TPE3000 THERMAL OIL HEATER IOM PROJ ECT: CO-O 750K TPA CIL GOLD PLANT April 11,

PLANT April 11, 2012







SECTION 9


INSTRUMENT DATA

TPE3000 THERMAL OIL HEATER IOM PROJ ECT: CO-O 750K TPA CIL GOLD PLANT April 11, 2012



CONTENT:

UNITED TEMPERATURE SWITCH F100-8BS
UNITED DIFFERENTIAL SWITCH J 21K-357
HARWILL FLOW SWITCH Q5SS/5/S/B
STACK OVERTEMP
PRESSURE GAUGE
TEMPERATURE GAUGE


GENERAL
Types B100 and C100 (Immersion Stem)
Temperature variations are sensed by a liquid filled sensor which expands
or contracts against a bellows which actuates a snap-action switch at a
predetermined set point.
Types E100 and F100 (Bulb & Capillary)
Temperature variations of a liquid filled sensing bulb are hydraulically
transmitted to a bellows which actuates a snap-acting switch at a
predetermined set point.
MAXIMUM TEMPERATURE IS THE HIGHEST TEMPERATURE TO
WHICH A SENSING ELEMENT MAY BE OCCASIONALLY EXPOSED TO
WITHOUT ADVERSELY AFFECTING SET POINT CALIBRATION AND
REPEATABILITY. MAXIMUM TEMPERATURE LIMITS STATED IN LITERATURE
AND ON NAMEPLATE MUST NEVER BE EXCEEDED, EVEN BY TEMPERATURE
OVERSHOOTS IN THE SYSTEM. OCCASIONAL OPERATION OF UNIT UP
TO MAX. TEMPERATURE IS ACCEPTABLE (E.G., START-UP, TESTING).
CONTINUOUS OPERATION SHOULD BE RESTRICTED TO THE DESIGNATED
ADJUSTABLE RANGE.
Please refer to product bulletin for product specifications. Product
bulletins may be found at www.ueonline.com.
Tools Needed
Adjustable wrench
Flathead screwdriver
Hammer (for alternate wire knockouts)
MOUNTING
INSTALL UNIT WHERE SHOCK, VIBRATION AND TEMPERATURE
FLUCTUATIONS ARE MINIMAL. DO NOT MOUNT UNIT IN AMBIENT
TEMPERATURES EXCEEDING PUBLISHED LIMITS. 100 SERIES
TEMPERATURE SWITCHES CAN BE MOUNTED IN ANY POSITION, PROVIDED
THE ELECTRICAL CONDUIT IS NOT FACING UP. ORIENT UNIT SO THAT
MOISTURE IS PREVENTED FROM ENTERING THE ENCLOSURE.
For remote mounting, mount the unit via the (2) 1/4 screw clearance holes
on the enclosure (See Dimensions on back page.) Fully immerse the bulb
and 6 capillary in the control zone. It is generally desirable to place the
bulb close to the heating or cooling source in order to sense temperature
fluctuations quickly. Be sure to locate the bulb so that it will not be exposed
to temperatures beyond the instrument range limits.
FOR LOCAL MOUNTING, ALWAYS HOLD A WRENCH ON THE
TEMPERATURE HOUSING HEX WHEN MOUNTING UNIT. DO NOT
TIGHTEN BY TURNING ENCLOSURE. THIS WILL DAMAGE SENSOR
AND WEAKEN SOLDERED OR WELDED JOINTS.
WIRING
DISCONNECT ALL SUPPLY CIRCUITS BEFORE WIRING UNIT.
ELECTRICAL RATINGS STATED IN LITERATURE AND ON NAMEPLATE
MUST NOT BE EXCEEDED. OVERLOAD ON A SWITCH CAN CAUSE
FAILURE ON THE FIRST CYCLE. WIRE UNITS ACCORDING TO NATIONAL AND
LOCAL ELECTRICAL CODES. MAXIMUM RECOMMENDED WIRE SIZE IS 14 AWG.
UNITED ELECTRIC
CONTROLS
Installation and Maintenance
Instructions
IMT100-04
100 Series
Temperature Switch

Types B100, C100, E100, F100
Please read all instructional literature carefully and thoroughly before starting. Refer to the final page for the listing of Recommended
Practices, Liabilities and Warrantees.
Part I - Installation
Remove the two screws retaining the cover and cover gasket. A 1/2 NPT
conduit connection is located on the left side of the enclosure. Two cast-in
7/8 diameter knockouts for electrical conduit are located on the side and
rear of enclosure. These can easily be knocked out by placing the blade
of a screwdriver in the groove and tapping sharply with a hammer.
Connect conduit to the enclosure and wire directly to the switch terminals
according to local and national electrical codes. Bring the wires up to
terminals from the rear of the enclosure allowing enough slack so as not
to affect switch movement when making setting adjustments. The three
switch terminals are clearly labeled common, norm open, and norm
closed. If lead wires are supplied, color coding is as follows:
SPDT
Common (COM) Violet
Normally Open (NO) Blue
Normally Closed (NC) Black
A grounding screw and clamp (cast in symbol) is provided which meets a
35 lb. pull test. Keep the wire as short as possible to prevent interference
with the plunger and, when provided, the adjustable deadband switch
wheel (option1519).
Tools Needed
3/16 open end wrench
NOTE: For set point adjustments and recalibration, immerse sensor
(immersion stem or bulb and 6" of capillary) in a calibrated temperature
source and stabilize unit.
Types C100 and F100
Remove cover. Switch has a hex adjustment screw inside enclosure (See
Figure 1). If switch transfer point differs from actual temperature, adjust
setting. To raise the temperature setting, turn the hex towards the left
(clockwise). To lower the temperature setting, turn the screw towards the
right (counter-clockwise). When making adjustments, do not exceed the
maximum temperature rating on nameplate.
Types B100 and E100 (with reference dial)
Controls are factory calibrated for maximum accuracy at the midpoint of
the scale.
To re-calibrate, turn dial to desired set point(See Figure 2). If the actual
temperature and set point temperature do not agree, turn hex adjustment
screw towards the left (clockwise) to raise and towards the right (counter-
clockwise) to lower temperature setting.
Part II - Adjustments
IMT100-04
CP12082500
Dimension A
Models Inches mm
120,121 9.38 238,2 Immersion stem
1B-8B 8.75 222,23 Bulb & capillary
Models 120-121
Models 1BC-8BC, 1BS-8BS
UNI TED ELECTRI C
CONTROLS
P.O. Box 9143, Watertown, MA 02471-9143 USA
617 926-1000 Fax 617 926-2568
http://www.ueonline.com
IMT100-04
COM. N.C. N.O.
HEX ADJUSTMENT
SCREW
COM. N.C. N.O.
DIAL
HEX ADJUSTMENT
SCREW
Types B100, C100, E100, F100
Dimensions
Dimensional drawings for all models may be found at www.ueonline.com.
C100, F100
B100, E100
4
2 4" WITH COVER
11
32
(59.4mm)
7
32
(107.2mm)
1
5
8
(41.4mm)
(101.6mm)
1/2 NPT
.895 (22.7mm) DIA.
KNOCK-OUT 2 PLACES
CLEARANCE FOR
1/4 (6.35mm) SCREW
2 MT'G. HOLES.
(69.9mm)
4
3
2
CONDUIT.
A
KNOCK
OUT
Figure 1
Figure 2
RECOMMENDED PRACTICES AND WARNINGS
United Electric Controls Company recommends careful consideration
of the following factors when specifying and installing UE pressure
and temperature units. Before installing a unit, the Installation
and Maintenance instructions provided with unit must be read and
understood.
To avoid damaging unit, proof pressure and maximum temperature
limits stated in literature and on nameplates must never be
exceeded, even by surges in the system. Operation of the unit up to
maximum pressure or temperature is acceptable on a limited basis
(e.g., start-up, testing) but continuous operation must be restricted
to the designated adjustable range. Excessive cycling at maximum
pressure or temperature limits could reduce sensor life.
A back-up unit is necessary for applications where damage to
a primary unit could endanger life, limb or property. A high or
low limit switch is necessary for applications where a dangerous
runaway condition could result.
The adjustable range must be selected so that incorrect,
inadvertent or malicious setting at any range point cannot result
in an unsafe system condition.
Install unit where shock, vibration and ambient temperature
fluctuations will not damage unit or affect operation. When
applicable, orient unit so that moisture does not enter the
enclosure via the electrical connection. When appropriate, this
entry point should be sealed to prevent moisture entry.
Unit must not be altered or modified after shipment. Consult UE
if modification is necessary.
Monitor operation to observe warning signs of possible damage
to unit, such as drift in set point or faulty display. Check unit
immediately.
Preventative maintenance and periodic testing is necessary for
critical applications where damage could endanger property or
personnel.
Electrical ratings stated in literature and on nameplate must
not be exceeded. Overload on a switch can cause damage, even
on the first cycle. Wire unit according to local and national
electrical codes, using wire size recommended in installation
sheet.
Do not mount unit in ambient temp. exceeding published limits.
LIMITED WARRANTY
Seller warrants that the product hereby purchased is, upon delivery,
free from defects in material and workmanship and that any such
product which is found to be defective in such workmanship or
material will be repaired or replaced by Seller (Ex-works, Factory,
Watertown, Massachusetts. INCOTERMS); provided, however, that this
warranty applies only to equipment found to be so defective within
a period of 36 months from the date of manufacture by the Seller.
Seller shall not be obligated under this warranty for alleged defects
which examination discloses are due to tampering, misuse, neglect,
improper storage, and in any case where products are disassembled
by anyone other than authorized Sellers representatives. EXCEPT FOR
THE LIMITED WARRANTY OF REPAIR AND REPLACEMENT STATED
ABOVE, SELLER DISCLAIMS ALL WARRANTIES WHATSOEVER WITH
RESPECT TO THE PRODUCT, INCLUDING ALL IMPLIED WARRANTIES
OF MERCHANTABILITY OR FITNESS FOR ANY PARTICULAR PURPOSE.
LIMITATION OF SELLERS LIABILITY
SELLERS LIABILITY TO BUYER FOR ANY LOSS OR CLAIM, INCLUDING
LIABILITY INCURRED IN CONNECTION WITH (I) BREACH OF ANY
WARRANTY WHATSOEVER, EXPRESSED OR IMPLIED, (II) A BREACH OF
CONTRACT, (III) A NEGLIGENT ACT OR ACTS (OR NEGLIGENT FAILURE
TO ACT) COMMITTED BY SELLER, OR (IV) AN ACT FOR WHICH
STRICT LIABILITY WILL BE INPUTTED TO SELLER, IS LIMITED TO THE
LIMITED WARRANTY OF REPAIR AND/OR REPLACEMENT AS SO
STATED IN OUR WARRANTY OF PRODUCT. IN NO EVENT SHALL THE
SELLER BE LIABLE FOR ANY SPECIAL, INDIRECT, CONSEqUENTIAL
OR OTHER DAMAGES OF A LIkE GENERAL NATURE, INCLUDING,
WITHOUT LIMITATION, LOSS OF PROFITS OR PRODUCTION, OR LOSS
OR EXPENSES OF ANY NATURE INCURRED BY THE BUYER OR ANY
THIRD PARTY.
UE specifications subject to change without notice.
IMJ21K-05
www.ueonline.com
Type J21K
Differential Pressure Switch
UNI TED ELECTRI C
CONTROLS
Installation and Maintenance
Instructions
IMJ21K-05
WIRING
DISCONNECT ALL SUPPLY CIRCUITS BEFORE WIRING UNIT. WIRE
UNITS ACCORDING TO NATIONAL AND LOCAL ELECTRICAL CODES.
MAXIMUM RECOMMENDED WIRE SIZE IS 14 AWG.
ELECTRICAL RATINGS STATED IN LITERATURE AND ON NAMEPLATES
MUST NOT BE EXCEEDED, OVERLOAD ON A SWITCH CAN CAUSE
FAILURE ON THE FIRST CYCLE.
Remove the four (4) screws retaining the cover and gasket. Remove cover.
Connect conduit to the enclosure using a conduit fitting that is suitable for your
installation. A watertight conduit fitting (option M900 or equivalent) must be
used for NEMA 4 protection. Wire directly to the switch terminals in accordance
with local and national electrical codes. Bring the wires up to the terminals
from the rear of the enclosure to prevent interference with the mechanism.
Part II - Adjustments
Tools Needed
- 5/16" open end wrench
For set point adjustment and re-calibration, connect the "High" pressure port
to a calibrated pressure source.
Set point adjustment is achieved by varying the gap between the mechanical
actuator and the plunger on the electrical switch
To raise the differential pressure setting, turn the 5/16" hex head screw left
(clockwise).
To lower the differential pressure setting, turn the 5/16" hex head screw right
(counter-clockwise).
Adjustable Deadband Option
J21K models with option code 1520 incorporate a snap-switch with integral
adjustment wheel. Turning this wheel raises or lowers the pressure rise
set point. The fall set point remains constant. Consult factory for additional
information.
GENERAL
BEFORE INSTALLING, CHECK THE SENSOR MODEL SELECTED FOR
COMPATIBILITY TO THE PROCESS MEDIA IN CONTACT WITH THE
SENSOR AND WETTED PARTS.
The J21K Differential Pressure Switch utilizes opposing metal bellows to detect
pressure differences between two pressure sources. When the pressure at the
high port exceeds the pressure at the low port by a pre-determined amount
(set point), the mechanism operates a single snap-action electrical switch.
Control set point may be adjusted by turning the internal adjustment hex screw
(see Part II - Adjustments).
DIFFERENTIAL PROOF PRESSURE* LIMITS STATED IN THE LITERA
TURE AND ON NAMEPLATE MUST NEVER BE EXCEEDED, EVEN BY
SURGES IN THE SYSTEM. OCCASIONAL OPERATION OF UNIT UP TO
DIFFERENTIAL PROOF PRESSURE IS ACCEPTABLE (E.G., START-UP,
TESTING). CONTINUOUS OPERATION SHOULD NOT EXCEED THE
DESIGNATED MAX WORKING PRESSURE.
*Differential Proof Pressure
The maximum differential pressure to which a pressure sensor may be
occasionally subjected, which causes no permanent damage (e.g., start-up,
testing). The unit may require calibration.
THESE PRODUCTS DO NOT HAVE ANY FIELD REPLACEABLE PARTS.
Please refer to product bulletin for product specifications. Product bulletin
may be found at www.ueonline.com.
Part I - Installation
Tools Needed
- Adjustable wrenches (2)
- Flat blade screwdriver
MOUNTING
INSTALL UNIT WHERE SHOCK, VIBRATION AND TEMPERATURE
FLUCTUATIONS ARE MINIMAL. MOUNT UNIT SO THAT MOISTURE
IS PREVENTED FROM ENTERING THE ENCLOSURE. DO NOT MOUNT
UNIT IN AMBIENT TEMPERATURES EXCEEDING PUBLISHED LIMITS.
Surface mount in any position via two mounting ears. Never turn this unit by
grasping enclosure. Always hold a wrench on the bellows housing (or fitting)
when connecting pressure joints.
Please read all instructional literature carefully and thoroughly before starting. Refer to the final page for the listing of Recommended
Practices, Liabilities and Warranties.
IMJ21K-05
www.ueonline.com
SP09085K
Dimensions
Dimensional drawings for all models may be found at www.UEonline.com
Dimension A
Models Inches mm NPT
127-150 8.06 204.7 1/4
S127B 8.94 227.1 1/2
S140B-S150B 8.86 225.0 1/2
232 6.53 165.9 1/4
254 6.50 165.1 1/4
357 6.88 174.8 1/4
Models 127-150 Models S127B-S150B
Model 232 Model 254
Model 357
UNI T E D E L E CT R I C
CONT R OL S
180 Dexter Avenue, P.O. Box 9143
Watertown, MA 02471-9143 USA
Telephone: 617 926-1000 Fax: 617 926-2568
http://www.ueonline.com
RECOMMENDED PRACTICES AND WARNINGS
United Electric Controls Company recommends careful consideration of the
following factors when specifying and installing UE pressure and temperature units.
Before installing a unit, the Installation and Maintenance instructions provided
with unit must be read and understood.
To avoid damaging unit, proof pressure and maximum temperature limits stated
in literature and on nameplates must never be exceeded, even by surges in the
system. Operation of the unit up to maximum temperature is acceptable on a
limited basis (i.e., start-up, testing) but continuous operation must be restricted to
the designated adjustable range. Excessive cycling at maximum temperature limits
could reduce sensor life.
A back-up unit is necessary for applications where damage to a primary unit
could endanger life, limb or property. A high or low limit switch is necessary for
applications where a dangerous runaway condition could result.
The adjustable range must be selected so that incorrect, inadvertent or
malicious setting at any range point cannot result in an unsafe system condition.
Install unit where shock, vibration and ambient temperature fluctuations will
not damage unit or affect operation. Mount the unit so that moisture does not
enter the enclosure via the electrical connection. When appropriate, this entry
point should be sealed to prevent moisture entry.
Unit must not be altered or modified after shipment. Consult UE if
modification is necessary.
Monitor operation to observe warning signs of possible damage to unit, such
as drift in set point or faulty display. Check unit immediately.
Preventative maintenance and periodic testing is necessary for critical
applications where damage could endanger property or personnel.
For all applications, a factory set unit should be tested before use.
Electrical ratings stated in literature and on nameplate must not be exceeded.
Overload on a switch can cause damage, even on the first cycle. Wire unit
according to local and national electrical codes, using wire size recommended in
installation sheet.
Do not mount unit in ambient temp. exceeding published limits.
LIMITED WARRANTY
Seller warrants that the product hereby purchased is, upon delivery, free from
defects in material and workmanship and that any such product which is found to
be defective in such workmanship or material will be repaired or replaced by Seller
(Ex-works, Factory, Watertown, Massachusetts. INCOTERMS); provided, however, that
this warranty applies only to equipment found to be so defective within a period of
24 months from the date of manufacture by the Seller. Seller shall not be obligated
under this warranty for alleged defects which examination discloses are due to
tampering, misuse, neglect, improper storage, and in any case where products are
disassembled by anyone other than authorized Sellers representatives. EXCEPT FOR
THE LIMITED WARRANTY OF REPAIR AND REPLACEMENT STATED ABOVE, SELLER
DISCLAIMS ALL WARRANTIES WHATSOEVER WITH RESPECT TO THE PRODUCT,
INCLUDING ALL IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR
ANY PARTICULAR PURPOSE.
LIMITATION OF SELLERS LIABILITY
Sellers liability to Buyer for any loss or claim, including liability incurred in
connection with (i) breach of any warranty whatsoever, expressed or implied,
(ii) a breach of contract, (iii) a negligent act or acts (or negligent failure to act)
committed by Seller, or (iv) an act for which strict liability will be inputted to seller,
is limited to the limited warranty of repair and/or replacement as so stated
in our warranty of product. In no event shall the Seller be liable for any special,
indirect, consequential or other damages of a like general nature, including, without
limitation, loss of profits or production, or loss or expenses of any nature incurred by
the buyer or any third party.
UE specifications subject to change without notice.
316 STAINLESS STEEL - TEFLON - VITON - WETTED SURFACES
For Use in Mildly Corrosive Chemicals
Generally accepted for use with 316 Stainless Steel
For instance, mildly corrosive uids such as:
Plus
Special Features
Fluid Flow Switch Model Q-5SS
10 to 102,000+ GPM
for pipes 1-48+

Aluminum
Sulfate

Crude Oil

Diluted Sulfuric
Acid

Ethyl Chloride

Hydrochloric
Acid

Lactic Acid

Magnesium
Hydroxide

Nickel Sulfate

Nitric Acid

Phenol

Potassium
Dichromate

Zinc Sulfate

Alcohols

Filtered Sewage Water

Gasoline

Glycols

Oils

Pure Water

Soap Solutions

Tap Water
541 Kinetic Drive, Oxnard, CA 93030
Tel (805) 988-6800 Fax (805) 988-6804
Email. harwil@harwil.com
www.harwil.com

Wetted surfaces of 316 stainless


steel, Teon and Viton

Responds to ow only,
independent of pressure and
temperature

Continuously adjustable while


operating

Mount in any position

Line pressure to 300 psig

Temperature to 180F continuous

No damage or calibration change


when subjected to reasonable
hydraulic hammer or surge pulses

Maintenance and checkout is a


snap for your present personnel
using an uncomplicated standard
test meter

Extensive Chemical Corrosive


List On Page 50
Limited Warranty
MOUNT IN
ANY POSITION
TURBULENT FLOW
REDUCTION
Reliable,
Inexpensive
Q - 5SS / 3 / 2 / B
Basic Model #
Drag Disk Size
Model Q-5SS
Model Selection Chart
Pipe
Size
NPT
Flow Limits
Between Which
Switch Point May
Be Set GPM
Part Number Part Number Part Number Part Number
Pipe
Size
NPT
Flow Limits
Between Which
Switch Point May
Be Set GPM
Model
Pivot
Shaft No.
Target
No.
Electric
Cable 1 or 2
1
10-20 Q-5SS 2 2 ---
1
20-60 Q-5SS 2 1 ---
1 1/2
14-42 Q-5SS 3 3 ---
1 1/2 20-60 Q-5SS 3 2 --- 1 1/2
30-90 Q-5SS 3 1 ---
2
21-63 Q-5SS 3 4 ---
2 30-90 Q-5SS 3 2 --- 2
60-180 Q-5SS 3 1 ---
2 1/2
36-108 Q-5SS 3 4 ---
2 1/2 90-150 Q-5SS 3 2 --- 2 1/2
90-270 Q-5SS 3 1 ---
3
45-135 Q-5SS 5 4 ---
3 75-225 Q-5SS 5 2 --- 3
130-390 Q-5SS 5 1 ---
3 1/2
56-168 Q-5SS 5 4 ---
3 1/2 85-285 Q-5SS 5 2 --- 3 1/2
180-540 Q-5SS 5 1 ---
4
77-231 Q-5SS 5 4 ---
4 130-390 Q-5SS 5 2 --- 4
235-705 Q-5SS 5 1 ---
5
84-252 Q-5SS 5 5 ---
5 200-600 Q-5SS 5 2 --- 5
350-1050 Q-5SS 5 1 ---
6
103-309 Q-5SS 5 6 ---
6
125-375 Q-5SS 5 5 ---
6
300-900 Q-5SS 5 2 ---
6
550-1650 Q-5SS 5 1 ---
8
189-567 Q-5SS 5 6 ---
8
232-696 Q-5SS 5 5 ---
8
550-1650 Q-5SS 5 2 ---
8
950-2850 Q-5SS 5 1 ---
10
292-876 Q-5SS 5 6 ---
10
358-1074 Q-5SS 5 5 ---
10
850-2550 Q-5SS 5 2 ---
10
1450-4350 Q-5SS 5 1 ---
LARGE PIPE SIZE INFORMATION AVAILABLE BY REQUEST. LARGE PIPE SIZE INFORMATION AVAILABLE BY REQUEST. LARGE PIPE SIZE INFORMATION AVAILABLE BY REQUEST. LARGE PIPE SIZE INFORMATION AVAILABLE BY REQUEST. LARGE PIPE SIZE INFORMATION AVAILABLE BY REQUEST. LARGE PIPE SIZE INFORMATION AVAILABLE BY REQUEST.
Hysteresis (% Flow Change
to Activate / Deactivate
Switch)
" 10% at upper end of ow
range
" 30% at lower end of ow
range
Differential Pressure Drops
Across Unit (Normal
Operating Conditions)
1" - 3" Pipe, less than 1 psi
4" - 48" Pipe, Negligible
Working Line Pressure
300 psig max. @ 180F Max
(Proof tested to 1200 psig @
room temperature)
Materials
316 Stainless steel body, Noryl
cover, 316 stainless steel
hardware.
Working uid sees 316
stainless, Teon gasket and
Viton elastomer seal.
Electrical Switch
Characteristics
SPDT, 15 amp, 1/2 hp @ 125 or
250 VAC,
1/2 amp @ 125 VDC, 1/4 amp @
250 VDC,
5 amp @ 125 VAC (tungsten
lamp load)
UL and CSA Listed
10,000,000 Operations Median
Model Q-5SS can also be
tted with a SPDT Gold
Cross Bar Switch for
computer/PLC interface.
Weight: 3.5 lb.
Target (Drag Disk/Strip) Number
Installation drawing and a
numbered parts list is
supplied with each unit.
Current Price Information is
Listed on Separate Sheet.
Special One Day Delivery
Available.
Input Power Cable Interface Options
O.D.
1/2 STRAIGHT F
1/2 90
F90
Grommet Size
pg. 9
Option No. 1
Basic Model #
Sample Part #
Drag Disk Size
Drag Disk Feedthru
Shaft Length
# Flexible Conduit
Fitting
Option No. 2
Sample Part #
Drag Disk Feedthru
Shaft Length
Q - 5SS / 3 / 2 / F
See grommet size chart on
page 9.
PLAN VIEW
1" NPT
4 3/16
SIDE VIEW
1 5/8
OPTION
1 OR 2
Q-5/3 = 1 1/4
Q-5/5 = 3 1/4
Q-5/7 = 5 1/4
2 1/16
FRONT VIEW
2 7/16
3 15/16
1 5/32
Installation Dimensions