CONSULTANT:
MAIN CONTRACTOR:
DASTUR ENGINEERING
INTERNATIONAL, GmbH
DUSSELDORF M.N DASTUR &
COMPANY (P) LTD. KOLKATA
SIEMENS W.L.L
Contract No
Date
Bay Number
Manufacturer
EF5 PROJECT
:
: 07-07-2013
: 1F12
:SIEMENS
Equipment-1
Equipment-2
Equipment-3
Equipment-4
Equipment Used:
IR Measurement
CPC100
Multi meter
Clamp meter
Sr. No
100710 / 2595
LJ552T / HK059
97100545
15730023
Make / Model
Megger-MIT510/2
Omicron
Fluke/179
Fluke/365
Calibration
Date:
13-07-2012
12-07-2012
06/07/2012
10/07/2012
Calibration Due:
12-08-2013
11-08-2013
06/08/2013
10/08/2013
W.L.L QATAR
DASTUR ENGINEERING
INTERNATIONAL, GmbH DUSSELDORF
M.N DASTUR & COMPANY (P) LTD.
QATAR STEEL
COMPANY
KOLKATA
Signature
Name
Muhammad Rafique
Date
Date: 16/06/2013
Signature
Signature
Name
Name
Date
Date
Page 1
SITE TEST REPORT FOR 6.6 /0.420kV 2.5 MVA POWER TRANSFOMER, CCM
CLIENT:
CONSULTANT:
MAIN CONTRACTOR:
DASTUR ENGINEERING
INTERNATIONAL, GmbH
DUSSELDORF M.N DASTUR &
COMPANY (P) LTD. KOLKATA
SIEMENS W.L.L
EF5 PROJECT
Contract No
Date
Bay Number
Manufacturer
:
: 07-07-2013
: 1F12
:SIEMENS
C. SAFETY PRECAUTIONS:
Safety Labels has been installed in Power Transformer Area (e.g. Power
Transformer testing under progress).
Testing area has been kept clean and have sufficient space during testing.
Bay reference
: 1F12 CCM
Serial Number
: Nr LEL-111449
Year of Mfg
: 2012
Power Rating
: 2.5MVA
Vector Group
: DYn11
Type of Cooling
: ONAN
Rated Frequency
: 50Hz
: 2.850KA
Rated HV Voltage
: 6600V
Rated LV Voltage
: 420V
HV Current
: 218.7A
LV Current
: 3437A
Tap Changer
: DETC
Range of Taps
: 5
: ERGON HYVOLTI
Ambient Temperature
: 55C
%Impedance at tap
No.3
: 7.7%
Temperature Rise
Winding/Oil
: 50/45K
Bushings
Date: 16/06/2013
Page 2
Breather
SITE TEST REPORT FOR 6.6 /0.420kV 2.5 MVA POWER TRANSFOMER, CCM
CLIENT:
CONSULTANT:
MAIN CONTRACTOR:
DASTUR ENGINEERING
INTERNATIONAL, GmbH
DUSSELDORF M.N DASTUR &
COMPANY (P) LTD. KOLKATA
SIEMENS W.L.L
Contract No
Date
Bay Number
Manufacturer
EF5 PROJECT
:
: 07-07-2013
: 1F12
:SIEMENS
Make
Type of
Check
Description
Result
Visual
O.K
75.7KV, Test
conducted
with BDV
KIT,
O.K
Valve Positions
Visual
O.K
Electrical
O.K
LV Bushings
Visual
O.K
Visual
O.K
Visual
O.K
Tap
R Y
Y - B
B R
414.7
415.03
414.85
25.86
20.21
26.41
Date: 16/06/2013
Page 3
SITE TEST REPORT FOR 6.6 /0.420kV 2.5 MVA POWER TRANSFOMER, CCM
CLIENT:
CONSULTANT:
MAIN CONTRACTOR:
DASTUR ENGINEERING
INTERNATIONAL, GmbH
DUSSELDORF M.N DASTUR &
COMPANY (P) LTD. KOLKATA
SIEMENS W.L.L
Contract No
Date
Bay Number
Manufacturer
EF5 PROJECT
:
: 07-07-2013
: 1F12
:SIEMENS
415.01
415.01
414.84
28.18
21.97
28.74
415.07
415.03
415.04
30.77
23.97
31.40
Apply 3-phase (415 V) to the low voltage bushings. Measure voltage between phases
and current on each phase.
Applied Voltage (V)
Tap
R Y
Y - B
B R
415.02
414.97
414.98
3.7333
3.7718
4.7629
Connection
Applied
Voltage
(Volts)
Measured Values ( G )
Polarization Index
R60
R300
R600
R300/R60
R600/R60
HV - (LV + E)
2500
1.21
2.1
2.40
1.74
2.0
LV ( HV + E)
250
1.61
3.54
4.25
2.2
2.64
HV LV
250
2.01
3.79
4.51
1.89
2.24
(HV+LV) E
250
1.62
2.88
3.36
1.77
2.027
Date: 16/06/2013
Page 4
SITE TEST REPORT FOR 6.6 /0.420kV 2.5 MVA POWER TRANSFOMER, CCM
CLIENT:
CONSULTANT:
MAIN CONTRACTOR:
DASTUR ENGINEERING
INTERNATIONAL, GmbH
DUSSELDORF M.N DASTUR &
COMPANY (P) LTD. KOLKATA
SIEMENS W.L.L
EF5 PROJECT
Contract No
Date
Bay Number
Manufacturer
:
: 07-07-2013
: 1F12
:SIEMENS
HV Winding Resistance:
Tap
Position
No.
Measured Resistance
Between Phase to Phase ()
Mean Value at
Reference Temp.75 C
Factory
Value at
26 C
Value at
Reference
Temp.
Factory
Value at
Reference
Temp.
%
Deviation
R Y
Y - B
B R
Measured
Value at
39.0 C
0.1308
0.1309
0.1314
0.1310
0.1487
0.1244
0.1238
0.1246
0.1242
0.121
0.1411
0.1437
1.80
0.1172
0.1165
0.1171
0.1169
0.1327
Date: 16/06/2013
Page 5
SITE TEST REPORT FOR 6.6 /0.420kV 2.5 MVA POWER TRANSFOMER, CCM
CLIENT:
CONSULTANT:
MAIN CONTRACTOR:
DASTUR ENGINEERING
INTERNATIONAL, GmbH
DUSSELDORF M.N DASTUR &
COMPANY (P) LTD. KOLKATA
SIEMENS W.L.L
EF5 PROJECT
Y B
B R
0.4633
0.4545
0.4638
Mean Value at
Meas. Value
at
39.0 C
0.4605
Factory
Value at
26 C
0.4290
Contract No
Date
Bay Number
Manufacturer
:
: 07-07-2013
: 1F12
:SIEMENS
Reference Temp.75 C
Value at
Reference
Temp.
Factory
Value at
Reference
Temp.
% Deviation
0.5210
0.5095
-2.25
Test Procedure
Dyn11
RY = R n + Y n,
Bb< By
Yb = Yy
Date: 16/06/2013
Page 6
SITE TEST REPORT FOR 6.6 /0.420kV 2.5 MVA POWER TRANSFOMER, CCM
CLIENT:
CONSULTANT:
MAIN CONTRACTOR:
DASTUR ENGINEERING
INTERNATIONAL, GmbH
DUSSELDORF M.N DASTUR &
COMPANY (P) LTD. KOLKATA
SIEMENS W.L.L
EF5 PROJECT
Contract No
Date
Bay Number
Manufacturer
:
: 07-07-2013
: 1F12
:SIEMENS
Test Results
Short R & r
Apply Voltage (Volts)
R Y
415.4
Y B
414.4
B R
414.3
391.4
414.4
415.2
16.07
391.3
390.7
399.20
Dyn11
R r = 0,
RY = R n + Y n,
Bb< By
Yb = Yy
Date: 16/06/2013
Page 7
SITE TEST REPORT FOR 6.6 /0.420kV 2.5 MVA POWER TRANSFOMER, CCM
CLIENT:
CONSULTANT:
MAIN CONTRACTOR:
DASTUR ENGINEERING
INTERNATIONAL, GmbH
DUSSELDORF M.N DASTUR &
COMPANY (P) LTD. KOLKATA
SIEMENS W.L.L
EF5 PROJECT
Contract No
Date
Bay Number
Manufacturer
:
: 07-07-2013
: 1F12
:SIEMENS
Test Procedure
Date: 16/06/2013
Page 8
SITE TEST REPORT FOR 6.6 /0.420kV 2.5 MVA POWER TRANSFOMER, CCM
CLIENT:
CONSULTANT:
MAIN CONTRACTOR:
DASTUR ENGINEERING
INTERNATIONAL, GmbH
DUSSELDORF M.N DASTUR &
COMPANY (P) LTD. KOLKATA
SIEMENS W.L.L
EF5 PROJECT
Contract No
Date
Bay Number
Manufacturer
:
: 07-07-2013
: 1F12
:SIEMENS
Test Results
Tap
Position
No.
Applied
Voltage
(V)
Rated
HV/LV
Ratio
415
% Error
R-Y/r-n
Y-B/y-n
R-B/b-n
Average
Ratio
R-Y/r-n
Y-B/y-n
R-B/b-n
28.625
28.625
28.625
28.625
415
27.927
27.927
27.927
27.927
415
27.217
27.270
27.270
27.270
27.270
-0.19
-0.19
-0.19
415
26.545
26.545
26.545
26.545
415
25.855
25.855
25.855
25.855
IEC Standard 60076-2000, Part 1, states that maximum allowable ratio error for the
principle tap is 0.5 % i.e. got it within the limit.
Date: 16/06/2013
Page 9
SITE TEST REPORT FOR 6.6 /0.420kV 2.5 MVA POWER TRANSFOMER, CCM
CLIENT:
CONSULTANT:
MAIN CONTRACTOR:
DASTUR ENGINEERING
INTERNATIONAL, GmbH
DUSSELDORF M.N DASTUR &
COMPANY (P) LTD. KOLKATA
SIEMENS W.L.L
EF5 PROJECT
Contract No
Date
Bay Number
Manufacturer
:
: 07-07-2013
: 1F12
:SIEMENS
Test Procedure
Test Results:
APPLIED VOLTAGE 230V HV SIDE
R Y
Y B
B R
r n
y n
b n
230.4
177.3
53.35
229.5
142.1
87.5
116.4
230.5
114.2
114.6
227.5
113.2
56.84
173.3
230.3
111.4
117.3
228.7
The measured values must be in conformance to the values in the factory Acceptance
report of this transformer. Normally in a well balanced magnetic circuit, voltage
applied at one phase would be the summation of other two phases. The required result
is achieved.
Date: 16/06/2013
Page 10
SITE TEST REPORT FOR 6.6 /0.420kV 2.5 MVA POWER TRANSFOMER, CCM
CLIENT:
CONSULTANT:
MAIN CONTRACTOR:
DASTUR ENGINEERING
INTERNATIONAL, GmbH
DUSSELDORF M.N DASTUR &
COMPANY (P) LTD. KOLKATA
SIEMENS W.L.L
Contract No
Date
Bay Number
Manufacturer
EF5 PROJECT
:
: 07-07-2013
: 1F12
:SIEMENS
Test Procedure
Test Results
Temp 40C
Tap
position
Connection.
3
Voltage
applied (V)
R-Y
Y-B
R-B
Average
Average
%Z
MVA
Current
% Z
134.80
133.0
130.9
132.9
35.2
35.8
34.6
35.30
12.19
2.5
218.7
7.7
Date: 16/06/2013
Page 11
SITE TEST REPORT FOR 6.6 /0.420kV 2.5 MVA POWER TRANSFOMER, CCM
CLIENT:
CONSULTANT:
MAIN CONTRACTOR:
DASTUR ENGINEERING
INTERNATIONAL, GmbH
DUSSELDORF M.N DASTUR &
COMPANY (P) LTD. KOLKATA
SIEMENS W.L.L
EF5 PROJECT
Contract No
Date
Bay Number
Manufacturer
:
: 07-07-2013
: 1F12
:SIEMENS
80.2 KV
58.9KV
80.1 KV
68.4KV
71.8 KV
72.9KV
80.2 KV
75.9KV
80.0 KV
71.8KV
80.1 KV
72.6KV
Mean Value
78.8 KV
70.1KV
Oil quality is very good, satisfied the IEC Standards 60156-95, for new oil the BDV
must be above 60KV
17. Insulation resistance test:
DESCRIPTION
Measurement
value
Test voltage
500VDC
Done it
Date: 16/06/2013
Page 12
SITE TEST REPORT FOR 6.6 /0.420kV 2.5 MVA POWER TRANSFOMER, CCM
CLIENT:
CONSULTANT:
MAIN CONTRACTOR:
DASTUR ENGINEERING
INTERNATIONAL, GmbH
DUSSELDORF M.N DASTUR &
COMPANY (P) LTD. KOLKATA
SIEMENS W.L.L
EF5 PROJECT
Date: 16/06/2013
Contract No
Date
Bay Number
Manufacturer
:
: 07-07-2013
: 1F12
:SIEMENS
Page 13