Beruflich Dokumente
Kultur Dokumente
I
25% 132.10 V 131.26 V 1441.5 mA
50% 131.76 V 130.03 V 2.81 A
75% 131.05 V 128.23 V 4.29 A
100% 130.52 V 127.09 V 5.58 A
Table 2: Two Sections of the Feeder in
Series.
Load
I
25% 132.17 V 130.89 V 1429.0 mA
50% 131.43 V 128.67 V 2.754 A
75% 130.85 V 125.90 V 4.213 A
100% 130.30 V 123.79 V 5.423 A
R
Generator
1 2
X
2 1
Resistive
Load
Experiment 2: Single-Phase Radial Network
Feeding I nductive and Capacitive Loads
Table 3A: Inductive Load.
Load
I
25% 132.44 V 127.11 V 1202.5 mA
50% 132.35 V 120.96 V 2.396 A
75% 132.17 V 114.93 V 3.581 A
100% 130.01 V 111.00 V 4.418 A
Table 3B: Capacitive Load.
Load
I
25% 133.88 V 140.48 V 1525.5 mA
50% 133.30 V 149.28 V 3.285 A
75% 133.47 V 145.69 V 5.232 A
100% 133.67 V 150.64 V 7.385 A
Experiment 3: Ring Distribution Network
Supplying Resistive, Inductive and Capacitive
Loads
Table 4A: Ring Network with Resistive Load.
= 132.05 V
Load
I
%
Regulation
25%
132.36
V
130.68
V
143.5
mA
0.26
50%
131.93
V
130.48
V
2783.8
mA
0.41
75%
131.13
V
128.65
V
4270.0
mA
1.84
100%
130.65
V
127.31
V
5.557A 2.91
Table 4B: Ring Network with Inductive Load.
= 132.41 V
Load
I
%
Regulation
25%
132.77
V
129.96
V
1234.6
mA
1.89
50%
132.51
V
126.38
V
2519.4
mA
4.77
75%
132.28
V
123.09
V
3839.8
mA
7.57
100%
132.09
V
120.67
V
4.828
A
9.73
Table 4C: Ring Network with Capacitive Load.
=133.10 V
Load
I
%
Regulation
25%
133.21
V
136.92
V
1492.8
mA
2.79
50%
133.34
V
141.10
V
3080.4
mA
5.67
75%
133.71
V
145.43
V
4.781
A
8.48
100%
133.89
V
149.55
V
6.594
A
10.99
III. DISCUSSIONS
Experiment 1: Single-Phase Radial Network
Feeding a Resistive Load
Procedure A: One Section of the Feeder
Circuit diagram obtained from the connection in
Appendix A;
The percentage regulation using the Equation 1.5
for each load setting;
% Regulation = 100
r
r s
V
V V
(1.5)
For load: 25%
For load: 50%
For load: 75%
For load: 100%
The percentage regulation against load current;
Graph 1.1
As we can see from the Graph 1.1, the
percentage regulation is increases due to the load
current increases. Regarding to Ohms Law, V=IR
it states that current flowing is directly
proportional to the voltage and inversely
proportional to the resistance. Therefore, if the
voltage is increased, the current will increase if the
resistance of the circuit does not change. Same
goes to the increasing resistance of the circuit will
lower the current flow if the voltage is not
changed. This formula shows that there is
relationship between this three variable.
Procedure B: Two Section of the Feeder
The circuit diagram obtained from the connection
in Appendix B;
The percentage regulation using the Equation 1.5
for each load setting;
For load: 25%
For load: 50%
For load: 75%
For load: 100%
0
2
4
6
0 1 2 3 4 5 6
P
e
r
c
e
n
t
a
g
e
r
e
g
u
l
a
t
i
o
n
(
%
)
Load current (A)
Percentage Regulation against load current for one
section of the feeder
X2
1 2
R
Generator
1 2
X
2 1
R2
2 1
Inductive
Load
The percentage regulation against load current;
Graph 1.2
Comparison of the regulation- load current
curves obtained when one section and two
sections of the feeder are used to supply the load;
Graph 1.3
In the Graph 1.3, the line curve percentage
regulation for two sections of the feeder is higher
than line curve percentage regulation for one
section of the feeder. Based on the Ohms Law. the
voltage will be higher as the impedance is increase
and that will lead to the higher percentage
regulation. In this experiment, the impedances for
two feeders, are higher rather than one feeder,
Based on the results, current is one of the
factors that determine the voltage regulation . As
the percentage of load current is negative, the
percentage regulation will be increase. Length of
the feeder also one of the factors that will affect the
voltage regulation. The percentage regulation will
be increase if we increase the length of the feeder.
So, we can see the effect of loading and
feeder length on the voltage regulation in a radial
distribution network feeding a resistive load.
Experiment 2: Single-Phase Radial Network
Feeding I nductive and Capacitive Loads
Procedure A: Inductive Load
The circuit diagram obtained from the connection
in Appendix C;
The percentage regulation using the Equation 1.6
for each load setting.
% Regulation = 100
r
r s
V
V V
(1.6)
For load: 25%
For load: 50%
For load: 75%
0
1
2
3
4
5
6
0 1 2 3 4 5 6
P
e
r
c
e
n
t
a
g
e
r
e
g
u
l
a
t
i
o
n
(
%
)
Load current(A)
Percentage Regulation against load current for two
section of the feeder
0
2
4
6
0 1 2 3 4 5 6 P
e
r
c
e
n
t
a
g
e
r
e
g
u
l
a
t
i
o
n
(
%
)
Load current(A)
Percentage regulation against load current for one and
two section of the feeder.
one section of
the feeder
two sections of
the feeder
For load: 100%
Graph 2.1
Comparison of the regulation- load current
curves obtained for inductive load and resistive
load;
Graph 2.2
As we can see in Graph 2.2, inductive load
having higher percentage regulation than resistive
load. It is show that inductive load has more
voltage loss when compared to resistive load.
Procedure B: Capacitive Load
The percentage regulation using the Equation 1.6
for each load setting.
For load: 25%
For load: 50%
For load: 75%
For load: 100%
0
2
4
6
8
10
12
14
16
18
20
0 1 2 3 4 5
P
e
r
c
e
n
t
a
g
e
r
e
g
u
l
a
t
i
o
n
(
%
)
Load currents(A)
Percentage regulation against load current for inductive
load
0
2
4
6
8
10
12
14
16
18
20
0 1 2 3 4 5 6
P
e
r
c
e
n
t
a
g
e
r
e
g
u
l
a
t
i
o
n
(
%
)
Load current (A)
Percentage regulation against load current for inductive
load and resistive load
inductive load
resistive load
0
2
4
6
8
10
12
0 2 4 6 8
P
e
r
c
e
n
t
a
g
e
r
e
g
u
l
a
t
i
o
n
(
%
)
Load current (A)
Percentage regulation against load current for capacitive
load
X2
1
2
R
Generator
1
2
X
2
1
R2
2
1
Resistive
Load
Graph 2.3
Comparison of the regulation- load current
curves obtained for capacitive load and inductive
load;
Graph 2.4
Based on calculation, capacitive load actually
having negative percentage regulation. So,
theoretically, the percentage regulation for
capacitive load is less than inductive load.
For the inductor, assume the current through is
it same as resistor, and the voltage across the
inductor is
which transforms to the phasor,
but
, and
, thus
showing that the voltage has a magnitude of
and a phase of The voltage and current
are out of phase. Specifically, the current lags
the voltage by .
For the capacitor, assume the voltage across it
is
And by referring to steps as we took for the
inductor, we obtain
showing that the current and voltage are out of
phase. To be specific, the current leads the voltage
by . And this explain why capacitive loads
results in less voltage regulation than inductive
loads.
Experiment 3: Ring Distribution Network
Supplying Resistive, Inductive and Capacitive
Loads
Procedure A: Resistive Load
The circuit diagram obtained from the connection
in Appendix D (for resistive load);
The percentage regulation for each load using the
expression;
% Regulation = 100
r
r nL
V
V V
(1.7)
0
2
4
6
8
10
12
14
16
18
20
0 2 4 6 8
P
e
r
c
e
n
t
a
g
e
r
e
g
u
l
a
t
i
o
n
(
%
)
Load current (A)
Percentage regulation against load current for capacitive
load and inductive load
inductive
capacitive
load
Inductive
Load
Generator
2
1
1
2
X2
1
2
R R2
2
1
X
For load: 25%
For load: 50%
For load: 75%
For load: 100%
Comparison results for the voltage regulation
with the corresponding results obtained from the
radial feeder in Experiment 1;
Graph 3.1
As can be seen in Graph 3.1, radial feeder
curve is slightly different than ring feeder. The
percentage regulation are almost the same for the
second , third and fourth point of the radial and
ring network.
Procedure B: Inductive Load
The circuit diagram obtained from the connection
in Appendix D (for inductive load);
The percentage regulation for each load using the
expression 1.6;
For load: 25%
For load: 50%
For load: 75%
For load: 100%
Comparison results for the voltage regulation
with the corresponding results obtained from the
radial feeder in Experiment 2;
0
0.5
1
1.5
2
2.5
3
3.5
0 1 2 3 4 5 6
P
e
r
c
e
n
t
a
g
e
r
e
g
u
l
a
t
i
o
n
(
%
)
load current (A)
Percentage regulation against load current for radial
network resistive load and radial network resistive load
radial
network
resistive load
ring network
resistive load
Capacitive
Load
Generator
2
1
1
2
X2
1
2
R R2
2
1
X
Graph 3.2
Referring to Graph 3.2, radial feeder curve
regulation-load current is rising higher than ring
feeder for each point.
Procedure C: Capacitive Load
The circuit diagram obtained from the connection
in Appendix D (for capacitive load);
The percentage regulation for each load using the
expression 1.6;
For load: 25%
For load: 50%
For load: 75%
For load: 100%
Comparison results for the voltage regulation
with the corresponding results obtained from the
radial feeder in Experiment 2;
Graph 3.3
The effect of load power factor upon voltage
regulation for each of resistive, inductive and
capacitive loads;
0
2
4
6
8
10
12
14
16
18
20
0 2 4 6
P
e
r
c
e
n
t
a
g
e
r
e
g
u
l
a
t
i
o
n
(
%
)
Load current (A)
Percentage regulation against load current for inductive
load in radial and ring feeder
radial
network
inductive
load
ring network
inductive
load
0
2
4
6
8
10
12
14
16
18
20
22
24
0 2 4 6 8
P
e
r
c
e
n
t
a
g
e
r
e
g
u
l
a
t
i
o
n
(
%
)
Load current (A)
Percentage regulation against load current for capacitive
load in radial and ring feeder
radial
network
capacitive
load
ring network
capacitive
load
Graph 3.4
In this experiment, we can calculate the
"power factor", which is defined as the cosine of
this angle based on the phase difference between
the voltage and current signals. In an electric
power system, a load with a low power factor
draws more current than a load with a high power
factor for the same amount of useful power
transferred. The higher currents increase the
energy lost in the distribution system, and require
larger wires and other equipment. Because of the
costs of larger equipment and wasted energy,
electrical utilities will usually charge a higher cost
to industrial or commercial customers where there
is a low power factor.
Linear loads with low power factor (such as
induction motors) can be corrected with a passive
network of capacitors or inductors. Non-linear
loads, such as rectifiers, distort the current drawn
from the system. In such cases, active or passive
power factor correction may be used to counteract
the distortion and raise the power factor. The
devices for correction of the power factor may be
at a central substation, spread out over a
distribution system, or built into power-consuming
equipment.
In a purely resistive AC circuit, voltage and
current waveforms are in step (or in phase),
changing polarity at the same instant in each cycle.
All the power entering the load is consumed (or
dissipated). Where reactive loads are present, such
as with capacitors or inductors, energy storage in
the loads results in a time difference between the
current and voltage waveforms.
If a load had a capacitive value, inductors
(also known as reactors in this context) are
connected to correct the power factor. In the
electricity industry, inductors are said to consume
reactive power and capacitors are said to supply it,
even though the energy is just moving back and
forth on each AC cycle.
When the load is inductive, the inductance
tends to oppose the flow of current, storing energy
then releasing it later in the cycle. The current
waveform lags behind the voltage waveform.
When the load is capacitive, the opposite occurs,
and the current waveform leads the voltage
waveform.
So, lagging and leading is another way of
saying the net reactance is either inductive or
capacitive.
IV. CONCLUSION
As a conclusion, we can say since the voltage
drop for the ring network is lower than radial
network, it means that the ring distribution network
is better than radial network. All the objectives for
this experiment are achieved as we assuredly
managed to investigate the effect of loading and
feeder length on the voltage regulation in a radial
distribution network feeding a resistive load, the
effect that the inductive and capacitive loads have
upon the voltage regulation of a radial feeder, and
the voltage regulation for a simple ring distribution
network when it supplies resistive, inductive and
capacitive loads. Other than that, we also make
comparison between ring and radial networks.
V. REFERENCES
1. http://en.wikipedia.org/wiki/Power_fact
or
2. http://www.allaboutcircuits.com/vol_2/ch
pt_11/3.html
3. http://en.wikipedia.org/wiki/Electric_pow
er_transmission
0
1
2
3
4
5
6
7
0 2 4 6 8
P
e
r
c
e
n
t
a
g
e
r
e
g
u
l
a
t
i
o
n
s
(
%
)
Load current (A)
Percentage regulation against load current for resistive,
inductive and capacitive load
resistive load
inductive load
capacitive
load
4. http://epb.apogee.net/foe/home.asp
5. http://yourelectrichome.blogspot.com