Sie sind auf Seite 1von 3

Search

Criteria
Light (Low) Hazard
Occupancy
Ordinary (Moderate)
Hazard Occupancy
Extra (High) Hazard
Occupancy
Minimum Rated single
extinguisher
2-A 2-A 4-A
Maximum floor area per
unit of A
3,000 ft2 1,500 ft2 1,000 ft2
Maximum floor area for
extinguisher
11,250 ft2 11,250 ft2 11,250 ft2
Maximum travel distance to
extinguisher
75 ft 75 ft 75 ft
Type of Hazard
Basic Minimum Extinguisher
Rating
Maximum Travel Distance to
Extinguisher
5-B 30 ft
Light (Low) 10-B 50 ft
10-B 30 ft
Ordinary
(Moderate)
20-B 50 ft
40-B 30 ft
Extra (High) 80-B 50 ft
There are four topics to review when installing portable fire extinguishers. You must first identify the
hazards that are present, and recognize even trace amounts of each fire classification to determine
the proper number of extinguishers required. Next, you must determine the size of the fire
extinguisher, and establish the quantity of extinguishers needed by the coverage allowed per Local
and National fire codes. Last, you must distribute the portable fire extinguishers per the allowable
travel distance to each fire extinguisher.

Class A Locations


Source: NFPA 10, 2007 edition Table 6.2.1.1 Fire Extinguisher Size and Placement for Class A
Hazards
Class B Locations



Source: NFPA 10, 2007 edition Table 6.3.1.1 Fire Extinguisher Size and Placement for Class B
Hazards
How Many Extinguishers are Required?
What are Fire
Classicfications
What are the Extinguisher
Sizes
What is the Area Hazard
Classification
How Many Extinguishers are
Required
Portable Fire
Extinguishers
Connect With Us


Home About Us Services Who We Serve FAQs Contact Us Request a Survey
Extinguisher Type
Test Interval
(years)
Stored-pressure water, water mist, loaded stream, and/or anti-freeze 1
Pump tank water and pump tank calcium chloride base 1
Dry chemical, cartridge and cylinder operated, with mild steel shells 1
Dry powder, cartridge and cylinder operated, with mild steel shells 1
Wetting agent 1
Stored pressure water 5
Class C Locations
Class C extinguishers are required where energized electrical equipment is directly involved in or
surrounding electrical equipment.

Class D Locations
Class D extinguisher locations shall not be located more than 75 ft. from the hazard. Size
determination for Class D locations is based on the specific combustible metal, particle size, area to
be covered, and manufacturer recommendations.

Class K Locations
Class K hazards shall have a fire extinguisher located where there is a potential for a fire involving
combustible cooking media (vegetable or animal oils and fats). The extinguisher shall be located no
more than 30 ft. from the hazard.
NFPA 10 requires you to maintain your fire protection equipment in good working order and maintain
inspection,
testing and maintenance records. Inspections will be performed on an Annual basis.
EXAMPLES OF WORK PERFORMED DURING AN INSPECTION INCLUDE:
Check that unit is properly hung with the proper manufacturers hanger.
Check the gauge pressure.
Check the condition of the gauge and its compatibility with the extinguisher.
Check the weight of the extinguisher.
Check that the last hydrostatic test date is within code requirements.
Check the last 6year maintenance inspection date if applicable.
Check the valve and shell for damage or corrosion.
Remove the hose and inspect it for cracks or splits.
Check the hose threads for signs of wear.
Check the condition of the discharge horn.
Check for obstructions that interfere with accessibility of the unit.
Break the extinguisher seal and remove the locking pin.
Replace the locking pin and reseal the extinguisher.
Check the valve opening for powder or any foreign matter.
For dry extinguishers, fluff the powder by turning the unit.
Check the condition of the hose/horn retention band at the side of the extinguisher.
Check that the units classification is properly identified with the appropriate decal/signage.
Check that the operating instructions are clean and legible.
Check that the unit is properly located within the normal path of travel, at the required height.
Check that the unit is visible, unobstructed and in proper location.
Compile a complete location report, explaining any deficiencies.
Recommend corrective action to be taken in accordance with recognized codes for care and
maintenance.
Upon completion of inspection and any necessary repairs, applicable inspection documents
and noted deficiencies shall be left at location and available electronically.
Tag all portable fire extinguishers as required and perform required record keeping.
| Mindscape
Stored-pressure dry chemical, with stainless steel shells
Carbon dioxide 5
Wet chemical 5
Dry chemical stored-pressure, with mild steel shells, brazed brass shells, and
aluminum shells
5
Halogenated agents 6
Dry powder, stored pressure, with mild steel shells 6
Field's Fire Protection, Inc. is a member of the National Fire Protection Association (NFPA)
2011 Fields Fire Protection Inc. All Rights Reserved.
Locations Helpful Links Our Mission
Corporate Office
Detroit Office
Chicago Office
Portable Fire Extinguishers
Backflow Devices
Special Hazard Systems
Exit and Emergency Lighting
Fire Extinguisher Guidlines
Fire Safety Training
Testing & Repair
Our Mission
Field's Fire Protection is
committed to exceeding
expectations. We understand the
value of integrity, honesty and
experience, and our dedicated
staff delivers that and more; first
time, every time.
Learn more about our mission.
1-888-670-FIRE
Request a Survey
Email Us
Join Our Team
Join Our Mailing List

Das könnte Ihnen auch gefallen