2 for categorisation.
SR
NO
Temperature
T, Degree C
Pipe
Diameter
D,Inch
NB
Piping
Material
Service and Description
1 All D > 2 All Category M (Lethal) fluid service per ASME B31.3 (Ref. Note
4).
2 All D > 3 All Piping which is exposed to winds of speed > 75 mph.(Ref
Note 5)
3 T < (-) 45 D > 3 All All Services.
4 T > 200 D > 3 All All Services.
5 T > 100 D > 16
(see note
3)
All All Services.
6 T > 65 D > 3 Non-
Metallic
All Services.
7 T > 65 D > 2 All Lines with pressure > 900 psig.
8A T < (-) 29 D > 3 All Piping connected to nozzle load-sensitive equipment, (see
note 1)
8B T > 65 D > 3 All air-cooled exchangers and rotating equipment (see note 1).
9 DeltaT > 27
(Note 2)
D > 2 All Jacketed piping.(D=Inner Pipe NB)
10
A
T > 65 D > 4 All Internally lined pipe (except glass lined).
10
B
T < (-) 29 D > 4
11 All All All Glass lined piping.
12
A
T < (-) 40 D > 4 Metallic
Underground Piping/Cross Country Piping.
12
B
T > 80 D > 4 Metallic
Underground Piping/Cross Country Piping.
12
C
T < (-) 29 D > 8 Metallic
Underground Piping/Cross Country Piping.
12
D
T > 70 D > 8 Metallic
Underground Piping/Cross Country Piping.
13 All D > 2 All Safety Relief Valve Outlet Pipeline.
14 All D > 2 All Pipelines connected to expansion joints or bellows (except
rubber bellows used for alignment purpose).
Jacobs
HPCL, Mumbai Stress Design Basis Part - III
LSTK DOC NO: 44LK-5100-00/L.02/0003/A4
Section- A
44LK 5100
Sheet 12 of 15
ATTACHMENT 10.2
Categorization for Seismic analysis
Definition: Plant Piping located in earthquake prone areas of the country will experience accelerations
imparted through foundations, structures and various equipment. Criticai piping {toxic, flammable, high
pressure, high temperature, emergency) which must remain leak;tight or operable (deliver, control or
shutoff flow) during or following the event, have nozzle loads within vendor's set limits, have minimum
sway to avoid impact or interference with adjacent equipment / pipes / structures need seismic analysis to
determine the effects.
Based on Indian code IS 1893-2002, areas falling under Zones IV and V are categorized as "Severe"
while Zones II and III are prone to earthquakes of "Moderate" or "Low" intensity. The IS 1893-2002
guidelines for BUILDINGS to be seismically designed are as beiow;
For regular buildings, if the building height is greater than 40 m in Zones IV and V or greater than
90 m in Zone II and III ;
For irregular buildings, if height is more than 12 m in Zones IV and V and more than 40 m in
Zones II and III,
Method: Process Plants normally fall within the irregular building category and hence the piping and
equipment are to be analysed accordingly. To get realistic results, it is essential that seismic analysis for
piping be carried out using the Dynamic analysis method viz. Time History method or Modal Response
Spectrum method. Piping connected to tail columns/vessels, chimneys and any slender structure should
preferably be analysed using dynamic analysis. Long-run piping on tall slender structures (such as flare
piping on trestles) should be analysed using composite analysis. For toxic/lethal piping systems, the
seismic anchor movements also need to be imposed during the dynamic analysis. However for
simplification's sake wherever dynamic analysis is not mandatory by the client or the response
spectra cannot be derived from data available, seismic design can be done using the Equivalent
Static (static coefficient) method.
The seismic accelerations, response spectra and anchor movement values are to be obtained from the
Civil Group.
For seismic analysis, earthquake loadings shall not be considered to act simultaneously with wind. Also it
is to be noted that cross-country pipelines, buried piping & piping for nuclear installations will need
rigorous analysis and the selection criteria below does not apply. Refer LWI 220 for explanatory
techniques for seismic design of piping systems (under development)
Selection: With due considerations to fluid criticality and intended operation, in order to assess maximum
impact it is recommended that only critical piping with higher sizes (i.e. higher mass and/or at higher
elevations which in turn reflects as higher force) be seismicaiiy computer analysed. Since not explicit in
Indian codes, following guidelines are a conservative selection.
All critical piping systems aboveground with a weight (self+fluid+insuiation) greater than 410
kg/m (corresponds to a 24" STD schedule water filled pipe).
All critical piping systems above ground with any portion routed at a height (height as per the
above IS 1893 building categorization) with a weight greater than 210 kg/m (corresponds to a 16"
STD schedule water filled pipe). Give due consideration to piping connected to tall equipment &
piping routed on tall slender structures.
All emergency service critical piping systems above ground with any portion routed at or
greater than 25m with a weight greater than 110 kg/m (corresponds to a 10" STD schedule
water filled pipe).
Smaller critical lines (3" to 10") routed above 10 m elevation need to be seismically analysed
provided the wind load does not govern.
Jacobs
HPCL, Mumbai Stress Design Basis Part - III
LSTK DOC NO: 44LK-5100-00/L.02/0003/A4
Section- A
44LK 5100
Sheet 13 of 15
Piping < 410 kg/m and below 10m elevation and non-critical piping can be considered as non-
seismic critical. Such systems shall be made rigid overall preferably by having every 2
Fld
/ 3
rd
support (appx 12m) as a seismic lateral restraint (guide) and every straight run (> 3 times
standard supporting span) with a longitudinal (axial) restraint. Equivalent Static Analysis needs to
be done only if peak spectral acceleration / static seismic coefficient is > 0.3 g, max
component weight is > 200kg and pipe centerline is > 1m.
Branch lines can be decoupled from the run lines if I
run
> 25 leaned where I = moment of inertia.
These guidelines are indicated graphically on Sht 2 of 2 of this attachment.
Jacobs
HPCL, Mumbai Stress Design Basis Part - III
LSTK DOC NO: 44LK-5100-00/L.02/0003/A4
Section- A
44LK 5100
Sheet 14 of 15
ATTACHMENT 10.2
Notes :
1. For site specific Zoning as per IS 1893, refer Project Initiation Checklist in Project
Procedure
2. If Dynamic Analysis is not mandatory by the client or the response spectra cannot be
derived from data available, Equivalent Static Analysis can be done. However, if
Equivalent Static Analysis yields uneconomical results, Dynamic Analysis methods
may be adopted to achieve realistic results.
3. Piping in this category are non-seismic critical. Systems shall be made rigid overall
preferably by having every 2
nd
/ 3
rd
support (appx 12m) as a seismic lateral restraint
(guide) and every straight run {> 3 times standard supporting span) with a longitudinal
(axial) restraint. Equivalent Static Analysis needs to be done only if peak spectral
acceleration / static seismic coefficient is > 0.3 g, max component weight is > 200kg and
pipe centerline is > 1m.
4. A Tall equipment (tower.etc) located at grade is analogous to a Building (RCC or steel
frame structure). Piping connected to be categorized accordingly.
5. Piping on tall slender structures (such as flare piping on trestles) should undergo
composite analysis.
Jacobs
HPCL, Mumbai Stress Design Basis Part - III
LSTK DOC NO: 44LK-5100-00/L.02/0003/A4
Section- A
44LK 5100
Sheet 15 of 15
6. Emergency services are isolation/relief systems which reduce the potential of a major
hazardous accident such as emergency process control, emergency pressure relief,
emergency venting / blowdown, emergency shutdown, emergency purging / cooling, etc
classified as safety critical by Process.