RELAY COORDINATION BASED ON THE FAULT MVA AT 11KV CLIENT SWITCH

BOARD AS 762MVA OR 40KA FAULT CURRENT.


Typical Relay Coordination Setting Between 800A Out Going ACB Feeder and 250A
MCCB at MCP applicable for the following 132KW Motors:
1. Hydraulic Casting Platform Pump No.s 1,2,3 & 4 from LCSS11.
2. Hydraulic Runout & Discharge Pump No.s 1,2,3,4,5 & 6 from LCSS12.
3. Hydraulic Casting Platform Pump No.s 1,2,3 & 4 from LCSS21.
4. Hydraulic Runout & Discharge Pump No.s 1,2,3,4,5 & 6 from LCSS22.
5. Hydraulic Casting Platform Pump No.s 1,2,3 & 4 from LCSS31.
6. Cold Charging Roller Table Hydraulic Unit Pump No.s 1,2 & 3 from LCSS34.
7. Discharge Hydraulic Unit Pump No.s 1,2,3,4,5 & 6 from LCSS34.
8. Hydraulic System for Runout Area Pump No.s 1,2,3 & 4 from LCSS42.
9. Casting Platform Hydraulic Pump No.s 1,2,3 & 4 from LCSS42.
10. Bloom Cross Transfer Manipulator Lifting Device from LCSS42.

Typical Relay Coordination Setting Between 800A Out Going ACB Feeder and 315A
MCCB at MCP applicable for the following 160KW Motors:
1. Mould Cooling Pump No.s 1,2,3 & 4 from LCSS11.
2. Mould Cooling Pump No.s 1,2,3 & 4 from LCSS21.
3. Mould Cooling Pump No.s 1,2,3 & 4 from LCSS31.
4. Closed Machine Cooling Pump No.s 1,2,3 & 4 from LCSS32.
5. Closed Machine Cooling Pump No.s 1,2 &3 from LCSS41.
6. Mould Cooling Pump No.s 1,2,3,4 & 5 from LCSS41.

Typical Relay Coordination Setting for 4000A Incomer at LCSS11 with Check For Start of
160KW Motor With Full Load On LCSS 11:

Typical Relay Coordination Setting Between 800A Out Going ACB Feeder for 160KW
MCP and Incomer at LCSS11:

Typical Relay Coordination Setting Between 1600A Out Going ACB Feeder for Common
MCC1 at LCSS11 and Incomer at Common MCC1:

The settings for LCSS11 are applicable for LCSS21 as the feeder ratings
and MD Calculation are similar.

Typical Relay Coordination Setting for 4000A Incomer at LCSS12 with Check For Start
of 132KW Motor With Full Load On LCSS 12:

Typical Relay Coordination Setting Between 1600A Out Going ACB Feeder for Strand
MCC1 and Incomer at Strand MCC1:

Typical Relay Coordination Setting Between 800A Out Going ACB Feeder for PDB at
LCSS13 and Incomer at PDB:

Typical Relay Coordination Setting Between 1600A Out Going ACB Feeder for EMS
PDB at LCSS13 and Incomer at EMS PDB:

Typical Relay Coordination Setting Between 1600A Out Going ACB Feeder for EMS
PDB at LCSS13 and Incomer at LCSS13:

Typical Relay Coordination Setting Between 4000A Incoming ACB at LCSS13, 800A
Outgoing ACB to Common MCC2 at LCSS13 and 800A Incoming ACB at Common
MCC2:

The settings for LCSS13 are applicable for LCSS23 as the feeder ratings
and MD Calculation are similar.

Typical Relay Coordination Setting Between 4000A Incoming ACB at LCSS22,


1600A Outgoing ACB for Strand MCC at LCSS22 and 1600A Incoming ACB at
Strand MCC:

Typical Relay Coordination Setting Between 4000A Incoming ACB at LCSS31,


1600A Outgoing ACB to Common MCC 1 at LCSS31 and 1600A Incoming ACB at
Common MCC 1:

Typical Relay Coordination Setting Between 4000A Incoming ACB at LCSS32,


1600A Outgoing ACB to Strand 123 MCC at LCSS32 and 1600A Incoming ACB at
Strand 123 MCC:

Note: Settings for Outgoing ACB to Strand 456 MCC are identical to Outgoing ACB
to Strand 456 MCC at LCSS 32.

Typical Relay Coordination Setting Between 4000A Incoming ACB at LCSS33,


2500A Outgoing ACB to EMS PDB at LCSS33, 2000A Incoming ACB at EMS PDB,
800A Outgoing ACB to Common MCC2 at LCSS33, 800A Incoming ACB at Common
MCC2, 800A Outgoing ACB to PDB at LCSS33 AND 800A Incoming ACB at PDB:

Typical Relay Coordination Setting Between 4000A Incoming ACB at LCSS34, 800A
Outgoing ACB to RT MCC1 at LCSS34, 800A Incoming ACB at RT MCC1, 800A
Outgoing ACB to RT MCC2 at LCSS34 and 800A Incoming ACB at RT MCC2:

Typical Relay Coordination Setting Between 4000A Incoming ACB at LCSS41, 800A
Outgoing ACB to TRT MCC at LCSS41, 800A Incoming ACB at TRT MCC, 1600A
Outgoing ACB to Common MCC at LCSS41 and 1600A Incoming ACB at Common
MCC:

Typical Relay Coordination Setting Between 4000A Incoming ACB at LCSS42, 800A
Outgoing ACB to Strand MCC at LCSS42, 800A Incoming ACB at Strand MCC,
Outgoing ACB to PDB at LCSS42, 800A Incoming ACB at PDB: