Sie sind auf Seite 1von 9

Electric al Cable Sizing

******** ***************

Name   :  H Dobson
Company:  ANZ Associates
Ref.   :  Example 11.1
Date   : 26­Mar­08 
Time   : 12:00:00 AM 
File   :  A:CABLE.WKS

Notes.
­­­­­
This wor ksheet allows the el ectrical d esign engi neer to
calculat e the capacity of ca ble sizes for differ ent
voltages , lengths and applic ations.
Enter th e load power, power factor and  cable len gth
for cabl e number one; copy t he data do wnwards to  the
other ca ble numbers. Select the correc t cable si ze.
Enter ne w data under column headings =========.
Calculat ed data is under hea dings *********.
Electric al Power Load ­ Data  Entry
******** ******************** ******

Input Data
==========

Power Lo ad              W : 7500  Watts

Power Fa ctor           PF : 0.75  dimensionl ess

Conducto r length      L1  : 60.000  m

Voltage                 V : 415  volts

Installa tion description  : grouped ca bles, clip ped direct

Three Ph ase 415 Volt, AC Cir cuits


******** ******************** *****
3 phase AC 415  volt
Maximum allowable voltage drop 4.0  %
Maximum allowable voltage drop 16.6  volt
Installa tion description  : grouped ca bles, clip ped direct 0 
­­­­­­­­ ­­­­­­­­­­­­­­­­­­­­ ­­­­­­­­­­ ­­­­­­­­­­ ­­­­­­­­­­­­­­­ ­­­­­­­­­­­­
Cable Conductor Maximum Voltage Load Load
No. Cross­sectional Current Drop Power Power
Area Rating Factor
mm2 Ampere mV/A m Watts PF
======= =================== ========= ========= ************** ***********
1  1.0  16.0  37.00  7500  0.75 
2  1.5  20.0  24.00  7500  0.75 
3  2.5  26.0  15.00  7500  0.75 
4  4.0  36.0  9.20  7500  0.75 
5  6.0  45.0  6.20  7500  0.75 
6  10.0  61.0  3.70  7500  0.75 
7  16.0  81.0  2.30  7500  0.75 
8  25.0  106.0  1.50  7500  0.75 
Three Ph ase 415 Volt, AC Cir cuits, con tinued.
­­­­­­­­ ­­­­­­­­­­­­­­­­­­­­ ­­­­­­­­­­ ­­­­­­­­­­ ­­­­­­­­­­­­­­­ ­­­­­­­­­­­­
Cable Conductor Maximum Voltage Load Load
No. Cross­sectional Current Drop Power Power
Area Rating Factor
mm2 Ampere mV/A m Watts PF
======= ******************* ********* ********* ************** ***********
9  35.0  130.0  1.10  7500  0.75 
10  50.0  160.0  0.82  7500  0.75 
11  70.0  200.0  0.59  7500  0.75 
12  95.0  240.0  0.45  7500  0.75 
13  120.0  280.0  0.38  7500  0.75 
14  150.0  320.0  0.34  7500  0.75 
15  185.0  365.0  0.30  7500  0.75 
16  240.0  430.0  0.27  7500  0.75 
17  300.0  500.0  0.25  7500  0.75 
18  400.0  610.0  0.24  7500  0.75 
19  500.0  710.0  0.23  7500  0.75 
20  630.0  820.0  0.22  7500  0.75 

Single Phhase 240 Volt, AC Ci rcuits
******** ******************** ******
1 phase AC 240  volt
Maximum allowable voltage drop 4.0  %
Maximum allowable voltage drop 9.6  volt
Installa tion description  : grouped ca bles, clip ped direct 0 
­­­­­­­­ ­­­­­­­­­­­­­­­­­­­­ ­­­­­­­­­­ ­­­­­­­­­­ ­­­­­­­­­­­­­­­ ­­­­­­­­­­­­
Cable Conductor Maximum Voltage Load Load
No. Cross­sectional Current Drop Power Power
Area Rating Factor
mm2 Ampere mV/A m Watts PF
======= ******************* ********* ********* ************** ***********
1  1.0  17.0  42.00  7500  0.75 
2  1.5  21.0  28.00  7500  0.75 
3  2.5  30.0  17.00  7500  0.75 
4  4.0  40.0  11.00  7500  0.75 
5  6.0  50.0  7.10  7500  0.75 
6  10.0  68.0  4.20  7500  0.75 
7  16.0  90.0  2.70  7500  0.75 
8  25.0  118.0  1.70  7500  0.75 
Single Phhase 12 Volt, Extra Low Voltag e Circuits
******** ******************** ********** **********
1 phase AC 12  volt
Maximum allowable voltage drop 4.0  %
Maximum allowable voltage drop 0.5  volt
Installa tion description  : grouped ca bles, clip ped direct 0 
­­­­­­­­ ­­­­­­­­­­­­­­­­­­­­ ­­­­­­­­­­ ­­­­­­­­­­ ­­­­­­­­­­­­­­­ ­­­­­­­­­­­­
Cable Conductor Maximum Voltage Load Load
No. Cross­sectional Current Drop Power Power
Area Rating Factor
mm2 Ampere mV/A m Watts PF
======= ******************* ********* ********* ************** ***********
1  1.0  17.0  42.00  7500  0.75 
2  1.5  21.0  28.00  7500  0.75 
3  2.5  30.0  17.00  7500  0.75 
4  4.0  40.0  11.00  7500  0.75 
5  6.0  50.0  7.10  7500  0.75 

END OF F ILE.
0.0 
­­­­­­­­­­ ­­­­­­­­­­ ­­­­­­­­­­ ­­­­­­­­­­­­ ­­­­­­­­­­­­ ­­­­­­­­­­­­­­­
Phase Maximum  Measured Voltage Percentage Voltage 
Current Conductor Conductor Drop Voltage Drop
Length Length Drop Acceptability
I(b) A L1 m L2 m V volt %
********* ********* ********* *********** *********** **************
13.9  32.2  60.0  30.9  7.4  Too high
13.9  49.7  60.0  20.0  4.8  Too high
13.9  79.5  60.0  12.5  3.0  Allowed
13.9  129.7  60.0  7.7  1.9  Allowed
13.9  192.5  60.0  5.2  1.2  Allowed
13.9  322.5  60.0  3.1  0.7  Allowed
13.9  518.8  60.0  1.9  0.5  Allowed
13.9  795.5  60.0  1.3  0.3  Allowed

­­­­­­­­­­ ­­­­­­­­­­ ­­­­­­­­­­ ­­­­­­­­­­­­ ­­­­­­­­­­­­ ­­­­­­­­­­­­­­­


Phase Maximum  Measured Voltage Percentage Acceptability
Current Conductor Conductor Drop Voltage
Length Length Drop
I(b) A L1 m L2 m V volt %
********* ********* ********* *********** *********** **************
13.9  1084.7  60.0  0.9  0.2  Allowed
13.9  1455.1  60.0  0.7  0.2  Allowed
13.9  2022.4  60.0  0.5  0.1  Allowed
13.9  2651.6  60.0  0.4  0.1  Allowed
13.9  3140.0  60.0  0.3  0.1  Allowed
13.9  3509.4  60.0  0.3  0.1  Allowed
13.9  3977.4  60.0  0.3  0.1  Allowed
13.9  4419.3  60.0  0.2  0.1  Allowed
13.9  4772.8  60.0  0.2  0.1  Allowed
13.9  4971.7  60.0  0.2  0.0  Allowed
13.9  5187.9  60.0  0.2  0.0  Allowed
13.9  5423.7  60.0  0.2  0.0  Allowed

0.0 
­­­­­­­­­­ ­­­­­­­­­­ ­­­­­­­­­­ ­­­­­­­­­­­­ ­­­­­­­­­­­­ ­­­­­­­­­­­­­­­
Phase Maximum  Measured Voltage Percentage Acceptability
Current Conductor Conductor Drop Voltage
Length Length Drop
I(b) A L1 m L2 m V volt %
********* ********* ********* *********** *********** **************
41.7  5.5  60.0  105.0  43.8  Too high
41.7  8.2  60.0  70.0  29.2  Too high
41.7  13.6  60.0  42.5  17.7  Too high
41.7  20.9  60.0  27.5  11.5  Too high
41.7  32.5  60.0  17.8  7.4  Too high
41.7  54.9  60.0  10.5  4.4  Too high
41.7  85.3  60.0  6.8  2.8  Allowed
41.7  135.5  60.0  4.3  1.8  Allowed
0.0 
­­­­­­­­­­ ­­­­­­­­­­ ­­­­­­­­­­ ­­­­­­­­­­­­ ­­­­­­­­­­­­ ­­­­­­­­­­­­­­­
Phase Maximum  Measured Voltage Percentage Acceptability
Current Conductor Conductor Drop Voltage
Length Length Drop
I(b) A L1 m L2 m V volt %
********* ********* ********* *********** *********** **************
833.3  0.0  60.0  2100.0  17500.0  Too high
833.3  0.0  60.0  1400.0  11666.7  Too high
833.3  0.0  60.0  850.0  7083.3  Too high
833.3  0.1  60.0  550.0  4583.3  Too high
833.3  0.1  60.0  355.0  2958.3  Too high
­­­­­­­­­­­­­
Current
Limit
Acceptability

**************
Allowed
Allowed
Allowed
Allowed
Allowed
Allowed
Allowed
Allowed

­­­­­­­­­­­­­
Current
Limit
Acceptability

**************
Allowed
Allowed
Allowed
Allowed
Allowed
Allowed
Allowed
Allowed
Allowed
Allowed
Allowed
Allowed

­­­­­­­­­­­­­
Current
Limit
Acceptability

**************
Too high
Too high
Too high
Too high
Allowed
Allowed
Allowed
Allowed
­­­­­­­­­­­­­
Current
Limit
Acceptability

**************
Too high
Too high
Too high
Too high
Too high

Das könnte Ihnen auch gefallen