Sie sind auf Seite 1von 20

Power Transmission and Distribution

SIPROTEC 7SD5/7SD6
Power Transmission and Distribution
No. 1 with
Energy Automation
Energy Automation Buenos Aires Nov 05 Page 2
Rels Diferenciales de lnea 87L-SIPROTEC
Relays diferenciales de lnea Universal
87L SIPROTEC
con interface / interfaces de comunicacin seriales
7SD610 / 7SD522 / 7SD523
7SD522/3 7SD522/3 7SD610
Power Transmission and Distribution
No. 1 with
Energy Automation
Energy Automation Buenos Aires Nov 05 Page 3
Hardware: opcin de interfaces de comunicacin
Interface Proteccin 2
Port E
Synchronous N x 64kB/ sec
7
S
D
5
2
3
s
o
lo
7SD523 solo
Interface Proteccin 1
Port D
Synchronous N x 64kB/sec
Entrada sinc.
Tiempo Serial
Receptor GPS
telegrama de tiempo
pulso 1 s (7SD52)
Interfacemodul 1
RS485 o FO
o RS232
Interface servicio
DIGSI 4; tambin para
conexin modem
y Browser de INTERNET
local-PC
interface
DIGSI
Browser
local
Control Subestacin
protocolo IEC103
comunicacin mdulos
FO (fibra optic) o RS485
o RS232
Available Protocols
IEC - standard
Interfacemodul 2
RS485 o FO
Interface control Subst.
mdulos
Plug in
Lnea Remota lado 2
Lnea Remota lado 1
7SD52 / 7SD610
Power Transmission and Distribution
No. 1 with
Energy Automation
Energy Automation Buenos Aires Nov 05 Page 4
Placa Principal
Zcalo para
mdulos
de Comunicacin
Placa Principal del rel con sus Interfaces de comunicacin
Power Transmission and Distribution
No. 1 with
Energy Automation
Energy Automation Buenos Aires Nov 05 Page 5
FO
820 nm, 1,5 km
1300 nm, 24 km
multimodo
monomodo
1300 nm, 60 km
1550 nm, 100 km
monomodo
monomodo
Conexin Directa con cables de fibra ptica (FO)
- Ofrece alta velocidad de disparo (16 ms), baudrate es 512 kBit/s
- Flexible: mdulos plug-in para diferentes fibras o distancias
distancia FO-cable conector
ST
LC
LC
LC
Aplicacin - conexin fibra ptica
Power Transmission and Distribution
No. 1 with
Energy Automation
Energy Automation Buenos Aires Nov 05 Page 6
lnea telefnica alquilada (standby o dial-up)
- 2 hilos cable de telefnico (max. 8 km)
E
O
O
E
820 nm, 1,5 km
Convertidor de
Comunicacin
par telefnico
max. 8 km
5 kV aislacin
integrada
Aplicacin - lnea telefnica alquilada
Power Transmission and Distribution
No. 1 with
Energy Automation
Energy Automation Buenos Aires Nov 05 Page 7
Aplicaciones - Lnea o cable con diferente relacin de CT
400:5, 10P10, 10VA, k
Alf
= 59, k = 50
opcin VT
No requerida
para funcin diff.
- Diferente relacin de CT permitida hasta1:8, 1A o 5A entrada ajustable en relay
- Los datos / errores de los CT son ajustados en el relay
y automticamente considerados en el calculo de la corriente
- Requerimientos de CT: k
Alf
para el CT local debe ser mayor que k (k
Alf
,
men
= 30)
600:1, 5P20, 20 VA, k
Alf
= 130, k = 33,3
___
I
N,CT
I
K,max
k=
20 kA
87L
50/51
50 BF (7SD610)
49
k
Alf
= k
ALF,N
P
i
+ P
N
P
i
+ P
B
Power Transmission and Distribution
No. 1 with
Energy Automation
Energy Automation Buenos Aires Nov 05 Page 8
20 MVA, 110 kV/20 kV, Yd1
10P10, 10 VA, 200:1 10P10, 10 VA, 500:5
-Ajustes de datos del Transformador en cada relay con ajuste de grupo de
conexin, adaptacin de relacin y eliminacin secuencia cero
-El setpoint diferencial es ajustado a la corriente nominal del Transformador
-Restriccin de Inrush con segunda armnica incluida (tiempo lmite para
bloqueo cruzado)
-Elemento de ajuste alto para disparo inmediato (16 ms) para grandes
corrientes internas de falla
disparo
comando
2 km
87T
50/51
50 BF (7SD610, 7SD52)
49
Aplicacin - Transformador y lnea/cable en la zona de Proteccin
Power Transmission and Distribution
No. 1 with
Energy Automation
Energy Automation Buenos Aires Nov 05 Page 9
Aplicacin para un terminal de tres extremos, configuracin
con 7SD523
Red de comunic
SDH
X21
G703.1
820 nm
max.
3 km
e
o
PCM
multi-
plexor
cable de fibra ptica monomodo hasta 100 kmcon interface de 1550 nm
relay distancia
7SA52
c
a
b
l
e

f
i
b
r
a

p
t
i
c
a

m
o
n
o
m
o
d
o
h
a
s
t
a

1
0


k
m
(
1
3
0
0

n
m

m
o
d
u
l
)
PCM
multi-
plexor
o
e
o
e
Comms-
converter
G703.1: 64 kBit
X21: N*64 kBit (1? N?8)
opcin:
GPS-
Sincronizacin
de tiempo
- Configuraciones mixtas posibles (FO y redes de datos)
- El sistema anillo ofrece redundancia diferencial
(cambiar de anillo-> el cambio a cadena toma 25 ms)
- Tagging de tiempo exacto en cada relay (resolucin 10 us)
- Entradas VT como estndar
(funcin 87 solo requiere CTs)
- conexi n a un sistema de comunicaciones con un equipo
provisto por SIEMENS
FC-conector
conector ST
ST-conector
Power Transmission and Distribution
No. 1 with
Energy Automation
Energy Automation Buenos Aires Nov 05 Page 10
Anillo cerrado Suma parcial
de corriente
I
3
I
2
I
1
lado 1
lado 2
lado 3
I
3
I
2
I
1
lado 1
lado 2
lado 3
I
3
+I
1
I
2
I
1
+I
2
I
3
I
3
+I
1
I
1
+I
2
conexin
a
otros
relays dif.
cambio Automtico de
anillo cerrado a cadena, si
una conexin se pierde
o no est disponible
Topologa de Anillo y Cadena
Prdida de una conexin de datos tolerado
Power Transmission and Distribution
No. 1 with
Energy Automation
Energy Automation Buenos Aires Nov 05 Page 11
Anillo cerrado
I
2
I
1
lado 1
lado 2
Conexin
Directa FO.
Conexin
Principal
512 kBit/s
Para la
funcin 87L
convertidor
De Comunic.
R
e
d

d
e

c
o
m
u
n
i
c

FO, 62,5/125 um
X21 or
G703.1
conexin
Hot standby.
supervisin
Permanente.
I
2
I
1
lado 1
convertidor
De Comunic.
R
e
d

d
e

c
o
m
u
n
i
c
FO, 62,5/125 um
X21 or
G703.1
(64 kBit/S)
conexin
Hot standby
activa ahora
para 87 L.
Cambio
toma 20 ms
Conexin
principal
interrump.
perdida de
conexin
principal
Conexin
principal
establecida
de nuevo
Conexin Hot - Standby
en configuracin de dos terminales
Power Transmission and Distribution
No. 1 with
Energy Automation
Energy Automation Buenos Aires Nov 05 Page 12
SIPROTEC 7SD52/7SD61
Alcance de funciones(1)
* Solo con 7SD523
Proteccin Diferencial ANSI No
Proteccin Diferencial multi-terminal Fase selectiva 87L,87T
(2 - 6 terminales*). Tiempo de Trip 15 ms con
Proteccin de comparacin de corriente rpida
(ajuste de IDiff>> a > 1,5 Icarga max)
Comparacin del vector Fundamental para el estado
de disparo sensitivo (ajuste de IDiff> < 0,2-0,3 IN)
Recierre automtico opcin 1/3 polos 79
Caractersticas de comunicacin
Asistencia de puesta en servicio
Proteccin de sobrecarga 49
Power Transmission and Distribution
No. 1 with
Energy Automation
Energy Automation Buenos Aires Nov 05 Page 13
SIPROTEC 7SD52/7SD61
Alcance de funciones(2)
ANSI No.
Sobrecorriente de respaldo/emergencia 50(N),51(N)
Proteccin Falla de Interruptor 50BF
Proteccin de cierre sobre falla
4 comandos remotos
Interdisparo (tambin desde un externo)
Lgica definida por el usuario (CFC)
Tagging de tiempo exacto para terminal local y remota 85-87
Sincronizacin por GPS
Power Transmission and Distribution
No. 1 with
Energy Automation
Energy Automation Buenos Aires Nov 05 Page 14
SIPROTEC 7SD52
Alcance de funciones
7SD52 + 7SA52
Proteccin Diferencial + Distancia ANSI No
Proteccin Diferencial multi-terminal Fase selectiva 87L,87T
(2 - 6 terminales*).
Proteccin de Distancia como respaldo de la 21
proteccin diferencial o como proteccin principal
Clculo de la distancia a la falla con la informacin FL
de ambos extremos
Funcionalidades completas de 7SD52+7SA52
Power Transmission and Distribution
No. 1 with
Energy Automation
Energy Automation Buenos Aires Nov 05 Page 15
Acceso a los relay con un Browser
1. Conexin Serial
- Directa o va
modem con una red
DIAL-UP estndar
sistema de ayuda en
INTRANET / INTERNET
http://www.siprotec.de
HTML
Pages
2. Pagina HTML vista en Browser
con la IP-address del relay
http://141.142.255.103
La homepage del relay es:
http://141.142.255.103
IP-address es ajustado con DIGSI 4
Para puerto frontal y posterior de
servicio
WEB server en el firmware
del relays
Server enva su pagina HTML
y JAVA-code al Browser
Despues de conexin DIAL-UP
87L SIPROTEC Tecnologa Web incluida
Power Transmission and Distribution
No. 1 with
Energy Automation
Energy Automation Buenos Aires Nov 05 Page 16
Puesta en servicio basada en un Browser
Power Transmission and Distribution
No. 1 with
Energy Automation
Energy Automation Buenos Aires Nov 05 Page 17
corrientes (amount / phasor) diferencial y restraint corriente Valores
d
i
f
e
r
e
n
c
i
a
l

c
o
r
r
i
e
n
t
e
Vista Grfica en un Browser
con carga 50%
Power Transmission and Distribution
No. 1 with
Energy Automation
Energy Automation Buenos Aires Nov 05 Page 18
Diagrama vectorial de mediciones local y remoto
Power Transmission and Distribution
No. 1 with
Energy Automation
Energy Automation Buenos Aires Nov 05 Page 19
Anlisis de falla completo con SIGRA 4
iEe iL1 iL2 iL3
t/s
-0,075 -0,050 -0,025 0,000 0,025 0,050 0,075 0,100 0,125
I/A
-2,00
-1,50
-1,00
-0,50
-0,00
0,50
1,00
1,50
uL1 uL2 uL3
t/s
-0,075 -0,050 -0,025 0,000 0,025 0,050 0,075 0,100 0,125
U/V
-80
-60
-40
-20
0
20
40
60
80
Power Transmission and Distribution
No. 1 with
Energy Automation
Energy Automation Buenos Aires Nov 05 Page 20
Condiciones de prefalla y falla en diagrama de vectores