Air System Sizing Summary for AHU-01

Project Name: PRIVATE SCHOOL @ ABU DHABI


Prepared by: Taiba Engineering Consultant

07/23/2014
09:01PM

Air System Information


Air System Name ............................................ AHU-01
Equipment Class ........................................... CW AHU
Air System Type ............................................... SZCAV

Number of zones ............................................................ 1


Floor Area .............................................................. 9257.0 ft
Location ................... Abu Dhabi, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone CFM ....................... Sum of space airflow rates
Space CFM ................... Individual peak space loads

Calculation Months ......................................... Jul to Aug


Sizing Data ..................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ........................................................ 35.5
Total coil load ...................................................... 425.7
Sensible coil load ................................................ 278.9
Coil CFM at Aug 1500 .......................................... 6922
Max block CFM .................................................... 6922
Sum of peak zone CFM ....................................... 6922
Sensible heat ratio .............................................. 0.655
ft/Ton .................................................................. 261.0
BTU/(hr-ft) ............................................................ 46.0
Water flow @ 10.0 F rise ................................... 85.18

Tons
MBH
MBH
CFM
CFM
CFM

gpm

Load occurs at .................................................. Aug 1500


OA DB / WB ................................................... 115.0 / 85.0
Entering DB / WB ............................................ 92.3 / 72.8
Leaving DB / WB ............................................. 54.9 / 53.5
Coil ADP .................................................................... 50.8
Bypass Factor .......................................................... 0.100
Resulting RH ................................................................ 49
Design supply temp. .................................................. 58.0
Zone T-stat Check .................................................. 0 of 1
Max zone temperature deviation ................................. 0.6

F
F
F
F
%
F
OK
F

Central Heating Coil Sizing Data


Max coil load ......................................................... 48.1
Coil CFM at Des Htg ............................................ 6922
Max coil CFM ....................................................... 6922
Water flow @ 20.0 F drop .................................... 4.81

MBH
CFM
CFM
gpm

Load occurs at .................................................... Des Htg


BTU/(hr-ft) .................................................................. 5.2
Ent. DB / Lvg DB ............................................. 63.9 / 70.4 F

Supply Fan Sizing Data


Actual max CFM ................................................... 6922 CFM
Standard CFM ...................................................... 6900 CFM
Actual max CFM/ft ............................................... 0.75 CFM/ft

Fan motor BHP .......................................................... 3.79 BHP


Fan motor kW ............................................................ 3.01 kW
Fan static ................................................................... 2.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM .............................................. 2281 CFM
CFM/ft .................................................................. 0.25 CFM/ft

Hourly Analysis Program v4.61

CFM/person ............................................................. 10.91 CFM/person

Page 1 of 30

Zone Sizing Summary for AHU-01


Project Name: PRIVATE SCHOOL @ ABU DHABI
Prepared by: Taiba Engineering Consultant

07/23/2014
09:01PM

Air System Information


Air System Name ............................................ AHU-01
Equipment Class ........................................... CW AHU
Air System Type ............................................... SZCAV

Number of zones ............................................................ 1


Floor Area .............................................................. 9257.0 ft
Location ................... Abu Dhabi, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone CFM ....................... Sum of space airflow rates
Space CFM ................... Individual peak space loads

Calculation Months ......................................... Jul to Aug


Sizing Data ..................................................... Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(MBH)
126.4

Design
Air
Flow
(CFM)
6922

Minimum
Air
Flow
(CFM)
6922

Time
of
Peak
Load
Aug 1500

Maximum
Heating
Load
(MBH)
16.1

Zone
Floor
Area
(ft)
9257.0

Zone
CFM/ft
0.75

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.
Space Loads and Airflows

Zone Name /
Space Name
Zone 1
GF-28-GYMNASIUM
GF-29-OFFICE

Hourly Analysis Program v4.61

Mult.

Cooling
Sensible
(MBH)

Time
of
Load

Air
Flow
(CFM)

Heating
Load
(MBH)

Floor
Area
(ft)

Space
CFM/ft

1
1

116.1
10.6

Aug 1500
Jul 1800

6342
581

15.3
0.8

7050.4
2206.6

0.90
0.26

Page 2 of 30

Ventilation Sizing Summary for AHU-01


Project Name: PRIVATE SCHOOL @ ABU DHABI
Prepared by: Taiba Engineering Consultant

07/23/2014
09:01PM

1. Summary
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ................................................................. 2281 CFM

2. Space Ventilation Analysis Table

Zone Name / Space Name


Zone 1
GF-28-GYMNASIUM
GF-29-OFFICE
Totals (incl. Space Multipliers)

Hourly Analysis Program v4.61

Mult.

Floor
Area
(ft)

Maximum
Occupants

1
1

7050.4
2206.6

196.0
13.0

Maximum
Required
Supply Air Outdoor Air
(CFM) (CFM/person)
6341.7
580.7
6922.4

0.00
5.30

Required
Outdoor Air
(CFM/ft)
0.30
0.06

Required
Required
Outdoor Air Outdoor Air
(CFM) (% of supply)
0.0
0.0

0.0
0.0

Uncorrected
Outdoor Air
(CFM)
2081.8
199.2
2281.0

Page 3 of 30

Air System Sizing Summary for AHU-02


Project Name: PRIVATE SCHOOL @ ABU DHABI
Prepared by: Taiba Engineering Consultant

07/23/2014
09:01PM

Air System Information


Air System Name ............................................ AHU-02
Equipment Class ........................................... CW AHU
Air System Type ............................................... SZCAV

Number of zones ............................................................ 1


Floor Area .............................................................. 8085.9 ft
Location ................... Abu Dhabi, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone CFM ....................... Sum of space airflow rates
Space CFM ................... Individual peak space loads

Calculation Months ......................................... Jul to Aug


Sizing Data ..................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ........................................................ 36.9
Total coil load ...................................................... 443.2
Sensible coil load ................................................ 311.2
Coil CFM at Aug 1500 .......................................... 9559
Max block CFM .................................................... 9559
Sum of peak zone CFM ....................................... 9559
Sensible heat ratio .............................................. 0.702
ft/Ton .................................................................. 218.9
BTU/(hr-ft) ............................................................ 54.8
Water flow @ 10.0 F rise ................................... 88.68

Tons
MBH
MBH
CFM
CFM
CFM

gpm

Load occurs at .................................................. Aug 1500


OA DB / WB ................................................... 115.0 / 85.0
Entering DB / WB ............................................ 85.9 / 69.3
Leaving DB / WB ............................................. 55.6 / 54.3
Coil ADP .................................................................... 52.3
Bypass Factor .......................................................... 0.100
Resulting RH ................................................................ 48
Design supply temp. .................................................. 58.0
Zone T-stat Check .................................................. 1 of 1
Max zone temperature deviation ................................. 0.0

F
F
F
F
%
F
OK
F

Central Heating Coil Sizing Data


Max coil load ......................................................... 48.2
Coil CFM at Des Htg ............................................ 9559
Max coil CFM ....................................................... 9559
Water flow @ 20.0 F drop .................................... 4.82

MBH
CFM
CFM
gpm

Load occurs at .................................................... Des Htg


BTU/(hr-ft) .................................................................. 6.0
Ent. DB / Lvg DB ............................................. 65.9 / 70.6 F

Supply Fan Sizing Data


Actual max CFM ................................................... 9559 CFM
Standard CFM ...................................................... 9529 CFM
Actual max CFM/ft ............................................... 1.18 CFM/ft

Fan motor BHP .......................................................... 5.24 BHP


Fan motor kW ............................................................ 4.15 kW
Fan static ................................................................... 2.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM .............................................. 2152 CFM
CFM/ft .................................................................. 0.27 CFM/ft

Hourly Analysis Program v4.61

CFM/person ............................................................. 14.54 CFM/person

Page 4 of 30

Zone Sizing Summary for AHU-02


Project Name: PRIVATE SCHOOL @ ABU DHABI
Prepared by: Taiba Engineering Consultant

07/23/2014
09:01PM

Air System Information


Air System Name ............................................ AHU-02
Equipment Class ........................................... CW AHU
Air System Type ............................................... SZCAV

Number of zones ............................................................ 1


Floor Area .............................................................. 8085.9 ft
Location ................... Abu Dhabi, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone CFM ....................... Sum of space airflow rates
Space CFM ................... Individual peak space loads

Calculation Months ......................................... Jul to Aug


Sizing Data ..................................................... Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(MBH)
170.6

Design
Air
Flow
(CFM)
9559

Minimum
Air
Flow
(CFM)
9559

Time
of
Peak
Load
Jul 1700

Maximum
Heating
Load
(MBH)
18.8

Zone
Floor
Area
(ft)
8085.9

Zone
CFM/ft
1.18

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.
Space Loads and Airflows

Zone Name /
Space Name
Zone 1
GF-30-K.G/CLASS ROOM-01
GF-31-K.G/CLASS ROOM-02
GF-32-K.G/CLASS ROOM-03
GF-33-K.G/CLASS ROOM-04
GF-34-K.G/CLASS ROOM-05
GF-35-K.G/CLASS ROOM-06
GF-36-K.G/CLASS ROOM-07
GF-37-K.G/CLASS ROOM-08
GF-38-ENCLOSED PLAY AREA
GF-39-CORRIDOR-03
GF-40-ENTRANCE K1
GF-41-SEN ROOM-02
GF-42-QUIET AREA
GF-43-PANTRY
GF-44-PRINCIPAL ROOM-02
GF-45-TEACHERS ROOM

Hourly Analysis Program v4.61

Mult.

Cooling
Sensible
(MBH)

Time
of
Load

Air
Flow
(CFM)

Heating
Load
(MBH)

Floor
Area
(ft)

Space
CFM/ft

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

12.7
12.9
12.7
13.5
13.6
13.5
13.7
12.7
26.2
5.1
9.8
5.2
1.5
4.6
3.3
14.0

Aug 1400
Aug 1400
Aug 1400
Jul 1700
Jul 1700
Jul 1700
Jul 1700
Jul 1700
Jul 1700
Jul 1800
Jul 1700
Aug 1400
Jul 1700
Jul 1800
Aug 1800
Aug 1600

694
703
693
739
741
739
749
693
1430
280
534
285
83
249
180
767

1.4
1.4
1.4
1.9
1.9
1.9
1.9
1.4
2.0
0.0
0.6
0.7
0.3
0.3
0.6
1.2

581.3
581.3
581.3
581.3
581.3
581.3
581.3
581.3
990.3
1362.7
161.5
215.3
215.3
38.8
193.8
258.3

1.19
1.21
1.19
1.27
1.27
1.27
1.29
1.19
1.44
0.21
3.31
1.33
0.39
6.44
0.93
2.97

Page 5 of 30

Ventilation Sizing Summary for AHU-02


Project Name: PRIVATE SCHOOL @ ABU DHABI
Prepared by: Taiba Engineering Consultant

07/23/2014
09:01PM

1. Summary
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ................................................................. 2152 CFM

2. Space Ventilation Analysis Table

Zone Name / Space Name


Zone 1
GF-30-K.G/CLASS ROOM-01
GF-31-K.G/CLASS ROOM-02
GF-32-K.G/CLASS ROOM-03
GF-33-K.G/CLASS ROOM-04
GF-34-K.G/CLASS ROOM-05
GF-35-K.G/CLASS ROOM-06
GF-36-K.G/CLASS ROOM-07
GF-37-K.G/CLASS ROOM-08
GF-38-ENCLOSED PLAY AREA
GF-39-CORRIDOR-03
GF-40-ENTRANCE K1
GF-41-SEN ROOM-02
GF-42-QUIET AREA
GF-43-PANTRY
GF-44-PRINCIPAL ROOM-02
GF-45-TEACHERS ROOM
Totals (incl. Space Multipliers)

Hourly Analysis Program v4.61

Mult.

Floor
Area
(ft)

Maximum
Occupants

1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1

581.3
581.3
581.3
581.3
581.3
581.3
581.3
581.3
990.3
1362.7
161.5
215.3
215.3
38.8
193.8
258.3

13.0
13.0
13.0
13.0
13.0
13.0
13.0
13.0
22.0
6.0
6.0
0.0
2.0
2.0
2.0
4.0

Maximum
Required
Supply Air Outdoor Air
(CFM) (CFM/person)
694.1
702.7
693.4
738.9
740.7
738.9
749.0
693.4
1430.1
279.7
534.1
285.3
83.0
249.5
179.8
766.7
9559.3

10.59
10.59
10.59
10.59
10.59
10.59
10.59
10.59
8.05
0.00
5.30
10.59
10.59
5.30
5.30
5.30

Required
Outdoor Air
(CFM/ft)
0.12
0.12
0.12
0.12
0.12
0.12
0.12
0.12
0.06
0.06
0.06
0.12
0.12
0.06
0.06
0.06

Required
Required
Outdoor Air Outdoor Air
(CFM) (% of supply)
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0

0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0

Uncorrected
Outdoor Air
(CFM)
206.4
206.4
206.4
206.4
206.4
206.4
206.4
206.4
235.6
80.5
41.3
25.4
46.6
12.9
22.0
36.4
2151.9

Page 6 of 30

Air System Sizing Summary for AHU-03


Project Name: PRIVATE SCHOOL @ ABU DHABI
Prepared by: Taiba Engineering Consultant

07/23/2014
09:01PM

Air System Information


Air System Name ............................................ AHU-03
Equipment Class ........................................... CW AHU
Air System Type ............................................... SZCAV

Number of zones ............................................................ 1


Floor Area .............................................................. 4456.3 ft
Location ................... Abu Dhabi, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone CFM ....................... Sum of space airflow rates
Space CFM ................... Individual peak space loads

Calculation Months ......................................... Jul to Aug


Sizing Data ..................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ........................................................ 30.0
Total coil load ...................................................... 360.0
Sensible coil load ................................................ 252.8
Coil CFM at Jul 1600 ............................................ 8079
Max block CFM .................................................... 8079
Sum of peak zone CFM ....................................... 8079
Sensible heat ratio .............................................. 0.702
ft/Ton .................................................................. 148.5
BTU/(hr-ft) ............................................................ 80.8
Water flow @ 10.0 F rise ................................... 72.04

Tons
MBH
MBH
CFM
CFM
CFM

gpm

Load occurs at .................................................... Jul 1600


OA DB / WB ................................................... 114.4 / 84.9
Entering DB / WB ............................................ 85.0 / 69.1
Leaving DB / WB ............................................. 56.0 / 54.6
Coil ADP .................................................................... 52.7
Bypass Factor .......................................................... 0.100
Resulting RH ................................................................ 49
Design supply temp. .................................................. 58.0
Zone T-stat Check .................................................. 1 of 1
Max zone temperature deviation ................................. 0.0

F
F
F
F
%
F
OK
F

Central Heating Coil Sizing Data


Max coil load ......................................................... 31.5
Coil CFM at Des Htg ............................................ 8079
Max coil CFM ....................................................... 8079
Water flow @ 20.0 F drop .................................... 3.16

MBH
CFM
CFM
gpm

Load occurs at .................................................... Des Htg


BTU/(hr-ft) .................................................................. 7.1
Ent. DB / Lvg DB ............................................. 65.9 / 69.5 F

Supply Fan Sizing Data


Actual max CFM ................................................... 8079 CFM
Standard CFM ...................................................... 8053 CFM
Actual max CFM/ft ............................................... 1.81 CFM/ft

Fan motor BHP .......................................................... 4.43 BHP


Fan motor kW ............................................................ 3.51 kW
Fan static ................................................................... 2.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM .............................................. 1748 CFM
CFM/ft .................................................................. 0.39 CFM/ft

Hourly Analysis Program v4.61

CFM/person ............................................................. 13.87 CFM/person

Page 7 of 30

Zone Sizing Summary for AHU-03


Project Name: PRIVATE SCHOOL @ ABU DHABI
Prepared by: Taiba Engineering Consultant

07/23/2014
09:01PM

Air System Information


Air System Name ............................................ AHU-03
Equipment Class ........................................... CW AHU
Air System Type ............................................... SZCAV

Number of zones ............................................................ 1


Floor Area .............................................................. 4456.3 ft
Location ................... Abu Dhabi, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone CFM ....................... Sum of space airflow rates
Space CFM ................... Individual peak space loads

Calculation Months ......................................... Jul to Aug


Sizing Data ..................................................... Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(MBH)
140.4

Design
Air
Flow
(CFM)
8079

Minimum
Air
Flow
(CFM)
8079

Time
of
Peak
Load
Jul 1700

Maximum
Heating
Load
(MBH)
10.2

Zone
Floor
Area
(ft)
4456.3

Zone
CFM/ft
1.81

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.
Space Loads and Airflows

Zone Name /
Space Name
Zone 1
GF-01-CLASS ROOM-01
GF-02-CLASS ROOM-02
GF-03-CLASS ROOM-03
GF-04-CLASS ROOM-04
GF-05-CLASS ROOM-05
GF-06-CLASS ROOM-06
GF-13-CORRIDOR-01

Hourly Analysis Program v4.61

Mult.

Cooling
Sensible
(MBH)

Time
of
Load

Air
Flow
(CFM)

Heating
Load
(MBH)

Floor
Area
(ft)

Space
CFM/ft

1
1
1
1
1
1
1

22.1
21.6
22.4
25.7
26.0
26.4
3.7

Jul 1000
Jul 0900
Jul 1000
Jul 1700
Jul 1700
Jul 1700
Jul 1800

1205
1180
1224
1405
1421
1444
200

1.5
1.2
1.7
1.8
1.9
2.1
0.0

601.7
601.7
601.7
601.7
601.7
601.7
846.0

2.00
1.96
2.03
2.33
2.36
2.40
0.24

Page 8 of 30

Ventilation Sizing Summary for AHU-03


Project Name: PRIVATE SCHOOL @ ABU DHABI
Prepared by: Taiba Engineering Consultant

07/23/2014
09:01PM

1. Summary
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ................................................................. 1748 CFM

2. Space Ventilation Analysis Table

Zone Name / Space Name


Zone 1
GF-01-CLASS ROOM-01
GF-02-CLASS ROOM-02
GF-03-CLASS ROOM-03
GF-04-CLASS ROOM-04
GF-05-CLASS ROOM-05
GF-06-CLASS ROOM-06
GF-13-CORRIDOR-01
Totals (incl. Space Multipliers)

Hourly Analysis Program v4.61

Mult.

Floor
Area
(ft)

Maximum
Occupants

1
1
1
1
1
1
1

601.7
601.7
601.7
601.7
601.7
601.7
846.0

20.0
20.0
20.0
20.0
20.0
20.0
6.0

Maximum
Required
Supply Air Outdoor Air
(CFM) (CFM/person)
1205.1
1179.8
1223.7
1404.8
1421.3
1444.0
200.4
8079.1

10.59
10.59
10.59
10.59
10.59
10.59
0.00

Required
Outdoor Air
(CFM/ft)
0.12
0.12
0.12
0.12
0.12
0.12
0.06

Required
Required
Outdoor Air Outdoor Air
(CFM) (% of supply)
0.0
0.0
0.0
0.0
0.0
0.0
0.0

0.0
0.0
0.0
0.0
0.0
0.0
0.0

Uncorrected
Outdoor Air
(CFM)
283.0
283.0
283.0
283.0
283.0
283.0
50.0
1747.7

Page 9 of 30

Air System Sizing Summary for AHU-04


Project Name: PRIVATE SCHOOL @ ABU DHABI
Prepared by: Taiba Engineering Consultant

07/23/2014
09:01PM

Air System Information


Air System Name ............................................ AHU-04
Equipment Class ........................................... CW AHU
Air System Type ............................................... SZCAV

Number of zones ............................................................ 1


Floor Area .............................................................. 5578.9 ft
Location ................... Abu Dhabi, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone CFM ....................... Sum of space airflow rates
Space CFM ................... Individual peak space loads

Calculation Months ......................................... Jul to Aug


Sizing Data ..................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ........................................................ 40.1
Total coil load ...................................................... 481.5
Sensible coil load ................................................ 339.8
Coil CFM at Aug 1600 ........................................ 10504
Max block CFM .................................................. 10504
Sum of peak zone CFM ..................................... 10504
Sensible heat ratio .............................................. 0.706
ft/Ton .................................................................. 139.0
BTU/(hr-ft) ............................................................ 86.3
Water flow @ 10.0 F rise ................................... 96.35

Tons
MBH
MBH
CFM
CFM
CFM

gpm

Load occurs at .................................................. Aug 1600


OA DB / WB ................................................... 114.4 / 84.9
Entering DB / WB ............................................ 85.9 / 69.3
Leaving DB / WB ............................................. 55.9 / 54.5
Coil ADP .................................................................... 52.5
Bypass Factor .......................................................... 0.100
Resulting RH ................................................................ 49
Design supply temp. .................................................. 58.0
Zone T-stat Check .................................................. 1 of 1
Max zone temperature deviation ................................. 0.0

F
F
F
F
%
F
OK
F

Central Heating Coil Sizing Data


Max coil load ......................................................... 47.6
Coil CFM at Des Htg .......................................... 10504
Max coil CFM ..................................................... 10504
Water flow @ 20.0 F drop .................................... 4.76

MBH
CFM
CFM
gpm

Load occurs at .................................................... Des Htg


BTU/(hr-ft) .................................................................. 8.5
Ent. DB / Lvg DB ............................................. 66.2 / 70.4 F

Supply Fan Sizing Data


Actual max CFM ................................................. 10504 CFM
Standard CFM .................................................... 10471 CFM
Actual max CFM/ft ............................................... 1.88 CFM/ft

Fan motor BHP .......................................................... 5.75 BHP


Fan motor kW ............................................................ 4.56 kW
Fan static ................................................................... 2.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM .............................................. 2247 CFM
CFM/ft .................................................................. 0.40 CFM/ft

Hourly Analysis Program v4.61

CFM/person ............................................................. 12.41 CFM/person

Page 10 of 30

Zone Sizing Summary for AHU-04


Project Name: PRIVATE SCHOOL @ ABU DHABI
Prepared by: Taiba Engineering Consultant

07/23/2014
09:01PM

Air System Information


Air System Name ............................................ AHU-04
Equipment Class ........................................... CW AHU
Air System Type ............................................... SZCAV

Number of zones ............................................................ 1


Floor Area .............................................................. 5578.9 ft
Location ................... Abu Dhabi, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone CFM ....................... Sum of space airflow rates
Space CFM ................... Individual peak space loads

Calculation Months ......................................... Jul to Aug


Sizing Data ..................................................... Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(MBH)
184.3

Design
Air
Flow
(CFM)
10504

Minimum
Air
Flow
(CFM)
10504

Time
of
Peak
Load
Jul 1700

Maximum
Heating
Load
(MBH)
15.7

Zone
Floor
Area
(ft)
5578.9

Zone
CFM/ft
1.88

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.
Space Loads and Airflows

Zone Name /
Space Name
Zone 1
FF-01-CLASS ROOM-01
FF-02-CLASS ROOM-02
FF-03-CLASS ROOM-03
FF-04-CLASS ROOM-04
FF-05-CLASS ROOM-05
FF-06-CLASS ROOM-06
FF-07-CLASS ROOM-07
FF-08-PRAY ROOM-01
FF-09-CORRIDOR-01

Hourly Analysis Program v4.61

Mult.

Cooling
Sensible
(MBH)

Time
of
Load

Air
Flow
(CFM)

Heating
Load
(MBH)

Floor
Area
(ft)

Space
CFM/ft

1
1
1
1
1
1
1
1
1

22.7
22.3
22.4
25.9
25.3
25.3
25.7
15.9
6.6

Jul 1000
Jul 1000
Jul 1000
Jul 1700
Jul 1700
Jul 1700
Jul 1700
Jul 1700
Jul 1400

1242
1217
1226
1418
1384
1384
1406
869
359

2.0
1.7
1.8
2.0
1.7
1.7
1.9
1.3
1.5

601.7
601.7
601.7
601.7
601.7
601.7
601.7
322.9
1044.1

2.06
2.02
2.04
2.36
2.30
2.30
2.34
2.69
0.34

Page 11 of 30

Ventilation Sizing Summary for AHU-04


Project Name: PRIVATE SCHOOL @ ABU DHABI
Prepared by: Taiba Engineering Consultant

07/23/2014
09:01PM

1. Summary
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ................................................................. 2247 CFM

2. Space Ventilation Analysis Table

Zone Name / Space Name


Zone 1
FF-01-CLASS ROOM-01
FF-02-CLASS ROOM-02
FF-03-CLASS ROOM-03
FF-04-CLASS ROOM-04
FF-05-CLASS ROOM-05
FF-06-CLASS ROOM-06
FF-07-CLASS ROOM-07
FF-08-PRAY ROOM-01
FF-09-CORRIDOR-01
Totals (incl. Space Multipliers)

Hourly Analysis Program v4.61

Mult.

Floor
Area
(ft)

Maximum
Occupants

1
1
1
1
1
1
1
1
1

601.7
601.7
601.7
601.7
601.7
601.7
601.7
322.9
1044.1

20.0
20.0
20.0
20.0
20.0
20.0
20.0
35.0
6.0

Maximum
Required
Supply Air Outdoor Air
(CFM) (CFM/person)
1242.1
1216.5
1225.8
1417.5
1384.3
1384.3
1405.8
869.1
358.6
10504.0

10.59
10.59
10.59
10.59
10.59
10.59
10.59
5.30
0.00

Required
Outdoor Air
(CFM/ft)
0.12
0.12
0.12
0.12
0.12
0.12
0.12
0.06
0.06

Required
Required
Outdoor Air Outdoor Air
(CFM) (% of supply)
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0

0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0

Uncorrected
Outdoor Air
(CFM)
283.0
283.0
283.0
283.0
283.0
283.0
283.0
204.5
61.7
2246.8

Page 12 of 30

Air System Sizing Summary for AHU-05


Project Name: PRIVATE SCHOOL @ ABU DHABI
Prepared by: Taiba Engineering Consultant

07/23/2014
09:01PM

Air System Information


Air System Name ............................................ AHU-05
Equipment Class ........................................... CW AHU
Air System Type ............................................... SZCAV

Number of zones ............................................................ 1


Floor Area .............................................................. 7158.0 ft
Location ................... Abu Dhabi, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone CFM ....................... Sum of space airflow rates
Space CFM ................... Individual peak space loads

Calculation Months ......................................... Jul to Aug


Sizing Data ..................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ........................................................ 26.5
Total coil load ...................................................... 317.9
Sensible coil load ................................................ 224.3
Coil CFM at Jul 1500 ............................................ 6683
Max block CFM .................................................... 6683
Sum of peak zone CFM ....................................... 6683
Sensible heat ratio .............................................. 0.706
ft/Ton .................................................................. 270.2
BTU/(hr-ft) ............................................................ 44.4
Water flow @ 10.0 F rise ................................... 63.61

Tons
MBH
MBH
CFM
CFM
CFM

gpm

Load occurs at .................................................... Jul 1500


OA DB / WB ................................................... 115.0 / 85.0
Entering DB / WB ............................................ 86.2 / 69.2
Leaving DB / WB ............................................. 55.0 / 53.6
Coil ADP .................................................................... 51.6
Bypass Factor .......................................................... 0.100
Resulting RH ................................................................ 47
Design supply temp. .................................................. 58.0
Zone T-stat Check .................................................. 1 of 1
Max zone temperature deviation ................................. 0.0

F
F
F
F
%
F
OK
F

Central Heating Coil Sizing Data


Max coil load ......................................................... 35.4
Coil CFM at Des Htg ............................................ 6683
Max coil CFM ....................................................... 6683
Water flow @ 20.0 F drop .................................... 3.54

MBH
CFM
CFM
gpm

Load occurs at .................................................... Des Htg


BTU/(hr-ft) .................................................................. 4.9
Ent. DB / Lvg DB ............................................. 65.9 / 70.8 F

Supply Fan Sizing Data


Actual max CFM ................................................... 6683 CFM
Standard CFM ...................................................... 6662 CFM
Actual max CFM/ft ............................................... 0.93 CFM/ft

Fan motor BHP .......................................................... 3.66 BHP


Fan motor kW ............................................................ 2.90 kW
Fan static ................................................................... 2.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM .............................................. 1526 CFM
CFM/ft .................................................................. 0.21 CFM/ft

Hourly Analysis Program v4.61

CFM/person ............................................................. 15.90 CFM/person

Page 13 of 30

Zone Sizing Summary for AHU-05


Project Name: PRIVATE SCHOOL @ ABU DHABI
Prepared by: Taiba Engineering Consultant

07/23/2014
09:01PM

Air System Information


Air System Name ............................................ AHU-05
Equipment Class ........................................... CW AHU
Air System Type ............................................... SZCAV

Number of zones ............................................................ 1


Floor Area .............................................................. 7158.0 ft
Location ................... Abu Dhabi, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone CFM ....................... Sum of space airflow rates
Space CFM ................... Individual peak space loads

Calculation Months ......................................... Jul to Aug


Sizing Data ..................................................... Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(MBH)
115.1

Design
Air
Flow
(CFM)
6683

Minimum
Air
Flow
(CFM)
6683

Time
of
Peak
Load
Jul 1600

Maximum
Heating
Load
(MBH)
12.3

Zone
Floor
Area
(ft)
7158.0

Zone
CFM/ft
0.93

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.
Space Loads and Airflows

Zone Name /
Space Name
Zone 1
GF-46-ENTRANCE LOBBY-01
GF-15-TEACHER ROOM-01
GF-21-SEN ROOM-01
GF-22-COMPUTER LAB
GF-23-CLINIC AREA
GF-17-ART ROOM
GF-18-MUSIC ROOM
GF-48-ENTRANCE LOBBY

Hourly Analysis Program v4.61

Mult.

Cooling
Sensible
(MBH)

Time
of
Load

Air
Flow
(CFM)

Heating
Load
(MBH)

Floor
Area
(ft)

Space
CFM/ft

1
1
1
1
1
1
1
1

25.7
4.9
8.0
26.7
9.3
15.4
18.0
14.4

Jul 0900
Aug 1400
Jul 1700
Jul 1700
Jul 1700
Aug 1500
Aug 1500
Jul 1800

1404
266
437
1460
506
839
983
787

3.0
0.5
1.2
1.5
1.1
1.6
1.7
1.6

699.7
290.6
366.0
753.5
430.6
775.0
775.0
3067.7

2.01
0.92
1.20
1.94
1.18
1.08
1.27
0.26

Page 14 of 30

Ventilation Sizing Summary for AHU-05


Project Name: PRIVATE SCHOOL @ ABU DHABI
Prepared by: Taiba Engineering Consultant

07/23/2014
09:01PM

1. Summary
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ................................................................. 1526 CFM

2. Space Ventilation Analysis Table

Zone Name / Space Name


Zone 1
GF-46-ENTRANCE LOBBY-01
GF-15-TEACHER ROOM-01
GF-21-SEN ROOM-01
GF-22-COMPUTER LAB
GF-23-CLINIC AREA
GF-17-ART ROOM
GF-18-MUSIC ROOM
GF-48-ENTRANCE LOBBY
Totals (incl. Space Multipliers)

Hourly Analysis Program v4.61

Mult.

Floor
Area
(ft)

Maximum
Occupants

1
1
1
1
1
1
1
1

699.7
290.6
366.0
753.5
430.6
775.0
775.0
3067.7

4.0
4.0
0.0
22.0
5.0
16.0
30.0
15.0

Maximum
Required
Supply Air Outdoor Air
(CFM) (CFM/person)
1404.3
265.9
437.5
1459.8
506.4
839.0
983.1
787.0
6683.0

5.30
5.30
10.59
10.59
10.59
10.59
10.59
5.30

Required
Outdoor Air
(CFM/ft)
0.06
0.06
0.12
0.12
0.18
0.18
0.06
0.06

Required
Required
Outdoor Air Outdoor Air
(CFM) (% of supply)
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0

0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0

Uncorrected
Outdoor Air
(CFM)
62.5
38.4
43.2
322.1
129.3
306.8
363.6
260.6
1526.4

Page 15 of 30

Air System Sizing Summary for AHU-06


Project Name: PRIVATE SCHOOL @ ABU DHABI
Prepared by: Taiba Engineering Consultant

07/23/2014
09:01PM

Air System Information


Air System Name ............................................ AHU-06
Equipment Class ........................................... CW AHU
Air System Type ............................................... SZCAV

Number of zones ............................................................ 1


Floor Area .............................................................. 6792.0 ft
Location ................... Abu Dhabi, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone CFM ....................... Sum of space airflow rates
Space CFM ................... Individual peak space loads

Calculation Months ......................................... Jul to Aug


Sizing Data ..................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ........................................................ 30.4
Total coil load ...................................................... 364.5
Sensible coil load ................................................ 264.7
Coil CFM at Aug 1400 .......................................... 7690
Max block CFM .................................................... 7690
Sum of peak zone CFM ....................................... 7690
Sensible heat ratio .............................................. 0.726
ft/Ton .................................................................. 223.6
BTU/(hr-ft) ............................................................ 53.7
Water flow @ 10.0 F rise ................................... 72.93

Tons
MBH
MBH
CFM
CFM
CFM

gpm

Load occurs at .................................................. Aug 1400


OA DB / WB ................................................... 114.4 / 84.9
Entering DB / WB ............................................ 87.0 / 69.1
Leaving DB / WB ............................................. 55.0 / 53.5
Coil ADP .................................................................... 51.5
Bypass Factor .......................................................... 0.100
Resulting RH ................................................................ 47
Design supply temp. .................................................. 58.0
Zone T-stat Check .................................................. 1 of 1
Max zone temperature deviation ................................. 0.0

F
F
F
F
%
F
OK
F

Central Heating Coil Sizing Data


Max coil load ......................................................... 41.9
Coil CFM at Des Htg ............................................ 7690
Max coil CFM ....................................................... 7690
Water flow @ 20.0 F drop .................................... 4.20

MBH
CFM
CFM
gpm

Load occurs at .................................................... Des Htg


BTU/(hr-ft) .................................................................. 6.2
Ent. DB / Lvg DB ............................................. 66.3 / 71.3 F

Supply Fan Sizing Data


Actual max CFM ................................................... 7690 CFM
Standard CFM ...................................................... 7665 CFM
Actual max CFM/ft ............................................... 1.13 CFM/ft

Fan motor BHP .......................................................... 4.21 BHP


Fan motor kW ............................................................ 3.34 kW
Fan static ................................................................... 2.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM .............................................. 1592 CFM
CFM/ft .................................................................. 0.23 CFM/ft

Hourly Analysis Program v4.61

CFM/person ............................................................. 14.74 CFM/person

Page 16 of 30

Zone Sizing Summary for AHU-06


Project Name: PRIVATE SCHOOL @ ABU DHABI
Prepared by: Taiba Engineering Consultant

07/23/2014
09:01PM

Air System Information


Air System Name ............................................ AHU-06
Equipment Class ........................................... CW AHU
Air System Type ............................................... SZCAV

Number of zones ............................................................ 1


Floor Area .............................................................. 6792.0 ft
Location ................... Abu Dhabi, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone CFM ....................... Sum of space airflow rates
Space CFM ................... Individual peak space loads

Calculation Months ......................................... Jul to Aug


Sizing Data ..................................................... Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(MBH)
137.8

Design
Air
Flow
(CFM)
7690

Minimum
Air
Flow
(CFM)
7690

Time
of
Peak
Load
Jul 1600

Maximum
Heating
Load
(MBH)
20.4

Zone
Floor
Area
(ft)
6792.0

Zone
CFM/ft
1.13

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.
Space Loads and Airflows

Zone Name /
Space Name
Zone 1
FF-11-SEN ROOM
FF-12-MUSIC ROOM
FF-10-TEACHER ROOM-E24
FF-13-TRAINING NITCHIEN
FF-15-COMPUTER LAB
FF-16-ART ROOM
FF-29-MAIN CORRIDOR

Hourly Analysis Program v4.61

Mult.

Cooling
Sensible
(MBH)

Time
of
Load

Air
Flow
(CFM)

Heating
Load
(MBH)

Floor
Area
(ft)

Space
CFM/ft

1
1
1
1
1
1
1

10.9
28.2
7.9
31.5
25.6
17.2
19.5

Jul 1700
Jul 1700
Jul 1000
Jul 1700
Aug 1500
Aug 1400
Jul 1500

598
1539
431
1720
1397
942
1063

1.8
3.1
1.1
3.3
2.9
3.0
5.3

409.0
1022.6
215.3
667.4
742.7
742.7
2992.4

1.46
1.51
2.00
2.58
1.88
1.27
0.36

Page 17 of 30

Ventilation Sizing Summary for AHU-06


Project Name: PRIVATE SCHOOL @ ABU DHABI
Prepared by: Taiba Engineering Consultant

07/23/2014
09:01PM

1. Summary
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ................................................................. 1592 CFM

2. Space Ventilation Analysis Table

Zone Name / Space Name


Zone 1
FF-11-SEN ROOM
FF-12-MUSIC ROOM
FF-10-TEACHER ROOM-E24
FF-13-TRAINING NITCHIEN
FF-15-COMPUTER LAB
FF-16-ART ROOM
FF-29-MAIN CORRIDOR
Totals (incl. Space Multipliers)

Hourly Analysis Program v4.61

Mult.

Floor
Area
(ft)

Maximum
Occupants

1
1
1
1
1
1
1

409.0
1022.6
215.3
667.4
742.7
742.7
2992.4

4.0
30.0
4.0
20.0
22.0
16.0
12.0

Maximum
Required
Supply Air Outdoor Air
(CFM) (CFM/person)
597.6
1539.4
430.6
1720.0
1396.5
942.3
1063.0
7689.5

10.59
10.59
5.30
10.59
10.59
10.59
0.00

Required
Outdoor Air
(CFM/ft)
0.12
0.06
0.06
0.12
0.12
0.18
0.06

Required
Required
Outdoor Air Outdoor Air
(CFM) (% of supply)
0.0
0.0
0.0
0.0
0.0
0.0
0.0

0.0
0.0
0.0
0.0
0.0
0.0
0.0

Uncorrected
Outdoor Air
(CFM)
90.7
378.2
33.9
290.7
320.8
301.1
176.7
1592.1

Page 18 of 30

Air System Sizing Summary for AHU-07


Project Name: PRIVATE SCHOOL @ ABU DHABI
Prepared by: Taiba Engineering Consultant

07/23/2014
09:01PM

Air System Information


Air System Name ............................................ AHU-07
Equipment Class ........................................... CW AHU
Air System Type ............................................... SZCAV

Number of zones ............................................................ 1


Floor Area .............................................................. 4789.9 ft
Location ................... Abu Dhabi, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone CFM ....................... Sum of space airflow rates
Space CFM ................... Individual peak space loads

Calculation Months ......................................... Jul to Aug


Sizing Data ..................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ........................................................ 37.2
Total coil load ...................................................... 446.4
Sensible coil load ................................................ 303.0
Coil CFM at Jul 1600 ............................................ 9408
Max block CFM .................................................... 9408
Sum of peak zone CFM ....................................... 9408
Sensible heat ratio .............................................. 0.679
ft/Ton .................................................................. 128.8
BTU/(hr-ft) ............................................................ 93.2
Water flow @ 10.0 F rise ................................... 89.32

Tons
MBH
MBH
CFM
CFM
CFM

gpm

Load occurs at .................................................... Jul 1600


OA DB / WB ................................................... 114.4 / 84.9
Entering DB / WB ............................................ 85.6 / 69.7
Leaving DB / WB ............................................. 55.7 / 54.4
Coil ADP .................................................................... 52.3
Bypass Factor .......................................................... 0.100
Resulting RH ................................................................ 50
Design supply temp. .................................................. 58.0
Zone T-stat Check .................................................. 1 of 1
Max zone temperature deviation ................................. 0.0

F
F
F
F
%
F
OK
F

Central Heating Coil Sizing Data


Max coil load ......................................................... 45.5
Coil CFM at Des Htg ............................................ 9408
Max coil CFM ....................................................... 9408
Water flow @ 20.0 F drop .................................... 4.56

MBH
CFM
CFM
gpm

Load occurs at .................................................... Des Htg


BTU/(hr-ft) .................................................................. 9.5
Ent. DB / Lvg DB ............................................. 66.0 / 70.5 F

Supply Fan Sizing Data


Actual max CFM ................................................... 9408 CFM
Standard CFM ...................................................... 9378 CFM
Actual max CFM/ft ............................................... 1.96 CFM/ft

Fan motor BHP .......................................................... 5.15 BHP


Fan motor kW ............................................................ 4.09 kW
Fan static ................................................................... 2.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM .............................................. 2168 CFM
CFM/ft .................................................................. 0.45 CFM/ft

Hourly Analysis Program v4.61

CFM/person ............................................................... 9.90 CFM/person

Page 19 of 30

Zone Sizing Summary for AHU-07


Project Name: PRIVATE SCHOOL @ ABU DHABI
Prepared by: Taiba Engineering Consultant

07/23/2014
09:01PM

Air System Information


Air System Name ............................................ AHU-07
Equipment Class ........................................... CW AHU
Air System Type ............................................... SZCAV

Number of zones ............................................................ 1


Floor Area .............................................................. 4789.9 ft
Location ................... Abu Dhabi, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone CFM ....................... Sum of space airflow rates
Space CFM ................... Individual peak space loads

Calculation Months ......................................... Jul to Aug


Sizing Data ..................................................... Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(MBH)
170.2

Design
Air
Flow
(CFM)
9408

Minimum
Air
Flow
(CFM)
9408

Time
of
Peak
Load
Jul 1700

Maximum
Heating
Load
(MBH)
12.3

Zone
Floor
Area
(ft)
4789.9

Zone
CFM/ft
1.96

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.
Space Loads and Airflows

Zone Name /
Space Name
Zone 1
GF-19-CAFETERIA-01
GF-20-CAFETERIA-02
GF-16-TEACHER ROOM-02
GF-24-PRINCIPAL ROOM-01
GF-26-MEETING ROOM
GF-25-RECEPTION
GF-27-ACCO+VP+SEN+ESL
GF-47-ENTRANCE LOBBY-02

Hourly Analysis Program v4.61

Mult.

Cooling
Sensible
(MBH)

Time
of
Load

Air
Flow
(CFM)

Heating
Load
(MBH)

Floor
Area
(ft)

Space
CFM/ft

1
1
2
1
1
1
1
1

32.9
52.5
4.9
15.4
11.0
3.4
17.4
29.9

Aug 1800
Aug 1600
Aug 1400
Jul 1700
Jul 1700
Jul 1700
Jul 1700
Jul 1700

1798
2866
266
840
603
183
952
1633

0.8
2.7
0.5
1.7
0.7
0.2
2.1
3.0

968.8
968.8
290.6
398.3
322.9
53.8
796.5
699.7

1.86
2.96
0.92
2.11
1.87
3.41
1.20
2.33

Page 20 of 30

Ventilation Sizing Summary for AHU-07


Project Name: PRIVATE SCHOOL @ ABU DHABI
Prepared by: Taiba Engineering Consultant

07/23/2014
09:01PM

1. Summary
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ................................................................. 2168 CFM

2. Space Ventilation Analysis Table

Zone Name / Space Name


Zone 1
GF-19-CAFETERIA-01
GF-20-CAFETERIA-02
GF-16-TEACHER ROOM-02
GF-24-PRINCIPAL ROOM-01
GF-26-MEETING ROOM
GF-25-RECEPTION
GF-27-ACCO+VP+SEN+ESL
GF-47-ENTRANCE LOBBY-02
Totals (incl. Space Multipliers)

Hourly Analysis Program v4.61

Mult.

Floor
Area
(ft)

Maximum
Occupants

1
1
2
1
1
1
1
1

968.8
968.8
290.6
398.3
322.9
53.8
796.5
699.7

90.0
90.0
4.0
4.0
15.0
4.0
4.0
4.0

Maximum
Required
Supply Air Outdoor Air
(CFM) (CFM/person)
1798.3
2866.2
265.9
840.4
602.6
183.5
952.3
1632.7
9407.8

8.05
8.05
5.30
5.30
5.30
5.30
5.30
5.30

Required
Outdoor Air
(CFM/ft)
0.18
0.18
0.06
0.06
0.06
0.06
0.06
0.06

Required
Required
Outdoor Air Outdoor Air
(CFM) (% of supply)
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0

0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0

Uncorrected
Outdoor Air
(CFM)
896.3
896.3
38.4
44.7
98.5
24.4
68.2
62.5
2167.6

Page 21 of 30

Air System Sizing Summary for AHU-08


Project Name: PRIVATE SCHOOL @ ABU DHABI
Prepared by: Taiba Engineering Consultant

07/23/2014
09:01PM

Air System Information


Air System Name ............................................ AHU-08
Equipment Class ........................................... CW AHU
Air System Type ............................................... SZCAV

Number of zones ............................................................ 1


Floor Area .............................................................. 4562.8 ft
Location ................... Abu Dhabi, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone CFM ....................... Sum of space airflow rates
Space CFM ................... Individual peak space loads

Calculation Months ......................................... Jul to Aug


Sizing Data ..................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ........................................................ 27.2
Total coil load ...................................................... 326.2
Sensible coil load ................................................ 237.2
Coil CFM at Aug 1500 .......................................... 7202
Max block CFM .................................................... 7202
Sum of peak zone CFM ....................................... 7202
Sensible heat ratio .............................................. 0.727
ft/Ton .................................................................. 167.8
BTU/(hr-ft) ............................................................ 71.5
Water flow @ 10.0 F rise ................................... 65.28

Tons
MBH
MBH
CFM
CFM
CFM

gpm

Load occurs at .................................................. Aug 1500


OA DB / WB ................................................... 115.0 / 85.0
Entering DB / WB ............................................ 86.3 / 69.0
Leaving DB / WB ............................................. 55.8 / 54.3
Coil ADP .................................................................... 52.4
Bypass Factor .......................................................... 0.100
Resulting RH ................................................................ 47
Design supply temp. .................................................. 58.0
Zone T-stat Check .................................................. 1 of 1
Max zone temperature deviation ................................. 0.0

F
F
F
F
%
F
OK
F

Central Heating Coil Sizing Data


Max coil load ......................................................... 39.9
Coil CFM at Des Htg ............................................ 7202
Max coil CFM ....................................................... 7202
Water flow @ 20.0 F drop .................................... 3.99

MBH
CFM
CFM
gpm

Load occurs at .................................................... Des Htg


BTU/(hr-ft) .................................................................. 8.7
Ent. DB / Lvg DB ............................................. 66.3 / 71.4 F

Supply Fan Sizing Data


Actual max CFM ................................................... 7202 CFM
Standard CFM ...................................................... 7179 CFM
Actual max CFM/ft ............................................... 1.58 CFM/ft

Fan motor BHP .......................................................... 3.94 BHP


Fan motor kW ............................................................ 3.13 kW
Fan static ................................................................... 2.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM .............................................. 1524 CFM
CFM/ft .................................................................. 0.33 CFM/ft

Hourly Analysis Program v4.61

CFM/person ............................................................. 20.05 CFM/person

Page 22 of 30

Zone Sizing Summary for AHU-08


Project Name: PRIVATE SCHOOL @ ABU DHABI
Prepared by: Taiba Engineering Consultant

07/23/2014
09:01PM

Air System Information


Air System Name ............................................ AHU-08
Equipment Class ........................................... CW AHU
Air System Type ............................................... SZCAV

Number of zones ............................................................ 1


Floor Area .............................................................. 4562.8 ft
Location ................... Abu Dhabi, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone CFM ....................... Sum of space airflow rates
Space CFM ................... Individual peak space loads

Calculation Months ......................................... Jul to Aug


Sizing Data ..................................................... Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(MBH)
128.0

Design
Air
Flow
(CFM)
7202

Minimum
Air
Flow
(CFM)
7202

Time
of
Peak
Load
Jul 1600

Maximum
Heating
Load
(MBH)
17.6

Zone
Floor
Area
(ft)
4562.8

Zone
CFM/ft
1.58

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.
Space Loads and Airflows

Zone Name /
Space Name
Zone 1
FF-17-SCIENTIFIC LAB-L9
FF-18-SCIENTIFIC LAB L12
FF-20-CLASS ROOM-08
FF-14-LIBRARY
FF-19-TEACHER ROOM-L5

Hourly Analysis Program v4.61

Mult.

Cooling
Sensible
(MBH)

Time
of
Load

Air
Flow
(CFM)

Heating
Load
(MBH)

Floor
Area
(ft)

Space
CFM/ft

1
1
1
1
1

16.3
35.8
22.7
49.1
7.9

Aug 1400
Aug 1600
Jul 1000
Jul 1700
Jul 1700

888
1955
1242
2684
433

2.5
3.9
2.0
8.1
1.1

742.7
742.7
601.7
2260.4
215.3

1.20
2.63
2.06
1.19
2.01

Page 23 of 30

Ventilation Sizing Summary for AHU-08


Project Name: PRIVATE SCHOOL @ ABU DHABI
Prepared by: Taiba Engineering Consultant

07/23/2014
09:01PM

1. Summary
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ................................................................. 1524 CFM

2. Space Ventilation Analysis Table

Zone Name / Space Name


Zone 1
FF-17-SCIENTIFIC LAB-L9
FF-18-SCIENTIFIC LAB L12
FF-20-CLASS ROOM-08
FF-14-LIBRARY
FF-19-TEACHER ROOM-L5
Totals (incl. Space Multipliers)

Hourly Analysis Program v4.61

Mult.

Floor
Area
(ft)

Maximum
Occupants

1
1
1
1
1

742.7
742.7
601.7
2260.4
215.3

16.0
16.0
20.0
20.0
4.0

Maximum
Required
Supply Air Outdoor Air
(CFM) (CFM/person)
888.2
1954.9
1242.1
2683.9
432.5
7201.7

10.59
10.00
10.59
10.59
5.30

Required
Outdoor Air
(CFM/ft)
0.18
0.18
0.12
0.18
0.06

Required
Required
Outdoor Air Outdoor Air
(CFM) (% of supply)
0.0
0.0
0.0
0.0
0.0

0.0
0.0
0.0
0.0
0.0

Uncorrected
Outdoor Air
(CFM)
301.1
293.7
283.0
612.4
33.9
1524.0

Page 24 of 30

Air System Sizing Summary for AHU-09


Project Name: PRIVATE SCHOOL @ ABU DHABI
Prepared by: Taiba Engineering Consultant

07/23/2014
09:01PM

Air System Information


Air System Name ............................................ AHU-09
Equipment Class ........................................... CW AHU
Air System Type ............................................... SZCAV

Number of zones ............................................................ 1


Floor Area .............................................................. 4456.3 ft
Location ................... Abu Dhabi, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone CFM ....................... Sum of space airflow rates
Space CFM ................... Individual peak space loads

Calculation Months ......................................... Jul to Aug


Sizing Data ..................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ........................................................ 29.7
Total coil load ...................................................... 356.0
Sensible coil load ................................................ 248.5
Coil CFM at Aug 1600 .......................................... 7857
Max block CFM .................................................... 7857
Sum of peak zone CFM ....................................... 7857
Sensible heat ratio .............................................. 0.698
ft/Ton .................................................................. 150.2
BTU/(hr-ft) ............................................................ 79.9
Water flow @ 10.0 F rise ................................... 71.24

Tons
MBH
MBH
CFM
CFM
CFM

gpm

Load occurs at .................................................. Aug 1600


OA DB / WB ................................................... 114.4 / 84.9
Entering DB / WB ............................................ 85.2 / 69.2
Leaving DB / WB ............................................. 55.8 / 54.5
Coil ADP .................................................................... 52.5
Bypass Factor .......................................................... 0.100
Resulting RH ................................................................ 49
Design supply temp. .................................................. 58.0
Zone T-stat Check .................................................. 1 of 1
Max zone temperature deviation ................................. 0.0

F
F
F
F
%
F
OK
F

Central Heating Coil Sizing Data


Max coil load ......................................................... 33.8
Coil CFM at Des Htg ............................................ 7857
Max coil CFM ....................................................... 7857
Water flow @ 20.0 F drop .................................... 3.39

MBH
CFM
CFM
gpm

Load occurs at .................................................... Des Htg


BTU/(hr-ft) .................................................................. 7.6
Ent. DB / Lvg DB ............................................. 66.2 / 70.2 F

Supply Fan Sizing Data


Actual max CFM ................................................... 7857 CFM
Standard CFM ...................................................... 7832 CFM
Actual max CFM/ft ............................................... 1.76 CFM/ft

Fan motor BHP .......................................................... 4.30 BHP


Fan motor kW ............................................................ 3.41 kW
Fan static ................................................................... 2.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM .............................................. 1748 CFM
CFM/ft .................................................................. 0.39 CFM/ft

Hourly Analysis Program v4.61

CFM/person ............................................................. 13.87 CFM/person

Page 25 of 30

Zone Sizing Summary for AHU-09


Project Name: PRIVATE SCHOOL @ ABU DHABI
Prepared by: Taiba Engineering Consultant

07/23/2014
09:01PM

Air System Information


Air System Name ............................................ AHU-09
Equipment Class ........................................... CW AHU
Air System Type ............................................... SZCAV

Number of zones ............................................................ 1


Floor Area .............................................................. 4456.3 ft
Location ................... Abu Dhabi, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone CFM ....................... Sum of space airflow rates
Space CFM ................... Individual peak space loads

Calculation Months ......................................... Jul to Aug


Sizing Data ..................................................... Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(MBH)
136.1

Design
Air
Flow
(CFM)
7857

Minimum
Air
Flow
(CFM)
7857

Time
of
Peak
Load
Jul 1700

Maximum
Heating
Load
(MBH)
7.7

Zone
Floor
Area
(ft)
4456.3

Zone
CFM/ft
1.76

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.
Space Loads and Airflows

Zone Name /
Space Name
Zone 1
GF-07-CLASS ROOM-07
GF-08-CLASS ROOM-08
GF-09-CLASS ROOM-09
GF-10-CLASS ROOM-10
GF-11-CLASS ROOM-11
GF-12-CLASS ROOM-12
GF-14-CORRIDOR-02

Hourly Analysis Program v4.61

Mult.

Cooling
Sensible
(MBH)

Time
of
Load

Air
Flow
(CFM)

Heating
Load
(MBH)

Floor
Area
(ft)

Space
CFM/ft

1
1
1
1
1
1
1

21.6
21.6
21.9
25.3
24.7
25.0
3.7

Jul 0900
Jul 0900
Jul 1000
Jul 1700
Jul 1700
Jul 1700
Jul 1800

1180
1180
1198
1383
1350
1366
200

1.2
1.2
1.4
1.5
1.2
1.3
0.0

601.7
601.7
601.7
601.7
601.7
601.7
846.0

1.96
1.96
1.99
2.30
2.24
2.27
0.24

Page 26 of 30

Ventilation Sizing Summary for AHU-09


Project Name: PRIVATE SCHOOL @ ABU DHABI
Prepared by: Taiba Engineering Consultant

07/23/2014
09:01PM

1. Summary
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ................................................................. 1748 CFM

2. Space Ventilation Analysis Table

Zone Name / Space Name


Zone 1
GF-07-CLASS ROOM-07
GF-08-CLASS ROOM-08
GF-09-CLASS ROOM-09
GF-10-CLASS ROOM-10
GF-11-CLASS ROOM-11
GF-12-CLASS ROOM-12
GF-14-CORRIDOR-02
Totals (incl. Space Multipliers)

Hourly Analysis Program v4.61

Mult.

Floor
Area
(ft)

Maximum
Occupants

1
1
1
1
1
1
1

601.7
601.7
601.7
601.7
601.7
601.7
846.0

20.0
20.0
20.0
20.0
20.0
20.0
6.0

Maximum
Required
Supply Air Outdoor Air
(CFM) (CFM/person)
1179.8
1179.8
1197.6
1383.1
1349.8
1366.2
200.4
7856.7

10.59
10.59
10.59
10.59
10.59
10.59
0.00

Required
Outdoor Air
(CFM/ft)
0.12
0.12
0.12
0.12
0.12
0.12
0.06

Required
Required
Outdoor Air Outdoor Air
(CFM) (% of supply)
0.0
0.0
0.0
0.0
0.0
0.0
0.0

0.0
0.0
0.0
0.0
0.0
0.0
0.0

Uncorrected
Outdoor Air
(CFM)
283.0
283.0
283.0
283.0
283.0
283.0
50.0
1747.7

Page 27 of 30

Air System Sizing Summary for AHU-10


Project Name: PRIVATE SCHOOL @ ABU DHABI
Prepared by: Taiba Engineering Consultant

07/23/2014
09:01PM

Air System Information


Air System Name ............................................ AHU-10
Equipment Class ........................................... CW AHU
Air System Type ............................................... SZCAV

Number of zones ............................................................ 1


Floor Area .............................................................. 5554.2 ft
Location ................... Abu Dhabi, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone CFM ....................... Sum of space airflow rates
Space CFM ................... Individual peak space loads

Calculation Months ......................................... Jul to Aug


Sizing Data ..................................................... Calculated

Central Cooling Coil Sizing Data


Total coil load ........................................................ 39.5
Total coil load ...................................................... 473.6
Sensible coil load ................................................ 332.4
Coil CFM at Jul 1600 .......................................... 10188
Max block CFM .................................................. 10188
Sum of peak zone CFM ..................................... 10188
Sensible heat ratio .............................................. 0.702
ft/Ton .................................................................. 140.7
BTU/(hr-ft) ............................................................ 85.3
Water flow @ 10.0 F rise ................................... 94.76

Tons
MBH
MBH
CFM
CFM
CFM

gpm

Load occurs at .................................................... Jul 1600


OA DB / WB ................................................... 114.4 / 84.9
Entering DB / WB ............................................ 86.2 / 69.5
Leaving DB / WB ............................................. 55.9 / 54.5
Coil ADP .................................................................... 52.6
Bypass Factor .......................................................... 0.100
Resulting RH ................................................................ 49
Design supply temp. .................................................. 58.0
Zone T-stat Check .................................................. 1 of 1
Max zone temperature deviation ................................. 0.0

F
F
F
F
%
F
OK
F

Central Heating Coil Sizing Data


Max coil load ......................................................... 45.4
Coil CFM at Des Htg .......................................... 10188
Max coil CFM ..................................................... 10188
Water flow @ 20.0 F drop .................................... 4.54

MBH
CFM
CFM
gpm

Load occurs at .................................................... Des Htg


BTU/(hr-ft) .................................................................. 8.2
Ent. DB / Lvg DB ............................................. 65.9 / 70.1 F

Supply Fan Sizing Data


Actual max CFM ................................................. 10188 CFM
Standard CFM .................................................... 10155 CFM
Actual max CFM/ft ............................................... 1.83 CFM/ft

Fan motor BHP .......................................................... 5.58 BHP


Fan motor kW ............................................................ 4.43 kW
Fan static ................................................................... 2.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM .............................................. 2245 CFM
CFM/ft .................................................................. 0.40 CFM/ft

Hourly Analysis Program v4.61

CFM/person ............................................................. 12.41 CFM/person

Page 28 of 30

Zone Sizing Summary for AHU-10


Project Name: PRIVATE SCHOOL @ ABU DHABI
Prepared by: Taiba Engineering Consultant

Air System Information


Air System Name ............................................ AHU-10
Equipment Class ........................................... CW AHU
Air System Type ............................................... SZCAV

Number of zones ............................................................ 1


Floor Area .............................................................. 5554.2 ft
Location ................... Abu Dhabi, United Arab Emirates

Sizing Calculation Information


Zone and Space Sizing Method:
Zone CFM ....................... Sum of space airflow rates
Space CFM ................... Individual peak space loads

Calculation Months ......................................... Jul to Aug


Sizing Data ..................................................... Calculated

Zone Sizing Data

Zone Name
Zone 1

Maximum
Cooling
Sensible
(MBH)
177.0

Design
Air
Flow
(CFM)
10188

Minimum
Air
Flow
(CFM)
10188

Time
of
Peak
Load
Jul 1600

Maximum
Heating
Load
(MBH)
15.2

Zone
Floor
Area
(ft)
5554.2

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.
Space Loads and Airflows

Zone Name /
Space Name
Zone 1
FF-20-CLASS ROOM-08
FF-21-CLASS ROOM-09
FF-22-CLASS ROOM-10
FF-23-CLASS ROOM-11
FF-24-CLASS ROOM-12
FF-25-CLASS ROOM-13
FF-26-CLASS ROOM-14
FF-27-CORRIDOR-02
FF-28-PRAY ROOM-02

Hourly Analysis Program v4.61

Mult.

Cooling
Sensible
(MBH)

Time
of
Load

Air
Flow
(CFM)

Heating
Load
(MBH)

Floor
Area
(ft)

Space
CFM/ft

1
1
1
1
1
1
1
1
1

22.7
22.3
22.3
22.6
25.3
25.3
25.3
6.5
14.2

Jul 1000
Jul 1000
Jul 1000
Jul 1000
Jul 1700
Jul 1700
Jul 1700
Jul 1500
Jul 1500

1242
1217
1217
1233
1384
1384
1384
353
774

2.0
1.7
1.7
1.9
1.7
1.7
1.7
1.5
1.3

601.7
601.7
601.7
601.7
601.7
601.7
601.7
1019.3
322.9

2.06
2.02
2.02
2.05
2.30
2.30
2.30
0.35
2.40

Zone
CFM/ft
1.83

Ventilation Sizing Summary for AHU-10


Project Name: PRIVATE SCHOOL @ ABU DHABI
Prepared by: Taiba Engineering Consultant

07/23/2014
09:01PM

1. Summary
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Design Ventilation Airflow Rate ................................................................. 2245 CFM

2. Space Ventilation Analysis Table

Zone Name / Space Name


Zone 1
FF-20-CLASS ROOM-08
FF-21-CLASS ROOM-09
FF-22-CLASS ROOM-10
FF-23-CLASS ROOM-11
FF-24-CLASS ROOM-12
FF-25-CLASS ROOM-13
FF-26-CLASS ROOM-14
FF-27-CORRIDOR-02
FF-28-PRAY ROOM-02
Totals (incl. Space Multipliers)

Hourly Analysis Program v4.61

Mult.

Floor
Area
(ft)

Maximum
Occupants

1
1
1
1
1
1
1
1
1

601.7
601.7
601.7
601.7
601.7
601.7
601.7
1019.3
322.9

20.0
20.0
20.0
20.0
20.0
20.0
20.0
6.0
35.0

Maximum
Required
Supply Air Outdoor Air
(CFM) (CFM/person)
1242.1
1216.5
1216.5
1233.0
1384.3
1384.3
1384.3
353.0
773.8
10187.8

10.59
10.59
10.59
10.59
10.59
10.59
10.59
0.00
5.30

Required
Outdoor Air
(CFM/ft)
0.12
0.12
0.12
0.12
0.12
0.12
0.12
0.06
0.06

Required
Required
Outdoor Air Outdoor Air
(CFM) (% of supply)
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0

0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0

Page 30 of 30

Uncorrected
Outdoor Air
(CFM)
283.0
283.0
283.0
283.0
283.0
283.0
283.0
60.2
204.5
2245.4