MiCOM I400
Digital Transducers
Introduction
The MiCOM I400 range of digital
transducers is designed to meet the
world market requirements of high
accuracy with optional digital
communications at a competitive
price.
Available in two compact case
sizes of 45mm and 100mm wide,
these transducers can be supplied
fully calibrated or as a device for
customer calibration.
A multifunction transducer is
available offering measurement of
all power system parameters in one
housing with up to three optional
analogue outputs.
Product features
Full range of ac and dc measurements
Programmable versions
Multifunction transducer available to measure
current, Volts, frequency, phase angle, power
factor, Watts, vars, VA, demands and harmonics.
Up to three isolated analogue outputs
Optional high speed RS485 or RS232
communications
Optional universal AC/DC power supply
High sample rate (64 samples per cycle) for
accurate measurement of harmonics
Two times continuous current overload rating
0.5% full scale accuracy for all transducers
Compact case design for DIN rail mounting
Stripped wire terminations
Tested to DIN 57875 level N for radio frequency
and electromagnetic interference immunity
Customer benefits
All requirements can be sourced from one supplier
Configurable on-site using a laptop PC. Simplified
ordering and easy to change configuration if site is
expanded or changed
Reduced costs for sites requiring multiple
measurements
Analogue schemes require fewer transducers
resulting in lower costs
Can be integrated into modern control schemes
utilising digital communication technologies
Provides flexibility in terms of power requirements
and reduced stocking
Gives accurate measurements of parameters critical
for optimum plant use
Lifetime durability and reliability
Occupies minimal panel space
Fast and secure wiring
Complies with relevant international standards
3
Applications
Applications are found in electrical
utilities, switchgear/switchboard
manufacturers, energy
management, SCADA, building
management and control, process
control and instrumentation.
MiCOM I400 digital transducers
provide local and remote indication
for precision electrical measurement
and control when used with
instruments, recorders, data loggers
and SCADA systems (Supervisory
Control and Data Acquisition).
Provision of both analogue outputs
and RS485/RS232 MODBUS
communications facilitates
integration within existing sites and
new facilities where digital
communications are used.
The ease of programmability of
digital transducers is an important
feature in the provision of cost
effective system control. Systems
can be easily changed or
expanded as required. Scaling
details may be delayed while the
system is being constructed without
causing costly project time delays.
Why MiCOM I400 digital
transducers?
As well as allowing integration into
digital control schemes, MiCOM
I400 digital transducers use state
of the art microprocessor
technology to enable customer
configuration using only a personal
computer and configuration
software.
Stability
The use of microprocessor
technology in the design of the
MiCOM I400 digital transducer
range guarantees accuracy and
stability over a range of
temperatures. The good long term
stability achieved reduces the
problem of long term drift that can
affect some analogue transducers.
This level of stability means that
MiCOM I400 digital transducers
can endure a lifetime of
maintenance-free operation.
Inherent design quality
ALSTOM T&D Ltd
Protection & Control operates
manufacturing and quality systems
that meet and exceed the
requirements of ISO 9001.
MiCOM I400 digital
transducer range
Mean sensing current
Mean sensing voltage
The mean sensing current or
voltage transducers do not
require a power supply.
A range of easy to order
standard scalings are available.
True rms current
True rms voltage
Suppressed zero voltage
(true rms)
True rms devices are available
with optional communications
output.
Frequency
0.1% of centre scale accuracy
Available with optional 0.01%
high accuracy communications
output
Watts, vars, phase angle and
power factor
Single phase
Three phase, three wire,
balanced or unbalanced load
Three phase, four wire,
balanced or unbalanced load
Available with optional
communications output
Combination transducers
Dual rms current/voltage
Dual frequency/rms voltage
Dual watt/var
Triple rms current
Triple rms voltage
All rms, frequency, power and dual
output transducers are supplied
with ac power supply as standard.
This must be specified at the time of
order. Optionally, a universal
ac/dc power supply is available.
All triple output versions are
supplied with universal ac/dc
power supply as standard.
Multifunction programmable
Each device measures volts,
current, frequency Watts, vars, VA,
phase angle, power factor, THD%,
dynamic demands, maximum
demands and optionally, harmonic
analysis.
All measurements are available via
the communications port.
The multifunction transducer is
always supplied with the universal
ac/dc power supply and
communications port for customer
configuration.
The multi-function transducer is
available with none, one, two or
three analogue outputs. Each
output can be programmed to any
of the following measured functions: -
RMS current:
Phase Ia, Ib, Ic,
I average, In
RMS voltage:
Line to neutral: Va, Vb, Vc,
VL-N average
Line to line: Vab, Vbc, Vca
VL-L average
Frequency
Power: Watts, vars, VA
(per phase and totals)
Phase angle (V-I) and (V-V)
Phase and total
Power angle atan 2 (PtQt)
Dynamic demands:
Phase current Ia, Ib, Ic
Total Watts, vars and VA
4
DC transducers
DC current
DC voltage
2 wire restance
Measurements also available
via communications port:
Total harmonic distortion, %THD
VL-N, Va, Vb, Vc
VL-L, Vab, Vbc, Vca
Phase currents Ia, Ib, Ic
Device internal temperature
Phase angles between voltages
Va-Vb, Vb-Vc, Vc-Va
Configuration
Transducers supplied without the
communications interface are
supplied factory pre-configured for
which the scaling details must be
supplied with the order.
Transducers with the
communications interface can be
ordered as factory pre-configured
or as a programmable version for
customer configuration. Free
software to allow customer
configuration from a PC is
available at the time of order
The programmable devices are
supplied with one of three output
ranges. Each can be programmed
for a unidirectional, a bidirectional
or a bent characteristic.
The three output types can be
programmed over the ranges as
below : -
Output reference Type P : -
101 mA to 505 mA
Output reference Type Q : -
606 mA to 20020 mA
Output reference Type R : -
101 V to 10010 V
Application information
Refer to Application Guide for
Electrical Measuring Transducers
Publication I9-113.
Information required with order
Specify order code
This is a reference that defines the basic type of transducer.
For mean sensing voltage and current transducers with any of the fixed
scalings shown in the selection table on page 5, the type reference is all
that is required.
Order code
Auxiliary supply
Self powered A
63.5V ac B
69.3V ac C
100V ac D
110V ac E
115V ac F
120V ac G
208V ac H
230V ac V
380V ac L
415V ac M
440V ac N
Universal DC/AC supply
24 ... 300V dc / 40 ... 276V ac U
Non standard (please specify) Z
Type ref (from selection table on page 5)
Output for transducers supplied calibrated
0 ... 1 mA A
0 ... 5 mA B
0 ... 10 mA D
0 ... 20 mA E
4 ... 20 mA F
4 ... 12 ... 20 mA G
0 ... 5 ... 10 mA H
1 ... 0 ... 1 mA J
10 ... 0 ... 10 mA K
20 ... 0 ... 20 mA U
10 ... 0 ...10 V M
None of the above and Z
combination transducers with differing outputs
(please specify on order)
Output for programmable transducers
Customer programmable P
Q
R
Communications
Not required 0
RS232 2
RS485 4
1mA to 5mA full scale
6mA to 20mA full scale
1V to 10V full scale
For devices to be supplied factory pre-configured please also specify the
transducer scaling details :-
Input scaling, CT ratio, VT ratio
Note : all transducers without communications must be supplied factory pre-
configured
Example of required order information
Order code I4WDKE2, Input 25025 MW, CT Ratio 400/5 A,
VT Ratio 33 kV/110 V
(Here the type reference indicates 2 El Watts transducer with
10010 mA output, 110 V ac auxiliary supply and RS232
communication).
5
Transducer selection table
Devices offered with fixed scaling must be specified at the time of order.
Programmable devices are supplied scaled in secondary terms (0.5 1 0.5 cos phi for Phase Angle transducer).
Types shown have ac auxiliaries as standard, except I4CA & I4VA (self powered).
Transducer type
Mean sensing current (see note 2)
Fixed scaling 0 ... 1A/0 ... 5mA
Fixed scaling 0 ... 1A/0 ... 10mA
Fixed scaling 0 ... 1A/0 ... 20mA
Fixed scaling 0 ... 5A/0 ... 5mA
Fixed scaling 0 ... 5A/0 ... 10mA
Fixed scaling 0 ... 5A/0 ... 20mA
Other input/output (request with order)
Type ref:
required
with order
True
zero
output
Biased
output
Universal
aux.
(see note 1)
RS232
or
RS485
Housing
size
(mm)
I4CAB-1
I4CAD-1
I4CAE-1
I4CAB-5
I4CAD-5
I4CAE-5
I4CA
Yes
Yes
Yes
Yes
Yes
Yes
Yes
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
45
45
45
45
45
45
45
True rms voltage
Supplied calibrated (request with order)
Programmable (see note 2)
I4VD
I4VD
Yes
Yes
45
45
Option
Yes
Option
Option
Option
Yes
Suppressed zero voltage
Supplied calibrated (request with order)
Programmable (see note 2)
I4VX
I4VX
Yes
Yes
45
45
Option
Yes
Option
Option
Option
Yes
Frequency
Supplied calibrated (request with order)
Programmable (see note 2)
I4FA
I4FA
Yes
Yes
45
45
Option
Yes
Option
Option
Option
Yes
Phase angle
Single phase (1 element)
3 phase 3 wire balanced (1 element)
3 phase 4 wire balanced (1 element)
3 phase 3 wire unbalanced (2 element)
3 phase 4 wire unbalanced (3 element)
Programmable (see note 2)
I4PA
I4PB
I4PC
I4PD
I4PF
I4PP
Yes
Yes
Yes
Yes
Yes
Yes
100
100
100
100
100
100
Option
Option
Option
Option
Option
Yes
Option
Option
Option
Option
Option
Option
Option
Option
Option
Option
Option
Yes
True rms current
Supplied calibrated (request with order)
Programmable (see note 2)
I4CD
I4CD
Yes
Yes
45
45
Option
Yes
Option
Option
Option
Yes
Mean sensing voltage (see note 2)
Fixed scaling 0 ... 110V/0 ... 5mA
Fixed scaling 0 ... 110V/0 ... 10mA
Fixed scaling 0 ... 110V/0 ... 20mA
Fixed scaling 0 ... 120V/0 ... 5mA
Fixed scaling 0 ... 120V/0 ... 10mA
Fixed scaling 0 ... 120V/0 ... 20mA
Fixed scaling 0 ... 250V/0 ... 5mA
Fixed scaling 0 ... 250V/0 ... 10mA
Fixed scaling 0 ... 250V/0 ... 20mA
Fixed scaling 0 ... 500V/0 ... 5mA
Fixed scaling 0 ... 500V/0 ... 10mA
Fixed scaling 0 ... 500V/0 ... 20mA
Other scaling (request with order)
I4VAB-110
I4VAD-110
I4VAE-110
I4VAB-120
I4VAD-120
I4VAE-120
I4VAB-250
I4VAD-250
I4VAE-250
I4VAB-500
I4VAD-500
I4VAE-500
I4VA
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
45
45
45
45
45
45
45
45
45
45
45
45
45
6
Transducer type Type ref:
True
zero
output
Biased
output
Universal
aux.
(see note 1)
RS232
or
RS485
Housing
size
(mm)
Watt
Single phase (1 element)
3 phase 3 wire balanced (1 element)
3 phase 4 wire balanced (1 element)
3 phase 3 wire unbalanced (2 element)
3 phase 4 wire unbalanced (3 element)
Programmable (see note 2)
I4WA
I4WB
I4WC
I4WD
I4WF
I4WP
Yes
Yes
Yes
Yes
Yes
Yes
100
100
100
100
100
100
Option
Option
Option
Option
Option
Yes
Option
Option
Option
Option
Option
Option
Option
Option
Option
Option
Option
Yes
Vars
Single phase (1 element)
3 phase 3 wire balanced (1 element)
3 phase 4 wire balanced (1 element)
3 phase 3 wire unbalanced (2 element)
3 phase 4 wire unbalanced (3 element)
Programmable (see note 2)
I4RA
I4RB
I4RC
I4RD
I4RF
I4RP
Yes
Yes
Yes
Yes
Yes
Yes
100
100
100
100
100
100
Option
Option
Option
Option
Option
Yes
Option
Option
Option
Option
Option
Option
Option
Option
Option
Option
Option
Yes
Combination transducers
RMS current/RMS voltage
Supplied calibrated (request with order)
Programmable (see note 2)
Frequency/RMS voltage
Supplied calibrated (request with order)
Programmable (see note 2)
Watt/vars
Single phase (1 element)
3 phase 3 wire balanced (1 element)
3 phase 4 wire balanced (1 element)
3 phase 3 wire unbalanced (2 element)
3 phase 4 wire unbalanced (3 element)
Programmable (see note 2)
Triple rms current
Supplied calibrated (request with order)
Programmable (see note 2)
Triple rms voltage
Supplied calibrated (request with order)
Programmable (see note 2)
I4XF
I4XF
I4YF
I4YF
I4JA
I4JB
I4JC
I4JD
I4JF
I4JP
I4CF
I4CF
I4VF
I4VF
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
100
100
100
100
100
100
100
100
100
100
100
100
100
100
Option
Yes
Option
Yes
Option
Option
Option
Option
Option
Yes
Option
Yes
Option
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Option
Yes
Option
Yes
Option
Option
Option
Option
Option
Yes
Option
Yes
Option
Yes
Multi-function (see note 2 & 3)
No analogue outputs
1 analogue output
2 analogue outputs
3 analogue outputs
I4M0
I4M1
I4M2
I4M3
N/A
Yes
Yes
Yes
100
100
100
100
N/A
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
DC voltage
DC current
2 wire resistance
I4DB
I4DC
I4DF
Yes
Yes
Yes
45
45
45
Option
Option
Option
Option
Option
Option
Option
Option
Option
1. Universal power supply covers nominal auxiliary voltage of 24 300Vdc and 40 276Vac
2. These programmable transducers are supplied with one of three default configurations:- 5...0...5mA for output code P, 10...0...10mA for output
code Q or 10...0...10V for output code R.
3. Multi-function transducers are fully customer programmable for: - Up to three electrical measurements with up to 3 analogue outputs, single
phase system, 3 phase 3 or 4 wires, balanced or unbalanced load
7
Technical specification
MiCOM I400 digital transducers are designed to comply with IEC 60688-1, IEC 60255-22-1, EN 61010-1990
Current mean
sensing non-
adjustable
(self powered)
RMS current
Voltage mean
sensing non-
adjustable
(self powered)
RMS voltage
Suppressed
zero RMS
voltage
Input range 0.5A to 6A fixed 0.5A to 6A
programmable
50V to 500V
fixed
50V to 500V
programmable
50V to 500V
programmable
Nominal values 1A, 5A 1A, 5A 57.7, 63.5, 69
100, 110, 120
127, 220, 240
380, 400, 415
500V
57.7, 63.5, 69
100, 110, 120
127, 220, 240
380, 400, 415
500V
57.7, 63.5, 69
100, 110, 120
127, 220, 240
380, 400, 415
500V
Nominal range of
input
0 ... 120% 0 ... 120% 10 ... 120% 0 ... 120% 0 ... 120%
Frequency range 45 ... 65Hz 45 ... 65Hz 45 ... 65Hz 45 ... 65Hz 45 ... 65Hz
Input circuit
Burden
Overload:
Continuous
10s
1s
2VA
2x
5x
20x
0.5VA
2x
5x
20x
2VA
1.2x
2x
1mA x Vn
1.5x
2x
1mA x Vn
1.5x
2x
AC auxiliary
Nominal volts, Vx
Operating range
Frequency range
Supply burden
Fixed value
57 ... 500V ac
80 ... 120% Vx
45 ... 65 Hz
3VA
Fixed value
57 ... 500V ac
80 ... 120% Vx
45 ... 65 Hz
3VA
Fixed value
57 ... 500V ac
80 ... 120% Vx
45 ... 65 Hz
3VA
AC / DC universal
auxiliary
Supply burden
19 ... 300V dc
40 ... 276V ac
3VA
19 ... 300V dc
40 ... 276V ac
3VA
19 ... 300V dc
40 ... 276V ac
3VA
Output
Accuracy % fsd
Reference range
Compliance volts
Nominal values
Maximum open
circuit voltage
0.5
0 ... 100% In
15V
0 ... 1, 0 ... 5mA
0 ... 10mA,
0 ... 20mA
30V
0.5
0 ... 120% In
15V
0 ... 1 to 0 ... 20mA
0.2 ... 1mA to
4 ... 20mA
30V
0.5
0 ... 100% Vn
15V
0 ... 1, 0 ... 5mA
0 ... 10mA,
0 ... 20mA
30V
0.5
0 ... 120% Vn
15V
0 ... 1 to 0 ... 20mA
0.2 ... 1mA to
4 ... 20mA
30V
0.5 (% of Vn)
0 ... 120% Vn
15V
0 ... 1 to 0 ... 20mA
0.2 ... 1mA to
4 ... 20mA
30V
Miscellaneous
Response time
(0 ... 99.5%)
Ripple
Temperature
coefficient
Working temp.
Storage temp.
300ms
0.35% rms
0.02%/C
-10 ... 55C
-40 ... 70C
300ms
0.35% rms
0.02%/C
-10 ... 55C
-40 ... 70C
300ms
0.35% rms
0.02%/C
-10 ... 55C
-40 ... 70C
300ms
0.35% rms
0.02%/C
-10 ... 55C
-40 ... 70C
300ms
0.35% rms
0.02%/C
-10 ... 55C
-40 ... 70C
Communications RS485/RS232 RS485/RS232 RS485/RS232
Baud rate 1200 ... 115200 1200 ... 115200 1200 ... 115200
* Other output values available on demand
8
Watts or vars Phase angle Frequency
Universal programmable
Watts, vars, VA, phase angle
frequency, Vrms, Irms
Input range 0.5A to 6A fixed 0.5A to 6A
programmable
50V to 500V 50V to 500V 0.5A to 6A
programmable
Nominal values 1A, 5A 0.5A, 1A, 5A 57.7, 63.5, 69
100, 110, 120
127, 220, 240
380, 400, 415
500V
57.7, 63.5, 69
100, 110, 120
127, 220, 240
380, 400, 415
500V
Nominal range of
input
0 ... 120% 0 ... 120% 10 ... 120% 0 ... 120%
Frequency range 45 ... 65Hz 45 ... 65Hz 45 ... 65Hz 45 ... 65Hz
Input circuit
Current burden
Voltage burden
Overload current:
Continuous
10s
1s
Overload voltage:
Continuous
10s
0.5VA
1mA x Vn
2x
5x
20x
1.2x
2x
0.5VA
1mA x Vn
2x
5x
20x
1.2x
2x
-
1mA x Vn
1.2x
2x
AC / DC universal
auxiliary
Supply burden
19 ... 300V dc
40 ... 276V ac
(40 ... 70Hz)
3VA
Output
Accuracy % fsd
Reference range
Compliance volts
Nominal values
Maximum V O/C
0.5
0 ... 120% In
0 ... 120% Vn
15V
0 ... 1mA, to
0 ... 20mA
0.2 ... 1mA to
4 ... 20mA
30V
Miscellaneous
Response time
(0 ... 99.5%)
Ripple
Temperature
coefficient
Working temp.
Storage temp.
300ms
0.35% rms
0.02%/C
-10 ... 55C
-40 ... 70C
300ms
0.35% rms
0.02%/C
-10 ... 55C
-40 ... 70C
300ms
0.35% rms
0.02%/C
-10 ... 55C
-40 ... 70C
300ms
0.35% rms
0.02%/C
-10 ... 55C
-40 ... 70C
Communications RS485/RS232 RS485/RS232
1A, 5A
0.01 x I
2
VA
0.2mA x Vn
2x
5x
20x
1.5x
2x
19 ... 300V dc
40 ... 276V ac
(40 ... 70Hz)
3VA
19 ... 300V dc
40 ... 276V ac
(40 ... 70Hz)
3VA
19 ... 300V dc
40 ... 276V ac (40 ... 70Hz)
3VA
0.5
0.05 ... 6 A
10 ... 500V
15V
0 ... 1mA, to
0 ... 20mA
0.2 ... 1mA to
4 ... 20mA
30V
0.1 (0.01 via
communications) #
-
3 ... 500V
15V
0 ... 1mA, to
0 ... 20mA
0.2 ... 1mA to
4 ... 20mA
30V
0.5
0 ... 120% In
0 ... 120% Vn
15V
0 ... 1mA, to 0 ... 20mA
0.2 ... 1mA to 4 ... 20mA
30V
RS485/RS232 RS485/RS232
Baud rate 1200 ... 115200 1200 ... 115200 1200 ... 115200
# Accuracy of frequency transducer is % of centre scale frequency
1200 ... 115200
9
DC current
Input ranges 1mA ... 10mA or
10mA ... 100mA
or Fixed
50mV ... 1V
1V ... 50V
50V ... 400V
or Fixed
DC voltage 2 wire resistance
10 ohms to 50k ohm
100 ohm to 500k ohm
or Fixed
Nominal values 1, 2, 5, 6, 10mA
20, 40, 50, 60, 100mA
50, 100, 500mV
1, 2, 5, 10, 20, 40V
50, 100, 150, 250, 400V
100 ohm, 1k, 2k, 5k ohm
10k, 20k, 50k ohm
100k, 200k, 500k ohm
Nominal range of input 0 ... 100% 0 ... 100% 10 ... 100%
Input circuit
Burden 1mA ... 10mA : 100 ohm
10 ... 100mA : 10 ohm
50mV ... 1V : 100k ohm
1V ... 50V : 400k ohm
50V ... 400V : 4M ohm
<20mA for
10 ohm ... 50k ohm range
<2mA for
100 ohm ... 500k ohm range
Overload:
Continuous
1s
2x In
20x In
1,2x Vn
2x Vn
-
-
AC auxiliary
Nominal volts, Vx
Operating range
Frequency range
Supply burden
Fixed value
57 ... 500V AC
80 ... 120% Vx
45 ... 65Hz
<3 VA
Fixed value
57 ... 500V AC
80 ... 120% Vx
45 ... 65Hz
<3 VA
Fixed value
57 ... 500V AC
80 ... 120% Vx
45 ... 65Hz
<3 VA
AC/DC universal
Supply burden
19 ... 300V DC
40 ... 276V AC
3VA
19 ... 300V DC
40 ... 276V AC
3VA
19 ... 300V DC
40 ... 276V AC
3VA
Output
Accuracy % fsd
Reference range
Compliance volts
Nominal values
Maximum open circuit
voltage
0.5
0 ... 100% In
15V
0 ... 1 to 0 ... 20mA
0.2 ... 1mA to 4 ... 20mA
30V
0.5
0 ... 100% Vn
15V
0 ... 1 to 0 ... 20mA
0.2 ... 1mA to 4 ... 20mA
30V
0.5
0 ... 100% Rn
15V
0 ... 1 to 0 ... 20mA
0.2 ... 1mA to 4 ... 20mA
30V
Miscellaneous
Response time (0 ... 99.5%)
Ripple
Temperature coefficient
Operating temperature
Storage temperature
500ms
0.35% rms
0.05%/deg C
-10 ... 55deg C
-40 ... 70 deg C
500ms
0.35% rms
0.05%/deg C
-10 ... 55deg C
-40 ... 70 deg C
500ms
0.35% rms
0.05%/deg C
-10 ... 55deg C
-40 ... 70 deg C
Communications
Baud rate
RS485/RS232
1200 ... 115200
RS485/RS232
1200 ... 115200
RS485/RS232
1200 ... 115200
10
Climatic class
JVE DIN 40040,
3 VDI/VDE 3540,
EN 60688, 1992 class III
Isolation
Insulation Class II. Routine
test at 3.7kV rms to
EN61010-1 1990
(500V rms for 60 s between
multiple outputs)
Impulse test
5kV (1.2/50s) to
IEC 60255-4/III
Surge withstand
IEC 60255-22-1 and
ANSI C37-90A IEEE Std 472
SWC where applicable
Electromagnetic compatibility
EN6100-4-4, 1995-01
Radio Interference protection
Level N, according to DIN 57875
Safety requirements
EN 61010-1:1990-09
protection class III(300V),
class II (600V)
Case protection
IP50, terminals IP20 to
EN 60529, 1989
Case flammability protection
UL 94 V-0
Electromagnetic
Compatibility Directive
89/336/EEC
Emissions standard
EN 50081-2 1994 Industrial
environment
Immunity Standard
EN 50082-2 1995 Industrial
Environment
(IEC 60801 parts 2,3 and 4)
Susceptibility to Electrostatic
Discharge
8kV air discharge/4kV contact.
WARNING: This specification
applies when the transducer case is
closed. If the transducer case is
opened then appropriate ESD
protection must be taken.
Low Voltage Directive
72/23/EEC
Designed to EN61010-1 and A3
1993 and 1995 safety
requirements.
Compliance
Voltage
Value of maximum output load () by output current rating
1mA 5mA 10mA 20mA
15V 15k 3k 1.5k 750
The output loading (k) can be obtained by dividing the
compliance voltage (V) by the maximum rated output (mA)
Voltage output
The minimum load for a 10V voltage output is 500 ohms
Transducer output loading
Current output:
11
Connection diagrams for MiCOM I400 digital transducers - Input connections
2 11
v
V
u
U
L
N
Volts, frequency
1 3
L K
L
N
Current
k l
L K
L1
N
Power - single phase
k l
1 3 2 11
V U
u v
Power - 3 wire balanced
1 2 3 5 8
u v
U V
L1
L2
L3
U V
u v
k l
K L
Power - 3 wire unbalanced
1 2 3 5 7 8 9
u v
U V
L1
L2
L3
U V
u v
k l
K L k l
K L
Power - 4 wire balanced
L K
L1
N
k l
1 3 2 11
V U
u v
L2
L3
Power - 4 wire unbalanced
L3
1 2 3 4 5 6 7 8 9 11
L2
L1
N
U U U
K L
K L
K L
k l
k l
k l
X X X
x x x
u u u
Triple current
L3
1 3 4 6 7 9
L2
L1
N
K L
K L
K L
k l
k l
k l
Triple voltage
L3
2 5 8 11
L2
L1
N
U U U
X X X
x x x
u u u
2 11
v
V
u
U
L
N
Volts + frequency
L K
L1
N
Current + volts
k l
1 3 2 11
V U
u v
Note: The diagrams referred to as Power are applicable to Watt, var,
VA, phase angle, Watt+var and multifunction transducers.
12
Other connections
Notes: I400 Communications port connections
RS232 Rx = terminal 21
Com = terminal 22
Tx = terminal 23
RS485 RxTxA = terminal 21
No connection = terminal 22
RxTxB = terminal 23
An auxiliary power supply is necessary for all the transducers except for the self powered current and
voltage transducers.
Output designations for multiple output transducers
Note: By default single output transducers always utilise the above terminal designations for output 1.
I400 Function I400 Terminal
Outputs
Output 1
Output 2
Output 3
Auxiliary power supply
Communication
RS232 / RS485
+
+
+
+/AC
/AC
Rx /A
Tx /B
Signal ground /NC
15
16
17
18
19
20
13
14
21
22
23
I400 Terminal
RS232 9 pin
connections to PC
PC Terminal
21
22
23
3
5
2
Transducer type Output 1 Output 2 Output 3 Comments
Watt + var Watts vars - For input connections use
power diagram on page
11 for specified system
RMS current + RMS volts Current Volts - -
Frequency + RMS volts Frequency Volts - -
Triple current Current L1 Current L2 Current L3 Can be used on 3 or 4
wire systems
Triple voltage Voltage L1-N Voltage L2-N Voltage L3-N Can be used on 3 or 4
wire systems
Connections for DC input transducers
Type Terminal
1 2 3 4 5 13 14 15 16 21, 22, 23
DC volts + Vin -Vin Vaux(+) Vaux(-) Output + Output - Comms
DC current -Iin +Iin Vaux(+) Vaux(-) Output + Output - Comms
2 wire resistance Rin Rin Vaux(+) Vaux(-) Output + Output - Comms
13
Case size and fixing details
104.5 100
75
All dimensions in mm
Maximum section of connection wires
< = 4.0mm
2
for one wire
< = 1.5mm
2
for two wires
44.8 104.5
75
Shipping weights
The following weights apply to
individual transducers:
In practice, export orders will have
additional secondary packaging -
consult factory for details.
Packed dimensions
Individual Units
45mm Housing
98 x 113 x 55 mm
100mm Housing
98 x 113 x 112 mm
Transducer type
Max. net
weight (g)
Power supply
Single measurement ac current,
ac voltage, frequency, dc current,
dc voltage or 2 wire resistance
transducer
AC auxiliary or
self powered
Housing
(mm)
45 320
Universal power
supply
45 200
Single measurement power
transducer
AC auxiliary 100 460
Single measurement power
transducer
100 340 Universal power
supply
Multiple measurement transducer 100 460 Universal power
supply
Single measurement ac current,
ac voltage, frequency, dc current,
dc voltage or 2 wire resistance
transducer
Associated
documentation
I9-113 Transducer Application
Guide
Caution! Refer to Operating &
Maintenance manual before
installing, commissioning, or
operating the equipment
1. Installation, commissioning and
maintenance should only be
carried out be suitably qualified
personnel.
2. Terminations exposed during
installation, commissioning and
maintenance may present a
hazard unless the equipment is
electrically isolated.
3. The equipment should only be
operated as intended eg. with
the covers in place, and within
the specified electrical and
environmental limits.
4. Due to the presence of
electrostatic sensitive devices on
the printed circuit board,
appropriate ESD protection must
be taken before commencing
installation, commissioning or
maintenance.
14
Notes:
Your contact:
15
P
u
b
l
i
c
a
t
i
o
n
:

i
4
0
0
/
E
N

B
R
/
B
c


2
0
0
2

A
L
S
T
O
M

-


0
7
0
2
0
1

C
l

m
e
n
t

i
m
p
r
i
m
e
u
r
s
Transmission & Distribution Energy Automation & Information, Le Sextant, 3 avenue Andr Malraux, 92300 Levallois-Perret. France
Tel: +33 (0) 1 41 49 20 00 Fax: +33 (0) 1 41 49 24 85 energy-automation.information@tde.alstom.com www.tde.alstom.com
Contact Centre on line 24 hours a day : +44 (0) 1785 25 00 70
ALSTOM, the ALSTOM logo and any alternative version thereof are trademarks and service marks of ALSTOM.
MiCOM is a registered trademark of ALSTOM. Other names mentioned, registered or not, are the property of their respective companies.