Controls
HARDWARE
Cable
COMSAB II
Fax +45 86 28 71 44
FUNCTION
Key the values you wish to read/write in the connected compressors into DB100. The
compressors must be keyed in in succession 1-2-3-4-5 etc. and there must not be any
gaps (see the section EXAMPLE OF KEYING IN IN DB100).
Each compressor has its own DB (DB70 DB83), where the numbers of the values you
wish to read/write are keyed in (in HEX format, see INSTRUCTION MANUAL COMSAB
II). Furthermore the values you wish to transfer to the compressors must be keyed in.
The following restrictions must be noticed: Maximum 14 compressors
Maximum 29 reading points
per compressor
Maximum 10 writing points
per compressor
3.
Reading in UNISAB
DWB2, point no. for what to read (HEX-figures from the table POINTS TO READ IN
THE COMSAB manual).
DWB58, do.
1
/VAR/WWW/APPS/CONVERSION/TMP/SCRATCH_6/239579978.DOC
Giro 6 47 75 34
Reg no. 152213
VAT no. DK10301491
DBW100, reply from COMSAB (decimal figures, according to table in the COMSAB
manual most of the values are in 1/10).
DBW156, do.
Sabroe
Controls
In a few words this means that all replies to DBW2 are returned as replies from
COMSAB in DBW100. Questions in DBW4 are returned as replies from COMSAB in
DBW102 etc.
Writing in UNISAB
DBW200, point no. for what to write to (HEX figures from the table POINTS TO READ
IN THE COMSAB manual).
DBW218, do.
Denmark
Phone +45 86 28 79 11
Fax +45 86 28 71 44
Sabroe Controls A/S
Gl. Kge Landevej 119
DK-2500 Valby
Denmark
DBW300, value for COMSAB (decimal figures, according to table in the COMSAB
manual most of the values are in 1/10).
DBW318, do.
Phone +45 36 45 00 42
Fax + 45 36 45 00 54
E-mail sc@sabroe-controls.com
Giro 6 47 75 34
Reg no. 152213
VAT no. DK10301491
In a few words this means that the point number you wish to write to must be keyed in in
DBW200 and the points nskevrdi (desired/wanted value) is keyed in in DBW300,
DBW202 belongs to DBW302 etc.
4.
DBW2 :
DBW62 :
DBW4
DBW64 :
Etc.
DBW2 DBW28 is reading pointer amount for compressor 1 14
DBW62 DBW88 is writing point amount for compressor 1 14
If a compressor has not been connected to the system you only need to key in 0 (zero)
in the DBW belonging to this one.
4.1
Sabroe
Controls
Sabroe Controls A/S
Wants to read:
Denmark
1.
oil temperature (hex 22, equivalent to point no. 34 from the table of reading
points).
Phone +45 86 28 79 11
2.
suction temperature (hex 20, equivalent to point no. 32 from the table of
reading points).
Fax +45 86 28 71 44
For COMSAB
DB76 for compressor 7:
Denmark
Phone +45 36 45 00 42
Fax + 45 36 45 00 54
5.2
E-mail sc@sabroe-controls.com
Giro 6 47 75 34
Reg no. 152213
VAT no. DK10301491
Wants to write:
1. suction pressure set point no. 1 (hex 2F, equivalent to point no. 47 from the table of
writing points).
2. suction pressure set point no. 2 (hex 30, equivalent to point no. 48 from the table of
writing points).
For COMSAB
DB72 for compressor 3:
The values from DBW300 and DBW302 are transferred to compressor 3 through the
COMSAB.