I n d i a WPCL 6 6 0 0MW Pr o j e c t Bi d d i n g Tec h n i c al Spe c i f i c at i o n o f I DCT

Page 7 of 25
3.3 Major Specification
Reinforced concrete (No.C30)framework structure and enclosure wallboard, counter flow
induced draft cooling tower. The FRP guide flow plate to be arranged under loop beam in tower
for improve the flow condition inside of tower. The stairs, walkway, handrails, lightning rods,
etc. shall be arranged outside of cooling tower for maintenance. Also the location of the above
parts should be easily for maintenance of fills, fans, motors,etc.
3.3.1 Fans
The fan blades are highly efficient wing typed and formed by the high strength expoxy glass
steel module.The angel of blades can be adjust.Each blades can be interchanged. Polyurethaned
marginal plate to protect against corrosion will be set at the fan blades. The diameter of fan
blade is mmto be filled by bidder.
To keep the fans of the cooling towers operated stable for a long time ,the transimission shaft
adopt the imported carboform shaft and adopt the imported oil seal.
The fans adjuster adopt the strengthen design.
Oil temperature, oil level and vibration supervisory equipments and DCS system whose
message was sent to the central control room shall be installed on each fans to real-time
supervise the oil temperature and oil level in deducer casing.
The performance of fans (wind flowing and wind pressure)shall meet the requirements
of the wind flowing and wind pressure in cooling towers.
Motors and fans shall be combined with speed reducer with smoothly operation,stable
performance,low noise,free artificial maintance .It is totally enclosed. The life span of speed
reducer bearing shall be no less than 100000 hours for continued usage.The manufactory of
speed reducer is filled by the bidderand the life span for the complete speed reducer
shall no less than 30 years. The manufactory of fans is filled by the bidderand the life
span for the fans shall no less than 30 years.
3.3.2 Motors
Motors matching fans and its auxiliaries shall be designed and manufactured as per interrelated
standards and specifications.
I n d i a WPCL 6 6 0 0MW Pr o j e c t Bi d d i n g Tec h n i c al Spe c i f i c at i o n o f I DCT
Page 8 of 25
Each motors shall be equipped with air space heater.
The motor type is Y type horizontal asynchronous motors and installed outside, the waterproof
casing to be arranged on the top of motors.
Insulation level : F class.
Protection level: IP55.
Working electrical condition: 415V/50Hz/3Ph.
PT-100 type temperature measurement parts to be set for the front & rear bearing and
3 phase coils of motor for ensure safety running.
Steel stracture base plate shall be used for motor mounting along with necessary
antisepsis measures.
3.3.3 Water distribution devices
Water distribution devices shall keep the hardness and strength with long life span.the tubes
adopt PVC-U pipes,evenly distribution shall be considered during the design period.the
connection between pipes shall be safe and reliable and all the hanging devices shall be made of
stainless steel.The nozzles made of ABS materials could be easily adjust to the water loading
and can satify the requirements of long-term safety operation.
3.3.4 Water decanier
The Water decanier adopt modification PVC materials and the index of fireproof oxygen higher
than 35. The Water decanier is formed by machine with the thickness no lower than 0.8mm.
The rate of the Water decanier shall be calucated as per the flowing ofrecirculated water and the
drift losing rate is no higher than 0.001.
The water decanier shall has the feature of highly rate of collecton,little air flow resistance,high
strengthen,nondeformable,easy installation and maintance.
The supporter adopt the nonmetal materials.
3.3.5 Air duct
The air duct adopts glass enforced fiber materials and recovery of kinetic energy air duct with
fire resistance property and oxygen index no lower than 28, value of recovery of kinetic
energy no lower than 30%.
The fasteners for air duct are made of steelness materials.
I n d i a WPCL 6 6 0 0MW Pr o j e c t Bi d d i n g Tec h n i c al Spe c i f i c at i o n o f I DCT
Page 9 of 25
The externally face shall having the feature of not cracked,constant the function of the color. the
surface adopts advanced imported gel coats and having anti ultraviolet ray.the bidder inviter
shall provide the colour of externally face ,the bidder shall comply with it.
The air duct adopts reinforced design and basic design wind pressure is 0.5kPa.
3.3.6 Filling
Filling materials adopt FRP or RPVC film fillings without reworked materials.
Filling materials are fire retardance with the index of fire retardanc oxygen no higher than 40.
The thickness of the substrate is no lower than 0.400.05mm.
Filling materials shall stickied into lumps with the sticking rate no lower than 95%.
The intensity of flat crushing 300kg/m
2

Filling frame adopts FRP or nonmetal materials.
Filling mareials shall be easier for maintance and exchange,nailing shall not be
adopted as the way of fastening.
3.3.7 Passage for maintance in cooling towers.
The bidder shall design and offer the maintance platform for fans and maintance passage for
components in towers.
Maintance platform and passage shall adopt stainless and nonmetal materials.
Qulckly opened access door shall be available in towers with high-quality tightness and easier
to dispatch. All the materials components shall adopt stainless steel materials.
3.3.8 Lightning system
The bidder shall be responsible for the design and supply the stainless lightning rings set on the
top of each air duct.
Lightning system on the top of tower shall be lead to downtowers to connect with the earthing
system of the power plant.
3.3.9 Others
The antisepsis measures to be condsidered by bidder for all steel parts in side of
cooling tower, the life span of these parts shall be not less than 30 years. The
antisepsis measures should be taken for the surface of water drench frame column
I n d i a WPCL 6 6 0 0MW Pr o j e c t Bi d d i n g Tec h n i c al Spe c i f i c at i o n o f I DCT
Page 10 of 25
and beams of tower.
The average moving load at the top of tower is 4kN/m
2
.
3.4 Deleted.
3.5 Requirement of C&I
3.5.1 Bider must be sure that the Equipments supplied could be operating safely and
practically under any operation conditions and bider submite the documents about
measurement point list and control requirements..All the control instruments shall be
supplied along with main equipments .Bider supply alarm value ,trip value and relative
control information.
3.5.2 Instruments supplied with main equipments shall be accordance with the
insrtruments selection .All the instruments selection must be approved by the owner.
3.5.3 The pressure and DP transmitters must be accordance with HART protocol and
transmitters will be 2 wired and smart.The accuracy will be 0.075 and external load
will be 500 ohm.Protection class shall be IP65. All cable interface must not be smaller
than 13mm.The interface will be sealed.
3.5.4 The logic switch accuracy will be 0.5 or more better ant protection class will be
IP65, All cable interface must not be smaller than 13mm.The interface will be sealed.
Switch contacts will be 2SPDT.
3.5.5 The local indicator accuracy will be 1.5.The external diameter shall not be smaller
than 150mm.Generally,the guage point will be 2/3~3/4 of full scale when normally
operationg.Temperature guage shall be universal type.Vibration-against guage will be
adopted for vibration area.
3.5.6 All analog signal will be 4~20mA DC,temperature signals that into DCS will be
from 3-wired RTD.The electric contacts will be DPDT and the contacts capacity will
be shall be as follows:
Type 230V AC 115V DC 230V DC
I closed contactssensibility loop 5A 10A 5A
II- continuous electrification 5A 5A 5A
III-broken contacts 2.5A 2A 0.5A
I n d i a WPCL 6 6 0 0MW Pr o j e c t Bi d d i n g Tec h n i c al Spe c i f i c at i o n o f I DCT
Page 11 of 25
3.5.7 Local control panel will be IP65 for outdoor and IP56 for indoor and the panel
must be meet the site requirements.The color shall be approved by the owner.The
instruments output signal cable will be linked to JB by contractor. Contractor should
supply the JB drawing to design institute.The cable from local instruments to JB shall
be supplied by contractor.JB will be bottom-into and the input will be sealed by PVC
plug.The terminal will be Phoenix and clip type mounted on track,Terminal spares shll
be 20%,and the space between two track will be 100mm.
3.5.8 All motor stator wind temperature shall be measured by 3-wired PT RTD and
than link into JB by contractor.l
(1) Motor stator wind temperature measurement will be six RTD,2 RTD each phase.
(2) Motor thrust bearing temperature will be measured by RTD.
3.5.9 Temperature measurements shall be meet following requirements:
(1) Mounted RTD will be clinged to bearing and easy to mount and replace outside the
equipments.
(2) Isolation layers will be very well After mount the temperature gauge.Be sure that
bearing will be isolated from earth.
3.5.10 Oil temperature measurement alarm instruments shall be supplied for gear
down box.
3.5.11 Vibrations and temperature measurement instrument shall be integrated with fas
or motor.Vibration measurement shall be done for X and Y ,and instrument output
signals shall be 4-20mADC and it will be connected into DCS.
4 Electrical requirement
Electrical equipments / systems shall comply the following International Standards
Standards Descriptions
IEC-60034 (Part-1
to Part-19)
Rotating electrical machines
IEC-60044-1 Current transformers
IEC-60044-2 Voltage transformer
IEC-60044-4 Instrument transformers: Measurement of Partial Discharges
IEC-60051(Part-1 to
Part-9)
Recommendations for Direct Acting indicating analogue
electrical measuring instruments and their accessories.
IEC-60076 (Part-1
to Part -5)
Power transformers
IEC-60076-10 Determination of transformer and Reactor Sound Levels
I n d i a WPCL 6 6 0 0MW Pr o j e c t Bi d d i n g Tec h n i c al Spe c i f i c at i o n o f I DCT
Page 12 of 25
Standards Descriptions
IEC-61095 Electromechanical Contactor for household and similar purposes
IEC-60099-425 Metal oxide surge arrestors without gaps
IEC-60129 Alternating Current Disconnectors (Isolators) and Earthing
switches
IEC-1129 Alternating Current Earthing Switches induced Current switching
IEC-60137 Insulated bushings for alternating voltages above 1000V
IEC-60168 Tests on indoor and outdoor post insulators of ceramic material
or glass for systems with nominal voltages greater than 1000V.
IEC-60183 Guide to the selection of high voltage cables
IEC-60189 (Part-1
to Part- 7)
Low frequency cables and wires with PVC insulation and PVC
sheath
IEC-60214 On-Load-Tap-Changers
IEC-60233 Tests on hollow insulators for use in electrical equipment
IEC-60255 (Part-1
to Part-23)
Electrical relays
IEC-60265 (Part-1
to Part 2)
High voltage switches
IEC-60273 Characteristics of indoor and outdoor post insulators for systems
with nominal voltages greater than 1000V
IEC-60289 Reactors
IEC-60297 (Part-1
to Part- 4)
Dimensions of mechanical structures of the 482.6mm(19 inches)
series
IEC-60376 Specification and Acceptance of New Sulphur Hexafloride
IEC-60437 Radio interference Test on high voltage insulators
IEC-60507 Artificial pollution tests on high voltage insulator to be used on
AC systems
IEC-60694 Common specification for high voltage switchgear & control gear
standards
IEC-60815 Guide for selection of insulators in respect of polluted
conditions
IEC-60865 (Part-1&
Part-2)
Short Circuit Current Calculation of effects
IEC-60354 Loading Guide for oil immersed power transformers
IEC-62271-100 High voltage alternating current circuit breakers
IEC-62271-102 Alternating current disconnectors and earth switches
IEC-60427 Synthetic Testing of High Voltage alternating current circuit
breakers
IEC-61264 Pressurized Hollow Column Insulators
IEC-60358 Coupling capacitors and capacitor dividers
IEC-60481 Coupling Devices for power line carrier systems
IEC-60529 Degree of protection provided by enclosures
IEC-60947-4-1 Low voltage switchgear and control gear
IEC-60439
(Part-1&2)
Low voltage switchgear and control gear assemblies
IEC-60353 Line traps for A.C. power systems
IEC-60495 Single sideboard power line carrier terminals
IEC-60683 Planning of (single side-board)power line carrier systems
IEC-60359 Expression of the performance of electrical and electronic
I n d i a WPCL 6 6 0 0MW Pr o j e c t Bi d d i n g Tec h n i c al Spe c i f i c at i o n o f I DCT
Page 13 of 25
Standards Descriptions
measuring equipment
IEC-60387 Symbols for alternating-current electricity meters
IEC-60447 Man Machine Interface (MMI)-actuating principles
IEC-60521 Class 0.5,1,and 2 alternating current watt hour meters
IEC-60547 Modular plug-in unit and standard 19-inch rack mounting unit
based on NIM standard(for electronic nuclear instruments)
IEC-60305 Insulators for overhead lines with nominal voltage above
1000V-ceramic or glass insulator units for ac. Systems
characteristics of string insulator units of the cap and pin type
IEC-60372 (1984) Locking devices for ball and socket couplings of string insulator
units: dimensions and tests
IEC-60383
(Part-1&2)
Insulators for overhead lines with a nominal voltage above
1000V
IEC-60433 Characteristics of string insulator units of the long rod type
IEC-60471 Dimension of clevis and tongue couplings of string insulator units
IEC-60227(part 1 to
7)
Polyvinyl chloride insulated cables of rated voltages up to and
including 450/750
IEC-60228 Conductor of insulated cables
IEC-60230 Impulse tests on cables and their accessories
IEC-60287 (Part-1
to 3)
Calculation of continuous current rating of cables (100% load
factor)
IEC-60304 Standard colours for insulation for low- frequency cables and
wires
IEC-60331 Fire resisting characteristic of electric cables
IEC-60332 (Part-1
to 3)
Tests on electric cables under fire conditions
IEC-60502 Extruded solid dielectric insulated power cables for rated
voltages from 1kV up to 30kV
IEC-754 (Part-1 to
2)
Tests on gases evolved during combustion of electric cables
IEC-60071 Insulation Co-ordination
IEC-60060 High voltage test techniques
IEC-60270 Partial discharge measurement
IEC-61233 Guide for inductive load switching
IEC-60298 AC metal enclosed switchgear and control gear up to 52kV
IEC-105 Bus bars (Aluminium)
IEC-61641 Enclosed low voltage switchgear and control gear assemblies.
Guide for testing under conditions of arcing due to internal fault
IEC-60292 Starters
IEC-60146 Semiconductor converters and Pulse transformer
IEC-61000-1995 Electromagnetic compatibility (EMC)
IEC-60148 Semiconductor rectifier assemblies and thyristor converters
IEC-60034-34 Guide for testing three phase induction motors
IEC-60079 Classification of hazardous areas
IEC-60896 Lead acid type With Plante positive plate
IEC-60309 Plugs, socket-outlets and couplers for industrial purposes
IEC-60598 Luminaries : General requirement
IEC-60726 Dry type power transformers
I n d i a WPCL 6 6 0 0MW Pr o j e c t Bi d d i n g Tec h n i c al Spe c i f i c at i o n o f I DCT
Page 14 of 25
Standards Descriptions
IEC-60870 Telecontrol equipment and systems
IEC-60874 Conductors for optical fibres
IEC-60921 Ballasts for tubular florescent lamps Performance
requirements
IEC-60929 AC-supplied electronic ballasts for tubular fluorescent lamps
Performance requirements
IEC-61850 Communication networks and systems in sub stations
IEC-60364 Electrical installations of buildings
IEEE-80 Std. 2000 Guide for safety in Alternating Current Sub station grounding
IEEE-665 Guide for generating station grounding
IEEE-446 Emergency standard power systems
IEEE-485 Recommended practice for sizing large lead acid storage
batteries for generating stations and sub-stations
IEEE-519 Harmonic limits in power systems
IEEE-32 Requirements, Terminology and test procedure for Neutral
Grounding Devices.
IEEE-48 Test Procedures and Requirement for High Voltage Alternating
Current Cable terminations.
IEEE-81 Measuring Earth Resistivity Ground Impedance and Earth
Surface Potentials of a Ground System.
ANSI/IEEE-242 Protection and Co-ordination of Industrial and Commercial
Power Systems.
IEEE-422/1986 Guide for the Design and Installation of Cable Systems in Power
Generating Stations.
IEEE/ 450-1995 Recommended Practice for maintenance, testing and
replacement of Large lead Storage Batteries for Generating
Stations and Substations.
IEEE-484 Installation Design and Installation of Large Lead Storage
Batteries for Generating Stations and Sub-stations.
IEEE/ 605 1998 Guide for Design of Sub-station Rigid Bus Structures.
IEEE/ 979 -1979 Guide for Sub-station Fire Protection.
IEEE/ 62.1/1984 IEEE Standard for Surge Arrestors for AC Power Circuits.
IEEE PAS VOL-97 Generator Neutral Grounding Some Aspects of Application for
Distribution Transformer with Secondary Resistor and Resonant
Types.
4.1 AC Motors shall be suitable for 3 phase, 50 Hz supply and shall be of the
squirrel-cage induction type suitable for direct-on-line starting. The temperature rise
over 50 deg.C ambient of all motors shall be limited to Class B. The motor winding
shall be of copper. Motor shall be suitable for voltage variation of 10%, frequency
variation of 5% and combined voltage and frequency variation of 10%,and also meet
the rating output.
I n d i a WPCL 6 6 0 0MW Pr o j e c t Bi d d i n g Tec h n i c al Spe c i f i c at i o n o f I DCT
Page 15 of 25
4.2 All insulated windings shall have Class F non-hygroscopic insulation systems rated
for Class B temperature rise above ambient temperature of 50C in accordance with the
standards.
4.3 The rating of each motor shall be with at least 15% extra margin over the input
power requirement and shall be continuously rated. Motor shall be considerd 1.1 times
operating current. Motors shall be capable of starting and accelerating to full speed at
80% of the nominal voltage and shall not stall at 70% of nominal voltage for one (1)
minute. With voltage and frequency within permissible variation band, the motors shall
be capable of 3 equally spaced starts in 1 hour with motor initially at temperature not
exceeding rated operating temperature. 2 start in succession with motor initially at a
temperature not exceeding rated operating temperature. The starting voltage of motors
shall be 70%-80% rating voltage (the value shall be finalized by purchaser).
4.4 All motors above 30 kW shall have space heater for avoiding condensation during
idle hours. The voltage of heater shall be 240V50Hz AC ,the power of heater shall be
__kW (To be filled in by CONTRACTOR ,finalized by purchaser) .
4.5 The noise level of motors shall be in accordance with IEC/IS 12065. The libration
shall be within the limit of IEC/IS12075. The motor shall be endure the the libration of
driving equipment.
4.6 Motors shall be self ventilated type; total enclosed fan cooled or closed air circuit
air-cooled type. Motors located outdoors shall be of weatherproof construction. The
degree of protection of motor enclosure shall not be less than IP-54 (indoor)/IP-55
(outdoor). All outdoor motors shall be provided with rain hood
4.7 All 11 kV motors shall have six (6) winding temperature detectors, bearing
temperature detectors, hot and cold air temperature indication (for CACA, CACW type).
In addition, flow switches shall be provided for water-cooled motors and forced
lubrication bearing, if used.
4.8 Motors up to 200 kW will be 415V, rated and above 200 KW will be of 11kV. Motors
of IDCT shall be consider 415V system.
4.9 Cable box and terminal box for 11 kV motors shall be phase segregated type where
ELASTIMOLD termination with protective cover is not provided. 415V motors shall have
I n d i a WPCL 6 6 0 0MW Pr o j e c t Bi d d i n g Tec h n i c al Spe c i f i c at i o n o f I DCT
Page 16 of 25
non-phase segregated cable box. Cable box shall withstand maximum fault current for duration
of 0.25 sec. The sealing equipment shall be ROXTEC.
4.10 The motors shall be designed to be energy-efficient and have high power factor and
low starting currents. All HT motors shall have efficiency and power factor higher than
0.90 and 0.88 respectively.
The ratio of rating starting current and rating of current of motor:
Upto to 20kW Id/In<7
above 20kW Id/In<6.5
11kV motor Id/In<6
4.11 The motor winding shall be of copper.
4.12 The overspeed of motor shall be 120% and two minutes.
4.13 All motors shall be provided two grounding point at two side of motor, and have
the visible grounding indication .
4.14 All motors shall be subjected to works routine tests. In addition, 11 kV motors
winding shall conform to the requirement and impulse voltage withstand levels as per
IEC 60034-15. Type test certificate on identical rated motors shall be furnished as a
proof of design.
4.15 The bearing of motor shall be sealed, prevent the entrance of water and dust.
4.16 The life of bearing shall be more than 15 years.
4.17 The connection of between inter cable and outer of cable of motor shall be
provided by bidder.
4.18 Datasheet of motor:(To be filled by bidder)
11.0.0
MOTORS

415V
11.1.0 GENERAL
11.1.1 Application
11.1.2 Quantity
11.1.3 Make
11.1.4 Frame Size
11.1.5 Applicable Standard
11.2.0 TYPE AND RATING
I n d i a WPCL 6 6 0 0MW Pr o j e c t Bi d d i n g Tec h n i c al Spe c i f i c at i o n o f I DCT
Page 17 of 25
11.2.1 Type of Motor
11.2.2 Service
11.2.3 Duty Cycle/Designation
11.2.4 Normal/Energy efficient
11.2.5 Rated Continuous Output
At 50C ambient KW
11.2.6 Rated Speed r.p.m.
11.2.7 Rated Voltage & % variation Volt
11.2.8 Rated Frequency & %
variation
Hz
11.2.9 Full load current Amps
11.2.10 No load current Amps
11.2.11 Rated Power Factor
a) Full load
b) load
c) load
11.2.12 Efficiency at rated voltage
and frequency

a) Full load %

b) load %
c) load %
11.3.0 PERFORMANCE
11.3.1 Method of Starting
11.3.2 Starting Current at rated
voltage inclusive of
tolerance
% f.l.c.
11.3.3 Starting Torque at rated
voltage
Kg.m
11.3.4 Starting time at
80% Voltage 100% Voltage

a) With load Sec.
I n d i a WPCL 6 6 0 0MW Pr o j e c t Bi d d i n g Tec h n i c al Spe c i f i c at i o n o f I DCT
Page 18 of 25
b) Without load (driven
equipment coupled)
Sec.
11.3.5 Safe stall time at 110%
rated voltage


a) Hot condition Sec.


b) Cold condition Sec.

11.4.0 CONSTRUCTION
11.4.1 Degree of Protection of
Enclosure

11.4.2 Method of Cooling
11.4.3 Insulation Class
a)
b)
c)
11.4.4 Temperature Rise Over
50C ambient (by resistance
Deg. C
11.4.5 Tropicalised Yes/No

11.4.6 Winding Connection
11.5.0 BEARINGS D.E. N.D.E
a. Make
kV
b. Type
c. Recommended
lubricant

11.6.0 MOTOR TERMINAL BOX
a. Type
b. Fault withstand
i) Current kA
ii) Time Sec.
c. Cable lugs & glands
furnished
Yes/No.
I n d i a WPCL 6 6 0 0MW Pr o j e c t Bi d d i n g Tec h n i c al Spe c i f i c at i o n o f I DCT
Page 19 of 25
11.7.0 ACCESSORIES
11.7.1 Space Heaters
a. No. X Watt
b. Voltage, phase &
frequency
Volt./Nos./Hz
11.7.2 Winding temperature
detector

a. Type
b. Nos. furnished
11.7.3 Bearing temperature
detector

a. Type
b. Nos. furnished
11.7.4 Temperature Indicators

a. Type
b. Nos. provided
c. Locations
11.7.5 Temperature Alarm
Contact



kV
a. Nos. provided
b. Locations
c. Contact rating
11.7.6 Flow Switch
a. Type
b. Nos. provided
c. Locations
d. Contact Rating
11.7.7 Current Transformer for
differential protection

I n d i a WPCL 6 6 0 0MW Pr o j e c t Bi d d i n g Tec h n i c al Spe c i f i c at i o n o f I DCT
Page 20 of 25
a. Nos. provided
b. Current Ratio
c. Class
11.7.8 Accessory Terminal Box
a. No. provided
b. Cable glands
furnished?
Yes/No.
11.8.0 GROUNDING
No. of grounding pads
provided

a. On motor body

b. On terminal box
11.9.0 MISCELLANEOUS
11.9.1 Type of mounting
11.9.2 Overall dimension (LxDxH) mm
11.10.0 MOMENT OF INERTIA
(GD
2
)

a. Stator Kg.m
2


kV
b. Rotor Kg.m
2

c. Total Kg.m
2

11.11.0 WEIGHT
a. Stator Kg
b. Rotor Kg
c. Total Kg
5 Quality and Performance Guarantee
5.1 Manufacture or inspection for cooling towers shall meet national standards and
manufactory standards. The designe of the cooling towers shall be under the
conditions of full design load with stable operation to reduce the loud noise and
vibration.
I n d i a WPCL 6 6 0 0MW Pr o j e c t Bi d d i n g Tec h n i c al Spe c i f i c at i o n o f I DCT
Page 21 of 25
5.2 Noise of the cooling towers shall satify the interrelated requirements.
5.3 If the cooling tower,withine the period of quality assurance can not meet
performance requirements due to equipments design and manufacture quality
issues,the bidder shall be responsible for solving the problems for free.
5.4 Noise in the place where 1.0m away from the exteriors of the cooling tower shall no
higher than 85 decibel. If the noise exceeds this value,the bidder shall provide
effective measures (devices) to meet the requirements of noise controlling.
5.5 The performance guarantee test will be carried out within 6 months after 14 days
reliability running of unit. The bidder will provides full cooperation for PG test and
comlete the correction for ensure the performance meet the requirement of contract.
6 Limits & interface of design and supply
The bidder shall ensure the whole performance and equipment quality of IDCTs.
The bidder shall provides all the equipments and materials of cooling tower above
0.000m elevation except civil work, it includes fillings, water drench devices, Water
decanier, air duct, fans, motors, speed reducer,etc. For the circulation cooling pipe, the
bidder shall provides the CW pipes above +2.000m elevation without isolation valves.
The bidder shall furnish all the installation drawings, civil construction drawings and
calculation books of IDCT as per requirement of design institute (NEPDI), these
drawings should be submitted to design institute (NEPDI) for review and approve, the
final construction drawing of IDCT will be furnished by design institute (NEPDI).
7 Major Technical Parameters Table(to be filled by bidder)
71 Physical Dimension of Induced Draft Cooling Tower in Every Section
Plane dimension of cooling tower:
Height of incoming pipe:
Diameter of incoming pipe: 1200mm
Water head needed by incoming pipe:
72 Water Quantity and Water Temperature of Mechenical Cooling Tower
1Quantity of Cooling Water in Every Group of Cooling Tower: 82454m3/h
2Incoming Water Temperature : 43
I n d i a WPCL 6 6 0 0MW Pr o j e c t Bi d d i n g Tec h n i c al Spe c i f i c at i o n o f I DCT
Page 22 of 25
3Outgoing Water Temperature: 33
7. 3 Cooling Tower Fan
1Model:
2Diameter of blade:
3Voltage of Supporting Electric Motor:
4Power of Supporting Electric Motor:
5Efficiency of Supporting Electric Motor:
6Vane Number:
7Input air:
74 Cooling Tower Equipment Major Data Sheet(to be filled by bidder) (to be filled by bidder) (to be filled by bidder) (to be filled by bidder)
No. No. No. No. Item Symbol
Unit Parameter Remarks
1
General Design Requirement of Cooling
Tower

1-1 Model of Cooling Tower
Reverse Flow Induced
draft cooling tower with
Reinforced Concrete
Structure

1-2 Arrangement of Tower Group
One unit contains 16
sections with back to
back arrangement
15 for work 1 for
standby
1-3 Sets of fan/ one unit 16
1-4 Structural Style of Cooling Tower
Reinforced
concrete

1-5 Equipment Spec.& Type
2
Loading conditions of hot water of cooling
tower
dry-bulb temperature:
34.5
Wet-bulb temperature:
28.6
Design relative
humidity: 60%

2-1
Design quantity
of general
circulating water
Q m
3
/h 82454 For one Unit
2-2
Maximum of
design quantity of
cooling tower for
Q m
3
/h 5497
I n d i a WPCL 6 6 0 0MW Pr o j e c t Bi d d i n g Tec h n i c al Spe c i f i c at i o n o f I DCT
Page 23 of 25
No. No. No. No. Item Symbol
Unit Parameter Remarks
single tower
2-3
Quantity of
cooling tower
section 16
15 for work 1 for
standby
2-4
Incoming water
temperature
t1 43
2-5
Outgoing water
temperature
t2 33
3 Technical Parameters of Cooling Tower
3-1
Area of water
drenching of single
tower
S mm
3-2 Air inlet height H1 m
3-3
Water supply
height
Hb m
3-4 Fill height h m
3-5
Density of water
drenching
q m3/(m
2
h)
3-6 Diameter of fan mm
3-7 Air input G m
3
/h
3-8 Type
3-9 Motor power N kW
3-10
Shaft power of
fan
N
kW s
3-11 Total pressure P Pa
3-12 Efficiency
3-13 Rotated speed r.p.m.
3-14 Relative humidity %
3-15 Air density a kg/m
3

3-16 Gas water ratio
3-17
Wind speed of
drenching water
section
V
m/s
3-18
Quality wind
speed
ga
kg/( m
2
s)
3-19 Design swap data
3-20
Drifting ratio
%
3-21
Reference noise
of single tower

dBA
3-22 Evaporation loss QE m
3
/h
Quatity of single
tower
3-23
Qualtity of makeup
water
QM m
3
/h
3-24
Use level of
concrete
m
3

Quatity of each
unit
3-25

Inlet piping
Diameter
mm 1200
I n d i a WPCL 6 6 0 0MW Pr o j e c t Bi d d i n g Tec h n i c al Spe c i f i c at i o n o f I DCT
Page 24 of 25
8 Materials of main components of equipment (filled out by bidder)
No.
Component name Material Remarks
1
Air duct
FRP

2
Drift Eliminator


3
Filling
FRP or PVC

4
Sparge pipe
ss

5
Nozzle


6
Fibre glass reinforced plastic filling
shelf


7
Fibre glass reinforced plastic flow
deflecting ring


8
Embeded parts & steel member


9 99 9 Cleaning, Painting Cleaning, Painting Cleaning, Painting Cleaning, Painting, ,, , Insulation Insulation Insulation Insulation and Name and Name and Name and Name- -- -plate plate plate plate
9.1 Cleaning
9.1.1 Prior to shipment, equipments shall be cleared.
9.1.2 All the internal objects, such as flitter, iron slag, welding slag, rag and other
impurities shall be removed from components, while the internal water shall be
drained and the equipments shall be sealed properly with a fixed end cover.
9.2 Painting Painting Painting Painting
9.2.1 Bidders shall choose the best way of painting to prevent the equipment from
corrosion during the shipment and storage.
9.2.2 Prior to the shipment, the bidder shall spray the equipment with two layers of primer
and three layers of top coat.
9.2.3 Bidders shall provide complete description of mitigate corrosion, including the
description of cleaning, painting technics and the characteristics of coating.
9.2.4 The surface painting colour code of IDCT will be confirmed by Owner and shall be
complied with by the bidder.
9.3 Name-plate
9. 3.1 The name-plate of the equipment shall be made of stainless steel.
9.3.2 The name-plate shall be installed in a location readily visible to the operators.
9.3.3 The contents of the nameplate shall at least include equipment name, manufacturer
name, manufacture date, factory number, the KKS code of equipment , the number of
I n d i a WPCL 6 6 0 0MW Pr o j e c t Bi d d i n g Tec h n i c al Spe c i f i c at i o n o f I DCT
Page 25 of 25
manufacture certificate, equipment model and classification, main parameters of the equipment,
and weight etc, while the contents of nameplate shall be made in Chinese & English
versions.















Annex-2 Attached Drawings
The layout of IDCT units please refer to the attachment.