A1. Alarm 1, prewarning A2. Alarm 2, alarms which will stop the unit
Alarm 2:
Error Error text Error description No.
00 A2 A01X41 EMERGENCY STOP Emergency stop has been activated.
10 A2 N02T01 TANK TEMP MAX2 The oil tank temperature is above 60C.
11 A2 N02T01 TANK TEMP MIN4 The oil tank temperature is below 1C.
12 A2 N01P01 HYDR PRES. MIN2 *The hydraulic pump has been in operation for 20 sec., but the pressure is still below min.
13 A2 D010L41 TANK LEVL MIN2 The oil level is below min2.
14 A2 D07Z41 VALVE HYDR. PUMP The main oil valve is closed.
15 A2 D04P41 PRESS. MAX CYL 1 The accumulator pressure for cylinder 1 is above max.
16 A2 D05P41 PRESS. MAX CYL 2 The accumulator pressure for cylinder 2 is above max.
17 A2 D06P41 PRESS. MAX CYL 3 The accumulator pressure for cylinder 3 is above max.
18 A2 M01C41 STOPPED TO LONG The circulation pump alarm occurs when the pump, during normal operation of the hydraulic system, has been stopped for more than 1 hour.
20 A2 E01C41 UNIT FAULT The MCC for E01 is not ready.
21 A2 E01C61 RETURN FAULT The E01 return signal from the MCC is not given after the command is given, or the E01 return signal from the MCC is given but not the command.
23 A2 N01P01 OUTSIDE LIMITS The pressure has been outside limit for 5 min.
24 A2 D04P42 PRESS. MIN CYL 1 The accumulator pressure for cylinder 1 is below min.
25 A2 D05P42 PRESS. MIN CYL 2 The accumulator pressure for cylinder 2 is below min.
26 A2 D06P42 PRESS. MIN CYL 3 The accumulator pressure for cylinder 3 is below min.
34 A2 M01C41 UNIT FAULT The MCC for M01 is not ready.
35 A2 M01C61 RETURN FAULT The M01 return signal from the MCC is not given after the command is given, or the M01 return signal from the MCC is given but not the command.
36 A2 M01C71 OVERLOAD FAULT Overload fault MCC for M01.
37 A2 M02C41 UNIT FAULT The MCC for M02 is not ready.
38 A2 M02C61 RETURN FAULT The M02 return signal from the MCC is not given after the command is given, or the M02 return signal from the MCC is given but not the command.
39 A2 M02C71 OVERLOAD FAULT Overload fault MCC for M02.
43 A2 N02T01 TANK TEMP MIN2 The hydraulic system is started and oil tank temperature drops below 15C.
49 A2 N2T01 INSTR. FAULT Broken wire or instrument fault on N02. Oil tank temperature.
50 A2 N01P01 INSTR. FAULT Broken wire or instrument fault on N01. Hydraulic pressure.
51 A2 B01L01 INSTR. FAULT Broken wire or instrument fault on B01. Layer thickness.
52 A2 A01P11 INSTR. FAULT Broken wire or instrument fault on N01. Hydraulic pressure setpoint from CCS.
59 A2 E01C71 OVERLOAD FAULT Overload fault MCC for E01.
Alarm 1:
Error Error text Error description No.
01 A1 A01X42 LOC. PERM.OVER Local permission is overridden from the Control Display.
09 A1 M01C41 CIRC. PUMP STOP Circulation pump is stopped from CD for filter change.
27 A1 D08P41 FILTER BLOCKED The oil filter is blocked.
28 A1 D09L41 TANK LEVEL MIN1 The oil level in the tank is below min.1.
29 A1 N01P01 HYDR PRES. MIN1 *The hydraulic pressure is still below min. even the hydraulic pump has been in operation for 20 sec.
30 A1 N01P01 HYDR PRES. MAX *The hydraulic pressure is above max.
31 A1 N02T01 TANK TEMP MAX1 The oil tank temperature is above 55C.
32 A1 N02T01 TANK TEMP MIN3 The oil tank temperature is below 5C.
40 A1 E01C41 UNIT FAULT If the temperature in the oil tank is above control range (40C), and the MCC for E1 is not ready, this prewarning will be generated.
41 A1 E01C61 RETURN FAULT If the temperature in the oil tank is above control range (40C), and the E01 return signal from the MCC is not given after the command is given, or the E01 return signal from the MCC is given but not the command, this prewarning will be generated.
42 A1 A01X45 EMPTY/FILLING Emptying or filling of oil tank from the local panel is selected.
44 A1 N02T01 TANK TEMP MIN1 The oil tank temperature is below 17C, and the hydraulic system is started.
48 A1 A01C68 GEAR STOPPED The gear unit is not in operation.
60 A1 E01C71 OVERLOAD FAULT Overload fault MCC for E01.