Engineers who are tasked with designing heating, ventilation and air-conditioning (HVAC) systems for buildings will need to assess the indoor air quality to
ensure optimum health and comfort for occupants and meet minimum regulatory requirements. Generally a HVAC CFD analysis will take into account
variables such as air temperature, relative humidity, air species concentrations and velocity. Additionally, CFD engineers can use ANSYS CFD to solve for
the local mean age of air (MAA) to assess the air quality within an indoor environment. By examining MAA across the habitable space within a building,
engineers can quantify the air change effectiveness (ACE) of their ventilation system and confirm that their design meets NABERS/GreenStar regulations.
How can I plot the Mean Age of Air in ANSYS CFD-Post?
Usually designers are interested in local distributions, therefore it is useful to plot the ACE as the ratio between the nominal time constant and the age of air or
its inverse. Within ANSYS CFD-Post, it is possible to calculate the ACE at a specified height with a simple expression defined using CEL.
This allows us to quantify the area occupied by air with an age exceeding the mean value across a reference surface (typically located at breathing height, ie.
1m above floor). According to many regulatory standards, the area exceeding the target value must be less than 5%.
The setup for the Normalised Age of Air variable (expressed as Age of Air/Nominal Time Constant).
Note that when solving using FLUENT, a variable called Scalar 0 will be present in the variable list. Its dimensions can be displayed by defining a new
expression such as
AgeofAir = Scalar 0 [s] and then creating a new variable which by definition is equal to AgeofAir.
Clipping the Age of Air to a specific range of values
This is useful to quantify the size of any pockets of air that may exceed our target MAA value (ie. the value prescribed by regulations). In order to visualize the
air which is older than this nominal value, we create an iso-clip for a value greater than the target value, applied to a plane located at a specified height above
the floor (typically 1 metre).
The result should look similar to the one shown in the image below. The holes are regions where the MAA values are above or below the threshold specified
in your iso-clip setup (in this case, anything below 1200 secs and above 1300 secs).
Ad by MinimumPrice | Close This Ad
Home Home Feat ur ed Feat ur ed Tips & Tricks: Calculating the Mean Age of Air for HVAC simulations in ANSYS CFD Tips & Tricks: Calculating the Mean Age of Air for HVAC simulations in ANSYS CFD
Search for:
Subscribe to Blog via Email
emailaddress
Leading Engineering Application Providers
Australia: 1300 88 22 40
New Zealand: 09 9777 444
Visit LEAP Website for more information on
CFD, FEA, CAD, CAM and related software
products, plus our training and webinar
schedule.
Foll ow Fol low
Recent Popular Popular Random Random
Ti ps & Tr i ck s:
Cal c ul at i ng t he
Mean Age of Ai r
f or HVAC
si mul at i ons i n
ANSYS CFD
Apr 22, 2014
Guest Post :
ANSYS CFD
hel ps Sunsw i f t
t ack l e t he
Wor l d Sol ar
Chal l enge
Apr 2, 2014
Sol vi ng
Conj ugat e Heat
Tr ansf er
pr obl ems
Mar 25, 2014
Recent Comments Recent Comments
Ti ps & Tr i ck s: Cal c ul at i ng t he Mean Age of Ai r f or HVAC si mul at i ons i n ANSYS CFD
Computational Fluid Dynamics (CFD) Blog - LEAP Australia & New... http://www.computationalfluiddynamics.com.au/tips-tricks-calculatin...
1 of 5 27-06-2014 09:12
Adding an additional variable in CFX-Pre
An iso-clip for the Age of Air Variable.

It is then straightforward to create an expression that quantifies the % area of the iso-clip to the full area of the plane. Typically engineers aim to ensure that
this does not exceed 5% (according to the ACE 0.95 criteria). In this example the CEL expression would be written as:
Ratio = area()@Iso Clip 1/area()@Plane 3
How to clip the Age of Air Variable to the desired values
How do I calculate mean age of air in my ANSYS CFD simulation?
The mean age of air (MAA) is not automatically included as a predefined variable in general purpose CFD software, such as ANSYS CFX and ANSYS Fluent.
It can be defined in the pre-processing stage as an additional variable using the methods outlined below. This section provides some background and further
details on how to include the MAA variable in both ANSYS CFX and ANSYS Fluent.
Some background
The mean age of air, denoted , is obtained by solving the following advection equation:
The derivative with respect of time of the source is 1 so that the integral itself is time. When integrated, the age scalar will equal the residence time.
In ANSYS CFD solvers, scalar quantities are multiplied by the density in the transport equations, so that is in this particular case the equation to use is:
The term on the right hand side of the equation is known as the source term, and it has to be taken into account when implementing the mean age of air
variable in the simulation.

According to the ACE 0.95 criteria for modern building regulations, for instance, the displacement air within the enclosed environment has to provide an air
change effectiveness (ACE) higher than 0.95 for at least 95 % of the net lettable area (NLA) when measured in accordance with ASHRAE 129-1997.
Air change effectiveness is defined as the ratio between the nominal time constant and the average of the age of air at a reference height
The nominal time constant is the ratio between the air volume of a space or building divided by the rate of outdoor air supply, which is the incoming volumetric
flow rate. Mean residence time
The reference surface is taken at 1 [m] above the floor to consider the breathing zone of the enclosed space.
ACE gives a measure of the distribution of air at the breathing height and a value close to unity indicates that the air distribution within the zone has reached
perfect mixing. According to the GBCAs Green Star requirements of IEQ-2 version 2, a well designed ceiling air diffusion system will achieve an ACE of near
unity (between 0.8 and 1.2) at design air flow rates. A displacement ventilation system typically achieves an ACE of greater than 1.2.
How to define the variable Age of Air in ANSYS CFX:
To calculate the age of air, it is necessary to create a new variable under the Expression, Functions and Variables tree in CFX-Pre. In this example the new
variable has been named Age of Air . It has units of seconds.








LEAP CFD Team on How does the
Reynolds Number affect my CFD model?
LEAP CFD Team on Tips & Tricks:
Estimating the First Cell Height for
correct Y+
LEAP CFD Team on Turbulence Part 4
Reviewing how well you have resolved
the Boundary Layer
LEAP CFD Team on Tips & Tricks:
Turbulence Part 2 Wall Functions and
Y+ requirements
LEAP CFD Team on Tips & Tricks:
Convergence and Mesh Independence
Study
2012 CSIRO CFD Conference acoustics
aerodynamics aerospace and
defence America's Cup ANSYS
ANSYS CFD
ANSYS Meshing Australian
International Airshow Awarded
Design CFD CFD
meshing methods CFD
modelling of
turbulent flows CFD
simulation
accuracy combustion common
misconceptions consumer products Convergence
design and testing design
optimisation Electromagnetics
eulerian modelling expert training
Face Sizing fluid-structure interaction formula
1 CFD granular flow HPC Inflation
Layer Meshing
innovation lagrangian particle
tracking Mesh Control settings mesh
independence minerals and
process industries
multiphase flow Multiphysics
simulation Navier Stokes parametric design
prediction of
aerodynamic flows
Shear-Stress Transport (SST)
turbulence model sports
engineering transition
modelling turbulence
modelling unsteady flow
models wall functions
Tags Tags
Computational Fluid Dynamics (CFD) Blog - LEAP Australia & New... http://www.computationalfluiddynamics.com.au/tips-tricks-calculatin...
2 of 5 27-06-2014 09:12
the setup for the creation of the Age of Air Variable
The setup of the Age of Air Variable in the Fluid
Models tab
Once created the sub domain is displayed in the Default
Domain tree
The setup for the source in the sub domain
Defining a User-Defined Scalar (UDS)


CFX solves a transport equation for the newly created variable . This is shown in the Fluid
Models tab of the default domain, under the Additional Variable Models. As the age of air does
not diffuse, it is not necessary to define a Kinematic Diffusivity for it. Note, that in ANSYS
CFX, turbulent diffusion is included by default.












As the transport equation is of type specific, it is necessary to add a source term equal to the fluid density. This is done by creating a sub domain (here
named AoA), under the Default Domain and defining the Source to be density as below.



















The last step in ANSYS CFX is to set a value for Age of Air at any boundary conditions where air can enter the domain. In this example, the Age of Air at the
diffuser and at the exhaust (for any return flow) has been set to 0 [s]. It is also possible to specify non-zero values if recycled air is used.
How to define the variable Age of Air in ANSYS Fluent
In the previous section weve described the method to include an additional variable (in the form of a transport equation) for calculating the age of air in
ANSYS CFX. Similarly, in ANSYS FLUENT we can calculate the age of air through use of a user defined scalar (UDS). This involves creates a user defined
scalar for the age of air then solving its equation after a solution for the flowfield has been obtained.









The following UDF computes the diffusivity to account for turbulent diffusion (which is not implicitly defined as in CFX) and the source for the mean age of air.
This function can be executed as an interpreted or compiled UDF.
#*******************************************************************
#include udf.h
#include prop.h
Computational Fluid Dynamics (CFD) Blog - LEAP Australia & New... http://www.computationalfluiddynamics.com.au/tips-tricks-calculatin...
3 of 5 27-06-2014 09:12
Definition of the UDS Diffusivity in the material dialog box
The setup of the source term for the UDS
Definition of the UDS at the boundaries
The User Scalar 0 in the Solution Controls panel . By
selecting it the solver will calculate a solution only for the
UDS.
#This define the AoA diffusivity
DEFINE_DIFFUSIVITY(mean_age_diff, c, t, i)
{
return C_MU_EFF(c,t)/0.7
}
#This defines the source
DEFINE_SOURCE(mean_age_source, c, t, dS, eqn)
{
real source;
source = C_R(c,t);
dS[eqn]=0;
return source;
}
#********************************************************************
After the UDF is interpreted or compiled, the name specified in the DEFI NE macro argument (e.g., mean_age_diff) will become visible and selectable in the
Create/Edit Materials dialog box in ANSYS FLUENT
The next step is to define the scalar in the volume of fluid representing the solution domain, as
shown in the Figure below.










Finally it is necessary to set a boundary condition for the scalar at all inlets and outlets. In this example uds-0 scalar values = 0 at the inlet (but, as in CFX,
can be set at a non-zero value if desired). The setup for the new variable for mean age of air in FLUENT is now complete.

















This post has aimed to provide an overview of the age of air parameter in CFD, and some tips on how to create and post-process the results for mean age of
air in ANSYS CFD. CFD simulations of this type are increasingly being performed by building designers and engineers to both meet stringent building codes
and help differentiate the sustainability and liveability aspects of their design. To this effect, ANSYS CFD provides engineers with a valuable tool to assess
the levels of thermal comfort for building occupants, by examining parameters such as the air temperature and radiant heat loads, as well as a tool to ensure
adequate air change effectiveness by solving and assessing the mean age of air. For further information or to discuss your own CFD problem within HVAC
industry, please leave a comment below.
Share this post
Aut hor : LEAP CFD Team
Computational Fluid Dynamics (CFD) Blog - LEAP Australia & New... http://www.computationalfluiddynamics.com.au/tips-tricks-calculatin...
4 of 5 27-06-2014 09:12
UA-33602782-1
Cat egor i es Subsc r i be t o Bl og vi a
Emai l
emailaddress
Rec ent Post s Cont ac t Us
LEAP Australia Pty Ltd
Leading Engineering Application Providers
ENQUIRIES:
Australia: 1300 88 22 40
New Zealand: 09 9777 444
Visit LEAP Website for more information on
CFD, FEA, CAD, CAM and related products,
plus our engineering software training and
webinar schedule.
2014 All rights reserved
Privacy & Terms
SubmitComment
Ad by MinimumPrice | Close This Ad
Submit a Comment
Your email address will not be published. Required fields are marked *
Name*
Email*
Website
Comment
You may use these HTML tags and attributes: <a hr ef =" " t i t l e="" > <abbr t i t l e=" "> <acr onymt i t l e="" > <b> <bl ockquot e ci t e="" >
<ci t e> <code> <del dat et i me=" "> <em> <i > <q ci t e="" > <st r i ke> <st r ong>
Business Benefits
Featured
Industry Focus
Technical Benefits
Tips & Tricks
Tips & Tricks: Calculating the Mean Age
of Air for HVAC simulations in ANSYS
CFD
Guest Post: ANSYS CFD helps Sunswift
tackle the World Solar Challenge
Solving Conjugate Heat Transfer
problems
New & Improved: The 2014 FIA Formula
One Series
Guest Post: Optimising FSAE
Aerodynamics at Monash Motorsport
Computational Fluid Dynamics (CFD) Blog - LEAP Australia & New... http://www.computationalfluiddynamics.com.au/tips-tricks-calculatin...
5 of 5 27-06-2014 09:12

Das könnte Ihnen auch gefallen