Sie sind auf Seite 1von 147

T Th he e S Sc co ot tt ti is sh h B Bu ui il ld di in ng g S St ta an nd da ar rd ds s A Ag ge en nc cy y

A AC CC CR RE ED DI IT TE ED D C CO ON NS ST TR RU UC CT TI IO ON N D DE ET TA AI IL LS S
( (S SC CO OT TL LA AN ND D) )



















ACCREDITED CONSTRUCTION DETAILS (SCOTLAND)
(FOR THE LIMITATION OF THERMAL BRIDGING AND AIR
LEAKAGE IN LOW AND MEDIUM RISE DOMESTIC TYPE)

Status of this document
This document provides guidance on one way to meet some of the requirements of
the functional standards set out in Regulation 9 of the Building (Scotland)
Regulations. There is however no need to follow the guidance in this document, as
there are other ways of meeting the functional standards. Access to the Technical
Handbook is available on the website of the Scottish Building Standards Agency at
www.sbsa.gov.uk, and it may be downloaded free of charge.


------------------------------------------------------------------


1 INTRODUCTION

Background
Improved energy performance measures for new construction work are now
reflected in the Scottish building regulations. Achieving these standards generally
means that buildings are more highly insulated and have better heating system
efficiencies than ever before, whilst simultaneously retaining a good level of
construction that limits:
air infiltration; and
heat-loss through junctions in the fabric.

The Scottish Building Standards Agency recognise the need to provide guidance on
how to address these two issues, whilst at the same time avoiding the risks which
can arise. The details presented in this document do not endeavour to attain
absolute levels of airtightness that will result in a change in the way that dwellings
are currently ventilated, but when followed with care will limit air infiltration to an
acceptable level. The details can be built using the construction skills currently
available and minimise the risk of both surface condensation and interstitial
condensation. The arrangements shown however go further than simply minimising
condensation risk, to making a useful contribution to reduce heat-loss at junctions of
building elements, where traditionally it can be difficult to maintain the insulation
levels that can be achieved within the elements themselves.

This document provides two levels of guidance. Specific guidance related to each
selected construction type and on each construction detail. Supplementary guidance
is also provided on associated issues including the selection of insulation, the
selection of membranes, air infiltration and some examples of construction issues.

Limitations on use
The details illustrated here do not form part of the Technical Handbooks but are
intended to provide sufficient information to enable users to achieve the level of
performance presented in these documents. These details are generic in nature,
show principles of construction and for this reason they are not dimensioned, nor
drawn to scale. It should be noted that not all permutations of thermal insulation are
shown; it is acceptable to provide multiple layers of insulation. Examples of this
would be, in the timber frame wall an additional layer of insulation with a preserved



cavity may be provided to the outside of the sheathing board, or in the masonry
cavity wall an insulated lining board may be installed in addition to the cavity
insulation. All details are suitable for use in domestic type buildings up to six storeys
high.

Details are provided for the most common construction types:
masonry walls with external insulation
masonry cavity walls with full fill insulation
masonry cavity walls with partial fill insulation
masonry walls with internal insulation
timber frame walls
steel frame walls
miscellaneous junctions, e.g. door thresholds and roof windows.

Aim
The main aim in providing these details is to illustrate a ready means:
to manage thermal loss (to reduce energy requirement)
to avoid interstitial condensation (which can damage construction)
to avoid surface condensation (which can lead to mould growth and endanger
health)
to limit air leakage (to reduce energy requirement)
to prevent rain penetration (which can damage construction and endanger
health).

The common factors which are illustrated in each detail are:
the position of insulation (to limit thermal bridging)
the position and extent of ventilation (to control condensation)
the position and the different performance characteristics of the building
membranes (to manage air and vapour movement and to prevent water
entering the building)
the position and type of cavity closers and cavity barriers (to minimise air
movement and in the case of the latter, to provide fire resistance). Where
these are proprietary types, it is assumed for the purposes of these details
that they incorporate a DPC which is capable of directing moisture away from
the inside of the building.

Other requirements of the Scottish building regulations which are not illustrated by
these details, but which should be considered by the designer include:
thermal performance of elements (U-values)
structural
fire resistance and flame spread
ventilation (of rooms)
airborne and impact noise (including flanking sound)
damp-proofing arrangements.







Supplementary Guidance

Selection of Insulation
The selection of insulation material and the choice of thickness of insulation to be
provided will be influenced by a number of factors which are determined by the
building procurer and the designer (e.g. architectural features). These fall outwith
the scope of this publication. In terms of construction of elements the key issues are
a combination of the following:
thermal transmittance (U-value) recommended in Scottish building regulations
thermal conductivity of the insulation material
thermal performance of the non-insulating part of the construction (e.g.
linings and structural components)
interaction of the insulation material and the remainder of construction (e.g.
insulation position in relation to ventilation of the element or bridging of
insulation by fixings).

The U-value calculation is outwith the scope of this document. Guidance on how this
can be done and the other options available are in Section 6 of the Technical
Handbooks.

Layers of differing insulation materials
Where different types of insulation are used within a construction, it is recommended
that the insulation nearest to the outer surface of the construction be the least
resistant to the passage of water vapour. This is to reduce the possibility of
condensation forming in between the insulation layers. For example, where mineral
wool is used in conjunction with polystyrene board, the mineral wool should be the
outer layer.

Where it is essential that the outer layers of insulation has a higher vapour resistivity
than the inner layer then condensation risk analysis should always be carried out.

Selection of Membranes
The details illustrate the location and characteristics of the membranes related to
their function in resisting water, water vapour or air. These characteristics are
fundamental to the success of the construction and selection of the correct
membrane should be made with care.

Vapour control layer
A vapour control layer should be used:
principally to reduce the spread of water vapour throughout the construction
element, where condensation can do harm to the building materials.
as a secondary function to improve the airtightness of the building fabric.

Typically this layer is provided on the inside face of the insulation in, timber or steel
frame walls, rooms in roof spaces, flat roofs and it may be incorporated as an
integral part of a proprietary wall lining board A vapour control layer is a material
with a vapour resistance greater than 200 MNs/g.






Vapour permeable or breather membrane
A vapour permeable or breather, water-resistant membrane should be used:
as a primary protection to vulnerable construction materials from the harmful
effects of precipitation during the construction process; and
as a secondary protection to vulnerable construction materials from the
harmful effects of precipitation, throughout the life of the building; and
to allow water vapour to escape from vulnerable construction materials that
would otherwise be entrapped due to lack of ventilation.

Typically this layer is provided on the outer face of the inner leaf of a timber frame
wall or above sarking insulation where the space between the tiles or slates is
ventilated. In the case of the former the membrane has a vapour resistance of no
more than 0.6 MNs/g and in the case of the latter, it has a vapour resistance of no
more than 0.25 MNs/g.

Non-vapour permeable roofing membrane
A non-vapour permeable, water-resistant roofing membrane should be used:
as a primary protection to vulnerable roof construction materials from the
harmful effects of precipitation during the construction process; and
as a primary protection to vulnerable roof construction materials from the
harmful effects of precipitation, for example the covering to a built-up felt flat
roof directly above the insulation; and
as a secondary protection to vulnerable roof construction materials from the
harmful effects of precipitation, for example as a roof tile underlay where the
roof space is ventilated above the insulation.

This type of layer has a vapour resistance of more than 0.25 MNs/g.

Sequence of construction
Some of the details presented in this document can only be followed effectively if
consideration is given to the sequence of construction. This is important with regard
to the placing of insulation materials and particularly where insulation needs access
from two sides to allow correct positioning. An example of this is at the eaves of a
roof where it may be necessary to fit the insulation which links the wall and roof
insulation before the soffit boards are fitted.

Dense Block
For the purposes of this document a dense block is one with a thermal conductivity
greater than 0.7 W/mK.

Thermal Conductivity (lambda - )
Thermal conductivity is a measure of a materials ability to conduct heat. It is
measured in W/mK and is the quantity of heat (in Watts) which will pass through 1
square metre of the material 1 metre thick for each degree difference in temperature
between one side of the material and the other.

Any quoted thermal conductivity of a given material is, therefore, independent of its
thickness.





Air infiltration
The details shown in this document contain measures designed to reduce air
infiltration. This depends on the form of construction and the level of workmanship
but the objective is to form a definable, continuous air barrier around the dwelling.
Ways of preventing air infiltration should then be considered at every penetration of
this barrier.

Particular care on site should be paid to:
joints between structural components e.g. wall to floors
joints around components and opening within walls
service penetrations plumbing, electrical and ventilation.

General
close any vertical ducts at the top and bottom where they meet the air barrier
(e.g. boxing round soil vent pipes)
seal any service penetrations through the air barrier
select the appropriate sealant or gap filler for the size of gap and degree of
movement anticipated.

Masonry Construction
ensure continuous ribbons of adhesive are used to fix to dry lining at
perimeters of external walls, openings, and services on external walls. The
importance of correct sealing of dry lining on dabs needs to be stressed, as
this is a key area of infiltration and can seriously affect the overall ventilation
rate
use joist hangers to support floor joists
seal under skirting boards where dry lining is used, or on suspended floors.

Timber Frame
ensure DPCs are turned up behind sole plates and lap with vapour control
layers; alternatively seal with mastic or a gasket between the DPC and sole
plate
place bead of mastic on timber floor deck before positioning wall panels
(timber ground floors and intermediate floors)
ensure sheet vapour control layers are properly lapped at junctions, and/or,
ensure any vapour control plasterboard is jointed in accordance with the
manufacturers instructions
always return vapour control layers into door and window reveals, head and
sills
cut vapour control layers tight to electrical outlets and seal at piped service
penetrations, (with tape or sealant as appropriate)
ensure all breather control membranes overlap each other and are stapled in
place.



Steel Frame
all joints between rigid insulation boards be lapped or sealed with tape
approved by insulation manufacturer
ensure sheet vapour control layers are properly lapped at junctions, and/or,
ensure any vapour control plasterboard is jointed in accordance with
manufacturers instructions
always return vapour control layers into door and window reveals, heads and
sills
cut vapour control layers tight to electrical outlets and seal at piped service
penetrations.

Examples of some common construction issues

Poorly positioned cavity insulation
The cavity wall insulation should be installed tight to the outer face of the inner leaf.
This will prevent air circulation between the block and insulation reducing the
performance of the insulation layer.

Debris bridging the cavity
Clear all debris including mortar droppings from the cavity as work progresses to
prevent cold bridging occurring between the inner and outer leaf.

Insulation cut short of the cavity closers
Ensure that cavity insulation is cut to suit boards/batts that tightly butt against each
other and against surrounding cavity closers and loose fill insulation.

Service Penetrations
Service penetrations should be core drilled to minimise damage to the insulation
layer and facilitate remedial air sealing. Any damage caused to the insulation layer
by penetrations through the air barrier should be made good following their
installation. This can be achieved by filling any large gaps with loose fibrous
insulation, expanding foam insulation and sealing with a thin mastic fillet. This
includes behind bath panels, shower trays, kitchen units and into service shafts.

Socket outlet/ switch plates
Where the air barrier is formed by a plasterboard lining it is recommended that a
continuous ribbon of adhesive is applied around the hole prior to installing the
plasterboard. This will reduce air leakage through the sockets/ switches into the void
beyond. Proprietary gasketed socket boxes and membranes are also available
where required.

Window and door frames
Air leakage is often found to occur between window/door frames and the surrounding
construction. Mastic seals are often required between plaster finishes, window
boards and frames.





Recessed light fittings
Recessed light fittings may permit air leakage where they breach the plasterboard
ceiling line into the voids or lofts beyond. They should only be allowed to penetrate
the primary air barrier if the units are of an air sealed type or a further secondary air
barrier is formed beyond.

Extract fans
Termination of extract fan ducts should be installed and sealed to prevent air
leakage occurring through plasterboard finishes. Where appropriate a continuous
ribbon of adhesive should be installed around the penetration. Where possible the
ducts should also be sealed to any masonry inner leaf. Extract fans may also be
fitted with external flaps to minimise air infiltration through the unit.

Stairs
Plaster finishes are typically omitted from voids below staircases. Air infiltration may
then occur through mortar joints in poor quality masonry into the externally ventilated
wall cavities. Plaster finishes should be installed below stairs or a thin render/parge
coat shoul be applied to the surface of the masonry.

Dormers in room in roof
The plasterboard linings surrounding the dormer will form the air barrier. Care
should be taken to ensure that the linings form a continuous air barrier and are fully
sealed to the window frames.







Section 1 Introduction and Supplementary Guidance

Section 2 2.00 Masonry: External Wall Insulation Link
2.01 Pitched Roof, Ventilated Roofspace, Eaves Link
2.02 Pitched Roof, Ventilated Roofspace, Gable Link
2.03 Pitched Roof, Ventilated Rafter Void, Eaves Link
2.04 Pitched Roof, Ventilated Rafter Void, Gable Link
2.05 Pitched Roof, Ventilated Batten Void (warm roof), Eaves Link
2.06 Pitched Roof, Ventilated Batten Void (warm roof), Gable Link
2.07 Timber Flat Roof Link
2.08 Timber Flat Roof with Parapet Link
2.09 Lintel at Window Head Link
2.10 Windows and doors, J ambs and sills Link
2.11 Ground Bearing Floor, Insulation Above Slab Link
2.12 Ground Bearing Floor. Insulation Below Slab Link
2.13 Raft Foundation Link
2.14 In-situ Suspended Ground Floor Slab Insulation Above Slab Link
2.15 In-situ Suspended Ground Floor Slab, Insulation Below Slab Link
2.16 Concrete Beam and Block Suspended Ground Floor Link
2.17 Timber Suspended Ground Floor Link
2.18 Separating Wall Link
2.19 Concrete Intermediate Floor Link
2.20 Timber Intermediate Floor Link

Section 3 3.00 Masonry: Cavity Wall Insulation: Full Fill Link
3.01 Pitched Roof, Ventilated Roofspace, Eaves Link
3.02 Pitched Roof, Ventilated Roofspace, Gable Link
3.03 Pitched Roof, Ventilated Rafter Void, Eaves Link
3.04 Pitched Roof, Ventilated Rafter Void, Gable Link
3.05 Pitched Roof, Ventilated Batten Void (warm roof), Eaves Link
3.06 Pitched Roof, Ventilated Batten Void (warm roof), Gable Link
3.07 Timber Flat Roof Link
3.08 Timber Flat Roof with Parapet Link
3.09 Windows and doors, Lintel Link
3.10 Windows and doors, Folded Lintel Link
3.11 Windows and doors, Independent Lintel Link
3.12 Windows and doors, J ambs and sills Link
3.13 Ground Bearing Floor. Insulation Above Slab Link
3.14 Ground Bearing Floor, Insulation Below Slab Link
3.15 Raft Foundation Link
3.16 In-situ Suspended Ground Floor Slab, Insulation above Slab Link
3.17 In-situ Suspended Ground Floor Slab, Insulation Below Slab Link
3.18 Concrete Beam and Block Suspended Ground Floor Link
3.19 Timber Suspended Ground Floor Link
3.20 Separating Wall Link
3.21 Concrete Intermediate Floor Link
3.22 Timber Intermediate Floor Link



Section 4 4.00 Masonry: Cavity Wall Insulation: Partial Fill Link
4.01 Pitched Roof. Ventilated Roofspace. Eaves. Link
4.02 Pitched Roof. Ventilated Roofspace. Gable Link
4.03 Pitched Roof, Ventilated Rafter Void, Eaves Link
4.04 Pitched Roof, Ventilated Rafter Void, Gable Link
4.05 Pitched Roof. Ventilated Batten Void (warm roof). Eaves. Link
4.06 Pitched Roof, Ventilated Batten Void (warm roof), Gable Link
4.07 Timber Flat Roof Link
4.08 Timber Flat Roof with Parapet Link
4.09 Lintel at Window Head Link
4.10 Windows and doors. Folded Lintel Link
4.11 Windows and doors. Independent Lintel Link
4.12 Windows and doors. J ambs and sills Link
4.13 Ground Bearing Floor. Insulation Above Slab Link
4.14 Ground Bearing Floor. Insulation Below Slab Link
4.15 Raft Foundation Link
4.16 In-situ Suspended Ground Floor Slab, Insulation above Slab Link
4.17 In-situ Suspended Ground Floor Slab, Insulation Below Slab Link
4.18 Concrete Beam and Block Suspended Ground Floor Link
4.19 Timber Suspended Ground Floor Link
4.20 Separating Wall Link
4.21 Concrete Intermediate Floor Link
4.22 Timber Intermediate Floor Link

Section 5 5.00 Masonry: Internal Wall Insulation Link
5.01 Pitched Roof, Ventilated Roofspace, Eaves Link
5.02 Pitched Roof. Ventilated Roofspace. Gable Link
5.03 Pitched Roof, Ventilated Rafter Void, Eaves Link
5.04 Pitched Roof. Ventilated Rafter Void. Gable Link
5.05 Pitched Roof, Ventilated Batten Void (warm roof), Eaves Link
5.06 Pitched Roof, Ventilated Batten Void (warm roof), Gable Link
5.07 Timber Flat Roof Link
5.08 Timber Flat Roof with Parapet Link
5.09 Lintel at Window Head Link
5.10 Windows and doors, Folded Lintel Link
5.11 Windows and doors. J ambs and sills Link
5.12 Ground Bearing Floor. Insulation Above Slab Link
5.13 Ground Bearing Floor. Insulation Below Slab Link
5.14 Raft Foundation Link
5.15 In-situ Suspended Ground Floor Slab Insulation above Slab Link
5.16 Concrete Beam & Block Suspended Ground Floor Link
5.17 Timber Suspended Ground Floor Link
5.18 Separating Wall Link
5.19 Concrete Intermediate Floor Link
5.20 Timber Intermediate Floor Link



Section 6 6.00 Timber Frame Link
6.01 Pitched Roof, Ventilated Roofspace, Eaves Link
6.02 Pitched Roof. Ventilated Roofspace. Gable Link
6.03 Pitched Roof, Ventilated Rafter Void, Eaves Link
6.04 Pitched Roof, Ventilated Rafter Void, Gable Link
6.05 Pitched Roof, Ventilated Batten Void (warm roof), Eaves Link
6.06 Pitched Roof, Ventilated Batten Void (warm roof), Gable Link
6.07 Timber Flat Roof Link
6.08 Timber Flat Roof with Parapet Link
6.09 Lintel at Window Head Link
6.10 Windows and doors, J ambs and sills Link
6.11 Ground Bearing Floor, Insulation Above Slab Link
6.12 Ground Bearing Floor, Insulation Below Slab Link
6.13 Raft Foundation Link
6.14 In-situ Suspended Ground Floor Slab. Insulation Above Slab Link
6.15 Concrete Beam and Block Ground Floor Link
6.16 Timber Suspended Ground Floor Link
6.17 Separating Wall Link
6.18 Timber Intermediate Floor Link
6.19 Wall junction Link

Section 7 7.00 Steel frame Link
7.01 Pitched Roof, Ventilated Roofspace, Eaves Link
7.02 Pitched Roof. Ventilated Roofspace. Gable Link
7.03 Pitched Roof, Ventilated Rafter Void, Eaves Link
7.04 Pitched Roof, Ventilated Rafter Void, Gable Link
7.05 Pitched Roof, Ventilated Batten Void (warm roof), Eaves Link
7.06 Pitched Roof, Ventilated Batten Void (warm roof), Gable Link
7.07 Timber Flat Roof Link
7.08 Timber Flat Roof with Parapet Link
7.09 Lintel at Window Head Link
7.10 Windows and doors, J ambs and sills Link
7.11 Ground Bearing Floor, Insulation Above Slab Link
7.12 Ground Bearing Floor, Insulation Below Slab Link
7.13 Raft Foundation Link
7.14 In-situ Suspended Ground Floor Slab. Insulation Above Slab Link
7.15 Concrete Beam and Block Ground Floor Link
7.16 Timber Suspended Ground Floor Link
7.17 Separating Wall Link
7.18 Timber Intermediate Floor Link
7.19 Wall junction Link

Section 8 General Arrangements
8.00 For future development Link
8.01 For future development Link
8.02 Roof Window, Ventilated Rafter Void Link
8.03 Roof Window. Ventilated batten Void (Warm Roof) Link
8.04 Roof Window. Ventilated batten Void (Warm Roof) Link
8.05 Level Threshold, Insulation above Slab, Ramped Access Link
8.06 Level Threshold, Insulation below Slab, Ramped Access Link
8.07 Level Threshold, Timber Floor, Ramped Access Link
8.08 Ceilings, Services Penetrations Link


plaster or plasterboard
on dabs
solid masonry wall
(any type)
cladding
(render finish shown)
externally applied insulation system,
various fixing methods (see BRE
publication Thermal Insulation:
avoiding risks - BR262 to establish
where it can be used avoiding
technical risk)
Revision E
2.00 Masonry: External Wall Insulation
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Masonry: External Wall Insulation
2.01 Pitched Roof, Ventilated Roofspace, Eaves
proprietary cross flow
ventilator to maintain
minimum 25mm air gap
lap roof and wall insulation,
minimum 50mm thickness at
narrowest point
consider sequence of construction,
see supplementary guidance
roofing membrane
continuous ribbon of plaster
adhesive, sealing joint
between wall and ceiling
board
ventilation gap equivilent to 10mm
minimum continuous opening is
required where the roof pitch is
above 15
or
ventilation gap equivilent to
25mm minimum continuous
opening is required where the
roof pitch is below 15,
insect mesh should be installed
Revision F
Read in conjunction with
Masonry: External Wall Insulation
Pitched Roof, Ventilated Roofspace, Gable
ventilation gap equivalent to 5mm
minimum continuous opening at ridge is
required where the roof pitch is
greater than 35 or the roof span is
more than 10m
sarking board
restraint required for insulation,
for example metal banding, wire
mesh or similar material, fixed
between rafters
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Masonry: External Wall Insulation
2.02 Pitched Roof, Ventilated Roofspace, Gable
continuous ribbon of plaster
adhesive, sealing joint
between wall and ceiling
board
insulation between last truss
and gable wall
Revision C
Read in conjunction with
Masonry: External Wall Insulation
Pitched Roof, Ventilated Roofspace, Eaves
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
30 minute fire resisting
cavity barrier
continuous ribbon of plaster
adhesive, sealing joint
between wall and ceiling
board
proprietary cross flow
ventilator to maintain minimum
25mm air gap
roofing membrane
inhabited space
where two insulation
types are used together
see supplementary
guidance
Masonry: External Wall Insulation
2.03 Pitched Roof, Ventilated Rafter Void, Eaves
Revision E
Read in conjunction with
Masonry: External Wall Insulation
Pitched Roof, Ventilated Rafter Void, Gable
ventilation to roofspace
sarking board
ventilation gap equivalent
to 5mm minimum
continuous opening at ridge
is required
50mm air gap
sarking board
lap roof and wall insulation,
minimum 50mm thickness at
narrowest point
consider sequence of construction,
see supplementary guidance
vapour control layer
ventilation gap equivilent to
25mm minimum continuous
opening,
insect mesh should be installed
restraint required for insulation,
for example metal banding, wire
mesh or similar material, fixed
between rafters
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
lap roof and wall insulation,
roof insulation to be
compressed between sarking
and wall head
continuous ribbon of plaster
adhesive, sealing joint
between wall and ceiling
board
Revision E
wall insulation should
be taken up level with
top of gable
Masonry: External Wall Insulation
2.04 Pitched Roof, Ventilated Rafter Void, Gable
Read in conjunction with
Masonry: External Wall Insulation
Pitched Roof, Ventilated Rafter Void, Eaves
fill gaps at top of gable
masonry with mortar to
form an even surface
50mm ventilation
path over insulation
vapour control layer
where two insulation types are
used together see
supplementary guidance
sarking board
roofing membrane
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Masonry: External Wall Insulation
2.05 Pitched Roof, Ventilated Batten Void (warm roof), Eaves.
ventilation to
batten void
vapour control layer
proprietary over
fascia ventilator
30 minute fire resisting
cavity barrier
continuous ribbon of plaster
adhesive, sealing joint
between wall and ceiling
board
lap roof and wall insulation
minimum 50mm
consider sequence of construction,
see supplementary guidance
vapour permeable membrane with a
vapour resistance of not more than
0.25 MN.s/g
support insulation between
rafters on battens or clips
inhabited space
Revision F
Read in conjunction with
Masonry: External Wall Insulation
Pitched Roof, Ventilated Batten Void (warm roof), Gable
where two insulation
types are used together
see supplementary
guidance
ventilation gap equivalent to
5mm minimum continuous
opening is required at ridge
rigid insulation as sarking
restraint required for
insulation, for example
metal banding, wire
mesh or similar
material, fixed
between rafters
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
vapour permeable membrane
(with a vapour resistance of not
more than 0.25 MN.s/g)
continuous ribbon of plaster
adhesive, sealing joint
between wall and ceiling
board
ventilation to tile batten
void
lap roof and wall insulation,
roof insulation to be
compressed between sarking
insulation and wall head
Revision E
vapour control layer
insulation between rafters
supported on battens or clips
ensure insulation is placed
between gable wall and last rafter
Masonry: External Wall Insulation
2.06 Pitched Roof, Ventilated Batten Void (warm roof), Gable
Read in conjunction with
Masonry: External Wall Insulation
Pitched Roof, Ventilated Batten Void (warm roof), Eaves
where two insulation types are
used together see supplementary
guidance
rigid insulation as sarking
wall insulation should be taken
up level with top of gable
fill gaps at top of gable
masonry with mortar to
form an even surface
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
continuous ribbon of plaster
adhesive, sealing joint
between wall and ceiling
board
Revision F
vapour control layer turned up
edge of roof insulation, lapped
with roof waterproofing layer,
and sealed
fix full height blocking piece
and tightly pack mineral wool
into void and under deck
consider sequence of
construction, see supplementary
guidance
roofing membrane
vapour control layer
Masonry: External Wall Insulation
2.07 Timber Flat Roof
declevity piece
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
roofing membrane
continuous ribbon of plaster
adhesive, sealing joint
between wall and ceiling
board
vapour control layer
Revision E
vapour control layer turned up
edge of roof insulation, lapped
with roof waterproofing layer,
and sealed
minimum distance 300mm
between top of edge
insulation and bottom of
roof insulation
place 20mm strip of insulation
with thermal conductivity (
value) not exceeding
0.025W/mK around parapet
flashing minimum 150mm
above finish roof level
Masonry: External Wall Insulation
2.08 Timber Flat Roof with Parapet
render or impervious cladding
declevity piece
roofing membrane
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
lintel of any type
15mm strip of insulation with
thermal conductivity ( value)
not exceeding 0.025W/mK
between packing pieces
Revision D
continuous ribbon of plaster adhesive, sealing
joint between wall and board
sealant to back of frame sealant to front of frame
Masonry: External Wall Insulation
2.09 Lintel at Window Head
The same thermal principles apply at the head of doors
damp proof course
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
wall insulation carried
up to underside of sill
sealant to front and
back of frame/sill
plan view
Revision E
continuous ribbon of plaster
adhesive, sealing joint between wall
and board
section view
Masonry: External Wall Insulation
2.10 Windows and doors, Jambs and sills
15mm strip of insulation with
thermal conductivity ( value)
not exceeding 0.025W/mK
between packing pieces
15mm strip of insulation with thermal
conductivity ( value) not exceeding
0.025W/mK between packing pieces
sealant to front and back of
frame/sill
continuous ribbon of plaster
adhesive, sealing joint between
wall and board
damp proof course
damp proof course
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
wall insulation continued at
least 150mm below top of
floor insulation
Revision F
vapour control layer
under timber floor finish
damp proof membrane
above or below slab
damp proof course
external ground level
Masonry: External Wall Insulation
2.11 Ground Bearing Floor, Insulation Above Slab
mastic seal
20mm strip of perimeter
insulation with thermal
conductivity (value) not
exceeding 0.025W/mK should be
installed around any screed
continuous ribbon of plaster
adhesive, sealing joint
between wall and board
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Revision F
wall insulation continued at
least 150mm below top of
floor insulation
damp proof membrane
damp proof course
external ground level
Masonry: External Wall Insulation
2.12 Ground Bearing Floor. Insulation Below Slab
mastic seal
20mm strip of perimeter
insulation with thermal
conductivity ( value) not
exceeding 0.025W/mK around
slab and any screed
continuous ribbon of plaster
adhesive, sealing joint
between wall and board
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Revision F
external ground level
wall insulation continued at
least 150mm below top of
floor insulation
damp proof course
damp proof membrane
Masonry: External Wall Insulation
2.13 Raft Foundation
20mm strip of perimeter
insulation with thermal
conductivity ( value) not
exceeding 0.025W/mK around
slab and any screed
mastic seal
continuous ribbon of plaster
adhesive, sealing joint
between wall and board
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
vapour control layer
under timber floor finish
Revision F
external ground level
wall insulation continued at
least 150mm below top of
floor insulation
damp proof course
damp proof membrane
Masonry: External Wall Insulation
2.14 In-situ Suspended Ground Floor Slab Insulation Above Slab
mastic seal
20mm strip of perimeter
insulation with thermal
conductivity ( value) not
exceeding 0.025W/mK should be
installed around any screed
continuous ribbon of plaster
adhesive, sealing joint
between wall and board
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Revision F
external ground level
wall insulation continued at
least 150mm below top of
perimeter insulation
damp proof course
damp proof membrane
20mm strip of perimeter
insulation with thermal
conductivity (value) not
exceeding 0.025W/mK
should be installed
around slab and any
screed
Masonry: External Wall Insulation
2.15 In-situ Suspended Ground Floor Slab, Insulation Below Slab
mastic seal
dense blocks should not be
used below slab
continuous ribbon of plaster
adhesive, sealing joint
between wall and board
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
vapour control layer under
timber floor finish
sub floor ventilation should
be provided, minimum
1500mm per metre run of
external wall or 500mm per
m floor area
Revision F
damp proof course
external ground level
wall insulation continued at
least 150mm below top of
floor insulation
damp proof membrane
solum
Masonry: External Wall Insulation
2.16 Concrete Beam and Block Suspended Ground Floor
mastic seal
N.B. 20mm strip of
perimeter insulation with
thermal conductivity (
value) not exceeding
0.025W/mK should be
installed around any screed
continuous ribbon of plaster
adhesive, sealing joint
between wall and board
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
insulation directly under flooring -
supported either on battens or on
netting draped over joists and stapled
at required depths
Revision F
damp proof course
external ground level
wall insulation continued at
least 150mm below top of
floor insulation
sub floor ventilation should be
provided, minimum 1500mm per
metre run of external wall or 500mm
per m floor area
expanding foam and continuous
sealant
20mm strip of perimeter
insulation with thermal
conductivity ( value) not
exceeding 0.025W/mK should be
installed between wall and last
joist
solum
Masonry: External Wall Insulation
2.17 Timber Suspended Ground Floor
mastic seal floor joist ends supported on joist
hangers or using scarcement wall
continuous ribbon of plaster adhesive
sealing joint between wall and board
damp proof membrane
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
plan view
Revision C
Masonry: External Wall Insulation
2.18 Separating Wall
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
continuous ribbon of plaster
adhesive, sealing joint
between wall and ceiling
board
wall insulation continued
across floor zone
gaps between wall and
floor sealed
Revision D
Masonry: External Wall Insulation
2.19 Concrete Intermediate Floor
continuous ribbon of plaster
adhesive, sealing joint
between wall and board
separating floors require
additional layers and
components to comply with
Section 2: Fire and
Section 5: Noise
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
continuous ribbon of plaster
adhesive, sealing joint
between wall and ceiling
board
Revision D
wall insulation continued
across floor zone
Masonry: External Wall Insulation
2.20 Timber Intermediate Floor
separating floors require
additional layers and
components to comply with
Section 2: Fire and
Section 5: Noise
continuous ribbon of plaster
adhesive, sealing joint
between wall and board
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
plaster or plasterboard on dabs
inner leaf (block shown)
outer leaf (brick shown)
full fill cavity wall insulation
(see BRE publication Thermal
Insulation: avoiding risks - BR262
to establish where it can be used
avoiding technical risk)
3.00 Masonry: Cavity Wall Insulation: Full Fill
Revision C
render finish if required/desired
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Masonry: Cavity Wall Insulation: Full Fill
3.01 Pitched Roof, Ventilated Roofspace, Eaves
proprietary cross flow
ventilator to maintain
minimum 25mm air gap
lap roof and wall insulation, minimum
50mm thickness at narrowest point
consider sequence of construction,
see supplementary guidance
roofing membrane
continuous ribbon of plaster
adhesive, sealing joint
between wall and ceiling
board
Revision E
Read in conjunction with
Masonry: Cavity Wall Insulation: Full Fill
Pitched Roof, Ventilated Roofspace, Gable
ventilation gap equivalent to 5mm
minimum continuous opening at ridge is
required where the roof pitch is
greater than 35 or the roof span is
more than 10m
sarking board
ventilation gap equivilent to 10mm
minimum continuous opening is
required where the roof pitch is
below 15
or
ventilation gap equivilent to 25mm
minimum continuous opening is
required where the roof pitch is 15
or above
insect mesh should be installed
cavity closer (thin calcium
silicate board or similar)
restraint required for insulation,
for example metal banding, wire
mesh or similar material, fixed
between rafters
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Masonry: Cavity Wall Insulation: Full Fill
3.02 Pitched Roof, Ventilated Roofspace, Gable
Revision D
Read in conjunction with
Masonry: Cavity Wall Insulation: Full Fill
Pitched Roof, Ventilated Roofspace, Eaves
continuous ribbon of plaster
adhesive, sealing joint
between wall and ceiling
board
insulation between last truss
and gable wall
continue wall insulation to top of
gable or alternatively 270mm above
bottom of ceiling tie and insert
cavity tray
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
30 minute fire
resisting
cavity barrier
continuous ribbon of plaster
adhesive, sealing joint
between wall and ceiling
board
proprietary cross flow
ventilator to maintain minimum
25mm air gap
roofing membrane
inhabited space
where two insulation
types are used together
see supplementary
guidance
Revision E
sarking board
ventilation gap equivalent
to 5mm minimum
continuous opening at ridge
is required
50mm air gap
sarking board
lap roof and wall insulation,
minimum 50mm thickness at
narrowest point
consider sequence of construction,
see supplementary guidance
vapour control layer
Masonry: Cavity Wall Insulation: Full Fill
3.03 Pitched Roof, Ventilated Rafter Void, Eaves
Read in conjunction with
Masonry: Cavity Wall Insulation: Full Fill
Pitched Roof, Ventilated Rafter Void, Gable
ventilation gap equivilent to 25mm
minimum continuous opening
insect mesh should be installed
cavity closer (thin calcium
silicate board or similar)
restraint required for insulation,
for example metal banding, wire
mesh or similar material, fixed
between rafters
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
continuous ribbon of plaster
adhesive, sealing joint
between wall and ceiling
board
Revision E
50mm ventilation
path over insulation
vapour control layer
where two insulation types are
used together see
supplementary guidance
sarking board
Masonry: Cavity Wall Insulation: Full Fill
3.04 Pitched Roof, Ventilated Rafter Void, Gable
Read in conjunction with
Masonry: Cavity Wall Insulation: Full Fill
Pitched Roof, Ventilated Rafter Void, Eaves
cavity closer (thin calcium
silicate board or similar)
lap roof and wall insulation,
roof insulation to be
compressed between sarking
and wall head
wall insulation should
be taken up level with
top of gable
fill gaps at top of gable
masonry with mortar to
form an even surface
roofing membrane
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Masonry: Cavity Wall Insulation: Full Fill
3.05 Pitched Roof, Ventilated Batten Void (warm roof), Eaves
Read in conjunction with
Masonry: Cavity Wall Insulation: Full Fill
Pitched Roof, Ventilated Batten Void (warm roof), Gable
ventilation to
batten void
proprietary over
fascia ventilator
30 minute fire resisting
cavity barrier
continuous ribbon of plaster
adhesive, sealing joint
between wall and ceiling
board
lap roof and wall insulation
minimum 50mm thickness at
narrowest point
consider sequence of construction,
see supplementary guidance
vapour permeable membrane
(with a vapour resistance of no more
than 0.25 MN.s/g)
support insulation between
rafters on battens or clips
inhabited space
Revision E
where two insulation
types are used together
see supplementary
guidance
ventilation gap equivalent to
5mm minimum continuous
opening is required at ridge
rigid insulation as sarking
vapour control layer
cavity closer (thin calcium
silicate board or similar)
restraint required for
insulation, for example
metal banding, wire
mesh or similar
material, fixed
between rafters
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
continuous ribbon of plaster
adhesive, sealing joint
between wall and ceiling
board
Revision E
vapour control layer
insulation between rafters
supported on battens or clips
ensure insulation is placed
between gable wall and last rafter
where two insulation types are
used together see supplementary
guidance
rigid insulation as sarking
Masonry: Cavity Wall Insulation: Full Fill
3.06 Pitched Roof, Ventilated Batten Void (warm roof), Gable
Read in conjunction with
Masonry: Cavity Wall Insulation: Full Fill
Pitched Roof, Ventilated Batten Void (warm roof), Eaves
cavity closer (thin calcium silicate
board or similar)
ventilation to tile batten
void
lap roof and wall insulation,
roof insulation to be
compressed between sarking
insulation and wall head
wall insulation should be taken
up level with top of gable
fill gaps at top of gable
masonry with mortar to
form an even surface
vapour permeable membrane
(with a vapour resistance of not
more than 0.25 MN.s/g)
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
continuous ribbon of plaster
adhesive, sealing joint between wall
and ceiling board
Revision E
vapour control layer turned up
edge of roof insulation, lapped
with roof waterproofing layer,
and sealed
fix full height blocking piece
and tightly pack mineral wool
into void and under deck
consider sequence of
construction, see supplementary
guidance
roofing membrane
vapour control layer
Masonry: Cavity Wall Insulation: Full Fill
3.07 Timber Flat Roof
declevity piece
cavity closer (thin calcium
silicate board or similar)
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
roofing membrane
continuous ribbon of plaster
adhesive, sealing joint
between wall and ceiling
board
vapour control layer
Revision E
vapour control layer turned up
edge of roof insulation, lapped
with roof waterproofing layer,
and sealed
minimum distance 300m
between top of edge
insulation and bottom of
roof insulation
place 20mm strip of insulation
with thermal conductivity (
value) not exceeding
0.025W/mK around parapet
flashing minimum 150mm
above finish roof level
render or impervious cladding
declevity piece
Masonry: Cavity Wall Insulation: Full Fill
3.08 Timber Flat Roof with Parapet
roofing membrane
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Revision E
steel lintel
continuous baseplate
steel lintel
perforated baseplate
sealant to back of
frame
continuous ribbon of
plaster adhesive,
sealing joint between
wall and board
sealant to front and back
of frame
sealant to front
of frame
continuous ribbon of
plaster adhesive, sealing
joint between wall and
board
Masonry: Cavity Wall Insulation: Full Fill
3.09 Windows and doors, Lintel
15mm strip of insulation with
thermal conductivity ( value)
not exceeding 0.025W/mK
N.B. in certain
circumstances the lintel
will require fire
resistance - check with
lintel manufacturer
weep hole taken through
render
weep hole taken through
render
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
folded steel lintel
no baseplate
folded steel lintel
Revision E
continuous baseplate
sealant to front
of frame sealant to front and
back of frame
continuous ribbon of
plaster adhesive,
sealing joint between
wall and board
continuous ribbon of plaster
adhesive, sealing joint
between wall and board
Masonry: Cavity Wall Insulation: Full Fill
3.10 Windows and doors, Folded Lintel
15mm strip of insulation with
thermal conductivity ( value)
not exceeding 0.025W/mK
N.B. in certain
circumstances the lintel
will require fire
resistance - check with
lintel manufacturer
weep hole taken
through render
weep hole taken
through render
weep hole taken through
render
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
insulation brought down to
window opening and cavity closed
cavity tray with a minimum
upstand of 140mm and stop ends
any lintel type can be used
Revision D
sealant to back of frame
sealant to front of frame
continuous ribbon of plaster
adhesive, sealing joint between wall
and board
Masonry: Cavity Wall Insulation: Full Fill
3.11 Windows and doors, Independent Lintel
weep hole taken through render
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
sealant to front and
back of sill
plan view
Revision E
continuous ribbon of plaster
adhesive, sealing joint between
wall and board
sealant to front and
back of sill
Masonry: Cavity Wall Insulation: Full Fill
3.12 Windows and doors, Jambs and sills
insulation between
packing pieces
sealant to front of
frame
section view
insulation between
packing pieces
sealant to back of
frame
continuous ribbon
of plaster
adhesive, sealing
joint between wall
and board
damp proof course
damp proof course
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
wall insulation continued at
least 150mm below top of
floor insulation
Revision E
damp proof course
external ground level
Masonry: Cavity Wall Insulation: Full-Fill
3.13 Ground Bearing Floor. Insulation Above Slab
vapour control layer
under timber floor finish
damp proof membrane
above or below slab
20mm strip of perimeter
insulation with thermal
conductivity (value) not
exceeding 0.025W/mK should be
installed around any screed
continuous ribbon of plaster
adhesive, sealing joint between wall
and board
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
external ground level
Masonry: Cavity Wall Insulation: Full Fill
3.14 Ground Bearing Floor, Insulation Below Slab
wall insulation continued at
least 150mm below top of
floor insulation
damp proof course
damp proof membrane
Revision E
20mm strip of perimeter
insulation with thermal
conductivity ( value) not
exceeding 0.025W/mK around
slab and any screed
continuous ribbon of plaster
adhesive, sealing joint between wall
and board
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Revision E
external ground level
wall insulation continued at
least 150mm below top of
perimeter insulation
damp proof course
damp proof membrane
Cavity Wall Insulation: Full Fill
3.15 Raft Foundation
20mm strip of perimeter
insulation with thermal
conductivity ( value) not
exceeding 0.025W/mK around
slab and any screed
continuous ribbon of plaster
adhesive, sealing joint between wall
and board
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
vapour control layer
under timber floor finish
Revision E
external ground level
wall insulation continued at
least 150mm below top of
floor insulation
damp proof course
damp proof membrane
Masonry: Cavity Wall Insulation: Full Fill
3.16 In-situ Suspended Ground Floor Slab, Insulation above Slab
20mm strip of perimeter
insulation with thermal
conductivity (value) not
exceeding 0.025W/mK around
any screed
continuous ribbon of plaster
adhesive, sealing joint between wall
and board
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Revision E
external ground level
wall insulation continued at
least 150mm below top of
perimeter insulation
damp proof course
damp proof membrane
20mm strip of perimeter
insulation with thermal
conductivity (value) not
exceeding 0.025W/mK
should be installed
around slab and any
screed
Masonry: Cavity Wall Insulation: Full Fill
3.17 In-situ Suspended Ground Floor Slab, Insulation Below Slab
dense blocks should not be
used below slab
continuous ribbon of
plaster adhesive, sealing
joint between wall and
board
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
vapour control layer under
timber floor finish
sub floor ventilation should
be provided, minimum
1500mm per metre run of
external wall or 500mm per
m floor area
Revision E
damp proof course
external ground level
wall insulation continued at
least 150mm below top of
floor insulation
damp proof membrane
solum
Masonry: Cavity Wall Insulation: Full Fill
3.18 Concrete Beam and Block Suspended Ground Floor
20mm strip of perimeter
insulation with thermal
conductivity ( value) not
exceeding 0.025W/mK
should be installed around
any screed
continuous ribbon of plaster
adhesive, sealing joint between wall
and board
cavity barrier type sleeve
through cavity
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
insulation directly under
flooring - supported either
on battens or on netting
draped over joists and
stapled at required depths
Revision E
damp proof course
external ground level
wall insulation continued at
least 150mm below top of
floor insulation
sub floor ventilation should be
provided, minimum 1500mm per metre
run of external wall or 500mm per m
floor area
expanding foam and
continuous sealant
20mm strip of perimeter
insulation with thermal
conductivity ( value) not
exceeding 0.025W/mK should be
installed between wall and last
joist
solum
Masonry: Cavity Wall Insulation: Full Fill
3.19 Timber Suspended Ground Floor
floor joist ends supported
on joist hangers or using
scarcement wall
continuous ribbon of plaster
adhesive, sealing joint between wall
and board
damp proof membrane
cavity barrier type sleeve
through cavity
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
plan view
Revision D
plan view
Masonry: Cavity Wall Insulation: Full Fill
3.20 Separating Wall
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
continuous ribbon of plaster
adhesive, sealing joint
between wall and board
wall insulation continued
across floor zone
gaps between wall and
floor sealed
Revision D
Masonry: Cavity Wall Insulation: Full Fill
3.21 Concrete Intermediate Floor
continuous ribbon of plaster
adhesive, sealing joint
between wall and board
separating floors require
additional layers and
components to comply with
Section 2: Fire and
Section 5: Noise
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
continuous ribbon of plaster
adhesive, sealing joint
between wall and board
Revision D
wall insulation continued
across floor zone
Masonry: Cavity Wall Insulation: Full Fill
3.22 Timber Intermediate Floor
separating floors require
additional layers and
components to comply with
Section 2: Fire and
Section 5: Noise
continuous ribbon of plaster
adhesive, sealing joint
between wall and board
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
plaster or plasterboard
on dabs
inner leaf (block shown)
outer leaf (brick shown)
partial fill cavity wall insulation
Revision C
render finish if required/desired
4.00 Masonry: Cavity Wall Insulation: Partial Fill
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Masonry: Cavity Wall Insulation: Partial Fill
4.01 Pitched Roof. Ventilated Roofspace. Eaves.
Revision D
proprietary cross flow
ventilator to maintain
minimum 25mm air gap
lap roof and wall insulation, minimum
50mm thickness at narrowest point
consider sequence of construction,
see supplementary guidance
roofing membrane
continuous ribbon of plaster
adhesive, sealing joint
between wall and ceiling
board
ventilation gap equivalent to 5mm
minimum continuous opening at ridge is
required where the roof pitch is
greater than 35 or the roof span is
more than 10m
sarking board
ventilation gap equivilent to 10mm
minimum continuous opening is
required where the roof pitch is
below 15
or
ventilation gap equivilent to
25mm minimum continuous
opening is required where the
roof pitch is 15 or above
insect mesh should be installed
30 minute fire resisting
cavity barrier (thin calcium
silicate board or similar)
Read in conjunction with
Masonry: Cavity Wall
Insulation : Partial Fill,
Ventilated Loft, Gable.
restraint required for insulation,
for example metal banding, wire
mesh or similar material, fixed
between rafters
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Masonry: Cavity Wall Insulation: Partial-Fill
4.02 Pitched Roof. Ventilated Roofspace. Gable.
continuous ribbon of plaster
adhesive, sealing joint
between wall and ceiling
board
Revision C
continue wall insulation to
top of gable or stop wall
insulation 270mm above
bottom of ceiling tie
place loft insulation between
last truss and gable wall
Read in conjunction with
Masonry: External Wall Insulation
Pitched Roof, Ventilated Roofspace, Eaves
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
proprietary cross flow
ventilator to maintain minimum
25mm air gap
roofing membrane
inhabited space
where two insulation
types are used together
see supplementary
guidance
Masonry: Cavity Wall Insulation - Partial Fill
4.03 Pitched Roof, Ventilated Rafter Void, Eaves
Revision E
ventilation gap equivalent to
25mm minimum continuous
opening
ventilation gap equivalent
to 5mm minimum
continuous opening at ridge
is required
50mm air gap
sarking board
lap roof and wall insulation
minimum 50mm thickness at
narrowest point - consider
sequence of construction
see supplementary guidance
vapour control layer
30 minute fire resisting
cavity barrier
continuous ribbon of
plaster adhesive, sealing
joint between wall and
ceiling board
30 minute fire resisting
cavity barrier (thin
calcium silicate board or
similar)
Read in conjunction with
Masonry: Cavity Wall Insulation: Partial Fill
Pitched Roof, Ventilated Rafter Void, Gable
restraint required for insulation,
for example metal banding, wire
mesh or similar material, fixed
between rafters
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Revision D
Masonry: Cavity Wall Insulation: Partial Fill
4.04 Pitched Roof, Ventilated Rafter Void, Gable
continuous ribbon of plaster
adhesive, sealing joint
between wall and ceiling
board
50mm ventilation
path over insulation
vapour control layer
where two insulation types are
used together see
supplementary guidance
sarking board
Read in conjunction with
Masonry: Cavity Wall Insulation: Partial Fill
Pitched Roof, Ventilated Rafter Void, Eaves
30 minute fire resisting
cavity barrier (thin calcium
silicate board or similar)
lap roof and wall insulation,
roof insulation to be
compressed between sarking
and wall head
wall insulation should
be taken up level with
top of gable
fill gaps at top of gable
masonry with mortar to
form an even surface
roofing membrane
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Masonry: Cavity Wall Insulation: Partial Fill
4.05 Pitched Roof. Ventilated Batten Void (warm roof). Eaves.
Revision C
ventilation to
batten void
30 minute fire resisting
cavity barrier
continuous ribbon of plaster
adhesive, sealing joint
between wall and ceiling
board
support insulation between
rafters on battens or clips
inhabited space
where two insulation
types are used together
see supplementary
guidance
ventilation gap equivalent to
5mm minimum continuous
opening is required at ridge
rigid insulation as sarking
Read in conjunction with
Masonry: Cavity Wall Insulation: Partial Fill
Pitched Roof, Ventilated Batten Void (warm roof), Gable
proprietary over
fascia ventilator
lap roof and wall insulation
minimum 50mm thickness at
narrowest point
consider sequence of construction,
see supplementary guidance
vapour permeable membrane
(with a vapour resistance of no more
than 0.25 MN.s/g)
vapour control layer
30 minute fire resisting
cavity barrier (thin calcium
silicate board or similar)
restraint required for
insulation, for example
metal banding, wire
mesh or similar
material, fixed between
rafters
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
vapour permeable membrane
(with a vapour resistance of
no more than 0.25 MN.s/g)
continuous ribbon of plaster
adhesive, sealing joint
between wall and ceiling
board
Revision D
vapour control layer
insulation between rafters
supported on battens or clips
ensure insulation is placed
between gable wall and last rafter
Masonry: Cavity Wall Insulation - Partial Fill
4.06 Pitched Roof, Ventilated Batten Void (warm roof), Gable
Read in conjunction with
Masonry: Cavity Wall Insulation - Partial Fill
Pitched Roof, Ventilated Batten Void (warm roof), Eaves
where two insulation types are
used together see supplementary
guidance
rigid insulation as sarking
30 minute fire resisting cavity
barrier (thin calcium silicate
board or similar)
lap roof and wall insulation,
roof insulation to be
compressed between sarking
and wall head
wall insulation should
be taken up level with
top of gable
fill gaps at top of gable
masonry with mortar to
form an even surface
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
continuous ribbon of plaster
adhesive, sealing joint
between wall and ceiling
board
Revision D
vapour control layer turned up
edge of roof insulation, lapped
with roof waterproofing layer
and sealed
fix full height blocking piece
and tightly pack mineral wool
into void and under deck
consider sequence of
construction, see supplementary
guidance
roofing membrane
vapour control layer
Masonry: Cavity Wall Insulation - Partial Fill
4.07 Timber Flat Roof
30 minute fire resisting
cavity barrier (thin calcium
silicate board or similar)
declevity piece
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
roofing membrane
continuous ribbon of plaster
adhesive, sealing joint
between wall and ceiling
board
vapour control layer
Revision E
vapour control layer turned up
edge of roof insulation, lapped
with roof waterproofing layer,
and sealed
minimum distance 300mm
between top of edge
insulation and bottom of
roof insulation
place 20mm strip of insulation
with thermal conductivity (
value) not exceeding
0.025W/mK around parapet
flashing minimum 150mm
above finish roof level
Masonry: Cavity Wall Insulation - Partial Fill
4.08 Timber Flat Roof with Parapet
render or impervious cladding
declevity piece
roofing membrane
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Revision C
sealant to back of
frame
continuous ribbon of
plaster adhesive,
sealing joint between
wall and board
Masonry: Cavity Wall Insulation: Partial Fill
4.09 Lintel at Window Head
note that the same
principal applies at the
head of doors
steel lintel
continuous baseplate
steel lintel
perforated baseplate
sealant to front and back
of frame
sealant to front
of frame
continuous ribbon of plaster
adhesive, sealing joint
between wall and board
15mm strip of insulation
with thermal conductivity (
value) not exceeding
0.025W/mK
N.B. in certain
circumstances the lintel
will require fire
resistance - check with
lintel manufacturer
N.B. in areas of extreme
exposure, a cavity tray
type damp proof course
will be applied on top of
the lintel - check with
lintel manufacturer
weep hole taken through
render
weep hole taken through
render
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Masonry: Cavity Wall Insulation: Partial-Fill
4.10 Windows and doors. Folded Lintel
sealant to back of
frame
continuous ribbon of
plaster adhesive,
sealing joint between
wall and board
15mm strip of insulation with
thermal conductivity ( value)
not exceeding 0.025W/mK
Revision C
N.B. in certain circumstances
the lintel will require fire
resistance - check with lintel
manufacturer
N.B. in areas of extreme
exposure, a cavity tray type
DPC will be applied on top of
the lintel - check with lintel
manufacturer
steel lintel
steel lintel with
continuous base plate
sealant to front and back
of frame
sealant to front
of frame
continuous ribbon of plaster
adhesive, sealing joint between
wall and board
weep hole taken
through render
weep hole taken
through render
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Masonry: Cavity Wall Insulation: Partial-Fill
4.11 Windows and doors. Independent Lintel
any lintel types
can be used
insulation brought down to window
opening and cavity closed
cavity tray with minimum
upstand of 140mm and stop
ends
sealant to back of frame
weep hole taken through render
continuous ribbon of plaster adhesive
sealing joint between wall and board
Revision B
sealant to front of frame
30 minute fire resisting cavity barrier
(thin calcium silicate board or similar)
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Masonry: Cavity Wall Insulation: Partial Fill
4.12 Windows and doors. Jambs and sills
plan view
Revision D
sealant to front and
back of sill
continuous ribbon of plaster
adhesive, sealing joint between
wall and board
sealant to front and
back of sill
insulation brought to
underside of sill and 30
minute fire resisting
proprietary fire /
insulating cavity barrier
incorporating damp proof
course
sealant to front of
frame
insulation brought to window frame and 30
minute fire resisting proprietary fire /
insulating cavity barrier incorporating damp
proof course
sealant to back of
frame
continuous ribbon of plaster
adhesive, sealing joint between
wall and board
section view
damp proof course
damp proof course
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
wall insulation continued at
least 150mm below top of
floor insulation
Revision C
damp proof membrane
above or below slab
damp proof course
external ground level
Masonry: Cavity Wall Insulation: Partial Fill
4.13 Ground Bearing Floor. Insulation Above Slab
vapour control layer
under timber floor finish
N.B. 20mm strip of perimeter
insulation with thermal
conductivity (value) not
exceeding 0.025W/mK should be
installed around any screed
continuous ribbon of plaster
adhesive, sealing joint between wall
and board
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Masonry: Cavity Wall Insulation: Partial Fill
4.14 Ground Bearing Floor. Insulation Below Slab
external ground level
wall insulation continued at
least 150mm below top of
floor insulation
damp proof course
damp proof membrane
20mm strip of perimeter
insulation with thermal
conductivity ( value) not
exceeding 0.025W/mK around
slab and any screed
continuous ribbon of
plaster adhesive sealing
joint between wall and
wallboard
Revision C
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Masonry: Cavity Wall Insulation: Partial-Fill
4.15 Raft Foundation
external ground level
wall insulation continued at
least 150mm below top of
perimeter insulation
damp proof course
damp proof membrane
20mm strip of perimeter
insulation with thermal
conductivity ( value) not
exceeding 0.025W/mK around
slab and any screed
Revision D
continuous ribbon of
plaster adhesive sealing
joint between wall and
wallboard
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Masonry: Cavity Wall Insulation: Partial Fill
4.16 In-situ Suspended Ground Floor Slab, Insulation above Slab
vapour control layer
under timber floor finish
external ground level
wall insulation continued at
least 150mm below top of
floor insulation
damp proof course
damp proof membrane
Revision D
continuous ribbon of
plaster adhesive sealing
joint between wall and
wallboard
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Revision C
external ground level
wall insulation continued at
least 150mm below top of
perimeter insulation
damp proof course
damp proof membrane
20mm strip of perimeter
insulation with thermal
conductivity (value) not
exceeding 0.025W/mK
should be installed
around slab and any
screed
Masonry: Cavity Wall Insulation: Partial Fill
4.17 In-situ Suspended Ground Floor Slab, Insulation Below Slab
dense blocks should not be
used below slab
continuous ribbon of
plaster adhesive sealing
joint between wall and
wallboard
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
vapour control layer under
timber floor finish
sub floor ventilation should
be provided, minimum
1500mm per metre run of
external wall or 500mm per
m floor area
Revision C
damp proof course
external ground level
wall insulation continued at
least 150mm below top of
floor insulation
damp proof membrane
solum
Masonry: Cavity Wall Insulation: Partial Fill
4.18 Concrete Beam and Block Suspended Ground Floor
continuous ribbon of plaster
adhesive sealing joint between
wall and board
cavity barrier type sleeve
through cavity
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Masonry: Cavity Wall Insulation: Partial-Fill
4.19 Timber Suspended Ground Floor
insulation directly under
flooring - supported either
on battens or on netting
draped over joists and
stapled at required depths
damp proof course
external ground level
wall insulation continued at
least 150mm below top of
floor insulation
sub floor ventilation should
be provided, minimum
1500mm per metre run of
external wall or 500mm per
m floor area
flexible insulation/expanding
foam and continuous sealant
20mm strip of perimeter insulation
with thermal conductivity ( value)
not exceeding 0.025W/mK should be
installed between wall and last joist
solum
floor joist ends supported
on joist hangers or using
scarcement wall
Revision B
continuous ribbon of plaster
adhesive sealing joint
between wall and board
damp proof membrane
cavity barrier type sleeve
through cavity
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Masonry: Cavity Wall Insulation: Partial Fill
4.20 Separating Wall
plan view
Revision B
plan view
damp proof course
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
continuous ribbon of plaster
adhesive, sealing joint
between wall and ceiling
board
wall insulation continued
across floor zone
gaps between wall and
floor sealed
Revision B
Masonry: Cavity Wall Insulation: Partial Fill
4.21 Concrete Intermediate Floor
continuous ribbon of plaster
adhesive, sealing joint
between wall and board
separating floors require
additional layers and
components to comply with
Section 2: Fire and
Section 5: Noise
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Masonry: Cavity Wall Insulation: Partial Fill
4.22 Timber Intermediate Floor
Revision B
continuous ribbon of plaster
adhesive, sealing joint
between wall and ceiling
board
separating floors require
additional layers and
components to comply with
Section 2: Fire and
Section 5: Noise
continuous ribbon of plaster
adhesive, sealing joint
between wall and board
wall insulation continued
across floor zone
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
plaster or plasterboard
outer leaf (brick shown)
internally applied insulation system
(various fixing methods)
5.00 Masonry: Internal Wall Insulation
Revision B
render finish if required/desired
inner leaf (block shown)
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
proprietary cross flow
ventilator to maintain
minimum 25mm air gap
lap roof and wall insulation,
minimum 50mm thickness at
narrowest point
consider sequence of construction,
see supplementary guidance
roofing membrane
continuous ribbon of plaster
adhesive, sealing joint
between wall and ceiling
board
ventilation gap equivilent to 10mm
minimum continuous opening is
required where the roof pitch is
below 15
or
ventilation gap equivilent to
25mm minimum continuous
opening is required where the
roof pitch is 15 or above
insect mesh should be installed
Revision C
Read in conjunction with
Masonry: Internal Wall Insulation
Pitched Roof, Ventilated Roofspace, Gable
ventilation gap equivalent to 5mm
minimum continuous opening at ridge is
required where the roof pitch is
greater than 35 or the roof span is
more than 10m
sarking board
30 minute fire resisting
cavity barrier (thin calcium
silicate board or similar)
Masonry: Internal Wall Insulation
5.01 Pitched Roof, Ventilated Roofspace, Eaves
restraint required for insulation,
for example metal banding, wire
mesh or similar material, fixed
between rafters
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
continuous ribbon of plaster
adhesive, sealing joint
between wall and ceiling
board
insulation between last truss
and gable wall
Revision A
Read in conjunction with
Masonry: Internal Wall Insulation
Pitched Roof, Ventilated Roofspace, Eaves
Masonry: Internal Wall Insulation
5.02 Pitched Roof. Ventilated Roofspace. Gable.
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
30 minute fire
resisting cavity
barrier
continuous ribbon of plaster
adhesive, sealing joint
between wall and ceiling
board
proprietary cross flow
ventilator to maintain minimum
25mm air gap
roofing membrane
inhabited space
where two insulation
types are used together
see supplementary
guidance
Revision C
Read in conjunction with
Masonry: External Wall Insulation
Pitched Roof, Ventilated Rafter Void, Gable
ventilation to roofspace
sarking board
ventilation gap equivalent
to 5mm minimum
continuous opening at ridge
is required
lap roof and wall insulation,
minimum 50mm thickness at
narrowest point
consider sequence of construction,
see supplementary guidance
vapour control layer
ventilation gap equivilent to
25mm minimum continuous
opening
insect mesh should be installed
Masonry: Internal Wall Insulation
5.03 Pitched Roof, Ventilated Rafter Void, Eaves
30 minute fire
resisting cavity barrier
(thin calcium silicate
board or similar)
50mm air gap
sarking board
restraint required for insulation,
for example metal banding, wire
mesh or similar material, fixed
between rafters
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
continuous ribbon of plaster
adhesive, sealing joint
between wall and ceiling
board
Revision C
Read in conjunction with
Masonry: Internal Wall Insulation
Pitched Roof, Ventilated Rafter Void, Eaves
50mm ventilation
path over insulation
where two insulation types are
used together see
supplementary guidance
sarking board
Masonry: Internal Wall Insulation
5.04 Pitched Roof. Ventilated Rafter Void. Gable.
lap roof and wall insulation,
roof insulation to be
compressed between sarking
and wall head
wall insulation should
be taken up level with
top of gable
fill gaps at top of gable
masonry with mortar to
form an even surface
roofing membrane
30 minute fire resisting
cavity barrier (thin calcium
silicate board or similar)
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Masonry: Internal Wall Insulation
5.05 Pitched Roof, Ventilated Batten Void (warm roof), Eaves.
ventilation to
batten void
vapour control layer
proprietary over
fascia ventilator
30 minute fire resisting
cavity barrier
continuous ribbon of plaster
adhesive, sealing joint
between wall and ceiling
board
lap roof and wall insulation
minimum 50mm thickness at
narrowest point
consider sequence of construction,
see supplementary guidance
vapour permeable membrane (with a
vapour resistance of no more than
0.25 MN.s/g)
support insulation between
rafters on battens or clips
inhabited space
Revision C
Read in conjunction with
Masonry: Internal Wall Insulation
Pitched Roof, Ventilated Batten Void (warm roof), Gable
where two insulation
types are used together
see supplementary
guidance
ventilation gap equivalent to
5mm minimum continuous
opening is required at ridge
rigid insulation as sarking
30 minute fire resisting
cavity barrier (thin calcium
silicate board or similar)
restraint required for
insulation, for example
metal banding, wire
mesh or similar
material, fixed
between rafters
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Revision C
Masonry: Internal Wall Insulation
5.06 Pitched Roof, Ventilated Batten Void (warm roof), Gable
Read in conjunction with
Masonry: Internal Wall Insulation
Pitched Roof, Ventilated Batten Void (warm roof), Eaves
continuous ribbon of plaster
adhesive, sealing joint
between wall and ceiling
board
vapour control layer
insulation between rafters
supported on battens or clips
ensure insulation is placed
between gable wall and last rafter
where two insulation types are
used together see supplementary
guidance
rigid insulation as sarking
vapour permeable membrane
(with a vapour resistance of
no more than 0.25 MN.s/g)
lap roof and wall insulation,
roof insulation to be
compressed between sarking
and wall head
fill gaps at top of gable
masonry with mortar to
form an even surface
30 minute fire resisting cavity
barrier (thin calcium silicate
board or similar)
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
continuous ribbon of plaster
adhesive, sealing joint
between wall and ceiling
board
Revision C
vapour control layer turned up
edge of roof insulation, lapped
with roof waterproofing layer,
and sealed
fix full height blocking piece
and tightly pack mineral wool
into void and under deck
consider sequence of
construction, see supplementary
guidance
roofing membrane
vapour control layer
Masonry: Internal Wall Insulation
5.07 Timber Flat Roof
declevity piece
30 minute fire resisting
cavity barrier (thin calcium
silicate board or similar)
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
roofing membrane
continuous ribbon of plaster
adhesive, sealing joint
between wall and ceiling
board
vapour control layer
Revision D
vapour control layer turned up
edge of roof insulation, lapped
with roof waterproofing layer,
and sealed
minimum distance 300mm
between top of edge
insulation and bottom of
roof insulation
place 20mm strip of insulation
with thermal conductivity (
value) not exceeding
0.025W/mK around parapet
flashing minimum 150mm
above finish roof level
Masonry: Internal Wall Insulation
5.08 Timber Flat Roof with Parapet
render or impervious cladding
declevity piece
roofing membrane
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Masonry: Internal Wall Insulation
5.09 Lintel at Window Head.
Revision C
The same thermal principles apply at the head of doors
N.B. in certain circumstances the
lintel will require fire resistance
- check with lintel manufacturer
N.B. in areas of extreme
exposure, a cavity tray type DPC
will be applied on top of the lintel
- check with lintel manufacturer
steel lintel
continuous baseplate
sealant to back of frame
sealant to front
of frame
continuous ribbon of plaster
adhesive, sealing joint between
wall and board
weep hole taken
through render 15mm strip of insulation with
thermal conductivity ( value)
not exceeding 0.025W/mK
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Masonry: Internal Wall Insulation
5.10 Windows and doors, Folded Lintel
Revision C
The same thermal principles apply at the head of doors
folded steel lintel
continuous baseplate
sealant to back of frame
sealant to front of frame
continuous ribbon of plaster
adhesive, sealing joint
between wall and board
N.B. in certain circumstances the
lintel will require fire resistance -
check with lintel manufacturer
N.B. in areas of extreme exposure,
a cavity tray type DPC will be
applied on top of the lintel - check
with lintel manufacturer
15mm strip of insulation with
thermal conductivity value)
not exceeding 0.025W/mK
weep hole taken through
render
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Masonry: Cavity Wall Insulation: Partial-Fill
5.11 Windows and doors. Jambs and sills
30 minute fire
resisting proprietary
fire / insulating cavity
barrier, incorporating
damp proof course
30 minute fire resisting proprietary fire / insulating
cavity barrier, incorporating damp proof course
sealant to front of frame
plan View
section view
Revision D
wall insulation carried
up to underside of sill
continuous ribbon of plaster
adhesive, sealing joint between wall
and board
sealant to back of frame
sealant to front and back
of sill
damp proof course
continuous ribbon of
plaster adhesive,
sealing joint between
wall and board
15mm strip of insulation
with thermal conductivity
value) not exceeding
0.025W/mK
15mm strip of insulation
with thermal conductivity
value) not exceeding
0.025W/mK
damp proof course
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Masonry: Internal Wall Insulation
5.12 Ground Bearing Floor. Insulation Above Slab
external ground level
damp proof course
vapour control layer
under timber floor finish
damp proof membrane
above or below slab
Revision D
20mm strip of perimeter
insulation with thermal
conductivity (value) not
exceeding 0.025W/mK should be
installed around any screed
flexible insulation /expanding foam
continuous ribbon of plaster adhesive
applied to perimeter of wall
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Masonry: Internal Wall Insulation
5.13 Ground Bearing Floor. Insulation Below Slab
external ground level
damp proof course
damp proof membrane
20mm strip of perimeter
insulation with thermal
conductivity (value) not
exceeding 0.025W/mK should be
installed around slab and any
screed
Revision D
flexible insulation /expanding foam
continuous ribbon of plaster
adhesive applied to perimeter of wall
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Masonry: Internal Wall Insulation
5.14 Raft Foundation
external ground level
damp proof course
damp proof membrane
20mm strip of perimeter
insulation with thermal
conductivity (value) not
exceeding 0.025W/mK should be
installed around slab and any
screed
Revision D
flexible insulation /expanding foam
continuous ribbon of plaster
adhesive applied to perimeter of wall
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Masonry: Internal Wall Insulation
5.15 In-situ Suspended Ground Floor Slab Insulation above Slab
Revision D
external ground level
vapour control layer
under timber floor finish
damp proof membrane
damp proof course
flexible insulation /expanding foam
continuous ribbon of plaster
adhesive applied to perimeter of wall
20mm strip of perimeter
insulation with thermal
conductivity ( value) not
exceeding 0.025W/mK should
be installed around any screed
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Masonry: Internal Wall Insulation
5.16 Concrete Beam & Block Suspended Ground Floor
external ground level
vapour control layer
under timber floor finish
damp proof course
damp proof membrane
Revision D
solum
sub floor ventilation should
be provided, minimum
1500mm per metre run of
external wall or 500mm per
m floor area
flexible insulation /expanding
foam
20mm strip of perimeter
insulation with thermal
conductivity ( value) not
exceeding 0.025W/mK should be
installed around any screed
cavity barrier type sleeve
through cavity
continuous ribbon of plaster
adhesive applied to perimeter
of wall
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Masonry: Internal Wall Insulation
5.17 Timber Suspended Ground Floor
insulation directly under
flooring - supported either
on battens or on netting
draped over joists and
stapled at required depths
external ground level solum
sub floor ventilation should be
provided, minimum 1500mm per
metre run of external wall or
500mm per m floor area
floor joist ends supported
on joist hangers or using
scarcement wall
Revision C
20mm strip of perimeter
insulation with thermal
conductivity ( value) not
exceeding 0.025W/mK
should be installed between
wall and last joist
flexible insulation /expanding foam
continuous ribbon of plaster adhesive
applied to perimeter of wall
cavity barrier type sleeve
through cavity and cavity
tray type damp proof course
locally over sleeve
damp proof membrane
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Masonry: Internal Wall Insulation
5.18 Separating Wall
Plan View
Revision C
damp proof course
continuous ribbon
of plaster
adhesive applied
to perimeter of
wall
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Masonry: Internal Wall Insulation
5.19 Concrete Intermediate Floor
continuous ribbon of plaster
adhesive, sealing joint between
wall and board
gaps between wall and floor
sealed
Revision C
insulation should be installed in
cavity projecting minimum
100mm above and below floor
zone (insulation may need to be
damp proof course faced in
areas of severe exposure)
100mm
100mm
flexible insulation /expanding foam
continuous ribbon of plaster adhesive
applied to perimeter of wall
separating floors require
additional layers &
components to comply with
Section 2: Fire and
Section 5: Noise
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Masonry: Internal Wall Insulation
5.20 Timber Intermediate Floor
continuous ribbon of plaster
adhesive, sealing joint
between wall and board
separating floors require
additional layers &
components to comply with
Section 2: Fire and
Section 5: Noise
Revision C
20mm strip of insulation with
thermal conductivity ( value)
not exceeding 0.025W/mK
continued accross floor zone
flexible insulation /expanding foam
continuous ribbon of plaster
adhesive applied to
perimeter of wall
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
plasterboard
sheathing board
outer leaf (brick shown)
Revision B
render finish if required/desired
6.00 Timber Frame
vapour control layer
structural timber frame
insulation
vapour permeable membrane (with a vapour
resistance of no more than 0.6 MN.s/g)
cavity
stainless steel wall tie
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
vapour permeable membrane (with a
vapour resistance of no more than
0.6 MN.s/g)
cavity barrier giving 30 minute fire
resistance - ensure cavity barrier is
not breeched by inappropriate
insulation material in timber frame
Timber Frame
6.01 Pitched Roof, Ventilated Roofspace, Eaves
proprietary cross flow
ventilator to maintain
minimum 25mm air gap
lap roof and wall insulation,
minimum 50mm thickness at
narrowest point
consider sequence of construction,
see supplementary guidance
roofing membrane
ventilation gap equivilent to 10mm
minimum continuous opening is
required where the roof pitch is
above 15
or
ventilation gap equivilent to
25mm minimum continuous
opening is required where the
roof pitch is below 15
insect mesh should be installed
Revision D
Read in conjunction with
Timber Frame
Pitched Roof, Ventilated Roofspace, Gable
ventilation gap equivalent to 5mm
minimum continuous opening at ridge is
required where the roof pitch is
greater than 35 or the roof span is
more than 10m
sarking board
vapour control layer
restraint required for insulation,
for example metal banding, wire
mesh or similar material, fixed
between rafters
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Timber Frame
6.02 Pitched Roof. Ventilated Roof Space. Gable
vapour control layer
loft insulation continued up
to sheathing of spandrel
panel
cavity barrier giving 30
minute fire resistance
vapour permeable membrane
(with a vapour resistance of
no more than 0.6 MN.s/g)
Revision C
Read in conjunction with
Timber Frame
Pitched Roof, Ventilated Roofspace, Eaves
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
30 minute fire resisting
cavity barrier
proprietary cross flow
ventilator to maintain minimum
25mm air gap
roofing membrane
inhabited space
where two insulation
types are used together
see supplementary
guidance
Timber Frame
6.03 Pitched Roof, Ventilated Rafter Void, Eaves
Revision C
Read in conjunction with
Timber Frame
Pitched Roof, Ventilated Rafter Void, Gable
sarking board
ventilation gap equivalent
to 5mm minimum
continuous opening at ridge
is required
50mm air gap
lap roof and wall insulation,
minimum 50mm thickness at
narrowest point
consider sequence of construction,
see supplementary guidance
vapour control layer
ventilation gap equivilent to
25mm minimum continuous
opening
insect mesh should be installed
vapour control layer
vapour permeable membrane
(with a vapour resistance of
no more than 0.6 MN.s/g)
cavity barrier giving 30 minute
fire resistance - ensure cavity
barrier is not breeched by
inappropriate insulation material
within timber frame
restraint required for insulation,
for example metal banding, wire
mesh or similar material, fixed
between rafters
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
differential movement gap sealed
with compressible foam or sealant
cavity barrier giving 30
minute fire resistance
50mm ventilation path over
insulation
lap roof and wall insulation, roof
insulation to be compressed
between sarking and timber frame
Revision C
Timber Frame
6.04 Pitched Roof, Ventilated Rafter Void, Gable
Read in conjunction with
Timber Frame
Pitched Roof, Ventilated Rafter Void, Eaves
vapour permeable membrane
(with a vapour resistance of
no more than 0.6 MN.s/g)
vapour control layer
sarking board
roofing membrane
where two insulation types are
used together see
supplementary guidance
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Timber Frame
6.05 Pitched Roof, Ventilated Batten Void (warm roof), Eaves.
ventilation to
batten void
vapour control layer
proprietary over
fascia ventilator
30 minute fire resisting
cavity barrier
lap roof and wall insulation
minimum 50mm thickness at
narrowest point
consider sequence of construction,
see supplementary guidance
vapour permeable membrane (with a
vapour resistance of not more than
0.6 MN.s/g)
support insulation between
rafters on netting, battens
or clips
inhabited space
Revision D
Read in conjunction with
Timber Frame
Pitched Roof, Ventilated Batten Void (warm roof), Gable
where two insulation
types are used together
see supplementary
guidance
ventilation gap equivalent to
5mm minimum continuous
opening is required at ridge to
batten space
rigid insulation as sarking
cavity barrier giving 30 minute fire
resistance - ensure cavity barrier is not
breeched by inappropriate insulation
material within timber frame
vapour control layer
vapour permeable membrane (with a
vapour resistance of no more than
0.6 MN.s/g)
restraint required for
insulation, for example
metal banding, wire
mesh or similar
material, fixed
between rafters
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
vapour permeable membrane
(with a vapour resistance of
no more than 0.25 MN.s/g)
ventilation to tile batten
void
lap roof and wall insulation,
roof insulation to be
compressed between
sarking and timber frame
Revision C
vapour control layer
insulation between rafters
supported on battens, clips or
netting
Timber Frame
6.06 Pitched Roof, Ventilated Batten Void (warm roof), Gable
Read in conjunction with
Timber Frame
Pitched Roof, Ventilated Batten Void (warm roof), Eaves
where two insulation types are
used together see supplementary
guidance
rigid insulation as sarking
cavity barrier giving 30
minute fire resistance
vapour control layer
differential movement gap sealed
with compressible foam or sealant
vapour permeable membrane
(with a vapour resistance of no
more than 0.6 MN.s/g)
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Revision D
vapour control layer turned up
edge of roof insulation, lapped
with roof waterproofing layer,
and sealed
eaves - fix full height blocking
piece and tightly pack mineral
wool into void and under deck
verge - tightly pack mineral wool
into void over wall and under
deck (not shown)
roofing membrane
vapour control layer
Timber Frame
6.07 Timber Flat Roof
declevity piece
vapour control layer
cavity barrier
vapour permeable membrane
(with a vapour resistance of
no more than 0.6 MN.s/g)
consider sequence of
construction, see supplementary
guidance
differential movement gap sealed
with compressible foam or sealant
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Revision A
vapour control layer
Timber Frame
6.08 Timber Flat Roof with Parapet
differential movement gap sealed
with compressible foam or sealant
cavity barrier giving 30 minute fire
resistance
vapour control layer turned up
edge of roof insulation, lapped
with roof waterproofing layer,
and sealed
roofing membrane to be taken
minimum 150mm above finished
roof level
declevity piece
vapour permeable membrane
(with a vapour resistance of
no more than 0.6 MN.s/g)
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
cavity barrier
giving 30 minute
fire resistance
vapour control layer
Revision E
Timber Frame
6.09 Lintel at Window Head
sealant to front
of frame
sealant to front and back
of frame
vapour permeable
membrane (with a vapour
resistance of no more
than 0.6 MN.s/g)
The same thermal principles apply at the head of doors.
steel lintel
vapour control layer
sealant to back of frame
vapour permeable
membrane (with a vapour
resistance of no more
than 0.6 MN.s/g)
N.B. in certain
circumstances the lintel will
require fire resistance -
check with lintel
manufacturer
N.B. in areas of extreme
exposure, a cavity tray
type DPC will be applied on
top of the lintel - check
with lintel manufacturer alternative for heavy duty lintel
10mm strip of insulation
with thermal conductivity
value) not exceeding
0.25W/mK
weep hole taken
through render
weep hole taken
through render
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
cavity barrier giving 30
minute fire resistance
sealant to front and back of
frame/sill
Plan View
Revision C
section view
Timber Frame
6.10 Windows and doors, Jambs and sills
sealant to front of frame
sealant to back of
frame
cavity barrier giving 30
minute fire resistance
damp proof course
damp proof course
vapour control layer
vapour permeable membrane
(with a vapour resistance of
no more than 0.6 MN.s/g)
vapour permeable membrane
(with a vapour resistance of
no more than 0.6 MN.s/g)
vapour control layer
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Revision D
vapour control layer
under timber floor finish
damp proof membrane
above or below slab
damp proof course
external ground level
Timber Frame
6.11 Ground Bearing Floor, Insulation Above Slab
20mm strip of perimeter
insulation with thermal
conductivity (value) not
exceeding 0.025W/mK should be
installed around any screed
vapour permeable membrane
(with a vapour resistance of
no more than 0.6 MN.s/g)
vapour control layer
perpend vent
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
external ground level
Timber Frame
6.12 Ground Bearing Floor, Insulation Below Slab
damp proof course
damp proof membrane
Revision D
20mm strip of perimeter
insulation with thermal
conductivity ( value) not
exceeding 0.025W/mK around
slab and any screed
vapour permeable membrane
(with a vapour resistance of
no more than 0.6 MN.s/g)
vapour control layer
perpend vent
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
vapour control layer under
timber floor finish
external ground level
damp proof course
damp proof membrane
Revision E
Timber Frame
6.13 Raft Foundation
vapour permeable membrane
(with a vapour resistance of
no more than 0.6 MN.s/g)
vapour control layer
20mm strip of perimeter
insulation with thermal
conductivity (value) not
exceeding 0.025W/mK around
slab and any screed
perpend vent
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
vapour control layer
under timber floor finish
Revision D
external ground level
damp proof course
damp proof membrane
Timber Frame
6.14 In-situ Suspended Ground Floor Slab. Insulation Above Slab
20mm strip of perimeter
insulation with thermal
conductivity (value) not
exceeding 0.025W/mK should be
installed around any screed
vapour permeable membrane
(with a vapour resistance of
no more than 0.6 MN.s/g)
vapour control layer
perpend vent
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
vapour control layer under
timber floor finish
sub floor ventilation should
be provided, minimum
1500mm per metre run of
external wall or 500mm per
m floor area
Revision C
damp proof course
external ground level
damp proof membrane
solum
Timber Frame
6.15 Concrete Beam and Block Ground Floor
20mm strip of perimeter
insulation with thermal
conductivity ( value) not
exceeding 0.025W/mK
should be installed around
any screed
vapour permeable membrane
(with a vapour resistance of
no more than 0.6 MN.s/g)
vapour control layer
cavity barrier type sleeve
through cavity
perpend vent
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
insulation directly under
flooring - supported either
on battens or on netting
draped over joists and
stapled at required depths
Revision D
damp proof course
external ground level
sub floor ventilation should
be provided, minimum
1500mm per metre run of
external wall or 500mm per
m floor area
expanding foam or
continuous sealant
solum
Timber Frame
6.16 Timber Suspended Ground Floor
vapour permeable membrane
(with a vapour resistance of
no more than 0.6 MN.s/g)
vapour control layer
damp proof membrane
perpend vent
cavity barrier type sleeve
through cavity
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Plan View
Revision D
Timber Frame
6.17 Separating Wall
acoustic insulation not shown
cavity barriers giving 30 minute fire
resistance, ensure cavity barriers
are not breeched by inappropriate
insulation material in the timber
frame
alternative corner details,
see Timber Frame, Wall
Junction
vapour permeable membrane
(with a vapour resistance of
no more than 0.6 MN.s/g)
vapour control layer
flexible cavity barrier
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
continuous bead of sealant
applied to floor deck prior to
positioning of upper wall panel
Revision E
Timber Frame
6.18 Timber Intermediate Floor
20mm strip of
insulation with thermal
conductivity (value)
not exceeding
0.025W/mK installed
around floor
perimeter
vapour control layer
vapour permeable membrane (with
a vapour resistance of no more
than 0.6 MN.s/g)
cavity barriers giving 30
minute fire resistance
separating floors require
additional layers and
components to comply with
Section 2: Fire and
Section 5: Noise
perpend vent
sealant between
skirting and floor
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
plan view
alternative detail where
required for structural reasons
- insulation placed in void
before wall panels are erected
standard corner
detail - insulation
tucked into corner
Revision C
Timber Frame
6.19 Wall Junction
vapour permeable membrane(with a
vapour resistance of no more than 0.6
MN.s/g)
vapour control layer
cavity barriers with 30 minute
fire resistance are not shown,
ensure that those provided are
not breeched by inappropriate
insulation in the timber frame
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
plasterboard
rigid insulated sheathing board
outer leaf (brick shown)
render finish if required/desired
7.00 Steel Frame
vapour control layer
structural light gauge steel frame
compressible mineral wool insulation
cavity
stainless steel wall tie in channels
fixed to stud structure through insulation
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
vapour control layer
cavity barrier giving 30 minute fire
resistance - ensure cavity barrier is
not breeched by inappropriate rigid
sheathing insulation material
Steel Frame
7.01 Pitched Roof, Ventilated Roofspace, Eaves
proprietary cross flow
ventilator to maintain
minimum 25mm air gap
lap roof and wall insulation,
minimum 50mm thickness at
narrowest point
consider sequence of construction,
see supplementary guidance
roofing membrane
ventilation gap equivilent to 10mm
minimum continuous opening is
required where the roof pitch is
above 15
or
ventilation gap equivilent to
25mm minimum continuous
opening is required where the
roof pitch is below 15
insect mesh should be installed
Read in conjunction with
Warm Steel Frame
Pitched Roof, Ventilated Roofspace, Gable
ventilation gap equivalent to 5mm
minimum continuous opening at ridge is
required where the roof pitch is
greater than 35 or the roof span is
more than 10m
sarking board
restraint required for insulation,
for example metal banding, wire
mesh or similar material, fixed
between rafters
mineral wool insulation between the studs
in addition to the rigid board over. This
insulation must be tightly packed and be in
direct contact with the rigid board
stainless steel wall tie in channels
fixed to stud structure through
insulation
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Steel Frame
7.02 Pitched Roof. Ventilated Roof Space. Gable
loft insulation continued up
to inner face of the rigid
sheathing insulant
Read in conjunction with
Steel Frame
Pitched Roof, Ventilated Roofspace, Eaves
cavity barrier giving 30 minute fire
resistance - ensure cavity barrier is
not breeched by inappropriate rigid
sheathing insulation material
mineral wool insulation between the
studs in addition to the rigid board
over.This insulation must be tightly
packed and be in direct contact with
the rigid board
vapour control layer
stainless steel wall tie in channels
fixed to stud structure through
insulation
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
30 minute fire resisting
cavity barrier
proprietary cross flow
ventilator to maintain minimum
25mm air gap
roofing membrane
inhabited space
where two insulation
types are used together
see supplementary
guidance
Steel Frame
7.03 Pitched Roof, Ventilated Rafter Void, Eaves
Read in conjunction with
Steel Frame
Pitched Roof, Ventilated Rafter Void, Gable
sarking board
ventilation gap equivalent
to 5mm minimum
continuous opening at ridge
is required
50mm air gap
lap roof and wall insulation,
minimum 50mm thickness at
narrowest point
consider sequence of construction,
see supplementary guidance
vapour control layer
ventilation gap equivilent to
25mm minimum continuous
opening
insect mesh should be installed
restraint required for insulation,
for example metal banding, wire
mesh or similar material, fixed
between rafters
mineral wool insulation between the
studs in addition to the rigid board
over.This insulation must be tightly
packed and be in direct contact with
the rigid board
vapour control layer
cavity barrier giving 30 minute fire
resistance - ensure cavity barrier is
not breeched by inappropriate rigid
sheathing insulation material
stainless steel wall tie in channels
fixed to stud structure through
insulation
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
differential movement gap sealed
with compressible foam or sealant
50mm ventilation path over
insulation
lap roof and wall insulation, roof
insulation to be compressed
between sarking and timber frame
Steel Frame
7.04 Pitched Roof, Ventilated Rafter Void, Gable
Read in conjunction with
Steel Frame
Pitched Roof, Ventilated Rafter Void, Eaves
sarking board
roofing membrane
where two
insulation types are
used together see
supplementary
guidance
cavity barrier giving 30 minute fire
resistance - ensure cavity barrier is
not breeched by inappropriate rigid
sheathing insulation material
mineral wool insulation between the
studs in addition to the rigid board
over.This insulation must be tightly
packed and be in direct contact with
the rigid board
vapour control layer
stainless steel wall tie in channels
fixed to stud structure through
insulation
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Steel Frame
7.05 Pitched Roof, Ventilated Batten
Void (warm roof), Eaves.
ventilation to
batten void
proprietary over
fascia ventilator
lap roof and wall insulation
minimum 50mm thickness at
narrowest point
consider sequence of construction,
see supplementary guidance
vapour permeable membrane (with a
vapour resistance of not more than
0.6 MN.s/g)
support insulation between
rafters on netting, battens
or clips
inhabited space
Read in conjunction with
Steel Frame
Pitched Roof, Ventilated Batten Void (warm roof), Gable
where two insulation
types are used together
see supplementary
guidance
ventilation gap equivalent
to 5mm minimum
continuous opening is
required at ridge to
batten space
rigid insulation as sarking
restraint required for
insulation, for example
metal banding, wire
mesh or similar
material, fixed
between rafters
cavity barrier giving 30 minute fire
resistance - ensure cavity barrier is
not breeched by inappropriate rigid
sheathing insulation material
mineral wool insulation between the
studs in addition to the rigid board
over.This insulation must be tightly
packed and be in direct contact with
the rigid board
vapour control layer
30 minute fire resisting
cavity barrier
vapour control layer
stainless steel wall tie in
channels
fixed to stud structure
through insulation
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
vapour permeable membrane
(with a vapour resistance of
no more than 0.25 MN.s/g)
ventilation to tile batten
void
lap roof and wall insulation,
roof insulation to be
compressed between
sarking and frame
insulation between rafters
supported on battens, clips or
netting
Steel Frame
7.06 Pitched Roof, Ventilated Batten Void (warm roof), Gable
Read in conjunction with
Steel Frame
Pitched Roof, Ventilated Batten Void (warm roof), Eaves
where two insulation types are
used together see
supplementary guidance
rigid insulation as sarking
vapour control layer
differential movement gap sealed
with compressible foam or sealant
cavity barrier giving 30 minute fire
resistance - ensure cavity barrier is
not breeched by inappropriate rigid
sheathing insulation material
mineral wool insulation between the
studs in addition to the rigid board
over. This insulation must be tightly
packed and be in direct contact with
the rigid board
vapour control layer
stainless steel wall tie in channels
fixed to stud structure through
insulation
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
vapour control layer turned up
edge of roof insulation, lapped
with roof waterproofing layer,
and sealed
eaves - fix full height blocking
piece and tightly pack mineral
wool into void and under deck
verge - tightly pack mineral wool
into void over wall and under
deck (not shown)
roofing membrane
vapour control layer
Steel Frame
7.07 Timber Flat Roof
declevity piece
consider sequence of
construction, see supplementary
guidance
differential movement gap sealed
with compressible foam or sealant
mineral wool insulation between the
studs in addition to the rigid board
over.This insulation must be tightly
packed and be in direct contact with
the rigid board
cavity barrier giving 30 minute fire
resistance - ensure cavity barrier is
not breeched by inappropriate rigid
sheathing insulation material
vapour control layer
stainless steel wall tie in channels
fixed to stud structure through
insulation
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Steel Frame
7.08 Timber Flat Roof with Parapet
differential movement gap sealed
with compressible foam or sealant
vapour control layer turned up
edge of roof insulation, lapped
with roof waterproofing layer,
and sealed
roofing membrane to be taken
minimum 150mm above finished
roof level
declevity piece
cavity barrier giving 30 minute fire
resistance - ensure cavity barrier is
not breeched by inappropriate rigid
sheathing insulation material
mineral wool insulation
between the studs in addition
to the rigid board over.This
insulation must be tightly
packed and be in direct
contact with the rigid board
vapour control layer
insulated upstand having a
minimum R value of 0.75 m2K/W
supported on a sheathing board
around the parapet
tightly packed compressible
insulant between the wall studs
above the level of the roof
deck
stainless steel wall tie in channels
fixed to stud structure through
insulation
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
proprietary cavity barrier
giving 30 minute fire
resistance
vapour control layer
Steel Frame
7.09 Lintel at Window Head
sealant to front
of frame
sealant to front and back
of frame
The same thermal principles apply at the head of doors.
steel lintel
vapour control layer
sealant to back of frame N.B. in certain
circumstances the lintel will
require fire resistance -
check with lintel
manufacturer
N.B. in areas of extreme
exposure, a cavity tray
type DPC will be applied on
top of the lintel - check
with lintel manufacturer alternative for heavy duty lintel
weep hole taken
through render
weep hole taken
through render
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
proprietary cavity barrier
giving 30 minute fire
resistance
sealant to front and back of
frame/sill
Plan View
section view
Steel Frame
7.10 Windows and doors, Jambs and sills
sealant to front of frame
sealant to back of
frame
proprietary cavity barrier
giving 30 minute fire
resistance
damp proof course
damp proof course
vapour control layer
vapour control layer
stainless steel wall tie
in channels
fixed to stud structure
through insulation
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
vapour control layer
under timber floor finish
damp proof membrane
above or below slab
damp proof course
external ground level
Steel Frame
7.11 Ground Bearing Floor, Insulation Above Slab
vapour control layer
perpend vent
seal between the wall and
floor membrane with a
flexible sealant or seal the
gap between the skirting
board and floor using a
flexible sealant
the wall insulation installed
below the wall DPC must be
fit for purpose with regards
to water absorption
stainless steel wall tie in channels
fixed to stud structure through
insulation
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Steel Frame
7.12 Ground Bearing Floor, Insulation Below Slab
damp proof course
external ground level
perpend vent
seal between the wall and floor
membrane with a flexible sealant or
seal the gap between the skirting
board and floor using a flexible
sealant
the wall insulation installed
below the wall DPC must be
fit for purpose with regards
to water absorption
damp proof membrane
20mm strip of perimeter
insulation with thermal
conductivity ( value) not
exceeding 0.025W/mK around
slab and any screed
vapour control layer
stainless steel wall tie in channels
fixed to stud structure through
insulation
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
vapour control layer under
timber floor finish
external ground level
damp proof course
damp proof membrane
Steel Frame
7.13 Raft Foundation
vapour control layer
20mm strip of perimeter
insulation with thermal
conductivity (value) not
exceeding 0.025W/mK around
slab and any screed
perpend vent
the wall insulation installed below
the wall DPC must be fit for
purpose with regards to water
absorption
seal between the wall and floor
membrane with a flexible sealant or
seal the gap between the skirting
board and floor using a flexible
sealant
stainless steel wall tie in channels
fixed to stud structure through
insulation
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Steel Frame
7.14 In-situ Suspended Ground Floor Slab. Insulation Above Slab
20mm strip of perimeter
insulation with thermal
conductivity (value) not
exceeding 0.025W/mK should
be installed around any screed
vapour control layer
under timber floor finish
damp proof membrane
damp proof course
external ground level
vapour control layer
perpend vent
Seal between the wall and floor
membrane with a flexible
sealant or seal the gap between
the skirting board and floor
using a flexible sealant
the wall insulation installed
below the wall DPC must be fit
for purpose with regards to
water absorption
stainless steel wall tie in channels
fixed to stud structure through
insulation
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
vapour control layer under
timber floor finish
sub floor ventilation should
be provided, minimum
1500mm per metre run of
external wall or 500mm per
m floor area
damp proof course
external ground level
damp proof membrane
solum
Steel Frame
7.15 Concrete Beam and Block Ground Floor
20mm strip of perimeter
insulation with thermal
conductivity ( value) not
exceeding 0.025W/mK should
be installed around any screed
cavity barrier type sleeve
through cavity
perpend vent
vapour control layer
seal between the wall and floor
membrane with a flexible
sealant or seal the gap
between the skirting board and
floor using a flexible sealant
the wall insulation installed
below the wall DPC must be
fit for purpose with regards
to water absorption
stainless steel wall tie in channels
fixed to stud structure through
insulation
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Steel Frame
7.16 Steel Suspended Ground Floor
vapour control layer under
timber floor finish
sub floor ventilation should
be provided, minimum
1500mm per metre run of
external wall or 500mm per
m floor area
insulating block
external ground level solum
cavity barrier type sleeve
through cavity
perpend vent
vapour control layer
seal the gap between the skirting
board and floor using a flexible
sealant
the wall insulation installed
below the wall DPC must be
fit for purpose with regards
to water absorption
optional mineral wool
insulation directly under
flooring
damp proof membrane
damp proof course
rigid insulation fixed to the
underside of the joists
light steel joist with
bitumen coated ends built
onto masonry wall
stainless steel wall tie in channels
fixed to stud structure through
insulation
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
Plan View
Steel frame
7.17 Separating Wall
acoustic insulation not shown
cavity barriers giving 30 minute fire
resistance, ensure cavity barriers
are not breeched by inappropriate
insulation material in the steel
frame
vapour control layer
stainless steel wall tie in channels
fixed to stud structure through
insulation
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
continue the wall insulation
across the floor abutment
zone
Steel Frame
7.18 Steel Intermediate Floor
vapour control layer
cavity barriers giving 30
minute fire resistance
separating floors require
additional layers and
components to comply with
Section 2: Fire and
Section 5: Noise
perpend vent
sealant between
skirting and floor
stainless steel wall tie in channels
fixed to stud structure through
insulation
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
plan view
Steel Frame
7.19 Wall Junction
vapour control layer
cavity barriers with 30 minute
fire resistance are not shown,
ensure that those provided are
not breached by inappropriate
rigid sheathing insulation
material
corner detail using
standard sized studs -
insulation placed in void
before second stud is
erected
alternative detail using
increased stud size - insulation
fitted within the stud
vapour control layer
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
ventilation to rafter void
consideration to be given
to maintenance of
circulation
roofing membrane
sarking board
vapour control layer
where two insulation
types are used together
see supplementary
guidance
window frame to be level
or lower than top of
counterbatten to minimise
thermal bridging
push flexible insulation into
gap between frame and tile
batten
10mm strip of insulation
with thermal conductivity
(value) not exceeding
0.025W/mK to be
installed around reveals
General Arrangements
8.02 Roof Window, Ventilated Rafter Void
pack with insulation
proprietary flashing
proprietary drainage
gutter
side gutter of proprietary
flashing
proprietary flashing
Revision B
For proprietary details
consult roof window
manufacturer
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
General Arrangements
8.03 Roof Window. Ventilated batten Void (Warm Roof)
ventilation to batten void
vapour permeable membrane (with a
vapour resistance of not more than
0.25MN.s/g)
rigid insulation as sarking
vapour control layer
where two insulation
types are used
together see
supplementary
guidance
push flexible insulation into
gap between frame and tile
batten
10mm strip of insulation
with thermal conductivity
(value) not exceeding
0.025W/mK to be
installed around reveals
proprietary flashing
proprietary drainage gutter
proprietary flashing
pack with insulation
Revision A
window frame to be level
or lower than top of
counterbatten to minimise
thermal bridging
side gutter of proprietary
flashing
For proprietary details
consult roof window
manufacturer
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
General Arrangements
8.04 Loft Hatch
ensure loft hatch / proprietary hatch is fully
draught sealed
counterbearers and boarding should be
provided if access to loft is required
U-value through loft hatch should not
exceed 0.35W/m K
revision B
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
vapour control layer under
timber floor finish
damp proof membrane above
or below slab
damp proof course stepped
down locally at entrance
continue floor insulation up
to back of sill
General Arrangements
8.05 Level Threshold, Insulation above Slab, Ramped Access
proprietary weather bar seal
for air leakage / rain
penetration
revision D
ramped access
surrounding ground level
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
damp proof membrane
damp proof course stepped
down locally at entrance
continue floor insulation up
to back of sill
proprietary weather bar seal
for air leakage / rain
penetration
for sill types other than timber /
plastic / composite also include a
perimeter of insulation to the
rear of sill, minimum 20mm thick,
with thermal conductivity (
value) not exceeding 0.025W/mK
General Arrangements
8.06 Level Threshold, Insulation below Slab, Ramped Access
revision C
ramped access
surrounding ground level
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
General Arrangements
8.07 Level Threshold, Timber Floor, Ramped Access
insert 20mm insulation with
thermal conductivity ( value) not
exceeding 0.025W/mK against
inner leaf and back of sill
sub floor ventilation should
be provided, minimum
1500mm per metre run of
external wall or 500mm per
m floor area
solum
surrounding ground level
proprietary weather bar seal
for air leakage and rain
penetration
revision C
ramped access
damp proof course
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.
General Arrangements
8.08 Ceilings, Service Penetrations
seal all service penetrations
with expanding foam or
other suitable sealant
for large voids mineral wool
or other material may be
used to provide a backing for
the sealant
similar arrangements should
be adopted for service
penetrations through ground
floors
N.B. insulation material has
been omitted for clarity
revision B
This detail is a constituent component of the SBSA, Technical Guide : Accredited Construction Details (Scotland) and should be used only after reference to the
introduction and the supplementary guidance where the relevance and any limitations on the use of this detail are set out.




WWW.SBSA.GOV.UK

Das könnte Ihnen auch gefallen