CGL W.O.T09935, Rev.1, Dt.05.05.

11
Prepared by:SS, Approved by:AVD
Page no. 1 of 12
TECHNICAL DATA SHEET OF AUTOTRANSFORMER
CUSTOMER : TECHNO ELECTRIC
RATING : 315 MVA, 400/220/33 kV, AUTO TRANSFORMER
1.0 Transformer application / designation Auto Transformer
2.0 Applicable standards IS 2026
3.0 Quantity required 4 nos
4.0 Full load rating MVA 315
5.0 3 Phase unit / bank of three (3) 1 phase units 3phase unit
6.0
Auto wound / two winding transformers / three
winding transformers
Auto Wound
7.0 Rated no-load voltages :
7.1 HV kV 400
7.2 IV kV 220
7.3 LV kV 33
8.0
Cooling (ONAN / ONAF / OFAN / OFAF /
OFWF)
ONAN/ONAF/OFAF

9.0 Ratings 189/252/315MVA
9.1 Ratings of windings
9.1.1 HV MVA 315MVA
9.1.2 IV MVA 315MVA
9.1.3 LV MVA 105MVA
9.2 Ratings corresponding to cooling methods
9.2.1 ONAN MVA 189
9.2.2 ONAF MVA 252
9.2.3 OFAF MVA 315

10.0
Guaranteed impedance voltage at rated current
for the principal tapping (indicate tolerance) at
315 MVA

10.1 HV LV % 60%(+15% Tol)
10.2 HV IV %
12.5%(+/-10% Tol) at principal
tap
10.3%(+/-15% Tol) at max. tap
15.4%(+/-15% Tol) at min. tap
10.3 IV LV % 45%(+15% Tol)

CGL W.O.T09935, Rev.1, Dt.05.05.11
Prepared by:SS, Approved by:AVD
Page no. 2 of 12
TECHNICAL DATA SHEET OF AUTOTRANSFORMER
CUSTOMER : TECHNO ELECTRIC
RATING : 315 MVA, 400/220/33 kV, AUTO TRANSFORMER
10.4
Zero Sequence impedance at principle tap
between HV & IV
%
0.9-1.0 times of Positive seq.
impedance

11.0 Efficiency at 75
0
C at unity p.f.
11.1 At full load % 99.84%
11.2 At full load % 99.86%
11.3 At full load. % 99.88%

Maximum efficiency will be
achieved at a load of 140.87
MVA

12.0
Regulation at full load, 0.8 P.F at 75
0
C
winding temperature
% 8.1%
12.1
Regulation at full load, Unity P.F at 75
0
C
winding temperature
% 0.92%

13.0 Rated frequency Hz. 50

14.0 External short circuit withstand capacity MVA
Fault MVA :29000 ie
3x420kVx40kA
for 3secs

15.0 Core :
15.1 Material of core lamination
Cold rolled grain oriented
silicon steel Grade M5
15.2 Thickness of core plates. 0.3mm (approx)
15.3 Insulation of core lamination. Karlite
15.4 Insulation of core bolts Fibre glass
15.5 Insulation of core bolt washers Fibre glass
15.6 Insulation of core clamping plates. Fibre glass

16.0 Winding connections :
16.1 HV Auto Star
16.2 IV Auto Star

CGL W.O.T09935, Rev.1, Dt.05.05.11
Prepared by:SS, Approved by:AVD
Page no. 3 of 12
TECHNICAL DATA SHEET OF AUTOTRANSFORMER
CUSTOMER : TECHNO ELECTRIC
RATING : 315 MVA, 400/220/33 kV, AUTO TRANSFORMER
16.3 LV Delta
16.4 Vector group YNa0d11

17.0 Tappings on winding Taps on HV for HV variation
17.1 On-load / off taps On Load Tap changer
17.2 On HV / IV / LV winding HV
17.3 Full power tapping range + % +10% to -10%

18.0 If ON load taps, specify details of OLTC gear. Easun MR, India
18.1 Manual / automatic control Manual / automatic
18.2 Remote / local control Remote
18.3
If remote control, whether the remote control
cubicle included in Bidders scope of supply
Yes
18.4 Voltage class of the OLTC 220 kV
18.5 Current rating of the OLTC A 802

19.0
Terminals of tertiary (stabilising) winding
brought out to bushings
Yes /
No
Yes

20.0 Winding insulation category : Class A
20.1 HV uniform / non-uniform Non-uniform
20.2 IV uniform / non-uniform Non-uniform
20.3 LV uniform / non-uniform Uniform

21.0 Type of axial coil supports
21.1 HV
Permawood , Pressboard
cylinders
21.2 IV
Permawood , Pressboard
cylinders
21.3 LV
Permawood , Pressboard
cylinders

22.0 Type of radial coil supports

CGL W.O.T09935, Rev.1, Dt.05.05.11
Prepared by:SS, Approved by:AVD
Page no. 4 of 12
TECHNICAL DATA SHEET OF AUTOTRANSFORMER
CUSTOMER : TECHNO ELECTRIC
RATING : 315 MVA, 400/220/33 kV, AUTO TRANSFORMER
22.1 HV
Permawood , Pressboard
cylinders
22.2 IV
Permawood , Pressboard
cylinders
22.3 LV
Permawood , Pressboard
cylinders

23.0 Impulse voltage withstand 1.2 / 50 s wave
23.1 HV kV/Peak 1300kVp
23.2 IV kV/Peak 950kVp
23.3 LV kV/Peak 250kVp

24.0
Power frequency withstand voltage (dry and
wet)

24.1 HV; HV neutral kV(rms)
P.D measurement shall be
carried out with u=364 kV at
200 Hz / 70 kVrms
24.2 IV kV(rms)
Shall be carried out with PD
measurement
24.3 LV kV(rms) 95kVrms

25.0 Guaranteed maximum temperature rise
25.1 Oil by thermometers
0
C 50
25.2 Winding by resistance for :
25.2.1 ONAN cooling
0
C 55
25.2.2 ONAFCooling
0
C 55
25.2.3 OFAF Cooling
0
C 55



26.0
Switching impulse withstand voltage for
highest equipment voltage > 145 kV.
HV(400kV) 1050kVp

27.0 Tank cover conventional / bell shaped Bell shaped

28.0
Minimum clearance height for lifting core and
windings from tank
mm 8650


CGL W.O.T09935, Rev.1, Dt.05.05.11
Prepared by:SS, Approved by:AVD
Page no. 5 of 12
TECHNICAL DATA SHEET OF AUTOTRANSFORMER
CUSTOMER : TECHNO ELECTRIC
RATING : 315 MVA, 400/220/33 kV, AUTO TRANSFORMER
29.0 Bushings HV/IV/LV/HVn
29.1 Rated voltage class kV 420 / 245 / 52 / 36
29.2 Rated current A 800 / 1250 / 3150 / 3150
29.3 1.2 / 50 s impulse withstand kV(p) 1425 / 1050 /250/170
29.4
One minute power frequency withstand dry
and wet
kV(rms) 630 /460/ 95/75
29.5 Minimum clearance in air(ph-ph/ph-gnd) mm
HV mm 4000/3500
IV mm 2350/2150
LV mm
530/480 .. (Outdoor Air
clearances)
HV & IV neutral mm 320 . (Line to Earth)
29.6 Minimum creepage distance
29.6.1 Total mm
HV mm 13020
IV mm 7595
LV mm 1612
HV & IV neutral mm 1116
29.6.2 Protected mm
Approx 50% of the total
protected creepage
29.7 Quantity of oil in oil filled bushings Litres HV Line : 200 ltr
IV Line : 50 ltr

LV Line : 5ltr;
LVN: Not Applicable
29.6.8
Free space required at top for removal of HV
Bushing
mm 12500

30.0
Load loss at rated current and 315MVA at
75
0
C winding temperature between IV & HV
(guaranteed subject to tolerance as per
applicable standard and excluding cooler
losses)

430kW(Max) at 75deg C on
principal tap.

467kW(Max) at 75deg C on
Maximum tap.

578kW(Max) at 75deg C on
Minimum tap.

31.0 Maximum cooler losses at full load kW 14kW(Max)

CGL W.O.T09935, Rev.1, Dt.05.05.11
Prepared by:SS, Approved by:AVD
Page no. 6 of 12
TECHNICAL DATA SHEET OF AUTOTRANSFORMER
CUSTOMER : TECHNO ELECTRIC
RATING : 315 MVA, 400/220/33 kV, AUTO TRANSFORMER

32.0
No load losses (core loss and di-electric loss) at
100% rated voltage and frequency, guaranteed
subject to tolerance as per applicable standard
86kW(Max)

33.0 Guaranteed no-load current :
33.1
When excited from LV side at 100% rated
voltage
A
Approx 0.5% of the Full load
current
33.2
When excited from LV side at 110% rated
voltage
A
Approx 1.5% of the Full load
current

34.0 Maximum flux density
At 100% rated voltage Wb/m
2
1.725
At 90% rated voltage Wb/m
2
1.55
At 110% rated voltage Wb/m
2
1.897
At 125% rated voltage Wb/m
2
2.156
At 140% rated voltage Wb/m
2
2.41
34.1 Overfluxing capability.
At 110% rated voltage Seconds Continuous
At 120% rated voltage Seconds 50
At 125% rated voltage Seconds 35
At 130% rated voltage Seconds 7
At 140% rated voltage Seconds 3
At 150% rated voltage Seconds 1
34.2 Voltage withstand time
At 110% rated voltage Seconds Continuous
At 120% rated voltage Seconds 50
At 125% rated voltage Seconds 35
At 130% rated voltage Seconds 7
At 140% rated voltage Seconds 3
At 150% rated voltage Seconds 1
35.0 Current density

CGL W.O.T09935, Rev.1, Dt.05.05.11
Prepared by:SS, Approved by:AVD
Page no. 7 of 12
TECHNICAL DATA SHEET OF AUTOTRANSFORMER
CUSTOMER : TECHNO ELECTRIC
RATING : 315 MVA, 400/220/33 kV, AUTO TRANSFORMER
35.1 HV A/cm
2
350(approx)
35.2 IV A/cm
2
350(approx)
35.3 LV A/cm
2
350(approx)

36.0 Wheels
36.1 Plain / flanged Flanged
36.2 Unidirectional / bi-directional Bi-directional
36.3 Quantity 8
36.4 Gauge (s) 1676

37.0 Vacuum withstand capability :
37.1 Main tank
mm of
Hg.
Full Vacuum
37.2 Radiators and accessories
mm of
Hg
Full Vacuum
37.3 Pressure withstand capability :
37.4 Main tank torr Normal Head+5 PSI (35 kPa)
37.5 Radiators and accessories torr As per CBIP

38.0 All accessories supplied as specified
Yes /
No
Yes

39.0
Cooler control scheme conforms to
specification
Yes /
No
Yes

40.0
OLTC control scheme conforms to
specification
Yes

41.0 Weights
41.1 Net weight of the core kg 70500 approx.
41.2 Net weight of copper
41.2.1 HV kg
24700 approx. (Series + Tap
winding)
41.2.2 LV kg
12500 approx. (Common
winding)

CGL W.O.T09935, Rev.1, Dt.05.05.11
Prepared by:SS, Approved by:AVD
Page no. 8 of 12
TECHNICAL DATA SHEET OF AUTOTRANSFORMER
CUSTOMER : TECHNO ELECTRIC
RATING : 315 MVA, 400/220/33 kV, AUTO TRANSFORMER
41.2.3 Tertiary kg 3600 approx.
41.2.4 Total kg 40800 approx.
41.3 Oil kg 77000 approx
41.4 Tank, coolers and fittings kg 77000 approx
41.5 Total Weight of transformer kg 314000 approx
41.6 Untanking weight kg 157000 approx
42.0 Sheet metal thickness
42.1 Outdoor cooler control cabinet mm 2.5 mm (approx)
42.2 Indoor OLTC control cabinet mm 2.5 mm (approx)

43.0
Cooling fans : (State separately for ONAF &
OFAF)

43.1 Type Propeller type
43.2 Quantity No.
8 nos. working + 2 nos.
Standby = 10 nos. total
43.3 Rating kW 0.7 kW per fan

44.0 Cooling oil pumps
44.1 Type Axial flow
44.2 Quantity No. 2 running + 2 standby
44.3 Rating kW 4.1 kW per pump

45.0 Cooling water pumps NA
45.1 Type NA
45.2 Quantity No. NA
45.3 Rating kW NA

46.0
Capability of transformer to remain in
operation from hot condition after failure of
forced cooling

46.1 Full load Minutes 10 minutes (approx)


CGL W.O.T09935, Rev.1, Dt.05.05.11
Prepared by:SS, Approved by:AVD
Page no. 9 of 12
TECHNICAL DATA SHEET OF AUTOTRANSFORMER
CUSTOMER : TECHNO ELECTRIC
RATING : 315 MVA, 400/220/33 kV, AUTO TRANSFORMER
47.0 On-load tap changer
47.1 Make Easun MR ,India
47.2 Type designation 3 x MI
47.3 Suitable for auto / manual operation Auto /manual
47.4 Rated voltage kV 245kV
47.5 Rated current Amp 800A
47.6 Number of steps 16
47.7 Step voltage Volts 1.25%
47.8 Rated voltage of drive motor V 400
47.9 Rated voltage of control circuit V 400
47.10
Time to complete tap changing operation from
any one step to next higher or lower step

47.10.1 On auto operation Sec. 5secs (approx)
47.10.2
On Manual operation i.e., through push
button
Sec. 5secs (approx)

48.0 List of routine tests to be carried out As per IS2026/ CBIP

49.0 Winding resistance, per phase at 75 deg.C
49.1 HV (from HV Line to Neutral) ohm 0.6867 approx.
49.2 IV (from IV Line to Neutral) ohm 0.4095approx.
49.3 LV ohm 0.12 approx.

50.0 Conductor area
50.1 Series winding sq.mm 250 approx.
50.2 Common winding sq.mm 150 approx.
50.3 Tap winding sq.mm 145 approx.
50.4 LV winding sq.mm 303 approx.
50.5
Inter turn insulation for LV,TAP, Common &
Series winding
Insulating Kraft Paper
50.6 Inter winding insulation Pre-compressed press boards

CGL W.O.T09935, Rev.1, Dt.05.05.11
Prepared by:SS, Approved by:AVD
Page no. 10 of 12
TECHNICAL DATA SHEET OF AUTOTRANSFORMER
CUSTOMER : TECHNO ELECTRIC
RATING : 315 MVA, 400/220/33 kV, AUTO TRANSFORMER
50.7 LV winding to Core insulation Pre-compressed press boards

51.0 Shipping section
51.1 Size of largest package (LxBxH) mm
16300 x 10450 x 10500
approx.
51.2 Weight of the largest package Tonnes 236 approx

52.0
Manufacturers maintenance procedure and
schedule for spare uncharged transformer
After final testing

53.0
Overload capacity of transformer for with all
fans working simultaneously.
As per IS 2026


54.0 Bushings CTs, if offered
54.1 Quantity

54.2 Ratio
54.3 VA burden
54.4 Accuracy class Refer Table below
54.5 Knee point voltage Volts
54.6 Magnetising current at knee-point voltage Amps
54.7 Secondary resistance Ohms

55.0
Values of transfer surge voltage withstand on
LV :

55.1 Lightning surges
55.1.1 Amplitude kVp <170 kVp
55.1.2 Rate kV/sec. 1.2/50 microsec. Approx.

56.0
Tertiary winding, if any, if kept isolated then
the Bidder to state whether one terminal to be
earthed or not.
NA

57.0 Torque for coil clamping bolts Kg-m NA, Tight fit pressure block

CGL W.O.T09935, Rev.1, Dt.05.05.11
Prepared by:SS, Approved by:AVD
Page no. 11 of 12
TECHNICAL DATA SHEET OF AUTOTRANSFORMER
CUSTOMER : TECHNO ELECTRIC
RATING : 315 MVA, 400/220/33 kV, AUTO TRANSFORMER
arrangement is used.

58.0
Whether neutral end surge diverter
recommended by the Bidder
Not required.

59.0 If yes, details of surge diverter NA
59.1 Make NA
59.2 Type NA
59.3 kV class NA
59.4 kV rating NA

60.0
If unit cooler arrangement offered for cooling,
advise ?

Pressed Steel sheet Radiators of
Unpainted Hot dipped
Galvanised are used
(520 Wide x 1.2 mm thk)
60.1 Total no. of unit coolers provided.
Radiators are arranged in 2
Banks of 50% capacity each.
60.2
No. of unit coolers which would be in service
for full load operation of transformer.

2 x 9 nos. per bank = 18 nos.
total
60.3 No. of spare unit coolers NA
60.4 No. of fans in each unit cooler nos
2 x (4 nos. working + 1 no.
standby) per bank
Total 10 Nos.
60.5 No. of pumps in each unit cooler
2 x (1no. working + 1nos.
standby) per bank
Total 4 nos.
60.6 Rating of each fan motor
3-Phase, 400V, 50Hz, 0.5A,
700Watts
60.7 Rating of each oil pump motor
4500LPM, 3-Phase, 415V
10%, 50Hz, 8A, 4.1kW

61.0 Quantity of paper used for insulation kg 1700 approx.

62.0 Quantity of copper used for each winding kg Specified in Cl. 41.2 above







CGL W.O.T09935, Rev.1, Dt.05.05.11
Prepared by:SS, Approved by:AVD
Page no. 12 of 12
TECHNICAL DATA SHEET OF AUTOTRANSFORMER
CUSTOMER : TECHNO ELECTRIC
RATING : 315 MVA, 400/220/33 kV, AUTO TRANSFORMER



Rev.01- Customer comments dated 4/05/11 are incorporated T1D/AVD-SS 05/05/11