50%(2)50% fanden dieses Dokument nützlich (2 Abstimmungen)
828 Ansichten40 Seiten
This manual is proprietary information of Limitorque Corporation furnished for customer use ONLY. It is intended to be a guide and should not be considered as a sole source of technical instruction. The choice of system components is the responsibility of the buyer, and the use of them cannot be Limitorque's liability.
This manual is proprietary information of Limitorque Corporation furnished for customer use ONLY. It is intended to be a guide and should not be considered as a sole source of technical instruction. The choice of system components is the responsibility of the buyer, and the use of them cannot be Limitorque's liability.
This manual is proprietary information of Limitorque Corporation furnished for customer use ONLY. It is intended to be a guide and should not be considered as a sole source of technical instruction. The choice of system components is the responsibility of the buyer, and the use of them cannot be Limitorque's liability.
1996 Copyright Limitorque Corporation, All rights reserved. Printed in the United States of America. Disclaimer All rights reserved. No part of this book shall be reproduced, stored in a retrieval system, or transmitted by any means, electronic, mechanical, photocopying, recording, or otherwise without the written permission from Limitorque. While every precaution has been taken in the preparation of the book, the publisher assumes no responsibility for errors or omissions. Neither is any liability assumed for damages resulting from the use of the information contained herein. This document is proprietary information of Limitorque Corporation furnished for customer use ONLY. No other uses are authorized without written permis- sion of Limitorque Corporation. Limitorque Corporation reserves the right to make changes, without notice, to this document and the products it describes. Limitorque Corporation shall not be liable for technical or editorial errors or omissions made herein; nor for inci- dental or consequential damages resulting from the furnishing, performance or use of this document. This manual contains information that is correct to the best of Limitorques knowledge. It is intended to be a guide and should not be considered as a sole source of technical instruction, replacing good technical judgment, since all possible situations cannot be anticipated. If there is any doubt as to exact installation, configuration, and/or use, call Limitorque Corporation at (804) 528-4400. The choice of system components is the responsibility of the buyer, and the use to which they are put cannot be the liability of Limitorque Corporation. However, Limitorques sales team and application engineers are always avail- able to assist you in making your decision. Acknowledgments Sections of this document are edited and/or reprinted with the written per- mission of A.E.G. Modicon Inc and Allen-Bradley a Rockwell International Company. LOGITORQUE and LIMITORQUE are registered trademarks of Limitorque Corporation Modbus is a registered trademarks of A.E.G. Modicon, Inc BITBUS is a registered trademark of Intel Corporation MS-DOS is a registered trademark of Microsoft Corporation IBM-PC is a registered trademark of International Business Machines Corporation Belden is a registered trademark of Belden, a division of Cooper Industries, Inc. Limitorque Corporation UEC-3 & UEC-3-MPC Installation & Commissioning Manual Bulletin 440-12100 6/96 i Contents 1. Introduction 1 1.1 Premise............................................................................................................................................1 1.2 Emphasis .........................................................................................................................................1 1.3 Audience ..........................................................................................................................................2 2. Product Description 3 2.1 UEC-3...............................................................................................................................................3 2.2 UEC-3-MPC.....................................................................................................................................3 3. General Information/Workmanship 5 3.1 Safety Information............................................................................................................................5 3.2 Electrostatic Discharge Awareness................................................................................................5 3.3 UEC-3 Label ....................................................................................................................................6 3.4 Dip Switch Location and Conventions ...........................................................................................7 3.5 EPROM Care and Installation ........................................................................................................9 3.5.1 Care and Storage...........................................................................................................9 3.5.2 Removal........................................................................................................................10 3.5.3 Installation.....................................................................................................................10 3.6 Supply Voltage...............................................................................................................................10 4. UEC-3/UEC-3-MPC Installation 13 4.1 Site preparation .............................................................................................................................13 4.2 Visual inspection ...........................................................................................................................13 4.3 Wire preparation............................................................................................................................13 4.4 Actuator Wiring..............................................................................................................................13 4.5 Grounding......................................................................................................................................14 5. UEC-3/UEC-3-MPC Commissioning 15 5.1 Initial inspection .............................................................................................................................15 5.2 Start-up procedure ........................................................................................................................15 5.2.1 Power LEDs .................................................................................................................17 5.2.2 Reset LEDs..................................................................................................................17 5.3 UEC-3-MPC Calibration Procedure.............................................................................................18 5.4 Troubleshooting..............................................................................................................................23 5.4.1 Troubleshooting Tools ..................................................................................................23 5.4.1.1 Universal Diagnostic Tool ...........................................................................23 5.4.1.2 Modsim Diagnostic Software.....................................................................23 5.4.2 Component Replacement ...........................................................................................24 5.4.2.1 Control Fuse Replacement........................................................................24 5.4.2.2 24VDC I/O Power Supply Fuse Replacement ........................................25 Limitorque Corporation UEC-3 & UEC-3-MPC Installation & Commissioning Manual Bulletin 440-12100 6/96 ii 5.4.2.3 Single Board Computer Replacement ......................................................26 5.4.2.4 Termination/Interconnect Board Replacement .........................................27 5.4.3 Complete Module Replacement .................................................................................28 6. Conversion of UEC-3 Basic Controller 31 6.1 Converting UEC-3 to UEC-3-MPC Position Controller ...............................................................31 6.1.1 Installation of PT20SD (optional) ................................................................................32 7. Parts 33 8. Customer Service 35 Figures 3-1 Model, Option, and Conguration Identication Label..................................................................6 3-2 Single Board Computer DIP Switch and Component Location...................................................7 3-3 DIP Switch Conventions .................................................................................................................8 3-4 Default DIP Switch Settings for UEC-3 and UEC-3-MPC............................................................9 3-5 Locating Power Supply Board .....................................................................................................11 3-6 Locating Power Supply Board Mounting Screw..........................................................................11 3-7 Locating Power Supply Bracket Retaining Screw.......................................................................12 3-8 Power Supply Board .....................................................................................................................12 5-1 UEC-3/UEC-3-MPC Start-up Procedure.....................................................................................16 5-2 UEC-3-MPC Calibration Procedure........................................................................................18-21 Tables 5-1 Table of Values for Proportional Band and Deadband................................................................22 Limitorque Corporation UEC-3 & UEC-3-MPC Installation & Commissioning Manual Bulletin 440-12100 6/96 iii 1. Introduction 1.1 Premise These instructions are to aid in the installation and commissioning of the UEC- 3 family of control modules. Your safety and satisfaction are important to Limitorque. Be sure to follow all instructions carefully. Pay special attention to safety. 1.2 Emphasis Please refer to the following methods used to emphasize text throughout this manual: Safety warnings, cautions, and notes present material that is important to user safety. Be sure to read any safety notices you see as they could prevent equipment damage, personal injury, or even death to you or a co-worker. Warning refers to personal safety. They alert you to potential danger or harm. Failure to follow warning notices could result in personal injury or death. Caution directs attention to general precautions, which if not followed, could result in personal injury and/or equipment damage. Note highlights information critical to your understanding or use of these products. Bold text highlights other important information that is critical to system com- ponents. CAPITALIZED text stresses attention to the details of the procedure. Underlined text emphasizes crucial words in sentences that could be mis- understood if the word is not recognized. The purpose of this section is to alert you to possible safety hazards associ- ated with this equipment and the precautions you can take to reduce the risk of personal injury and damage to the equipment. Safety notices in this manual provide important information. Read and be famil- iar with these instructions before attempting installation, operation, or maintenance. Failure to observe these precautions could result in serious bodily injury, damage to the equipment, or operational difculty. Limitorque Corporation UEC-3 & UEC-3-MPC Installation & Commissioning Manual Bulletin 440-12100 6/96 1 1.3 Audience This Installation and Commissioning Manual is designed to help you to prop- erly install and commission the UEC-3 Control Module and the UEC-3 Modulating Position Controller. You do not have to be an expert in electronics or digital controls to utilize this manual. However, this manual assumes you have a working understanding of basic electronics and a fundamental under- standing of microprocessor concepts. The material in this manual supplements the following Limitorque publication: UEC-3 Operation Manual - Bulletin 440-12000 Rev. A. It is recommended that you completely read all the general information and all sections pertaining to the type of UEC-3 module for your application so that you can promptly nd any information you need. It is also recommended that you have a copy of the Operation Manual for your UEC-3 module as well as the applicable actuator wiring diagram available before attempting to install or commission a UEC-3 or UEC-3-MPC controlled actuator. Limitorque Corporation UEC-3 & UEC-3-MPC Installation & Commissioning Manual Bulletin 440-12100 6/96 2 2. Product Description The UEC-3 is a microprocessor based controller for the complete range of Limitorque actuators. It provides many protection and control features which are designed to be individually congured to t specic customer needs. This conguration may be altered in the eld as process requirements change or as the real needs of the actuator are realized. 2.1 UEC-3 (Universal Electronic Controller) The basic UEC-3 model provides control, indication, alarm, and protection features. It is intended for use with open/close or pushbutton throttling valves. 2.2 UEC-3-MPC (Modulating Position Controller) This model is designed to position valves in accordance with a 4-20mA command signal, thereby controlling level, ow, pressure, etc. All the indica- tion, alarm, and protection features of the basic UEC-3 are retained in this model. Limitorque Corporation UEC-3 & UEC-3-MPC Installation & Commissioning Manual Bulletin 440-12100 6/96 3 This page is intentionally blank. Limitorque Corporation UEC-3 & UEC-3-MPC Installation & Commissioning Manual Bulletin 440-12100 6/96 4 3. General Information/Workmanship Throughout this manual, the designation UEC-3 will refer to a basic Universal Electronic Controller with a 4-wire conguration. UEC-3-MPC will refer to the Universal Electronic Controller with positioning control. The information in this section is applicable to all members of the UEC-3 family of controllers. 3.1 Safety Information Practice all plant and safety codes and standards. Failure to follow instructions can result in personal injury and/or property damage. To prevent the possible ignition of hazardous atmospheres, do NOT remove the cover of Division 1 units with power applied. All servicing should be performed by qualified technicians. Dangerous volt- ages may be present on the circuit boards and terminations. Use extreme caution when working around power-input cables. These cables have potentially lethal voltages on them. When fuse replacement is required, use only Limitorque specified parts for continued safe operation. Have qualied personnel verify all wiring and connections against vendor draw- ings prior to energizing the equipment. Incorrect wiring and/or connections can result in equipment damage. 3.2 Electrostatic Discharge Awareness The circuit boards in the UEC products may contain components that are subject to damage from electrostatic discharge (static electricity). The follow- ing precautions and procedures are recommended when handling circuit boards or components. Failure to observe these practices when handling and shipping circuit board products may void your warranty. Keep plastics and other materials prone to the buildup of electrostatic charges (static electricity) away from boards, components, and work area. Avoid synthetic or wool clothing and wear cotton or cotton blend materials. Keep components and circuit boards away from clothing and hair. Discharge static electricity on your body by touching and momentarily holding a grounded metal object before handling electronic components. This is espe- Limitorque Corporation UEC-3 & UEC-3-MPC Installation & Commissioning Manual Bulletin 440-12100 6/96 5 cially important after walking across carpeted areas. Handle components in the eld as little as necessary. Handle components only by the edges, and avoid contact with leads, circuits, or connectors. Do not touch the printed circuit board, the connectors, or the components with conductive devices or with your hands. Always place the component or board into an anti-static protective bag for transportation or storage. Transport all static-sensitive components only in static-shielding carriers or packages. Place static awareness labels on all components to prevent removal from static-shielding container during transit. Handle all static-sensitive components at a static-safe work area including: oor mat, wrist strap, air ionizer, ground cord, and conductive table mat. Do not subject components to sliding movements over any surface, at any time. 3.3 UEC-3 Labels Labels are afxed to the housings of all UEC modules. The information included on this label indicates: type of UEC-3 (basic, MPC or DDC), options, trans- former voltage, module serial number and status of LK1 link. The label also contains space for the user to record the settings of the configuration DIP switches. See Figure 3-1 Figure 3-1 - Model, Option, and Conguration Identication Label Limitorque Corporation UEC-3 & UEC-3-MPC Installation & Commissioning Manual Bulletin 440-12100 6/96 6 S2 S3 S1 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 ON OFF ON OFF ON OFF (DDC Only) OUT IN LK1: UEC-3 BASIC CONFIGURATION SWITCH POSITIONS Serial No. Model Options UEC-3 BASIC UEC-3-MPC Potentiometer PT20S (R-1) Logitorque UEC-3-DDC Type A Transformer Type/Tapping Type B 4 6 0 V 4 1 5 V 3 8 0 V 2 2 0 V 5 7 5 V 5 2 5 V 2 2 0 V 1 1 5 V 3.4 DIP Switch Location and Conventions The UEC-3 and UEC-3-MPC units are congured using DIP switches S1 and S2 located on the Single Board Computer (SBC) as shown in Figure 3-2 Limitorque Corporation UEC-3 & UEC-3-MPC Installation & Commissioning Manual Bulletin 440-12100 6/96 7 Figure 3-2 - Single Board Computer DIP Switch and Component Location RAM 34 Pin Bus connector for connection to Diagnostic Tools EPROM (program storage) Microprocessor with EEPROM (permanent variable storage) Analog to Digital (A/D) Converter Chip (Optional) Analog Input Connector Reset LED Digital I/O Isolation 34 Pin Power and I/O Connector Switching Pre-regulator Linear 5V Regulator DIP Switch S1 (feature selection) DIP Switch S2 (feature selection) Figure 3-3 shows an example of a DIP switch and the conventions that are used in describing the conguration of the DIP switches. An individual switch position is said to be ON when the switch is in the CLOSED state. In the ON position, the switch is towards the ON indication on the switch housing and away from the number designation. All tables showing DIP switch congura- tions indicate a 1 when the switch state is ON. Conversely, the switch position is said to be OFF when the switch is in the OPEN state. In the OFF position, the switch is towards the number designa- tion and away from the ON indication on the switch housing. The tables indicate a 0 when the switch is OFF or OPEN. Care should be taken to assure that the each DIP switch is pushed rmly in either the open or closed direction. Figure 3-3 - DIP Switch Conventions Caution Always use a small non-metallic tool to move the DIP switches. NEVER use a pencil because graphite lings may cause short circuits on the printed circuit boards or in the switches. Note If changes to the DIP switches are made while power is present at the actuator, it is important to turn the power off and on again in order to initialize the changes. To change DIP switch settings for a particular application, refer to the UEC-3 Operation Manual Bulletin# 440-12000 Rev. A. Limitorque Corporation UEC-3 & UEC-3-MPC Installation & Commissioning Manual Bulletin 440-12100 6/96 8 1 2 3 4 5 6 7 8 OFF ON Dip Swich SX-7 Position 7 If sufcient information is provided at the time of order, the DIP switches will be set according to the order. If the specic details are not provided at time of order, the actuator will be provided with the default settings shown in Figure 3-4. ESD action - CLOSE - S1-1,-2 Remote control mode - 4 WIRE - S2-1,-2-3 Local inching - DISABLED - S1-3 Seating method at close - POSITION - S2-4 Modulating mode - DISABLED - S1-4 Autophase control - ENABLED - S2-5 Slow speed opening - DISABLED - S1-5 Slow speed closing - DISABLED - S2-6 Closing rotation - CLOCKWISE - S1-6 Thermostat bypass - DISABLED - S1-7 NOTE: FOR A STANDARD UEC-3 Interlock / Inhibit - DISABLED - S1-8 ALWAYS SELECT: EEPROM - DISABLED - S2-7 Software Control - ENABLED - S2-8 Figure 3-4 - Default DIP Switch Settings for UEC-3 and UEC-3-MPC 3.5 EPROM Care and Installation Normally you will not need to handle the EPROM. However, if you do need to handle the EPROM, (for example, to install a rmware upgrade), you should follow these instructions. 3.5.1 EPROM Care and Storage The UEC-3 family of control modules are equipped with EPROM integrated circuits (IC) which are fragile and static sensitive. Care should be taken in the storage and handling of the EPROMs. Do not ship or store EPROMs near strong electrostatic, electromagnetic, mag- netic or radioactive elds. Do not remove labels from EPROMs. Store EPROMs away from direct sunlight at temperatures from -40C to 85C (-40F to 185F). Store EPROMs in static free containers with care to prevent breakage from shock or damage to pins. Limitorque Corporation UEC-3 & UEC-3-MPC Installation & Commissioning Manual Bulletin 440-12100 6/96 9 S1 ON OFF 1 2 3 4 5 6 7 8 ON OFF KEY S2 ON OFF 1 2 3 4 5 6 7 8 3.5.2 EPROM Removal It is recommended that an integrated circuit (IC) inserter/extractor tool be used to remove EPROMs from the socket. If an IC inserter/extractor is unavailable, use the following procedure: Carefully insert a small flathead screwdriver into the space between the EPROM and the socket. Slowly and gently pry the EPROM out of the socket taking care not to bend or break the pins. 3.5.3 EPROM Installation It is recommended that an IC inserter/extractor be used to hold the EPROM for installation. To insert a replacement EPROM, use the following procedure: The notch at the top of the EPROM must be lined up with the notch at the top of the socket. Failure to position properly will result in damage to the EPROM. Gently place the pins of one side of the EPROM in the socket. Roll the EPROM over until the pins on the other side are lined up. You may have to use some back pressure to get the pins to line up. When you are sure all pins are lined up with the socket holes, push down on the top of the EPROM rmly until the pins are well seated in the socket. 3.6 Supply Voltage The transformer voltage on the UEC module will be factory set to the supply voltage specied at the time of order. This setting is recorded, at the factory, on the label afxed to the side of the UEC housing. The following procedure should be used to change the transformer voltage: Tools required to change the transformer voltage: Medium phillips head screwdriver Flat blade screwdriver Long-handled needle nose pliers No additional parts are required to change the transformer voltage 1. Isolate power from actuator. 2. It is not necessary to remove wires from terminal strip to termination/inter- connect board. 3. Remove the larger clear cover by pressing down with both thumbs on indented areas on top edge of cover. 4. Unlatch and release the 34-pin ribbon cable connector on the SBC located near the heat sink. 5. Remove the four screws securing the SBC and remove the SBC. 6. Remove the insulator sheet. Limitorque Corporation UEC-3 & UEC-3-MPC Installation & Commissioning Manual Bulletin 440-12100 6/96 10 Limitorque Corporation UEC-3 & UEC-3-MPC Installation & Commissioning Manual Bulletin 440-12100 6/96 11 Figure 3-5 Locating Power Supply Board Figure 3-6 Locating Power Supply Board Mounting Screw 7. Unlatch and release the 50 pin connector located on the Power Supply Board between the fuse cartridge and the phase LEDs. Move this ribbon cable over the edge of the enclosure to permit access to the metal plate. 8. Remove the four screws securing the metal plate. Insert a at blade screw- driver under the plate and gently lift and set aside. This plate will be connected to the assembly via a green ground wire. It is not necessary to remove the ground wire from the plate. 9. Locate the Power Supply Board which is mounted on the wall of the enclo- sure opposite the Termination/Interconnect board. See Figure 3-5. 10. Remove and retain the single screw from the outside of housing which secures the power board from the bottom. See Figure 3-6. 11. Using a long phillips head screwdriver, partially unscrew the screw located on the inside base of the UEC housing which holds the bracket to the housing. See Figure 3-7. Unscrew only enough to separate the bracket from the housing. DO NOT COMPLETELY REMOVE THIS SCREW. 12. Slide the power board slowly up and out of the housing being careful to move wiring aside. Care should be taken to prevent damage to the wiring insulation by coming into contact with the edges of the bracket. It is only necessary that the power board be moved enough to locate and change the transformer jumpers. (continued on next page) Termination/ Interconnect Board Power Supply Board Power Supply Board Mounting Screw 13. Locate the transformer jumpers as shown in Figure 3-8. 14. Using pliers, carefully remove the jumper and reinsert into position for the desired input voltage: Std. Optional LK1 for 460V 575V LK2 for 415V 525V LK3 for 380V 220V LK4 for 220V 115 15. If the main power is single phase, set all three LK7 jumpers (located beside the ribbon cable connector) to the 1 phase setting to disable phase detection. 16. Carefully slide the power board back into the housing. 17. Tighten the bracket screw at the base of the housing. 18. Replace and tighten the screw on the outside of the housing. 19. Replace the metal plate and secure with 4 screws. 20. Reconnect the 50-pin ribbon connector. 21. Replace the insulator sheet on top of the ribbon cable keeping the 34-pin connector free. 22. Reconnect 34-pin connector into the SBC. 23. Replace the SBC and secure with 4 screws. 24. Replace the UEC clear cover. 25. It is recommended that the new voltage with date changed be recorded and initialed on the label located on the side of the UEC housing. Limitorque Corporation UEC-3 & UEC-3-MPC Installation & Commissioning Manual Bulletin 440-12100 6/96 12 Figure 3-7 - Locating Power Supply Bracket Retaining Screw Figure 3-8 - Power Supply Board Power Supply Bracket Retaining Screw Transformer Jumpers LK7 - Phase Detector Jumpers 4. UEC-3/UEC-3-MPC Installation 4.1 Site Preparation Proper site preparation is essential to the successful operation of the UEC-3 controlled actuators. 1. A site map or detailed site plan should be available. This should include location and tag numbers of all actuators, junction boxes and terminal strips. 2. Free access to the control compartments of each actuator will be required for set-up, conguration and troubleshooting. 3. All wires should be properly labeled or identied. 4. Control and power wiring for the actuator should both be installed in proper conduit but never in the same conduit. Shielding is not enough to prevent induction of stray voltages onto signal leads from power lines. 5. Power distribution grid should be available to identify the impact of power isolation to a particular actuator or group of actuators. 4.2 Visual Inspection The UEC module contained in your Limitorque actuator has been tested prior to shipment. It is recommended that a visual check of the module take place prior to applying power to the actuator. Check for any physical damage to the UEC module Verify that all ribbon cables are fully seated and that the clips are in a verti- cal position. Verify that all EPROMs are properly aligned and fully seated. 4.3 Wire Preparation For connections to the Termination/Interconnect Board, an 18 gage, 380V wire is recommended. All wires should be stripped 0.25 inch (6 mm) from the end and tinned with resin core solder for best results. 4.4 Actuator Wiring It is essential that all wiring is in accordance with the wiring diagram provided with your actuators. Copies of the wiring diagram are mailed to purchasers of Limitorque actuators and one copy is normally placed inside the actuators control compartment before shipment. Becoming familiar with the wiring diagram will ease setup. Wiring Verication should be done with the actuator isolated from power. Limitorque Corporation UEC-3 & UEC-3-MPC Installation & Commissioning Manual Bulletin 440-12100 6/96 13 Note: The transformer voltage on the UEC module will be factory set to suit the supply voltage specied at the time of order. This setting is recorded, at the factory, on the label afxed to the side of the UEC housing. 1. Check to make sure that the transformer voltage on the UEC-3 label is the same as the incoming supply. If not, refer to Section 2.6 -Supply Voltage for the procedure to change the voltage. 2 Verify that actuator wiring is in accordance with the wiring diagram shipped with the actuator. 3. If the external control voltage is above 90VAC or 90VDC, link LK1 must be removed. Locate LK1 at the bottom of the Termination/Interconnect Board near the SBC. To remove, grasp the black housing and pull straight up. 4. Verify that DIP switch settings on the SBC are correct to enable the desired functionality. See Section 2-3 of this manual for DIP switch key and basic settings. The unit is now ready for commissioning. See Section 5 for instructions. 4.5 Grounding The remote control inputs on the Termination/Interconnect Board are opto-iso- lated to protect the internal logic circuits from high voltage transients and ground loops. Additional grounding for these inputs is not required. Please refer to the wiring diagram for your particular Limitorque actuator for additional grounding requirements. Limitorque Corporation UEC-3 & UEC-3-MPC Installation & Commissioning Manual Bulletin 440-12100 6/96 14 5. UEC-3/UEC-3-MPC Commissioning 5.1 Initial Checkout All UEC-3 and UEC-3-MPC modules and their corresponding actuators are tested before shipment to ensure proper operation. After assembly, the actu- ator is cycled through normal operation, thereby assuring that the motor, wiring, and controller are all functioning properly. Final setup is not complete until the actuator is installed. Field setup is required. Please use the instruction and maintenance manual appropriate for your actu- ator to adjust the limit and torque switches. Verify that the connectors for the ribbon cables are properly seated and that the clips are in closed position. Verify that all socketed integrated circuits are properly aligned and fully seated. Make sure that for MPC applications, the Analog to Digital Converter chip is installed. 5.2 Start-up Procedure The start-up procedure for the UEC-3 and UEC-3-MPC is given in the form of a ow chart in Figure 5-1. Note: The settings of the DIP switches S1 and S2 on the SBC Board should be recorded before beginning any procedure. Limitorque Corporation UEC-3 & UEC-3-MPC Installation & Commissioning Manual Bulletin 440-12100 6/96 15 Figure 5-1 - UEC-3/UEC-3-MPC Start-up Procedure Limitorque Corporation UEC-3 & UEC-3-MPC Installation & Commissioning Manual Bulletin 440-12100 6/96 16 Do you want phase correction? SW2-5 on Power off, then on Yes Set position limits Center Pot at 50% valve position. Selector switch to Local No Power off Swap incoming power leads Power on Yellow LED on? (Phase Rotation OK) SW2-5 off Power off, then on Yes No Test pushbuttons Open PB=> Open dir Close PB=> Close dir Verify Change position of SW1-6 (Direction to close) No Power off, then on Yes Change other options as required in std. configuration Power off, then on Wait 15 sec SW93 LEDs on? See Section 6.4 Troubleshooting No Yes UEC-3-MPC go to calibration procedure UEC-3 End of Start-up 5.2.1 Power LEDs During start-up check the LEDs on the power supply board. (See Figure 5-1 of Bulletin 440-12000 Rev. A. for the location of the LEDs.) The Power Supply Boards on most versions of the UEC-3 and UEC-3 MPC Modules have three LED indicators - red, yellow, and green. The state of these indicators for various operating conditions are given below: On units which have been congured for three phase power, both the red and yellow LEDs should be illuminated when power is present to the actuator, and the green indicator should not be illuminated If the yellow LED is not illuminated, the unit is out of phase and incoming power leads (L1 & L3) should be switched. If the red LED is not illuminated, one of the phases is not present and incom- ing power connections should be checked. On units which have been congured for three phase power, all of the LEDs should be illuminated when power is present to the actuator. The green LED indicates that the phase detector circuit has been bypassed and that there is no phase protection. 5.2.2 Reset LED During Start-up, check the Reset LED on the Single Board Computer. (See Figure 5-2 of Bulletin 440-12000 Rev. A. for the location of the RESET LED.) On all UEC modules the Reset LED should be steadily illuminated when power is present to the actuator. If Reset LED blinks every 1.5 sec, check that EPROMs are properly seated and that no pins are damaged or missing. If Reset LED blinks every 11-12 seconds, check that module is not in extended conguration mode. See Bulletin 440-12000 Rev. A. for other faults which may cause this LED to blink. Limitorque Corporation UEC-3 & UEC-3-MPC Installation & Commissioning Manual Bulletin 440-12100 6/96 17 5.3 UEC-3-MPC Calibration Procedure The calibration procedure for the UEC-3-MPC is given in the form of a flow chart in Figure 5-2. This procedure is also discussed in the Operation Manual. *Note Span and Zero reference must always be changed together Figure 5-2 - UEC-3-MPC Calibration Procedure (Sheet 1 of 4) Limitorque Corporation UEC-3 & UEC-3-MPC Installation & Commissioning Manual Bulletin 440-12100 6/96 18 SW2-1,2&3 on SW2-5,6,7 off Selector switch to Local Press Open button Wait until actuator stops at OPEN Set SW2-5 ON Press Close button Wait until actuator stops at Closed Set command as needed (20mA?) Set command as needed (4mA?) Change position of SW2-4 Change position of SW2-4 Setting Span and Zero* Are MPC parameters stored? No Yes Skip to section that requires adjustment Go to Test (Sheet 3) Note The default level for proportional band was factory set at 14.0% Note Default level for deadband was factory set at 1.0% Figure 5-2 - UEC-3-MPC Calibration Procedure (Sheet 2 of 4) Limitorque Corporation UEC-3 & UEC-3-MPC Installation & Commissioning Manual Bulletin 440-12100 6/96 19 Set S1 to the desired value as shown on Table 5-1 Change the position of SW2-4 Set SW2-1,2,3,6 & 8 ON Set SW2- 5 & 7 OFF Go to Test (Sheet 3) Set Proportional Band Set S1 to the desired value as shown on Table 5-1 Change the position of SW2-4 Set SW2-1,2,3,5,6 &8 ON Set SW2- 7 OFF Go to Test (Sheet 3) Set Deadband Figure 5-2 - UEC-3-MPC Calibration Procedure (Sheet 3 of 4) Limitorque Corporation UEC-3 & UEC-3-MPC Installation & Commissioning Manual Bulletin 440-12100 6/96 20 Set S1 for desired action.* Change the position of S2-4 Set S1-3,4,5,6,7,8 OFF Set S2-1,2,3,7 & 8 ON Set S2- 5 & 6 OFF Go to Test Set Action On Loss of Signal *S1-1 S1-2 Action OFF OFF CLOSE ON OFF STOP ON ON OPEN Figure 5-2 - UEC-3-MPC Calibration Procedure (Sheet 4 of 4) Limitorque Corporation UEC-3 & UEC-3-MPC Installation & Commissioning Manual Bulletin 440-12100 6/96 21 Set S2-1,2,3,5, 7 & 8 on Change the position of SW2-4 No Actuator movement properly follows command signal? See Section 6.4 Troubleshooting No Control satisfactory(response time, overshoot, accuracy?) Yes Yes Apply external 4- 20mA command signal Selector Switch to Remote S2-1,2,3,5,6,7,8 ON Change position of S2-4 S2-2 off Test Response to Signal Exit Extended Configuration SAVE TO EEPROM Remove external 4-20mA command signal Loss of signal action correct ? Yes No See Section 5.4 Troubleshooting Adjust proportional band & deadband See Sheet 2 End calibration Set S1 &2 for desired features Power OFF then ON Set action on loss of signal Table 5-1 - Table of Values for Proportional Band and Deadband % DIP S1 % DIP S1 12345678 123456 78 1 10000000 26 01011000 2 01000000 27 11011000 3 11000000 28 00111000 4 00100000 29 10111000 5 10100000 30 01111000 6 01100000 31 11111000 7 11100000 32 00000100 8 00010000 33 10000100 9 10010000 34 01000100 10 01010000 35 11000100 11 11010000 36 00100100 12 00110000 37 10100100 13 10110000 38 01100100 14 01110000 39 11100100 15 11110000 40 00010100 16 00001000 41 10010100 17 10001000 42 01010100 18 01001000 43 11010100 19 11001000 44 00110100 20 00101000 45 10110100 21 10101000 46 01110100 22 01101000 47 11110100 23 11101000 48 00001100 24 00011000 49 10001100 25 10011000 50 01001100 Limitorque Corporation UEC-3 & UEC-3-MPC Installation & Commissioning Manual Bulletin 440-12100 6/96 22 5.4 Troubleshooting If no Pushbutton Station LEDs are illuminated, see the Troubleshooting Charts. (See Figures 9-2, 9-3, and 9-4 of the Operation Manual.) 5.4.1 Troubleshooting Tools Limitorque has developed diagnostic tools to aid in troubleshooting UEC-3 and UEC-3-MPC controlled actuators. The use of either of these tools will assist in the quick diagnosis of actuator alarms and faults. 5.4.1.1 Universal Diagnostic Tool The Universal Diagnostic Tool (UDT) is a hand held device that can determine and diagnose the source of valve actuator alarms and faults on any UEC- 3 or UEC-3-MPC based actuator. It is designed as a rst-level diagnostic tool providing preliminary troubleshooting information and is very easy to use. Please refer to the UEC-3 and DDC-100 Diagnostic Interface Installation and Operation Manual - Bulletin 437-10000 for instructions on using the UDT. 5.4.1.2 Modsim Diagnostic Software A personal computer and Modsim diagnostic software can be used to trou- bleshoot the UEC-3 controlled actuator. Modsim is designed to provide detailed diagnostic information in addition to the information provided by the UDT. Please refer to the UEC-3 and DDC-100 Diagnostic Interface Installation and Operation Manual - Bulletin 437-10000 for UEC-3 to PC connectivity. Please refer to the Modsim Modbus Simulation Software Operation Manual - Bulletin 435-23001 for instructions for using Modsim. Limitorque Corporation UEC-3 & UEC-3-MPC Installation & Commissioning Manual Bulletin 440-12100 6/96 23 5.4.2 Component Replacement Limitorque recommends the eld replacement of Control and I/O Power Supply fuses, Single Board Computer, and Termination /Interconnect Board. If any other components within the UEC-3 or UEC-3-MPC module require replace- ment, it is recommended that the complete UEC-3 or UEC-3-MPC module be replaced. See Section 5.4.3 for instructions on replacing the complete UEC module. 5.4.2.1 Control Fuse Replacement The following procedure should be used to replace the 120V control power fuse (FS3) on the Power Supply Board: Tools required: Small athead screwdriver Parts Required: Control fuse: P/N: EF2-5X20MM-1A-250V 1. ISOLATE POWER FROM THE ACTUATOR. 2. Remove cover bolts and open control compartment cover. 3. Remove the larger clear cover of the UEC-3 by pressing down with both thumbs on indented areas on top edge of cover. 4. Locate the fuse cartridge near the 50 pin IDC connector and the heat sink. 5. Insert screwdriver into slot on cap of fuse cartridge and turn 90in the direction of the arrow. 6. Lift cap with fuse out of the cartridge. 7. Pull fuse out of cap and replace with Limitorque P/N: EF2-5X20MM-1A- 250V 8. Inspect replacement fuse to conrm that it is the correct size and undam- aged. 9. Be sure to insert replacement fuse rmly in cap. 10. Align the brackets on the cap and fuse assembly with the notch in the car- tridge and push straight in to insert. 11. Insert screwdriver into slot on cap of fuse cartridge and turn 90opposite direction of ARROW. 12. Replace clear cover. Limitorque Corporation UEC-3 & UEC-3-MPC Installation & Commissioning Manual Bulletin 440-12100 6/96 24 5.4.2.2. 24 VDC I/O Power Supply Fuse Replacement Tools required: Small at head screwdriver Parts required: 24VDC I/O Power Fuse P/N: EF2-5X20MM-1A-250V 1. ISOLATE POWER FROM ACTUATOR. 2. Remove cover bolts and open control compartment cover. 3. To gain access to the Termination/ Interconnect Board, remove the smaller clear cover on the UEC-3 by inserting a at head screwdriver in the gap at the front of the cover and lifting up and towards the base of the housing. 4. Locate the fuse near the pushbutton station IDC connector. 5. Remove the protective shroud from the fuse by inserting the screwdriver blade under the shroud at each end and pry gently. 6. Remove fuse by inserting the screwdriver blade under one end of the fuse and pry gently until it is free from the fuse holder. 7. Inspect the replacement fuse (Limitorque P/N: EF2-5X20MM-1A-250V) to conrm that it is the correct size and undamaged. 8. Insert the replacement fuse by lining up the metal ends with the metal brackets on the fuse holder and pushing the fuse straight down into the fuse holder. 9. Replace protective shroud over the fuse and holder. To ease replacement, squeeze the ends of the shroud gently to expand as you are replacing. 10. Replace clear plastic cover. Limitorque Corporation UEC-3 & UEC-3-MPC Installation & Commissioning Manual Bulletin 440-12100 6/96 25 5.4.2.3. Single Board Computer (SBC) Replacement The following procedure should be used to replace the SBC: Tools required: Medium phillips head screwdriver Small non-metallic tool for DIP Switch setting Parts Required: Single Board Computer: P/N: 61-825-0996-1 1. ISOLATE POWER FROM ACTUATOR. 2. Remove cover bolts and open control compartment cover. 3. Remove the larger clear cover of the UEC-3 by pressing down with both thumbs on indented areas on top edge of cover. 4. Unlatch and release the 34-pin ribbon cable on the SBC located near the heat sink. 5. Remove the four screws securing the SBC and remove the board. 6. It is not necessary to replace the insulator sheet with a new sheet unless visible damage is present. 7. Inspect replacement SBC for obvious damage and verify that the Analog to Digital Converter (ADC) chip (if required) is installed. Note Make sure that Analog to Digital Converter (ADC) chip is installed for modulating applications. 8. Connect the 34-pin connector into the replacement SBC. 9. Position replacement SBC on top of the insulator sheet and secure with four screws. 10. Set the DIP switch on the replacement SBC to match the one being replaced. 11. Replace the UEC-3 clear cover. Limitorque Corporation UEC-3 & UEC-3-MPC Installation & Commissioning Manual Bulletin 440-12100 6/96 26 5.4.2.4. Termination/Interconnect Board Replacement The following procedure should be used to replace the Termination /Interconnect Board: Tools required: Medium phillips head screwdriver Small at head screwdriver Parts required: Termination/Interconnect Board: P/N: TM74-743-0050 1. ISOLATE POWER FROM ACTUATOR. 2. Remove cover bolts and open control compartment cover. 3. Remove the larger clear cover of the UEC-3 by pressing down with both thumbs on indented areas on top edge of cover. 4. Unlatch and remove the 50 pin ribbon connector located at the end of the Termination/Interconnect Board adjacent to the SBC near the 34 pin con- nector. Return the release latches to the closed position. 5. Remove smaller clear cover by inserting a at head screwdriver in the gap at the bottom of the cover and lifting up and towards the base of the housing. 6. Disconnect all incoming wires to the Termination/Interconnect Board. Make sure all wires are labeled for easy reconnection. 7. Position latches for both IDC connectors on the Termination/ Interconnect Board to the closed position before attempting to remove. 8. Remove and retain the 4 mounting screws on the Termination/Interconnect Board. Pull the Termination/Interconnect Board away from the SBC to clear the 50 pin connector to remove. 9. Inspect the replacement Termination/Interconnect Board for obvious damage. 10. Position latches for both IDC connectors on the replacement Termination/ Interconnect Board to the closed position before attempting to install. 11. Install the replacement board by gently inserting the 50 pin connector into the slot adjacent to SBC. The 40 pin connector will t in the slot provided. Secure this board with 4 mounting screws. 12. Reconnect wires to the terminals on the replacement Termination/ Interconnect Board. 13. Replace small clear cover. 14. Reconnect the 50 pin ribbon cable to the Termination/Interconnect Board. 15. Replace larger clear cover. 16. Reconnect IDC connector (J6). Limitorque Corporation UEC-3 & UEC-3-MPC Installation & Commissioning Manual Bulletin 440-12100 6/96 27 5.4.3 Complete UEC-3 or UEC-3-MPC Module Replacement The procedure for the replacement of the complete UEC-3 or UEC-3-MPC module is as follows: Tools required to replace the complete UEC-3 or UEC-3-MPC Module: Small at blade screwdriver Medium at blade screwdriver Small non-metallic DIP switch tool Parts Required: Replacement UEC-3 or UEC-3-MPC Module - contact your local distributor or Limitorque Parts Department for correct P/N for your application. 1. ISOLATE POWER FROM THE ACTUATOR. 2. Remove cover bolts and open control compartment cover. 3. Disconnect leads from the UEC module at the terminal strip. 4. Disconnect ribbon cable connections to Pushbutton Station and geared limit switch at Termination/Interconnect Board. 5. Disconnect remaining Termination/Interconnect Board wiring to other devices such as an R/I converter. 6. Remove and save the 4 mounting screws on the base of the UEC module and remove the assembly. 7. Set the DIP switches on the SBC of the replacement module to match those of the module removed. 8. Check to make sure that the transformer voltage on the replacement module is the same as on the module removed. If not, please refer to Section 2.6 - Supply Voltage for the procedure to change the voltage. Note Replacement UEC-3 and UEC-3-MPC modules are shipped with 460V transformer voltage as standard unless otherwise specied on parts order. 9. Mount the new UEC-3 module on the mounting plate using 4 screws. Note For replacement in L-120 actuators, it is necessary that the module be secured rst by the mounting screw closest to the input wires, followed by the screw on the opposite side of the box. These should hold the module secure while the remaining screws are put in. Limitorque Corporation UEC-3 & UEC-3-MPC Installation & Commissioning Manual Bulletin 440-12100 6/96 28 10. Reconnect wiring and ribbon cables to the Termination/Interconnect Board. 11. Connect wires from UEC-3 module to terminal strip according to wiring diagram supplied with actuator. 12. Reapply power to the actuator. 13. Verify proper operation. See Section 5.2. Limitorque Corporation UEC-3 & UEC-3-MPC Installation & Commissioning Manual Bulletin 440-12100 6/96 29 This page is intentionally blank. Limitorque Corporation UEC-3 & UEC-3-MPC Installation & Commissioning Manual Bulletin 440-12100 6/96 30 6. Conversion of the UEC-3 Basic Controller An installed UEC-3 control module can be modied in the eld to operate as a UEC-3-MPC controller. These changes should be performed by a qualied technician using genuine Limitorque parts and following the procedures in this section. All tools and parts required are listed in each procedure. 6.1 Converting UEC-3 to UEC-3-MPC Position Controller The UEC-3-MPC is a 4-20 milliAmp controller which will change the position of the valve in proportion to a current signal received from a set point con- troller or similar device. An actuator originally supplied with UEC-3 controls may be changed to UEC- 3-MPC controlled actuator. The following procedures should be used to convert a UEC-3 actuator to a UEC-3-MPC actuator: Tools required: Small non-metallic DIP switch tool Small at blade screwdriver Medium at blade screwdriver Parts required: Feedback potentiometer: Consult factory for part required Analog Interface Board: P/N: 61-825-0962-2 A/D Converter Chip: P/N: 61-825-0733-1 Optional UEC-3-MPC parts: PT20SD Position Transmitter: P/N: TM74-743-0066 1. ISOLATE POWER FROM THE ACTUATOR. 2. Remove actuator cover bolts and open control compartment cover. 3. Install potentiometer if not already installed in actuator. See actuator Instruction and Maintenance manual for installation instructions or contact your local Limitorque distributor for information. 4. Install Analog Interface Board. Analog board installation differs with type and size of actuator. Consult factory or nearest service center for instal- lation instructions. Limitorque Corporation UEC-3 & UEC-3-MPC Installation & Commissioning Manual Bulletin 440-12100 6/96 31 5. Remove the large clear cover on the UEC-3 module and connect ribbon cable, J3A, from the Analog Interface Board to J3 connector on the Single Board Computer (SBC). When the cover is replaced, the ribbon cable will t through the cut-out in the cover. 6. Before replacing the cover, install the Analog to Digital Converter chip into U18 on the Single Board Computer being careful to match notches and avoid bending pins. The location of the Analog to Digital Converter (U18) is shown in Figure 5-2 of the Operation Manual. 7. Calibrate the UEC-3-MPC (See UEC-3 Operation Manual - Bulletin 440- 12000 Rev. A., and Section 5.3 of this manual for calibration procedure). 6.1.1 Installation of the PT20SD (Optional) The procedure and parts required for the installation of PT20SD differs accord- ing to the type and size of Limitorque actuator. Please consult the nearest Limitorque Blue Ribbon Service facility or Limitorques Service Department for assistance. Limitorque Corporation UEC-3 & UEC-3-MPC Installation & Commissioning Manual Bulletin 440-12100 6/96 32 7. Parts X indicates that parts are standard. O indicates that parts are optional. Item Part Number UEC MPC Single Board Computer 61-825-0996-4 X X Termination/Interconnect Board 61-825-1060-3 X X 3 Phase Power Supply Board 61-825-1235-4 X X Single Phase & Special Power Supply Boards 61-825-1234-4 O O Primary Fuses (FS1 & FS2) EF4-TDC11-250MA X X Control Fuse (FS3) EF2-5X20MM-1A-250V X X 24VDC I/O Power Fuse (FS4) EF2-5X20MM-1A-250V X X PT 20SD TM74-743-0066 O O SBC Analog Board 61-825-0962-2 X SW93 Pushbutton Station TM74-790-0033 X X Customer Service Kit TM0700504 O O Universal Diagnostic Tool 61-825-0950-3 O O UDT Serial Interface Adapter 61-825-0951-3 O O ADC Chip 61-825-0733-1 X Note Part Numbers are subject to change as product improvements are introduced. Consult Limitorque for current part numbers. Limitorque Corporation UEC-3 & UEC-3-MPC Installation & Commissioning Manual Bulletin 440-12100 6/96 33 This page is intentionally blank. Limitorque Corporation UEC-3 & UEC-3-MPC Installation & Commissioning Manual Bulletin 440-12100 6/96 34 8. Customer Service For parts or parts information, call your local Limitorque distributor or the Parts Department in Lynchburg, VA, at 804-522-9833. For fastest response, please have the order number and serial number from the actuator available when contacting Limitorque for parts or parts information. This information can be found on a Limitorque label afxed to the main housing of the actuator. For service information, call your local Limitorque distributor, Blue Ribbon Service Center or the Service Department in Lynchburg, VA, at 804-845-9366. For fastest service, please have the order number and serial number from the actuator available when contacting Limitorque with service questions. This information can be found on a Limitorque label afxed to the main housing of the actuator. Limitorque Corporation UEC-3 & UEC-3-MPC Installation & Commissioning Manual Bulletin 440-12100 6/96 35 Limitorque
Bulletin 440-12100 6/96
For further Limitorque service assistance call: Limitorque Corporation 7615 Boeing Drive Greensboro, NC 27409-8347 Phone (910) 668-0871 Fax (910) 605-5310 Limitorque Corporation 8901 Jameel Road Suite 180 Houston, TX 77040 Phone (713) 690-1960 Fax (713) 690-1277 or contact the Limitorque ofces listed below Limitorque Corporation 5114 Woodall Road P.O. Box 11318 Lynchburg, VA 24506-1318 Phone (804) 528-4400 Fax (804) 845-9736 Limitorque International Trinity House Kennet Side Newbury Berkshire, RG15 5EH England Phone 44-1-635-46999 Fax 44-1-635-36034 Limitorque/Nippon Gear Co. Ltd. Tennoz Central Tower 2-2-4, Higashi-Shinagawa, Shinagawa-Ku, Tokyo 140, Japan Phone 03-5460-7516 Fax 03-5460-8396 Limitorque of India, Ltd. E-45/2 Okhla Industrial Area, Phase-II New Delhi 110 020, India Phone 91-129-277135 Fax 91-11-683-9329 Limitorque Australia Ltd. Division of Control Engineering (Aust.) Pty., Ltd. 17 Scoresby Road Bayswater, Victoria 3153, Australia Phone 613-729-0555 Fax 613-729-8225 Limitorque Asia Pte Ltd. 75 Bukit Timah Rd. #05-01/02 Boon Siew Building Singapore 229833 Phone 65-332-9100 Fax 65-332-9112