CONFIGURATIONREC670(C30)

VERSION1.2,1&1/2BREAKER
Description WorkSheet
OVERVIEW Listofcontent
AI Alanogueinputs
BI_T01 BinaryInputforT01
Disturbancereportbinaryinputs DREP_BI
DisturbancereportScada DREP_SAS
COMMON_BI CommonBinaryInput
TAP_LOGIC_TR_T01 TappositionlogicforT01
TAP_LOGIC_TR_T02 TappositionlogicforT02
TAP_LOGIC_TR_T03 TappositionlogicforT03
TAP_LOGIC_TR_T01-T02 TappositionlogicforT01andT02
TAP_LOGIC_TR_T02-T03 TappositionlogicforT02andT03
TAP_LOGIC_TR_T03-T01 TappositionlogicforT03andT01
COMMON_INTERLOCK Commoninterlockfortransformers
TRANSFER_LOGIC TransferLogicforalltransformer
SYNCH Syncronizinglogicforbus-1andbus-2
BOM Binaryoutput
DREP_AI Disturbancereportforanalogueinput
BI_T02 BinaryInputforT02
BI_T03 BinaryInputforT03
COMMON CommonInput
A A
B B
C C
D D
E E
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
Main Application: OVERVIEW, Page: 1
Rev. Modification Rel. date Created by
Replacing
Based on
Project
UMLUJJ 380_33_13.8KV PROTECTION
Responsible department
ABB Ltd.
UMLUJJ 380_33_13.8KV
PROTECTION.Substation.13.8KV.ABTS
Technical reference Document kind
Graphical Application Configuration
Doc. designation
AA1J4Q03A1
Created by Title
REC670-ABTS
Document id.
Approved by Rev.
0
Rel. date
13/08/2014
Lang.
en
1 / 52
SMAI1
BUS-A_VT
O:1|T:3|I:1
BLOCK
DFTSPFC
BUS-A_UR
GRP1L1
BUS-A_UY
GRP1L2
BUS-A_UB
GRP1L3
Not used
GRP1N
SPFCOUT
AI3P
AI1
AI2
AI3
AI4
AIN
SMAI2
BUS-B_VT
O:1|T:3|I:2
BLOCK
BUS-B_UR
GRP2L1
BUS-B_UY
GRP2L2
BUS-B_UB
GRP2L3
Not used
GRP2N
AI3P
AI1
AI2
AI3
AI4
AIN
SMAI3
BUS-C_VT
O:1|T:3|I:3
BLOCK
Not used
GRP3L1
Not used
GRP3L2
Not used
GRP3L3
Not used
GRP3N
AI3P
AI1
AI2
AI3
AI4
AIN
SMAI4
BUS-A_VT_REF
O:1|T:3|I:4
BLOCK
BUS-A_UR_REF
GRP4L1
BUS-A_UY_REF
GRP4L2
BUS-A_UB_REF
GRP4L3
Not used
GRP4N
AI3P
AI1
AI2
AI3
AI4
AIN
SMAI1
BUS-AVT PROT
O:1|T:8|I:13
BLOCK
DFTSPFC
Not used
GRP1L1
Not used
GRP1L2
Not used
GRP1L3
Not used
GRP1N
SPFCOUT
AI3P
AI1
AI2
AI3
AI4
AIN
SMAI2
BUS-B VT PROT
O:1|T:8|I:14
BLOCK
Not used
GRP2L1
Not used
GRP2L2
Not used
GRP2L3
Not used
GRP2N
AI3P
AI1
AI2
AI3
AI4
AIN
SMAI3
BUS-C VT PROT
O:1|T:8|I:15
BLOCK
Not used
GRP3L1
Not used
GRP3L2
Not used
GRP3L3
Not used
GRP3N
AI3P
AI1
AI2
AI3
AI4
AIN
FALSE
BUS-A_U3P
BUS-A_UR
BUS-A_UY
BUS-A_UB
FALSE
BUS-B_U3P
BUS-B_UR
BUS-B_UY
BUS-B_UB
FALSE
BUS-C_U3P
BUS-C_UR
BUS-C_UY
BUS-C_UB
FALSE
BUS-A_U3P_REF
BUS-A_UR_REF
BUS-A_UY_REF
BUS-A_UB_REF
REAL_ZERO
REAL_ZERO
FALSE
FALSE
BUS-B_UL3
TRM_6I_6U_31.CH12
BUS-B_UL1
TRM_6I_6U_31.CH10
BUS-A_UL2
TRM_6I_6U_31.CH8
BUS-B_UL2
TRM_6I_6U_31.CH11
BUS-A_UL1
TRM_6I_6U_31.CH7
BUS-C_UL3
TRM_6I_6U_32.CH9
BUS-C_UL2
TRM_6I_6U_32.CH8
BUS-C_UL1
TRM_6I_6U_32.CH7
BUS-A_UL3
TRM_6I_6U_31.CH9
BUS-A_UL1
TRM_6I_6U_31.CH7
BUS-A_UL2
TRM_6I_6U_31.CH8
BUS-A_UL3
TRM_6I_6U_31.CH9
BUS-B_UL1
TRM_6I_6U_31.CH10
BUS-B_UL2
TRM_6I_6U_31.CH11
BUS-B_UL3
TRM_6I_6U_31.CH12
BUS-C_UL1
TRM_6I_6U_32.CH7
BUS-C_UL2
TRM_6I_6U_32.CH8
BUS-C_UL3
TRM_6I_6U_32.CH9
BUS-A_UL2
TRM_6I_6U_31.CH8
BUS-A_UL1
TRM_6I_6U_31.CH7
BUS-A_UL3
TRM_6I_6U_31.CH9
A A
B B
C C
D D
E E
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
Main Application: ANALOGUE, Page: 1
Rev. Modification Rel. date Created by
Replacing
Based on
Project
UMLUJJ 380_33_13.8KV PROTECTION
Responsible department
ABB Ltd.
UMLUJJ 380_33_13.8KV
PROTECTION.Substation.13.8KV.ABTS
Technical reference Document kind
Graphical Application Configuration
Doc. designation
AA1J4Q03A1
Created by Title
REC670-ABTS
Document id.
Approved by Rev.
0
Rel. date
13/08/2014
Lang.
en
2 / 52
VDCPTOV
O:490|T:8|I:1
U3P1
U3P2
BLOCK
TRIP
START
ALARM
U1LOW
U2LOW
UL1DIFF
UL2DIFF
UL3DIFF
OR
O:203|T:3|I:1
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:205|T:3|I:2
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:207|T:3|I:3
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
BUS-A_FFR OPTD
VT-A_MCB TRIP
FALSE
FALSE
BUS-A_HEALTHY
BUS-B_FFR OPTD
VT-B_MCB TRIP
FALSE
FALSE
BUS-B_HEALTHY
BUS-C_FFR OPTD
VT-C_MCB TRIP
FALSE
FALSE
BUS-C_HEALTHY
BUS-A_U3P
BUS-A_U3P_REF
FALSE
VT-A_FFR OPTD
BUS-A VOLT LOW
BUS-B VOLT LOW
BUS-C VOLT LOW
A A
B B
C C
D D
E E
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
Main Application: ANALOGUE, Page: 2
Rev. Modification Rel. date Created by
Replacing
Based on
Project
UMLUJJ 380_33_13.8KV PROTECTION
Responsible department
ABB Ltd.
UMLUJJ 380_33_13.8KV
PROTECTION.Substation.13.8KV.ABTS
Technical reference Document kind
Graphical Application Configuration
Doc. designation
AA1J4Q03A1
Created by Title
REC670-ABTS
Document id.
Approved by Rev.
0
Rel. date
13/08/2014
Lang.
en
3 / 52
TIMERSET
O:1212|T:3|I:5
INPUT ON
OFF
INV
O:201|T:3|I:1
INPUT OUT
AND
O:5706|T:100|I:218
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:6108|T:100|I:235
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:6110|T:100|I:236
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
BUS-A VOLT LOW
BUS-B VOLT LOW
BUS-C VOLT LOW
BUS-B_FFR OPTD
Undervoltage_OPTD_BS-2
TRUE TRUE
TRUE
TRUE
BUS-A_FFR OPTD
Undervoltage_OPTD_BS-1
Undervoltage_OPTD_BS-3
BUS-C_FFR OPTD
TRUE
TRUE
A A
B B
C C
D D
E E
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
Main Application: ANALOGUE, Page: 3
Rev. Modification Rel. date Created by
Replacing
Based on
Project
UMLUJJ 380_33_13.8KV PROTECTION
Responsible department
ABB Ltd.
UMLUJJ 380_33_13.8KV
PROTECTION.Substation.13.8KV.ABTS
Technical reference Document kind
Graphical Application Configuration
Doc. designation
AA1J4Q03A1
Created by Title
REC670-ABTS
Document id.
Approved by Rev.
0
Rel. date
13/08/2014
Lang.
en
4 / 52
SMBI
TR01 TAPS
O:150|T:3|I:1
TR01_TAP_1
VIn1
TR01_TAP_2
VIn2
TR01_TAP_3
VIn3
TR01_TAP_4
VIn4
TR01_TAP_5
VIn5
TR01_TAP_6
VIn6
TR01_TAP_7
VIn7
TR01_TAP_8
VIn8
NOT USED
VIn9
NOT USED
VIn10
TR01_TAP_1
BI1
TR01_TAP_2
BI2
TR01_TAP_3
BI3
TR01_TAP_4
BI4
TR01_TAP_5
BI5
TR01_TAP_6
BI6
TR01_TAP_7
BI7
TR01_TAP_8
BI8
NOT USED
BI9
NOT USED
BI10
SMBI
TR01 TAPS
O:151|T:3|I:2
TR01_TAP_9
VIn1
TR01_TAP_10
VIn2
TR01_TAP_11
VIn3
TR01_TAP_12
VIn4
TR01_TAP_13
VIn5
TR01_TAP_14
VIn6
TR01_TAP_15
VIn7
TR01_TAP_16
VIn8
NOT USED
VIn9
NOT USED
VIn10
TR01_TAP_9
BI1
TR01_TAP_10
BI2
TR01_TAP_11
BI3
TR01_TAP_12
BI4
TR01_TAP_13
BI5
TR01_TAP_14
BI6
TR01_TAP_15
BI7
TR01_TAP_16
BI8
NOT USED
BI9
NOT USED
BI10
SMBI
TR01 TAPS
O:152|T:3|I:3
TR01_TAP_17
VIn1
TR01_TAP_18
VIn2
TR01_TAP_19
VIn3
TR01_TAP_20
VIn4
TR01_TAP_21
VIn5
TR01_TAP_22
VIn6
TR01_TAP_23
VIn7
TR01_TAP_24
VIn8
TR01_TAP_25
VIn9
TR01_TAP_26
VIn10
TR01_TAP_17
BI1
TR01_TAP_18
BI2
TR01_TAP_19
BI3
TR01_TAP_20
BI4
TR01_TAP_21
BI5
TR01_TAP_22
BI6
TR01_TAP_23
BI7
TR01_TAP_24
BI8
TR01_TAP_25
BI9
TR01_TAP_26
BI10
SMBI
TR01 TAPS
O:167|T:3|I:18
TR01_TAP_27
VIn1
Not used
VIn2
Not used
VIn3
RTCC1
VIn4
Not used
VIn5
Not used
VIn6
Not used
VIn7
Not used
VIn8
Not used
VIn9
Not used
VIn10
TR01_TAP_27
BI1
Not used
BI2
Not used
BI3
RTCC1
BI4
Not used
BI5
Not used
BI6
Not used
BI7
Not used
BI8
Not used
BI9
Not used
BI10
SMBI
RTCC1 STATUS
O:169|T:3|I:20
MASTER SEL.
VIn1
FOLLOWER SEL.
VIn2
INDPEN SEL.
VIn3
MANUAL SEL.
VIn4
Not used
VIn5
Not used
VIn6
Not used
VIn7
Not used
VIn8
Not used
VIn9
Not used
VIn10
MASTER SEL.
BI1
FOLLOWER SEL.
BI2
INDPEN SEL.
BI3
MANUAL SEL.
BI4
Not used
BI5
Not used
BI6
Not used
BI7
Not used
BI8
Not used
BI9
Not used
BI10
TR01_TAP_1
TR01_TAP_2
TR01_TAP_3
TR01_TAP_4
TR01_TAP_5
TR01_TAP_6
TR01_TAP_7
TR01_TAP_8
TR01_TAP_9
TR01_TAP_10
TR01_TAP_11
TR01_TAP_12
TR01_TAP_13
TR01_TAP_14
TR01_TAP_15
TR01_TAP_16
TR01_TAP_17
TR01_TAP_18
TR01_TAP_19
TR01_TAP_20
TR01_TAP_21
TR01_TAP_22
TR01_TAP_23
TR01_TAP_24
TR01_TAP_25
TR01_TAP_26
TR01_TAP_27
RTCC1_MASTER_SELECTED
RTCC1_FOLLOWER_SELECTED
RTCC1_INDEPENDENT_SELECTED
RTCC1_MANUAL_SELECTED
TR01_TAP_16
BIM_3.BI16
TR01_TAP_3
BIM_3.BI3
TR01_TAP_22
BIM_5.BI6
TR01_TAP_11
BIM_3.BI11
TR01_TAP_27
BIM_5.BI11
TR01_TAP_15
BIM_3.BI15
TR01_TAP_19
BIM_5.BI3
TR01_TAP_21
BIM_5.BI5
TR01_TAP_8
BIM_3.BI8
TR01_TAP_24
BIM_5.BI8
TR01_TAP_14
BIM_3.BI14
TR01_TAP_18
BIM_5.BI2
TR01_TAP_6
BIM_3.BI6
TR01_TAP_25
BIM_5.BI9
TR01_TAP_7
BIM_3.BI7
TR01_TAP_2
BIM_3.BI2
TR01_TAP_12
BIM_3.BI12
TR01_TAP_10
BIM_3.BI10
TR01_TAP_1
BIM_3.BI1
TR01_TAP_17
BIM_5.BI1
TR01_TAP_5
BIM_3.BI5
TR01_TAP_4
BIM_3.BI4
TR01_TAP_9
BIM_3.BI9
TR01_TAP_20
BIM_5.BI4
TR01_TAP_26
BIM_5.BI10
TR01_TAP_23
BIM_5.BI7
TR01_TAP_13
BIM_3.BI13
A A
B B
C C
D D
E E
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
Main Application: TR01_BIM, Page: 1
Rev. Modification Rel. date Created by
Replacing
Based on
Project
UMLUJJ 380_33_13.8KV PROTECTION
Responsible department
ABB Ltd.
UMLUJJ 380_33_13.8KV
PROTECTION.Substation.13.8KV.ABTS
Technical reference Document kind
Graphical Application Configuration
Doc. designation
AA1J4Q03A1
Created by Title
REC670-ABTS
Document id.
Approved by Rev.
0
Rel. date
13/08/2014
Lang.
en
5 / 52
SMBI
TR02 TAPS
O:154|T:3|I:5
TR02_TAP_8
VIn1
TR02_TAP_9
VIn2
TR02_TAP_10
VIn3
TR02_TAP_11
VIn4
TR02_TAP_12
VIn5
TR02_TAP_13
VIn6
TR02_TAP_14
VIn7
TR02_TAP_15
VIn8
NOT USED
VIn9
NOT USED
VIn10
TR02_TAP_8
BI1
TR02_TAP_9
BI2
TR02_TAP_10
BI3
TR02_TAP_11
BI4
TR02_TAP_12
BI5
TR02_TAP_13
BI6
TR02_TAP_14
BI7
TR02_TAP_15
BI8
NOT USED
BI9
NOT USED
BI10
SMBI
TR02 TAPS
O:155|T:3|I:6
TR02_TAP_16
VIn1
TR02_TAP_17
VIn2
TR02_TAP_18
VIn3
TR02_TAP_19
VIn4
TR02_TAP_20
VIn5
TR02_TAP_21
VIn6
TR02_TAP_22
VIn7
TR02_TAP_23
VIn8
TR02_TAP_24
VIn9
TR02_TAP_25
VIn10
TR02_TAP_16
BI1
TR02_TAP_17
BI2
TR02_TAP_18
BI3
TR02_TAP_19
BI4
TR02_TAP_20
BI5
TR02_TAP_21
BI6
TR02_TAP_22
BI7
TR02_TAP_23
BI8
TR02_TAP_24
BI9
TR02_TAP_25
BI10
SMBI
TR02 TAPS
O:153|T:3|I:4
Not used
VIn1
TR02_TAP_1
VIn2
TR02_TAP_2
VIn3
TR02_TAP_3
VIn4
TR02_TAP_4
VIn5
TR02_TAP_5
VIn6
TR02_TAP_6
VIn7
TR02_TAP_7
VIn8
Not used
VIn9
Not used
VIn10
Not used
BI1
TR02_TAP_1
BI2
TR02_TAP_2
BI3
TR02_TAP_3
BI4
TR02_TAP_4
BI5
TR02_TAP_5
BI6
TR02_TAP_6
BI7
TR02_TAP_7
BI8
Not used
BI9
Not used
BI10
SMBI
TR02 TAPS
O:168|T:3|I:19
TR02_TAP_26
VIn1
TR02_TAP_27
VIn2
Not used
VIn3
Not used
VIn4
Not used
VIn5
Not used
VIn6
Not used
VIn7
Not used
VIn8
Not used
VIn9
Not used
VIn10
TR02_TAP_26
BI1
TR02_TAP_27
BI2
Not used
BI3
Not used
BI4
Not used
BI5
Not used
BI6
Not used
BI7
Not used
BI8
Not used
BI9
Not used
BI10
SMBI
RTCC2 STATUS
O:170|T:3|I:21
MASTER SEL.
VIn1
FOLLOWER SEL.
VIn2
INDPEN SEL.
VIn3
MANUAL SEL.
VIn4
Not used
VIn5
Not used
VIn6
Not used
VIn7
Not used
VIn8
Not used
VIn9
Not used
VIn10
MASTER SEL.
BI1
FOLLOWER SEL.
BI2
INDPEN SEL.
BI3
MANUAL SEL.
BI4
Not used
BI5
Not used
BI6
Not used
BI7
Not used
BI8
Not used
BI9
Not used
BI10
TR02_TAP_1
TR02_TAP_2
TR02_TAP_3
TR02_TAP_4
TR02_TAP_5
TR02_TAP_6
TR02_TAP_7
TR02_TAP_8
TR02_TAP_9
TR02_TAP_10
TR02_TAP_11
TR02_TAP_12
TR02_TAP_13
TR02_TAP_14
TR02_TAP_15
TR02_TAP_16
TR02_TAP_17
TR02_TAP_18
TR02_TAP_19
TR02_TAP_20
TR02_TAP_21
TR02_TAP_22
TR02_TAP_23
TR02_TAP_24
TR02_TAP_25
TR02_TAP_26
TR02_TAP_27
RTCC2_MASTER_SELECTED
RTCC2_FOLLOWER_SELECTED
RTCC2_INDEPENDENT_SELECTED
RTCC2_MANUAL_SELECTED
TR02_TAP_4
BIM_5.BI15
TR02_TAP_3
BIM_5.BI14
TR02_TAP_2
BIM_5.BI13
TR02_TAP_5
BIM_5.BI16
TR02_TAP_7
BIM_6.BI2
TR02_TAP_10
BIM_6.BI5
TR02_TAP_6
BIM_6.BI1
TR02_TAP_1
BIM_5.BI12
TR02_TAP_11
BIM_6.BI6
TR02_TAP_8
BIM_6.BI3
TR02_TAP_9
BIM_6.BI4
TR02_TAP_15
BIM_6.BI10
TR02_TAP_12
BIM_6.BI7
TR02_TAP_20
BIM_6.BI15
TR02_TAP_17
BIM_6.BI12
TR02_TAP_16
BIM_6.BI11
TR02_TAP_13
BIM_6.BI8
TR02_TAP_18
BIM_6.BI13
TR02_TAP_14
BIM_6.BI9
TR02_TAP_19
BIM_6.BI14
TR02_TAP_26
BIM_7.BI5
TR02_TAP_21
BIM_6.BI16
TR02_TAP_23
BIM_7.BI2
TR02_TAP_22
BIM_7.BI1
TR02_TAP_24
BIM_7.BI3
TR02_TAP_27
BIM_7.BI6
TR02_TAP_25
BIM_7.BI4
A A
B B
C C
D D
E E
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
Main Application: TR02_BIM, Page: 1
Rev. Modification Rel. date Created by
Replacing
Based on
Project
UMLUJJ 380_33_13.8KV PROTECTION
Responsible department
ABB Ltd.
UMLUJJ 380_33_13.8KV
PROTECTION.Substation.13.8KV.ABTS
Technical reference Document kind
Graphical Application Configuration
Doc. designation
AA1J4Q03A1
Created by Title
REC670-ABTS
Document id.
Approved by Rev.
0
Rel. date
13/08/2014
Lang.
en
6 / 52
SMBI
TR03 TAPS
O:158|T:3|I:9
TR03_TAP_15
VIn1
TR03_TAP_16
VIn2
TR03_TAP_17
VIn3
TR03_TAP_18
VIn4
TR03_TAP_19
VIn5
TR03_TAP_20
VIn6
TR03_TAP_21
VIn7
TR03_TAP_22
VIn8
not used
VIn9
not used
VIn10
TR03_TAP_15
BI1
TR03_TAP_16
BI2
TR03_TAP_17
BI3
TR03_TAP_18
BI4
TR03_TAP_19
BI5
TR03_TAP_20
BI6
TR03_TAP_21
BI7
TR03_TAP_22
BI8
not used
BI9
not used
BI10
SMBI
TR03 TAPS
O:159|T:3|I:10
TR03_TAP_23
VIn1
TR03_TAP_24
VIn2
TR03_TAP_25
VIn3
TR03_TAP_26
VIn4
TR03_TAP_27
VIn5
Not Used
VIn6
Not Used
VIn7
Not Used
VIn8
Not Used
VIn9
Not Used
VIn10
TR03_TAP_23
BI1
TR03_TAP_24
BI2
TR03_TAP_25
BI3
TR03_TAP_26
BI4
TR03_TAP_27
BI5
Not Used
BI6
Not Used
BI7
Not Used
BI8
Not Used
BI9
Not Used
BI10
SMBI
TR03 TAPS
O:156|T:3|I:7
Not used
VIn1
Not used
VIn2
TR03_TAP_1
VIn3
TR03_TAP_2
VIn4
TR03_TAP_3
VIn5
TR03_TAP_4
VIn6
TR03_TAP_5
VIn7
TR03_TAP_6
VIn8
Not used
VIn9
Not used
VIn10
Not used
BI1
Not used
BI2
TR03_TAP_1
BI3
TR03_TAP_2
BI4
TR03_TAP_3
BI5
TR03_TAP_4
BI6
TR03_TAP_5
BI7
TR03_TAP_6
BI8
Not used
BI9
Not used
BI10
SMBI
TR03 TAPS
O:157|T:3|I:8
TR03_TAP_7
VIn1
TR03_TAP_8
VIn2
TR03_TAP_9
VIn3
TR03_TAP_10
VIn4
TR03_TAP_11
VIn5
TR03_TAP_12
VIn6
TR03_TAP_13
VIn7
TR03_TAP_14
VIn8
Not used
VIn9
Not used
VIn10
TR03_TAP_7
BI1
TR03_TAP_8
BI2
TR03_TAP_9
BI3
TR03_TAP_10
BI4
TR03_TAP_11
BI5
TR03_TAP_12
BI6
TR03_TAP_13
BI7
TR03_TAP_14
BI8
Not used
BI9
Not used
BI10
SMBI
RTCC3 STATUS
O:171|T:3|I:22
MASTER SEL.
VIn1
FOLLOWER SEL.
VIn2
INDPEN SEL.
VIn3
MANUAL SEL.
VIn4
Not used
VIn5
Not used
VIn6
Not used
VIn7
Not used
VIn8
Not used
VIn9
Not used
VIn10
MASTER SEL.
BI1
FOLLOWER SEL.
BI2
INDPEN SEL.
BI3
MANUAL SEL.
BI4
Not used
BI5
Not used
BI6
Not used
BI7
Not used
BI8
Not used
BI9
Not used
BI10
TR03_TAP_1
TR03_TAP_2
TR03_TAP_3
TR03_TAP_4
TR03_TAP_5
TR03_TAP_6
TR03_TAP_7
TR03_TAP_8
TR03_TAP_9
TR03_TAP_10
TR03_TAP_11
TR03_TAP_12
TR03_TAP_13
TR03_TAP_14
TR03_TAP_15
TR03_TAP_16
TR03_TAP_17
TR03_TAP_18
TR03_TAP_19
TR03_TAP_20
TR03_TAP_21
TR03_TAP_22
TR03_TAP_23
TR03_TAP_24
TR03_TAP_25
TR03_TAP_26
TR03_TAP_27
RTCC3_MASTER_SELECTED
RTCC3_FOLLOWER_SELECTED
RTCC3_INDEPENDENT_SELECTED
RTCC3_MANUAL_SELECTED
TR03_TAP_21
BIM_8.BI11
TR03_TAP_20
BIM_8.BI10
TR03_TAP_5
BIM_7.BI11
TR03_TAP_26
BIM_8.BI16
TR03_TAP_25
BIM_8.BI15
TR03_TAP_10
BIM_7.BI16
TR03_TAP_11
BIM_8.BI1
TR03_TAP_17
BIM_8.BI7
TR03_TAP_6
BIM_7.BI12
TR03_TAP_13
BIM_8.BI3
TR03_TAP_23
BIM_8.BI13
TR03_TAP_24
BIM_8.BI14
TR03_TAP_22
BIM_8.BI12
TR03_TAP_4
BIM_7.BI10
TR03_TAP_19
BIM_8.BI9
TR03_TAP_1
BIM_7.BI7
TR03_TAP_8
BIM_7.BI14
TR03_TAP_2
BIM_7.BI8
TR03_TAP_15
BIM_8.BI5
TR03_TAP_27
BIM_9.BI1
TR03_TAP_14
BIM_8.BI4
TR03_TAP_7
BIM_7.BI13
TR03_TAP_18
BIM_8.BI8
TR03_TAP_9
BIM_7.BI15
TR03_TAP_16
BIM_8.BI6 TR03_TAP_3
BIM_7.BI9
TR03_TAP_12
BIM_8.BI2
A A
B B
C C
D D
E E
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
Main Application: TR03_BIM, Page: 1
Rev. Modification Rel. date Created by
Replacing
Based on
Project
UMLUJJ 380_33_13.8KV PROTECTION
Responsible department
ABB Ltd.
UMLUJJ 380_33_13.8KV
PROTECTION.Substation.13.8KV.ABTS
Technical reference Document kind
Graphical Application Configuration
Doc. designation
AA1J4Q03A1
Created by Title
REC670-ABTS
Document id.
Approved by Rev.
0
Rel. date
13/08/2014
Lang.
en
7 / 52
SMBI
COMMON_INPUTS
O:162|T:3|I:13
TR04_BL_94-2
VIn1
TR01_ST_SET-2
VIn2
TR01_BL_SET-2
VIn3
TR01_BL_H18_F
VIn4
T05_ST_94-1
VIn5
TR05_BL_94-2
VIn6
TR02_ST_SET-2
VIn7
TR02_BL_SET-2
VIn8
NOT USED
VIn9
Not used
VIn10
TR04_BL_94-2
BI1
TR01_ST_SET-2
BI2
TR01_BL_SET-2
BI3
TR01_BL_H18_F
BI4
T05_ST_94-1
BI5
TR05_BL_94-2
BI6
TR02_ST_SET-2
BI7
TR02_BL_SET-2
BI8
NOT USED
BI9
Not used
BI10
SMBI
COMMON_INPUTS
O:163|T:3|I:14
TR01_BL_H36_F
VIn1
T06_ST_94-1
VIn2
TR06_BL_94-2
VIn3
TR03_ST_SET-2
VIn4
TR03_BL_SET-2
VIn5
NOT USED
VIn6
BUS-A_PROTN_T
VIn7
BUS-B_PROTN_T
VIn8
NOT USED
VIn9
NOT USED
VIn10
TR01_BL_H36_F
BI1
T06_ST_94-1
BI2
TR06_BL_94-2
BI3
TR03_ST_SET-2
BI4
TR03_BL_SET-2
BI5
NOT USED
BI6
BUS-A_PROTN_T
BI7
BUS-B_PROTN_T
BI8
NOT USED
BI9
NOT USED
BI10
SMBI
COMMON_INPUTS
O:160|T:3|I:11
CB_AH10_OPEN
VIn1
CB_AH10_CLOSE
VIn2
CB_AH10_INSE
VIn3
CB_A3H17_OPEN
VIn4
CB_A3H17_CLOS
VIn5
CB_A3H17_INSE
VIn6
CB_AH25_OPEN
VIn7
CB_AH25_CLOSE
VIn8
Not used
VIn9
Not used
VIn10
CB_AH10_OPEN
BI1
CB_AH10_CLOSE
BI2
CB_AH10_INSE
BI3
CB_A3H17_OPEN
BI4
CB_A3H17_CLOS
BI5
CB_A3H17_INSE
BI6
CB_AH25_OPEN
BI7
CB_AH25_CLOSE
BI8
Not used
BI9
Not used
BI10
SMBI
COMMON_INPUTS
O:161|T:3|I:12
CB_AH25_INSER
VIn1
CB_AH32_OPEN
VIn2
CB_AH32_CLOSE
VIn3
CB_AH32_INSER
VIn4
CB_AH40_OPEN
VIn5
CB_AH40_CLOSE
VIn6
CB_AH40_INSER
VIn7
T03_ST_94-1
VIn8
Not used
VIn9
Not used
VIn10
CB_AH25_INSER
BI1
CB_AH32_OPEN
BI2
CB_AH32_CLOSE
BI3
CB_AH32_INSER
BI4
CB_AH40_OPEN
BI5
CB_AH40_CLOSE
BI6
CB_AH40_INSER
BI7
T03_ST_94-1
BI8
Not used
BI9
Not used
BI10
CB_A302_OPEN_STATUS
CB_A304_CLOSE_STATUS
CB_A304_INSERVICE
BUS-A_PROTN_TRIP
CB_A305_OPEN_STATUS
CB_A305_CLOSE_STATUS
CB_A305_INSERVICE
BUS-B_PROTN_TRIP
CB_A301_OPEN_STATUS
CB_A301_CLOSE_STATUS
CB_A301_INSERVICE
TR01_ABTS_START
TR01_ABTS_BLOCK
CB_A304_OPEN_STATUS
CB_A302_CLOSE_STATUS
CB_A302_INSERVICE
CB_A303_OPEN_STATUS
CB_A303_CLOSE_STATUS
CB_A303_INSERVICE
TR01_ABTS_START_BY_TER(OC/REF)_TRIP
TR01_ABTS_BLK_BY_HV(OC&EF)_TRIP
TR02_ABTS_START
TR02_ABTS_BLOCK
TR02_ABTS_START_BY_TER(OC/REF)_TRIP
TR02_ABTS_BLK_BY_HV(OC&EF)_TRIP
TR03_ABTS_START
TR03_ABTS_BLOCK
TR03_ABTS_START_BY_TER(OC/REF)_TRIP
TR03_ABTS_BLK_BY_HV(OC&EF)_TRIP
TR01_ABTS_BLK_BY_A304_TC_FAULTY
TR02_ABTS_BLK_BY_A305_TC_FAULTY
TR04_BL_94-2
BIM_10.BI2
T06_ST_94-1
BIM_10.BI5
TR06_BL_94-2
BIM_10.BI6
T04_ST_94-1
BIM_10.BI1
BUS-A_PROTN_T
BIM_10.BI9
BUS-B_PROTN_T
BIM_10.BI10
CB_AH10_CLOSE
BIM_9.BI3
CB_A3H17_CLOS
BIM_9.BI6
CB_AH32_OPEN
BIM_9.BI11
CB_AH25_INSER
BIM_9.BI10
CB_AH25_OPEN
BIM_9.BI8
CB_AH40_INSER
BIM_9.BI16
CB_A3H10_INSE
BIM_9.BI4
CB_AH25_CLOSE
BIM_9.BI9
CB_AH40_CLOSE
BIM_9.BI15
CB_AH40_OPEN
BIM_9.BI14
CB_A3H17_OPEN
BIM_9.BI5
CB_AH32_CLOSE
BIM_9.BI12
CB_AH10_OPEN
BIM_9.BI2
CB_AH32_INSER
BIM_9.BI13
CB_A3H17_INSE
BIM_9.BI7
T05_ST_94-1
BIM_10.BI3
TR05_BL_94-2
BIM_10.BI4
A A
B B
C C
D D
E E
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
Main Application: COMM_BIM, Page: 1
Rev. Modification Rel. date Created by
Replacing
Based on
Project
UMLUJJ 380_33_13.8KV PROTECTION
Responsible department
ABB Ltd.
UMLUJJ 380_33_13.8KV
PROTECTION.Substation.13.8KV.ABTS
Technical reference Document kind
Graphical Application Configuration
Doc. designation
AA1J4Q03A1
Created by Title
REC670-ABTS
Document id.
Approved by Rev.
0
Rel. date
13/08/2014
Lang.
en
8 / 52
SMBI
COMMON_INPUTS
O:164|T:3|I:15
BUS-C_PROTN_T
VIn1
BS_AH17_PR_OP
VIn2
BS_AH32_PR_OP
VIn3
NOT USED
VIn4
NOT USED
VIn5
Not used
VIn6
Not used
VIn7
Not used
VIn8
Not used
VIn9
Not used
VIn10
BUS-C_PROTN_T
BI1
BS_AH17_PR_OP
BI2
BS_AH32_PR_OP
BI3
NOT USED
BI4
NOT USED
BI5
Not used
BI6
Not used
BI7
Not used
BI8
Not used
BI9
Not used
BI10
SMBI
COMMON_INPUTS
O:165|T:3|I:16
T601 OP
VIn1
SPARE
VIn2
T601 OP BK
VIn3
T602 OP
VIn4
SPARE
VIn5
T602_BK
VIn6
T603_OP
VIn7
RESET_PB
VIn8
Not used
VIn9
Not used
VIn10
T601 OP
BI1
SPARE
BI2
T601 OP BK
BI3
T602 OP
BI4
SPARE
BI5
T602_BK
BI6
T603_OP
BI7
RESET_PB
BI8
Not used
BI9
Not used
BI10
SMBI
COMMON_INPUTS
O:166|T:3|I:17
ABTS_ON
VIn1
ABTS_OFF
VIn2
BUS-A_FFR OPT
VIn3
BUS-B_FFR OPT
VIn4
BUS-C_FFR OPT
VIn5
U/V BS-1 OPTD
VIn6
U/V BS-2 OPTD
VIn7
U/V BS-3 OPTD
VIn8
Not used
VIn9
Not used
VIn10
ABTS_ON
BI1
ABTS_OFF
BI2
BUS-A_FFR OPT
BI3
BUS-B_FFR OPT
BI4
BUS-C_FFR OPT
BI5
U/V BS-1 OPTD
BI6
U/V BS-2 OPTD
BI7
U/V BS-3 OPTD
BI8
Not used
BI9
Not used
BI10
FXDSIGN
O:35|T:1|I:1
OFF
ON
INTZERO
INTONE
INTALONE
REALZERO
STRNULL
ZEROSMPL
GRP_OFF
SMBI
COMMON_INPUTS
O:172|T:3|I:23
SPARE
VIn1
T603_OP_BK
VIn2
BUS1_PT_FAIL
VIn3
BUS2_PT_FAIL
VIn4
BUS3_PT_FAIL
VIn5
T601_AVR_BLK
VIn6
T602_AVR_BLK
VIn7
T603_AVR_BLK
VIn8
ABTS_LOCAL
VIn9
ABTS_REMOTE
VIn10
SPARE
BI1
T603_OP_BK
BI2
BUS1_PT_FAIL
BI3
BUS2_PT_FAIL
BI4
BUS3_PT_FAIL
BI5
T601_AVR_BLK
BI6
T602_AVR_BLK
BI7
T603_AVR_BLK
BI8
ABTS_LOCAL
BI9
ABTS_REMOTE
BI10
ABTS_ON
ABTS_OFF
BUS-A_FFR OPTD
BUS-B_FFR OPTD
BUS-C_FFR OPTD
RESET_PUSH-BUTTON
FALSE
TRUE
INTZERO
GRP_OFF
BUS-C_PROTN_TRIP
BS-A304_PROTN_OPTD
BS-A305_PROTN_OPTD
REAL_ZERO
Undervoltage_OPTD_BS-1
Undervoltage_OPTD_BS-2
Undervoltage_OPTD_BS-3
ABTS_LOCAL
ABTS_REMOTE
T601_AVR_BLOCK
T602_AVR_BLOCK
T603_AVR_BLOCK
ABTS_TEST_ON
ABTS_TEST_OFF
BUS-A_FFR OPT
BIM_11.BI8
BS_AH32_PR_OP
BIM_10.BI13
BS_AH17_PR_OP
BIM_10.BI12
ABTS_ON
BIM_11.BI6 BUS-C_PROTN_T
BIM_10.BI11
BUS-B_FFR OPT
BIM_11.BI9
ABTS_OFF
BIM_11.BI7
RESET_PB
BIM_11.BI5
BUS-C_FFR OPT
BIM_11.BI10
BUS-1 FUSE FL
BIM_11.BI2
BUS-2 FUSE FL
BIM_11.BI3
BUS-3 FUSE FL
BIM_11.BI4
A A
B B
C C
D D
E E
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
Main Application: COMM_BIM, Page: 2
Rev. Modification Rel. date Created by
Replacing
Based on
Project
UMLUJJ 380_33_13.8KV PROTECTION
Responsible department
ABB Ltd.
UMLUJJ 380_33_13.8KV
PROTECTION.Substation.13.8KV.ABTS
Technical reference Document kind
Graphical Application Configuration
Doc. designation
AA1J4Q03A1
Created by Title
REC670-ABTS
Document id.
Approved by Rev.
0
Rel. date
13/08/2014
Lang.
en
9 / 52
QCBAY
O:4300|T:100|I:1
LR_OFF
LR_LOC
LR_REM
LR_VALID
BL_UPD
BL_CMD
PSTO
UPD_BLKD
CMD_BLKD
LOC
REM
VSGGIO
O:180|T:100|I:1
BLOCK
PSTO
IPOS1
IPOS2
BLOCKED
POSITION
POS1
POS2
CMDPOS12
CMDPOS21
ABTS_LOCAL
ABTS_REMOTE
TRUE
ABTS_OFF
ABTS_ON
ABTS ON CMD
ABTS OFF CMD
HMI_CONT_ON
A A
B B
C C
D D
E E
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
Main Application: COMM_BIM, Page: 3
Rev. Modification Rel. date Created by
Replacing
Based on
Project
UMLUJJ 380_33_13.8KV PROTECTION
Responsible department
ABB Ltd.
UMLUJJ 380_33_13.8KV
PROTECTION.Substation.13.8KV.ABTS
Technical reference Document kind
Graphical Application Configuration
Doc. designation
AA1J4Q03A1
Created by Title
REC670-ABTS
Document id.
Approved by Rev.
0
Rel. date
13/08/2014
Lang.
en
10 / 52
OR
O:410|T:3|I:8
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:504|T:3|I:9
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:506|T:3|I:10
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:508|T:3|I:11
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:510|T:3|I:12
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:704|T:3|I:13
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:706|T:3|I:14
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:1527|T:100|I:139
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:1675|T:100|I:146
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:1677|T:100|I:147
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:1679|T:100|I:148
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:1733|T:100|I:149
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:1739|T:100|I:152
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:1823|T:100|I:153
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
TR01_TAP_1
TR01_TAP2
FALSE
FALSE
FALSE
FALSE
TR01_TAP1
TR01_TAP_2
TR01_TAP3
FALSE
FALSE
FALSE
FALSE
TR01_TAP2
TR01_TAP_3
TR01_TAP4
FALSE
FALSE
FALSE
FALSE
TR01_TAP3
TR01_TAP_4
TR01_TAP5
FALSE
FALSE
FALSE
FALSE
TR01_TAP4
TR01_TAP_5
TR01_TAP6
FALSE
FALSE
FALSE
FALSE
TR01_TAP5
TR01_TAP_6
TR01_TAP7
TR01_TAP6
TR01_TAP_7
TR01_TAP8
TR01_TAP7
TR01_TAP_8
TR01_TAP9
FALSE
FALSE
FALSE
FALSE
TR01_TAP8
TR01_TAP_9
TR01_TAP10
FALSE
FALSE
FALSE
FALSE
TR01_TAP9
TR01_TAP_10
TR01_TAP11
FALSE
FALSE
FALSE
FALSE
TR01_TAP10
TR01_TAP_11
TR01_TAP12
FALSE
FALSE
FALSE
FALSE
TR01_TAP11
TR01_TAP_12
TR01_TAP13
FALSE
FALSE
FALSE
FALSE
TR01_TAP12
TR01_TAP_13
TR01_TAP14
FALSE
FALSE
FALSE
FALSE
TR01_TAP13
TR01_TAP_14
TR01_TAP15
FALSE
FALSE
FALSE
FALSE
TR01_TAP14
A A
B B
C C
D D
E E
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
Main Application: TR01_TAP, Page: 1
Rev. Modification Rel. date Created by
Replacing
Based on
Project
UMLUJJ 380_33_13.8KV PROTECTION
Responsible department
ABB Ltd.
UMLUJJ 380_33_13.8KV
PROTECTION.Substation.13.8KV.ABTS
Technical reference Document kind
Graphical Application Configuration
Doc. designation
AA1J4Q03A1
Created by Title
REC670-ABTS
Document id.
Approved by Rev.
0
Rel. date
13/08/2014
Lang.
en
11 / 52
OR
O:804|T:3|I:17
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:806|T:3|I:18
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:808|T:3|I:19
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:810|T:3|I:20
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:1004|T:3|I:21
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:1006|T:3|I:22
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:1008|T:3|I:23
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:1010|T:3|I:24
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:1825|T:100|I:154
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:1839|T:100|I:160
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:408|T:3|I:7
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:3306|T:3|I:58
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
TR01_TAP_15
TR01_TAP16
TR01_TAP15
TR01_TAP_16
TR01_TAP17
TR01_TAP16
TR01_TAP_17
TR01_TAP18
FALSE
FALSE
FALSE
FALSE
TR01_TAP17
TR01_TAP_18
TR01_TAP19
FALSE
FALSE
FALSE
FALSE
TR01_TAP18
TR01_TAP_19
TR01_TAP20
FALSE
FALSE
FALSE
FALSE
TR01_TAP19
TR01_TAP_20
TR01_TAP21
FALSE
FALSE
FALSE
FALSE
TR01_TAP20
TR01_TAP_21
TR01_TAP22
FALSE
FALSE
FALSE
FALSE
TR01_TAP21
TR01_TAP_22
TR01_TAP23
FALSE
FALSE
FALSE
FALSE
TR01_TAP22
TR01_TAP_23
TR01_TAP24
FALSE
FALSE
FALSE
FALSE
TR01_TAP23
TR01_TAP_24
FALSE
FALSE
FALSE
FALSE
TR01_TAP24
TR01_TAP25
TR01_TAP_25
FALSE
FALSE
FALSE
FALSE
TR01_TAP25
TR01_TAP26
TR01_TAP_26
FALSE
FALSE
FALSE
FALSE
TR01_TAP26
TR01_TAP_27
A A
B B
C C
D D
E E
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
Main Application: TR01_TAP, Page: 2
Rev. Modification Rel. date Created by
Replacing
Based on
Project
UMLUJJ 380_33_13.8KV PROTECTION
Responsible department
ABB Ltd.
UMLUJJ 380_33_13.8KV
PROTECTION.Substation.13.8KV.ABTS
Technical reference Document kind
Graphical Application Configuration
Doc. designation
AA1J4Q03A1
Created by Title
REC670-ABTS
Document id.
Approved by Rev.
0
Rel. date
13/08/2014
Lang.
en
12 / 52
OR
O:2003|T:3|I:33
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:2005|T:3|I:34
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:2007|T:3|I:35
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:1210|T:3|I:28
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:1604|T:3|I:29
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:1606|T:3|I:30
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:1608|T:3|I:31
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:1610|T:3|I:32
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:2009|T:3|I:36
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:2103|T:3|I:37
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:2105|T:3|I:38
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:2107|T:3|I:39
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:2109|T:3|I:40
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:2904|T:3|I:49
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
TR02_TAP_1
TR02_TAP2
FALSE
FALSE
FALSE
FALSE
TR02_TAP1
TR02_TAP_2
TR02_TAP3
FALSE
FALSE
FALSE
FALSE
TR02_TAP2
TR02_TAP_3
TR02_TAP4
FALSE
FALSE
FALSE
FALSE
TR02_TAP3
TR02_TAP_4
TR02_TAP5
FALSE
FALSE
FALSE
FALSE
TR02_TAP4
TR02_TAP_5
TR02_TAP6
FALSE
FALSE
FALSE
FALSE
TR02_TAP5
TR02_TAP_6
TR02_TAP7
FALSE
FALSE
FALSE
FALSE
TR02_TAP6
TR02_TAP_7
TR02_TAP8
FALSE
FALSE
FALSE
FALSE
TR02_TAP7
TR02_TAP_8
TR02_TAP9
FALSE
FALSE
FALSE
FALSE
TR02_TAP8
TR02_TAP_9
TR02_TAP10
FALSE
FALSE
FALSE
FALSE
TR02_TAP9
TR02_TAP_10
TR02_TAP11
FALSE
FALSE
FALSE
FALSE
TR02_TAP10
TR02_TAP_11
TR02_TAP12
FALSE
FALSE
FALSE
FALSE
TR02_TAP11
TR02_TAP_12
TR02_TAP13
FALSE
FALSE
FALSE
FALSE
TR02_TAP12
TR02_TAP_13
TR02_TAP14
FALSE
FALSE
FALSE
FALSE
TR02_TAP13
TR02_TAP_14
TR02_TAP15
FALSE
FALSE
FALSE
FALSE
TR02_TAP14
A A
B B
C C
D D
E E
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
Main Application: TR02_TAP, Page: 1
Rev. Modification Rel. date Created by
Replacing
Based on
Project
UMLUJJ 380_33_13.8KV PROTECTION
Responsible department
ABB Ltd.
UMLUJJ 380_33_13.8KV
PROTECTION.Substation.13.8KV.ABTS
Technical reference Document kind
Graphical Application Configuration
Doc. designation
AA1J4Q03A1
Created by Title
REC670-ABTS
Document id.
Approved by Rev.
0
Rel. date
13/08/2014
Lang.
en
13 / 52
OR
O:2906|T:3|I:50
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:2908|T:3|I:51
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:2504|T:3|I:41
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:2506|T:3|I:42
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:2508|T:3|I:43
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:2510|T:3|I:44
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:2604|T:3|I:45
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:2606|T:3|I:46
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:2608|T:3|I:47
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:2610|T:3|I:48
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:1583|T:100|I:141
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:1877|T:100|I:161
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
TR02_TAP_15
TR02_TAP16
FALSE
FALSE
FALSE
FALSE
TR02_TAP15
TR02_TAP_16
TR02_TAP17
FALSE
FALSE
FALSE
FALSE
TR02_TAP16
TR02_TAP_17
TR02_TAP18
FALSE
FALSE
FALSE
FALSE
TR02_TAP17
TR02_TAP_18
TR02_TAP19
FALSE
FALSE
FALSE
FALSE
TR02_TAP18
TR02_TAP_19
TR02_TAP20
FALSE
FALSE
FALSE
FALSE
TR02_TAP19
TR02_TAP_20
TR02_TAP21
FALSE
FALSE
FALSE
FALSE
TR02_TAP20
TR02_TAP_21
TR02_TAP22
FALSE
FALSE
FALSE
FALSE
TR02_TAP21
TR02_TAP_22
TR02_TAP23
FALSE
FALSE
FALSE
FALSE
TR02_TAP22
TR02_TAP_23
TR02_TAP24
FALSE
FALSE
FALSE
FALSE
TR02_TAP23
FALSE
FALSE
FALSE
FALSE
TR02_TAP24 TR02_TAP_24
TR02_TAP25
FALSE
FALSE
FALSE
FALSE
TR02_TAP25 TR02_TAP_25
TR02_TAP26
FALSE
FALSE
FALSE
FALSE
TR02_TAP26 TR02_TAP_26
TR02_TAP_27
A A
B B
C C
D D
E E
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
Main Application: TR02_TAP, Page: 2
Rev. Modification Rel. date Created by
Replacing
Based on
Project
UMLUJJ 380_33_13.8KV PROTECTION
Responsible department
ABB Ltd.
UMLUJJ 380_33_13.8KV
PROTECTION.Substation.13.8KV.ABTS
Technical reference Document kind
Graphical Application Configuration
Doc. designation
AA1J4Q03A1
Created by Title
REC670-ABTS
Document id.
Approved by Rev.
0
Rel. date
13/08/2014
Lang.
en
14 / 52
OR
O:103|T:8|I:61
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:105|T:8|I:62
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:107|T:8|I:63
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:109|T:8|I:64
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:153|T:8|I:65
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:155|T:8|I:66
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:157|T:8|I:67
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:159|T:8|I:68
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:703|T:8|I:69
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:705|T:8|I:70
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:707|T:8|I:71
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:709|T:8|I:72
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:803|T:8|I:73
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:805|T:8|I:74
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
TR03_TAP_1
TR03_TAP2
FALSE
FALSE
FALSE
FALSE
TR03_TAP1
TR03_TAP_2
TR03_TAP3
FALSE
FALSE
FALSE
FALSE
TR03_TAP2
TR03_TAP_3
TR03_TAP4
FALSE
FALSE
FALSE
FALSE
TR03_TAP3
TR03_TAP_4
TR03_TAP5
FALSE
FALSE
FALSE
FALSE
TR03_TAP4
TR03_TAP_5
TR03_TAP6
FALSE
FALSE
FALSE
FALSE
TR03_TAP5
TR03_TAP_6
TR03_TAP7
FALSE
FALSE
FALSE
FALSE
TR03_TAP6
TR03_TAP_7
TR03_TAP8
FALSE
FALSE
FALSE
FALSE
TR03_TAP7
TR03_TAP_8
TR03_TAP9
FALSE
FALSE
FALSE
FALSE
TR03_TAP8
TR03_TAP_9
TR03_TAP10
FALSE
FALSE
FALSE
FALSE
TR03_TAP9
TR03_TAP_10
TR03_TAP11
FALSE
FALSE
FALSE
FALSE
TR03_TAP10
TR03_TAP_11
TR03_TAP12
FALSE
FALSE
FALSE
FALSE
TR03_TAP11
TR03_TAP_12
TR03_TAP13
FALSE
FALSE
FALSE
FALSE
TR03_TAP12
TR03_TAP_13
TR03_TAP14
FALSE
FALSE
FALSE
FALSE
TR03_TAP13
TR03_TAP_14
TR03_TAP15
FALSE
FALSE
FALSE
FALSE
TR03_TAP14
A A
B B
C C
D D
E E
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
Main Application: TR03_TAP, Page: 1
Rev. Modification Rel. date Created by
Replacing
Based on
Project
UMLUJJ 380_33_13.8KV PROTECTION
Responsible department
ABB Ltd.
UMLUJJ 380_33_13.8KV
PROTECTION.Substation.13.8KV.ABTS
Technical reference Document kind
Graphical Application Configuration
Doc. designation
AA1J4Q03A1
Created by Title
REC670-ABTS
Document id.
Approved by Rev.
0
Rel. date
13/08/2014
Lang.
en
15 / 52
OR
O:807|T:8|I:75
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:809|T:8|I:76
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:903|T:8|I:77
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:905|T:8|I:78
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:907|T:8|I:79
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:909|T:8|I:80
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:1003|T:8|I:81
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:1005|T:8|I:82
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:1007|T:8|I:83
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:1009|T:8|I:84
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:1403|T:8|I:93
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:1529|T:100|I:140
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
TR03_TAP_15
TR03_TAP16
FALSE
FALSE
FALSE
FALSE
TR03_TAP15
TR03_TAP_16
TR03_TAP17
FALSE
FALSE
FALSE
FALSE
TR03_TAP16
TR03_TAP_17
TR03_TAP18
FALSE
FALSE
FALSE
FALSE
TR03_TAP17
TR03_TAP_18
TR03_TAP19
FALSE
FALSE
FALSE
FALSE
TR03_TAP18
TR03_TAP_19
TR03_TAP20
FALSE
FALSE
FALSE
FALSE
TR03_TAP19
TR03_TAP_20
TR03_TAP21
FALSE
FALSE
FALSE
FALSE
TR03_TAP20
TR03_TAP_21
TR03_TAP22
FALSE
FALSE
FALSE
FALSE
TR03_TAP21
TR03_TAP_22
TR03_TAP23
FALSE
FALSE
FALSE
FALSE
TR03_TAP22
TR03_TAP_23
TR03_TAP24
FALSE
FALSE
FALSE
FALSE
TR03_TAP23
TR03_TAP_24
TR03_TAP25
FALSE
FALSE
FALSE
FALSE
TR03_TAP24
TR03_TAP_25
TR03_TAP26
FALSE
FALSE
FALSE
FALSE
TR03_TAP25
TR03_TAP_26
TR03_TAP_27
FALSE
FALSE
FALSE
FALSE
TR03_TAP26
A A
B B
C C
D D
E E
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
Main Application: TR03_TAP, Page: 2
Rev. Modification Rel. date Created by
Replacing
Based on
Project
UMLUJJ 380_33_13.8KV PROTECTION
Responsible department
ABB Ltd.
UMLUJJ 380_33_13.8KV
PROTECTION.Substation.13.8KV.ABTS
Technical reference Document kind
Graphical Application Configuration
Doc. designation
AA1J4Q03A1
Created by Title
REC670-ABTS
Document id.
Approved by Rev.
0
Rel. date
13/08/2014
Lang.
en
16 / 52
OR
O:1253|T:8|I:85
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:1255|T:8|I:86
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
AND
O:505|T:3|I:9
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
OR
O:1257|T:8|I:87
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
AND
O:507|T:3|I:10
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:509|T:3|I:11
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:511|T:3|I:12
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
OR
O:1259|T:8|I:88
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
AND
O:2406|T:100|I:198
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:2408|T:100|I:199
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:2410|T:100|I:200
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:5708|T:100|I:219
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:5710|T:100|I:220
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:5804|T:100|I:221
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:5806|T:100|I:222
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:5908|T:100|I:227
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:5910|T:100|I:228
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:6004|T:100|I:229
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:6006|T:100|I:230
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:6008|T:100|I:231
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
TR01_TAP1
TRUE
TRUE
TR02_TAP1
FALSE
FALSE
TR01>TR02_1
TR01_TAP2
TRUE
TRUE
TR02_TAP2
TR01_TAP3
TRUE
TRUE
TR02_TAP3
TR01_TAP4
TRUE
TRUE
TR02_TAP4
TR01_TAP1
TR02_TAP1
TRUE
TRUE
FALSE
FALSE
TR02>TR01_1
TR01_TAP2
TR02_TAP2
TRUE
TRUE
TR01_TAP3
TR02_TAP3
TRUE
TRUE
TR01_TAP4
TR02_TAP4
TRUE
TRUE
TR01_TAP5
TRUE
TRUE
TR02_TAP5
FALSE
FALSE
TR01>TR02_2
TR01_TAP6
TRUE
TRUE
TR02_TAP6
TR01_TAP7
TRUE
TRUE
TR02_TAP7
TR01_TAP8
TRUE
TRUE
TR02_TAP8
TR01_TAP5
TR02_TAP5
TRUE
TRUE
FALSE
FALSE
TR02>TR01_2
TR01_TAP6
TR02_TAP6
TRUE
TRUE
TR01_TAP7
TR02_TAP7
TRUE
TRUE
TR01_TAP8
TR02_TAP8
TRUE
TRUE
A A
B B
C C
D D
E E
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
Main Application: TR01_TR02, Page: 1
Rev. Modification Rel. date Created by
Replacing
Based on
Project
UMLUJJ 380_33_13.8KV PROTECTION
Responsible department
ABB Ltd.
UMLUJJ 380_33_13.8KV
PROTECTION.Substation.13.8KV.ABTS
Technical reference Document kind
Graphical Application Configuration
Doc. designation
AA1J4Q03A1
Created by Title
REC670-ABTS
Document id.
Approved by Rev.
0
Rel. date
13/08/2014
Lang.
en
17 / 52
OR
O:1305|T:8|I:90
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:1307|T:8|I:91
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
AND
O:1211|T:3|I:28
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:1605|T:3|I:29
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
OR
O:1309|T:8|I:92
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
AND
O:1607|T:3|I:30
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:1609|T:3|I:31
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:1611|T:3|I:32
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:1882|T:100|I:163
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:2000|T:100|I:172
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:2104|T:100|I:173
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:2106|T:100|I:174
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
OR
O:1735|T:100|I:150
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
AND
O:2108|T:100|I:175
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:2110|T:100|I:176
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:2144|T:100|I:177
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:2146|T:100|I:178
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:2158|T:100|I:183
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:2160|T:100|I:184
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:2204|T:100|I:185
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
TR01_TAP9
TRUE
TRUE
TR02_TAP9
FALSE
FALSE
TR01>TR02_3
TR01_TAP10
TRUE
TRUE
TR02_TAP10
TR01_TAP11
TRUE
TRUE
TR02_TAP11
TR01_TAP12
TRUE
TRUE
TR02_TAP12
TR01_TAP9
TR02_TAP9
TRUE
TRUE
FALSE
FALSE
TR02>TR01_3
TR01_TAP10
TR02_TAP10
TRUE
TRUE
TR01_TAP11
TR02_TAP11
TRUE
TRUE
TR01_TAP12
TR02_TAP12
TRUE
TRUE
TR01_TAP13
TRUE
TRUE
TR02_TAP13
FALSE
FALSE
TR01>TR02_4 TR01_TAP14
TRUE
TRUE
TR02_TAP14
TR01_TAP15
TRUE
TRUE
TR02_TAP15
TR01_TAP16
TRUE
TRUE
TR02_TAP16
TR01_TAP13
TR02_TAP13
TRUE
TRUE
FALSE
FALSE
TR02>TR01_4
TR01_TAP14
TR02_TAP14
TRUE
TRUE
TR01_TAP15
TR02_TAP15
TRUE
TRUE
TR01_TAP16
TR02_TAP16
TRUE
TRUE
A A
B B
C C
D D
E E
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
Main Application: TR01_TR02, Page: 2
Rev. Modification Rel. date Created by
Replacing
Based on
Project
UMLUJJ 380_33_13.8KV PROTECTION
Responsible department
ABB Ltd.
UMLUJJ 380_33_13.8KV
PROTECTION.Substation.13.8KV.ABTS
Technical reference Document kind
Graphical Application Configuration
Doc. designation
AA1J4Q03A1
Created by Title
REC670-ABTS
Document id.
Approved by Rev.
0
Rel. date
13/08/2014
Lang.
en
18 / 52
OR
O:1405|T:8|I:94
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
AND
O:2505|T:3|I:41
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
OR
O:1407|T:8|I:95
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
AND
O:2507|T:3|I:42
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:2511|T:3|I:44
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:2605|T:3|I:45
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:2607|T:3|I:46
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
OR
O:1409|T:8|I:96
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
AND
O:2609|T:3|I:47
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:2611|T:3|I:48
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:2905|T:3|I:49
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:2907|T:3|I:50
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:2148|T:100|I:179
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:2150|T:100|I:180
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:2154|T:100|I:181
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:6010|T:100|I:232
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
OR
O:1737|T:100|I:151
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
AND
O:1824|T:100|I:153
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:1826|T:100|I:154
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:1828|T:100|I:155
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:2156|T:100|I:182
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:2206|T:100|I:186
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
TR01_TAP17
TRUE
TRUE
TR02_TAP17
FALSE
FALSE
TR01>TR02_5
TR01_TAP18
TRUE
TRUE
TR02_TAP18
TR01_TAP19
TRUE
TRUE
TR02_TAP19
TR01_TAP20
TRUE
TRUE
TR02_TAP20
TR01_TAP17
TR02_TAP17
TRUE
TRUE
FALSE
FALSE
TR02>TR01_5
TR01_TAP18
TR02_TAP18
TRUE
TRUE
TR01_TAP19
TR02_TAP19
TRUE
TRUE
TR01_TAP20
TR02_TAP20
TRUE
TRUE
TR01_TAP21
TRUE
TRUE
TR02_TAP21
FALSE
TR01>TR02_6
TR01_TAP22
TRUE
TRUE
TR02_TAP22
TR01_TAP23
TRUE
TRUE
TR02_TAP23
TR01_TAP24
TRUE
TRUE
TR02_TAP24
TRUE
TRUE
TR01_TAP21
TR02_TAP21
TRUE
TRUE
FALSE
TR02>TR01_6
TR01_TAP22
TR02_TAP22
TRUE
TRUE
TR01_TAP23
TR02_TAP23
TRUE
TRUE
TR01_TAP24
TR02_TAP24
TRUE
TRUE
TRUE
TRUE
TR01_TAP25
TR02_TAP25
TR01_TAP25
TR02_TAP25
A A
B B
C C
D D
E E
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
Main Application: TR01_TR02, Page: 3
Rev. Modification Rel. date Created by
Replacing
Based on
Project
UMLUJJ 380_33_13.8KV PROTECTION
Responsible department
ABB Ltd.
UMLUJJ 380_33_13.8KV
PROTECTION.Substation.13.8KV.ABTS
Technical reference Document kind
Graphical Application Configuration
Doc. designation
AA1J4Q03A1
Created by Title
REC670-ABTS
Document id.
Approved by Rev.
0
Rel. date
13/08/2014
Lang.
en
19 / 52
OR
O:503|T:100|I:121
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:507|T:100|I:123
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:505|T:100|I:122
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
AND
O:2220|T:100|I:192
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
OR
O:1879|T:100|I:162
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
AND
O:2304|T:100|I:193
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:5404|T:100|I:205
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
OR
O:1881|T:100|I:163
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
AND
O:5406|T:100|I:206
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
OR
O:1883|T:100|I:164
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:1887|T:100|I:165
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
TR01>TR02_1
TR01>TR02_2
TR01>TR02_3
TR01>TR02_4
TR01>TR02_5
TR01>TR02_6
TR01>TR02
FALSE
FALSE
FALSE
FALSE
TR01=TR02
TR02>TR01_1
TR02>TR01_2
TR02>TR01_3
TR02>TR01_4
TR02>TR01_5
TR02>TR01_6
TR02>TR01
TR01_TAP26
TRUE
TRUE
TR02_TAP26
FALSE
TR01>TR02_7
TR01_TAP_27
TRUE
TRUE
TR02_TAP_27
TR01_TAP26
TR02_TAP26
TRUE
TRUE
FALSE
TR02>TR01_7
TR01_TAP_27
TR02_TAP_27
TRUE
TRUE
FALSE
FALSE
FALSE
FALSE
FALSE
FALSE
TR01>TR02_7
TR02>TR01_7
FALSE
FALSE
FALSE
FALSE
FALSE
FALSE
FALSE
FALSE
A A
B B
C C
D D
E E
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
Main Application: TR01_TR02, Page: 4
Rev. Modification Rel. date Created by
Replacing
Based on
Project
UMLUJJ 380_33_13.8KV PROTECTION
Responsible department
ABB Ltd.
UMLUJJ 380_33_13.8KV
PROTECTION.Substation.13.8KV.ABTS
Technical reference Document kind
Graphical Application Configuration
Doc. designation
AA1J4Q03A1
Created by Title
REC670-ABTS
Document id.
Approved by Rev.
0
Rel. date
13/08/2014
Lang.
en
20 / 52
OR
O:1503|T:8|I:97
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:1505|T:8|I:98
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:1507|T:8|I:99
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:1509|T:8|I:100
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
AND
O:110|T:8|I:64
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:154|T:8|I:65
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:156|T:8|I:66
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:1830|T:100|I:156
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:1834|T:100|I:157
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:1836|T:100|I:158
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:1838|T:100|I:159
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:1840|T:100|I:160
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:1884|T:100|I:164
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:1888|T:100|I:165
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:1890|T:100|I:166
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:1892|T:100|I:167
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:1894|T:100|I:168
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:1998|T:100|I:171
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:5408|T:100|I:207
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:2214|T:100|I:189
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
TR02_TAP1
TRUE
TRUE
TR03_TAP1
FALSE
FALSE
TR02>TR03_1
TR02_TAP2
TRUE
TR03_TAP2
TR02_TAP3
TRUE
TRUE
TR03_TAP3
TR02_TAP4
TRUE
TRUE
TR03_TAP4
TR02_TAP1
TR03_TAP1
TRUE
TRUE
FALSE
FALSE
TR03>TR02_1
TR02_TAP2
TR03_TAP2
TRUE
TRUE
TR02_TAP3
TR03_TAP3
TRUE
TRUE
TR02_TAP4
TR03_TAP4
TRUE
TRUE
TR02_TAP5
TRUE
TRUE
TR03_TAP5
FALSE
FALSE
TR02>TR03_2
TR02_TAP6
TRUE
TRUE
TR03_TAP6
TR02_TAP7
TRUE
TR03_TAP7
TR02_TAP8
TRUE
TRUE
TR03_TAP8
TR02_TAP5
TR03_TAP5
TRUE
TRUE
FALSE
FALSE
TR03>TR02_2
TR02_TAP6
TR03_TAP6
TRUE
TRUE
TR02_TAP7
TR03_TAP7
TRUE
TRUE
TR02_TAP8
TR03_TAP8
TRUE
TRUE
A A
B B
C C
D D
E E
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
Main Application: TR02_TR03, Page: 1
Rev. Modification Rel. date Created by
Replacing
Based on
Project
UMLUJJ 380_33_13.8KV PROTECTION
Responsible department
ABB Ltd.
UMLUJJ 380_33_13.8KV
PROTECTION.Substation.13.8KV.ABTS
Technical reference Document kind
Graphical Application Configuration
Doc. designation
AA1J4Q03A1
Created by Title
REC670-ABTS
Document id.
Approved by Rev.
0
Rel. date
13/08/2014
Lang.
en
21 / 52
AND
O:158|T:8|I:67
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
OR
O:1803|T:8|I:101
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
AND
O:160|T:8|I:68
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:704|T:8|I:69
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:706|T:8|I:70
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:708|T:8|I:71
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
OR
O:1805|T:8|I:102
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
AND
O:710|T:8|I:72
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:804|T:8|I:73
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:806|T:8|I:74
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
OR
O:1807|T:8|I:103
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
AND
O:810|T:8|I:76
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:904|T:8|I:77
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:906|T:8|I:78
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:908|T:8|I:79
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
OR
O:1809|T:8|I:104
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
AND
O:910|T:8|I:80
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:1004|T:8|I:81
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:1006|T:8|I:82
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:2216|T:100|I:190
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT TR02_TAP9
TRUE
TRUE
TR03_TAP9
FALSE
FALSE
TR02>TR03_3
TR02_TAP10
TRUE
TRUE
TR03_TAP10
TR02_TAP11
TRUE
TRUE
TR03_TAP11
TR02_TAP12
TRUE
TRUE
TR03_TAP12
TR02_TAP9
TR03_TAP9
TRUE
TRUE
FALSE
FALSE
TR03>TR02_3
TR02_TAP10
TR03_TAP10
TRUE
TRUE
TR02_TAP11
TR03_TAP11
TRUE
TRUE
TR02_TAP12
TR03_TAP12
TRUE
TRUE
TR02_TAP13
TRUE
TRUE
TR03_TAP13
FALSE
FALSE
TR02>TR03_4
TR02_TAP14
TRUE
TRUE
TR03_TAP14
TR02_TAP15
TRUE
TRUE
TR03_TAP15
TR02_TAP16
TRUE
TRUE
TR03_TAP16
TR02_TAP13
TR03_TAP13
TRUE
TRUE
FALSE
FALSE
TR03>TR02_4
TR02_TAP14
TR03_TAP14
TRUE
TRUE
TR02_TAP15
TR03_TAP15
TRUE
TRUE
TR02_TAP16
TR03_TAP16
TRUE
TRUE
A A
B B
C C
D D
E E
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
Main Application: TR02_TR03, Page: 2
Rev. Modification Rel. date Created by
Replacing
Based on
Project
UMLUJJ 380_33_13.8KV PROTECTION
Responsible department
ABB Ltd.
UMLUJJ 380_33_13.8KV
PROTECTION.Substation.13.8KV.ABTS
Technical reference Document kind
Graphical Application Configuration
Doc. designation
AA1J4Q03A1
Created by Title
REC670-ABTS
Document id.
Approved by Rev.
0
Rel. date
13/08/2014
Lang.
en
22 / 52
AND
O:1008|T:8|I:83
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
OR
O:1903|T:8|I:105
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
AND
O:1010|T:8|I:84
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:1254|T:8|I:85
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:1256|T:8|I:86
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:1258|T:8|I:87
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
OR
O:1905|T:8|I:106
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
AND
O:1260|T:8|I:88
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:1304|T:8|I:89
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:1306|T:8|I:90
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:1308|T:8|I:91
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
OR
O:1907|T:8|I:107
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
AND
O:1310|T:8|I:92
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:1404|T:8|I:93
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:1406|T:8|I:94
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:1408|T:8|I:95
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:1410|T:8|I:96
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
OR
O:1909|T:8|I:108
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
AND
O:1504|T:8|I:97
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:1506|T:8|I:98
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:1508|T:8|I:99
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:1510|T:8|I:100
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
TR02_TAP17
TRUE
TRUE
TR03_TAP17
FALSE
FALSE
TR02>TR03_5
TR02_TAP18
TRUE
TRUE
TR03_TAP18
TR02_TAP19
TRUE
TRUE
TR03_TAP19
TR02_TAP20
TRUE
TRUE
TR03_TAP20
TR02_TAP17
TR03_TAP17
TRUE
TRUE
FALSE
FALSE
TR03>TR02_5
TR02_TAP18
TR03_TAP18
TRUE
TRUE
TR02_TAP19
TR03_TAP19
TRUE
TRUE
TR02_TAP20
TR03_TAP20
TRUE
TRUE
TR02_TAP21
TRUE
TRUE
TR03_TAP21
FALSE
TR02>TR03_6
TR02_TAP22
TRUE
TRUE
TR03_TAP22
TR02_TAP23
TRUE
TRUE
TR03_TAP23
TR02_TAP24
TRUE
TRUE
TR03_TAP24
TRUE
TRUE
TR03_TAP25
TR02_TAP21
TR03_TAP21
TRUE
TRUE
FALSE
TR03>TR02_6
TR02_TAP22
TR03_TAP22
TRUE
TRUE
TR02_TAP23
TR03_TAP23
TRUE
TRUE
TR02_TAP24
TR03_TAP24
TRUE
TRUE
TR03_TAP25
TRUE
TRUE
TR02_TAP25
TR02_TAP25
A A
B B
C C
D D
E E
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
Main Application: TR02_TR03, Page: 3
Rev. Modification Rel. date Created by
Replacing
Based on
Project
UMLUJJ 380_33_13.8KV PROTECTION
Responsible department
ABB Ltd.
UMLUJJ 380_33_13.8KV
PROTECTION.Substation.13.8KV.ABTS
Technical reference Document kind
Graphical Application Configuration
Doc. designation
AA1J4Q03A1
Created by Title
REC670-ABTS
Document id.
Approved by Rev.
0
Rel. date
13/08/2014
Lang.
en
23 / 52
OR
O:509|T:100|I:124
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:605|T:100|I:126
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:603|T:100|I:125
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
AND
O:2218|T:100|I:191
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
OR
O:1889|T:100|I:166
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
AND
O:2306|T:100|I:194
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:6104|T:100|I:233
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
OR
O:1891|T:100|I:167
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
AND
O:6106|T:100|I:234
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
OR
O:1893|T:100|I:168
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:1993|T:100|I:169
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
TR02>TR03_1
TR02>TR03_2
TR02>TR03_3
TR02>TR03_4
TR02>TR03_5
TR02>TR03_6
TR02>TR03
FALSE
FALSE
FALSE
FALSE
TR02=TR03
TR03>TR02_1
TR03>TR02_2
TR03>TR02_3
TR03>TR02_4
TR03>TR02_5
TR03>TR02_6
TR03>TR02
TR02_TAP26
TRUE
TRUE
TR03_TAP26
FALSE
TR02>TR03_7
TR02_TAP_27
TRUE
TRUE
TR03_TAP_27
TR02_TAP26
TR03_TAP26
TRUE
TRUE
FALSE
TR03>TR02_7
TR02_TAP_27
TR03_TAP_27
TRUE
TRUE
FALSE
FALSE
FALSE
FALSE
FALSE
FALSE
TR02>TR03_7
TR03>TR02_7
FALSE
FALSE
FALSE
FALSE
FALSE
FALSE
FALSE
FALSE
A A
B B
C C
D D
E E
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
Main Application: TR02_TR03, Page: 4
Rev. Modification Rel. date Created by
Replacing
Based on
Project
UMLUJJ 380_33_13.8KV PROTECTION
Responsible department
ABB Ltd.
UMLUJJ 380_33_13.8KV
PROTECTION.Substation.13.8KV.ABTS
Technical reference Document kind
Graphical Application Configuration
Doc. designation
AA1J4Q03A1
Created by Title
REC670-ABTS
Document id.
Approved by Rev.
0
Rel. date
13/08/2014
Lang.
en
24 / 52
AND
O:1804|T:8|I:101
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
OR
O:2003|T:8|I:109
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
AND
O:1806|T:8|I:102
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:1808|T:8|I:103
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:1810|T:8|I:104
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:1904|T:8|I:105
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
OR
O:2005|T:8|I:110
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
AND
O:1906|T:8|I:106
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:1908|T:8|I:107
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:1910|T:8|I:108
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:2004|T:8|I:109
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
OR
O:2007|T:8|I:111
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
AND
O:2006|T:8|I:110
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:2008|T:8|I:111
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:2010|T:8|I:112
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:2504|T:8|I:113
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
OR
O:2009|T:8|I:112
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
AND
O:2506|T:8|I:114
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:2508|T:8|I:115
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:2510|T:8|I:116
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
TR01_TAP1
TRUE
TRUE
TR03_TAP1
FALSE
FALSE
TR01>TR03_1
TR01_TAP2
TRUE
TRUE
TR03_TAP2
TR01_TAP3
TRUE
TRUE
TR03_TAP3
TR01_TAP4
TRUE
TRUE
TR03_TAP4
TR01_TAP1
TR03_TAP1
TRUE
TRUE
FALSE
FALSE
TR03>TR01_1
TR01_TAP2
TR03_TAP2
TRUE
TRUE
TR01_TAP3
TR03_TAP3
TRUE
TRUE
TR01_TAP4
TR03_TAP4
TRUE
TRUE
TR01_TAP5
TRUE
TRUE
TR03_TAP5
FALSE
FALSE
TR01>TR03_2
TR01_TAP6
TRUE
TRUE
TR03_TAP6
TR01_TAP7
TRUE
TRUE
TR03_TAP7
TR01_TAP8
TRUE
TRUE
TR03_TAP8
TR01_TAP5
TR03_TAP5
TRUE
TRUE
FALSE
FALSE
TR03>TR01_2
TR01_TAP6
TR03_TAP6
TRUE
TRUE
TR01_TAP7
TR03_TAP7
TRUE
TRUE
TR01_TAP8
TR03_TAP8
TRUE
TRUE
A A
B B
C C
D D
E E
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
Main Application: TR03_TR01, Page: 1
Rev. Modification Rel. date Created by
Replacing
Based on
Project
UMLUJJ 380_33_13.8KV PROTECTION
Responsible department
ABB Ltd.
UMLUJJ 380_33_13.8KV
PROTECTION.Substation.13.8KV.ABTS
Technical reference Document kind
Graphical Application Configuration
Doc. designation
AA1J4Q03A1
Created by Title
REC670-ABTS
Document id.
Approved by Rev.
0
Rel. date
13/08/2014
Lang.
en
25 / 52
AND
O:2544|T:8|I:117
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
OR
O:2503|T:8|I:113
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
AND
O:2546|T:8|I:118
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:2548|T:8|I:119
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:2550|T:8|I:120
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:504|T:100|I:121
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
OR
O:2505|T:8|I:114
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
AND
O:506|T:100|I:122
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:508|T:100|I:123
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:510|T:100|I:124
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:604|T:100|I:125
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
OR
O:2507|T:8|I:115
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
AND
O:606|T:100|I:126
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:608|T:100|I:127
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:610|T:100|I:128
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:704|T:100|I:129
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
OR
O:2509|T:8|I:116
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
AND
O:706|T:100|I:130
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:708|T:100|I:131
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:710|T:100|I:132
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
TR01_TAP9
TRUE
TRUE
TR03_TAP9
FALSE
FALSE
TR01>TR03_3
TR01_TAP10
TRUE
TRUE
TR03_TAP10
TR01_TAP11
TRUE
TRUE
TR03_TAP11
TR01_TAP12
TRUE
TRUE
TR03_TAP12
TR01_TAP9
TR03_TAP9
TRUE
TRUE
FALSE
FALSE
TR03>TR01_3
TR01_TAP10
TR03_TAP10
TRUE
TRUE
TR01_TAP11
TR03_TAP11
TRUE
TRUE
TR01_TAP12
TR03_TAP12
TRUE
TRUE
TR01_TAP13
TRUE
TRUE
TR03_TAP13
FALSE
FALSE
TR01>TR03_4
TR01_TAP14
TRUE
TRUE
TR03_TAP14
TR01_TAP15
TRUE
TRUE
TR03_TAP15
TR01_TAP16
TRUE
TRUE
TR03_TAP16
TR01_TAP13
TR03_TAP13
TRUE
TRUE
FALSE
FALSE
TR03>TR01_4
TR01_TAP14
TR03_TAP14
TRUE
TRUE
TR01_TAP15
TR03_TAP15
TRUE
TRUE
TR01_TAP16
TR03_TAP16
TRUE
TRUE
A A
B B
C C
D D
E E
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
Main Application: TR03_TR01, Page: 2
Rev. Modification Rel. date Created by
Replacing
Based on
Project
UMLUJJ 380_33_13.8KV PROTECTION
Responsible department
ABB Ltd.
UMLUJJ 380_33_13.8KV
PROTECTION.Substation.13.8KV.ABTS
Technical reference Document kind
Graphical Application Configuration
Doc. designation
AA1J4Q03A1
Created by Title
REC670-ABTS
Document id.
Approved by Rev.
0
Rel. date
13/08/2014
Lang.
en
26 / 52
AND
O:804|T:100|I:133
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
OR
O:2543|T:8|I:117
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
AND
O:806|T:100|I:134
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:808|T:100|I:135
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:810|T:100|I:136
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:1524|T:100|I:137
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
OR
O:2545|T:8|I:118
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
AND
O:1526|T:100|I:138
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:1528|T:100|I:139
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:1530|T:100|I:140
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:1584|T:100|I:141
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
OR
O:2547|T:8|I:119
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
AND
O:1586|T:100|I:142
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:1588|T:100|I:143
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:1590|T:100|I:144
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:1674|T:100|I:145
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:1676|T:100|I:146
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
OR
O:2549|T:8|I:120
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
AND
O:1678|T:100|I:147
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:1680|T:100|I:148
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:1734|T:100|I:149
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:1736|T:100|I:150
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
TR01_TAP17
TRUE
TRUE
TR03_TAP17
FALSE
FALSE
TR01>TR03_5
TR01_TAP18
TRUE
TRUE
TR03_TAP18
TR01_TAP19
TRUE
TRUE
TR03_TAP19
TR01_TAP20
TRUE
TRUE
TR03_TAP20
TR01_TAP17
TR03_TAP17
TRUE
TRUE
FALSE
FALSE
TR03>TR01_5
TR01_TAP18
TR03_TAP18
TRUE
TRUE
TR01_TAP19
TR03_TAP19
TRUE
TRUE
TR01_TAP20
TR03_TAP20
TRUE
TRUE
TR01_TAP21
TRUE
TRUE
TR03_TAP21
FALSE
TR01>TR03_6
TR01_TAP22
TRUE
TRUE
TR03_TAP22
TR01_TAP23
TRUE
TRUE
TR03_TAP23
TR01_TAP24
TRUE
TRUE
TR03_TAP24
TRUE
TRUE
TR03_TAP25
TR01_TAP21
TR03_TAP21
TRUE
TRUE
FALSE
TR03>TR01_6
TR01_TAP22
TR03_TAP22
TRUE
TRUE
TR01_TAP23
TR03_TAP23
TRUE
TRUE
TR01_TAP24
TR03_TAP24
TRUE
TRUE
TR03_TAP25
TRUE
TRUE
TR01_TAP25
TR01_TAP25
A A
B B
C C
D D
E E
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
Main Application: TR03_TR01, Page: 3
Rev. Modification Rel. date Created by
Replacing
Based on
Project
UMLUJJ 380_33_13.8KV PROTECTION
Responsible department
ABB Ltd.
UMLUJJ 380_33_13.8KV
PROTECTION.Substation.13.8KV.ABTS
Technical reference Document kind
Graphical Application Configuration
Doc. designation
AA1J4Q03A1
Created by Title
REC670-ABTS
Document id.
Approved by Rev.
0
Rel. date
13/08/2014
Lang.
en
27 / 52
OR
O:607|T:100|I:127
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:703|T:100|I:129
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:609|T:100|I:128
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
AND
O:2404|T:100|I:197
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
OR
O:1995|T:100|I:170
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
AND
O:5410|T:100|I:208
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:6204|T:100|I:237
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
OR
O:1997|T:100|I:171
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
AND
O:6206|T:100|I:238
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
OR
O:1999|T:100|I:172
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:2103|T:100|I:173
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
TR01>TR03_1
TR01>TR03_2
TR01>TR03_3
TR01>TR03_4
TR01>TR03_5
TR01>TR03_6
TR01>TR03
FALSE
FALSE
FALSE
FALSE
TR01=TR03
TR03>TR01_1
TR03>TR01_2
TR03>TR01_3
TR03>TR01_4
TR03>TR01_5
TR03>TR01_6
TR03>TR01
TR01_TAP26
TRUE
TRUE
TR03_TAP26
TR01>TR03_7
TR01_TAP_27
TRUE
TRUE
TR03_TAP_27
TR01_TAP26
TR03_TAP26
TRUE
TRUE
FALSE
TR03>TR01_7
TR01_TAP_27
TR03_TAP_27
TRUE
TRUE
FALSE
FALSE
FALSE
FALSE
FALSE
FALSE
FALSE
TR01>TR03_7
TR03>TR01_7
FALSE
FALSE
FALSE
FALSE
FALSE
FALSE
FALSE
FALSE
A A
B B
C C
D D
E E
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
Main Application: TR03_TR01, Page: 4
Rev. Modification Rel. date Created by
Replacing
Based on
Project
UMLUJJ 380_33_13.8KV PROTECTION
Responsible department
ABB Ltd.
UMLUJJ 380_33_13.8KV
PROTECTION.Substation.13.8KV.ABTS
Technical reference Document kind
Graphical Application Configuration
Doc. designation
AA1J4Q03A1
Created by Title
REC670-ABTS
Document id.
Approved by Rev.
0
Rel. date
13/08/2014
Lang.
en
28 / 52
OR
O:2910|T:3|I:52
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
AND
O:1740|T:100|I:152
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:1738|T:100|I:151
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
XOR
O:218|T:3|I:1
INPUT1
INPUT2
OUT
NOUT
XOR
O:519|T:3|I:2
INPUT1
INPUT2
OUT
NOUT
XOR
O:819|T:3|I:3
INPUT1
INPUT2
OUT
NOUT
TIMER
O:212|T:3|I:1
INPUT ON
OFF
XOR
O:1019|T:3|I:4
INPUT1
INPUT2
OUT
NOUT
XOR
O:1219|T:3|I:5
INPUT1
INPUT2
OUT
NOUT
OR
O:1835|T:100|I:158
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
BUS-A_PROTN_TRIP
BUS-B_PROTN_TRIP
BUS-C_PROTN_TRIP
BS-A304_PROTN_OPTD
BS-A305_PROTN_OPTD
FALSE
BB_PROT_OPTD
CB_A301_INSERVICE
CB_A304_INSERVICE
CB_A302_INSERVICE
ALL CB_INSER
CB_A305_INSERVICE
CB_A303_INSERVICE
CB_A301_OPEN_STATUS
CB_A301_CLOSE_STATUS
FALSE
CB_A304_OPEN_STATUS
CB_A304_CLOSE_STATUS
CB_A302_OPEN_STATUS
CB_A302_CLOSE_STATUS
ALL_CB_FAULTY
CB_A305_OPEN_STATUS
CB_A305_CLOSE_STATUS
CB_A303_OPEN_STATUS
CB_A303_CLOSE_STATUS
A A
B B
C C
D D
E E
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
Main Application: COMMON_INTERLOCK, Page: 1
Rev. Modification Rel. date Created by
Replacing
Based on
Project
UMLUJJ 380_33_13.8KV PROTECTION
Responsible department
ABB Ltd.
UMLUJJ 380_33_13.8KV
PROTECTION.Substation.13.8KV.ABTS
Technical reference Document kind
Graphical Application Configuration
Doc. designation
AA1J4Q03A1
Created by Title
REC670-ABTS
Document id.
Approved by Rev.
0
Rel. date
13/08/2014
Lang.
en
29 / 52
OR
O:3308|T:3|I:59
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:3310|T:3|I:60
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
PULSETIMER
O:2614|T:3|I:8
INPUT OUT
PULSETIMER
O:2914|T:3|I:9
INPUT OUT
PULSETIMER
O:3314|T:3|I:10
INPUT OUT
OR
O:1827|T:100|I:155
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:1829|T:100|I:156
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:1833|T:100|I:157
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:1837|T:100|I:159
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:3204|T:3|I:53
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:3206|T:3|I:54
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:3208|T:3|I:55
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:3210|T:3|I:56
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
BUS-A_PROTN_TRIP
BUS-B_PROTN_TRIP
BUS-C_PROTN_TRIP
FALSE
FALSE
FALSE
BB PROT_LOCKOUT OPTD
BS-A304_PROTN_OPTD
BS-A305_PROTN_OPTD
FALSE
FALSE
FALSE
FALSE
BS PROT_OPTD
TR01_ABTS_START
TR01_ABTS_BLOCK
TR03_ABTS_START
TR LOCKOUT OPTD
TR03_ABTS_BLOCK
TR BACKUP PROT OPTD
TR02_ABTS_START
TR02_ABTS_BLOCK
TR01_ABTS_START T01_ABTS_START
TR01_ABTS_BLOCK T01_ABTS_BLOCK
TR02_ABTS_START T02_ABTS_START
TR02_ABTS_BLOCK T02_ABTS_BLOCK
TR03_ABTS_BLOCK
TR03_ABTS_START T03_ABTS_START
T03_ABTS_BLOCK
FALSE
FALSE
FALSE
FALSE
FALSE
FALSE
FALSE
FALSE
FALSE
FALSE
FALSE
FALSE
FALSE
FALSE
FALSE
FALSE
FALSE
FALSE
FALSE
FALSE
FALSE
BB_PROT_OPTD
FALSE
FALSE
FALSE
FALSE
FALSE
FALSE
FALSE
FALSE
FALSE
FALSE
FALSE
FALSE
A A
B B
C C
D D
E E
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
Main Application: COMMON_INTERLOCK, Page: 2
Rev. Modification Rel. date Created by
Replacing
Based on
Project
UMLUJJ 380_33_13.8KV PROTECTION
Responsible department
ABB Ltd.
UMLUJJ 380_33_13.8KV
PROTECTION.Substation.13.8KV.ABTS
Technical reference Document kind
Graphical Application Configuration
Doc. designation
AA1J4Q03A1
Created by Title
REC670-ABTS
Document id.
Approved by Rev.
0
Rel. date
13/08/2014
Lang.
en
30 / 52
PULSETIMER
O:213|T:3|I:1
INPUT OUT
AND
O:1878|T:100|I:161
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:1880|T:100|I:162
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
TIMER
O:1013|T:3|I:4
INPUT ON
OFF
SRMEMORY
O:214|T:3|I:1
SET
RESET
OUT
NOUT
AND
O:206|T:3|I:2
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:208|T:3|I:3
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:210|T:3|I:4
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:405|T:3|I:5
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:711|T:3|I:16
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:104|T:8|I:61
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
ALL CB_INSER
BUS-B_HEALTHY
BUS-C_HEALTHY
BB_PROT_OPTD
T01_ABTS_START
T01_ABTS_BLOCK
RESET_1,2,3
TRANSFER_1
TR03_BLK AVR_1
TR02_BLK AVR_1
CB_A301_OPEN_STATUS
CB_A302_CLOSE_STATUS
FALSE
CB_A303_CLOSE_STATUS
CB_A304_CLOSE_STATUS
CB_A305_OPEN_STATUS
TR02_ABTS_BLK_BY_A305_TC_FAULTY
TR02_AUTO_1
TR03_AUTO_1
TR02>TR03
TRUE
FALSE
TR03_TAP RAISE_1
TR03>TR02
TRUE
FALSE
TR02_TAP RAISE_1
TR02=TR03
TRUE
FALSE
A305_START SYN_1
ABTS_ON
ABTS_ABORT
TRUE
TR02_MASTER1
TR03_FOLLOWER1
TR02_AVR_MANUAL1
TR03_AVR_MANUAL1
TR02_AVR_INDEPENDENT1
TR03_AVR_INDEPENDENT1
TRANSFER1
A A
B B
C C
D D
E E
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
Main Application: TRANS_123456, Page: 1
Rev. Modification Rel. date Created by
Replacing
Based on
Project
UMLUJJ 380_33_13.8KV PROTECTION
Responsible department
ABB Ltd.
UMLUJJ 380_33_13.8KV
PROTECTION.Substation.13.8KV.ABTS
Technical reference Document kind
Graphical Application Configuration
Doc. designation
AA1J4Q03A1
Created by Title
REC670-ABTS
Document id.
Approved by Rev.
0
Rel. date
13/08/2014
Lang.
en
31 / 52
PULSETIMER
O:514|T:3|I:2
INPUT OUT
AND
O:1994|T:100|I:169
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:1996|T:100|I:170
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
TIMER
O:1213|T:3|I:5
INPUT ON
OFF
SRMEMORY
O:515|T:3|I:2
SET
RESET
OUT
NOUT
AND
O:407|T:3|I:6
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:409|T:3|I:7
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:411|T:3|I:8
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:705|T:3|I:13
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:707|T:3|I:14
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:709|T:3|I:15
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
ALL CB_INSER
BUS-B_HEALTHY
BUS-C_HEALTHY
BB_PROT_OPTD
T02_ABTS_START
TRUE
T02_ABTS_BLOCK
RESET_1,2,3
TRANSFER_2
TR03_BLK AVR_2
TR01_BLK AVR_1
CB_A301_CLOSE_STATUS
CB_A302_OPEN_STATUS
FALSE
TR01_AUTO_1
TR03_AUTO_2
CB_A303_CLOSE_STATUS
CB_A304_CLOSE_STATUS
CB_A305_OPEN_STATUS
TR02_ABTS_BLK_BY_A305_TC_FAULTY
TR01>TR03
TRUE
FALSE
TR03_TAP RAISE_2
TR03>TR01
TRUE
FALSE
TR01_TAP RAISE_1
TR01=TR03
TRUE
FALSE
A305_START SYN_2
ABTS_ON
ABTS_ABORT
TR01_MASTER1
TR03_FOLLOWER2
TR01_AVR_MANUAL1
TR03_AVR_MANUAL2
TR01_AVR_INDEPENDENT1
TR03_AVR_INDEPENDENT2
TRANSFER2
A A
B B
C C
D D
E E
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
Main Application: TRANS_123456, Page: 2
Rev. Modification Rel. date Created by
Replacing
Based on
Project
UMLUJJ 380_33_13.8KV PROTECTION
Responsible department
ABB Ltd.
UMLUJJ 380_33_13.8KV
PROTECTION.Substation.13.8KV.ABTS
Technical reference Document kind
Graphical Application Configuration
Doc. designation
AA1J4Q03A1
Created by Title
REC670-ABTS
Document id.
Approved by Rev.
0
Rel. date
13/08/2014
Lang.
en
32 / 52
SRMEMORY
O:815|T:3|I:3
SET
RESET
OUT
NOUT
AND
O:2909|T:3|I:51
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:2911|T:3|I:52
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:3205|T:3|I:53
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:3207|T:3|I:54
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:3209|T:3|I:55
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
ALL CB_INSER
BUS-A_HEALTHY
BUS-B_HEALTHY
BB_PROT_OPTD
RESET_1,2,3
TRANSFER_3
A305_CLOSE_1
T03_ABTS_START
T03_ABTS_BLOCK
CB_A301_CLOSE_STATUS
CB_A302_CLOSE_STATUS
FALSE
CB_A303_OPEN_STATUS
CB_A304_CLOSE_STATUS
CB_A305_OPEN_STATUS
TR02_ABTS_BLK_BY_A305_TC_FAULTY
BUS-C VOLT LOW
ABTS_ON
ABTS_ABORT
A A
B B
C C
D D
E E
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
Main Application: TRANS_123456, Page: 3
Rev. Modification Rel. date Created by
Replacing
Based on
Project
UMLUJJ 380_33_13.8KV PROTECTION
Responsible department
ABB Ltd.
UMLUJJ 380_33_13.8KV
PROTECTION.Substation.13.8KV.ABTS
Technical reference Document kind
Graphical Application Configuration
Doc. designation
AA1J4Q03A1
Created by Title
REC670-ABTS
Document id.
Approved by Rev.
0
Rel. date
13/08/2014
Lang.
en
33 / 52
SRMEMORY
O:1015|T:3|I:4
SET
RESET
OUT
NOUT
AND
O:3211|T:3|I:56
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:3305|T:3|I:57
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:3307|T:3|I:58
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:3309|T:3|I:59
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:3311|T:3|I:60
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
ALL CB_INSER
BUS-B_HEALTHY
BUS-C_HEALTHY
BB_PROT_OPTD
RESET_4,5,6
TRANSFER_4
A304_CLOSE_1
T01_ABTS_START
T03_ABTS_BLOCK
FALSE
CB_A304_OPEN_STATUS
CB_A305_CLOSE_STATUS
TR02_ABTS_BLK_BY_A304_TC_FAULTY
CB_A303_CLOSE_STATUS
BUS-A VOLT LOW
ABTS_ON ABTS_ABORT
CB_A301_OPEN_STATUS
CB_A302_CLOSE_STATUS
A A
B B
C C
D D
E E
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
Main Application: TRANS_123456, Page: 4
Rev. Modification Rel. date Created by
Replacing
Based on
Project
UMLUJJ 380_33_13.8KV PROTECTION
Responsible department
ABB Ltd.
UMLUJJ 380_33_13.8KV
PROTECTION.Substation.13.8KV.ABTS
Technical reference Document kind
Graphical Application Configuration
Doc. designation
AA1J4Q03A1
Created by Title
REC670-ABTS
Document id.
Approved by Rev.
0
Rel. date
13/08/2014
Lang.
en
34 / 52
PULSETIMER
O:814|T:3|I:3
INPUT OUT
AND
O:2208|T:100|I:187
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:2210|T:100|I:188
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
TIMER
O:1613|T:3|I:6
INPUT ON
OFF
SRMEMORY
O:1215|T:3|I:5
SET
RESET
OUT
NOUT
AND
O:805|T:3|I:17
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:807|T:3|I:18
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:809|T:3|I:19
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:811|T:3|I:20
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:1005|T:3|I:21
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:2106|T:3|I:38
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
ALL CB_INSER
BUS-A_HEALTHY
BUS-B_HEALTHY
BB_PROT_OPTD
T02_ABTS_START
TRUE
T02_ABTS_BLOCK
RESET_4,5,6
TRANSFER_5
TR03_BLK AVR_3
TR01_BLK AVR_2
CB_A301_CLOSE_STATUS
CB_A302_OPEN_STATUS
FALSE
CB_A303_CLOSE_STATUS
CB_A304_OPEN_STATUS
CB_A305_CLOSE_STATUS
TR02_ABTS_BLK_BY_A304_TC_FAULTY
TR01_AUTO_2
TR03_AUTO_3
TR01>TR03
TRUE
FALSE
TR03_TAP RAISE_3
TR03>TR01
TRUE
FALSE
TR01_TAP RAISE_2
TR01=TR03
TRUE
FALSE
A304_START SYN_1
ABTS_ON
ABTS_ABORT
TR03_AVR_INDEPENDENT3
TR03_AVR_MANUAL3
TR01_AVR_INDEPENDENT2
TR01_AVR_MANUAL2
TR01_MASTER2
TR03_FOLLOWER3
A A
B B
C C
D D
E E
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
Main Application: TRANS_123456, Page: 5
Rev. Modification Rel. date Created by
Replacing
Based on
Project
UMLUJJ 380_33_13.8KV PROTECTION
Responsible department
ABB Ltd.
UMLUJJ 380_33_13.8KV
PROTECTION.Substation.13.8KV.ABTS
Technical reference Document kind
Graphical Application Configuration
Doc. designation
AA1J4Q03A1
Created by Title
REC670-ABTS
Document id.
Approved by Rev.
0
Rel. date
13/08/2014
Lang.
en
35 / 52
PULSETIMER
O:1014|T:3|I:4
INPUT OUT
AND
O:2308|T:100|I:195
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:2310|T:100|I:196
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
TIMER
O:2913|T:3|I:9
INPUT ON
OFF
SRMEMORY
O:1615|T:3|I:6
SET
RESET
OUT
NOUT
AND
O:1007|T:3|I:22
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:1009|T:3|I:23
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:1011|T:3|I:24
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:2004|T:3|I:33
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:2006|T:3|I:34
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:2108|T:3|I:39
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
ALL CB_INSER
BUS-A_HEALTHY
BUS-B_HEALTHY
BB_PROT_OPTD
T03_ABTS_START
TRUE
TR03_ABTS_BLK
RESET_4,5,6
TRANSFER_6
TR02_BLK AVR_2
TR01_BLK AVR_3
CB_A301_CLOSE_STATUS
CB_A302_CLOSE_STATUS
FALSE
CB_A303_OPEN_STATUS
CB_A304_OPEN_STATUS
CB_A305_CLOSE_STATUS
TR02_ABTS_BLK_BY_A304_TC_FAULTY
TR01_AUTO_3
TR02_AUTO_2
TR01>TR02
TRUE
FALSE
TR02_TAP RAISE_2
TR02>TR01
TRUE
FALSE
TR01_TAP RAISE_3
TR01=TR02
TRUE
FALSE
A304_START SYN_2
ABTS_ON
ABTS_ABORT
TR02_AVR_INDEPENDENT2
TR01_AVR_INDEPENDENT3
TR02_AVR_MANUAL2
TR01_AVR_MANUAL3
TR01_MASTER3
TR02_FOLLOWER1
A A
B B
C C
D D
E E
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
Main Application: TRANS_123456, Page: 6
Rev. Modification Rel. date Created by
Replacing
Based on
Project
UMLUJJ 380_33_13.8KV PROTECTION
Responsible department
ABB Ltd.
UMLUJJ 380_33_13.8KV
PROTECTION.Substation.13.8KV.ABTS
Technical reference Document kind
Graphical Application Configuration
Doc. designation
AA1J4Q03A1
Created by Title
REC670-ABTS
Document id.
Approved by Rev.
0
Rel. date
13/08/2014
Lang.
en
36 / 52
AND
O:5304|T:100|I:201
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
TIMER
O:513|T:3|I:2
INPUT ON
OFF
OR
O:803|T:100|I:133
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
TIMER
O:813|T:3|I:3
INPUT ON
OFF
AND
O:5306|T:100|I:202
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
OR
O:705|T:100|I:130
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
AND
O:5308|T:100|I:203
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
OR
O:707|T:100|I:131
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
AND
O:5310|T:100|I:204
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
OR
O:709|T:100|I:132
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
TRUE
TRUE
FALSE
FALSE
TRUE
FALSE
TR01_TAP RAISE CMD
TR01_TAP RAISE_1
TR01_TAP RAISE_2
TR01_TAP RAISE_3
FALSE
FALSE
FALSE
TRUE
FALSE
TR02_TAP RAISE CMD
TR02_TAP RAISE_1
TR02_TAP RAISE_2
FALSE
FALSE
FALSE
FALSE
TRUE
FALSE
TR03_TAP RAISE CMD
TR03_TAP RAISE_1
TR03_TAP RAISE_2
TR03_TAP RAISE_3
FALSE
FALSE
FALSE
FALSE
A A
B B
C C
D D
E E
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
Main Application: TRANS_123456, Page: 7
Rev. Modification Rel. date Created by
Replacing
Based on
Project
UMLUJJ 380_33_13.8KV PROTECTION
Responsible department
ABB Ltd.
UMLUJJ 380_33_13.8KV
PROTECTION.Substation.13.8KV.ABTS
Technical reference Document kind
Graphical Application Configuration
Doc. designation
AA1J4Q03A1
Created by Title
REC670-ABTS
Document id.
Approved by Rev.
0
Rel. date
13/08/2014
Lang.
en
37 / 52
TIMER
O:2012|T:3|I:7
INPUT ON
OFF
OR
O:807|T:100|I:135
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
AND
O:5504|T:100|I:209
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:5506|T:100|I:210
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:5508|T:100|I:211
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:5510|T:100|I:212
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:5604|T:100|I:213
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:5606|T:100|I:214
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:2008|T:3|I:35
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:2010|T:3|I:36
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:106|T:8|I:62
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:1205|T:3|I:25
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:1207|T:3|I:26
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:1209|T:3|I:27
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
OR
O:1208|T:3|I:27
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
TRANS_FAIL TRANSFER_1
TRANSFER_2
TRANSFER_3
TRANSFER_4
TRANSFER_5
TRANSFER_6
TRANSFER_1
TRUE
FALSE
TRANS_1 FAIL
TRANSFER_2
TRUE
FALSE
TRANS_2 FAIL
TRANSFER_3
TRUE
FALSE
TRANS_3 FAIL
TRANSFER_4
TRUE
FALSE
TRANS_4 FAIL
TRANSFER_5
TRUE
FALSE
TRANS_5 FAIL
TRANSFER_6
TRUE
FALSE
TRANS_6 FAIL
TRANSFER_1
TRANSFER_2
TRANSFER_3
TRANSFER_4
TRANSFER_5
TRANSFER_6
A305_CLOSE CMD
CB_A305_CLOSE_STATUS
A304_CLOSE CMD
CB_A304_CLOSE_STATUS
CB_A305_CLOSE_STATUS
A305_CLOSE CMD
A305_CLOSE CMD
CB_A305_CLOSE_STATUS
A304_CLOSE CMD
CB_A304_CLOSE_STATUS
A304_CLOSE CMD
CB_A304_CLOSE_STATUS
TRANSFER_1 SUCCESS
TRANSFER_2 SUCCESS
TRANSFER_3 SUCCESS
TRANSFER_4 SUCCESS
TRANSFER_5 SUCCESS
TRANSFER_6 SUCCESS
TRANSFER_1 SUCCESS
TRANSFER_2 SUCCESS
TRANSFER_3 SUCCESS
TRANSFER_4 SUCCESS
TRANSFER_5 SUCCESS
TRANSFER_6 SUCCESS
TRANSFER_SUCCESS
A A
B B
C C
D D
E E
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
Main Application: TRANS_123456, Page: 8
Rev. Modification Rel. date Created by
Replacing
Based on
Project
UMLUJJ 380_33_13.8KV PROTECTION
Responsible department
ABB Ltd.
UMLUJJ 380_33_13.8KV
PROTECTION.Substation.13.8KV.ABTS
Technical reference Document kind
Graphical Application Configuration
Doc. designation
AA1J4Q03A1
Created by Title
REC670-ABTS
Document id.
Approved by Rev.
0
Rel. date
13/08/2014
Lang.
en
38 / 52
OR
O:805|T:100|I:134
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:809|T:100|I:136
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:1523|T:100|I:137
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:1673|T:100|I:145
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
TIMER
O:2613|T:3|I:8
INPUT ON
OFF
AND
O:5608|T:100|I:215
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:5610|T:100|I:216
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:5704|T:100|I:217
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
TR01_BLK AVR_1
TR01_BLK AVR_2
TR01_BLK AVR_3
FALSE
FALSE
FALSE
TR01_BLK AVR CMD
TR02_BLK AVR_1
TR02_BLK AVR_2
FALSE
FALSE
FALSE
FALSE
TR02_BLK AVR CMD
TR03_BLK AVR_1
TR03_BLK AVR_2
TR03_BLK AVR_3
FALSE
FALSE
FALSE
TR03_BLK AVR CMD
FALSE
FALSE
FALSE
AVR-FAULTY
TRUE
TRUE
TRUE
TRUE
TRUE
TRUE
T601_AVR_BLOCK
T602_AVR_BLOCK
T603_AVR_BLOCK
A A
B B
C C
D D
E E
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
Main Application: TRANS_123456, Page: 9
Rev. Modification Rel. date Created by
Replacing
Based on
Project
UMLUJJ 380_33_13.8KV PROTECTION
Responsible department
ABB Ltd.
UMLUJJ 380_33_13.8KV
PROTECTION.Substation.13.8KV.ABTS
Technical reference Document kind
Graphical Application Configuration
Doc. designation
AA1J4Q03A1
Created by Title
REC670-ABTS
Document id.
Approved by Rev.
0
Rel. date
13/08/2014
Lang.
en
39 / 52
OR
O:1525|T:100|I:138
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
TIMER
O:1592|T:100|I:23
INPUT ON
OFF
SRMEMORY
O:2014|T:3|I:7
SET
RESET
OUT
NOUT
AND
O:204|T:3|I:1
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
OR
O:3304|T:3|I:57
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
AND
O:2104|T:3|I:37
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
OR
O:406|T:3|I:6
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
FALSE
FALSE
FALSE
FALSE
RESET_1,2,3 A305_CLOSE CMD
TRUE
FALSE
FALSE
FALSE
FALSE
FALSE
RESET_4,5,6
A304_CLOSE CMD
CB_A304_CLOSE_STATUS
TRUE
FALSE
ALL_CB_FAULTY
TRANS_FAIL
A305_SYN FAIL
A304_SYN FAIL
RESET_PUSH-BUTTON
ABTS_ABORT
CB_A305_CLOSE_STATUS
AVR-FAULTY
FALSE
A A
B B
C C
D D
E E
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
Main Application: TRANS_123456, Page: 10
Rev. Modification Rel. date Created by
Replacing
Based on
Project
UMLUJJ 380_33_13.8KV PROTECTION
Responsible department
ABB Ltd.
UMLUJJ 380_33_13.8KV
PROTECTION.Substation.13.8KV.ABTS
Technical reference Document kind
Graphical Application Configuration
Doc. designation
AA1J4Q03A1
Created by Title
REC670-ABTS
Document id.
Approved by Rev.
0
Rel. date
13/08/2014
Lang.
en
40 / 52
OR
O:1585|T:100|I:142
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:1587|T:100|I:143
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:1589|T:100|I:144
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:2105|T:100|I:174
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:2107|T:100|I:175
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:2143|T:100|I:177
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:2145|T:100|I:178
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:2109|T:100|I:176
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:2147|T:100|I:179
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:2149|T:100|I:180
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:2153|T:100|I:181
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:2155|T:100|I:182
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:2157|T:100|I:183
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
TR01_AUTO_1
TR01_AUTO_2
TR01_AUTO_3
FALSE
FALSE
FALSE
TR01_AUTO CMD
TR02_AUTO_1
TR02_AUTO_2
FALSE
FALSE
FALSE
FALSE
TR02_AUTO CMD
TR03_AUTO_1
TR03_AUTO_2
TR03_AUTO_3
FALSE
FALSE
FALSE
TR03_AUTO CMD
TR01_MASTER1
TR01_MASTER2
TR01_MASTER3
TR02_MASTER1
TR01_MASTER_CMD
TR02_MASTER_CMD
TR02_FOLLOWER1
TR03_FOLLOWER1
TR03_FOLLOWER2
TR03_FOLLOWER3
TR02_FOLLOWER_CMD
TR03_FOLLOWER_CMD
TR01_AVR_INDEPENDENT1
TR01_AVR_INDEPENDENT2
TR01_AVR_INDEPENDENT3
TR02_AVR_INDEPENDENT1
TR02_AVR_INDEPENDENT2
TR03_AVR_INDEPENDENT1
TR03_AVR_INDEPENDENT2
TR03_AVR_INDEPENDENT3
TR01_AVR_INDEPENDENT_CMD
TR02_AVR_INDEPENDENT_CMD
TR03_AVR_INDEPENDENT_CMD
TR01_AVR_MANUAL1
TR01_AVR_MANUAL2
TR01_AVR_MANUAL3
TR02_AVR_MANUAL1
TR02_AVR_MANUAL2
TR03_AVR_MANUAL1
TR03_AVR_MANUAL2
TR03_AVR_MANUAL3
TR01_AVR_MANUAL_CMD
TR02_AVR_MANUAL_CMD
TR03_AVR_MANUAL_CMD
AUTOCOMMAND
MASTERCOMMAND FOLLOWERCOMMAND
INDEPENDENTCOMMAND
MANUALCOMMAND
A A
B B
C C
D D
E E
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
Main Application: TRANS_123456, Page: 11
Rev. Modification Rel. date Created by
Replacing
Based on
Project
UMLUJJ 380_33_13.8KV PROTECTION
Responsible department
ABB Ltd.
UMLUJJ 380_33_13.8KV
PROTECTION.Substation.13.8KV.ABTS
Technical reference Document kind
Graphical Application Configuration
Doc. designation
AA1J4Q03A1
Created by Title
REC670-ABTS
Document id.
Approved by Rev.
0
Rel. date
13/08/2014
Lang.
en
41 / 52
AND
O:5808|T:100|I:223
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:5810|T:100|I:224
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:5904|T:100|I:225
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
AND
O:5906|T:100|I:226
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
PULSETIMER
O:1614|T:3|I:6
INPUT OUT
PULSETIMER
O:2013|T:3|I:7
INPUT OUT
TIMERSET
O:211|T:3|I:1
INPUT ON
OFF
TIMERSET
O:512|T:3|I:2
INPUT ON
OFF AND
O:2110|T:3|I:40
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
SRMEMORY
O:3315|T:3|I:10
SET
RESET
OUT
NOUT
TIMER
O:3313|T:3|I:10
INPUT ON
OFF
TIMER
O:162|T:8|I:11
INPUT ON
OFF
AND
O:2509|T:3|I:43
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
SRMEMORY
O:164|T:8|I:11
SET
RESET
OUT
NOUT
OR
O:708|T:3|I:15
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:710|T:3|I:16
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
AND
O:108|T:8|I:63
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
OR
O:1303|T:8|I:89
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
AND
O:808|T:8|I:75
INPUT1
INPUT2
INPUT3
INPUT4N
OUT
NOUT
TIMER
O:812|T:8|I:12
INPUT ON
OFF
CB_A301_CLOSE_STATUS
CB_A302_CLOSE_STATUS
CB_A303_CLOSE_STATUS
FALSE
A305_TRIP
CB_A304_CLOSE_STATUS
FALSE
CB_A305_OPEN_STATUS
CB_A304_OPEN_STATUS
A304_TRIP
CB_A301_CLOSE_STATUS
CB_A302_CLOSE_STATUS
CB_A303_CLOSE_STATUS
FALSE
CB_A304_CLOSE_STATUS
CB_A305_CLOSE_STATUS
FALSE
CB_A305_CLOSE_STATUS
CB_A304_OPEN_STATUS
CB_A301_OPEN_STATUS
CB_A305_OPEN_STATUS
CB_A302_OPEN_STATUS
CB_A303_OPEN_STATUS
CB_A304_OPEN_STATUS
CB_A301_OPEN_STATUS
CB_A305_OPEN_STATUS
CB_A302_OPEN_STATUS
CB_A303_OPEN_STATUS
A305_TRIP_1
A305_TRIP_1
CB_A305_CLOSE_STATUS
CB_A303_CLOSE_STATUS CB_A302_CLOSE_STATUS
CB_A301_CLOSE_STATUS
CB_A304_CLOSE_STATUS
ABTS_OFF
ABTS_ON
ABTS_ON
A A
B B
C C
D D
E E
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
Main Application: TRANS_123456, Page: 12
Rev. Modification Rel. date Created by
Replacing
Based on
Project
UMLUJJ 380_33_13.8KV PROTECTION
Responsible department
ABB Ltd.
UMLUJJ 380_33_13.8KV
PROTECTION.Substation.13.8KV.ABTS
Technical reference Document kind
Graphical Application Configuration
Doc. designation
AA1J4Q03A1
Created by Title
REC670-ABTS
Document id.
Approved by Rev.
0
Rel. date
13/08/2014
Lang.
en
42 / 52
SESRSYN
O:1701|T:8|I:1
U3PBB1
U3PBB2
U3PLN1
U3PLN2
BLOCK
BLKSYNCH
BLKSC
BLKENERG
B1QOPEN
B1QCLD
B2QOPEN
B2QCLD
LN1QOPEN
LN1QCLD
LN2QOPEN
LN2QCLD
UB1OK
UB1FF
UB2OK
UB2FF
ULN1OK
ULN1FF
ULN2OK
ULN2FF
STARTSYN
TSTSYNCH
TSTSC
TSTENERG
AENMODE
MENMODE
SYNOK
AUTOSYOK
AUTOENOK
MANSYOK
MANENOK
TSTSYNOK
TSTAUTSY
TSTMANSY
TSTENOK
USELFAIL
B1SEL
B2SEL
LN1SEL
LN2SEL
SYNPROGR
SYNFAIL
UOKSYN
UDIFFSYN
FRDIFSYN
FRDIFFOK
FRDERIVA
UOKSC
UDIFFSC
FRDIFFA
PHDIFFA
FRDIFFM
PHDIFFM
INADVCLS
UDIFFME
FRDIFFME
PHDIFFME
UBUS
ULINE
MODEAEN
MODEMEN
OR
O:209|T:3|I:4
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:404|T:3|I:5
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
PULSETIMER
O:163|T:8|I:11
INPUT OUT
PULSETIMER
O:813|T:8|I:12
INPUT OUT
A305_CLOSE_1
A305_CLOSE CMD_1
A305_START SYN_1
A305_START SYN_2
A305_CLOSE CMD
BUS-B_U3P
GRP_OFF
BUS-C_U3P
GRP_OFF
FALSE
FALSE
FALSE
FALSE
TRUE
FALSE
FALSE
FALSE
TRUE
FALSE
FALSE
BUS-B_HEALTHY
FALSE
FALSE
FALSE
BUS-C_HEALTHY
FALSE
FALSE
FALSE
FALSE
FALSE
FALSE
FALSE
INTZERO
INTZERO
A305_SYN IN PROG
A305_SYN FAIL
A305_SYN_OK
A305_START_SYN
A A
B B
C C
D D
E E
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
Main Application: SYNCH, Page: 1
Rev. Modification Rel. date Created by
Replacing
Based on
Project
UMLUJJ 380_33_13.8KV PROTECTION
Responsible department
ABB Ltd.
UMLUJJ 380_33_13.8KV
PROTECTION.Substation.13.8KV.ABTS
Technical reference Document kind
Graphical Application Configuration
Doc. designation
AA1J4Q03A1
Created by Title
REC670-ABTS
Document id.
Approved by Rev.
0
Rel. date
13/08/2014
Lang.
en
43 / 52
PULSETIMER
O:1214|T:3|I:5
INPUT OUT
SESRSYN
O:1702|T:8|I:2
U3PBB1
U3PBB2
U3PLN1
U3PLN2
BLOCK
BLKSYNCH
BLKSC
BLKENERG
B1QOPEN
B1QCLD
B2QOPEN
B2QCLD
LN1QOPEN
LN1QCLD
LN2QOPEN
LN2QCLD
UB1OK
UB1FF
UB2OK
UB2FF
ULN1OK
ULN1FF
ULN2OK
ULN2FF
STARTSYN
TSTSYNCH
TSTSC
TSTENERG
AENMODE
MENMODE
SYNOK
AUTOSYOK
AUTOENOK
MANSYOK
MANENOK
TSTSYNOK
TSTAUTSY
TSTMANSY
TSTENOK
USELFAIL
B1SEL
B2SEL
LN1SEL
LN2SEL
SYNPROGR
SYNFAIL
UOKSYN
UDIFFSYN
FRDIFSYN
FRDIFFOK
FRDERIVA
UOKSC
UDIFFSC
FRDIFFA
PHDIFFA
FRDIFFM
PHDIFFM
INADVCLS
UDIFFME
FRDIFFME
PHDIFFME
UBUS
ULINE
MODEAEN
MODEMEN
OR
O:1204|T:3|I:25
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
OR
O:1206|T:3|I:26
INPUT1
INPUT2
INPUT3
INPUT4
INPUT5
INPUT6
OUT
NOUT
PULSETIMER
O:1013|T:8|I:13
INPUT OUT A304_CLOSE_1
FALSE
FALSE
FALSE
A304_CLOSE CMD_1
A304_START SYN_1
A304_START SYN_2
FALSE
FALSE
FALSE A304_CLOSE CMD
BUS-A_U3P
GRP_OFF
BUS-B_U3P
GRP_OFF
FALSE
FALSE
FALSE
FALSE
TRUE
FALSE
FALSE
FALSE
TRUE
FALSE
FALSE
BUS-A_HEALTHY
FALSE
FALSE
FALSE
BUS-B_HEALTHY
FALSE
FALSE
FALSE
FALSE
FALSE
FALSE
FALSE
INTZERO
INTZERO
A304_SYN IN PROG
A304_SYN FAIL
AH304_SYN_OK
A304_START_SYN
A A
B B
C C
D D
E E
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
Main Application: SYNCH, Page: 2
Rev. Modification Rel. date Created by
Replacing
Based on
Project
UMLUJJ 380_33_13.8KV PROTECTION
Responsible department
ABB Ltd.
UMLUJJ 380_33_13.8KV
PROTECTION.Substation.13.8KV.ABTS
Technical reference Document kind
Graphical Application Configuration
Doc. designation
AA1J4Q03A1
Created by Title
REC670-ABTS
Document id.
Approved by Rev.
0
Rel. date
13/08/2014
Lang.
en
44 / 52
SMBO
OUTPUTS
O:4300|T:3|I:1
BO1
BO2
BO3
BO4
BO5
BO6
BO7
BO8
BO9
BO10
RTCC1 RAISE
BO1
RTCC1 BLK CMD
BO2
RTCC1 AUT CMD
BO3
RTCC1 MAN CMD
BO4
A304_CLOSE
BO5
A304_CLOSE
BO6
RTCC1 MASTER
BO7
RTCC1 FOLLWER
BO8
RTCC1 INDEPEN
BO9
Not used
BO10
SMBO
OUTPUTS
O:4301|T:3|I:2
BO1
BO2
BO3
BO4
BO5
BO6
BO7
BO8
BO9
BO10
RTCC2 RAISE
BO1
RTCC2 BLK CMD
BO2
RTCC2 AUT CMD
BO3
RTCC2 MAN CMD
BO4
A305 CLOSE
BO5
A305 CLOSE
BO6
RTCC2 MASTER
BO7
RTCC2 FOLLWER
BO8
RTCC2 INDEPEN
BO9
Not used
BO10
SMBO
OUTPUTS
O:4302|T:3|I:3
BO1
BO2
BO3
BO4
BO5
BO6
BO7
BO8
BO9
BO10
RTCC3 RAISE
BO1
RTCC3 BLK CMD
BO2
RTCC3 AUT CMD
BO3
RTCC3 MAN CMD
BO4
AH17_CLOSE_CM
BO5
AH17_CLOSE_CM
BO6
RTCC3 MASTER
BO7
RTCC3 FOLLWER
BO8
RTCC3 INDPEND
BO9
NOT USED
BO10
SMBO
OUTPUTS
O:4303|T:3|I:4
BO1
BO2
BO3
BO4
BO5
BO6
BO7
BO8
BO9
BO10
A304_TRIP
BO1
A304_TRIP
BO2
AH32_CLOSE CM
BO3
AH32_CLOSE CM
BO4
AH32_OPEN CMD
BO5
AH32_OPEN CMD
BO6
A304 CL BLK
BO7
A305 CL BLK
BO8
ABTS ON CMD
BO9
ABTS OFF CMD
BO10
A305_CLOSE CMD
A304_CLOSE CMD
A304_TRIP
A305_TRIP
TR01_TAP RAISE CMD
TR01_BLK AVR CMD
TR01_AUTO CMD
TR02_TAP RAISE CMD
TR02_BLK AVR CMD
TR02_AUTO CMD
TR03_TAP RAISE CMD
TR03_BLK AVR CMD
TR03_AUTO CMD
A304_CLOSE CMD_1
A305_CLOSE CMD_1
TR01_AVR_MANUAL_CMD
TR01_AVR_MANUAL_CMD
TR01_MASTER_CMD
TR06_AVR_MANUAL_CMD
TR03_FOLLOWER_CMD
TR02_AVR_MANUAL_CMD
TR02_MASTER_CMD
TR02_FOLLOWER_CMD
TR01_AVR_INDEPENDENT_CMD
TR03_AVR_INDEPENDENT_CMD
TR02_AVR_INDEPENDENT_CMD
BS-A304_PROTN_OPTD
BS-A305_PROTN_OPTD
ABTS ON CMD
ABTS OFF CMD
RTCC1 MASTER
BOM_4.BO2
RTCC1 RAIS CM
BOM_4.BO1
RTCC3 RAISE
BOM_4.BO7
RTCC2 MASTER
BOM_4.BO5
ABTS OFF CMD
BOM_4.BO16
ABTS ON CMD
BOM_4.BO15
AH17_CLOSE_CM
BOM_4.BO17
AH17_CLOSE_CM
BOM_4.BO18
AH17 OPEN CMD
BOM_4.BO19
AH17 OPEN CMD
BOM_4.BO20
AH32_CLOSE CM
BOM_4.BO21
AH32_CLOSE CM
BOM_4.BO22
AH32_OPEN CMD
BOM_4.BO23
AH32_OPEN CMD
BOM_4.BO24
RTCC2 RAISE
BOM_4.BO4
A A
B B
C C
D D
E E
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
Main Application: BOM, Page: 1
Rev. Modification Rel. date Created by
Replacing
Based on
Project
UMLUJJ 380_33_13.8KV PROTECTION
Responsible department
ABB Ltd.
UMLUJJ 380_33_13.8KV
PROTECTION.Substation.13.8KV.ABTS
Technical reference Document kind
Graphical Application Configuration
Doc. designation
AA1J4Q03A1
Created by Title
REC670-ABTS
Document id.
Approved by Rev.
0
Rel. date
13/08/2014
Lang.
en
45 / 52
SMBO
O:4304|T:3|I:5
BO1
BO2
BO3
BO4
BO5
BO6
BO7
BO8
BO9
BO10
Not used
BO1
Not used
BO2
Not used
BO3
Not used
BO4
Not used
BO5
Not used
BO6
Not used
BO7
Not used
BO8
Not used
BO9
Not used
BO10
SMBO
O:4305|T:3|I:6
BO1
BO2
BO3
BO4
BO5
BO6
BO7
BO8
BO9
BO10
Not used
BO1
Not used
BO2
Not used
BO3
Not used
BO4
Not used
BO5
Not used
BO6
Not used
BO7
Not used
BO8
Not used
BO9
Not used
BO10
T01_ABTS_START
T02_ABTS_START
T03_ABTS_START
ABTS_ABORT
TRANSFER_SUCCESS
TRANSFER_1
TRANSFER_2
TRANSFER_3
TRANSFER_4
TRANSFER_5
A304_CLOSE CMD
A305_CLOSE CMD
A304_TRIP
A305_TRIP
TRANSFER_6
A A
B B
C C
D D
E E
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
Main Application: BOM, Page: 2
Rev. Modification Rel. date Created by
Replacing
Based on
Project
UMLUJJ 380_33_13.8KV PROTECTION
Responsible department
ABB Ltd.
UMLUJJ 380_33_13.8KV
PROTECTION.Substation.13.8KV.ABTS
Technical reference Document kind
Graphical Application Configuration
Doc. designation
AA1J4Q03A1
Created by Title
REC670-ABTS
Document id.
Approved by Rev.
0
Rel. date
13/08/2014
Lang.
en
46 / 52
A1RADR
O:3702|T:3|I:1
BUS-A_UR
INPUT1
BUS-A_UY
INPUT2
BUS-A_UB
INPUT3
BUS-B_UR
INPUT4
BUS-B_UY
INPUT5
BUS-B_UB
INPUT6
BUS-C_UR
INPUT7
BUS-C_UY
INPUT8
BUS-C_UB
INPUT9
NOT USED
INPUT10
BUS-A_UR
BUS-A_UY
BUS-A_UB
BUS-B_UR
BUS-B_UY
BUS-B_UB
BUS-C_UR
BUS-C_UY
BUS-C_UB
GRP_OFF
A A
B B
C C
D D
E E
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
Main Application: DREP_AI, Page: 1
Rev. Modification Rel. date Created by
Replacing
Based on
Project
UMLUJJ 380_33_13.8KV PROTECTION
Responsible department
ABB Ltd.
UMLUJJ 380_33_13.8KV
PROTECTION.Substation.13.8KV.ABTS
Technical reference Document kind
Graphical Application Configuration
Doc. designation
AA1J4Q03A1
Created by Title
REC670-ABTS
Document id.
Approved by Rev.
0
Rel. date
13/08/2014
Lang.
en
47 / 52
B1RBDR
O:3711|T:3|I:1
CB_AH10_OPEN
INPUT1
CB_AH10_CLOSE
INPUT2
CB_AH10_INSER
INPUT3
CB_AH18_OPEN
INPUT4
CB_AH18_CLOSE
INPUT5
CB_AH18_INSER
INPUT6
CB_AH25_OPEN
INPUT7
CB_AH25_CLOSE
INPUT8
CB_AH25_INSER
INPUT9
CB_AH36_OPEN
INPUT10
CB_AH36_CLOSE
INPUT11
CB_AH36_INSER
INPUT12
CB_AH44_OPEN
INPUT13
CB_AH44_CLOSE
INPUT14
CB_AH44_INSER
INPUT15
NOT USED
INPUT16
B2RBDR
O:3712|T:3|I:2
BUS-A_PROTN_T
INPUT17
BUS-B_PROTN_T
INPUT18
BUS-C_PROTN_T
INPUT19
BS-AH18_PR_OP
INPUT20
BS-AH36_PR_OP
INPUT21
Not used
INPUT22
ABTS_LOCAL
INPUT23
ABTS_REMOTE
INPUT24
ABTS_ON
INPUT25
ABTS_OFF
INPUT26
BUS-A_FFR OPT
INPUT27
BUS-B_FFR OPT
INPUT28
BUS-C_FFR OPT
INPUT29
T601_AVR_BLK
INPUT30
T602_AVR_BLK
INPUT31
T603_AVR_BLK
INPUT32
B3RBDR
O:3713|T:3|I:3
BB_PROT_OPTD
INPUT33
ALL CB_INSER
INPUT34
CB_FAULTY
INPUT35
BB PROT_LOCKO
INPUT36
BS PROT_OPTD
INPUT37
TR LOCKOUT OP
INPUT38
TR BACKUP PRO
INPUT39
T01_ABTS_STAR
INPUT40
T01_ABTS_BLK
INPUT41
T02_ABTS_STAR
INPUT42
T02_ABTS_BLK
INPUT43
T03_ABTS_STAR
INPUT44
T03_ABTS_BLK
INPUT45
RESET_PB
INPUT46
NOT USED
INPUT47
NOT USED
INPUT48
B4RBDR
O:3714|T:3|I:4
TRANSFER_1
INPUT49
TRANSFER_2
INPUT50
TRANSFER_3
INPUT51
TRANSFER_4
INPUT52
TRANSFER_5
INPUT53
TRANSFER_6
INPUT54
AVR-FAULTY
INPUT55
TRANS_FAIL
INPUT56
ABTS_ABORT
INPUT57
TR01_TAP RAIS
INPUT58
TR01_BLK AVR
INPUT59
TR01_AUTO CMD
INPUT60
TR02_TAP RAIS
INPUT61
TR02_BLK AVR
INPUT62
TR02_AUTO CMD
INPUT63
NOT USED
INPUT64
CB_A301_OPEN_STATUS
CB_A301_CLOSE_STATUS
CB_A301_INSERVICE
CB_A304_OPEN_STATUS
CB_A304_CLOSE_STATUS
CB_A304_INSERVICE
CB_A302_OPEN_STATUS
CB_A302_CLOSE_STATUS
CB_A302_INSERVICE
CB_A305_OPEN_STATUS
CB_A305_CLOSE_STATUS
CB_A305_INSERVICE
CB_A303_OPEN_STATUS
CB_A303_CLOSE_STATUS
CB_A303_INSERVICE
FALSE
BUS-A_PROTN_TRIP
BUS-B_PROTN_TRIP
BUS-C_PROTN_TRIP
BS-A304_PROTN_OPTD
BS-A305_PROTN_OPTD
ABTS_ON
ABTS_OFF
BUS-A_FFR OPTD
BUS-B_FFR OPTD
BUS-C_FFR OPTD
BB_PROT_OPTD
ALL CB_INSER
ALL_CB_FAULTY
BB PROT_LOCKOUT OPTD
BS PROT_OPTD
TR LOCKOUT OPTD
TR BACKUP PROT OPTD
T01_ABTS_START
T01_ABTS_BLOCK
T02_ABTS_START
T02_ABTS_BLOCK
T03_ABTS_START
T03_ABTS_BLOCK
RESET_PUSH-BUTTON
FALSE
FALSE
AVR-FAULTY
FALSE
TRANSFER_1
TRANSFER_2
TRANSFER_3
TRANSFER_4
TRANSFER_5
TRANSFER_6
TRANS_FAIL
ABTS_ABORT
TR01_TAP RAISE CMD
TR01_BLK AVR CMD
TR01_AUTO CMD
TR02_TAP RAISE CMD
TR02_BLK AVR CMD
TR02_AUTO CMD
FALSE
T601_AVR_BLOCK
T602_AVR_BLOCK
T603_AVR_BLOCK
ABTS_LOCAL
ABTS_REMOTE
A A
B B
C C
D D
E E
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
Main Application: DREP_BI, Page: 1
Rev. Modification Rel. date Created by
Replacing
Based on
Project
UMLUJJ 380_33_13.8KV PROTECTION
Responsible department
ABB Ltd.
UMLUJJ 380_33_13.8KV
PROTECTION.Substation.13.8KV.ABTS
Technical reference Document kind
Graphical Application Configuration
Doc. designation
AA1J4Q03A1
Created by Title
REC670-ABTS
Document id.
Approved by Rev.
0
Rel. date
13/08/2014
Lang.
en
48 / 52
B5RBDR
O:3715|T:3|I:5
TR03_TAP RAIS
INPUT65
TR03_BLK AVR
INPUT66
TR03_AUTO CMD
INPUT67
AH18_CLOSE CM
INPUT68
AH18_TRIP
INPUT69
AH36_CLOSE CM
INPUT70
AH36_TRIP
INPUT71
TRANSFER_1 OK
INPUT72
TRANSFER_2 OK
INPUT73
TRANSFER_3 OK
INPUT74
TRANSFER_4 OK
INPUT75
TRANSFER_5 OK
INPUT76
TRANSFER_6 OK
INPUT77
NOT USED
INPUT78
NOT USED
INPUT79
NOT USED
INPUT80
B6RBDR
O:3716|T:3|I:6
TR02>TR03
INPUT81
TR03>TR02
INPUT82
TR02=TR03
INPUT83
TR01>TR03
INPUT84
TR03>TR01
INPUT85
TR01=TR03
INPUT86
TR01>TR02
INPUT87
TR02>TR01
INPUT88
TR01=TR02
INPUT89
AH18_SYN_ST
INPUT90
AH36_SYN_ST
INPUT91
AH18_SYN_PRO
INPUT92
AH18_SYN_FAIL
INPUT93
AH36_SYN_PRO
INPUT94
AH36_SYN_FAIL
INPUT95
NOT USED
INPUT96
FALSE
FALSE
FALSE
A305_CLOSE CMD
A304_CLOSE CMD
A304_TRIP
A305_TRIP
TR03_TAP RAISE CMD
TR03_BLK AVR CMD
TR03_AUTO CMD
TRANSFER_1 SUCCESS
TRANSFER_2 SUCCESS
TRANSFER_3 SUCCESS
TRANSFER_4 SUCCESS
TRANSFER_5 SUCCESS
TRANSFER_6 SUCCESS
TR02>TR03
TR03>TR02
TR02=TR03
TR01>TR03
TR03>TR01
TR01=TR03
TR01=TR02
TR02>TR01
TR01>TR02
A304_START_SYN
A305_START_SYN
A304_SYN IN PROG
A304_SYN FAIL
A305_SYN IN PROG
A305_SYN FAIL
A A
B B
C C
D D
E E
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
Main Application: DREP_BI, Page: 2
Rev. Modification Rel. date Created by
Replacing
Based on
Project
UMLUJJ 380_33_13.8KV PROTECTION
Responsible department
ABB Ltd.
UMLUJJ 380_33_13.8KV
PROTECTION.Substation.13.8KV.ABTS
Technical reference Document kind
Graphical Application Configuration
Doc. designation
AA1J4Q03A1
Created by Title
REC670-ABTS
Document id.
Approved by Rev.
0
Rel. date
13/08/2014
Lang.
en
49 / 52
SP16GGIO
O:3750|T:3|I:1
BLOCK
BUS-A_PROTN_T
IN1
BUS-B_PROTN_T
IN2
BUS-C_PROTN_T
IN3
BS-AH18_PR_OP
IN4
BS-AH36_PR_OP
IN5
BUS-A_FFR OPT
IN6
BUS-B_FFR OPT
IN7
BUS-C_FFR OPT
IN8
ABTS_ON
IN9
ABTS_OFF
IN10
ABTS_LOCAL
IN11
ABTS_REMOTE
IN12
NOT USED
IN13
NOT USED
IN14
NOT USED
IN15
NOT USED
IN16
SP16GGIO
O:3755|T:3|I:2
BLOCK
BB_PROT_OPTD
IN1
ALL CB_INSER
IN2
CB_FAULTY
IN3
BB PROT_LOCKO
IN4
TR LOCKOUT OP
IN5
TR BACKUP PRO
IN6
T01_ABTS_STAR
IN7
T01_ABTS_BLK
IN8
T02_ABTS_STAR
IN9
T02_ABTS_BLK
IN10
T03_ABTS_STAR
IN11
T03_ABTS_BLK
IN12
RESET_PB
IN13
BS PROT_OPTD
IN14
NOT USED
IN15
NOT USED
IN16
SP16GGIO
O:3760|T:3|I:3
BLOCK
TRANSFER_1
IN1
TRANSFER_2
IN2
TRANSFER_3
IN3
TRANSFER_4
IN4
TRANSFER_5
IN5
TRANSFER_6
IN6
AVR-FAULTY
IN7
TRANS_FAIL
IN8
ABTS_ABORT
IN9
TR01_TAP RAIS
IN10
TR01_BLK AVR
IN11
TR01_AUTO CMD
IN12
TR02_TAP RAIS
IN13
TR02_BLK AVR
IN14
TR02_AUTO CMD
IN15
NOT USED
IN16
SP16GGIO
O:3765|T:3|I:4
BLOCK
TR03_TAP RAIS
IN1
TR03_BLK AVR
IN2
TR03_AUTO CMD
IN3
AH18_CLOSE CM
IN4
AH18_TRIP
IN5
TRANSFER_1 OK
IN6
TRANSFER_2 OK
IN7
TRANSFER_3 OK
IN8
TRANSFER_4 OK
IN9
TRANSFER_5 OK
IN10
TRANSFER_6 OK
IN11
NOT USED
IN12
NOT USED
IN13
NOT USED
IN14
NOT USED
IN15
NOT USED
IN16
BUS-A_PROTN_TRIP
BUS-B_PROTN_TRIP
BUS-C_PROTN_TRIP
BS-A304_PROTN_OPTD
BS-A305_PROTN_OPTD
ABTS_ON
ABTS_OFF
FALSE
FALSE
FALSE
BB_PROT_OPTD
ALL CB_INSER
ALL_CB_FAULTY
BB PROT_LOCKOUT OPTD
BS PROT_OPTD
TR LOCKOUT OPTD
TR BACKUP PROT OPTD
T01_ABTS_START
T01_ABTS_BLOCK
T02_ABTS_START
T02_ABTS_BLOCK
T03_ABTS_START
T03_ABTS_BLOCK
RESET_PUSH-BUTTON
FALSE
FALSE
AVR-FAULTY
FALSE
TRANSFER_1
TRANSFER_2
TRANSFER_3
TRANSFER_4
TRANSFER_5
TRANSFER_6
TRANS_FAIL
ABTS_ABORT
TR01_TAP RAISE CMD
TR01_BLK AVR CMD
TR01_AUTO CMD
TR02_TAP RAISE CMD
TR02_BLK AVR CMD
TR02_AUTO CMD
FALSE
FALSE
FALSE
FALSE
FALSE
A304_CLOSE CMD
A304_TRIP
TR03_TAP RAISE CMD
TR03_BLK AVR CMD
TR03_AUTO CMD
FALSE
FALSE
FALSE
FALSE
TRANSFER_1 SUCCESS
TRANSFER_2 SUCCESS
TRANSFER_3 SUCCESS
TRANSFER_4 SUCCESS
TRANSFER_5 SUCCESS
TRANSFER_6 SUCCESS
BUS-A_FFR OPTD
BUS-B_FFR OPTD
BUS-C_FFR OPTD
FALSE
ABTS_LOCAL
ABTS_REMOTE
A A
B B
C C
D D
E E
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
Main Application: DREP_SAS, Page: 1
Rev. Modification Rel. date Created by
Replacing
Based on
Project
UMLUJJ 380_33_13.8KV PROTECTION
Responsible department
ABB Ltd.
UMLUJJ 380_33_13.8KV
PROTECTION.Substation.13.8KV.ABTS
Technical reference Document kind
Graphical Application Configuration
Doc. designation
AA1J4Q03A1
Created by Title
REC670-ABTS
Document id.
Approved by Rev.
0
Rel. date
13/08/2014
Lang.
en
50 / 52
SP16GGIO
O:8351|T:100|I:5
BLOCK
AH36_CLOSE CM
IN1
AH36_TRIP
IN2
NOT USED
IN3
NOT USED
IN4
NOT USED
IN5
NOT USED
IN6
NOT USED
IN7
NOT USED
IN8
NOT USED
IN9
NOT USED
IN10
NOT USED
IN11
NOT USED
IN12
NOT USED
IN13
NOT USED
IN14
NOT USED
IN15
NOT USED
IN16
A305_CLOSE CMD
A305_TRIP
FALSE
FALSE
FALSE
FALSE
FALSE
FALSE
FALSE
FALSE
FALSE
FALSE
FALSE
FALSE
FALSE
FALSE
FALSE
A A
B B
C C
D D
E E
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
Main Application: DREP_SAS, Page: 2
Rev. Modification Rel. date Created by
Replacing
Based on
Project
UMLUJJ 380_33_13.8KV PROTECTION
Responsible department
ABB Ltd.
UMLUJJ 380_33_13.8KV
PROTECTION.Substation.13.8KV.ABTS
Technical reference Document kind
Graphical Application Configuration
Doc. designation
AA1J4Q03A1
Created by Title
REC670-ABTS
Document id.
Approved by Rev.
0
Rel. date
13/08/2014
Lang.
en
51 / 52
ActiveGroup
O:10|T:8|I:1
ACTGRP1
ACTGRP2
ACTGRP3
ACTGRP4
ACTGRP5
ACTGRP6
GRP1
GRP2
GRP3
GRP4
GRP5
GRP6
SETCHGD
CHNGLCK
O:3300|T:100|I:1
LOCK
LEDGEN
O:3600|T:3|I:1
BLOCK
RESET
LEDTEST
NEWIND
ACK LocalHMI
O:4200|T:100|I:1
CLRLEDS HMI-ON
RED-S
YELLOW-S
YELLOW-F
CLRPULSE
LEDSCLRD
INTERRSIG
O:32|T:1000|I:1
FAIL
WARNING
CPUFAIL
CPUWARN
TIMEERR
O:31|T:1000|I:1
TSYNCERR
RTCERR
TESTMODE
O:250|T:3|I:1
INPUT ACTIVE
OUTPUT
SETTING
NOEVENT
BI_ACTIVE_GROUP1
BI_ACTIVE_GROUP2
FALSE
FALSE
FALSE
FALSE
ACGR-GRP1
ACGR-GRP2
ACGR-SETCHGD
BI_CHANGE_LOCK
FALSE
BI_RESET_LEDS
BI_LED_TEST
LHMI-LEDSCLRD
IES-FAIL
IES-WARNING
CPUFAIL
CPUWARN
TIME-TSYNCERR
TIME-RTCERR
BI_ACTIVATE_TESTMODE TEST-ACTIVE
ACTIVESETTINGGROUP
LEDMONITOR
ERRORSIGNALS
TESTMODEON/OFF
A A
B B
C C
D D
E E
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
Main Application: COMMON, Page: 1
Rev. Modification Rel. date Created by
Replacing
Based on
Project
UMLUJJ 380_33_13.8KV PROTECTION
Responsible department
ABB Ltd.
UMLUJJ 380_33_13.8KV
PROTECTION.Substation.13.8KV.ABTS
Technical reference Document kind
Graphical Application Configuration
Doc. designation
AA1J4Q03A1
Created by Title
REC670-ABTS
Document id.
Approved by Rev.
0
Rel. date
13/08/2014
Lang.
en
52 / 52