Classifying Duct Leakage By Lee Feigenbaum, Student Member ASHRAE A s an ever-increasing number of buildings seek LEED certica- tion, energy-conserving initia- tives call for HVAC systems that deliver high levels of performance at relatively low pressures. 1 To that end, engineers routinely specify air duct leakage testing to verify that their finished systems meet acceptable standards for air conveyance. Based on the SMACNA standard for leakage testing, leakage classication helps relate leakage to duct surface area. 1 To avoid unnecessary costs or lost productivity resulting from failed leakage tests in the eld, it is important to understand how leakage classication impacts the leakage factor, or permis- sible leakage. Leakage classication is the value that ties static pressure (in. w.g.) to acceptable leakage rates. At any given pressure, leak- age classication identies a permissible leakage rate measured in cfm/100 ft 2 (L/s per 20 m 2 ) of duct surface area at 1 in. w.g. (249 Pa). 1
To simplify the procedure of calcu- lating acceptable leakage, SMACNA provides leakage factors that correspond to Leakage Classications 2, 4, 8, and 16 in Table E-1. 1 Although leakage classi- cation can be expressed by any number (including decimals and/or fractions), it should not be selected arbitrarily. SMACNA provides suggested values in its leakage standards as a general guideline. Other values are also accept- able given that they are achievable us- ing the correct fabrication and sealing techniques. ASHRAE/IES Standard 90.1-2010 recommends Leakage Class 6 for ductwork at 1 in. w.g. (249 Pa). To maintain efciency while conduct- ing leakage testing, it is important to understand how to properly calculate the specied allowable leakage. One example would be when the specified leakage class is 5. Many engineers and contractors in this situ- ation quickly jump to the next most restrictive classification as set forth in SMACNA Table E-1. In doing so they exceed the specifications, which is un- This article was published in ASHRAE Journal, September 2012. Copyright 2012 ASHRAE. Posted at www.ashrae.org. This article may not be copied and/or distributed electronically or in paper form without permission of ASHRAE. For more information about ASHRAE Journal, visit www.ashrae.org. ENGINEERS NOTEBOOK Advertisement formerly in this space. Classifying Duct Leakage Advertisement formerly in this space. ENGINEERS NOTEBOOK ENGINEERS NOTEBOOK 80 ASHRAE Jour nal Sept ember 2012 necessary and potentially expensive on a first cost basis. The proper formula to calculate allow- able leakage is: F= C L P N where F =Maximum leakage rate per unit of duct surface area as cfm/100 ft 2 (L/s per 20 m 2 ) (L max in Standard 90.1-2010) C L =Leakage Class (given) P =Static Pressure (given) N =0.65 (constant value unless specied otherwise) 1
Using this formula on a duct systemconstructed to 4 in. w.g. (996 Pa) and Leakage Class 6, the leakage factor (F) is 14.8 cfm/100 ft 2
(15 L/s per 20 m 2 ). The same system at Leakage Class 5 yields a slightly more restrictive factor of 12.3 cfm/100 ft 2 (12 L/s per 20 m 2 ). At Leakage Class 4 this system only allows a stingy factor of 9.8 cfm/100 ft 2 (10 L/s per 20 m 2 ). When applied over a large test area, this difference becomes signicant. For instance, assume a test area of 2,000 ft 2 (186 m 2 ) at Leakage Class 5. If an engineer or contractor follows Table E-1 and jumps to the next most restrictive Leakage Class 4, rather than calculating the leakage factor for Leakage Class 5, he essentially forfeits 50 cfm (24 L/s) of allowable leakage (Table 1). That is roughly equivalent to testing the system with an undampered air Static Pressure (P) Leakage Class (C L ) Maximum Leakage Rate (F) Test Area (ft 2 ) Allowable Leakage 4 in. w.g. 4 9.8 2,000 196 4 in. w.g. 5 12.3 2,000 246 4 in. w.g. 6 14.8 2,000 296 Table 1: Allowable leakage of sample section of duct tested to 4 in. w.g. (996 Pa) and various leakage classifcations. outlet fully open. The impact to a contractors productivity and/or protability under these undesirable circumstances is unacceptable. Leakage classication is an important component of leakage calculations. When multiplied by the surface area of a test sec- tion the leakage classication can become a powerful and costly hindrance if not given proper consideration and care. Diligence while calculating leakage factors is important, as unexpected consequences of erroneous calculations may include unrealistic leakage goals and lost productivity. To that end, SMACNA states that prudent contractors must take testing seriously; work se- quence, work duration and costs can be signicantly affected. 1
References 1. SMACNA. 2012. HVAC Air Duct Leakage Test Manual (2 nd ed). Lee Feigenbaumis a project manager at Heritage Mechanical Services: An EMCOR Co. in Farmingdale, N.Y. He is studying for an MBA degree at Hofstra University. Advertisement formerly in this space.